Cable Sizing Calculation
Cable Sizing Calculation
Cable Sizing Calculation
Contents
1 Introduction
o 1.1 Why do the calculation?
o 1.2 When to do the calculation?
2 General Methodology
o 2.1 Step 1: Data Gathering
2.1.1 Load Details
2.1.2 Cable Construction
2.1.3 Installation Conditions
o 2.2 Step 2: Cable Selection Based on Current Rating
2.2.1 Base Current Ratings
2.2.2 Installed Current Ratings
2.2.3 Cable Selection and Coordination with Protective Devices
2.2.3.1 Feeders
2.2.3.2 Motors
o 2.3 Step 3: Voltage Drop
2.3.1 Cable Impedances
2.3.2 Calculating Voltage Drop
2.3.3 Maximum Permissible Voltage Drop
2.3.4 Calculating Maximum Cable Length due to Voltage Drop
o 2.4 Step 4: Short Circuit Temperature Rise
2.4.1 Minimum Cable Size Due to Short Circuit Temperature
Rise
2.4.2 Initial and Final Conductor Temperatures
2.4.3 Short Circuit Energy
o 2.5 Step 5: Earth Fault Loop Impedance
2.5.1 The Earth Fault Loop
2.5.2 Maximum Cable Length
3 Worked Example
o 3.1 Step 1: Data Gathering
o 3.2 Step 2: Cable Selection Based on Current Rating
o 3.3 Step 3: Voltage Drop
o 3.4 Step 4: Short Circuit Temperature Rise
o 3.5 Step 5: Earth Fault Loop Impedance
4 Waterfall Charts
5 International Standards
o 5.1 IEC
o 5.2 NEC
o 5.3 BS
o 5.4 AS/NZS
6 Computer Software
7 What next?
Introduction
This article examines the sizing of electrical cables (i.e. cross-sectional area) and its
implementation in various international standards. Cable sizing methods do differ
across international standards (e.g. IEC, NEC, BS, etc) and some standards emphasise
certain things over others. However the general principles underlying any cable sizing
calculation do not change. In this article, a general methodology for sizing cables is
first presented and then the specific international standards are introduced.
The proper sizing of an electrical (load bearing) cable is important to ensure that the
cable can:
This calculation can be done individually for each power cable that needs to be sized,
or alternatively, it can be used to produce cable sizing waterfall charts for groups of
cables with similar characteristics (e.g. cables installed on ladder feeding induction
motors).
General Methodology
All cable sizing methods more or less follow the same basic six step process:
1) Gathering data about the cable, its installation conditions, the load that it
will carry, etc
2) Determine the minimum cable size based on continuous current carrying
capacity
3) Determine the minimum cable size based on voltage drop considerations
4) Determine the minimum cable size based on short circuit temperature rise
5) Determine the minimum cable size based on earth fault loop impedance
6) Select the cable based on the highest of the sizes calculated in step 2, 3, 4
and 5
Step 1: Data Gathering
The first step is to collate the relevant information that is required to perform the
sizing calculation. Typically, you will need to obtain the following data:
Load Details
The characteristics of the load that the cable will supply, which includes:
Cable Construction
Installation Conditions
Current flowing through a cable generates heat through the resistive losses in the
conductors, dielectric losses through the insulation and resistive losses from current
flowing through any cable screens / shields and armouring.
The component parts that make up the cable (e.g. conductors, insulation, bedding,
sheath, armour, etc) must be capable of withstanding the temperature rise and heat
emanating from the cable. The current carrying capacity of a cable is the maximum
current that can flow continuously through a cable without damaging the cable's
insulation and other components (e.g. bedding, sheath, etc). It is sometimes also
referred to as the continuous current rating or ampacity of a cable.
Cables with larger conductor cross-sectional areas (i.e. more copper or aluminium)
have lower resistive losses and are able to dissipate the heat better than smaller cables.
Therefore a 16 mm2 cable will have a higher current carrying capacity than a 4 mm2
cable.
International standards and manufacturers of cables will quote base current ratings of
different types of cables in tables such as the one shown on the right. Each of these
tables pertain to a specific type of cable construction (e.g. copper conductor, PVC
insulated, 0.6/1kV voltage grade, etc) and a base set of installation conditions (e.g.
ambient temperature, installation method, etc). It is important to note that the current
ratings are only valid for the quoted types of cables and base installation conditions.
In the absence of any guidance, the following reference based current ratings may be
used.
Installed Current Ratings
When the proposed installation conditions differ from the base conditions, derating
(or correction) factors can be applied to the base current ratings to obtain the actual
installed current ratings.
International standards and cable manufacturers will provide derating factors for a
range of installation conditions, for example ambient / soil temperature, grouping or
bunching of cables, soil thermal resistivity, etc. The installed current rating is
calculated by multiplying the base current rating with each of the derating factors, i.e.
