COSIMAT N Plus E
COSIMAT N Plus E
COSIMAT N Plus E
2. Brief summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.1 General diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Adjusting elements and their effects . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Optimising the regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3. Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1 Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Monitoring alternator voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.4 Desired value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.5 Droop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.6 Control amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.7 Additional functions of the ”COSIMAT N+” . . . . . . . . . . . . . . . . . . . . . 10
3.7.1 Underspeed protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.7.2 Protection functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.8 Power stage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7. Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8. Diagrams of connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
8.1 Assembly for DSG alternators 52 – 74 . . . . . . . . . . . . . . . . . . . . . . . 21
8.2 Assembly for DSG alternators 86 – 125 . . . . . . . . . . . . . . . . . . . . . . . 22
8.3 Assembly for DIG medium-voltage alternators with UN ≤ 11.5 kV . . . . . . . . . . . . 23
8.4 Assembly for DIG medium-voltage alternators with UN > 11.5 kV . . . . . . . . . . . . 24
8.5 De-excitation circuit on the ”COSIMAT N+” . . . . . . . . . . . . . . . . . . . . . 25
8.6 Monitoring field current and voltage on the ”COSIMAT N+” . . . . . . . . . . . . . . 25
2
2. Brief summary
2.1 General-arrangement diagram
3
2.2 Adjusting elements and their effects
4
2.3 Start-up
Figure 3 - Start-up
5
2.4 Optimisation of the regulator It is not necessary to adjust the D parameter in order to
optimise the control properties. It is generally determined just
To optimise regulation, it is necessary to connect loads to the once, in accordance with the size of the alternator. In the case
alternator. of alternators > 1 MVA, switch S2.4 is switched to the ON
position.
To allow the trend of the control property following a change
in the P or I parameter to be evaluated, the load connected To decide whether the D parameter should be increased
must be reproducible. beyond this, it is necessary to take specific measurements of
the alternator voltage and at the output of the regulator.
The factor with the greatest general significance in achieving
an optimum regulating system is an overshoot amplitude xm Satisfactory optimisation of the regulator will normally be
which is as small as possible. The essential criterion in the achieved by the free adjustment of the P and I parameters.
evaluation of the regulating process with respect to time is the
settling time taus.
6
3. Functional description
3.1 Block diagram
7
3.2 Power supply 3.3 Monitoring alternator voltage
Power is supplied to the "COSIMAT N+" by means of The "COSIMAT N+" measures alternator voltages from 90 to
so-called auxiliary excitation voltages, which are produced 500 V AC (external conductor voltage) within two selectable
in the alternators. The excitation energy and the supply ranges by means of an internal three-phase measuring trans-
voltage for the "COSIMAT N+" are derived from the auxiliary former.
excitation voltages.
To measure higher voltages, corresponding voltage transfor-
In the case of AvK alternators in Series DSG and DIG with mers must be connected in series.
UN ≤ 11.5 kV, the "COSIMAT N+" is supplied with power
via two single-phase auxiliary windings, which are inserted Signal input N allows intervention into the internal formation
into the main stator. The windings are designated UH1/UH2 of the actual value.
and WH1/WH2.
The secondary AC measurement voltage of the measuring
The voltages UH1 and UH2 are offset by 90° with respect transformer is converted into a DC voltage, smoothed, condi-
to WH1 and WH2 and are 80 V AC ± 20 % at the nominal tioned and output as an actual value to the regulator circuit.
voltage of the alternator.
The measured value which is produced corresponds to the
In the case of AvK alternators belonging to Series DIG with arithmetic mean of the rectified three-phase AC measurement
UN > 11.5 kV, the "COSIMAT N+" is supplied with power voltage.
via a two-phase auxiliary exciter machine. The windings are
designated UH1, UH2, UH3 and WH1, WH2. Three-phase measurement allows for asymmetric loads.
