Teg 1120 Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 63

1120

Thermoelectric
Generator
Operating Manual
Global Thermoelectric
#9, 3700 - 78 AVE., S.E.,
Calgary, Alberta, Canada
T2C 2L8
Phone: 1 (403) 236-5556
Fax: 1 (403) 236-5575

Table of Contents
1

General
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-1
1.1
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-1
1.2
Definition of Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-1
1.3
Theory of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
1.4
Physical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-4
1.5
Electrical Output Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-6
1.6
Ambient Temperature Effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-9
1.7
Rated Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-9
1.8
Fuel Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-9
1.9
Boiling Temperature of Fuel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-9
1.10
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-10
1.11
Machanical Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-10
1.12
Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-11
1.13
Fuel Supply Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-13
1.14
Start up Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-14

Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
2.1
Data Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
2.2
Start-Up Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2
2.3
Starting Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2
2.4
Heat Up to Rated Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
2.5
Vset Versus Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-4
2.6
Vset Versus Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-4
2.7
Determining Required Vset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-5
2.8
Fuel and Air Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-6
2.9
Air Shutter Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-6
2.10
Fuel Pressure Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-8
2.11
Apply Customre Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-10

Service
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
3.1
1120 TEG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
3.2
Power Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
3.3
Burner Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
3.4
Fuel Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-3
3.5
Ignitor Housing Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
3.6
Conduit Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
3.7
Electronics Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-5
3.8
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-10
3.9
Field Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-11
3.10
1120 TEG Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-15
3.11
Ignitor Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-17
3.12
Burner Parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-18
3.13
Fuel System Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-20
3.14
Conduit Assembly Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-21
3.15
Ignitor Housing Assembly Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-22
3.16
Electronics Box L/C Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-23
3.17
Electronics Box Lid L/C Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-24

Appendix
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-1
4.1
Gas Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-1

List of Figures
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

TEG Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3


Physical Description, 1120 TEG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-5
Electrial Output Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-7
Power Vs. Ambient Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-8
TEG Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-11
Machanical Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-12
Recommended Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-13
Applying Thread Sealant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-14
Change in Fuel Pressure Vs. Elevation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2
TEG Start-U[ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
Vset Vs. Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-4
Vset Vs. Set Up Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-6
Change in Vset Vs. Air Shutting Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-7
Fuel Pressure Vs. Vset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-9
TEG Subsystems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
Power Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
Auto Shut off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-3
Schematic Diagram, 1120 TEG (sheet 1 of 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-6
Schematic Diagram, 1120 TEG (sheet 2 of 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-7
Electronics Diagram, 1120 TEG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-8
Removing Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-13
Fuel Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-13
1120 TEG Parts Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-15
Ignitor Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-17
Burner Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-18
Fuel System Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-20
Conduit Assembly Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-21
Ignitor Housing Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-22
Electronics Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-23
Electronics Box Lid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-24

MODEL 1120
HAZARDOUS AREA GENERATING SYSTEM
DESIGNED FOR
CLASS I, DIVISION I, GROUP D
T3 OPERATION

SPECIFICATIONS
Output Voltage
Nominal

12-18 VDC
24-30 VDC

Power Output

100 Watts Minimum

Special Features

Digital Panel Meter, LCD, Voltage and Current


Integral Blocking Diode
Voltage Sensing Alarm with dry contacts
Auto Shutoff
Spark Ignition
Auto Re-ignition

Fuel Consumption Natural Gas: 0.36 m3 per hour, (13 ft.3per hour)
Propane: 0.24 kg per hour, (0.54 lbs. per hour)
Dimensions
Width

61 cm (24.0 in.) with electronics box closed


92 cm (36.0 in.) with electronics box open

Depth

80 cm (31.5 in.)

Height

113 cm (44.5 in.)

Weight

123 kg. (270 lbs.)

Operating Temperature

-40C (-40F) to +65C (149F)

Storage Temperature

-65C (-85F) to +65C (149F)

GENERAL

1.1

General Information
This manual provides installation, operation and maintenance instructions for the Global
Model 1120 Thermoelectric Generator System.
Special Customer Option: If the Generator System was ordered with specially engineered
options, they are completely described in the red Special Customer Option section of the manual.

1.2

Definition of Terms
To correctly use this manual the reader must interpret the meaning of the following words as
herein defined:
Thermoelectric Generator: A device that produces electrical power through the direct conversion of heat energy to electrical energy.
Power Unit: The hermetically sealed portion of the generator that contains the thermoelectric materials and the cooling fins.
TEG: A thermoelectric generator.
Matched Load: A condition of load where:
a)
the load voltage of the generator is one-half of the open circuit voltage.
b)
the load resistance is equal to the internal resistance of the generator.
Optimum Load: A condition of load where the power output of the generator is maximized.
Precision Load: The precision resistor contained on the generator that provides the optimum
load condition. The voltage across the resistor is defined as Vset and is used to analyze generator electrical performance.
Power Conditioner: A broad term used to describe an electronic device attached to the generator output that converts, adjusts, limits or otherwise conditions power.
Auto Shutoff: The 1120 generator is equipped with a thermocouple controlled solenoid valve
that can be manually reset. In the event of extended flame failure the thermocouple output
will be reduced sufficiently to release the solenoid and stop fuel gas flow to the burner.
Converter: A specific electronic device attached between the generator and load that converts one level of DC voltage to another.
Limiter: A specific electronic device attached across the generator output that limits the voltage level.

Global Thermoelectric
27762 rev. 2

1-1

Generator System: The system consisting of the generator including its factory options, the
power conditioner including its factory options, and the special customer options.
Safe Operation, Operate Safely, Operating Safely: These are terms used to describe the
operation of the 1120 Generating System, when its operating area or zone, should suddenly
or gradually go hazardous towards or beyond the lower explosive limit (LEL). The generator
will either operate at reduced power or extinguish completely due to lack of oxygen. The generator system will not, either while running or attempting to be ignited, ignite the surrounding
hazardous atmosphere. If the operating area should clear within a short period of time the
generator will attempt to reignite itself. See short term auto ignition.
Short Term Auto Ignition: The generators high voltage ignition system will automatically
come on to reignite itself in the event of a flame failure due to either a blow out or short duration gas failure. Fuel gas must be present and the shut off valve must not have operated for
the auto reignition to occur.
Hazardous Area: (definition per Canadian Electrical Code, Part 1, Section 18)
18-002 Classification: Hazardous locations shall be classified according to the nature of the
hazard, as follows:
a)

Class I locations are those in which flammable gases or vapours are or may be sufficient to produce explosive or ignitible mixtures;

b)

Class II locations are those which are hazardous because of the presence of combustible or electrically conductive dusts;

c)

Class III locations are those which are hazardous because of the presence of easily
ignitible fibers or flyings, but in which such fibers or flyings are not likely to be in suspension in air in quantities sufficient to produce ignitible mixtures.

18-004 Division of Class I locations: Class I locations shall be further divided into two divisions as follows:
a)

Division 1, comprising Class I locations in which:


(i)

Hazardous concentrations of flammable gases or vapours exist continuously,


intermittently, or periodically under normal operating conditions; or

(ii)

Hazardous concentrations of flammable gases or vapours may exist frequently


because of repair or maintenance operation or because of leakage; or

(iii)

Equipment is operated or processes carried on of such nature that breakdown


or faulty operation thereof could result in the release of hazardous concentrations of flammable gases or vapours and simultaneous failure of electrical
equipment;

Global Thermoelectric
27762 rev. 2

1-2

b)

c)

Division 2, comprising Class 1 locations in which:


(i)

Flammable volatile liquids, flammable gases or vapours are handled,


processed, or used, but in which the liquids, gases, or vapours are normally
confined within closed containers or closed systems from which they can
escape only as a result of accidental rupture or breakdown of the containers or
systems or the abnormal operation of the equipment by which the liquids or
gases are handled, processed, or used or;

(ii)

Hazardous concentration of gases or vapours are normally prevented by positive mechanical ventilation, but which may become hazardous as the result of
failure or abnormal operation of the ventilation equipment or;

(iii)

The location is adjacent to a Class 1, Division 1 location, from which a hazardous concentration of gases or vapours could be communicated, unless such
communication is prevented by adequate positive pressure ventilation from a
source of clean air, and effective safeguards against ventilation failure are provided.

Group D includes propane, methane, butane.

NOTE:

1.3

Throughout this manual the words Generator, Thermoelectric Generator, TEG and
Generator System will be used interchangeably.

