Operations and Service Manual: Container Refrigeration
Operations and Service Manual: Container Refrigeration
Operations and Service Manual: Container Refrigeration
T-370 Rev F
OPERATIONS AND SERVICE
MANUAL
For
69NT40-601-100 to 199
i T-370
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–1
3.1 GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–1
3.1.1 Refrigeration Unit - Front Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–1
3.1.2 Fresh Air Makeup Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–1
3.1.3 Evaporator Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–2
3.1.4 Compressor and Flash Tank Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–3
3.1.5 Gas Cooler / Intercooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–6
3.1.6 Control Box Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–7
3.1.7 Communications Interface Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–7
3.1.8 Water-Cooled Condenser Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–8
3.2 REFRIGERATION SYSTEM DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–8
3.3 TORQUE REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–9
3.4 ELECTRICAL SYSTEM DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–10
3.5 SAFETY AND PROTECTIVE DEVICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–12
3.6 REFRIGERATION CIRCUIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–12
3.6.1 Standard Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–12
3.6.2 First Stage Discharge Port & Suction Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–13
3.6.3 Unloaded Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–13
3.6.4 Economized Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–13
3.6.5 Electronic Expansion Valve (EEV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–13
MICROPROCESSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–1
4.1 TEMPERATURE CONTROL MICROPROCESSOR SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . 4–1
4.1.1 Display Module and Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–1
4.1.2 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–3
4.2 CONTROLLER SOFTWARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–4
4.2.1 Configuration Variables (CnF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–4
4.2.2 Operational Software (Cd Function Codes) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–4
4.3 CONTROLLER SEQUENCE AND MODES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–4
4.3.1 System Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–5
4.3.2 Perishable Mode Temperature Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–5
4.3.3 Perishable Mode Cooling - Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–5
4.3.4 Perishable Mode Heating - Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–6
4.3.5 Perishable Mode Dehumidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–6
4.3.6 Perishable Dehumidification - Bulb Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–7
4.3.7 Frozen Mode Temperature Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–7
4.3.8 Frozen Mode Cooling - Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–8
4.3.9 Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–9
4.3.10 Defrost Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–9
4.3.11 Defrost Related Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–10
4.4 PROTECTION MODES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–10
4.4.1 Evaporator Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–10
4.4.2 Failure Action, Cd29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–10
4.4.3 Generator Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–11
4.4.4 Compressor High Temperature, Low Pressure Protection . . . . . . . . . . . . . . . . . . . . . . . . . 4–11
4.4.5 Compressor Internal Protector (IP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–11
4.5 CONTROLLER ALARMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–11
4.5.1 Displaying Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–11
T-370 ii
4.6 PRE-TRIP DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–12
4.6.1 Auto Test Operation from Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–12
4.6.2 Manual Test Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–13
4.6.3 Auto Test Operation from Serial Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–13
4.6.4 Terminating Pre-trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–13
4.6.5 Results Reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–13
4.7 DATACORDER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–13
4.7.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–13
4.7.2 DataCORDER Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–14
4.7.3 Sensor Configuration (dCF02) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–14
4.7.4 Logging Interval (dCF03) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–15
4.7.5 Thermistor Format (dCF04) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–15
4.7.6 Sampling Type (dCF05 & dCF06) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–15
4.7.7 Alarm Configuration (dCF07 - dCF10) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–16
4.7.8 DataCORDER Power Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–17
4.7.9 Pre-Trip Data Recording . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–17
4.7.10 DataCORDER Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–17
4.7.11 DataCORDER Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–18
4.7.12 ISO Trip Header . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–19
4.7.13 USDA Cold Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–19
4.7.14 USDA Cold Treatment Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–20
4.8 OPTIONAL FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–22
4.8.1 Automatic Cold Treatment (ACT) Cd51 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–22
4.8.2 Automatic Setpoint Change (ASC) Cd53 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–23
4.9 CONTROLLER CONFIGURATION VARIABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–24
4.10 CONTROLLER FUNCTION CODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–26
4.11 CONTROLLER ALARM INDICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–33
4.12 CONTROLLER PRE-TRIP TEST CODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–47
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–1
5.1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–1
5.2 CONNECT POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–1
5.2.1 Connection To 380/460 VAC Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–1
5.3 ADJUST FRESH AIR MAKEUP VENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–1
5.3.1 Upper Fresh Air Makeup Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–2
5.3.2 Vent Position Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–2
5.4 CONNECT WATER COOLED CONDENSER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–3
5.5 CONNECT REMOTE MONITORING RECEPTACLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–3
5.5.1 Starting the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–3
5.5.2 Stopping the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–3
5.6 START-UP INSPECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–4
5.6.1 Physical Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–4
5.6.2 Check Controller Function Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–4
5.6.3 DataCORDER Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–4
5.6.4 Complete Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–4
5.7 PRE-TRIP DIAGNOSIS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–4
5.7.1 Starting a Pre-Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–5
5.7.2 Displaying Pre-Trip Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–6
iii T-370
5.8 OBSERVE UNIT OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–6
5.8.1 Probe Diagnostic Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–6
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–1
6.1 UNIT WILL NOT START OR STARTS THEN STOPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–1
6.2 UNIT OPERATES LONG OR CONTINUOUSLY IN COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . 6–1
6.3 UNIT RUNS BUT HAS INSUFFICIENT COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–2
6.4 UNIT WILL NOT HEAT OR HAS INSUFFICIENT HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–2
6.5 UNIT WILL NOT TERMINATE HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–2
6.6 UNIT WILL NOT DEFROST PROPERLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–3
6.7 ABNORMAL PRESSURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–3
6.8 ABNORMAL NOISE OR VIBRATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–3
6.9 MICROPROCESSOR MALFUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–4
6.10 NO EVAPORATOR AIR FLOW OR RESTRICTED AIR FLOW . . . . . . . . . . . . . . . . . . . . . . . . . . 6–4
6.11 ELECTRONIC EXPANSION VALVE (EEV) MALFUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–4
6.12 HIGH PRESSURE EXPANSION VALVE (HPXV) MALFUNCTION . . . . . . . . . . . . . . . . . . . . . . . 6–5
6.13 ABNORMAL TEMPERATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–5
6.14 ABNORMAL CURRENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–5
6.15 FUSE F1 OR F2 BLOWN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–5
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–1
7.1 ANNUAL MAINTENANCE PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–1
7.2 SERVICE GAUGE SET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–1
7.2.1 Service Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–2
7.2.2 Connecting Service Gauges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–2
7.2.3 Removing Service Gauges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–3
7.2.4 Manually Opening Solenoid Valves and High Pressure Expansion Valve . . . . . . . . . . . . . . 7–3
7.2.5 Removing Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–3
7.2.6 Refrigerant Leak (Tightness) Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–4