For example, suppose a cable had an ambient temperature derating factor of kamb =
0.94 and a grouping derating factor of kg = 0.85, then the overall derating factor kd =
0.94x0.85 = 0.799. For a cable with a base current rating of 42A, the installed current
rating would be Ic = 0.799x42 = 33.6A.
In the absence of any guidance, the following reference derating factors may be used.
Feeders
When sizing cables for non-motor loads, the upstream protective device (fuse or
circuit breaker) is typically selected to also protect the cable against damage from
thermal overload. The protective device must therefore be selected to exceed the full
load current, but not exceed the cable's installed current rating, i.e. this inequality
must be met:
Motors
Motors are normally protected by a separate thermal overload (TOL) relay and
therefore the upstream protective device (e.g. fuse or circuit breaker) is not required to
protect the cable against overloads. As a result, cables need only to be sized to cater
for the full load current of the motor, i.e.
Where is the full load current (A)
Of course, if there is no separate thermal overload protection on the motor, then the
protective device needs to be taken into account as per the case for feeders above.
Current flow through the cable – the higher the current flow, the higher
the voltage drop
Impedance of the conductor – the larger the impedance, the higher the
voltage drop
Cable Impedances
The impedance of the cable is a function of the cable size (cross-sectional area) and
the length of the cable. Most cable manufacturers will quote a cable’s resistance and
reactance in Ω/km. The following typical cable impedances for low voltage AC and
DC single core and multicore cables can be used in the absence of any other data.
For AC systems, the method of calculating voltage drops based on load power factor
is commonly used. Full load currents are normally used, but if the load has high
startup currents (e.g. motors), then voltage drops based on starting current (and power
factor if applicable) should also be calculated.
For a DC system:
Maximum voltage drops across a cable are specified because load consumers (e.g.
appliances) will have an input voltage tolerance range. This means that if the voltage
at the appliance is lower than its rated minimum voltage, then the appliance may not
operate correctly.
In general, most electrical equipment will operate normally at a voltage as low as 80%
nominal voltage. For example, if the nominal voltage is 230VAC, then most
appliances will run at >184VAC. Cables are typically sized for a more conservative
maximum voltage drop, in the range of 5 – 10% at full load.
It may be more convenient to calculate the maximum length of a cable for a particular
conductor size given a maximum permissible voltage drop (e.g. 5% of nominal
voltage at full load) rather than the voltage drop itself. For example, by doing this it is
possible to construct tables showing the maximum lengths corresponding to different
cable sizes in order to speed up the selection of similar type cables.
The maximum cable length that will achieve this can be calculated by re-arranging the
voltage drop equations and substituting the maximum permissible voltage drop (e.g.
5% of 415V nominal voltage = 20.75V). For a three phase system:
For a DC system:
During a short circuit, a high amount of current can flow through a cable for a short
time. This surge in current flow causes a temperature rise within the cable. High
temperatures can trigger unwanted reactions in the cable insulation, sheath materials
and other components, which can prematurely degrade the condition of the cable. As
the cross-sectional area of the cable increases, it can dissipate higher fault currents for
a given temperature rise. Therefore, cables should be sized to withstand the largest
short circuit that it is expected to see.
The minimum cable size due to short circuit temperature rise is typically calculated
with an equation of the form:
The temperature rise constant is calculated based on the material properties of the
conductor and the initial and final conductor temperatures (see the derivation here).
Different international standards have different treatments of the temperature rise
constant, but by way of example, IEC 60364-5-54 calculates it as follows:
The short circuit energy is normally chosen as the maximum short circuit that the
cable could potentially experience. However for circuits with current limiting devices
(such as HRC fuses), then the short circuit energy chosen should be the maximum
prospective let-through energy of the protective device, which can be found from
manufacturer data.
Sometimes it is desirable (or necessary) to consider the earth fault loop impedance of
a circuit in the sizing of a cable. Suppose a bolted earth fault occurs between an active
conductor and earth. During such an earth fault, it is desirable that the upstream
protective device acts to interrupt the fault within a maximum disconnection time so
as to protect against any inadvertent contact to exposed live parts.
Ideally the circuit will have earth fault protection, in which case the protection will be
fast acting and well within the maximum disconnection time. The maximum
disconnection time is chosen so that a dangerous touch voltage does not persist for
long enough to cause injury or death. For most circuits, a maximum disconnection
time of 5s is sufficient, though for portable equipment and socket outlets, a faster
disconnection time is desirable (i.e. <1s and will definitely require earth fault
protection).
However for circuits that do not have earth fault protection, the upstream protective
device (i.e. fuse or circuit breaker) must trip within the maximum disconnection time.