Theory of Operation
A TEG produces electrical power through the direct conversion of heat energy into electrical
energy. It operates on the same principle as the thermocouples that are used for measuring
temperatures and in safety shutoff controls for gas water heaters, home furnaces, etc..
However, the TEG utilizes semiconducting
thermoelectric materials that are much
more efficient and thus permit practical
thermoelectric power sources. A thermocouple consists of two dissimilar materials (usually in wire form) which are joined
together at one end. If this junction is
heated to a higher temperature than the
other end of the wire, a voltage will exist
across the cooler end. Further, electrical
power will be delivered to a load placed in
the circuit. This process will continue
provided that the temperature difference
is maintained. A TEG is a system which
provides the means to maintain these
required conditions.
Figure 1 illustrates how this is accomplished in the model 1120 TEG. A thermo-

Global Thermoelectric
27762 rev. 2

Figure1 TEG Design


1-3

couple is formed by a P type and an N type thermoelectric element joined together electrically by a hot junction electrode. Adjacent thermocouples are joined together electrically by cold
junction electrodes. Eighty thermocouples, each producing 84mV are connected in series so
the power unit produces 120 Watts at 6.7 Volts and 18 Amperes.
The hot junction of the thermocouples is maintained at a high temperature (538C or 1000F)
by a burner which operates on gaseous fuels such as propane or natural gas. The cold junction of the thermocouples is maintained at a lower temperature (163C or 325F) by an array
of cooling fins which transfer the heat to ambient air by natural convection. The thermocouples are contained in a hermetically sealed enclosure because they are adversely affected
when exposed to air at operating temperatures. They are surrounded by thermal insulation
to minimize heat loss.
Maximum power is delivered to the load when: (a) the load voltage is one-half of the open circuit voltage and (b) the load resistance is equal to the internal resistance. This condition is
called the matched-load power (also maximum efficiency) when the load voltage is slightly
higher than one-half (approx. 55%) of the open circuit voltage.
The TEG is supplied with a precision load resistor that provides a known load. This resistor
is used both in adjusting the TEG for proper operation and in evaluating its performance. The
fuel flow to the burner is adjusted so that the proper voltage exists across this precision resistor. At this condition the TEG is operating at the intended junction temperature and is delivering maximum power.
The TEG is supplied with a protective device which prevents its output voltage from rising
beyond 11.4 Volts. This is required because under extended open circuit (or slightly loaded)
conditions the hot junction temperature could increase beyond the safe operating range.
The burner operates at moderate pressures from 28 to 70 kPa (4 to 10 psi). The gas is
expanded through an orifice and then flows through a venturi where it draws in air needed for
combustion. The fuel flow is controlled by a pressure regulator and is adjusted by the operator to obtain the desired power output.
In summary, the TEG produces electrical power when a temperature difference is maintained
between the hot and cold junctions of the thermoelectric materials. The temperature difference, and therefore the amount of power produced, depends on the rate at which fuel is supplied to the burner. The operation of the TEG is simply the control of the fuel pressure to the
burner which results in the desired power output.
1.4

Physical Description
Figure 2 shows the generator in its normal operating position. Its physical description is:
length

798 mm

31.4 in.

602 mm

23.7 in.

880 mm

35.0 in. with Electronics Enclosure open

height

1150 mm

45.3 in.

weight

123.0 kg

270 lb

width

Global Thermoelectric
27762 rev. 2

1-4

Figure 2 Physical Description, 1120 TEG


Global Thermoelectric
27762 rev. 2

1-5

1.5

Electrical Output Characteristics


Figure 3 shows the electrical output characteristics of the Model 1120 power unit, which gives
the power, current and voltage as a function of the load resistance. The TEG will operate at
any load condition from short circuit to open circuit. Observe that the power goes through a
broad maximum between 0.3 and 0.5 ohms. Rated power (120 Watts) can be obtained only
if the load resistance is within this range. The graph is useful in determining power, current
and voltage at various customer load conditions. Refer to the graph and consider the following example:
1)

You are installing a Model 1120 TEG at a gas wellhead to cathodically protect the wellcasing from corrosion.

2)

You have measured and determined your total ground bed resistance to be 1.0 ohm.

3)

Find 1.0 ohm on the horizontal axis.

4)

Read vertically until intersecting the power, current, and voltage curves.

5)

Read horizontally to the vertical axis to determine the values of power, current and voltage.

6)

Which are 106 Watts, 10.2 Amps and 10.3 Volts.

Global Thermoelectric
27762 rev. 2

1-6

Figure 3 Electrical Output Characteristics


Global Thermoelectric
27762 rev. 2

1-7

Figure 4 Power Vs Ambient Temperature


Global Thermoelectric
27762 rev. 2

1-8

1.6

Ambient Temperature Effects


The electrical output of the TEG is dependent on ambient temperature as shown in Figure 4.
Observe that the power decreases as ambient temperature increases.
Statement of Rated Power
1)
2)
3)

1.7

The Power Unit produces 120 Watts when operated at an ambient temperature of
24C.
With the fuel flow held constant, the power changes at a rate of 0.288% per C (0.16%
per F) of temperature change.
The TEG can be operated at rated power to a maximum ambient temperature of
65.5C (150F).

Rated Power
The TEG can be adjusted for rated power at an ambient temperature by using the rated power
curve as shown in Figure 4. Consider the following example:
1)
2)
3)
4)
5)

1.8

The present site temperature is 40C.


Find 40C on the horizontal axis.
Read vertically until intersecting the rated power curve.
Read horizontally to the vertical axis to find the set-up power.
Which is 114 watts.

Fuel Consumption
The fuel consumption of the TEG operated at rated power is shown below. The TEG can be
operated at less than rated power, down to 75% or 90 Watts.

1.9

Boiling Temperature of Fuel


FUEL CONSUMPTION
AT RATED POWER

PROPANE
C 3H 8

BUTANE
C4H10

NATURAL GAS
METHANE CH4

LB/HR

0.54

0.54

GAL/HR

0.13

0.13

KG/HR

0.25

0.25

L/HR

0.48

0.42

CU FT/HR

4.70

3.52

13.0

CU M/HR

0.133

0.099

0.368

Boiling point of liquefied fuels at atmospheric pressure are:


methane
propane
butane
Global Thermoelectric
27762 rev. 2

- 166.5C (-258.7F)
- 42.1C ( -43.7F)
- 0.5C (+31.1F)
1-9

1.10

Installation
This generator must be installed by qualified personnel in accordance with international
and/or local electrical codes.
Carefully unpack the TEG from shipping container. Retain the shipping container until the
TEG is operational.
Identify and locate the following items from the shipping container:
A.
B.

Generator System Complete.


Customer Assy Kit.

Mount the TEG on a generator stand, if a stand has not been prepared, a field proven mounting arrangement is shown in Figure 5. Ensure that the TEG is mounted in accordance with
following notes:
A.
B.
C.
D.

The TEG must be mounted with the fin duct in a vertical position.
The air flow through the cooling fins must not be obstructed.
The TEG should be mounted at a height sufficient to prevent direct flooding or heavy
snowfall from interfering with the flow of cooling or intake air.
When the generator is installed near a building, field experience has shown that the
best locations are on the roof or on the windward side, with a minimum distance of 3.0
meters (10 feet) from the building. Be sure that the TEG location relative to buildings
and fuel containers are in accordance with local regulations.

When the TEG has been mounted on the stand, proceed with a complete mechanical inspection.
1.11

Mechanical Inspection (see Figure 6)


Remove the fin duct front cover and the eight 8-32 x 1/4" long screws. Locate the exhaust
flame arrestor and drip cap. Ensure that the exhaust flame arrestor assembly is screwed tight
to the exhaust stack. Loosen the two screws securing the drip cap. Remove and visually
inspect the flame arrestor element by looking down the exhaust pipe, ensure that there is no
visual damage or fractures, re-install the drip cap assembly and secure it in place. Replace
the fin duct cover.
Open the front doors of the cabinet and locate the burner mounting bolts, tighten the cap nuts,
and locate the air intake flame arrestor assemblies. Ensure that they are tightly secured.
Locate the Igniter housing assembly, remove the cap and visually inspect the ignitor connections, re-installing the cap securely. Check that all conduit connections are secure and the
mountings are tight.
Locate the fuel system assembly and ensure that all the connections are tight.