7.2.7 Evacuation and Dehydration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–4
7.2.8 Charging, Vapor Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–5
7.3 COMPRESSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–8
7.3.1 Removal and Replacement of Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–8
7.4 O-RING INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–10
7.4.1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–10
7.4.2 Adding Loctite 55 Thread Sealing Cord . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–10
7.5 HIGH PRESSURE SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–11
7.5.1 Checking a High Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–11
7.5.2 Replacing a High Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–11
7.6 PRESSURE TRANSDUCER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–12
7.6.1 Replacing a Pressure Transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–12
7.7 PRESSURE RELIEF VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–12
7.7.1 Replacing a Pressure Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–12
7.8 GAS COOLER / INTERCOOLER COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–12
7.8.1 Gas Cooler Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–12
7.8.2 Gas Cooler Coil Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–12
7.9 GAS COOLER FAN AND MOTOR ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–13
7.10 FILTER DRIER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–13
7.11 EVAPORATOR COIL ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–14
7.11.1 Evaporator Coil Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–14
T-370 iv
7.12 EVAPORATOR HEATER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–14
7.12.1 Evaporator Heater Removal and Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–14
7.12.2 Megger Testing the Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–15
7.13 EVAPORATOR FAN AND MOTOR ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–16
7.13.1 Replacing the Evaporator Fan Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–17
7.13.2 Disassemble the Evaporator Fan Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–17
7.13.3 Assemble the Evaporator Fan Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–18
7.14 EVAPORATOR SECTION CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–18
7.15 ELECTRONIC EXPANSION VALVE (EEV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–19
7.15.1 Removing an EEV or HPXV: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–19
7.15.2 Installing an EEV or HPXV: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–19
7.16 HUMIDITY SENSOR (HS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–20
7.16.1 Checking the Operation of the Humidity Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–20
7.17 ECONOMIZER SOLENOID VALVE, UNLOADER SOLENOID VALVE . . . . . . . . . . . . . . . . . . . 7–21
7.17.1 Removing / Replacing the ESV or USV Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–22
7.17.2 Removing / Replacing the ESV or USV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–22
7.18 REMOVING / REPLACING THE FLASH TANK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–22
7.19 CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–23
7.19.1 Handling Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–23
7.19.2 Controller Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–24
7.19.3 Controller Programming Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–25
7.19.4 Removing and Installing a Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–27
7.19.5 Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–27
7.20 VARIABLE FREQUENCY DRIVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–28
7.20.1 Remove and Replace Variable Frequency Drive Cooling Fan . . . . . . . . . . . . . . . . . . . . . . 7–28
7.20.2 Variable Frequency Drive (VFD) Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–29
7.21 VENT POSITION SENSOR SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–32
7.21.1 Upper VPS Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–32
7.22 TEMPERATURE SENSOR SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–32
7.22.1 Ice Bath Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–32
7.22.2 Sensor Checkout Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–33
7.22.3 GDP Supply and Return Sensor Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–35
7.22.4 Sensor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–40
7.22.5 Sensor STS and SRS Re-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–41
7.22.6 Sensors RRS and RTS Re-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–41
7.22.7 Sensor DTS Re-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–42
7.22.8 Sensors ETS1 Re-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–42
7.22.9 Sensor, CPDS Re-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–42
7.23 TRANSDUCER SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–42
7.24 COMMUNICATIONS INTERFACE MODULE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . 7–43
7.25 MAINTENANCE OF PAINTED SURFACES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–44
7.26 TEMPERATURE / PRESSURE CHART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–44
7.27 BOLT TORQUE VALUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–47
ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS ........................................ 8–1
EU DECLARATION OF CONFORMITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9–1
INDEX .......................................................................... INDEX–1
v T-370
LIST OF ILLUSTRATIONS
FIGURE NUMBER Page
T-370 vi
Figure 7.15 Heater Arrangement ......................................................... 7–14
Figure 7.16 Evaporator Fan Assembly ..................................................... 7–17
Figure 7.17 HPXV Coil Boot ............................................................. 7–19
Figure 7.18 HPXV Valve Body Dimples .................................................... 7–19
Figure 7.19 Coil View of Economizer Solenoid Valve (ESV) .................................... 7–22
Figure 7.20 Controller Section of the Control Box ............................................ 7–24
Figure 7.21 VFD Fan Screws ............................................................ 7–28
Figure 7.22 VFD Fan Removal ........................................................... 7–28
Figure 7.23 VFD Phase Wiring ........................................................... 7–29
Figure 7.24 DataLINE - Probe Calibration .................................................. 7–37
Figure 7.25 DataLINE - Calibrate Sensors Button ............................................ 7–37
Figure 7.26 DataLINE - Enter Service Information ............................................ 7–38
Figure 7.27 Ice Bath ................................................................... 7–38
Figure 7.28 DataLINE - Start Cal Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–39
Figure 7.29 DataLINE - Calibration Results ................................................. 7–39
Figure 7.30 Sensor Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–40
Figure 7.31 Sensor and Cable Splice ...................................................... 7–40
Figure 7.32 Supply Sensor Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–41
Figure 7.33 Return Sensor Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–42
Figure 7.34 Evaporator Temperature Sensor Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–42
Figure 7.35 Open End Wrench ........................................................... 7–43
Figure 7.36 Communications Interface Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–44
Figure 8.1 Schematic Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8–1
Figure 8.2 Schematic Diagram - Standard Unit Configuration .................................... 8–2
Figure 8.3 Unit Wiring Diagram - Standard Unit Configuration Sheet 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . 8–3
Figure 8.4 Unit Wiring Diagram -Standard Unit Configuration - Sheet 2 of 2 ......................... 8–4
vii T-370
LIST OF TABLES
TABLE NUMBER Page
T-370 viii
SECTION 1
SAFETY SUMMARY
1.1 General Safety Notices
The following general safety notices supplement specific warnings and cautions appearing elsewhere in this
manual. They are recommended precautions that must be understood and applied during operation and
maintenance of the equipment covered herein. The general safety notices are presented in the following three
sections labeled: First Aid, Operating Precautions and Maintenance Precautions. A listing of the specific warnings
and cautions appearing elsewhere in the manual follows the general safety notices.
Keep hands, clothing and tools clear of the evaporator and gas cooler fans.
No work should be performed on the unit until all circuit breakers and start-stop switches are turned off, power
supply is disconnected, and Lock Out / Tag Out has been applied.
In case of severe vibration or unusual noise, stop the unit and investigate.
Beware of unannounced starting of the evaporator and gas cooler fans. Do not open the gas cooler fan grille or
evaporator access panels before turning power off, disconnecting and securing the power plug and performing the
Lock Out / Tag Out procedure at the end if the Safety Summary.
Be sure power is turned off before working on motors, controllers, solenoid valves and electrical control switches.
Lock Out / Tag Out the circuit breaker and power supply to prevent accidental energizing of circuit.
Do not bypass any electrical safety devices, e.g. bridging an overload, or using any sort of jumper wires. Problems
with the system should be diagnosed, and any necessary repairs performed by qualified service personnel.
When performing any arc welding on the unit or container, disconnect all wire harness connectors from the
modules in control boxes. Do not remove wire harness from the modules unless you are grounded to the unit frame
with a static safe wrist strap.
In case of electrical fire, open circuit switch and extinguish with CO2 (never use water).