The voltages UH1 and UH2 are offset by 90° with respect Note:
to WH1 and WH2 and are 80 V AC ± 20 % at the nominal For non-linear loads (static thyristor converter or rectifier),
speed of the machine. additional module TF (RC – low-pass filter) is recommended
as a measuring adapter. High non-linear loads may
The above-mentioned auxiliary exciter windings UH1 and require overdimensioning of the alternator.
UH2 and WH1 and WH2 are plugged into the correspon-
dingly designated terminals of the "COSIMAT N+":
3.4 Desired value
Special application
Three-phase auxiliary exciter machine The desired value for the "COSIMAT N+" is taken from a
If a three-phase auxiliary exciter machine is used, the winding temperature-compensated reference source.
terminals are designated UH1-VH1-WH1. The external con-
ductor voltage is 3 x 75 V AC ± 20 % at the nominal speed The signal input ”n” allows intervention in the internal formation
of the machine. of the desired value.
If the auxiliary excitation voltage is taken This potentiometer is used for fine adjustment of the alternator
from a constant "external" power source (e.g. voltage (= ”exact” desired value).
the mains), the supply must be switched on
only after the alternator has been started. The adjustment range is limited to ± 5 % to ± 10 % around
When switching off the alternator, the the nominal value, depending on the potentiometer used.
supply should be switched off before the
machine comes to a halt (see 11.10 External The ES additional module allows the adjustment range of the
power supply). external set-point potentiometer to be extended from remanence
to the nominal voltage.
8
If the ES module is used on AvK alternators, the regulator If, when the alternator is connected in parallel, the fixed mains
system must be provided with an external power supply. This forces it down to a figure which is 6 % lower, the reactive
must be decided on a case by case basis, depending on the current is inductive and equivalent to 100 % of the nominal
application and the excitation system used (auxiliary excitati- alternator current.
on windings or auxiliary excitation machine?)
In parallel operation, regulation of the synchronous alternator
is made possible by the droop sensing signal.
3.5 Droop For stand-alone operation, adjustment is performed on the test
rig using a reactive load. The droop effect is set to 3 %.
Once an alternator has been connected in parallel, voltage
regulation is no longer possible because the system voltage The droop sensing signal in the "COSIMAT N+" influences
is fixed. The slightest fluctuation in the system voltage would the desired value and is produced by means of a geometrical
lead to the alternator producing reactive current > IN. addition of the external conductor voltage U-W and a
current-dependent voltage signal from the V phase.
To stabilise the alternator reactive current it is therefore
necessary to have a measured variable which is dependent In AvK synchronous machines, the corresponding current
on the reactive current and incorporates the magnitude of the transformer is located in phase V. The K side of the transfor-
current and the reactive power (inductive or capacitive). This mers points towards the alternator’s main winding (see Figure
measured variable is introduced at the addition point (com- 6 – Block diagram).
parison point of the desired value and the actual value) of the
control amplifier circuit. Internally load-relieved bushing-type transformers are used.
This produces a static droop control characteristic, which The outlet end of the secondary connections ( = potted end
represents the relationship between: of the transformer) is the primary-side K point (= current input).
the change in the alternator voltage in relation to the nominal The wire marked in white is the secondary-side k point.
voltage and
the change in the alternator reactive current in relation to the The secondary connections k and I of the droop current
nominal current. transformer should be plugged into the correspondingly mar-
ked terminals of the "COSIMAT N+".
The droop is represented by the slope of the characteristic
curve produced i.e. is the quotient of the above ratio. In the case of alternators for parallel and stand-alone opera-
tion, the measuring input k – I can be short-circuited by means
In the "COSIMAT N+" a linear droop characteristic is gene- of a switch for stand-alone operation. This gives better voltage
rated. The droop effect can be adjusted from 0 to 6 % using stability (see 8. Diagrams of connections, 11.5 Droop
the potentiometer R 7. switch).
Caution:
9
kink point” is set to 0.95 x fN. Above the kink point, voltage
Caution: regulation is constant.
Switch position 0 is not allowed; never pass The voltage reduction is delayed by about 2 seconds to
through 0. eliminate the effect of transient drops in the speed of the drive
machine.
