Peltier Ussage
Peltier Ussage
Peltier Ussage
Thermoelectric
Generator
Operating Manual
23295 Rev. 2
Global Thermoelectric
Bay 9, 3700 - 78 AVE., S.E.
Calgary, Alberta
Canada, T2C 2L8
Phone: 1 (403) 236-5556
Fax: 1 (403) 236-5575
www.globalte.com5120 Quick Start Procedure
5120-SI-SO
Turn on gas supply to TEG. Hold down the button on Shut Off (SO) valve. The spark ignition
system (SI) should begin clicking and the sound of combustion heard within 15 seconds.
Continue holding the button for 90 seconds then release it. The SO valve should remain open
and the TEG should continue to operate.
Adjust the fuel pressure to 10-15% less than noted on Data Nameplate.
Install the jumper clip between terminals 3 & 4 of TB-1
After one hour measure the voltage, Vset
, between terminals 2(+) and 4(-) of TB-1. The Vset
should be approximately 6.7 volts. See Section 2.6 to adjusting for ambient temperature.
Return the jumper clip to between terminals 1 and 2 of TB-1
Apply Customer load
Fuel Pressure
Cathodic Protection Interface System (CP): The Cathodic Protection Interface System provides for
adjustment and monitoring of power to a cathodic protection (CP) load. The anode
and cathode cables enter the cabinet at the bottom and connect directly to a heavy duty terminal block.
A0 to 1 Ohm resistor, 300 watt variable resistor is provided for adjusting the output power applied to
the CP system.
TEG Mounting Stands (Pole and Bench Type): The Pole Stand consists of a 76"long piece
of 3" diameter pipe with an "H" shaped bracket welded to one end which the TEG can be firmly attached
to using 1/4" fasteners (not included). The Bench Stand consists of 3" by 3" and
2" by 2" aluminum angle sections that are assembled together to provide a sturdy structure to
support the TEG.Global Thermoelectric 1-3
23295 rev. 2
1.3 Definition of Terms
Thermoelectric Generator: A device that produces electrical power through the direct conversion of
heat energy to electrical energy.
Power Unit: The hermetically sealed portion of the generator that contains the thermoelectric materials
and the cooling fins.
TEG: AThermoelectric Generator.
Limiter-Converter (L/C): A specific electronic device attached between the generator and
load that converts one level of DC voltage to another, and limits the voltage level.
Generator System: The system consisting of the generator, including its factory options, the
limiter-converter, including its factory options, and the special customer options.
Set-up Voltage, Vset
: The set-up voltage of the generator.
Matched Load: Acondition of load where the load voltage of the generator is one-half of the
open circuit voltage and the load resistance is equal to the internal resistance of the generator.
Precision load: The precision resistor contained on the generator that provides the optimum
load condition. The voltage across the resistor is defined as Vset and is used to analyze generator
electrical performance.
Rated Power: The amount of power a generator can be operated at when the ambient temperature of
the site is expected to peak at 65C. As the ambient temperature increases the
rated-power decreases.
Rated Vset
: The amount of Vset
a generator can be operated at when the ambient temperature of the site is expected to peak at 65C.
As the ambient temperature increases the rated
Vset
decreases.
Open Circuit Voltage, V
OC: The voltage at the terminals of a power source when no appreciable current is flowing.
1.4 Theory of Operation
A thermoelectric generator (TEG) produces electrical power through the direct conversion of
heat energy into electrical energy.
This is done by joining two dissimilar, thermoelectric materials at one end and then heating
the junction end to a higher temperature than the other end. This creates a voltage across
the cooler end. Since this voltage is relatively small, the junctions are joined in series to
achieve a useful electrical output. If the temperature difference is maintained, electrical power
can be delivered to a load placed in this circuit.Figure 1 illustrates how this is done in the
model 5120 TEG. A thermocouple is
formed by P type and N type thermoelectric
elements joined together at one end by a
hot electrode. Adjacent thermocouples are
joined at the other end by cold electrodes.
Eighty thermocouples, each producing 84
mV are connected in series so that the TEG
The 5120 TEGs power unit produces 120 Watts gross at 20C at the beginning of its
service life.