! DANGER
DANGER - means an immediate hazard that WILL result in severe personal injury or death.
! WARNING
WARNING - means to warn against hazards or unsafe conditions that COULD result in severe
personal injury or death.
1–1 T-370
! CAUTION
CAUTION - means to warn against potential hazard or unsafe practice that could result in
minor personal injury, product or property damage.
NOTICE
NOTICE - means to warn against potential product or property damage.
The following statements are applicable to the refrigeration unit and appear elsewhere in this manual. These
recommended precautions must be understood and applied during operation and maintenance of the equipment
covered herein.
! DANGER
Only manifold gauge sets designed and manufactured for R-744 (CO2) are to be used on these
units.
! DANGER
There are no serviceable parts on the Pressure Relief Valve (PRV). Attempting to repair or alter
the PRV is not permitted. If the PRV has released pressure, the entire PRV must be replaced.
! DANGER
There are no serviceable parts on the flash tank. Attempting to repair the flash tank or welding
on the flash tank vessel is not permitted. If the flash tank should be damaged in any way the
entire flash tank must be replaced.
! WARNING
Beware of unannounced starting of the evaporator and gas cooler fans. The unit may cycle the
fans and compressor unexpectedly as control requirements dictate.
! WARNING
Make sure that the unit circuit breaker (CB-1) and the START-STOP switch (ST) are in the “O”
(OFF) position before connecting to any electrical power source.
! WARNING
Always turn OFF the unit circuit breaker (CB-1), disconnect main power supply, and perform
Lock Out / Tag Out before working on moving parts.
! WARNING
Make sure power to the unit is OFF and power plug disconnected before replacing the
compressor.
T-370 1–2
! WARNING
Before disassembly of the compressor, be sure to relieve the internal pressure very carefully
by slightly loosening the couplings to break the seal.
! WARNING
Do not use a nitrogen or CO2 cylinder without a pressure regulator. Do not use oxygen in or
near a refrigeration system as an explosion may occur.
! WARNING
Do not open the Gas Cooler fan grille before turning power OFF, disconnecting power plug,
and performing Lock Out / Tag Out procedure.
! WARNING
Always turn OFF the unit circuit breaker (CB-1) and disconnect main power supply before
working on moving parts.
! WARNING
Installation requires wiring to the main unit circuit breaker, CB-1. Make sure the power to the
unit is off and power plug disconnected before beginning installation.
! WARNING
Do not use in a potentially explosive atmosphere.
! WARNING
Do not operate unit near flammable gases.
! WARNING
Do not use unit for any other use other than intermodal refrigerated transportation.
! WARNING
Any technical modifications to the unit must be performed using authorized service personnel.
! CAUTION
Charge according to nameplate specifications to ensure optimal unit performance.
! CAUTION
Use only thick walled tubing.
1–3 T-370
! CAUTION
Do not remove wire harnesses from controller modules unless you are grounded to the unit
frame with a static safe wrist strap.
! CAUTION
Unplug all controller module wire harness connectors before performing arc welding on any
part of the container.
! CAUTION
Do not attempt to use an ML2i PC card in an ML3 equipped unit. The PC cards are physically
different and will result in damage to the controller.
! CAUTION
Pre-trip diagnostics should not be performed with critical temperature cargoes in the container.
! CAUTION
When PRE-TRIP key is pressed, economy, dehumidification and bulb mode will be deactivated. At
the completion of Pre-trip activity, economy, dehumidification and bulb mode must be reactivated.
! CAUTION
When a failure occurs during automatic testing, the unit will suspend operation awaiting
operator intervention.
! CAUTION
When Pre-trip test Auto 2 runs to completion without being interrupted, the unit will terminate
Pre-trip and display “Auto 2” “end.” The unit will suspend operation until the user depresses
the ENTER key.
! CAUTION
To prevent trapping liquid refrigerant in the manifold gauge set be sure that the set is isolated
from the system and pressure is released before disconnecting.
! CAUTION
Never use air or gases containing oxygen for leak testing or operating refrigerant
compressors. Pressurized mixtures of air or gases containing oxygen can lead to explosion.
! CAUTION
Opening the Manifold Gauge Valve wide open quickly can cause excessive noise and possible
loss of the system oil charge.
T-370 1–4
! CAUTION
Do not touch the filter drier to check for temperature difference while the unit is operating.
Refer to troubleshooting for when to replace the filter drier due to restriction.
! CAUTION
Unplug all module connectors before performing arc welding on any part of the container.
! CAUTION
The unit must be OFF whenever a programming card is inserted or removed from the controller
programming port.
! CAUTION
Use care when cutting wire ties to avoid nicking or cutting wires.
! CAUTION
Do not allow moisture to enter wire splice area as this may affect the sensor resistance.
! CAUTION
Variable Frequency Drive Electrical Hazard. After disconnecting from power supply, wait seven
minutes before servicing.
! CAUTION
Sound pressure level of 79dB(A) was measured at workstation.
! CAUTION
Operator needs to provide sufficient lighting when ambient light is low.
! CAUTION
Installation: Refrigeration unit must be inserted into the container so that all four flanges
contact the container at nearly the same time and no “wrenching” of the unit occurs. Inserting
the unit into the container while the unit remains tilted on forks so that one flange of the unit
hits hard against the container first can cause serious damage to the unit.
NOTICE
The NaturaLINE platform must use the green label controller only (part number 12-55011).
NOTICE
Compressor is shipped without oil in the compressor.
NOTICE
When installing service fittings and the suction pressure transducer, a new O-ring must
installed with each. See Section 7.4 for instructions on installing the O-rings.
1–5 T-370
1.6 Lockout / Tagout (LO/TO)
1. Shut down the unit by turning the START-STOP switch (SW) to the “O” (Off) position.
2. Ensure CB-1 (460V) circuit breaker is in the off position.
3. Disconnect, lock and tag the power plug using a plug clip or locking directly on the power cable (pic #1 & 2).
4. Remove and lock the battery connection (picture #3) for Genset units.
5. All employees working on the reefer must have their own personal lock in place.
6. Check that circuit−testing devices are working properly by using an energized test source.
7. Prior to servicing the unit, a check must be made with a “proximity voltage sensor” to ensure that the reefer
unit and the container body are not energized.
8. Verify the absence of electrical current or voltage with a circuit−testing device.
#1 #2 #3
T-370 1–6
SECTION 2
INTRODUCTION
2.1 Introduction
The Carrier Transicold model 69NT40-601-XXX series units are of lightweight aluminum frame construction,
designed to fit in the front of a container and serve as the container’s front wall.
They are one piece, self-contained, all electric units, which include cooling and heating systems to provide precise
temperature control.
The units are supplied with a complete charge of refrigerant R-744 (CO2) and compressor lubricating oil. Units are
ready for operation upon installation.
The base unit operates on nominal 380/460 volt, 3-phase, 50/60 hertz (Hz) power. Power for the control system is
provided by a transformer which steps the supply power down to 18 and 24 volts, single phase.