The parameter of the P section can be varied by means of In exceptional circumstances, the underspeed protection fun-
potentiometer R 1. During this process, the adjustment range ction can be deactivated by means of code switch S2.2 (see
shown in Figure 8 should not be exceeded. 9.2 Adjusting elements).
Caution:
10
Time limitation of the maximum excitation cur- 3.8 Power stage
rent
The power stage of the "COSIMAT N+" provides an excita-
When the actuator is fully on, the excitation current tion current that corresponds to the output signal of the control
reaches a maximum. amplifier.
If this state is allowed to continue, the exciter system will A MOSFET transistor is used as the actuator, with pulse width
be damaged. modulation, i.e. the turn-on time varies but the switching
frequency remains constant.
However, the fully-on state only occurs in the case of
compensating processes or short circuits at the main The excitation energy is taken from the rectified supply
terminals of the alternator. voltage, the rectifier circuit being located in the power stage.
It allows the rectification of two single-phase or three-phase
The monitoring system of the "COSIMAT N+" limits supply voltages (see 3.2 Power supply).
maximum excitation to 8 to 10 seconds.
There is a short-circuit thyristor in the DC circuit. The protective
After this, the protection circuit isolates the exciter field circuit of the "COSIMAT N+" switches this thyristor on if faults
from the source of excitation energy by tripping the occur in the control circuit. The resulting short-circuit current
protection fuses. trips the two protection fuses on the front plate of the "COSI-
MAT N+" and the exciter field is isolated from the source of
Checking the direction of action of the control excitation energy.
amplifier and the actuator
Fuse:
This feature monitors the positioning transistor for short 10 A super quick-acting
circuits. 32 mm x 6.3 mm ø
IEC G 144.400
Short-circuiting of the positioning transistor leads to maxi-
mum excitation. The control amplifier tries to counteract
this but has no effect on the faulty actuator. The actuator
and the control amplifier act in opposite directions and Caution:
the fuses trip immediately.
Replacement fuses must be of the above type.
The following circumstances also lead to maximum excitation The power stage may suffer permanent dama-
and can trip the fuses: ge if the wrong type of fuse is used.
● Short circuit in the I1 / K1 exciter lead To ensure adequate cooling for the power semi-conductors in
the power stage, you must follow the instructions in Chapter
● Faulty exciter rectifier in the "COSIMAT N+" 11.2 Mounting the regulator.
Note:
Additional module ER1 can be used to limit the excitation
current when the alternator is operated in parallel.
11
4. Transfer function of the "COSIMAT N+"
There are three ways of influencing the control parameters in The time constant of the input low-pass filter is:
the "COSIMAT N+”:
TP1 = 3.62 ms
Potentiometer R1 (500 kΩ) for changing the P parameter. At
the right-hand stop, R1 is 0Ω. The time constant of the output low-pass filter is:
Switch S1 for changing the I parameter in 15 steps (from 0.22 TP2 = 0.268 x T2
to 3.85 µF) each of 0.22 µF (C1).
