COSIMAT N Plus E

Download as pdf or txt
Download as pdf or txt
You are on page 1of 40

Description and adjustment instructions

”COSIMAT N+” voltage regulator


for DSG and DIG alternators
Description of ”COSIMAT N +”
1. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2. Brief summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.1 General diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Adjusting elements and their effects . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Optimising the regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3. Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1 Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Monitoring alternator voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.4 Desired value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.5 Droop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.6 Control amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.7 Additional functions of the ”COSIMAT N+” . . . . . . . . . . . . . . . . . . . . . 10
3.7.1 Underspeed protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.7.2 Protection functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.8 Power stage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

4. Transfer function of the ”COSIMAT N+” . . . . . . . . . . . . . . . . . . . . . . 12

5. Special functions and additional equipment . . . . . . . . . . . . . . . . . . . . 13


5.1 Stand-by and emergency manual switchover . . . . . . . . . . . . . . . . . . . . . 13
5.2 Additional modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

6. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

7. Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

8. Diagrams of connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
8.1 Assembly for DSG alternators 52 – 74 . . . . . . . . . . . . . . . . . . . . . . . 21
8.2 Assembly for DSG alternators 86 – 125 . . . . . . . . . . . . . . . . . . . . . . . 22
8.3 Assembly for DIG medium-voltage alternators with UN ≤ 11.5 kV . . . . . . . . . . . . 23
8.4 Assembly for DIG medium-voltage alternators with UN > 11.5 kV . . . . . . . . . . . . 24
8.5 De-excitation circuit on the ”COSIMAT N+” . . . . . . . . . . . . . . . . . . . . . 25
8.6 Monitoring field current and voltage on the ”COSIMAT N+” . . . . . . . . . . . . . . 25

9. Connections, adjusting elements and displays . . . . . . . . . . . . . . . . . . . 26


9.1 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
9.2 Adjusting elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
9.3 Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

10. Start-up of the ”COSIMAT N+” . . . . . . . . . . . . . . . . . . . . . . . . . . . 29


10.1 Basic setting and visual check . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
10.2 Desired value setting range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
10.3 Regulating parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
10.4 Underspeed protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
10.5 Droop adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

11. Important notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30


11.1 Protection concept for external mounting of regulator . . . . . . . . . . . . . . . . . 30
11.2 Mounting the regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
11.3 Excitation build-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
11.4 Code switch S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
11.5 Droop switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
11.6 Changing the direction of rotation . . . . . . . . . . . . . . . . . . . . . . . . . . 31
11.7 Synchronous motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
11.8 Protection fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
11.9 Drying out the alternator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
11.10 External power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
11.11 400 Hz alternators and converters . . . . . . . . . . . . . . . . . . . . . . . . . 32
11.12 Checking the insulation voltage of the electric machine . . . . . . . . . . . . . . . . 32
11.13 Exchange/replacement; ”COSIMAT N/N3” by ”COSIMAT N+” . . . . . . . . . . . 32
11.14 Malfunctions, causes and remedies . . . . . . . . . . . . . . . . . . . . . . . . . 33

12. List of figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36


1. General With the use of additional modules it is possible to intervene
in set-point and actual value formation via the ”COSIMAT N+”
The ”COSIMAT N+” is a compact voltage regulator designed signal inputs:
to control synchronous alternators both in single and parallel
operation. There are a large number of additional modules available for
a wide variety of control applications e.g.
In single operation, the alternator voltage is held constant
irrespective of power, frequency and temperature. ● cos phi regulation of a synchronous alternator or motor

When operated in parallel with the mains or with other or


alternators, a stable reactive power is produced.
● Limitation of start-up current when connecting up a large
Via its power stage, the ”COSIMAT N+” adjusts the excitation asynchronous motor to the alternator
current to match the operating conditions.
or
The main features of the ”COSIMAT N+” are:
● Cable compensation via load current detection or mea-
● Integrated measuring transformers for three-phase meas- sured value of the external alternator voltage.
urement of the alternator voltage up to 500 V AC
(external conductor voltage). Its additional modules make the "COSIMAT N+" suitable for
various applications on test rigs, in power-train technology
● Stable reactive power thanks to current-voltage vector etc. (see 5.2 Additional modules).
measuring system (droop). A load-relieved current trans-
former is required in alternator phase ”V”.

● Internal and external alternator voltage set-point ad-


justment.

● PID control amplifier with large adjustment range.

● Disproportionate drop in desired value when alternator


operates at underfrequency.

● Permanent monitoring of the actuator and time limit on


the max. possible excitation current.

● Internal protection devices trip whenever a fault occurs,


thus separating the excitation field from its energy source.

● Compact construction with interchangeable power


stage.

● Fully potted in to protect it from environmental effects.

● Long life thanks to high-quality components.

2
2. Brief summary
2.1 General-arrangement diagram

Figure 1 – General-arrangement diagram

3
2.2 Adjusting elements and their effects

Figure 2 – Adjusting elements

4
2.3 Start-up

Figure 3 - Start-up

5
2.4 Optimisation of the regulator It is not necessary to adjust the D parameter in order to
optimise the control properties. It is generally determined just
To optimise regulation, it is necessary to connect loads to the once, in accordance with the size of the alternator. In the case
alternator. of alternators > 1 MVA, switch S2.4 is switched to the ON
position.
To allow the trend of the control property following a change
in the P or I parameter to be evaluated, the load connected To decide whether the D parameter should be increased
must be reproducible. beyond this, it is necessary to take specific measurements of
the alternator voltage and at the output of the regulator.
The factor with the greatest general significance in achieving
an optimum regulating system is an overshoot amplitude xm Satisfactory optimisation of the regulator will normally be
which is as small as possible. The essential criterion in the achieved by the free adjustment of the P and I parameters.
evaluation of the regulating process with respect to time is the
settling time taus.

To follow the trend of the control property, use an oscilloscope


to monitor the manipulated variable.

The "COSIMAT N+" regulator allows ”free” adjustment of the


P and I parameters. The D parameter can be switched over
in two stages using code switch S2.4.

