Cable Sizing Calculation - Open Electrical (Wiki)
Cable Sizing Calculation - Open Electrical (Wiki)
Cable Sizing Calculation - Open Electrical (Wiki)
Contents
1 Introduction
1.1 Why do the calculation?
1.2 When to do the calculation?
2 General Methodology
2.1 Step 1: Data Gathering
2.1.1 Load Details
2.1.2 Cable Construction
2.1.3 Installation Conditions
2.2 Step 2: Cable Selection Based on Current Rating
2.2.1 Base Current Ratings
2.2.2 Installed Current Ratings
2.2.3 Cable Selection and Coordination with Protective Devices
2.2.3.1 Feeders
2.2.3.2 Motors
2.3 Step 3: Voltage Drop
2.3.1 Cable Impedances
2.3.2 Calculating Voltage Drop
2.3.3 Maximum Permissible Voltage Drop
2.3.4 Calculating Maximum Cable Length due to Voltage Drop
2.4 Step 4: Short Circuit Temperature Rise
2.4.1 Minimum Cable Size Due to Short Circuit Temperature Rise
2.4.2 Initial and Final Conductor Temperatures
2.4.3 Short Circuit Energy
2.5 Step 5: Earth Fault Loop Impedance
2.5.1 The Earth Fault Loop
2.5.2 Maximum Cable Length
3 Worked Example
3.1 Step 1: Data Gathering
3.2 Step 2: Cable Selection Based on Current Rating
3.3 Step 3: Voltage Drop
https://wiki.openelectrical.org/index.php?title=Cable_Sizing_Calculation 1/16
4/6/2020 Cable Sizing Calculation - Open Electrical
Introduction
This article examines the sizing of electrical cables (i.e. cross-sectional area) and its implementation in various international
standards. Cable sizing methods do differ across international standards (e.g. IEC, NEC, BS, etc) and some standards
emphasise certain things over others. However the general principles underlying any cable sizing calculation do not change.
In this article, a general methodology for sizing cables is first presented and then the specific international standards are
introduced.
The proper sizing of an electrical (load bearing) cable is important to ensure that the cable can:
This calculation can be done individually for each power cable that needs to be sized, or alternatively, it can be used to produce cable sizing waterfall charts for
groups of cables with similar characteristics (e.g. cables installed on ladder feeding induction motors).
https://wiki.openelectrical.org/index.php?title=Cable_Sizing_Calculation 2/16
4/6/2020 Cable Sizing Calculation - Open Electrical
General Methodology
All cable sizing methods more or less follow the same basic six step process:
1) Gathering data about the cable, its installation conditions, the load that it will carry, etc
2) Determine the minimum cable size based on continuous current carrying capacity
3) Determine the minimum cable size based on voltage drop considerations
4) Determine the minimum cable size based on short circuit temperature rise
5) Determine the minimum cable size based on earth fault loop impedance
6) Select the cable based on the highest of the sizes calculated in step 2, 3, 4 and 5
The first step is to collate the relevant information that is required to perform the sizing calculation. Typically, you will need to obtain the following data:
Load Details
The characteristics of the load that the cable will supply, which includes:
Cable Construction
Installation Conditions
Current flowing through a cable generates heat through the resistive losses in the conductors, dielectric losses through the insulation and resistive losses from
current flowing through any cable screens / shields and armouring.
The component parts that make up the cable (e.g. conductors, insulation, bedding, sheath, armour, etc) must be capable of withstanding the temperature rise and
heat emanating from the cable. The current carrying capacity of a cable is the maximum current that can flow continuously through a cable without damaging the
cable's insulation and other components (e.g. bedding, sheath, etc). It is sometimes also referred to as the continuous current rating or ampacity of a cable.
Cables with larger conductor cross-sectional areas (i.e. more copper or aluminium) have lower resistive losses and are able to dissipate the heat better than smaller
cables. Therefore a 16 mm2 cable will have a higher current carrying capacity than a 4 mm2 cable.