The controller is a Carrier Transicold Micro-Link 3 microprocessor. The controller will operate automatically to
select cooling, holding or heating as required to maintain the desired set point temperature within very close limits.
The controller has a keypad and display for viewing or changing operating parameters. The display is also
equipped with lights to indicate various modes of operation.
If a problem occurs, please refer to the information on this nameplate and make a note of the model and serial
number before calling for assistance. This information will be needed when you contact the technician so that he
may properly assist you.
Unit Nameplate
Carrier Transicold Pte Ltd
251 Jalan Ahmad Ibrahim
Singapore 629146
Item: Months: Warranty Period From Date In Service In Accordance With 62-02439-01
Except As Noted
Basic Unit: xx
Fan Motors: xx
Warranty Number: xxxxxxxxx
Compressor: xx
MADE IN SINGAPORE
PED label
Units LS MS HS
2–1 T-370
Figure 2.2 Unit Nameplate
Item: Months: Warranty Period From Date In Service In Accordance With 62-02439-01
Except As Noted
Basic Unit: xx
Fan Motors: xx
Warranty Number: xxxxxxxxx
Compressor: xx
MADE IN SINGAPORE
T-370 2–2
! CAUTION
Installation: Refrigeration unit must be inserted into the container so that all four flanges con-
tact the container at nearly the same time and no “wrenching” of the unit occurs. Inserting the
unit into the container while the unit remains tilted on forks so that one flange of the unit hits
hard against the container first can cause serious damage to the unit.
2.4.5 Compressor
The unit is fitted with a reciprocating compressor equipped with suction, discharge and mid-stage connections.
2.4.7 Evaporator
The Evaporator section contains an evaporator coil and heaters, two three-phase fan motors, and is equipped with
an Electronic Expansion Valve (EEV). Opening of an evaporator fan internal protector will shut down the unit.
2.4.10 Interrogator
Units that use the DataCORDER function are fitted with interrogator receptacles for connection of equipment to
download the recorded data. Two receptacles may be fitted; one is accessible from the front of the container and
the other is mounted inside the container (with the USDA receptacles).
2–3 T-370
2.5 Option Descriptions
Various options may be factory or field equipped to the base unit. These options are listed and described in the
following sub-paragraphs.
2.5.1 Battery
The refrigeration controller may be fitted with standard replaceable batteries or a rechargeable battery pack.
Rechargeable battery packs may be fitted in the standard or in a secure location.
2.5.2 Dehumidification
The unit may be fitted with a Humidity Sensor (HS). This sensor allows setting of a humidity set point in the
controller. In dehumidification mode, the controller will operate to reduce internal container moisture level.
2.5.3 USDA
The unit may be supplied with fittings for additional temperature probes, which allow recording of USDA Cold
Treatment data by the integral DataCORDER function of the Micro-Link refrigeration controller.
2.5.6 Handles
The unit may be equipped with handles to facilitate access to stacked containers. These fixed handles are located
on either side of the unit.
2.5.12 Labels
Safety instruction and function code listing labels differ, depending on the options installed. Labels available with
additional languages are listed in the parts list.
T-370 2–4
SECTION 3
DESCRIPTION
3.1 General Description
3.1.1 Refrigeration Unit - Front Section
The refrigeration unit is designed so that the majority of components are accessible from the front (see Figure 3.1).
3
17
6
16
7
15 8
10
14
13
12 11
1) Upper Fresh Air Makeup Vent Panel. Located 9) Unit Nameplate: Serial Number, Model Number
inside are Evaporator Fan #2, Defrost Temperature and Parts Identification Number (PID)
Sensor (DTS) 10) Power Cables & Plug location
2) Access Panel. Located inside are Evaporator Fan 11) Ambient Temperature Sensor (AMBS)
#1, Electronic Expansion Valve (EEV), Heat Termi- 12) Unloader Solenoid Valve (USV)
nation Thermostat (HTT)
13) Compressor
3) Fork Lift Pockets
14) Flash Tank
4) Control Box
15) Filter Drier
5) Unit Display
16) Gas Cooler Fan
6) Key Pad
17) TIR (Transports Internationaux Routiers) Sealing
7) Interrogator Connector (Front right) Provisions - Typical All Panels
8) Variable Frequency Drive (VFD)
-----
3–1 T-370
3.1.3 Evaporator Section
The two evaporator fans circulate air through the container by pulling air in from the top of the unit, directing the air
through the evaporator coil where it is cooled or heated, and then discharging the conditioned air at the bottom of
the unit.
Most evaporator components are accessible by removing the upper rear panel (as shown in Figure 3.2) or by
removing the evaporator fan access panels (see Figure 3.1).
3
15
2
1
14
13
12
11
10
5 6 7 8
9
T-370 3–2
3.1.4 Compressor and Flash Tank Section
Figure 3.3 Compressor and Flash Tank Section - PIDs lower than NT5010
11 12 3
13
17
15
8 14
10 19,20
6 5 4 2 1 16 18
3–3 T-370
Figure 3.4 Compressor and Flash Tank Section - PIDs NT5010 and higher
11 12 5 3
13 16
17
15
8
14
10
19, 20
18
7 6 4 2 1
T-370 3–4
Figure 3.5 Compressor Detail
12
8
15
6 1
14
5
2
13
11
4 3
15 6
14 1
5
11 2
3–5 T-370
3.1.5 Gas Cooler / Intercooler
The gas cooler / intercooler coil acts as a heat exchanger in which compressed refrigerant gas from the
compressor is lowered in temperature as it circulates through the coil tubes. The gas cooler / intercooler fan pulls
external, ambient air through all four sides of the coil, heat from the refrigerant is transferred to the air, and then the
warm air is discharged horizontally through the front of the fan grille.
5
8
6 7
T-370 3–6
3.1.6 Control Box Section
2 3 4
1 5 6 7
8
9
19
20
18 17 16 15 14 13 12 11 10
3–7 T-370
3.1.8 Water-Cooled Condenser Section
The water-cooled condenser section (Figure 3.8) consists of a water-cooled condenser, water couplings, and a
water pressure switch.
! CAUTION
Charge according to nameplate specifications to ensure optimal unit performance.