In order for the protective device to trip, the fault current due to a bolted short circuit
must exceed the value that will cause the protective device to act within the maximum
disconnection time. For example, suppose a circuit is protected by a fuse and the
maximum disconnection time is 5s, then the fault current must exceed the fuse
melting current at 5s (which can be found by cross-referencing the fuse time-current
curves).
By simple application of Ohm's law:
Where is the earth fault current required to trip the protective device within the
minimum disconnection time (A)
It can be seen from the equation above that the impedance of the earth fault loop must
be sufficiently low to ensure that the earth fault current can trip the upstream
protection.
The earth fault loop can consist of various return paths other than the earth conductor,
including the cable armour and the static earthing connection of the facility. However
for practical reasons, the earth fault loop in this calculation consists only of the active
conductor and the earth conductor.
Assuming that the active and earth conductors have identical lengths, the earth fault
loop impedance can be calculated as follows:
The maximum earth fault loop impedance can be found by re-arranging the equation
above:
Note that the voltage V0 at the protective device is not necessarily the nominal phase
to earth voltage, but usually a lower value as it can be downstream of the main
busbars. This voltage is commonly represented by applying some factor to the
nominal voltage. A conservative value of = 0.8 can be used so that:
Suppose the ambient temperature derating is 0.89 and the grouping derating for 3
bunched cables on a single layer is 0.82. The overall derating factor is 0.89 0.82 =
2 2
0.7298. Given that a 16 mm and 25 mm have base current ratings of 80A and 101A
respectively (based on Reference Method E), which cable should be selected based on
current rating considerations?
The installed current ratings for 16 mm2 and 25 mm2 is 0.7298 80A = 58.38A and
0.7298 101A = 73.71A respectively. Given that the full load current of the motor
is 61A, then the installed current rating of the 16 mm2 cable is lower than the full load
current and is not suitable for continuous use with the motor. The 25 mm2 cable on the
other hand has an installed current rating that exceeds the motor full load current, and
is therefore the cable that should be selected.
Suppose a 25 mm2 cable is selected. If the maximum permissible voltage drop is 5%,
is the cable suitable for a run length of 90m?
The cable is operating normally at 75C and has a prospective fault capacity (I2t) of
90,000 A2s. What is the minimum size of the cable based on short circuit temperature
rise?
PVC has a limiting temperature of 160C. Using the IEC formula, the short circuit
temperature rise constant is 111.329. The minimum cable size due to short circuit
temperature rise is therefore:
In this example, we also use the fuse for earth fault protection and it needs to trip
within 5s, which is at the upper end of the adiabatic period where the short circuit
temperature rise equation is still valid. Therefore, it's a good idea to also check that
the cable can withstand the short circuit temperature rise for for a 5s fault. The 80A
motor fuse has a 5s melting current of 550A. The short circuit temperature rise is thus:
Suppose there is no special earth fault protection for the motor and a bolted single
phase to earth fault occurs at the motor terminals. Suppose that the earth conductor for
our 25 mm2 cable is 10 mm2. If the maximum disconnection time is 5s, is our 90m
long cable suitable based on earth fault loop impedance?
The 80A motor fuse has a 5s melting current of 550A. The ac resistances of the active
and earth conductors are 0.884 Ω/km and 2.33 Ω/km) respectively. The reactances of
the active and earth conductors are 0.0895 Ω/km and 0.0967 Ω/km) respectively.
The cable run is 90m and the maximum length allowed is 108m, therefore our cable is
suitable based on earth fault loop
impedance. In fact, our 25 mm2 cable has passed all the tests and is the size that
should be selected.
Waterfall Charts
These charts are often called "waterfall charts" and typically show a list of load
ratings and the maximum of length of cable permissible for each cable size. Where a
particular cable size fails to meet the requirements for current carrying capacity or
short circuit temperature rise, it is blacked out on the chart (i.e. meaning that you can't
choose it).
Preparing a waterfall chart is common practice when having to size many like cables
and substantially cuts down the time required for cable selection.
International Standards
IEC
IEC 60364-5-52 (2009) "Electrical installations in buildings - Part 5-52: Selection and
erection of electrical equipment - Wiring systems" is the IEC standard governing
cable sizing.
NEC
NFPA 70 (2011) "National Electricity Code" is the equivalent standard for IEC 60364
in North America and includes a section covering cable sizing in Article 300.
BS
AS/NZS
Computer Software
Cablesizer is a free online application for sizing cables to IEC standards.
Most of the major electrical analysis packages (e.g. ETAP, PTW, etc) have a cable
sizing module. There also exists other (offline) software packages that include cable
sizing (for example from Solutions Electrical UK).
What next?
Having sized the power / load-bearing cables, the cable schedule can now be
developed and then the cable material take-offs (MTO).