Power decreases at a rate of 0.288% per C rise in Temperature (0.16% per F) see
Figure 7.
Maximum allowable ambient temperature for operation is 45C (115F).
Global Thermoelectric 1-4
23295 rev. 2
Figure 1 TEG Design2 Operation
2.1 Physical Description
5120 Dimension Chart
Length 757 mm (29.8 in.)
Width 370 mm (14.6 in.)
Height 987 mm (38.9 in.)
Weight 60 kg (132 lb)
Shipping Weight 79 kg (175 lb)
Mounting Holes 267 mm X 457 mm (10.50 wide X 18.00 deep)
2.2 Unpacking, Assembly and Mounting
Tools Required:
1x DC Voltmeter accurate to 0.1V.
2x Small adjustable wrenches that will open to 16mm (5/8 inch).
1x Flat head screwdriver.
4x #1/4-20 bolts & nuts for mounting.
1x Phillips Screwdriver.
Unpack the 5120 TEG from its shipping crate. Keep the crate until the TEG is operational.
Check the TEG for damage which may have occurred during shipping. Any damage must be
reported as soon as possible. The damage may make the generator inoperable therefore,
Check with Global Customer Service before starting a damaged TEG.
Locate and identify the following items that were shipped with the 5120 TEG.
1 x1Fin Duct.
1x Intake Stack with Clamp.
1x Exhaust Stack with Clamp.
1x Thread Sealing Compound.
7x #8 - 32 x inch long Screws (1 spare).
7x #8 Washers, external lock.
Assemble the TEG as follows (see Figure 2):
1) Attach the fin duct using the #8 screws and washers supplied.
2) Insert the intake and exhaust stacks into the top of the cabinet.
3) Slide the clamps over the bottoms of each stack and tighten the clamp screws.
Global Thermoelectric 2-1
23295 rev. 2Global Thermoelectric 2-2
23295 rev. 2
Mount the TEG to a firm and stable base, using 1/4-20 bolts, See Appendix Figure 25, page
4-2, for mounting hole locations. The base must be level and sturdy enough to support the
41 kg (90 lb) TEG. The TEG should be mounted high enough to avoid direct flooding or heavy
snowfall interfering with the flow of cooling air. Allow a minimum of 150 mm (6 in.) clearance
under the cooling fins.
WARNING: Operation of the TEG in locations where cooling air flow may be obstructed will cause
overheating of the TEG.
Figure 2 Assembling TEGGlobal Thermoelectric 2-3
23295 rev. 2
2.3 Data Plate
The data plate is located on the inside of the TEG cabinet door and indicates the following:
Fuel Type: An X is stamped in the appropriate box for Natural gas or Propane. Each fuel
type requires a different orifice, therefore the TEG must be used with the fuel indicated.
Model Number: The model number is interpreted as follows:
Serial Number: Unique to each TEG.
Power, Fuel Pressure, Voltage: These were measured during the factory performance test
and are for reference only. The operating power, fuel pressure and voltage are determined
and adjusted as per Section 2.6.
2.4 Fuel Supply
Fuel Considerations
Clean Fuel: The fuel used to operate the 5120 TEG must be clean (see gas specifications
inAppendix, page 4-3). If dirty fuel is anticipated
then a customer supplied, in-line fuel filter is recommended.
Low Temperature: When using propane (C3
H8
)
at temperatures below -30C (-22F) special consideration must be given to the low vapour pressure of
the fuel.
Pressure: Make sure that fuel pressure is at
least 69 kPa (10 psig) and will not exceed 172
kPa (25 psig). If it is expected that the fuel supply pressure will vary greatly, the use of an additional
primary regulator is recommended. This
will hold the input pressure relatively constant. Figure 3 Applying Thread Sealant
5120Global Thermoelectric 2-4
23295 rev. 2
Check the TEG data plate for the fuel type. DO NOT use a different type of fuel than indicated.
A fuel shut-off valve MUST be installed between the TEG and the fuel supply. All fuel piping
must be in accordance with local regulations.
1) Inspect the fuel lines and fittings to be sure they are free of foreign material.