Global Thermoelectric
27762 rev. 2

1-10

Figure 5 TEG Mounting


Check that all hardware and mountings are secure and tighten as necessary. When the
mechanical inspection is complete, proceed to electrical connection.
1.12

Electrical Connection
NOTE:

This TEG incorporates a high voltage ignition system that operates from an internal
2 Volt battery. This battery is charged by the TEG. Disconnect one end of the 2
Volt ignitor battery and proceed with connection of the customer wiring (see Figure
7). Proceed to fuel connection.

Ensure that circuit breakers or disconnects are used at the load end of the wiring and that the
circuit is open prior to connection to the TEG (see Figure 7). If the 2 Volt battery and the disconnects are not open then the ignition system is still live and could cause an explosion.
Provision has been made in the electronics housing for two 3/4" NPT rigid conduit entries.
Sealing of these fittings must be used to maintain the system integrity. For access to the electronics assembly, remove the twenty 3/8-16 bolts installed in the lid and swing the lid open.
Terminal blocks have been factory installed for customer connection. TB2-2 is +24 Volts, TB23 is -24 Volts. The voltage sensing relay terminals are located on the Limiter Converter board
mounted on the lid.

Global Thermoelectric
27762 rev. 2

1-11

Figure 6 Mechanical Inspection


Global Thermoelectric
27762 rev. 2

1-12

Figure 7 Recommended Connections


1.13

Fuel Supply Connection


Although the TEG fuel regulator incorporates a liquid trap and 40-50 micron stainless steel filter, the generator system has been designed to operate on sales or instrument quality fuel.
Due to site specific fuel characteristics, ensure that necessary pre-filtration has been installed
prior to connection to TEG fuel lines.
The maximum regulator input pressure is 1724 kPa (250 psi). For good stability it is recommended that the regulator input pressure be a minimum of 172 kPa (25 psi) in applications
where multi-stage regulation is employed. Install a shut off valve immediately upstream to the
TEG connection in a convenient and readily accessible location. Connect the fuel supply to
TEG as follows:
1.13.1 Check Data Plate for type of fuel. Data Plate is located on the inside right-hand cabinet door. An X is stamped in the appropriate box for fuel type, natural gas or propane.
Important: Each fuel type requires a particular orifice. Use only the fuel indicated on Data Plate.
NOTE:

If unit was ordered for use with butane, the Data Plate will indicate propane. This
is because the energy contents are the same, therefore they require the same orifice.

Also note that in the case of propane and butane ensure that the fuel input is a vapour fuel as
opposed to liquid fuel, unless the generating system has been ordered with a vaporizing system. Next if ambient temperatures below 5C (41F) are expected, be sure that the fuel contains an additive to prevent any moisture in the fuel from freezing. Anhydrous methanol added
Global Thermoelectric
27762 rev. 2

1-13

in the ratio of one litre of methanol to 800


litres of fuel tank capacity is recommended.
1.13.2 Apply thread sealant to all pipe
connections using the method illustrated in Figure 8. A "Union" type
connection is recommended at the
TEG.
1.13.3 Inspect the fuel line from the fuel
supply and insure that it is free of
foreign material. Purge fuel line
prior to connection.
Figure 8 Applying Thread Sealant
The TEG is Equipped with a 1/4 NPT
Male Input Connection. Remove the
protecting plastic cap and connect the fuel line. Test all connections to ensure they are leak
tight with leak detector.
1.14

Start Up Preparation
1.14.1 Ensure that the fuel is turned off.
1.14.2 Reconnect the 2 Volt battery. Ensure that all electrical connections are secure. Install
ionizing corrosion inhibitor on the floor of the electronics housing.
1.14.3 Close the electronics housing and install the twenty 3/8-16 bolts. The Customer must
Tighten all Bolts to Establish Explosion Proof Seal of the assembly and provide
weather proofing.
1.14.4 Test the ignitor system. While pushing the manual ignitor button, listen at the ignitor
housing. A sharp snap should be heard as the ignitor discharges. If this is not audible, refer to Trouble Shooting (section 3.9) for set up of ignitor system and correct.
1.14.5 Proceed to Section 2, Operation.

Global Thermoelectric
27762 rev. 2

1-14

OPERATION

2.1

Data Plate
2.1.1 Location: Data Plate is located on the inside of the right-hand cabinet door.
2.1.2 Fuel Type: An "X" is stamped in the appropriate box for Natural Gas or Propane.
IMPORTANT: Each type of fuel requires a particular orifice, therefore use only the fuel indicated on the data plate.
NOTE:

If butane is used, the data plate will indicate propane. This is because the energy
content of propane and butane are nearly equal; therefore, they require the same
orifice.

2.1.3 Model Number: The model number on the Data Plate is interpreted as follows.
2.1.4 Fuel Pressure, Power, Voltage: The fuel pressure, power output and voltage across
1120 ( ) - ( )
FUEL TYPE:
L = PROPANE
N = NATURAL GAS
POWER CONDITIONER VOLTAGE:
12, 24 or 48 V

the precision load that were measured during the factory performance test are recorded on the data plate. Observe that the fuel pressure is stamped in kPa and that the
pressure gauge has scales for both kPa and psi. Figure 9 shows how the fuel gauge
pressure differs from that stamped on the data plate if the TEG site is at an elevation
different than Global's factory (750 meters). This is due to the fact that the gauge reading varies with atmospheric pressure which changes with site elevation. This information is provided for reference only because, as you will see, the fuel pressure is adjusted to obtain the desired power.
2.1.5 Serial Number: The serial number is a unique number assigned by Global to provide
traceability.

Global Thermoelectric
27762 rev. 2

2-1

Figure 9 Change in Fuel Pressure Vs Elevation


2.2

Start-Up Data Sheets


Start-up Data Sheets are provided at the back of this section to assist you in setting up the
TEG properly. During set up you will be asked to record data on these sheets so remove one
at this time and keep it available. It is recommended that a Data Sheet be used each time
the TEG is started. They are valuable for future reference. If additional sheets are needed
they can be duplicated.

2.3

Starting Generator
Perform the following steps (see Figure 10):
2.3.1 Turn on fuel. Loosen the lock nut on the fuel regulator.
2.3.2 If required, correct the factory set fuel pressure for the elevation as per Figure 9,
Change in Fuel Pressure Vs. Elevation.
2.3.3 Adjust the air shutters to slightly fuel rich from the factory set position. Note that the
air shutters should always be adjusted equally in small increments.
2.3.4 Set the "Power Switch" to set up position.
2.3.5 Set the "Output Voltage Adjust" to middle position.

Global Thermoelectric
27762 rev. 2

2-2

Figure 10 TEG Start Up


2.3.6 Press down the button on the shut off valve. The TEG should immediately start firing,
as noted by a popping inside the combustion chamber. The TEG will pop until sustained ignition occurs (purring sound). Record the time of sustained ignition.
Note:

2.4

If popping and sustained ignition cannot be obtained quickly, adjust the air shutters
to air rich position until sustained ignition occurs, then using several small steps,
return the air shutters to the factory set position.

Heat Up to Rated Power


TEG performance is determined by measuring the voltage across the precision load. This
voltage is defined as Vset and is measured by the digital panel meter when the power switch
is in the set up position.

Global Thermoelectric
27762 rev. 2

2-3

2.5

Vset Versus Time


The heat up characteristic of the TEG is shown in
Figure 11, which gives Vset as a function of time
after ignition. This curve is for a TEG set at the fuel
pressure that produces rated power. During this
heat up period, measure the Vset and record it as
item 2 on the start up data sheet at the time intervals specified. To monitor progress during heat
up, compare your measurements with those
shown in Figure11.
After 20 minutes of operation observe the Vset and
determine the following:
1)

If Vset is near 6 volts, the fuel pressure is set


for rated power.
Figure 11 Vset Vs Time

2)

If Vset is less than 5.5 volts, the fuel pressure


is set for less than rated power, but do not adjust at this time.

3)

If Vset is greater than 6.5 volts, the fuel pressure is set for more than rated power.
Reduce the fuel pressure by 9.8 kPa (1.4 psi) at this time, see Figure10 and Figure 13.