T-370 3–8
Unit Configuration Charge Requirements
3–9 T-370
Service Fittings / Service PIDs lower than NT5010
Valves
Suction Service Fitting 25.7-28.5 Nm (19-21 ft-lb)
T-370 3–10
Nominal Supply 380 VAC, 3 Phase, 460 VAC, 3 Phase,
50 Hz +/- 2.5% Hz 60 Hz +/- 2.5% Hz
Full Load Amps High Speed 1.07 0.9
Full Load Amps Low Speed 0.47 0.47
Nominal Horsepower High 0.36 0.63
Speed
Evaporator Fan Motors
Nominal Horsepower Low Speed 0.05 0.08
Rotations Per Minute High Speed 2850 rpm 3450 rpm
Rotations Per Minute Low Speed 1425 rpm 1725 rpm
Voltage 360 - 460 VAC 400 - 500 VAC
Bearing Lubrication Factory lubricated, additional grease not required
Rotation CW when viewed from shaft end
Control Circuit 7.5 amps (F3A, F3B)
Fuses
Controller / DataCORDER 5 amps (F1, F2)
Electrical Output 0.5 VDC to 4.5 VDC over 90 degree range
Vent Position Sensor
Supply Voltage 5 VDC +/- 10%
(VPS)
Supply Current 5 mA (typical)
Nominal Resistance @ 20° C 12.4 ohms +/- 5%
Solenoid Valve Coils (68°F)
(ESV/USV) 24 VAC
Maximum Current Draw 0.7 amps
Electronic Expansion Nominal Resistance 100 ohms A-B and C-D
Valve (EEV) Supply Voltage 12 VDC +/- 10%
30 ohms from Ground / Common 1 to 2, 3, 4 and
High Pressure Expansion Nominal Resistance 5 on the KE plug
Valve (HPXV)
Supply Voltage 12 VDC +/- 10%
Variable Frequency Drive
460 Volts Variable Frequency
(VFD)
Orange wire Power
Red wire Output
Brown wire Ground
Input voltage 5 VDC
Output voltage 0 to 3.3 VDC
Humidity Sensor (HS)
Output voltage readings verses relative humidity (RH) percentage:
30% 0.99 V
50% 1.65 V
70% 2.31 V
90% 2.97 V
Controller Setpoint Range -40 to +30°C (-40 to +86°F)
3–11 T-370
3.5 Safety and Protective Devices
Unit components are protected from damage by safety and protective devices listed in Table 3–1. These devices
monitor the unit operating conditions and open a set of electrical contacts when an unsafe condition occurs.
Open safety switch contacts on either or both of devices IP-CP or HPS will shut down the compressor.
Open safety switch contacts on device IP-CM will shut down the Gas Cooler fan motor.
The entire refrigeration unit will shut down if one of the following safety devices open: (a) circuit breaker(s); (b) fuse
(F3A / F3B, 7.5A); or (c) evaporator fan motor internal protector(s) - (IP).
Excessive current draw Circuit Breaker (CB-1) - Manual Trips at 25 amps (460 VAC)
Reset
Excessive current draw in the Fuse (F3A & F3B) 7.5 amp rating
control circuit
Excessive current draw by the Fuse (F1 & F2) 5 amp rating
controller Fuse
T-370 3–12
As refrigerant travels through the tubes in the Gas Cooler, ambient air flowing across the coil fins and tubes
removes heat from the refrigerant gas. As heat from the refrigerant is transferred to the ambient air, the refrigerant
gas cools and then passes through the Filter Drier. The Filter Drier ensures that the refrigerant is clean and dry.
The flow of refrigerant from the Filter Drier to the Flash Tank is regulated by the High Pressure Expansion Valve
(HPXV). The HPXV is controlled by the operating software for optimal performance and efficiency. As the
microprocessor receives temperature and pressure data, the HPXV stepper motor will open or close in order to
control and maintain maximum system efficiency. As refrigerant flows through the variable orifice of the HPXV, the
reduced pressure causes the refrigerant to flash (flash gas) while entering the Flash Tank. In the Flash Tank, vapor
and liquid are separated.
The liquid refrigerant from the Flash Tank continues through the liquid line to the Electronic Expansion Valve (EEV).
The EEV is used to control the superheat of the refrigerant leaving the Evaporator. As the microprocessor receives
suction pressure and temperature data, the microprocessor transmits electronic pulses to the EEV stepper motor
which opens or closes the variable valve orifice in order to control and maintain proper superheat. Superheat is
controlled to ensure that liquid refrigerant never enters the compressor.
The liquid refrigerant flows through the Evaporator, absorbing heat from the return air as the return air flows across
the fins and tubes of the Evaporator coil. As the liquid refrigerant in the Evaporator coil absorbs heat, the
refrigerant vaporizes, and the vapor flows through the suction port back to the compressor.
3–13 T-370
Figure 3.9 Refrigeration Circuit Schematic - PIDs lower than NT5010
17
16
6
18
11 15 14
23 4
21 20
5 3
10
19
1
13 7
12
23
9 8
22
T-370 3–14
Figure 3.10 Refrigeration Circuit Schematic - PIDs NT5010 and higher
17
16
6
18
14 8
21
22 19
11 15
23 4
20
5 3
10
1
12 13
23 7
3–15 T-370
Figure 3.11 Refrigeration Circuit Schematic (WCC) - PIDs lower than NT5010
19
18
8
20
13 17 16
25 4
23 22
5 3
12
21
1
15
14 9
11 10 6
24
7
T-370 3–16
Figure 3.12 Refrigeration Circuit Schematic (WCC) - PIDs NT5010 and higher
19
18
8
20
2
16 10 24
23
21
13 17
25
25 4
22
5 3
12
1
14 15
9
6
11
7
3–17 T-370
SECTION 4
MICROPROCESSOR
4.1 Temperature Control Microprocessor System
The temperature control Micro-Link 3 microprocessor system (see Figure 4.1) consists of a keypad, display module,
the control module (controller) and interconnecting wiring. The controller houses the temperature control software and
the DataCORDER software. The temperature control software functions to operate the unit components as required to
provide the desired cargo temperature and humidity. The DataCORDER software functions to record unit operating
parameters and cargo temperature parameters for future retrieval. Coverage of the temperature control software
begins with Section 4.2. Coverage of the DataCORDER software is provided in Section 4.7.
4–1 T-370
Figure 4.2 Display Module Figure 4.3 Keypad
CODE PRE
SELECT TRIP
MANUAL
ALARM
DEFROST/
LIST
INTERVAL
ENTER
RETURN C
SUPPLY F
BATTERY ALT
POWER MODE
T-370 4–2
4.1.2 Controller
! CAUTION
Do not remove wire harnesses from controller modules unless you are grounded to the unit
frame with a static safe wrist strap.
! CAUTION
Unplug all controller module wire harness connectors before performing arc welding on any
part of the container.
! CAUTION
Do not attempt to use an ML2i PC card in an ML3 equipped unit. The PC cards are physically
different and will result in damage to the controller.
NOTICE
Do not attempt to service the controller modules. Breaking the seal will void the warranty.
The Micro-Link 3 controller is a dual module microprocessor as shown in Figure 4.4. It is fitted with test points, har-
ness connectors and a software card programming port.
1 2 3 3 4 5 3 6 7 3 8 3
EN12830
CONTROLLER With
(7.5A)
(7.5A)
KB
OC1
(5A)
(5A)
F3A
F3B
KA
MC
MA
MB
CARRIER
KH
TP
F2
F1
4–3 T-370
4.2 Controller Software
The controller software is a custom designed program that is subdivided into configuration software and opera-
tional software. The controller software performs the following functions:
• Control supply or return air temperature to required limits, provide modulated refrigeration operation, econo-
mized operation, unloaded operation, electric heat control and defrost. Defrost is performed to clear buildup
of frost and ice in order to ensure proper air flow across the evaporator coil.