Figure 4 – Characteristic quantities of the regulating system

Figure 5 – Trend of the control property

6
3. Functional description
3.1 Block diagram

Figure 6 – Block diagram

7
3.2 Power supply 3.3 Monitoring alternator voltage

Power is supplied to the "COSIMAT N+" by means of The "COSIMAT N+" measures alternator voltages from 90 to
so-called auxiliary excitation voltages, which are produced 500 V AC (external conductor voltage) within two selectable
in the alternators. The excitation energy and the supply ranges by means of an internal three-phase measuring trans-
voltage for the "COSIMAT N+" are derived from the auxiliary former.
excitation voltages.
To measure higher voltages, corresponding voltage transfor-
In the case of AvK alternators in Series DSG and DIG with mers must be connected in series.
UN ≤ 11.5 kV, the "COSIMAT N+" is supplied with power
via two single-phase auxiliary windings, which are inserted Signal input N allows intervention into the internal formation
into the main stator. The windings are designated UH1/UH2 of the actual value.
and WH1/WH2.
The secondary AC measurement voltage of the measuring
The voltages UH1 and UH2 are offset by 90° with respect transformer is converted into a DC voltage, smoothed, condi-
to WH1 and WH2 and are 80 V AC ± 20 % at the nominal tioned and output as an actual value to the regulator circuit.
voltage of the alternator.
The measured value which is produced corresponds to the
In the case of AvK alternators belonging to Series DIG with arithmetic mean of the rectified three-phase AC measurement
UN > 11.5 kV, the "COSIMAT N+" is supplied with power voltage.
via a two-phase auxiliary exciter machine. The windings are
designated UH1, UH2, UH3 and WH1, WH2. Three-phase measurement allows for asymmetric loads.

The voltages UH1 and UH2 are offset by 90° with respect Note:
to WH1 and WH2 and are 80 V AC ± 20 % at the nominal For non-linear loads (static thyristor converter or rectifier),
speed of the machine. additional module TF (RC – low-pass filter) is recommended
as a measuring adapter. High non-linear loads may
The above-mentioned auxiliary exciter windings UH1 and require overdimensioning of the alternator.
UH2 and WH1 and WH2 are plugged into the correspon-
dingly designated terminals of the "COSIMAT N+":
3.4 Desired value
Special application
Three-phase auxiliary exciter machine The desired value for the "COSIMAT N+" is taken from a
If a three-phase auxiliary exciter machine is used, the winding temperature-compensated reference source.
terminals are designated UH1-VH1-WH1. The external con-
ductor voltage is 3 x 75 V AC ± 20 % at the nominal speed The signal input ”n” allows intervention in the internal formation
of the machine. of the desired value.

Special application The reference voltage reaches the set-point potentiometer R 4


External power supply mounted on the front end of the "COSIMAT N+". This
The "COSIMAT N+" can also be operated with a constant potentiometer allows coarse adjustment of the alternator
external voltage. It is generally supplied via a three-phase voltage over a wide range (= ”approximate” desired value).
transformer (Yy 0) with a secondary voltage of 3 x 75 V AC
± 20 %. The nominal power should be at least 500 VA. In parallel operation of the alternator, the reference voltage
is influenced by the droop-measuring system (see 3.5 Droop)
and, in the case of underfrequency, by the underspeed
protection.

A set-point potentiometer can be connected to the "COSIMAT N+"


Caution: for external adjustment of the desired value.

If the auxiliary excitation voltage is taken This potentiometer is used for fine adjustment of the alternator
from a constant "external" power source (e.g. voltage (= ”exact” desired value).
the mains), the supply must be switched on
only after the alternator has been started. The adjustment range is limited to ± 5 % to ± 10 % around
When switching off the alternator, the the nominal value, depending on the potentiometer used.
supply should be switched off before the
machine comes to a halt (see 11.10 External The ES additional module allows the adjustment range of the
power supply). external set-point potentiometer to be extended from remanence
to the nominal voltage.

8
If the ES module is used on AvK alternators, the regulator If, when the alternator is connected in parallel, the fixed mains
system must be provided with an external power supply. This forces it down to a figure which is 6 % lower, the reactive
must be decided on a case by case basis, depending on the current is inductive and equivalent to 100 % of the nominal
application and the excitation system used (auxiliary excitati- alternator current.
on windings or auxiliary excitation machine?)
In parallel operation, regulation of the synchronous alternator
is made possible by the droop sensing signal.
3.5 Droop For stand-alone operation, adjustment is performed on the test
rig using a reactive load. The droop effect is set to 3 %.
Once an alternator has been connected in parallel, voltage
regulation is no longer possible because the system voltage The droop sensing signal in the "COSIMAT N+" influences
is fixed. The slightest fluctuation in the system voltage would the desired value and is produced by means of a geometrical
lead to the alternator producing reactive current > IN. addition of the external conductor voltage U-W and a
current-dependent voltage signal from the V phase.
To stabilise the alternator reactive current it is therefore
necessary to have a measured variable which is dependent In AvK synchronous machines, the corresponding current
on the reactive current and incorporates the magnitude of the transformer is located in phase V. The K side of the transfor-
current and the reactive power (inductive or capacitive). This mers points towards the alternator’s main winding (see Figure
measured variable is introduced at the addition point (com- 6 – Block diagram).
parison point of the desired value and the actual value) of the
control amplifier circuit. Internally load-relieved bushing-type transformers are used.

This produces a static droop control characteristic, which The outlet end of the secondary connections ( = potted end
represents the relationship between: of the transformer) is the primary-side K point (= current input).

the change in the alternator voltage in relation to the nominal The wire marked in white is the secondary-side k point.
voltage and
the change in the alternator reactive current in relation to the The secondary connections k and I of the droop current
nominal current. transformer should be plugged into the correspondingly mar-
ked terminals of the "COSIMAT N+".
The droop is represented by the slope of the characteristic
curve produced i.e. is the quotient of the above ratio. In the case of alternators for parallel and stand-alone opera-
tion, the measuring input k – I can be short-circuited by means
In the "COSIMAT N+" a linear droop characteristic is gene- of a switch for stand-alone operation. This gives better voltage
rated. The droop effect can be adjusted from 0 to 6 % using stability (see 8. Diagrams of connections, 11.5 Droop
the potentiometer R 7. switch).

Example: The droop sensing system of the "COSIMAT N+" is matched


In the case of an inductive reactive current of 100 % of the to the nominal current of the alternator by means of potentio-
nominal current of the alternator and with the droop set to 6 %, meter R 6.
the alternator voltage is reduced by 6 %.

Caution:

For the droop sensing system to function


correctly, the "COSIMAT N+" requires a
clockwise rotating field at its measurement
voltage terminals. If the direction of rotation
is reversed, measuring leads U and W
should be interchanged.

3.6 Control amplifier

The control amplifier of the "COSIMAT N+" has a PID


characteristic. The parameter of the I section can be varied
in steps from 1 to F using switch S 1. During this process, the
integration time constant increases.
Figure 7 – Droop characteristic

9
kink point” is set to 0.95 x fN. Above the kink point, voltage
Caution: regulation is constant.