2) Purge fuel lines of all air.
The TEG has a 1/4 in. NPT, male fuel inlet. Remove the plastic protective cap and apply
thread sealant, see Figure 3. Connect the fuel line and test all joints for leaks using a commercial leak
detector.
2.5 Start Up
System Performance Logs are located at the back of this manual,Appendix 4.4. Use of these
logs is recommended each time the site is visited. This information is valuable for future reference.
1) Move the jumper on TB-1 from between terminals 1 and 2 to between terminals 3 and
4, see Figure 4 or Figure 5..
2) Connect a DC Voltmeter to terminals 2(+) and 4(-) of TB-1. This will be measuring Vset
.
3) Make sure that all of the connections in the fuel system are tight and have been
checked for leaks.
Figure 4 Wiring Diagram 5120 TEG with Limiter ConverterGlobal Thermoelectric 2-5
23295 rev. 2
Check the ignition system, see Figure 6.
1) Loosen the ignitor rod wing-nut.
2) Push the ignitor rod in as far as it will go, (it should extend about 25mm (1 in.) past the
holding screw), then pull it back 3 mm (1/8 in.).
3) Tighten the wing-nut, DO NOT over tighten as the ignitor rod will crack.
2.5.1 SI-SO Start
1) Turn on the fuel supply.
2) Push in the button on top of shut-off valve. The spark ignitor should begin clicking and
the sound of combustion will begin. In some cases it may be necessary to bleed air
from the fuel line before combustion will begin.
3) Continue to hold the button down for at least 90 seconds after combustion begins, then
release the button.
4) If the sound of combustion stops, push the button again until combustion is sustained.
Note: It is necessary to fully depress the button before releasing it.
Figure 5 Wiring Diagram 5120 TEG with no Limiter/ConverterGlobal Thermoelectric 2-6
23295 rev. 2
2.5.3 Manual Start
If the TEG's SI system is malfunctioning, one can manually start the generator. It should be
noted that the malfunctioning SI be repaired as soon as possible as the TEG will not be able
to reignite itself in the event that the TEG's burner goes out because of fuel interruptions.
1) Remove the SI electrode from the burner
2) Push in the button on top of shut-off valve.
3) Place a lighted match or similar flame source to the electrode port. Ignition should
occur quickly and the sound of combustion will begin. For SI-SO fuel system continue
to hold the button on the shut-off valve for 90 seconds.
4) Repair and replace SI system as soon as possible.
Figure 6 SI-SO Start UpFigure 7 Rated Gross Power of Power Unit vs. Ambient Temperature at Beginning
of Life
Global Thermoelectric 2-7
23295 rev. 2
2.6 Evaluation
2.6.1 Set-Up Power and Vset
The power in the 5120 TEG is produced by the difference in temperature between the burner and the
cooling fins. This means that the power output of the 5120 TEG will be affected by
(Power) Check
After ignition has occurred the voltage
between terminals 2(+) and terminals
4(-), that is, Vset
will begin to climb as
shown on the graph in Figure 9.
The Vset
will rise quickly at first then
begin to level out. It will take at least
one hour for the Vset
to stabilize. When
Vset
no longer changes (0.2 V in ten
minutes) compare this value with rated
Vset
as determined in section 2.6.1,
these should be within 0.2 Volts of
each other.
If the measured Vset
is greater than
rated Vset
then the fuel pressure needs
to be reduced. If the measured Vset
is
less than rated Vset
then proceed as
follows.Global Thermoelectric 2-10
23295 rev. 2
2.6.4 Air-shutter Adjustment
1) Record the Vset
.
2) Open the doors and loosen the adjustment screw lock-nut Figure 6.
3) Turn the adjusting screw one turn counterclockwise.
4) Close the doors, wait ten minutes then measure Vset
.
IfVset
is greaterthan the original value or did not change (airrich)turn the adjusting screw
another turn counter-clockwise and wait ten minutes. Continue until you observe a decrease
in Vset
then proceed to next paragraph.
If Vset
is less than original value (fuel rich) refer to Figure 11. Notice that the peak of the
graph is within one quarter of a turn (either direction) of the adjusting screw. Set the adjusting screw so
that it is one half turn air rich.