T1 = R1 x C1
T2 = 6,8 kΩ x C2
T3 = 22 kΩ x C1
TI = T1 + T2
TD = T1 x T2
T1 + T2
K1 =2,56 T1 + T2
T3
K2 = 716,1 ms x K1
Tl
K3 = 1 = 0,066
15
12
5. Special functions and additional
equipment
5.1 Stand-by and emergency manual switchover
13
6. Technical data
GENERAL DATA Type : fully potted aluminium housing incl. power stage
Maintenance : maintenance-free
Rated switch-on time : continuous operation
Installation position : mount with longitudinal axis vertical at
convectional cooling or longitudinal axis
in air flow direction at fan cooling
Installation clearance : 3 cm all round
(see 11.2 Mounting the regulator)
HOUSING, DIMENSIONS,
WEIGHT AND INSTALLATION Height x width x depth : 121 x 115 x 162.5 mm
Fixing : 4 M6 bolts, washers and circlips
Weight : 2 kg
18
7. Dimensions
Figure 25 – Dimensions
19
8. Diagrams of connections
Legend for diagrams of connections
G1 Main machine
G2 Exciter/excitation windings
V1 Rotating rectifier
X1 Main terminals
X2 – 6 Terminal strip
R3 Underspeed protection
R1 P component
S1 I component
R7 Droop adjustment
T6 Droop transformer
20
8.1 Assembly for DSG alternators 52 - 74
21
8.2 Assembly for DSG alternators 86 – 125
22
8.3 Assembly for DIG medium-voltage alternators with UN ≤ 11.5 kV
23
8.4 Assembly for DIG medium-voltage alternators with UN >11.5 kV
24
8.5 De-excitation circuit on the "COSIMAT N+" 8.6 Monitoring field current and voltage on the
"COSIMAT N+"
If a de-excitation circuit is fitted, the bridges on the double
terminals UH1/UH1’ and WH1/WH1’ should be removed. The "COSIMAT N+" is provided with double terminals I1/I1’
Switch contacts should be connected to the double terminals and K1/K1’ to allow the exciter field to be connected. Bridge
to de-excite the alternator when they open (see Figure 34 – I1/I1’ must be removed to allow the field current and voltage
De-excitation circuit). These de-excitation contacts must meet to be monitored (see Figure 35 – Field current/field voltage
the following specification: monitoring).
Current carrying capacity:10 AAC The measuring range for field voltage monitoring is 150 VDC;
Voltage carrying capacity:160 V AC for field current monitoring it is 10 ADC. Rotary coil or
moving-iron instruments are recommended. Under certain
The switch elements used must have dust-protected contact conditions, digital instruments may give false readings.
chambers. Ensure that contact resistance is low – the contacts
must be sensitive to low-level signals. Note:
In the case of AvK alternators (DSG 86 – 125, DIG),
Note:
there are connecting terminals for monitoring the field
One of the factors which determines the build-up of
current and voltage on terminal strip X2.
excitation is the quality of these contacts.
On AvK alternators (DSG 86 – 125, DIG), connecting
terminals for de-excitation are provided in the auxiliary
terminal box (see legend of the order-specific circuit
diagram).
25
9. Connections, adjusting elements and Monitoring droop current:
displays
k–I
9.1 Connections
4.8 x 0.8 mm flat plugs and/or 2.5 mm2/4 mm Ø screw
terminals
Voltage supply:
UH1 Caution:
UH2 (VH1)
WH1 Measuring input k – I is not a current input;
WH2 standard transformers should be load-relieved
accordingly.
4.8 x 0.8 mm flat plugs and/or 2.5 mm2/4mm Ø screw
terminals
Supply can be 2 x single-phase (80 V AC ± 20 %) or The droop current transformer must be installed in the "V"
phase of the alternator.
three-phase (75 V AC ± 20 % external conductor voltage).
Internally load-relieved droop current transformers are
2 x single-phase = UH1-UH2, WH1-WH2
used in AvK alternators.
three-phase = UH1-VH1-WH1
At the nominal current of the alternator, a voltage of 3 to
For de-excitation circuits, the bridges on the double
7 V AC is required at the terminals k – I (see 3.5 Droop
terminals must be removed (see 8.5 De-excitation circuit
and 6. Technical Data).
or order-specific circuit diagram).
Connecting leads to the transformer must be shielded if
Caution:
the regulator is installed externally. Connecting leads to
the short-circuit droop switch (see 11.5 Droop switch)
If there is an external power supply (e.g.
should be shielded in all cases. The shield should be
from the mains), it must not be switched on
earthed at one end on the "COSIMAT N+" (see 8.
until after the alternator has run up. It
Diagrams of connections).
should be switched off before the machine
has come to a halt (see 11.10 External
power supply).
Exciter field:
I1 – K1
Measuring alternator voltage:
4.8 x 0.8 mm flat plugs and/or 2.5 mm2/4 mm Ø screw
U-V-W 250 to 500 V AC terminals as double terminal.