Switch position 0 is not allowed; never pass The voltage reduction is delayed by about 2 seconds to
through 0. eliminate the effect of transient drops in the speed of the drive
machine.

The parameter of the P section can be varied by means of In exceptional circumstances, the underspeed protection fun-
potentiometer R 1. During this process, the adjustment range ction can be deactivated by means of code switch S2.2 (see
shown in Figure 8 should not be exceeded. 9.2 Adjusting elements).

Caution:

For standard applications of the "COSIMAT N+",


the underspeed protection function must be
active and correctly set. Code switch S2.2
must be in the ”ON” position.

The underspeed protection function is active on 50/60 Hz


alternators. For other nominal frequencies, the UF module
should be used or the alternator should be deexcited when
being shut down.

Figure 8 – P adjustment range

Further adjustment in the clockwise direction leads to hunting,


while further adjustment in the anticlockwise direction leads
to control errors.

The D parameter can be changed by switching code switch


S2.4 to the ”ON” position. This increases the effect of the D
parameter, as required by larger alternators (DIG and DSG
74 ... 125).

The D parameter can furthermore be varied at the ”D-Opt.”


optimisation points. At the specified polarity, a capacitor can
additionally be soldered in.

When installing additional D-section capacitors, it is important


to note their polarity (electrolyte capacitor) and nominal
voltage (= 35 V DC). The maximum recommended value is
150 µF.

Figure 9 – Underspeed protection


3.7 Additional functions of the "COSIMAT N+"
3.7.2 Protective functions
3.7.1 Underspeed protection
The auxiliary exciter windings (see 3.2 Power supply) have a
While a drive machine (motor or turbine) is warming up, the very high short-circuit capacity. If the actuator is faulty, the
alternator is operated at underfrequency. To prevent overexci- high short-circuit power involved may cause severe damage.
tation and thermal damage in the exciter system, the "COSI-
MAT N+" allows frequency-dependent reduction of the To prevent this damage, the "COSIMAT N+" has two protecti-
regulator’s desired value or alternator voltage in accordance ve functions which monitor its actuator and prevent overloa-
with a linear function (see Figure 9 – Underspeed protection). ding of the exciter system:

The point at which the voltage drops is defined by a corre-


sponding frequency value set by means of R3. The reduction
for underspeed is indicated by H1. Before delivery, the ”U/f

10
Time limitation of the maximum excitation cur- 3.8 Power stage
rent
The power stage of the "COSIMAT N+" provides an excita-
When the actuator is fully on, the excitation current tion current that corresponds to the output signal of the control
reaches a maximum. amplifier.

If this state is allowed to continue, the exciter system will A MOSFET transistor is used as the actuator, with pulse width
be damaged. modulation, i.e. the turn-on time varies but the switching
frequency remains constant.
However, the fully-on state only occurs in the case of
compensating processes or short circuits at the main The excitation energy is taken from the rectified supply
terminals of the alternator. voltage, the rectifier circuit being located in the power stage.
It allows the rectification of two single-phase or three-phase
The monitoring system of the "COSIMAT N+" limits supply voltages (see 3.2 Power supply).
maximum excitation to 8 to 10 seconds.
There is a short-circuit thyristor in the DC circuit. The protective
After this, the protection circuit isolates the exciter field circuit of the "COSIMAT N+" switches this thyristor on if faults
from the source of excitation energy by tripping the occur in the control circuit. The resulting short-circuit current
protection fuses. trips the two protection fuses on the front plate of the "COSI-
MAT N+" and the exciter field is isolated from the source of
Checking the direction of action of the control excitation energy.
amplifier and the actuator
Fuse:
This feature monitors the positioning transistor for short 10 A super quick-acting
circuits. 32 mm x 6.3 mm ø
IEC G 144.400
Short-circuiting of the positioning transistor leads to maxi-
mum excitation. The control amplifier tries to counteract
this but has no effect on the faulty actuator. The actuator
and the control amplifier act in opposite directions and Caution:
the fuses trip immediately.
Replacement fuses must be of the above type.
The following circumstances also lead to maximum excitation The power stage may suffer permanent dama-
and can trip the fuses: ge if the wrong type of fuse is used.

● Faulty sensor leads


The power stage is located on a profiled heat sink. It is
● Deactivated or incorrectly adjusted underspeed protecti- plugged into the regulator and screwed into the substructure
on function of the "COSIMAT N+".

● Short circuit in the I1 / K1 exciter lead To ensure adequate cooling for the power semi-conductors in
the power stage, you must follow the instructions in Chapter
● Faulty exciter rectifier in the "COSIMAT N+" 11.2 Mounting the regulator.

● Extreme overloading of the alternator (short circuit) if this


has not been switched off after 8 to 10 seconds.

The protection device integrated into the "COSIMAT N+"


responds to a large number of defects and faults.

Note:
Additional module ER1 can be used to limit the excitation
current when the alternator is operated in parallel.

11
4. Transfer function of the "COSIMAT N+"

Figure 10 – Equivalent control circuit diagram

There are three ways of influencing the control parameters in The time constant of the input low-pass filter is:
the "COSIMAT N+”:
TP1 = 3.62 ms
Potentiometer R1 (500 kΩ) for changing the P parameter. At
the right-hand stop, R1 is 0Ω. The time constant of the output low-pass filter is:

Switch S1 for changing the I parameter in 15 steps (from 0.22 TP2 = 0.268 x T2
to 3.85 µF) each of 0.22 µF (C1).

Code switch S2.4 for increasing the D parameter from 10.1 µF


(S2.4 = OFF) to 32.1 µF (S2.4 = ON) (C2).

The individual parameters in the equivalent circuit diagram


(see Figure 10 – Equivalent control circuit diagram) can be
calculated as follows:

T1 = R1 x C1
T2 = 6,8 kΩ x C2
T3 = 22 kΩ x C1

TI = T1 + T2

TD = T1 x T2
T1 + T2

K1 =2,56 T1 + T2
T3

K2 = 716,1 ms x K1
Tl

K3 = 1 = 0,066
15

12
5. Special functions and additional
equipment
5.1 Stand-by and emergency manual switchover

Where higher availability is required, there are ”stand-by”


circuits.

Stand-by circuits contain two "COSIMAT N+" voltage regula-


tors.

The alternator is regulated by one of these regulators (main


regulator). If this regulator is defective, it is possible to switch
to the second (stand-by) regulator.

Stand-by circuits are available in either manual or automatic


form.