WARNING: To prevent damage to the TEG do not allow the Vset to exceed 7.1 volts at ambient temperatures above 24C (75F).
2.6

Vset Versus Power


Vset the voltage across the precision load, is a measure of power. The value of the precision
load (0.387 ohms) is selected to provide the optimum load condition for the TEG.
The relationship between Vset and power (P) is:
P = Vset2
0.387
This relationship is shown in Figure 12. The graph gives Vset as a function of set-up power.
In determining power (P) consider the following example:
1)

Your Vset is 6.12 volts.

2)

Locate 6.12 volts on the vertical axis.

3)

Read horizontally until intersecting the curve.

4)

Read vertically downward to the horizontal axis to determine power.

Global Thermoelectric
27762 rev. 2

2-4

5)

Which is 97 watts.

In determining Vset consider the following:

2.7

1)

The power is 120 watts.

2)

Locate 120 watts on the horizontal axis.

3)

Read vertically until intersecting the curve.

4)

Read horizontally to the vertical axis to determine Vset.

5)

Which is 6.8 volts.

Determining Required Vset


This heat up period is the ideal time to determine the Vset. Vset is based on set up power as
follows:
SET UP POWER
from Figure 4

Vset
from Figure 12

Set up power is found by adjusting the desired power for ambient temperature. Vset is determined from set up power as shown in Figure 12.
1)

Estimate the maximum ambient temperature expected at the side and record on the
start up data sheet as Item 3.

2)

Measure or estimate the present ambient temperature and record as Item 4.

If rated power or maximum allowable power is desired:


3)

Use the information in Figure 4 and the procedures in section 1.7 to determine the corresponding set up power and record as Item 5.

4)

Use Figure 12 to determine the related Vset and record as Item 6.

If less than rated power is desired:


5)

Determine the desired power output.

6)

Determine the corresponding set up power by adding 0.3 watts to the desired power
for each C difference between the present and maximum ambient temperatures.

7)

Refer to Figure 12 to determine the related Vset and record as Item 6.

Global Thermoelectric
27762 rev. 2

2-5

Figure 12 Vset Vs Set up Power


2.8

Fuel & Air Adjustment


After the TEG has been operating for one hour, Vset should not be changing with time. The
readings on the start up data sheet at 40 and 60 minutes should not differ by more than 0.2
volts. When you are satisfied that Vset is not changing with time, compare the measured value
of Vset with the required Vset, Item 6. Proceed with air shutter adjustments to optimize the
burner first (section 2.9) then adjust the fuel pressure as required (section 2.10).

2.9

Air Shutter adjustment


This burner contains dual air shutters which control the amount of air used for combustion.
See Figure 10.
If too little air is used (fuel rich), combustion is incomplete and not all the energy in the fuel is
converted to heat.

Global Thermoelectric
27762 rev. 2

2-6

If too much air is used (air rich), additional energy is required to heat the excess air to exhaust
temperature.
In both cases fuel is being wasted. When the air shutter is at its optimum setting (neither of
above) the TEG is operating at maximum efficiency.
NOTE:

If available a combustion analyzer will facilitate rapid air shutter optimizing as you
need not wait for Vset to change.

Figure 13 shows change in Vset as a function of air shutter settings. Observe that Vset
decreases more rapidly on the fuel rich side than on the air rich side. For this reason a fuel
rich operation is to be avoided.
Make initial adjustments of air shutters towards the fuel rich side by decreasing the air holes.
Both air shutters are to be adjusted equally in small increments. Wait 5 to 10 minutes for burner to stabilize. Note the Vset and record.
If Vset increased or did not change, the burner is air rich. Continue decreasing the air holes
until a slight decrease is observed.
Note:

You must wait the required time after each adjustment. When a decrease in Vset
has occurred, increase the air hole size by rotating the air shutter back about
2.5mm. This should ensure slightly air rich (optimum) settings.

Figure 13 Change in Vset Vs Air Shutting Setting


Global Thermoelectric
27762 rev. 2

2-7

If Vset decreased you are presently fuel rich. Enlarge the air holes until Vset peaks then
increase the air holes slightly more towards the air rich side (optimum settings).
After the unit has stabilized, read Vset and compare with required Vset Item 6.
If these values are not within 0.1 volts, proceed to fuel pressure adjustment (paragraph
2.10).
If these values are within 0.1 volts, the TEG is ready to switch to operate mode.
2.10

Fuel Pressure Adjustment


To change Vset it is necessary to change the fuel pressure. Figure 14 shows the change in
Vset as a function of the change in fuel pressure for a typical TEG operating at rated power.
The following examples will illustrate how this curve can be used.
1)

Suppose the measured Vset is 6.5 volts, but 6.7 volts or a change of +0.2 volts is
required.

2)

Locate the 0.2 volts on the vertical axis and read horizontally until intersecting the
curve.

3)

Read vertically down to the horizontal axis and find the required change in fuel pressure.

4)

Which is 5.5 kPa (0.8 psi).

You must increase the fuel pressure by 5.5 kPa or 0.8 psi.
5)

Suppose the measured Vset is 6.8 volts and that 6.5 volts or a change of -0.3 volts is
required.

6)

Locate -0.3 on the vertical axis and read horizontally until intersecting the curve.

7)

Read vertically down to the horizontal axis and find the required change in fuel pressure.

8)

Which is -8.3 kPa (-1.2 psi).

You must decrease the fuel pressure by 8.3 kPa or 1.2 psi.
2.10.1 Use the following procedures to make the adjustment in fuel pressure:
1)

Record Vset after a minimum of one hour of operation as Item 7.

Global Thermoelectric
27762 rev. 2

2-8

Figure 14 Fuel Pressure Vs Vset


Global Thermoelectric
27762 rev. 2

2-9

2)

Determine the required change in Vset by subtracting Item 7 from Item 6 and record as
Item 8.

3)

Record the fuel pressure as Item 9.

4)

Determine the required change in fuel pressure from Figure 14 and record as Item 10.

5)

Determine the new fuel pressure by adding Item 10 to Item 9 and record as Item 11.
EXAMPLE:
Item 9 = 37.9 kPa (5.5 psi)
Item 10 = 2.1 kPa (0.3 psi)
New Fuel
Pressure = 35.8 kPa (5.2 psi)

2.11

6)

Adjust the fuel pressure to the value in Item 11. Close the cabinet doors and record
the time.

7)

Wait at least 10 minutes and record Vset as Item 12.

8)

Compare this new value of Vset in Item 12 to the required value in Item 6. If the two
are still different by an unacceptable amount, repeat this procedure using the latest values of Vset and fuel pressures as Items 7 and 9.

9)

When the measured and required values of Vset are in agreement, the TEG is ready to
switch to operation mode.

Applying Customer Load


The TEG is now operating at the required power output. If this is a single TEG system, it is
ready to connect to the customer load. If there are multiple TEGs ensure that all units are
ready before proceeding.
1)

If station batteries are present, measure and record their voltage. Batteries should be
fully charged; if they are discharged below 22 volts, the 1120 TEG will not charge the
station battery.

2)

Set power switch to "Run" position, see Figure 10. The TEG "normal" light should
come on. Adjust the voltage control to the desired operating voltage plus 0.7 volts
using the Output Voltage Adjust dial on the electronics box and the reading on digital
panel meter. If a multiple TEG system is in use, ensure that all outputs are equal.

Note:

Global Thermoelectric
27762 rev. 2

The TEG incorporates a protective series diode. The output voltage will drop 0.7
volts from the no load to loaded condition.

2-10

Push the red "Meter Select" button to read the current.


3)

Connect the customer load via disconnects mentioned in Electrical Connection section
1.12. The TEG "Normal" light should remain as a steady glow, if the lamp dims or the
output voltage drops significantly, the TEG is being overloaded. Ensure that the load is
no more than 100 watts at 24-30 volts.

4)

In multiple generator systems ensure that all outputs are set the same.

Global Thermoelectric
27762 rev. 2

2-11

Global Thermoelectric
27762 rev. 2

2-12

SERVICE

3.1

1120 TEG
This section contains service information and theory of operation on the 1120 generator system only. If the system contains any options, they are described in the Special Options section.
The 1120 Generator can be broken down into several subsystems consisting of the following
(see Figure 15):

Power Unit Assembly


Burner Assembly
Igniter Housing Assembly
Fuel System Assembly
Conduit Assembly Electronics
Electronics Assembly

Figure 15 TEG Subsystems

Global Thermoelectric
27762 rev. 2

3-1

3.2

Power Unit: See Figure 16.