Tighten the lock-nut.
Figure 11 Change in Vset
vs Air Shutter SettingGlobal Thermoelectric 2-11
23295 rev. 2
Figure 12 Change in Vset
vs Fuel Pressure Adjustment
2.6.5 Fuel Pressure Adjustment
If the fuel system and burner appear to be operating correctly, the fuel pressure may be slightly
adjusted to match the TEG's voltage with the rated Vset
value. Figure 12 can be used to
determine how much to adjust the fuel pressure.
EXAMPLE: Rated Vset
= 6.5 V
Measured Vset
= 6.8 V
Difference = -0.3 V
As seen on the graph, the fuel pressure must be increased 8.5 kPa (1.2 psi).
1) To adjust the fuel pressure, remove the cover on the regulator and loosen the lock nut.
2) Turn the adjusting screw (clockwise to increase pressure) until the required change in
pressure is obtained.Global Thermoelectric 2-12
23295 rev. 2
WARNING: Do not exceed the following values:
Natural Gas:31 kPa (4.5 psi)
Propane: 45 kPa (6.5 psi)
3) Wait at least 10 minutes before measuring Vset
. If the TEG still does not reach Vset
value then a problem exists with one of the TEG's systems. See section 3.3, trouble
shooting, for evaluation.
4) Replace the cover on the fuel regulator.
2.7 Customer Load Wiring
1) Use only copper wire, properly sized for the load current.
2) Bring the customer load wires through the strain relief bushing (located on the TEG
cabinet floor). Allow enough wire to connect to the terminal block TB-1.
At least once a year, perform a Power Check as outlined below. This should be the first procedure during
any service visit and will determine what further service may be needed.
3.1.1 Power Check
The Power Check is completed to ensure the TEG is operating at the correct Vset
for the current ambient temperature. This should be the first procedure completed during any service
visit and will determine what further service may be required.
1) Determine the rated Vset
for the current ambient temperature (see Section 2.6.1).
2) Move the jumper clip on the terminal block TB-1 to between terminals 3 and 4.
3) Connect a voltmeter between terminals 2 (+) and 4 (-). This is Vset
and should match
the Vset
for the current temperature see section 2.6.1.
If the measured Vset
is more than 0.2 volts above rated Vset
:The fuel pressure must be
reduced. Proceed with the basic service as per Section 3.1.2, but remember to adjust the fuel
pressure during restart or before leaving the site, see Section 2.6. DO NOT continue to operate above
Set Power.
If the measured Vset is within 0.2 volts of rated Vset: The TEG is functioning well and
requires only the basic service indicated in Section 3.1.2 below.
If the measured Vset
is more than 0.2 volts below rated Vset
: The cause must be evaluated. Referto the last entry in theSystem Performance Log. From the log,
determine if theTEGGlobal Thermoelectric 3-2
23295 rev. 2
was left operating at the correct Vset
Spark Ignition (SI) Module: When the fuel is turned on, the gas pressure causes the pressure switch
(located on fuel system) to close. This signals the SI module to generate 12 kV
sparks, which arc from the SI electrode to the combustion chamber wall, causing ignition to
occur. Once the fuel is burning the exhaust heat will signal the SI module to stop sparking.
Limiter Converter (L/C): The 220 Watt L/C consists of two separate circuits. The first is a
shunt type voltage limiter that regulates the output of the generator. The second is a DC to
DC converter that switches the input voltage to a different output voltage.
Protective Limiter: When the TEG does not have a Limiter Converter it will have a Protective
Limiter located on the underside of the cabinet. It is a shunt type voltage limiter that regulates
the output of the generator
Cabinet: The power unit, burner and fuel system are enclosed in the stainless steel cabinet.
Fin Duct: The fin duct acts as a chimney, causing ambient air to rise through the cooling fins,
thus cooling the thermopile.
3.2.1 Power Unit
The power unit contains the thermoelectric materials which produce the electrical power.
Because these materials corrode in atmospheric conditions at high temperatures they are
contained in a sealed unit.