Manual stand-by circuit (SB1)

In the event of a malfunction, a changeover switch permits


the stand-by regulator to be selected.

The changeover switch switches over all the signals apart


from the sensing voltage and supply connections UH2
(VH1) and WH2.

Automatic stand-by circuit (SB2)

The stand-by circuit monitors the main regulator.

Common operating variables with respect to the response


of the regulator allow fault detection and switchover to
the stand-by regulator.

The stand-by regulator operates in simulated control


mode and is likewise monitored.

The switch between the two regulators can take place


during the operation of the alternator and can be perfor-
med manually, by means of a test function or, in the case
of a malfunction, automatically.

13
6. Technical data

GENERAL DATA Type : fully potted aluminium housing incl. power stage
Maintenance : maintenance-free
Rated switch-on time : continuous operation
Installation position : mount with longitudinal axis vertical at
convectional cooling or longitudinal axis
in air flow direction at fan cooling
Installation clearance : 3 cm all round
(see 11.2 Mounting the regulator)

MEASURING CIRCUITS Alternator voltage


Nominal voltage : 90 ... 250 V AC / 250 ... 500 V AC
Frequency : 50 ... 400 Hz
Power consumption : 4 VA / 6 VA

Droop current sensing


(Voltage input)
Voltage at IN : 3 ... 7 V AC
Power consumption : 0.15 ... 0.35 W

AUXILIARY CIRCUITS Supply voltage : 2 x single-phase 80 V AC ±20 %


or
1 x three-phase 75 V AC ±20 %
Power consumption : depending on excitation requirement
Nominal frequency : 50 ... 1200 Hz

OUTPUT CIRCUITS Actuator


Intermediate circuit voltage UZK : 85 to 130 V DC
(dependent on the supply voltage)
Continuous excitation current : 7 ADC (continuous)
Minimum field resistance RIK : 5Ω (cold)
Minimum required
field time constant τIK : 0.06 s
Short circuit exciter current : 20 ADC for 5 seconds
(at RIK = Ω5 and UZK = 100 VDC)
Protective fuse : 10 A-FF / 250 V – 6.3 x 32

ACCURACY Control accuracy : ±1 % at 0 to 60 °C


±5 % speed fluctuations and
apparent power 0 ... 100 %

TESTS Vibration test : German Lloyd category 2


EMV : CE-compliant in accordance with EN50081
and EN50082

AMBIENT CONDITIONS Storage temperature : - 40 ... + 70 °C


Operating temperature : -25 ... + 70 °C
(Special version "COSIMAT N+T"
- 55 ... + 70 °C)

HOUSING, DIMENSIONS,
WEIGHT AND INSTALLATION Height x width x depth : 121 x 115 x 162.5 mm
Fixing : 4 M6 bolts, washers and circlips
Weight : 2 kg

18
7. Dimensions

Figure 25 – Dimensions

19
8. Diagrams of connections
Legend for diagrams of connections

F1 Circuit breakers for G3


Operate only when stationary

G1 Main machine

G2 Exciter/excitation windings

G3 Auxiliary windings/Auxiliary exciter machine

R11/V3 Rotating varistor

T24 Voltage transformer for regulator


Must be disconnected if the star
point of G1 is open

T32 Voltage transformer for G3


with integrated circuit breaker F1
Operate F1 only when stationary!

V1 Rotating rectifier

X1 Main terminals

X2 – 6 Terminal strip

U1 "COSIMAT N+" voltage regulator

R3 Underspeed protection

R4 Internal desired value

R1 P component

S1 I component

R7 Droop adjustment

R6 Droop transformer matching

R1 Desired value potentiometer alternator


voltage (R = 500Ω)

T6 Droop transformer

20
8.1 Assembly for DSG alternators 52 - 74

Figure 26 – Internal mounting, DSG alternators 52 – 74

Figure 27 – External mounting, DSG alternators 52 – 74

21
8.2 Assembly for DSG alternators 86 – 125

Figure 28 – Internal mounting, DSG alternators 86 – 125

Figure 29 – External mounting, DSG alternators 86 – 125

22
8.3 Assembly for DIG medium-voltage alternators with UN ≤ 11.5 kV

Figure 30 - Internal mounting, DIG medium-voltage alternators with U N ≤ 11.5 kV

Figure 31 - External mounting, DIG medium-voltage alternators with UN ≤ 11.5 kV

23
8.4 Assembly for DIG medium-voltage alternators with UN >11.5 kV

Figure 32 - Internal mounting, DIG medium-voltage alternators with U N > 11.5 kV

Figure 33 - External mounting, DIG medium-voltage alternators with UN > 11.5 kV

24
8.5 De-excitation circuit on the "COSIMAT N+" 8.6 Monitoring field current and voltage on the
"COSIMAT N+"
If a de-excitation circuit is fitted, the bridges on the double
terminals UH1/UH1’ and WH1/WH1’ should be removed. The "COSIMAT N+" is provided with double terminals I1/I1’
Switch contacts should be connected to the double terminals and K1/K1’ to allow the exciter field to be connected. Bridge
to de-excite the alternator when they open (see Figure 34 – I1/I1’ must be removed to allow the field current and voltage
De-excitation circuit). These de-excitation contacts must meet to be monitored (see Figure 35 – Field current/field voltage
the following specification: monitoring).

Current carrying capacity:10 AAC The measuring range for field voltage monitoring is 150 VDC;
Voltage carrying capacity:160 V AC for field current monitoring it is 10 ADC. Rotary coil or
moving-iron instruments are recommended. Under certain
The switch elements used must have dust-protected contact conditions, digital instruments may give false readings.
chambers. Ensure that contact resistance is low – the contacts
must be sensitive to low-level signals. Note:
In the case of AvK alternators (DSG 86 – 125, DIG),
Note:
there are connecting terminals for monitoring the field
One of the factors which determines the build-up of
current and voltage on terminal strip X2.
excitation is the quality of these contacts.
On AvK alternators (DSG 86 – 125, DIG), connecting
terminals for de-excitation are provided in the auxiliary
terminal box (see legend of the order-specific circuit
diagram).