The power unit is a solid state high reliability design that requires little maintenance. It produces constant output power if the correct temperatures are maintained. See discussion in
Theory of Operation section 1.3.
Note:
a)
b)

The correct temperatures


will be maintained if:
The fuel and air flow to burner
are constant.
The flow of cooling air to the
fins is not obstructed.

The power unit assembly consists of


cooling fins on one end, a hermetically sealed thermoelectric pile in the
middle and a combustion chamber on
the other end which accepts the burner assembly.
3.3

Burner Assembly: See Figure 25


The burner assembly consists of the
burner components, the heat
exchanger, and flame arrestors, air
intake and exhaust . This assembly
performs several functions.

Figure 16 Power Unit

The orifice introduces fuel at a predetermined pressure to the burner. This fuel flows through
the venturi tube and the venturi effect causes air to be drawn in through the intake flame
arrestors. The air shutters regulate the combustion air quantity. Thus fuel and air are mixed
in the venturi tube and passed through the burner screen to the back of the combustion chamber, where it is ignited and burned to produce the operating temperature required. See Figure
1, section 1.3.
The exhaust gases from the combustion chamber are then drawn through the heat exchanger and exhaust flame arrestor to the atmosphere. The function of this heat exchanger is to
reduce the temperature of these gases to below the T3 temperature rating of 200C (392F)
and maintain surface temperatures below this rating as well.
The function of the intake and exhaust flame arrestors is to prohibit the propagation of any
flame from the combustion chamber to the surrounding atmosphere. The flame arrestors
come into play mainly on a cold ignition of the generator. The flame arrestor elements are a
45 grade nickel chromium foam metal able to withstand corrosion and the operating temperatures encountered.
The burner assembly requires no maintenance.
Global Thermoelectric
27762 rev. 2

3-2

Figure 17 Auto Shut Off


3.4

Fuel Assembly: See Figure 26.


The major components of the fuel assembly are the regulator, pressure gauge, shut off valve
and thermocouple, pressure switch, fuel line and orifice.
The regulator used here is a Fisher type 67 CF. Maximum inlet pressure is 1724 kPa (250
psi). This regulator incorporates a liquid trap and a 40-50 micron filter for added protection.
The actual outlet adjustment range of this regulator is from 0 to 103 kPa (0 to 15 psi), which
is monitored with a pressure gauge of this range.
The fuel supply is then fed to the shut off valve which in conjunction with the thermocouple
works as an auto shut off system designed to shut off the gas supply if the TEG burner should
go out for an extended period of time. Figure 17 shows the electrical operation of the shut off
valve and thermocouple.
NOTE:

The time required for dropout of the shutoff valve can vary from 1 to 7 minutes. This
time being determined by the holding current requirements of shut off valve coil,
spring pressure, thermocouple output and operating temperature.

The auto shutoff valve is a manually operated valve and must be reset by pushing the button
and holding it in until sufficient heat acting on the thermocouple will hold the coil energized.

Global Thermoelectric
27762 rev. 2

3-3

The pressure switch mounted on the output side of the shutoff valve operates at approximately 14 kPa (2 psi). This switch on closing applies 2 VDC and power to the ignition system discussed above. This feature gives auto ignition at start up and a short term auto re-ignition in
the event of a flame out, due to blow out, short term loss of gas, or short term severe hazard
condition.
The fuel is next fed to the flexible fuel line and then to the orifice. The flexible fuel line is standard, however the orifice is unique to the type of fuel used, natural gas or propane.
3.5

Igniter Housing Assembly: See Figure 28.


The ignitor housing assembly consists of a junction box housing, the associated fittings and
the high voltage ignitor module. Also it contains the ignitor electrode assembly, the interconnect cable and the mounting connector.
The ignitor housing is mounted to the heat exchanger with the electrode inserted into the
burner and connected to the high voltage ignitor module.
The electrode is inserted through the burner into the combustion chamber and properly
gapped (1/8" to 3/16" from the combustion chamber wall). The electrode is then connected
by the cable to the output of the high voltage ignitor module and is ready for ignition.
The ignition system operates on 2 VDC applied to the high voltage ignition module, which in
turn generates a 12 kilovolt spark which arcs from the electrode to the combustion chamber
wall. When power is applied the module will generate approximately one spark per second
until ignition occurs and combustion is sustained, at which time flame ionization causes a
small current to flow and holds off the sparking module.
Power to the ignitor assembly is supplied by the electronics assembly (see Figure15) and
routed through the conduit assembly.
Control is by the manual ignition switch of the electronics assembly or the pressure switch of
the fuel assembly.

3.6

Conduit Assembly: See Figure 27.


The conduit assembly is a distribution system for the routing of signal and control wires to and
from the fuel system, ignitor system, electronics system and digital panel meter. It consists of
a junction box for distribution and interconnection, flexible conduit assemblies with seals for
maintaining the integrity of assemblies, and a digital panel meter for display of voltage and
current settings. The digital panel meter is not field repairable and requires replacement of
both the display section and monitor board (located in electronic housing) in the event of failure.

Global Thermoelectric
27762 rev. 2

3-4

3.7

Electronics Assembly: See Figure 18, Figure 19, Figure 29.


The electronics assembly consists of a housing assembly, protective limiter, converter, precision load resistors, voltage sensing alarm circuit, battery charger control module and battery,
protective diode and current shunt, voltmeter input circuits, and all associated switches and
controls. Refer to Figure 29 for physical location of circuits and Figure 18 and Figure 19 for
schematic diagram of these circuits.
3.7.1 Electronic Housing: This box has been designed to meet the requirements of Class
I, Division I, hazardous areas. It also performs as a heat sink capable of dissipating
the full output power of the TEG when in a set up or no load condition.
3.7.2 Precision Load: Two 0.75 ohm, 50 watt resistors connected in parallel (resulting in
0.375 ohm) as well as their associated wiring, which when switched to the power unit,
give us a precision load resistance of 0.387 ohm (approximately), provide the optimum
load condition for the TEG. This precision load is used for adjusting the TEG and evaluating its performance. A load voltage of 6.87 volts would give 120 watts from the TEG.
3.7.3 Protective Limiter: This is a protective device connected directly across the output of
the power unit which prevents its output voltage from rising beyond 12 volts. The
schematic diagram for the protective limiter is shown in Figure 19. Refer to Figure 29
for the location of the limiter resistors and limiter converter board.
The limiter is designed to operate in a linear mode (good regulation) up to a power level of
102 watts. Above 102 watts it saturates (fully on) and the limiter goes into a nonlinear mode.
As it goes from linear to nonlinear the limit voltage begins to increase slightly.
When the TEG is set up to produce rated power, its output is 90 watts at 11.4 volts (or 12 watts
below the saturation point of the limiter). In no case will the limiter allow the voltage to rise
beyond 12 volts.

Global Thermoelectric
27762 rev. 2

3-5

Figure 18 Schematic Diagram, 1120 TEG (sheet 1 of 2)

Global Thermoelectric
27762 rev. 2

3-6

Figure 19 Schematic Diagram, 1120 TEG (Sheet 2 of 2)

