Abb Rel561 Setting Calculation
Abb Rel561 Setting Calculation
Abb Rel561 Setting Calculation
4
AL-QADISIYYAH 115/13.8KV SUBSTATION EE-065767
115KV NORTH MUBARRAZ LINE, SET-1 Rev-A
Relay details
Relay type: REL561 (Set -1 ) - 1MRK 002 496-AE
Line differential protection relay with distance protection 3
Zones, 3 & 1 ph. tripping, FFR, PSB, SOTF, WEI & Echo,
FL, Communication Assisted DEF, Mutual Compensation
Current Rating: 5A
AC Voltage Rating: 115 V
DC Voltage Rating: 125 V
Features: QUAD characteristic
SOTF: Enabled
PERMISSIVE TRIP: Disabled
Weak End Feed: N/A
TRIP: 3 Phase Trip
5
AL-QADISIYYAH 115/13.8KV SUBSTATION EE-065767
115KV NORTH MUBARRAZ LINE, SET-1 Rev-A
22.13 Ohms
= 22.13 x COS(80)
3.84 Ohms
= 22.13 x SIN(80)
21.79 Ohms
0.15 Ohms
0.98 Ohms
1.09 Ohms
4.45 Ohms
4.30 Ohms
6
AL-QADISIYYAH 115/13.8KV SUBSTATION EE-065767
115KV NORTH MUBARRAZ LINE, SET-1 Rev-A
23.93 Ohms
= SQRT(4.3^2 + 23.93^2)
24.31 Ohms
2731.19 A
= 28710 x 5 / 2731.19^1.4
2.22 Ohms
16.60 Ohms
= 16.6 x COS(85)
1.45 Ohms
7
AL-QADISIYYAH 115/13.8KV SUBSTATION EE-065767
115KV NORTH MUBARRAZ LINE, SET-1 Rev-A
Total Resistance = 1.45 + 0.15
1.60 Ohms
= 0.19 X 0.4
= 1.23 X 0.4
8
AL-QADISIYYAH 115/13.8KV SUBSTATION EE-065767
115KV NORTH MUBARRAZ LINE, SET-1 Rev-A
Line resistance (secondary) = Primary resistance X CT Ratio/PT ratio
= 1.361217 X 0.4
= 5.56 X 0.4
Similarly
Zone-1 Reactance setting Forward Direction (Quad)
X1PP - Z1 = 80 % of pos. seq. Line Reactance
= 0.8 X 0.492
= 0.394 Ohms
= 0.8 X 2.224
= 1.779 Ohms
Zone-1 Resistance setting Forward Direction (Quad)
R1PP - Z1 = 80 % of pos. seq. Line Resistance
= 0.8 X 0.076
= 0.061 Ohms
= 0.8 X 0.5445
0.436 Ohms
9
AL-QADISIYYAH 115/13.8KV SUBSTATION EE-065767
115KV NORTH MUBARRAZ LINE, SET-1 Rev-A
= 8.89 Ohms
Zone-1 E/F total resistance (secondary) =(((R1+R1+R0)/3)+ Arc. Res. + Tower foot Res.)
= ( ( (0.19+0.19+1.361217)/3 ) + 2.22 + 20) x 400 / 1000
= 9.12 Ohms
10
AL-QADISIYYAH 115/13.8KV SUBSTATION EE-065767
115KV NORTH MUBARRAZ LINE, SET-1 Rev-A
Load Impedance
≤ 18.3362 Ohms
The maximum RFPE setting is 14.23 ohms which is less than 18.34ohms.
The maximum RFPP setting is 1.84 ohms which is less than 37.91ohms.
11
AL-QADISIYYAH 115/13.8KV SUBSTATION EE-065767
115KV NORTH MUBARRAZ LINE, SET-1 Rev-A
Earth fault compensation setting:
1 Z 0 L - ZL
Earth fault compensation =
3 ZL
= (SQRT(0.34903^2 + 1.4268^2)
Z0L / ZL =
(SQRT(0.04745^2 + 0.31495^2)
= 4.61
76.25
81.43
-5.18 Deg
{ }
= (4.61 Ang -5.18) - 1
Z OL
⟨ - 1⟩
ZL = (2.81- j 0.471) - 1
= 1.81-j 0.471
1.87
1 Z0 L - ZL = (1 / 3) x 1.87
3 ZL 0.62
{ }
ANGLE = X0 -X L XL
L
arctan ⟨ ⟩ - arctan ⟨ ⟩
R 0 L− R L RL
ANGLE =ATAN((1.4268-0.31495)/(0.34903-0.04745))-ATAN(0.31495/0.04745)
-0.115334510122086
-6.61 DEG
Earth fault compensation 0.62 ANG - -6.61
12
AL-QADISIYYAH 115/13.8KV SUBSTATION EE-065767
115KV NORTH MUBARRAZ LINE, SET-1 Rev-A
NOTE:
1. The phase selection logic RFPP setting shall be higher than (1.82xR1PP + 0.32xX1PP+0.91xRFPP)
2 ohms. Also it shall be less than 32 ohms (1.35 x RL min).