International standards and manufacturers of cables will quote base current ratings of different types of cables in tables such as the one shown on the right. Each of
these tables pertain to a specific type of cable construction (e.g. copper conductor, PVC insulated, 0.6/1kV voltage grade, etc) and a base set of installation
conditions (e.g. ambient temperature, installation method, etc). It is important to note that the current ratings are only valid for the quoted types of cables and base
installation conditions.
In the absence of any guidance, the following reference based current ratings may be used.
When the proposed installation conditions differ from the base conditions, derating (or correction) factors can
be applied to the base current ratings to obtain the actual installed current ratings.
International standards and cable manufacturers will provide derating factors for a range of installation
conditions, for example ambient / soil temperature, grouping or bunching of cables, soil thermal resistivity, etc.
The installed current rating is calculated by multiplying the base current rating with each of the derating
factors, i.e.
Ic = Ib . k d
For example, suppose a cable had an ambient temperature derating factor of kamb = 0.94 and a grouping
derating factor of kg = 0.85 , then the overall derating factor kd = 0.94x0.85 = 0.799 . For a cable with
a base current rating of 42A, the installed current rating would be Ic = 0.799x42 = 33.6A .
Table 1. Example of base current rating table
In the absence of any guidance, the following reference derating factors may be used. (Excerpt from IEC 60364-5-52)
Feeders
When sizing cables for non-motor loads, the upstream protective device (fuse or circuit breaker) is typically selected to also protect the cable against damage from
thermal overload. The protective device must therefore be selected to exceed the full load current, but not exceed the cable's installed current rating, i.e. this
inequality must be met:
Il ≤ Ip ≤ Ic
Motors
https://wiki.openelectrical.org/index.php?title=Cable_Sizing_Calculation 5/16
4/6/2020 Cable Sizing Calculation - Open Electrical
Motors are normally protected by a separate thermal overload (TOL) relay and therefore the upstream protective device (e.g. fuse or circuit breaker) is not required
to protect the cable against overloads. As a result, cables need only to be sized to cater for the full load current of the motor, i.e.
Il ≤ Ic
Of course, if there is no separate thermal overload protection on the motor, then the protective device needs to be taken into account as per the case for feeders
above.
A cable's conductor can be seen as an impedance and therefore whenever current flows through a cable, there will be a voltage drop across it, which can be derived
by Ohm’s Law (i.e. V = IZ). The voltage drop will depend on two things:
Current flow through the cable – the higher the current flow, the higher the voltage drop
Impedance of the conductor – the larger the impedance, the higher the voltage drop
Cable Impedances
The impedance of the cable is a function of the cable size (cross-sectional area) and the length of the cable. Most cable manufacturers will quote a cable’s
resistance and reactance in Ω/km. The following typical cable impedances for low voltage AC and DC single core and multicore cables can be used in the absence
of any other data.
For AC systems, the method of calculating voltage drops based on load power factor is commonly used. Full load currents are normally used, but if the load has
high startup currents (e.g. motors), then voltage drops based on starting current (and power factor if applicable) should also be calculated.
https://wiki.openelectrical.org/index.php?title=Cable_Sizing_Calculation 6/16
4/6/2020 Cable Sizing Calculation - Open Electrical
For a DC system:
2I R c L
Vdc =
1000
It is customary for standards (or clients) to specify maximum permissible voltage drops, which is the highest voltage drop that is allowed across a cable. Should
your cable exceed this voltage drop, then a larger cable size should be selected.
Maximum voltage drops across a cable are specified because load consumers (e.g. appliances) will have an input voltage tolerance range. This means that if the
voltage at the appliance is lower than its rated minimum voltage, then the appliance may not operate correctly.
https://wiki.openelectrical.org/index.php?title=Cable_Sizing_Calculation 7/16
4/6/2020 Cable Sizing Calculation - Open Electrical
In general, most electrical equipment will operate normally at a voltage as low as 80% nominal voltage. For example, if the nominal voltage is 230VAC, then most
appliances will run at >184VAC. Cables are typically sized for a more conservative maximum voltage drop, in the range of 5 – 10% at full load.
It may be more convenient to calculate the maximum length of a cable for a particular conductor size given a maximum permissible voltage drop (e.g. 5% of
nominal voltage at full load) rather than the voltage drop itself. For example, by doing this it is possible to construct tables showing the maximum lengths
corresponding to different cable sizes in order to speed up the selection of similar type cables.