• Provide default independent readouts of setpoint and supply or return air temperatures.
• Provide ability to read and (if applicable) modify the configuration software variables (CnF, see Table 4–6),
operating software function codes (Cd, see Table 4–7) and alarm code (AL, see Table 4–8) indications.
• Provide a Pre-trip step by step checkout of refrigeration unit performance including: proper component oper-
ation, electronic and refrigeration control operation, heater operation, probe calibration, pressure limiting and
current limiting settings. See Section 4.12.
• Provide battery-powered ability to access or change selected codes and setpoint without AC power connected.
• Provide the ability to reprogram the software through the use of a memory card.
NOTICE
Compressor Contactor is always ON. The compressor speed is determined by specific operat-
ing conditions then the Micro will send commands to the Variable Frequency Drive.
General operation sequences for cooling, heating and defrost are provided in the following sub-paragraphs. Sche-
matic representation of controller action is provided in Figure 4.5.
The operational software responds to various inputs. These inputs come from the temperature and pressure sensors,
the temperature setpoint, the settings of the configuration variables and the function code assignments. The action
taken by the operational software will change if any one of the inputs change. Overall interaction of the inputs is
described as a “mode” of operation. The modes of operation include perishable (chill) mode and frozen mode.
Descriptions of the controller interaction and modes of operation are provided in the following sub paragraphs.
T-370 4–4
4.3.1 System Start Up
At start up, the controller logic checks for proper phase sequencing and compressor rotation. If incorrect sequenc-
ing is causing the compressor and three-phase evaporator and condenser fan motors to rotate in the wrong direc-
tion, the controller will energize or de-energize relay TCP as required (see Figure 8.2). Relay TCP will switch its
contacts, energizing or de-energizing relays PA and PB. Relay PA is wired to energize the circuits on L1, L2 and
L3. Relay PB is wired to energize the circuits on L3, L2, and L1, thus providing reverse rotation.
Upon start up, valves are opened to allow for equalization of system pressures. As the start up procedure transi-
tions to control mode, the evaporator and gas cooler fans cycle on, the Economizer Solenoid Valve (ESV) will ener-
gize, and the compressor and Variable Frequency Drive (VFD) ramp up.
During normal operation of the refrigeration system, system pressures and suction superheat are controlled by pre-
determined algorithms within the software. Temperature control is maintained by VFD speed and cycling of the gas
cooler fan (high / low / off).
NOTICE
In the Standard Perishable Mode of Operation, the evaporator fan motors run in high speed.
In Perishable Mode, the yellow SUPPLY indicator light is illuminated on the display module, the default reading on
the display window reflects the Supply Temperature Sensor (STS) reading, and the controller maintains supply air
temperature to setpoint. When supply air temperature reaches the In-Range Tolerance (Cd30), the green IN
RANGE light will energize.
The unit will be in Perishable Mode whenever setpoint is higher than -10°C (+14°F) [-5°C (+23°F) depends upon
the CnF26 (Heat Lockout Change Option) setting].
When operating in Perishable Mode, the microprocessor continuously controls the system in an effort to maintain
supply air temperature within the perishable limit of +/-0.25°C. In Perishable Mode, capacity reduction controls may
be implemented to ensure that the refrigeration system (compressor) does not shut down. Capacity reduction mea-
sures include modulation of the Gas Cooler Fan speed (high, low, off), closing of the ESV, opening of the USV, and
VFD speed reduction. After all of the capacity reduction measures have been implemented, if the temperature con-
tinues to fall below the control limit, the unit will turn off the refrigeration circuit (compressor) and run with evapora-
tor fans only. If the temperature continues to fall below setpoint, the unit will engage the heaters to maintain
temperature within the control band.
4–5 T-370
Figure 4.5 Controller Operation - Perishable Mode
+2.5qC
(+4.5qF)
Cooling, Cooling,
Unloaded Economized
+.25qC
Set
ï.25qC Cooling, Point
Air Circulation Unloaded
ï.25qC ï.25qC
ï.25qC
Air Circulation
ï.50qC
ï.50qC
Heating
Heating
Falling Rising
Temperature Temperature
T-370 4–6
If the above conditions are true, the evaporator fans will switch from high speed to low speed; evaporator fan
speed will switch every hour thereafter as long as all conditions are maintained. If any condition except item (1)
becomes false OR if the relative humidity sensed is 2% below the humidity setpoint, the high speed evaporator
fans will be energized.
During dehumidification, power is applied to the heaters; this added heat causes the controller to force the evapo-
rator temperature down in order to compensate for the increased load. The low coil temperature chills the return air
(below dew point), causing excess moisture to condensate on the coil. The water that is collected from the coil is
drained out of the system through the drain pan. The air is then reheated to setpoint, and the dehumidified supply
air is sent back to the container.
When the relative humidity sensed is 2% below the humidity setpoint, the controller will de-energize the heat relay,
however the controller will continue to cycle heating, when required, to maintain relative humidity below the
selected setpoint. If the dehumidification is terminated by a condition other than the sensed humidity level, e.g., an
out-of-range or compressor shutdown condition, the Heater Contactor (HR) is de-energized immediately.
To prevent rapid cycling and consequent Heater Contactor (HR) wear, two timers are activated during dehumidifi-
cation mode:
1. Heater Debounce Timer (five minutes) - The Heater Debounce Timer is started whenever the Heater Con-
tactor (HR) status is changed. The HR remains energized (or de-energized) for at least five minutes even if
the setpoint criteria are satisfied.
2. Out-of-Range Timer (five minutes) - The out-of-range timer is started to maintain heater operation for dehu-
midification during a temporary temperature out-of-range condition. If the supply air temperature remains
out of range for more than five minutes, the heaters will be de-energized to allow the system to recover. The
out-of-range timer starts as soon as the temperature exceeds the in-range tolerance value set by function
code Cd30.
4–7 T-370
Figure 4.6 Controller Operation - Frozen Mode
Frozen Mode
Controller Set Point at or BELOW ï10qC (+14qF),
or ï5qC (+23qF) optionally
+2.5qC
(+4.5qF)
Cooling,
Economized
+.25qC
Set Point
ï.25qC
Air Circulation
Falling Rising
T-370 4–8
4.3.9 Defrost
Defrost is initiated to remove ice buildup from the evaporator coil which can obstruct air flow and reduce the cooling
capacity of the unit. The defrost cycle may consist of up to three distinct operations depending upon the reason for
the defrost or model number configuration. The first is de-icing of the coil, the second is defrost due to a probe
check cycle and the third is a snap freeze process based on the unit model configuration.
• De-icing the coil consists of removing power to the cooling components (compressor, evaporator fans, and con-
denser fan), closing the EEV, and turning on the heaters, which are located below the evaporator coil. During
normal operation, de-icing will continue until temperatures indicate that the ice on the coil has been removed,
proper air flow has been restored, and the unit is ready to control temperature efficiently.