Global Thermoelectric
27762 rev. 2

3-7

Figure 20 Electronics Diagram, 1120 TEG

Global Thermoelectric
27762 rev. 2

3-8

The limiter circuit operates in the following manner. Referring to Figure 18 and Figure 19, note
that the limiter is connected directly across the TEG output. The normal state of the limiter
circuit is that all transistors are turned OFF. As the TEG voltage approaches the limiter set
point, dictated by the voltage divider adjustment of the 10K trim pot, the 2N4403 and IRFPO44
transistors gradually turn ON. The degree at which the IRFPO44 is turned ON depends on
the current flow from the TEG required to maintain the set point voltage. The limiter will have
a good regulation until the IRFP044 becomes saturated.
3.7.4 DC/DC Converter: The converter PCB assembly is shown in Figure 29, item F11. All
components are mounted on the PCB attached to the door assembly. The DC/DC
Converter schematic is shown in Figure 18.
This converter is a high efficiency switching regulator designed to step the TEG output voltage up to 12 V or 24 V nominal. The dip switch settings for the different outputs are shown
in Figure 18. Fine tuning of the output voltage is accomplished by adjusting S4 located on the
front of the electronics box.
The TL497A switching regulator IC is used to drive the IRFD110 FET, which in turn drives the
IRFPO44 FET. The pulse width modulation from the TL497A determines the switching duty
cycle of the FETs which determines the increase in voltage across L1. The SR3040 isolation
diodes are located before and after the low pass filter which consists of transformer T1 and
two 2200 F capacitors.
The input current is limited through the shunt mounted to the main PCB. The LM2908 OpAmps drive transistor 2N4401 which increases the current limit sense voltage drop at pin 13
of the TL497 as it turns on. The 20K trim pot is used to set the gain of the OP-AMP to limit
the current at 15 AMPs. This is factory set and should not be adjusted by field personnel.
3.7.5 Voltage Sensing Relay Circuit (VSR): Refer to Figure 19. The VSR circuit uses a
LM311 voltage comparator to operate the relay K1. The 2.5 Volt level created by the
LM285Z 2.5 voltage reference is used as one input while the output from the tap of the
10K trim pot is used as the other. The LM317T is configured as a 10.0 volt regulator
to provide a stable voltage for the relay and comparator to operate with either a 12 or
24V output voltage. The 10K trim pot is set so that the relay is energized for normal
operation, and de-energizes for an alarm. The relay contacts are brought out to the
edge of the main PCB shown in Figure 30.
3.7.6 Battery Charge Control Module and Battery: Refer to Figure 29 for the location of
the battery and control module. Refer to Figure 19 for the schematic diagram. The primary purpose of this circuit is to supply 2 VDC to the spark ignitor module (located in
ignitor housing assembly). The main source for this supply voltage is the 2 volt sealed
re-chargeable lead acid battery. As all batteries tend to self-discharge, the control
charger circuit is incorporated to maintain the battery at a constant charge. The charging circuit will accept an input voltage of 2.3 volts to maintain the battery at a fully
charged condition. The dual inductor and two 100uF caps filter any noise. Power to
the ignitor circuit is switched by the manual ignition switch (Push to Ignite) or the fuel
system pressure switch.

Global Thermoelectric
27762 rev. 2

3-9

Note: The battery charge circuit is normally charged from the 6 volt TEG output.
3.7.7 Digital Panel Meter: The digital panel meter consists of two subassemblies, the display portion (Figure 27, item D10) which is a light emitting diode display and the control portion (Figure 29, item F7) which conditions the voltages for the display portion.
The digital panel meter is a 3.5 digit auto-ranging meter. When the power switch is in the "Set
Up" position, the meter will show the Vset voltage. When the power switch is set to the "Run"
position, the meter will show the output voltage of the system. In addition when the "Meter
Select" switch is pressed the meter will show the output current flowing to the load.
The meter is powered directly by the power unit. When the TEG is first started, the panel
meter will not function until the TEG voltage reaches 4.5 volts.
3.8

Service
3.8.1 On Site Visits
1)

Drain the sediment bowl of the fuel regulator by opening the drain cock.

2)

Read and record the fuel pressure and the output of TEG pressure regulator. If a master fuel gauge is present, record this pressure.

3)

Notice if the normal light is lit. The lamp should glow steady (generator running). If
the lamp is out, check and replace the bulb. If the lamp is flashing, overload condition
exists. Trouble shoot the system.

4)

Read and record the output voltage and current.

5)

Visually check for loose components or hardware. Tighten any loose hardware and
connections.

NOTE:

No adjustment should be made to any devices, unless malfunctions were found and
corrected.

3.8.2 Annual Service


1)

Perform on site visit as above and record data.

2)

Check and record the power output of the generator. Switch the power switch to set
up position, allow approximately 10 minutes to stabilize. Read the Vset voltage, calculate the output power of the TEG, E2/R, using the precision load resistance (0.387
ohms). Record and compare with set up figures.

If power is within 5% of set up power then the unit is performing properly. If the power output exceeds this limit then troubleshoot the system.

Global Thermoelectric
27762 rev. 2

3-10

3.9

Field Troubleshooting
NOTE:

This generator has been designed for use in hazardous areas. If this unit is being
used in a hazardous area, no housings, junction boxes or fittings may be removed
or disconnected while unit is running. The field troubleshooting section assumes
that whenever a test, check or remedy requires that a housing, junction box or fitting be removed or opened that the generator is first turned OFF.

Whenever major work or repairs are required other than that called out in field troubleshooting:
1)

The generator or electronics assembly must be removed to a safe area. Or:

2)

The area in which the generator is being used must be rendered safe in accordance
with all regulations governing the operations area.

Global Thermoelectric
27762 rev. 2

3-11

FIELD TROUBLE SHOOTING


SYMPTOMS
Burner does not ignite.

CAUSE AND/OR REMEDY


No fuel:
Turn on fuel.
Adjust regulator.
No spark:
Listen for audible spark, if not present try manual ignition switch.
If spark is present, check the pressure switch and
pressure switch wiring.
If no spark is present check if electrode is gapped.
Check the battery. Replace if necessary.
Replace the high voltage ignition module.

If ignition occurs and unit continues to fire, but will not stabilize (sustained combustion) note the position of the air shutBurner does not remain ignited.
ters and adjust for sustained ignition. Reset the air shutters
when the unit warms up.
Burner does not remain ignited
when shut off valve button is
released.

Replace thermocouple.
Replace shut off valve.
Incorrect fuel adjustment, see section 2.10.

Output power or voltage low


(TEG in Set Up position).

Incorrect air adjustment, see section 2.9.


Dirty fuel filter, orifice, or intake flame arrestors.
Protective limiter faulty.

Output power or voltage high.

Incorrect fuel adjustment, see section 2.10.

Output power or voltage low


(TEG in Operate position).

If any problems are encountered with the power conditioner,


the generator or electronics assembly should be removed to
a safe area.

Global Thermoelectric
27762 rev. 2

3-12

3.9.1 Changing the Fuel Filter (Figure 20,


Figure 21)
If it is necessary to remove the fuel filter, the
complete fuel assembly must be removed.
1)

Shut off fuel, disconnect the fuel input at


point A.

2)

Disconnect the flexible fuel line at point


B.

3)

Remove the two nuts holding the regulator to the mounting bracket (point D).

4)

Remove the four socket cap screws from


the bottom of the regulator. Remove the
bottom, complete with the rubber gasket
(see Figure 22).

5)

Remove and inspect the filter, clean or


replace as required.

6)

Re-assemble in reverse order.

7)

Ensure that all joints are leak checked


prior to starting generator.

Figure 21 Removing Fuel System

Figure 22 Fuel Regulator

Global Thermoelectric
27762 rev. 2

3-13

3.9.2 Electronics Trouble Shooting

ELECTRONICS TROUBLE SHOOTING


SYMPTOM
TEG Normal light is dim.

CAUSE AND/OR REMEDY


The converter circuit is being overloaded.
Disconnect the load; the light should come on
steady. If steady, the problem is on the load side.
Trouble shoot the load.
If the light remains flashing, the problem is internal (electronics housing). The generator will have
to be moved to a safe area for testing, or make
area safe. Trouble shoot the electronics.

TEG Normal light is out, voltmeter reading is OK,


TEG is running.

TEG lamp burned out. Replace the lamp.


Lamp driver circuit is bad.
Possible short circuit condition, disconnect the
load. If the lamp lights OK and the voltmeter is
OK then trouble shoot the load.

TEG Normal light is out, voltmeter is out, TEG is


If the lamp does not light and the voltmeter does
running
not come on switch to "Set Up". If the voltmeter
reads 6 Volts or more there is probably an internal
short in the electronics housing. Trouble shoot
the electronics assembly.

Global Thermoelectric
27762 rev. 2

3-14

3.10

1120 TEG Parts Lists

Figure 23 1120 Parts Illustration


Item
A1

Part No.