The maximum cable length that will achieve this can be calculated by re-arranging the voltage drop equations and substituting the maximum permissible voltage
drop (e.g. 5% of 415V nominal voltage = 20.75V). For a three phase system:
1000V3ϕ
Lmax =
–
√3I (R c cos ϕ + Xc sin ϕ)
1000V1ϕ
Lmax =
2I (R c cos ϕ + Xc sin ϕ)
For a DC system:
https://wiki.openelectrical.org/index.php?title=Cable_Sizing_Calculation 8/16
4/6/2020 Cable Sizing Calculation - Open Electrical
1000Vdc
Lmax =
2I R c
During a short circuit, a high amount of current can flow through a cable for a short time. This surge in current flow causes a temperature rise within the cable.
High temperatures can trigger unwanted reactions in the cable insulation, sheath materials and other components, which can prematurely degrade the condition of
the cable. As the cross-sectional area of the cable increases, it can dissipate higher fault currents for a given temperature rise. Therefore, cables should be sized to
withstand the largest short circuit that it is expected to see.
The minimum cable size due to short circuit temperature rise is typically calculated with an equation of the form:
−−
2
√i t
A =
k
The temperature rise constant is calculated based on the material properties of the conductor and the initial and final conductor temperatures (see the derivation
here). Different international standards have different treatments of the temperature rise constant, but by way of example, IEC 60364-5-54 calculates it as follows:
−−−−−−−−−−−−−−−−
θf − θi
k = 226√ln(1 + ) (for copper conductors)
234.5 + θi
https://wiki.openelectrical.org/index.php?title=Cable_Sizing_Calculation 9/16
4/6/2020 Cable Sizing Calculation - Open Electrical
−−−−−−−−−−−−−−−
θf − θi
k = 148√ln(1 + ) (for aluminium conductors)
228 + θi
The initial conductor temperature is typically chosen to be the maximum operating temperature of the cable. The final conductor temperature is typically chosen to
be the limiting temperature of the insulation. In general, the cable's insulation will determine the maximum operating temperature and limiting temperatures.
As a rough guide, the following temperatures are common for the different insulation materials:
PVC 75 160
EPR 90 250
XLPE 90 250
The short circuit energy i2 t is normally chosen as the maximum short circuit that the cable could potentially experience. However for circuits with current
limiting devices (such as HRC fuses), then the short circuit energy chosen should be the maximum prospective let-through energy of the protective device, which
can be found from manufacturer data.
Sometimes it is desirable (or necessary) to consider the earth fault loop impedance of a circuit in the sizing of a cable. Suppose a bolted earth fault occurs between
an active conductor and earth. During such an earth fault, it is desirable that the upstream protective device acts to interrupt the fault within a maximum
disconnection time so as to protect against any inadvertent contact to exposed live parts.
https://wiki.openelectrical.org/index.php?title=Cable_Sizing_Calculation 10/16
4/6/2020 Cable Sizing Calculation - Open Electrical
Ideally the circuit will have earth fault protection, in which case the protection will be fast acting and well within the maximum disconnection time. The maximum
disconnection time is chosen so that a dangerous touch voltage does not persist for long enough to cause injury or death. For most circuits, a maximum
disconnection time of 5s is sufficient, though for portable equipment and socket outlets, a faster disconnection time is desirable (i.e. <1s and will definitely require
earth fault protection).
However for circuits that do not have earth fault protection, the upstream protective device (i.e. fuse or circuit breaker) must trip within the maximum
disconnection time. In order for the protective device to trip, the fault current due to a bolted short circuit must exceed the value that will cause the protective
device to act within the maximum disconnection time. For example, suppose a circuit is protected by a fuse and the maximum disconnection time is 5s, then the
fault current must exceed the fuse melting current at 5s (which can be found by cross-referencing the fuse time-current curves).
V0
IA =
Zs
Where IA is the earth fault current required to trip the protective device within the minimum disconnection time (A)
It can be seen from the equation above that the impedance of the earth fault loop must be sufficiently low to ensure that the earth fault current can trip the upstream
protection.