• If defrost was initiated by the probe check logic, then the Probe Check is carried out after the completion of the
defrost cycle. A Probe Check is initiated only when there is an inaccuracy between the controller temperature
sensors.
• Snap Freeze allows the system to cool for a period of time after de-icing, with the evaporator fans turned off and
is only carried out if configured by model number. Snap-Freeze allows for the removal of latent de-icing heat
from the evaporator coils, and freezes any remaining moisture that might otherwise be blown into the container.
For more information on Probe Check, see Section 5.8.
4–9 T-370
a. In Perishable Pull Down - Delta T increases to greater than 12°C, and 90 minutes of compressor run
time have been recorded.
b. In Perishable Steady State - A baseline Delta T is recorded following the first defrost cycle after steady
state conditions are reached, (the unit is cooling, and the evaporator fans and heaters must remain in a
stable state for a period of five minutes). Defrost will be initiated if Delta T increases to greater than 4°C
above the baseline, and 90 minutes of compressor run time have been recorded.
c. In Frozen Mode - Defrost will be initiated if Delta T increases to greater than 16°C and 90 minutes of
compressor run time have been recorded.
When defrost is initiated, the controller closes the EEV, opens contacts TC, TN and TE (or TV) to de-energize the
compressor, condenser fan and evaporator fans.
The controller then closes contacts TH to supply power to the heaters. The orange DEFROST light and heat light
are illuminated and the COOL light is also de-energized.
The EEV and DUV are independently operated by the microprocessor. Complete schematics and legends are
located in Section 9.
Defrost will terminate when the DTS reading rises above one of two model number configurable options selection,
either an upper setting of 25.6°C (78°F) which is default or lower setting of 18°C (64°F). When the DTS reading
rises to the configured setting, the de-icing operation is terminated.
DTS Failure
When the return air temperature falls to 7°C (45°F), the controller ensures that the defrost temperature sensor
(DTS) reading has dropped to 10°C or below. If it has not, it indicates a failed DTS. A DTS failure alarm is triggered
and the defrost mode is operated by the Return Temperature Sensor (RTS). Defrost will terminate after 1 hour.
If the DTS fails to reach is termination setting, the defrost terminate after 2 hours of operation.
Defrost Timer
If CnF23 is configured to “SAv” (save), then the value of the defrost interval timer will be saved at power down and
restored at power up. This option prevents short power interruptions from resetting an almost expired defrost inter-
val, and possibly delaying a needed defrost cycle. If the save option is not selected the defrost timer will re-initiate
and begin recounting.
If CnF11 is model number configured to OFF the operator will be allowed to choose “OFF” as a defrost interval
option.
If CnF64 is configured in the operator will be allowed to choose “PuLS” as a defrost interval option. For units oper-
ating with “PuLS” selected, defrost interval is determined by the unit temperature setpoint and the Evap Fan Puls-
ing Temp setting on the Trip Settings screen. When the unit temperature setpoint is equal to or less than the
Evaporator Fan Pulsing Temperature Setting, the defrost interval is set to 6 hours. Otherwise, the defrost interval is
determined using the Automatic Defrost Interval Determination logic. In either case, “PuLS” remains displayed in
this function select code.
If any Auto Pretrip sequence is initiated, the Defrost Interval setting will be set to “AUTO” unless CnF49 (OEM
Reset) is set to “Custom” AND CnF64 (Evaporator Fan Pulsing Logic) configuration variable is set to IN, in which
case the Defrost Interval setting on the Trip Settings screen will be set to “Pulse”.
If defrost does not terminate correctly and temperature reaches the setpoint of the Heat Termination Thermostat
(HTT) 54°C (130°F), the HTT will open to de-energize the heaters (AL059 & AL060). If the HTT does not open and
termination does not occur within two hours, the controller will terminate defrost. AL060 will be activated to inform
of a possible DTS failure.
T-370 4–10
4.4.3 Generator Protection
Function codes Cd31(Stagger Start, Offset Time) and Cd32 (Current Limit) may be operator set to control the start
up sequence of multiple units and operating current draw. The factory default allows on demand starting (no delay)
of units and normal current draw. See Table 4–7.
NOTICE
AL26 is active when all of the sensors are not responding. Check the connector at the back of
the controller; if it is loose or unplugged, reconnect it, then run a Pre-trip test P5 to clear AL26.
4–11 T-370
4.6 Pre-Trip Diagnostics
Pre-trip Diagnostics is an independent mode that suspends normal Control Mode activities to verify system functional-
ity by running a series of individual tests. The tests can be run in Auto Mode, which automatically performs a pre pro-
grammed sequence of tests, or Manual Mode, which allows the operator to select and run any of the tests individually.
A description of each individual Pre-trip test can be found in Section 4.12. Detailed operating instructions are pro-
vided in Section 5.7.
! CAUTION
Pre-trip diagnostics should not be performed with critical temperature cargoes in the container.
! CAUTION
When PRE-TRIP key is pressed, economy, dehumidification and bulb mode will be deactivated. At
the completion of Pre-trip activity, economy, dehumidification and bulb mode must be reactivated.
Pre-trip testing is initiated by pressing the PRE-TRIP key. This causes “SeLCt PrtrP” to be displayed for five seconds
or until an Arrow key is pressed. Pressing an Arrow key opens the test selection menu. Scroll through the menu with
the Arrow keys and then press the ENTER key to start the indicated test sequence or individual test.
Selecting “P rSLts” and pressing the ENTER key displays the results of all Pre-trip sub-tests. The results are dis-
played as “PASS” or “FAIL” for all tests run to completion since power on, and displayed as “-----” for tests not run.
During selection mode, failure to press either an Arrow key or ENTER key for 5 seconds will return the system to its
default display, and normal operating mode.
There are two Auto Mode test sequences:
• Short Pre-trip Sequence tests most functions, sensors, and system components. The Short Sequence
does not test the high pressure switch, heater performance, or cooling performance, due to their duration.
• Long Pre-trip Sequence includes all of the Short Sequence Tests, as well as tests for the high pressure
switch, heater performance, and cooling performance. The Long Sequence is only available if enabled by
configuration. Units configured for the Long Sequence can run either the Short Sequence or the Long
Sequence.
Manual Mode allows individual Pre-trip tests to be run one at a time, giving operators the ability to test individual
system components.
Pre-trip diagnostics may also be initiated via communication; however individual Manual Mode tests can only be
initiated at the keypad.
While a Pre-trip test is running, PX-X will be displayed on the left, where the X’s indicate the test number and sub-
test. The right display will show a countdown timer in minutes and seconds. During the Long Sequence, various
relevant temperature and pressure information will replace the countdown timer on the right display.
T-370 4–12
4.6.2 Manual Test Operation
Individually selected Pre-trip tests, other than the LED / Display test (P0-0), allow the operator to verify the func-
tionality of an individual component. At the conclusion of the selected test, “PASS” or “FAIL” will be displayed. Upon
failure, the SUPPLY and RETURN LED’s will flash on alternately. This message will remain displayed for up to
three minutes, in which time the operator may select another test. If three minutes expires, the system will termi-
nate Pre-trip and return to control mode operation. Following any individually selected Pre-trip test, all outputs will
be de-energized.