Figure 34 - De-excitation circuit

Figure 35 - Field current/field voltage monitoring

25
9. Connections, adjusting elements and Monitoring droop current:
displays
k–I
9.1 Connections
4.8 x 0.8 mm flat plugs and/or 2.5 mm2/4 mm Ø screw
terminals
Voltage supply:

UH1 Caution:
UH2 (VH1)
WH1 Measuring input k – I is not a current input;
WH2 standard transformers should be load-relieved
accordingly.
4.8 x 0.8 mm flat plugs and/or 2.5 mm2/4mm Ø screw
terminals

Supply can be 2 x single-phase (80 V AC ± 20 %) or The droop current transformer must be installed in the "V"
phase of the alternator.
three-phase (75 V AC ± 20 % external conductor voltage).
Internally load-relieved droop current transformers are
2 x single-phase = UH1-UH2, WH1-WH2
used in AvK alternators.
three-phase = UH1-VH1-WH1
At the nominal current of the alternator, a voltage of 3 to
For de-excitation circuits, the bridges on the double
7 V AC is required at the terminals k – I (see 3.5 Droop
terminals must be removed (see 8.5 De-excitation circuit
and 6. Technical Data).
or order-specific circuit diagram).
Connecting leads to the transformer must be shielded if
Caution:
the regulator is installed externally. Connecting leads to
the short-circuit droop switch (see 11.5 Droop switch)
If there is an external power supply (e.g.
should be shielded in all cases. The shield should be
from the mains), it must not be switched on
earthed at one end on the "COSIMAT N+" (see 8.
until after the alternator has run up. It
Diagrams of connections).
should be switched off before the machine
has come to a halt (see 11.10 External
power supply).
Exciter field:

I1 – K1
Measuring alternator voltage:
4.8 x 0.8 mm flat plugs and/or 2.5 mm2/4 mm Ø screw
U-V-W 250 to 500 V AC terminals as double terminal.
U-V-W 90 to 250 V AC
If the regulator is mounted externally, the I1/K1 field leads to
6.3 x 0.8 mm flat plugs the alternator must be run through a separately shielded cable
(LSYCY or LIYCY).
Caution:
The shield should be earthed at one end on the "COSIMAT N+"
(see 8. Diagrams of connections).
A clockwise rotary field is required. If the
alternator rotates anticlockwise, U and W
should be interchanged (see 3.5 Droop).
External set-point potentiometer

The specified voltage ranges relate to the nominal exter- s–t


nal conductor voltage of the alternator. For higher volta-
ges, appropriate measuring transducers with a design 4.8 x 0.8 mm flat plugs and/or 2.5 mm2/4 mm Ø
rating of 10 VA should be connected on the input side screw terminals as double terminal.
(see 3.3 Monitoring alternator voltage).
The value of the set-point potentiometer determines the
The applicable voltage range should be taken from the adjustment range:
order-specific circuit diagram. For DIG alternators with
UN >1 kV, the range 90 – 250 V AC is generally chosen. 250 Ω = about ± 5 %
Consult AvK before initial start-up if required. 500 Ω = about ± 10 %

26
The rated power of the potentiometer must be at least 1 This potential is not connected when the "COSIMAT N+"
W. A multiple-turn potentiometer must be used (see 3.4 is used for standalone operation.
Desired value).

If the regulator or the set-point potentiometer is mounted 9.2 Adjusting elements


externally, the set-point lead must be provided with its
own separate shield. The shield should be earthed at one Underspeed protection
end on the "COSIMAT N+". If the regulator is mounted
externally and the set-point leads are longer than >10 m, R3
a motor-actuated potentiometer should be used near to
the "COSIMAT N+". 25-gang trim potentiometer

Function:
Control inputs: Adjustment of the frequency-dependent lowering of alter-
nator voltage (see 3.7.1 Underspeed protection).
N
M/m Direction of action:
n Left-hand stop = beginning of reduction at >50/60 Hz.
Right-hand stop = beginning of reduction only after
4.8 x 0.8 mm flat plugs and/or 2.5 mm2/4 mm Ø about > 30 Hz.
screw terminals.
In special cases, the underspeed protection can be
A number of additional modules from the "COSIMAT N+" deactivated by means of switch S2.2 (see 9.2 Adjusting
equipment range can be connected to these control elements).
inputs (see 5.2 Additional modules).
This is necessary when regulating a DC voltage by way
of additional module UDC or in some cases when using
Caution: external UF modules.

Only AvK additional modules must be used


at the control inputs. 20 mA standard si- Desired value:
gnals must not be used at these inputs.
R4

The inputs have the following functions: 25-gang trim potentiometer

N Access to the internal actual value circuit Function:


M/m Reference point for additional equipment Adjusting the alternator voltage (see 4.3 Desired value,
n Access to the internal desired value circuit 10.2 Desired value adjustment range).

Direction of action:
Circuit earth: Left-hand stop = minimum alternator voltage
Right-hand stop = maximum alternator voltage
-

The circuit earth is likewise used as reference potential Caution:


for a number of ”controlling” additional modules.
Before the "COSIMAT N+" is started up, R4
This potential is not connected when the "COSIMAT N+" must be turned to the left-hand stop position
is used for stand-alone operation. (see 10. Starting up the "COSIMAT N+"). A
regulator which is checked and delivered
together with an alternator is already preset.
Load earth:

Z
P component:
The load earth is used for connecting the internal interme-
diate circuit capacitors.
R1
Additional external capacitors can be connected between
the second Z connection tab (MINUS) and terminal I1 1-gang trim potentiometer
(PLUS).

27
Function: Direction of action:
Varying the proportional component of the control cha- Left-hand stop = maximum compensation value
racteristic. Right-hand stop = minimum compensation value

Direction of action: At nominal alternator current, R6 should be used to carry


Anticlockwise = small P component out trimming to 2.5 V AC at the measuring points
Clockwise = large P component ”MP-STATIK – DROOP”. If the alternator load current is
less than the nominal current, this may be trimmed to a
The recommended adjustment range shown in Fig. 8 – proportional voltage value.
P adjustment range must not be exceeded (see 10.3
Regulating parameters).
Code switch:
I component:
S2
S1
4-pole dip switch

Function:
Caution:

Switch position ”0” is not permitted. Switch FUNCTION ON OFF

S2.1 none ./. ./.


16-stage code switch Activation and
S2.2 deactivation Active Not
Function: of underspeed active
protection
Varying the I component in the regulating characteristic
(see 10.3 Regulating parameters). Reduction of
S2.3 actual value Nominal Reduced
smoothing
Direction of action:
Left (1 <- F) = small I component Increasing the
Right (1 -> F) = large I component S2.4 D-parameter Increased Nominal

Droop:
Required basic setting:
R7
AvK DSG alternators up to size 62:
1-gang trim potentiometer
S2.1 = no function
S2.2 = ON (underspeed protection)
Function:
S2.3 = ON (actual value smoothing)
Adjustment of the droop effect.
S2.4 = OFF (D parameter)
Direction of action:
AvK DIG, DSG 74 – 125 alternators
Left-hand stop = no droop effect (0 %)
parallel operation not possible.
S2.1 = no function
Right-hand stop = droop effect 6 %
S2.2 = ON (underspeed protection)
S2.3 = ON (actual value smoothing)
If the direction of rotation is reversed, sensing voltage
S2.4 = ON (D parameter)
connections U and W must be interchanged.