U-V-W 90 to 250 V AC
If the regulator is mounted externally, the I1/K1 field leads to
6.3 x 0.8 mm flat plugs the alternator must be run through a separately shielded cable
(LSYCY or LIYCY).
Caution:
The shield should be earthed at one end on the "COSIMAT N+"
(see 8. Diagrams of connections).
A clockwise rotary field is required. If the
alternator rotates anticlockwise, U and W
should be interchanged (see 3.5 Droop).
External set-point potentiometer
26
The rated power of the potentiometer must be at least 1 This potential is not connected when the "COSIMAT N+"
W. A multiple-turn potentiometer must be used (see 3.4 is used for standalone operation.
Desired value).
Function:
Control inputs: Adjustment of the frequency-dependent lowering of alter-
nator voltage (see 3.7.1 Underspeed protection).
N
M/m Direction of action:
n Left-hand stop = beginning of reduction at >50/60 Hz.
Right-hand stop = beginning of reduction only after
4.8 x 0.8 mm flat plugs and/or 2.5 mm2/4 mm Ø about > 30 Hz.
screw terminals.
In special cases, the underspeed protection can be
A number of additional modules from the "COSIMAT N+" deactivated by means of switch S2.2 (see 9.2 Adjusting
equipment range can be connected to these control elements).
inputs (see 5.2 Additional modules).
This is necessary when regulating a DC voltage by way
of additional module UDC or in some cases when using
Caution: external UF modules.
Direction of action:
Circuit earth: Left-hand stop = minimum alternator voltage
Right-hand stop = maximum alternator voltage
-
Z
P component:
The load earth is used for connecting the internal interme-
diate circuit capacitors.
R1
Additional external capacitors can be connected between
the second Z connection tab (MINUS) and terminal I1 1-gang trim potentiometer
(PLUS).
27
Function: Direction of action:
Varying the proportional component of the control cha- Left-hand stop = maximum compensation value
racteristic. Right-hand stop = minimum compensation value
Function:
Caution:
Droop:
Required basic setting:
R7
AvK DSG alternators up to size 62:
1-gang trim potentiometer
S2.1 = no function
S2.2 = ON (underspeed protection)
Function:
S2.3 = ON (actual value smoothing)
Adjustment of the droop effect.
S2.4 = OFF (D parameter)
Direction of action:
AvK DIG, DSG 74 – 125 alternators
Left-hand stop = no droop effect (0 %)
parallel operation not possible.
S2.1 = no function
Right-hand stop = droop effect 6 %
S2.2 = ON (underspeed protection)
S2.3 = ON (actual value smoothing)
If the direction of rotation is reversed, sensing voltage
S2.4 = ON (D parameter)
connections U and W must be interchanged.
9.3 Displays
Droop matching:
Underspeed protection:
R6
H1
25-gang trim potentiometer
yellow 5 mm Ø LED
Function:
Matching the various alternator nominal currents and
current transformer ratios to the droop monitoring system.
28
H 1 lights up when the desired value or lowering of alternator g) Is the field connected with the correct polarity?
voltage in the case of underfrequency is active (3.7.1 Under-
speed protection)
10.2 Desired value setting range
Caution:
Once all the basic settings and visual checks have been
carried out, the alternator can be started up.
The regulator is set during the testing of the
alternator at the factory. See test protocol a) Run up alternator to nominal speed.
and order-specific circuit diagram.
b) Set external set-point potentiometer to the central position.
R3 right-hand stop position a) If the basic settings of R1 and S1 (see 10.1 Basic setting
R4 left-hand stop position and visual check) lead to continuous periodic fluctuations
R1 central position (stability limit), adjust R1 slowly to the left.
(in the case of DIG, DSG alternators, 1/4
rotation anticlockwise from the central position) b) If there is temporarily a tendency towards weakly
damped hunting in the event of load surges, adjust S1 one
S1 Pos. 4 or two positions to the right.