Description

4100-05260
4100-05261
4100-05258
4100-05259

Fin
Fin
Fin
Fin

A3
A4
A5
A6

4500-02275
6100-02446
2514-20954
4100-07028

Drip Cap Assy


Burner Assy
Screw, Mach, P-H-P, 1/4-20 X 5/8, 316 SS
Cabinet Top Assy

A7
A8
A9
A10

3400-20828
4900-03323
4900-03322
2400-07336

Thermocouple, 24", K16RA-24, Soldered


Heat Shield, 1120 Meter
Cover, Digital Panel Meter
Bezel, Digital Panel Meter

1
1
1
1

A11
A12

2506-29606
4200-02405
4200-02406
2806-02394

Screw, Mach, P-H-P, 6-32 X 3/8, 316 SS


Orifice Assy, #7, Propane
Orifice Assy, #8, Natural Gas
Washer, Disc Spring, #8 SS

4
1
1
2

A2

A13

Global Thermoelectric
27762 rev. 2

Duct,
Duct,
Duct,
Duct,

Upper,
Upper,
Upper,
Upper,

QTY
Front
Back
Left Side
Right Side

1
1
1
1
1
1
28
1

3-15

3.10

1120 TEG Parts Lists (Contd)

Figure 23 1120 Parts Illustration


Item

Part No.

A14
A15
A16

2506-29603
4000-02460
4900-02311

Screw, Mach, P-H-P, 6-32 X 5/8, 316 SS


Air Shutter, Teflon
Ignitor Housing Assy

2
2
1

A17

6400-22383
2514-20955
2814-22024
2714-20952

Fuel System Assy, W/CF Regulator


Screw, Hex, HD, 1/4-20 X 3 1/2", 316 SS
Washer, Lock, 1/4, 316 SS
Nut, Hex, 1/4-20, 316 SS

1
2
2
2

A18
A19
A20

6200-21773
4200-05286
4100-02218
4100-02219

Cabinet Assy
Fuel Line Kit
Leg, Left
Leg, Right

1
1
1
1

Global Thermoelectric
27762 rev. 2

Description

QTY

3-16

3.11

Ignitor Detail

Figure 24 Ignitor Details


Item

Part No.

A21
A22
A23
A24

4900-07615
4000-02411
2538-39608
4900-02254

Conduit Assy, Electronics


Pressure Switch Boot
Screw, Hex. HD, 3/8 - 16 x 3/4, 316 SS
Mounting Bracket, Electronics Box

A25
A26
A27
A28

2838-22021
6300-05667
2538-23566
4900-02266

Washer, Lock, Spring, 3/8, 316 SS


Limiter Converter Assy
Screw, Cap, Hex-HD, 3/8-16 X 1 1/2, 316 SS
Mounting Rod, Burner

24
1
20
4

A29
A30
A31
A32

2756-21131
2514-24638
2508-24491
2808-23811

Nut, Hex, 5/16-18, 316 SS


Screw, Mach., Hex-HD, 1/4-20 x 3/8, 316 SS
Screw, Mach, P-H-P, 8-32 X 1/4, 316 SS
Washer, Lock Spring, #8, 316 SS

4
8
40
6

A33
A34
A35
A36

2814-22024
2714-20952
4100-02339
7900-08905

Washer, Lock Spring, 1/4, 316 SS


Nut, Hex, 1/4-20, 316 SS
Fin Duct, Lower
Power Unit

16
16
1
1

A37
A38
A39

4900-07625
4900-02032
3026-06362

Conduit Assy, Power Unit


Electrode Assy, Spark Ignition
Connector, 3/16-1/8, Nylon, NY-300-1-2

Global Thermoelectric
27762 rev. 2

Description

QTY
1
1
4
4

1
1
1
3-17

3.12

Burner Part List

Figure 25 Burner Parts


Item

Part No.

Description

QTY

B1
B2
B3
B4

4000-02278
4000-02301
4000-00701
4000-00693

Burner Back Assy


Insulation Support
Spacer, Insulation
Screen Holder

1
1
1
1

B5
B6
B7
B8

4000-00873
4000-00694
4000-02302
4000-02401

Screen, Burner
Insert Ring, Burner
Insulation Block
Venturi Tube Holder

1
1
1
1

B9
B10
B11
B12

4000-00971
2506-00479
4000-02389
4000-02454

Venturi
Screw, Set, Soc. HD, 6-32 X 1/8, SS
Burner Cover Assy
Flame Arrestor Assy, Air Intake

1
1
1
2

Global Thermoelectric
27762 rev. 2

3-18

3.12

Burner Part List (Contd)

Figure 25 Burner Parts


Item

Part No.

B13
B14
B15
B16

2710-00609
2810-00469
4000-02415
4000-05241

Nut, Hex, 10-32, SS


Washer, Int. Lock, #10, SS
Flame Arrestor Assy, Exhaust
Flame Arrestor Housing, Upper

2
2
1
1

B17
B18
B19

4000-02452
2514-02413
2814-00541

Exhaust Stack
Screw, Hex HD, 1/4-20 X 1.00, SS
Washer, Lock, Spring, 1/4, SS

1
8
8

Global Thermoelectric
27762 rev. 2

Description

QTY

3-19

3.13

Fuel System Parts List

Figure 26 Fuel System Parts


Item

Part No.

Description

QTY

C1
C2
C3
C4

3100-22362
3041-02359
3071-02357
3200-02350

Regulator, Fisher 67 CF, 0-20 PSI


Nipple, 1/4 NPT X 1.5 LG, SS
Tee, 1/4 NPT, SS
Gauge, Pressure, 0-15 PSI

1
2
1
1

C5
C6
C7
C8

3090-00176
3400-01429
3031-20071
4200-05286

Valve, Shut off, BASCO H19-TA3


Pressure Switch, H0BBS 78628
Elbow, 1/4 NPT X 1/4 Tube, SS
Fuel Line Kit

1
1
1
1

C9
C10
C11
C12

3400-20828
3031-02356
3041-02358
3011-02360

Thermocouple, 24", K16RA-24, Soldered


Elbow, Street, 1/4 NPT, SS
Nipple, 1/4 NPT X 3", SS
Adaptor, 1/4 NPT, SS

1
1
1
1

C13

4200-20067

Vent Tube Assy, 1120

Global Thermoelectric
27762 rev. 2

3-20

3.14

Conduit Assembly Parts List

Figure 27 Conduit Assembly Parts


Item

Part No.

Description

QTY

D1
D2
D3
D4

5216
2300-02428
2300-02163
3058-05222

Junction Box, 4 Outlet


Connector, Strain Relief, 1/2 NPT
Connector, 90 , 3/8 Conduit, 1/2 NPT
Plug, Close Up, 1/2 NPT, CUP-1

1
2
2
1

D5
D6
D7

2300-02168
2300-02168
2300-20156
2300-20155

Conduit, Liquid Tight Flex, 3/8"


Conduit, Liquid Tight Flex, 3/8"
Barrier Gland, 3/4 NPT
Reducer Bushing, 3/4" X 1/2", ALUM

22
10
2
2

D8
D9
D10
D11

4900-02456
4900-6372
4900-07266
2455

Cable Assembly
Ignitor Cable, Conduit Assy
Digital Panel Meter, Datel DMS-30PC-1-RH
Cable, 7 Conductor, Beldon 9537

1
1
1
44

Global Thermoelectric
27762 rev. 2

3-21

3.15

Ignitor Housing Assembly Parts List

Figure 28 Ignitor Housing Parts


Item

Part No.

Description

QTY

E1
E2
E3
E4

3088-02173
3048-02372
4900-02340
4900-05247

Union, 1/2", Alum, UL Class 1, Group D


Nipple, 1/2 NPT, Close, Alum
Holder Assy, Ignitor
Junction Box, 1 1/4 NPT, Class 1, Group D1

1
1
1

E5
E6
E7
E9

2400-06248
3026-06362
4900-02032
2706-21650

Ignitor Broad Assy


*Connector, 3/16-1/8, Nylon, NY-300-1-2
*Electrode Assy, Spark Ignitor
Nut, Hex, 6-32, SS, 1/4 Across Flats

1
1
1
2

2030-05205
2120-00137
2010-00204

Ground Cable, SI
Female Disconnect, DNF18-250Fib
Wire, 20AWG,Green, 6"
Terminal, Ring, 1/4 RED, PNF18-14R

1
1
1
1

3068-02379
3038-02376

Reducer, 1 1/4 X 3/4 NPT, ALUM


Connector, 90 , M-F, 3/4 NPT, ALUM

1
1

E10

E11
E12

*NOTE: Parts not included if ordering entire ignitor housing, must be ordered separately.
Global Thermoelectric
27762 rev. 2

3-22

3.16

Electronics box L/C Parts List

Figure 29 Electronic Box


Item

Part No.