9.3 Displays
Droop matching:
Underspeed protection:
R6
H1
25-gang trim potentiometer
yellow 5 mm Ø LED
Function:
Matching the various alternator nominal currents and
current transformer ratios to the droop monitoring system.

28
H 1 lights up when the desired value or lowering of alternator g) Is the field connected with the correct polarity?
voltage in the case of underfrequency is active (3.7.1 Under-
speed protection)
10.2 Desired value setting range
Caution:
Once all the basic settings and visual checks have been
carried out, the alternator can be started up.
The regulator is set during the testing of the
alternator at the factory. See test protocol a) Run up alternator to nominal speed.
and order-specific circuit diagram.
b) Set external set-point potentiometer to the central position.

c) Adjust nominal voltage using R4.


10. Starting up the "COSIMAT N+"
d) The alternator voltage can be adjusted around its
10.1 Basic setting and visual check nominal value using the external set-point potentiometer.

Before start-up, the following basic settings of the "COSIMAT N+"


voltage regulator must be checked: 10.3 Regulating parameters

R3 right-hand stop position a) If the basic settings of R1 and S1 (see 10.1 Basic setting
R4 left-hand stop position and visual check) lead to continuous periodic fluctuations
R1 central position (stability limit), adjust R1 slowly to the left.
(in the case of DIG, DSG alternators, 1/4
rotation anticlockwise from the central position) b) If there is temporarily a tendency towards weakly
damped hunting in the event of load surges, adjust S1 one
S1 Pos. 4 or two positions to the right.
(in the case of DIG, DSG alternators Pos. 6,
at 600/750 rpm Pos. 9)
S2 S2.1 = no function 10.4 Underspeed protection
S2.2 = ON
S2.3 = ON a) 50/60 Hz alternators to 0.95 x fN.
S2.4 = OFF (ON in the case of DIG and DSG
alternators from size 74) b) In the case of 50/60 Hz alternators, turn R3 slowly in
the anticlockwise direction starting from the right-hand stop
R7 Central position position until H1 lights up. Then turn it slowly in the clock-
R6 Left-hand stop wise direction until H1 goes out.

After basic setting, the following visual checks must be carried c) Run the alternator up to nominal speed.
out:

a) Have the sensing voltage connections (U, V, W 10.5 Droop adjustment


90...250 / 250...500) been correctly selected?
a) Load the alternator with nominal current. Measure the AC
b) Do the sensing voltage connections possess a clockwise- voltage at the droop sensing points ”MP-STATIK-DROOP”.
rotating field? (If rotation is anticlockwise, interchange U Adjust to 2.5 V AC using potentiometer R6.
and W).
b) For partial loading, the calibration value can be reduced
c) Is the supply voltage correctly connected (2 x single- proportionately.
phase UH1/UH2 and WH1/WH2; three-phase UH1,
VH1, WH1)? c) If a stronger droop effect is required, R7 (percentage
droop) should be turned clockwise starting from its central
d) Is the excess current circuit breaker in the alternator position.
switched on?
Note:
e) Is the droop transformer installed in the V phase? Where a number of alternators are run in parallel, the
droop device must be at the same setting in all the
f) Is the k – I phase position of the droop current transformer "COSIMAT N+" regulators and be active!
correctly connected? (In the case of external installation,
check from the alternator to the regulator).

29
Recommended droop settings: to flow freely through its power stage. Note the installation
position marking ”UNTEN” (= BOTTOM) (connecting
3% Parallel to the mains (If the mains supply is not leads towards the power stage). At fan cooling, the longitu-
stable, the setting may have to be increased). dinal axis of the "COSIMAT N+" has to be in air flow
direction. Deviating mounting is only suitable after checking
2% Parallel operation with identical alternators. by AvK.

6% Parallel operation with different alternators whose There must be a 3 cm clearance all the way round between
regulators do not have a linear droop. the "COSIMAT N+" and any structural elements that might
hinder flow (cable ducts, plates). This rule does not apply to
1% Parallel operation with different alternators which laterally mounted additional modules.
also have "COSIMAT N” or ”N+" regulators.

11.3 Excitation build-up


11. Important notes
At the nominal speed, the auxiliary excitation windings on
11.1 Protection concept for external mounting DSG and DIG alternators must produce a remanent voltage
of regulator of at least 10 V AC in order to ensure a satisfactory excitation
build-up.
The following protective measures must be taken if the regu-
lator is installed externally in the switching station: However, problems with excitation build-up may also be
caused by dirty de-excitation contacts or a field connection
The sensing line U-V-W is to be laid using short-circuit-proof of incorrect polarity.
cable (1.5 mm2) from the alternator terminal strip X2 to the
switching station. AvK recommends the installation of a In the case of alternators which have been stationary for a
three-phase circuit breaker with a thermal tripping current of prolonged period, it may be necessary to introduce an
approximately 0.5 A. If this circuit breaker is tripped, the external excitation voltage. To do this, a 4.5 V or 6 V battery
alternator must be de-excited and stopped immediately. is briefly connected by its positive terminal to I1 and by its
negative terminal to K1 at nominal speed. In the case of
If the regulator is installed externally, the connecting leads for two-phase auxiliary excitation machines, the battery should
the external set-point potentiometer, the droop current transfor- be connected to I2(POSITIVE)/K2(NEGATIVE).
mer, the droop switch and the I1/K1 exciter line are to be
provided with separate shielding. The shields must be earthed
at one end on the "COSIMAT N+". 11.4 Code switch S2

Protection concept: For standard applications of the "COSIMAT N+", the following
The exciter system should be protected from excessive exciter basic settings must be made before start-up at code switch S2
currents and voltages by a field discharge switch or relay. (see 9.2 Adjusting elements):
This switch or relay should be connected as shown in the
relevant order-specific circuit diagram. The tripping criteria AvK DSG alternators up to size 62
will be determined by the protection required by the alterna- S2.1 = no function
tor. S2.2 = ON (underspeed protection)
S2.3 = ON (actual value smoothing)
Where the alternator is operated in stand-alone mode, an S2.4 = OFF (D parameter)
overvoltage protection system must be installed in the swit-
ching station. In the case of operation in parallel with the AvK DIG and DSG 74 – 125 alternators:
mains or other alternators, an overcurrent protection system is S2.1 = no function
to be added. S2.2 = ON (underspeed protection)
S2.3 = ON (actual value smoothing)
DSG/DIG alternators with auxiliary windings: S2.4 = ON (D parameter)
DSG and DIG alternators with auxiliary windings are fitted
with an excess-current circuit breaker F1. This protects the Any differences from these settings must be agreed with the
auxiliary windings from excessively high thermal loading e.g. manufacturer beforehand and taken into account in the way
as the result of an external short circuit involving the auxiliary the alternator is operated.
exciter voltage UH1-UH2 or WH1-WH2.