(in the case of DIG, DSG alternators Pos. 6,
at 600/750 rpm Pos. 9)
S2 S2.1 = no function 10.4 Underspeed protection
S2.2 = ON
S2.3 = ON a) 50/60 Hz alternators to 0.95 x fN.
S2.4 = OFF (ON in the case of DIG and DSG
alternators from size 74) b) In the case of 50/60 Hz alternators, turn R3 slowly in
the anticlockwise direction starting from the right-hand stop
R7 Central position position until H1 lights up. Then turn it slowly in the clock-
R6 Left-hand stop wise direction until H1 goes out.
After basic setting, the following visual checks must be carried c) Run the alternator up to nominal speed.
out:
29
Recommended droop settings: to flow freely through its power stage. Note the installation
position marking ”UNTEN” (= BOTTOM) (connecting
3% Parallel to the mains (If the mains supply is not leads towards the power stage). At fan cooling, the longitu-
stable, the setting may have to be increased). dinal axis of the "COSIMAT N+" has to be in air flow
direction. Deviating mounting is only suitable after checking
2% Parallel operation with identical alternators. by AvK.
6% Parallel operation with different alternators whose There must be a 3 cm clearance all the way round between
regulators do not have a linear droop. the "COSIMAT N+" and any structural elements that might
hinder flow (cable ducts, plates). This rule does not apply to
1% Parallel operation with different alternators which laterally mounted additional modules.
also have "COSIMAT N” or ”N+" regulators.
Protection concept: For standard applications of the "COSIMAT N+", the following
The exciter system should be protected from excessive exciter basic settings must be made before start-up at code switch S2
currents and voltages by a field discharge switch or relay. (see 9.2 Adjusting elements):
This switch or relay should be connected as shown in the
relevant order-specific circuit diagram. The tripping criteria AvK DSG alternators up to size 62
will be determined by the protection required by the alterna- S2.1 = no function
tor. S2.2 = ON (underspeed protection)
S2.3 = ON (actual value smoothing)
Where the alternator is operated in stand-alone mode, an S2.4 = OFF (D parameter)
overvoltage protection system must be installed in the swit-
ching station. In the case of operation in parallel with the AvK DIG and DSG 74 – 125 alternators:
mains or other alternators, an overcurrent protection system is S2.1 = no function
to be added. S2.2 = ON (underspeed protection)
S2.3 = ON (actual value smoothing)
DSG/DIG alternators with auxiliary windings: S2.4 = ON (D parameter)
DSG and DIG alternators with auxiliary windings are fitted
with an excess-current circuit breaker F1. This protects the Any differences from these settings must be agreed with the
auxiliary windings from excessively high thermal loading e.g. manufacturer beforehand and taken into account in the way
as the result of an external short circuit involving the auxiliary the alternator is operated.
exciter voltage UH1-UH2 or WH1-WH2.
30
operation if the k – I inputs of the "COSIMAT N+" are it is installed in the synchronous machine and the way the
short-circuited (see 8. Diagrams of connections). droop current transformer is connected to the "COSIMAT N+"
remains the same (see 8. Diagrams of connections).
The lead between the droop switch and the regulator must be
screened. For motor control, a cos phi controller (COS module) is
required additionally.
The screen must be earthed at one end on the "COSIMAT N+".
Caution:
Caution:
● Given a falling exciter current (underexcitation), the synchro- Two spare fuses are mounted on the underside of the "COSI-
nous machine becomes an acceptor of reactive power. MAT N+" (see 7. Dimensions).
When used as a generator, the synchronous machine is taken
as the reference point; where it is used as a motor, the mains 11.9 Drying out the alternator
are taken as the reference point.
If, because of inadequate insulation resistance, the alternator
When used as a generator, the synchronous machine supplies has to be dried out at nominal current by the short-circuit
”inductive” reactive power to the mains when overexcited. method, the "COSIMAT N+" should be disconnected from
the supply and exciter field connections.
When used as a motor, the synchronous machine draws
”inductive” reactive power from the mains when underexcited. The alternator is dried out by applying an external source of
excitation.