2. The phase selection logic RFPE setting shall be higher than (Earth loop resis. + RFPE)
14 Ohms
The fallowing settings based on relay manufacturer's recommedation for identical CTs
at both ends are proposed.
I Minsat = 300%
13
DOCUMENT: RELAY SETTING CALCULATION DOC NO: KE - 597315
STATION: 132kV Markaz Zallum Substation Rev. No. : A
Page 14
DOCUMENT: RELAY SETTING CALCULATION DOC NO: KE - 597315
STATION: 132kV Markaz Zallum Substation Rev. No. : A
Relay detail
Relay type: MiCOMho P443
Current Rating: 5A
AC Voltage Rating: 115 V
DC Voltage Rating: 125 V
Features: Quad/Mho
SOTF: Enabled
PERMISSIVE TRIP: Disabled
Weak End Feed: N/A
ECHO: 0 KV
TRIP: 3 Phase Trip
Internal Fuse Fail: 0 KV
Page 15
DOCUMENT: RELAY SETTING CALCULATION DOC NO: KE - 597315
STATION: 132kV Markaz Zallum Substation Rev. No. : A
22.13 Ohms
= 22.13 x COS(80)
3.84 Ohms
= 22.13 x SIN(80)
21.79 Ohms
RF(Tower Foot resistance) = 20.00 Ohms
0.15 Ohms
0.98 Ohms
1.09 Ohms
4.45 Ohms
24.30 Ohms
23.93 Ohms
Page 16
DOCUMENT: RELAY SETTING CALCULATION DOC NO: KE - 597315
STATION: 132kV Markaz Zallum Substation Rev. No. : A
34.10 Ohms
1947.08 A
= 28707 x 5 / 1947.08^1.4
3.56 Ohms
= 3.56 / (1 + 1.2)
1.62 Ohms
Arc resistance (secondary) 1.62 x 300/2000
= 0.65 Ohms
16.60 Ohms
= 16.6 x COS(85)
1.45 Ohms
17.52 Ohms
= SQRT(1.6^2 + 17.52^2)
17.59 Ohms
Page 17
DOCUMENT: RELAY SETTING CALCULATION DOC NO: KE - 597315
STATION: 132kV Markaz Zallum Substation Rev. No. : A
3774.60 A
PH to Ph fault current = 0.866 x 3 phase fault current
= 0.866 x 3774.6
3268.80 A
= 28707 x 5 / 3268.8^1.4
1.73 Ohms
Setting Calculation
Positive Sequence Values
Line resistance (Primary) = +ve seq. resistance/KM X Line length
= 0.04745 X 3.9
R1(Pri) = 0.1851 Ohms
= 1.228305 X 400
1000
X1(Sec) = 0.4913 Ohms
Page 18
DOCUMENT: RELAY SETTING CALCULATION DOC NO: KE - 597315
STATION: 132kV Markaz Zallum Substation Rev. No. : A
= 5.56452 X 400
1000
X0(Sec) = 2.2258 Ohms
Note: Resistance setting 1.0 ohms will cover Arc resistance Value 0.23 Ohms & Line zone1 resistance.
Page 19
DOCUMENT: RELAY SETTING CALCULATION DOC NO: KE - 597315
STATION: 132kV Markaz Zallum Substation Rev. No. : A
Zone-2 P/F total Res. (RFPP-Z2) 1.25 Ohms (1.25 times of zone 1 RFPP-Z1)
Forward Direction
Zone-2 E/F toal Res. (RFPE-Z2) 4.78 (1.1 times of zone 1 RFPE-Z1)
Zone3 P/F total res. (RFPP-Z3) = 1.56 Ohms (1.1 times of zone 2 RFPE)
Forward Direction
Zone-3E/F Res. (RFPE-Z3) setting 5.26 Ohms (1.1 times of zone 2 RFPE)
Page 20
DOCUMENT: RELAY SETTING CALCULATION DOC NO: KE - 597315
STATION: 132kV Markaz Zallum Substation Rev. No. : A
Load Impedance
Page 21
DOCUMENT: RELAY SETTING CALCULATION DOC NO: KE - 597315
STATION: 132kV Markaz Zallum Substation Rev. No. : A
4.61
76.25
81.43
-5.18 Deg
{ }
= (4.61 Ang -5.18) - 1
Z OL
⟨ - 1⟩
ZL = (4.59 + j -0.27) - 1
= 3.59 + j -0.27
3.6
1 Z 0 L - ZL = (1 / 3) x 3.6
3 ZL 1.20
{ }
ANGLE = X0 -X L XL
L
arctan ⟨ ⟩ - arctan ⟨ ⟩
R 0 L− R L RL
ANGLE = ATAN ((1.4268 - 0.31495) / (0.34903 - 0.04745))-ATAN(0.31495 / 0.04745)
-0.115334510122086
-6.61 DEG
Z1 = SQRT(0.04745^2 + 0.31495^2)
0.32 Ohms
Angle #VALUE!