11.5 Droop switch


11.2 Mounting the regulator
If alternators are to be used for both single and parallel
The "COSIMAT N+" must be mounted with its longitudinal operation, better voltage stability can be achieved in single
axis vertical in case of convectional cooling to allow the air

30
operation if the k – I inputs of the "COSIMAT N+" are it is installed in the synchronous machine and the way the
short-circuited (see 8. Diagrams of connections). droop current transformer is connected to the "COSIMAT N+"
remains the same (see 8. Diagrams of connections).
The lead between the droop switch and the regulator must be
screened. For motor control, a cos phi controller (COS module) is
required additionally.
The screen must be earthed at one end on the "COSIMAT N+".

Caution:

In parallel operation, the switch must be


opened.

11.6 Changing the direction of rotation

To enable the droop sensing system to exercise the correct


effect, the "COSIMAT N+" requires a clockwise-rotating field
at its measuring voltage connections.

Caution:

If the direction of rotation is reversed, in-


terchange sensing leads U and W.
Figure 36 – Modes of operation of a synchronous machine
Note:
The desired direction of rotation should be specified
when ordering the alternator. This is important with 11.8 Protective fuses
regard to ventilation.
When the protective fuses are tripped, they must be replaced
with fuses of the same type.
11.7 Synchronous motors
Fuse type:
Synchronous motors operate in a similar way to synchronous
alternators in parallel operation. The direction of the active
10 A super quick-acting IEC G 144.400
power is rotated through 180° relative to the alternator (see
Figure 36 – Operation of the synchronous machine).
Caution:
Starting from cos phi = 1, this has the following implications
for the reactive power: The power stage may be permanently da-
maged if slow or medium time-lag fuses
● Given a rising exciter current (overexcitation), the synchro- with a rating equal to or higher than 10 A
nous machine becomes a source of reactive power. are used!

● Given a falling exciter current (underexcitation), the synchro- Two spare fuses are mounted on the underside of the "COSI-
nous machine becomes an acceptor of reactive power. MAT N+" (see 7. Dimensions).
When used as a generator, the synchronous machine is taken
as the reference point; where it is used as a motor, the mains 11.9 Drying out the alternator
are taken as the reference point.
If, because of inadequate insulation resistance, the alternator
When used as a generator, the synchronous machine supplies has to be dried out at nominal current by the short-circuit
”inductive” reactive power to the mains when overexcited. method, the "COSIMAT N+" should be disconnected from
the supply and exciter field connections.
When used as a motor, the synchronous machine draws
”inductive” reactive power from the mains when underexcited. The alternator is dried out by applying an external source of
excitation.
The droop system in the "COSIMAT N+" operates with the
correct direction of action whether the machine is being Further information on how to dry out the alternator can be
operated as a motor or a generator. The direction in which found in the alternator instructions.

31
11.10 External power supply must be connected to the correspondingly named connecting
terminal of the "COSIMAT N+".
If the auxiliary exciter voltage is taken from a different,
”external” source (e.g. the mains), the supply must not be
switched on until the alternator has started up.
When shutting down the alternator, the supply must be
switched off before the machine comes to a halt.

The switch-on and switch-off point of the supply should be set


to 0.95 x fN using a frequency relay (BF1).

The double terminals at connections UH1 and WH1 can be


used to switch the supply on and off (see 8.5 De-excitation
circuit).

Caution:

When the alternator is stationary and an


auxiliary exciter voltage is applied, the
exciter current flowing is at its maximum!
The protective circuit of the "COSIMAT N+"
will trip the protection fuses on the front
plate after about 8 seconds.

11.11 400 Hz alternator/converter

On 400 Hz alternators < 100 kVA (as single machines or


converters), switch S2.3 must be set to the "OFF" position.

11.12 Checking the insulation voltage of the


electric machine

Before checking the insulation voltage of the electric machine,


the following connections of the "COSIMAT N+" must be
disconnected:

Measuring voltage U, V, W
Supply UH1-UH2, WH1-WH2
Exciter field I1-K1

The supply and measurement connections of additional regu-


lator components must also be disconnected.

All disconnected or interrupted connections should be isolated


in the appropriate manner.

11.13 Exchange/replacement; "COSIMAT N/N3"


by "COSIMAT N+"

On AvK alternators of series DSG, DIDBN, DIDBH and DIG,


sizes ...74-86-99-114-125, switch S2.4 on the "COSIMAT
N+" should be switched to the ”ON” position. Switches S2.2
and S2.3 should be switched to the ”ON” position. Switch
S2.1 should be set to the ”OFF” position.

The sequence of terminals WH1 and WH1’ has been


reversed on the "COSIMAT N+". The connecting cable WH1

32
11.14 Malfunctions, causes and remedies

Malfunction Cause Remedy

Alternator voltage is too low. Input speed too low. Check whether LED H1 on regulator
lights up. If so, underspeed protection
device has been activated, run up al-
ternator to nominal speed.

Measuring leads incorrectly con- Check measuring-lead connections U,


nected. V, W on the regulator. Check whether
the nominal voltage of the alternator is
within the voltage range indicated on
the "COSIMAT N+".

Alternator voltage is too low and can- Set-point potentiometer or its con- Check set-point potentiometer or its
not be adjusted with the set-point po- necting leads are disconnected/inter- connecting leads. Rectify fault.
tentiometer. rupted.

Alternator voltage is too high. Broken measuring lead. Rectify fault.

Measuring leads incorrectly con- Check measuring lead connections U,


nected. V, W on the regulator. Check whether
the nominal voltage of the alternator is
within the voltage range indicated on
the "COSIMAT N+".

Alternator voltage is too high and can- Set-point potentiometer or its con- Check set-point potentiometer for short
not be adjusted with the set-point po- necting leads have a short circuit. circuit. Change potentiometer. Check
tentiometer. set-point leads for short circuits. Elimina-
te short circuit.

Severe voltage dip upon loading. Input speed falls upon loading. Check regulator of driving machine.

Defective protection fuse. Check protection fuse on the regulator


and exchange if necessary.