The droop system in the "COSIMAT N+" operates with the
correct direction of action whether the machine is being Further information on how to dry out the alternator can be
operated as a motor or a generator. The direction in which found in the alternator instructions.
31
11.10 External power supply must be connected to the correspondingly named connecting
terminal of the "COSIMAT N+".
If the auxiliary exciter voltage is taken from a different,
”external” source (e.g. the mains), the supply must not be
switched on until the alternator has started up.
When shutting down the alternator, the supply must be
switched off before the machine comes to a halt.
Caution:
Measuring voltage U, V, W
Supply UH1-UH2, WH1-WH2
Exciter field I1-K1
32
11.14 Malfunctions, causes and remedies
Alternator voltage is too low. Input speed too low. Check whether LED H1 on regulator
lights up. If so, underspeed protection
device has been activated, run up al-
ternator to nominal speed.
Alternator voltage is too low and can- Set-point potentiometer or its con- Check set-point potentiometer or its
not be adjusted with the set-point po- necting leads are disconnected/inter- connecting leads. Rectify fault.
tentiometer. rupted.
Alternator voltage is too high and can- Set-point potentiometer or its con- Check set-point potentiometer for short
not be adjusted with the set-point po- necting leads have a short circuit. circuit. Change potentiometer. Check
tentiometer. set-point leads for short circuits. Elimina-
te short circuit.
Severe voltage dip upon loading. Input speed falls upon loading. Check regulator of driving machine.
Alternator does not respond to excitati- Input speed too low. Less than 0,5 x nN. Check the speed regulator of the input
on. machine. Check the power transmissi-
on to the alternator.
Exciter protection switch has tripped. Switch on the protective switch again.
If it trips once more, search for the fault
and repair it.
33
Malfunction Cause Remedy
Alternator does not respond to excitati- Remanence too low. Alternator with auxiliary winding:
on. Briefly connect positive terminal of 4.5
or 6 V battery to I1 and negative
terminal to K1 (at nominal speed).
Alternator with two-phase auxiliary
exciter machine:
Briefly connect positive terminal of 4.5
or 6 V battery to I2 and negative
terminal to K2 (at nominal speed).
DIG alternators (UN > 11.5 kV): With alternator standing still!
Interruption in exciter windings I1/K1 Check windings I1/K1 and I2/K2 for
and/or I2/K2. interruptions using an ohmmeter. Elimi-
nate faults.
Periodic fluctuations in the alternator Incorrect regulator setting. Adjust R1 carefully in the anticlockwise
voltage when operated singly (stability direction and turn S1 one or two steps
limit)! to the right.
34
Malfunction Cause Remedy
Alternator voltage fluctuates at irregular Temporary interruption in one of the Check connecting leads to the regula-
intervals. regulator supply leads. tor. Check connections at the terminal
board of the alternator. Tighten all con-
tact screws and nuts.
Reactive power output too high in par- Droop set too low. Adjust R7 slightly in the clockwise di-
allel operation. rection on the "COSIMAT N+".
Phase angle connection (k/I) of the Check connecting leads from the alter-
droop current transformer has been nator to the regulator. Interchange k/I
wrongly positioned. if necessary. The white secondary con-
nection of the droop current transformer
is ”k”.
Droop switch is not in alternator phase Install droop transformer in phase ”V”.
”V”.
Reactive power output too low in par- Droop set too high. Adjust R7 slightly in the anticlockwise
allel operation. direction on the "COSIMAT N+".
Active load not equally distributed. This is affected by the driving machine Check the drive motor and its regulator.
only.
The "COSIMAT N+" affects only the
reactive power.
35
12. List of figures
36
AvK Deutschland GmbH & Co. KG
Niederlassung Dreieich
Benzstraße 47 - 49
D - 63303 Dreieich
Telefon: ISDN 0 61 03/50 39 - 0
Telefax: 0 61 02/50 39 - 40
BV COSIMAT N+.1 -31101 E
e-mail: [email protected]
http://www.newage-avkseg.com