#VALUE!
Page 22
DOCUMENT: RELAY SETTING CALCULATION DOC NO: KE - 597315
STATION: 132kV Markaz Zallum Substation Rev. No. : A
PARAMETERS SETTINGS
CONFIGURATION
Setting Group 1 Enabled
Distance Enabled
Directional E/F Enabled
Delta Dir Disabled
Power Swing Block Enabled
Supervision Enabled
Setting Values Secondary
SYSTEM DATA
Page 23
DOCUMENT: RELAY SETTING CALCULATION DOC NO: KE - 597315
STATION: 132kV Markaz Zallum Substation Rev. No. : A
Page 24
DOCUMENT: RELAY SETTING CALCULATION DOC NO: KE - 597315
STATION: 132kV Markaz Zallum Substation Rev. No. : A
Page 25
DOCUMENT: RELAY SETTING CALCULATION DOC NO: KE - 597315
STATION: 132kV Markaz Zallum Substation Rev. No. : A
GROUP 1 DIRECTIONAL FN
DEF SCHEME
DEF STATUS Enabled
DEF Polarizing Zero Sequence
DEF Char Angle -60o
DEF Vnpol Set 3V
DEF Threshold 0.1
SUPERVISION
Page 26
System details
Substation AL-QADISIYYAH 115/13.8KV
Line 115KV NORTH MUBARRAZ
System voltage: 115 KV
Max. Load current: 850 A
Load Angle 25 Deg
3 phase Bus fault level 4000 A
3 phase fault angle 85.00 Deg
1 phase Bus fault level 3000 A
1 phase fault angle 80.00 Deg
Feeder: OVER HEAD LINE
Feeder length: 3.900 Km
+ve seq. Resistance/Km: 0.0475 Ohms
+ve seq. Reactance/Km: 0.3150 Ohms
Line angle 81.00 deg
Zero seq. Resistance/Km: 0.3490 Ohms
Zero seq. Reactance/Km: 1.4268 Ohms
Mutual Resistance/Km: N/A
Mutual Reactance/Km: N/A
ARC resitance: TO BE CALCULATED
Tower-foot resistance 20 Ohms
Conductor to Ground Distance 5.0 Mtr
Conductor to Conductor
Distance 5.0 Mtr
Zone-1 coverage: 80 % of the Protected line
Zone-2 coverage: 120 % of the Protected line
Zone-3 coverage: 220 % of the Protected line
Zone-4 coverage: N/A
Power swing: N/A
Cable portion
Feeder length:
+ve seq. Resistance/KM:
+ve seq. Reactance/KM:
Zero seq. Resistance/KM:
Zero seq. Reactance/KM:
Longest line at remote end
Feeder length:
+ve seq. Resistance/KM:
+ve seq. Reactance/KM:
Zero seq. Resistance/KM:
Zero seq. Reactance/KM:
Longest line at remote end
Feeder length:
+ve seq. Resistance/KM:
+ve seq. Reactance/KM:
Zero seq. Resistance/KM:
Zero seq. Reactance/KM:
Tr Rating at other end
Tr % impedance:
Tr. X/R Ratio
Infeed at remote:
Power swing:
Page 2 of 28
Circuit Breaker:
CT core:
CT py. Current 2000 A
CT sec. Current 5A
CT Ratio 400
PT sec. Voltage: 115 V
PT Ratio 1000
Page 3 of 28
TRIP: 3 Phase Trip
Page 4 of 28
Column1
Page 5 of 28
Enabled
Disabled
Considered
Not considered
1
5
100
110
115
Quad
Mho
Quad/Mho
Over Reach (POTT)
Under reach (PUTT)
Disabled
3 phase Trip
1 phase Trip
Echo & Trip
Echo only
Off
N/A
Page 6 of 28