If all other parts of the TEG have been checked out and it still does not produce rated power
then the power unit may be faulty. Check the momentary open circuit voltage as follows:Global
Thermoelectric 3-4
23295 rev. 2
Figure 14 TEG Main Parts
1) Place the jumper in Vset
position between terminals 3 and 4 of TB-1.
2) Connect a volt meter to terminals 2(+) and 4(-)
3) Open the circuit by quickly removing the jumper from the terminal block. Record the
voltage within 2 seconds. It will increase quickly and should be approximately 13 volts.
Immediately replace the jumper.
4) If the momentary open circuit voltage is below 12 volts, then the TEG is operating cold
and the fuel system and burner should be thoroughly checked and/or adjusted. If the
momentary open circuit voltage appears reasonable, but Vset
remains below 6.7 volts,
then the power unit is damaged and will need to be replaced.
Warning: Do not let the open circuit voltage exceed 13.5 Volts
3.2.2 Fuel System
The fuel system includes a FISHER 67CFR regulator which controls the fuel pressure to the
orifice. The regulator contains both a sediment bowl with a manual drain cock and a fuel filter. The
outlet of the pressure regulator leads to a manifold on which is mounted a pressure
gauge to monitor the fuel pressure. The fuel flows through the manifold to the fuel line whichGlobal
Thermoelectric 3-5
23295 rev. 2
connects to a orifice mounted on front of the burner. The orifice contains a jewel with a precisely drilled
hole to control the fuel flow into the burner. An SO valve is located between the
manifold and fuel line, and the SI pressure switch is mounted on the SO valve, see Figure
15.
3.2.2.1 Draining the Sediment Bowl
The sediment bowl will collect impurities in the fuel. Drain the regulator as follows:
1) Shut off the fuel supply to the TEG.
2) Open the drain cock located on the under side of the TEG cabinet. Any impurities will
drain through the cock.
3) Close drain cock.
Figure 15 SI-SO Fuel System ServiceGlobal Thermoelectric 3-6
23295 rev. 2
start cycle. If the battery is completely discharged it will require fifteen hours to fully recharge.
3.2.5.2 SI Maintenance
WARNING: To prevent high voltage shock remove the orange wire from the pressure
switch and make sure it can not come into contact with other electrical
connections.
1) Check the operation of the SI system as follows:
a) Remove theSparkElectrode by loosening the wing-nut and sliding the electrode
out.
b) Inspect the electrode for any cracks in the ceramic rod. If any cracks are found
the electrode must be replaced.
c) Slide the electrode back into position until it stops, then pull it back 3 to 6mm
(1/8 to1/4"). The ceramic rod should extend about 25mm (1") from the holding
screw.
d) Tighten the wing-nut only until it is snug. DO NOT over tighten or the ceramic
rod will crack.
e) Loosen the orange and brown wire connectors from the terminals on the pressure switch and then
short the circuit between the two terminals. Arcing should
occurin the combustion chamber(making a clicking noise) at the rate of one per
second.
f) If arcing occurs the system is functioning well.Global Thermoelectric 3-10
23295 rev. 2
2) Check the pressure switch. It should close at a pressure of 13.8 kPa (2 psig) and open
at 6.9 kPa (1 psig). Replace the pressure switch if necessary.
3) Check the battery voltage as follows:
a) Measure the voltage between the brown lead and terminal 4 of TB-1. The voltage should be greater
than 2 volts.
b) If the voltage is less than 2 volts the battery needs recharging or replacing.
c) Make sure all wire connections are secure.
4) Check the battery charger and spark generator as follows:
a) Manually light the TEG by placing a lighted match at the port of the SI electrode.
b) After twenty minutes of operation check the battery voltage as per step 3. The
voltage should be 2.35 volts.
c) Perform step 1 again. If sparking does not occur the control module needs to
be replaced.
5) Check if the battery will hold charge as follows:
a) Remove the thin white/red wire from terminal 2 of TB-1.
b) Connect the orange wire to the brown wire.
c) Measure battery voltage between the orange wire and terminal 4 of TB-1.
d) If the voltage is less than 2.0 volts, replace the battery.
e) To replace the battery open the control module.
f) Disconnect the battery leads.
g) Install a new battery, taking note of polarity.