Rotating diodes defective. Check rotating diodes V1 and surge


voltage protector V3 and R11 and
exchange if necessary.

Alternator does not respond to excitati- Input speed too low. Less than 0,5 x nN. Check the speed regulator of the input
on. machine. Check the power transmissi-
on to the alternator.

Exciter protection switch has tripped. Switch on the protective switch again.
If it trips once more, search for the fault
and repair it.

33
Malfunction Cause Remedy

Alternator does not respond to excitati- Remanence too low. Alternator with auxiliary winding:
on. Briefly connect positive terminal of 4.5
or 6 V battery to I1 and negative
terminal to K1 (at nominal speed).
Alternator with two-phase auxiliary
exciter machine:
Briefly connect positive terminal of 4.5
or 6 V battery to I2 and negative
terminal to K2 (at nominal speed).

DSG, DIG alternators: With alternator standing still!


Interruption in the auxiliary exciter win- Check windings UH1/UH2 and
dings. WH1/WH2 for interruptions using an
ohmmeter. Eliminate faults.

DIG alternators (UN ≤ 11,5kV): With alternator standing still!


Interruption in the auxiliary exciter Check windings WH1/WH2 and
machine windings. UH2/UH1/UH3 for interruptions
using an ohmmeter. Eliminate faults.

DSG, DIG alternators: With alternator standing still!


Interruption in exciter windings I1/K1. Check windings I1/K1 for interruptions
using an ohmmeter. Eliminate faults.

DIG alternators (UN > 11.5 kV): With alternator standing still!
Interruption in exciter windings I1/K1 Check windings I1/K1 and I2/K2 for
and/or I2/K2. interruptions using an ohmmeter. Elimi-
nate faults.

Fault in regulator. Check protective fuses and exchange


if necessary. Is the regulator receiving
excitation release and are the bridges
present at the double terminals I1/I1’,
K1/K1’, UH1/UH1’ and WH1/WH1’?
Check and eliminate fault.

Fault in the regulator connections. Check all regulator connections, input


and output leads. Eliminate faults.

Regulator defective. Exchange regulator.

Rotating diodes defective. Check rotating diodes V1 and voltage


surge protector V3 and R11 and
exchange if necessary.

Periodic fluctuations in the alternator Incorrect regulator setting. Adjust R1 carefully in the anticlockwise
voltage when operated singly (stability direction and turn S1 one or two steps
limit)! to the right.

34
Malfunction Cause Remedy

Alternator voltage fluctuates at irregular Temporary interruption in one of the Check connecting leads to the regula-
intervals. regulator supply leads. tor. Check connections at the terminal
board of the alternator. Tighten all con-
tact screws and nuts.

Mechanical regulator of the driving Check speed regulator of the driving


machine is sticking. machine. Eliminate fault.

Reactive power output too high in par- Droop set too low. Adjust R7 slightly in the clockwise di-
allel operation. rection on the "COSIMAT N+".

Transformer connections k/I have Open bridge.


been bridged by the droop switch.

Phase angle connection (k/I) of the Check connecting leads from the alter-
droop current transformer has been nator to the regulator. Interchange k/I
wrongly positioned. if necessary. The white secondary con-
nection of the droop current transformer
is ”k”.

Droop switch is not in alternator phase Install droop transformer in phase ”V”.
”V”.

Measuring voltage connections U, V, Check the sensing lead. "COSIMAT


W wrongly positioned. N+" requires a clockwise-rotating field.
Interchange U and W if necessary (in
the case of anticlockwise rotation).

Reactive power output too low in par- Droop set too high. Adjust R7 slightly in the anticlockwise
allel operation. direction on the "COSIMAT N+".

Measuring voltage connections U, V, Check the sensing lead. "COSIMAT


W wrongly positioned N+" requires a clockwise-rotating field.
Interchange U and W if necessary (in
the case of anticlockwise rotation).

Active load not equally distributed. This is affected by the driving machine Check the drive motor and its regulator.
only.
The "COSIMAT N+" affects only the
reactive power.

We reserve the right to make technical changes.

35
12. List of figures

Figure 1 General arrangement diagram . . . . . . . . . . . . . . . . . . . . . . . . . . 3


Figure 2 Adjusting elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 3 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 4 Characteristic quantities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 5 Trend of the control property . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 6 Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 7 Droop characteristic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 8 P adjustment range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 9 Underspeed protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 10 Equivalent control circuit diagram . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 11 Additional module COS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 12 Additional module QPF A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 13 Additional module QPF B . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 14 Additional module QPF C . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 15 Additional module SB2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 16 Additional module TF1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 17 Additional module ES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 18 Additional module UF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 19 Additional module UF3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 20 Additional module SR2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 21 Additional module EI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 22 Additional module UDC2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 23 Additional module KP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 24 Additional module ER1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 25 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 26 Internal mounting, DSG alternators 52 – 74 . . . . . . . . . . . . . . . . . . . . 21
Figure 27 External mounting, DSG alternators 52 – 74 . . . . . . . . . . . . . . . . . . . . 21
Figure 28 Internal mounting, DSG alternators 86 – 125 . . . . . . . . . . . . . . . . . . . 22
Figure 29 External mounting, DSG alternators 86 – 125 . . . . . . . . . . . . . . . . . . . 22
Figure 30 Internal mounting, DIG medium-voltage alternators with UN ≤ 11.5 kV . . . . . . . . 23
Figure 31 External mounting, DIG medium-voltage alternators with UN ≤ 11.5 kV . . . . . . . . 23
Figure 32 Internal mounting, DIG medium-voltage alternators with UN > 11.5 kV . . . . . . . . 24
Figure 33 External mounting, DIG medium-voltage alternators with UN > 11.5 kV . . . . . . . . 24
Figure 34 De-excitation circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 35 Field current/field voltage monitoring . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 36 Modes of operation of a synchronous machine . . . . . . . . . . . . . . . . . . . 31

36
AvK Deutschland GmbH & Co. KG
Niederlassung Dreieich
Benzstraße 47 - 49
D - 63303 Dreieich
Telefon: ISDN 0 61 03/50 39 - 0
Telefax: 0 61 02/50 39 - 40
BV COSIMAT N+.1 -31101 E

e-mail: [email protected]
http://www.newage-avkseg.com

AvK Deutschland GmbH & Co. KG


Bunsenstraße 17
D - 85053 Ingolstadt
Telefon: 08 41/7 92 - 0
Telefax: 08 41/7 92 - 2 50
e-mail: [email protected]
http://www.newage-avkseg.com

You might also like