Description

QTY

F1
F2
F3
F4

2400-02373
2400-27019
2400-06527
2400-02282

Switch, Push Button, Illuminated


Battery, 2V, 2.5 AH, D Size
Shunt, 10A, 50mV, Holloway Type SW w/base
Control Board, Spark Ignitor

1
1
1
1

F5
F6
F7
F8

2200-02418
2400-07329
2200-01815
2400-02374

Terminal Block, 7 Position


PCB, Voltmeter Control, LED
Terminal Block, 3 Pole, Heavy Duty
Actuator, Potentiometer Adjust

1
1
1
1

F9
F10

2400-02160
2400-07810

Switch, Push Button


Switch, CAM, BACO PR 26 225

1
1

Global Thermoelectric
27762 rev. 2

3-23

3.17

Electronics box Lid L/C Parts List

Figure 30 Electronic Box Lid


Item

Part No.

F11
F12
F13

2400-05317
2410-00114
2410-02183

PCB Assy, Limiter Converter, 220W


Resistor, 0.75 OHM, 50W, 1%
Resistor, 2.0 OHM, 50W, 1%

1
2
2

F14
F15
F16

4900-05350
2400-06181
2400-29529

Heat Sink, Limiter Converter


Potentiometer, 1 turn 2 KOhm, 2 Watt
LED, Green, BA9S-G, 28 Volt

1
1
1

Global Thermoelectric
27762 rev. 2

Description

QTY

3-24

APPENDIX

4.1

Gas Specifications
STANDARD SPECIFICATIONS FOR GASEOUS FUELS FOR TEGS
A.

Shall not contain sand, dust, gums, crude oil, impurities or other objectionable substances in quantities which are likely to clog fuel filters or regulators.

B.

Shall not have a hydrocarbon dew point in excess of 0C (32F) at the supply pressure.

C.

Shall not contain more than 115 mg/Sm3* (approx. 169 ppm) of H2S.

D.

Shall not contain more than 60 mg/Sm3* (approx. 88 ppm) of mercaptan sulphur.

E.

Shall Not contain more than 200 mg/Sm3* (approx. 294 ppm) of total sulphur.

F.

Shall not contain more than 2 1/2% by volume of CO2.

Note:

Generators can usually be adjusted to operate at reduced power on gas containing


up to 25% CO2).

G.

Shall not contain more than 120 mg/Sm3 (5 g/100 cu.ft.) of water vapour.

H.

Shall not contain more than 1% by volume of free oxygen.

I.

Shall have a gross heating value of not less than 28 mJ/m3 (6700 kCal/m3) (750
BTU/cu.ft.) and not more than 121 mJ/m3 (29000 kCal/m3) (3260 BTU/cu.ft.)

Note:
J.

Various orifices and fuel settings are available for Natural Gas, LPG (Propane),
Methane or Butane.
Shall not exceed 65C (150F) in temperature.

* Sm3 = Standard cubic meter of gas at 101.325 kPa at 15C.

Global Thermoelectric
27762 rev. 2

4-1

Global Thermoelectric
27762 rev. 2

4-2

1120 TEG Start Up Data Sheet


Date:
Site:
TEG Serial No:

1120 TEG Start Up Data Sheet

Data By:

Date:
Site:
TEG Serial No:
1

Time of sustained ignition


Time - minutes after ignition

10

20

30

40

Time of sustained ignition


Time - minutes after ignition

2
50

Data By:

10

60

20

30

40

50

60

Vset

Vset
3

Temp. -

Temp. -

Temp. - Present ambient at site

Temp. - Present ambient at site

Set Up Power -

Set Up Power -

Vset - required to obtain set up power see

Vset - required to obtain set up power see

Vset

- measured one hour after ignition

Vset

- measured one hour after ignition

Vset

Vset

max. ambient expected at site

see Figure 4

Figure 12

change necessary to obtain item 6

Vset. Item 6 minus Item 7

Fuel Pressure

10

Fuel Pressure

11

New Fuel Pressure

one hour after ignition

- Change necessary to
obtain Item 6 Vset.
- Item 9 plus

max. ambient expected at site

see Figure 4

Figure 12

change necessary to obtain item 6

Vset. Item 6 minus Item 7

Fuel Pressure

10

Fuel Pressure

11

New Fuel Pressure

one hour after ignition

- Change necessary to
obtain Item 6 Vset.
- Item 9 plus

Item 10

Time -

New Vset

13

Vset

measured 10 minutes after

fuel adjust for item 11

measured 10 minutes after fuel

adjust for item 11

14

Air Shutter Adjustment


ccw
cw

New Vset

16

Vset

Global Thermoelectric
27762 rev. 2

New Vset

13

Vset

- measured 10 minutes afte


air shutter adjustment

measured (final before applying

load)

measured 10 minutes after

fuel adjust for item 11

measured 10 minutes after fuel

adjust for item 11

14

Air Shutter Adjustment


ccw
cw

- of air shutter adjustment

15

of fuel pressure adjust

12

Air Shutter Direction


Time

Notes:

Time -

of fuel pressure adjust

12

Item 10

Air Shutter Direction


Time

- of air shutter adjustment

15

New Vset

16

Vset

- measured 10 minutes afte


air shutter adjustment

measured (final before applying

load)

Notes:

4-3

1120 TEG Start Up Data Sheet


Date:
Site:
TEG Serial No:

1120 TEG Start Up Data Sheet


Date:
Site:
TEG Serial No:

Data By:

Time of sustained ignition


Time - minutes after ignition

10

20

30

40

Time of sustained ignition


Time - minutes after ignition

2
50

Data By:

10

60

20

30

40

50

60

Vset

Vset
3

Temp. -

Temp. -

Temp. - Present ambient at site

Temp. - Present ambient at site

Set Up Power -

Set Up Power -

Vset - required to obtain set up power see

Vset - required to obtain set up power see

Vset

- measured one hour after ignition

Vset

- measured one hour after ignition

Vset

Vset

max. ambient expected at site

see Figure 4

Figure 12

change necessary to obtain item 6

Vset. Item 6 minus Item 7

Fuel Pressure

10

Fuel Pressure

11

New Fuel Pressure

one hour after ignition

- Change necessary to
obtain Item 6 Vset.
- Item 9 plus

max. ambient expected at site

see Figure 4

Figure 12

change necessary to obtain item 6

Vset. Item 6 minus Item 7

Fuel Pressure

10

Fuel Pressure

11

New Fuel Pressure

one hour after ignition

- Change necessary to
obtain Item 6 Vset.
- Item 9 plus
Item 10

Item 10

Time -

12

New Vset

13

Vset

14

Air Shutter Adjustment

measured 10 minutes after

fuel adjust for item 11

measured 10 minutes after fuel

adjust for item 11

ccw
cw

New Vset

16

Vset

Global Thermoelectric
27762 rev. 2

- measured 10 minutes afte


air shutter adjustment

measured (final before applying

load)

New Vset

13

Vset

14

Air Shutter Adjustment

measured 10 minutes after

fuel adjust for item 11

measured 10 minutes after fuel

adjust for item 11

ccw
cw

- of air shutter adjustment

15

of fuel pressure adjust

12

Air Shutter Direction


Time

Notes:

Time -

of fuel pressure adjust

Air Shutter Direction


Time

- of air shutter adjustment

15

New Vset

16

Vset

- measured 10 minutes afte


air shutter adjustment

measured (final before applying

load)

Notes:

4-4

4-5

Site:

Date

Global
Thermoelectric

Data By

Time
Ambient
Temp C
Fuel
Pressure

TEG Serial No:

1120 System Performance Log

Air Shutter
Vset
Volts
Set Up Power
Watts
Output Voltage
Conv/Limiter
Voltage
Customer Load
Amperage
Customer Load

Maintenance
Repair Notes

TEG Group NO:

4-6

Site:

Date

Global Thermoelectric
27762 rev. 2

Data By

Time
Ambient
Temp C
Fuel
Pressure

TEG Serial No:

1120 System Performance Log

Air Shutter
Vset
Volts
Set Up Power
Watts
Output Voltage
Conv/Limiter
Voltage
Customer Load
Amperage
Customer Load

Maintenance
Repair Notes

TEG Group NO:

Global Thermoelectric
27762 rev. 2

4-7

You might also like