Figure 19 Spark Ignitor Wiring DiagramGlobal Thermoelectric 3-11
23295 rev. 2
3.2.6 Automatic Shut-Off (SO) System
TheAutomatic Shut-Off System is designed to turn off the fuel supply to the TEG if the burner goes out.
The SO valve contains an electromagnet that is powered by a thermocouple
mounted on the burner (see Figure 15). When the thermocouple is no longer heated by the
flame, the current will drop to zero, causing the valve to close.
If the SO valve fails to stay open after the generator has warmed up for five minutes then the
SO system needs to be checked.
1) Make sure that the button on the SO valve is fully depressed before releasing it. This
23295 rev. 2
3.4 5120 TEG Parts List
Item Part No. Description
A13 6400-22367 Fuel System, SI
6400-22368 Fuel System, SI-SO
6400-22369 Fuel System, SI-SO, SS Option
A14 2200-02110 Terminal Block, 8 Position
A15 6300-20144 Control Module, SI II
A16 4100-01019 Leg, Left
4100-01020 Leg, Right
A17 2514-20535 Screw, Mach, Hex hd, 1/4 - 20 S 5/8 SS
A18 2710-00601 Nut, Wing, 10-32, SS
A19 4900-07004 Pin, Mounting, SI Electrode
A20 2756-07004 Nut, Wing, 5/16 - 18, SS
A21 4900-02032 Spark Electrode SI
A22 4900-00900 Bar, Mounting
A23 2508-07410 Screw, Mach, P-H-P, 8-32 x 1/4, SS
A24 2808-00472 Washer, Lock, Ext., #8, SS
A25 4400-07260 Resistor Assy, 50 W, 0.75 W
A26 2410-001222 Resistor, 1 W, 100 W, 5%
Figure 20 5120 TEG Parts IllustrationGlobal Thermoelectric 3-16
23295 rev. 2
3.5 5120 Burner Parts List
Item Part No. Description
B1 4000-00983 Burner Back Assembly
S.
4. Shall not contain more than 60 mg/Sm3
(approx. 88 pmm) of Mercaptan Sulphur.
5. Shall not contain more than 200 mg/Sm3
(approx. 294 ppm) of total Sulphur.
6. Shall not contain more than 10% [CO2
] and/or [N2
] by volume, nor vary more than +/- 1%
[CO2
] and/or [N2
] during operation.
7. Shall not contain more than 120 mg/Sm3
of water vapour.
8. Shall not contain more than 1% by volume of free oxygen.
9. Shall have a nominal gross heating value of:
Natural Gas: 37 MJ/Sm3 (1000 BTU/cu.ft.)
(1)
Propane/LPG: 93 MJ/Sm3 (2500 BTU/cu.ft.)
(1)
Butane: 108 MJ/Sm3 (2900 BTU/cu.ft)
(1)
10. Shall not exceed 60C (140F) in temperature.
Notes:
(1) - For gaseous fuels outside of these specifications, please contact Global Thermoelectric.
(2) - Sm3
= Standard cubic meter of gas at 101.325 kPa at 20C (NIST).Global Thermoelectric 4-4
23295 rev. 2Global Thermoelectric 4-5
23295 rev. 2
4.4 5120 Performance Log
MODEL NO:
TEG SERIAL NO:
FUEL TYPE:
LIMITER/CONVERTER SERIAL NO:
Maintenance
Repair Notes
Date
Time
Ambient Temp
C
Rated Power
(Watts)
Rated Vset
(volts)
Measured
Power
Fuel Pressure
Open Circuit
Voltage
Measured Vset
(volts)Global Thermoelectric 4-6
23295 rev. 2
4.4 5120 Performance Log
MODEL NO:
TEG SERIAL NO:
FUEL TYPE:
LIMITER/CONVERTER SERIAL NO:
Maintenance
Repair Notes
Date
Time
Ambient Temp
C
Rated Power
(Watts)
Rated Vset
(volts)
Measured
Power
Fuel Pressure
Open Circuit
Voltage
Measured Vset
(volts)