The earth fault loop can consist of various return paths other than the earth conductor, including the cable armour and the static earthing connection of the facility.
However for practical reasons, the earth fault loop in this calculation consists only of the active conductor and the earth conductor.
Zs = Zc + Ze
Assuming that the active and earth conductors have identical lengths, the earth fault loop impedance can be calculated as follows:
https://wiki.openelectrical.org/index.php?title=Cable_Sizing_Calculation 11/16
4/6/2020 Cable Sizing Calculation - Open Electrical
L −−−−−−−−−−−−−−−−−−−−
2 2
Zs = √(R c + R e ) + (Xc + Xe )
1000
Rc and Re are the ac resistances of the active and earth conductors respectively (Ω/km)
Xc and Xe are the reactances of the active and earth conductors respectively (Ω/km)
The maximum earth fault loop impedance can be found by re-arranging the equation above:
V0
Zs,max =
IA
1000V0
Lmax =
−−−−−−−−−−−−−−−−−−−−
2 2
IA √(R c + R e ) + (Xc + Xe )
Note that the voltage V0 at the protective device is not necessarily the nominal phase to earth voltage, but usually a lower value as it can be downstream of the
main busbars. This voltage is commonly represented by applying some factor c to the nominal voltage. A conservative value of c = 0.8 can be used so that:
V0 = cVn = 0.8Vn
Worked Example
In this example, we will size a cable for a 415V, 37kW three-phase motor from the MCC to the field.
Suppose the ambient temperature derating is 0.89 and the grouping derating for 3 bunched cables on a single layer is 0.82. The overall derating factor is 0.89 ×
0.82 = 0.7298. Given that a 16 mm2 and 25 mm2 have base current ratings of 80A and 101A respectively (based on Reference Method E), which cable should
be selected based on current rating considerations?
2 2
The installed current ratings for 16 mm and 25 mm is 0.7298 × 80A = 58.38A and 0.7298 × 101A = 73.71A respectively. Given that the full load current of
the motor is 61A, then the installed current rating of the 16 mm2 cable is lower than the full load current and is not suitable for continuous use with the motor.
2
The 25 mm cable on the other hand has an installed current rating that exceeds the motor full load current, and is therefore the cable that should be selected.
Suppose a 25 mm2 cable is selected. If the maximum permissible voltage drop is 5%, is the cable suitable for a run length of 90m?
2
A 25 mm cable has an ac resistance of 0.884 Ω/km and an ac reactance of 0.0895 Ω/km. The voltage drop across the cable is:
90 – −1
Vd = × √3 × 61 × [0.884 × 0.85 + 0.0895 × sin(cos (0.85)] = 7.593V
1000
https://wiki.openelectrical.org/index.php?title=Cable_Sizing_Calculation 13/16
4/6/2020 Cable Sizing Calculation - Open Electrical
7.593
A voltage drop of 7.593V is equivalent to = 1.83 , which is lower than the maximum permissible voltage dorp of 5%. Therefore the cable is suitable for
415
the motor based on voltage drop considerations.
The cable is operating normally at 75C and has a prospective fault capacity (I 2 t) of 90,000 A 2 s . What is the minimum size of the cable based on short circuit
temperature rise?
PVC has a limiting temperature of 160C. Using the IEC formula, the short circuit temperature rise constant is 111.329. The minimum cable size due to short circuit
temperature rise is therefore:
−−−− −−
√90, 000
2
A = = 2.695mm
111.329
In this example, we also use the fuse for earth fault protection and it needs to trip within 5s, which is at the upper end of the adiabatic period where the short circuit
temperature rise equation is still valid. Therefore, it's a good idea to also check that the cable can withstand the short circuit temperature rise for for a 5s fault. The
80A motor fuse has a 5s melting current of 550A. The short circuit temperature rise is thus:
−−−−−−−
2
√550 × 5
2
A = = 11.047mm
111.329
2
Therefore, our 25 mm cable is still suitable for this application.
Suppose there is no special earth fault protection for the motor and a bolted single phase to earth fault occurs at the motor terminals. Suppose that the earth
2 2
conductor for our 25 mm cable is 10 mm . If the maximum disconnection time is 5s, is our 90m long cable suitable based on earth fault loop impedance?
The 80A motor fuse has a 5s melting current of 550A. The ac resistances of the active and earth conductors are 0.884 Ω/km and 2.33 Ω/km) respectively. The
reactances of the active and earth conductors are 0.0895 Ω/km and 0.0967 Ω/km) respectively.
(1000)(0.8)(240)
Lmax = −−−−−−−−−−−−−−−−−−−−−−−−−−−−− = 108.43m
2 2
550√(0.884 + 2.33) + (0.0895 + 0.0967)
https://wiki.openelectrical.org/index.php?title=Cable_Sizing_Calculation 14/16
4/6/2020 Cable Sizing Calculation - Open Electrical
The cable run is 90m and the maximum length allowed is 108m, therefore our cable is suitable based on earth fault loop impedance. In fact, our 25 mm2 cable
has passed all the tests and is the size that should be selected.
Waterfall Charts
Sometimes it is convenient to group together similar types of cables (for example, 415V PVC
motor cables installed on cable ladder) so that instead of having to go through the laborious
exercise of sizing each cable separately, one can select a cable from a pre-calculated chart.
These charts are often called "waterfall charts" and typically show a list of load ratings and the
maximum of length of cable permissible for each cable size. Where a particular cable size fails
to meet the requirements for current carrying capacity or short circuit temperature rise, it is
blacked out on the chart (i.e. meaning that you can't choose it).
Preparing a waterfall chart is common practice when having to size many like cables and
substantially cuts down the time required for cable selection.
Table 2. Example of a cable waterfall chart
International Standards
IEC
IEC 60364-5-52 (2009) (https://webstore.iec.ch/publication/1878) "Electrical installations in buildings - Part 5-52: Selection and erection of electrical equipment -
Wiring systems" is the IEC standard governing cable sizing.
NEC
NFPA 70 (2011) (http://www.nfpa.org/aboutthecodes/AboutTheCodes.asp?DocNum=70&cookie_test=1) "National Electricity Code" is the equivalent standard for
IEC 60364 in North America and includes a section covering cable sizing in Article 300.
BS
BS 7671 (2008) (http://electrical.theiet.org/wiring-regulations/index.cfm) "Requirements for Electrical Installations - IEE Wiring Regulations" is the equivalent
standard for IEC 60364 in the United Kingdom.
AS/NZS
https://wiki.openelectrical.org/index.php?title=Cable_Sizing_Calculation 15/16
4/6/2020 Cable Sizing Calculation - Open Electrical
AS/NZS 3008.1 (2009) (http://infostore.saiglobal.com/store/Details.aspx?productid=1141542) "Electrical installations - Selection of cables - Cables for alternating
voltages up to and including 0.6/1 kV" is the standard governing low voltage cable sizing in Australia and New Zealand. AS/NZS 3008.1.1 is for Australian
conditions and AS/NZS 3008.1.2 is for New Zealand conditions.
Computer Software
Desktop
Most of the major power systems analysis software packages (e.g. ETAP, PTW, etc) have a cable sizing module. There also exists other (offline) software packages
that include cable sizing (for example from Solutions Electrical UK (http://www.electricalsoftware.co.uk/cable_calculations.php)).
Online
Cablesizer (http://www.cablesizer.com) - a free web application for sizing cables to NEC and IEC standards
Ele Study: AS 3008 (http://www.as3008.com/) - a free web application for sizing cables to AS 3008 standards
myElectrical Cable Sizing Calculator (http://myelectrical.com/tools/cable-sizing-calculator) - free web application for sizing cables to BS/IEE standards
Mobile
Cablesizer for Android (https://play.google.com/store/apps/details?id=com.altersource.cablesizer&hl=en) - a free (beta) Android version of the cable sizing
tool "Cablesizer".
What next?
Having sized the power / load-bearing cables, the cable schedule can now be developed and then the cable material take-offs (MTO).
https://wiki.openelectrical.org/index.php?title=Cable_Sizing_Calculation 16/16