4.7 DataCORDER
4.7.1 Description
Carrier Transicold “DataCORDER” software is integrated into the controller and serves to eliminate the tempera-
ture recorder and paper chart. DataCORDER functions may be accessed by keypad selections and viewed on the
display module. The unit is also fitted with interrogation connections (see Figure 4.1) which may be used with the
Carrier Transicold Data Reader to download data. A computer with Carrier Transicold DataLINE software may also
be used to download data and configure settings. The DataCORDER consists of:
Configuration Software
Operational Software
Data Storage Memory
Real Time Clock (with internal battery backup)
Six Thermistor Inputs
Interrogation Connections
Power Supply (battery pack)
Operational Software
The Operational Software reads and records inputs from the operational components. How the component infor-
mation is recorded and stored is determined the DataCORDER configurations. The values of these components
can be viewed through the DataCORDER function codes. To access the function codes, do the following:
2. Press an Arrow key until the left window displays the desired code number. The right window will display the
value of this item for five seconds before returning to the normal display mode.
3. If a longer display time is desired, press the ENTER key to extend the display time to five minutes.
Configurations
The recording and alarm functions of the DataCORDER based on the configurations. Reprogramming to the factory
installed configuration is achieved via a configuration card. Changes to the unit DataCORDER configuration may be
made using the DataLINE interrogation software. A listing of the configuration variables is provided in Table 4–3.
Descriptions of DataCORDER operation for each variable setting are provided in the following paragraphs.
Standard Mode
In Standard Mode, the user may configure the DataCORDER to record data using one of seven standard configu-
rations. The seven standard configuration variables, with their descriptions, are listed in Table 4–3. The inputs of
the six thermistors (supply, return, USDA #1, #2, #3 and cargo probe) and the Humidity Sensor (HS) input will be
generated by the DataCORDER.
T-370 4–14
NOTICE
The DataCORDER software uses the Supply and Return Recorder Sensors (SRS, RRS). The
temperature control software uses the Supply and Return Temperature Sensors (STS, RTS).
Generic Mode
Generic Mode allows user selection of the network data points to be recorded. The user may select up to a total of
eight data points for recording. A list of data points available for recording follows. Changing the configuration to
generic and selecting which data points to record may be done using the Carrier Transicold Data Retrieval Program.
1. Control mode
2. Control temperature
3. Frequency
4. Humidity
5. Phase A current
6. Phase B current
7. Phase C current
8. Main voltage
9. Evaporator Expansion Valve percentage
10. Discrete outputs (Bit mapped - require special handling if used)
11. Discrete inputs (Bit mapped - require special handling if used)
12. Ambient Temperature Sensor (AMBS)
13. Evaporator Temperature Sensor (ETS)
14. Compressor Discharge Sensor (CPDS)
15. Return Temperature Sensor (RTS)
16. Supply Temperature Sensor (STS)
17. Defrost Temperature Sensor (DTS)
18. Discharge Pressure Transducer (DPT)
19. Suction Pressure Transducer (SPT)
20. Flash Tank Pressure Transducer (FPT)
21. Vent Position Sensor (VPS)
4–15 T-370
4.7.7 Alarm Configuration (dCF07 - dCF10)
The USDA and cargo probe alarms may be configured to OFF, ON or AUTO.
If a probe alarm is configured to OFF, the alarm for this probe is always disabled.
If a probe alarm is configured to ON, the associated alarm is always enabled.
If the probes are configured to AUTO, they act as a group. This function is designed to assist users who keep their
DataCORDER configured for USDA recording, but do not install the probes for every trip. If all the probes are dis-
connected, no alarms are activated. As soon as one of the probes is installed, all of the alarms are enabled and the
remaining probes that are not installed will give active alarm indications.
T-370 4–16
4.7.8 DataCORDER Power Up
The DataCORDER may be powered up in any one of four ways:
a. Normal AC power: The DataCORDER is powered up when the unit is turned on via the stop-start switch.
b. Controller DC battery pack power: If a battery pack is installed, the DataCORDER will power up for commu-
nication when an interrogation cable is plugged into an interrogation receptacle.
c. External DC battery pack power: A 12 volt battery pack may also be plugged into the back of the interroga-
tion cable, which is then plugged into an interrogation port. No controller battery pack is required with this
method.
d. Real Time Clock demand: If the DataCORDER is equipped with a charged battery pack and AC power is not
present, the DataCORDER will power up when the real time clock indicates that a data recording should
take place. When the DataCORDER is finished recording, it will power down.
During DataCORDER power-up, while using battery-pack power, the controller will perform a hardware voltage
check on the battery. If the hardware check passes, the controller will energize and perform a software battery volt-
age check before DataCORDER logging. If either test fails, the real time clock battery power-up will be disabled
until the next AC power cycle. Further DataCORDER temperature logging will be prohibited until that time.
An alarm will be generated when the battery voltage transitions from good to bad indicating that the battery pack
needs recharging. If the alarm condition persists for more than 24 hours on continuous AC power, the battery pack
needs replacement.
DataBANK Card
The DataBANK™ card is a PCMCIA card that interfaces with the controller through the programming slot and can
download the data at a much faster rate compared to the PC or DataReader. Files downloaded to DataBANK card
files are accessible through an Omni PC Card Drive. The files can then be viewed using the DataLINE software.
DataLINE Software
DataLINE software for a personal computer is supplied on both floppy disks and CD. This software allows interroga-
tion, configuration variable assignment, screen view of the data, hard copy report generation, cold treatment probe cal-
ibration and file management. Refer to Data Retrieval manual 62-10629 for a more detailed explanation of the
DataLINE interrogation software. The DataLINE manual may be found on the internet at www.container.carrier.com.
4–17 T-370
4.7.11 DataCORDER Alarms
The alarm display is an independent DataCORDER function. If an operating parameter is outside of the expected
range or a component does not return the correct values to the DataCORDER, an alarm is generated. The Data-
CORDER contains a buffer of up to eight alarms. A listing of the DataCORDER alarms is provided in Table 4–5.
See Section 4.7.7 for configuration information.
T-370 4–18
Table 4–5 DataCORDER Alarm Indications
Code Title Description
dAL86 RTC Battery Low The real time clock (RTC) backup battery is too low to adequately
maintain the RTC reading.
A real time clock failure is critical to the operation of the unit. If this alarm
occurs, replace the RTC battery at the next available opportunity. After
replacing the battery the following actions are required:
Update the RTC setting
• Update the unit’s software configuration
• Update the operational software
• Update all user selectable function code settings (defrost, set-
point, etc)
dAL87 RTC Failure An invalid time has been detected. Either the DataCORDER run time
hour and minute have not changed at the start of the hour, or the real
time clock (RTC) time has gained or lost more than 2 minutes in the
hour. This situation may be corrected by cycling the power, setting the
clock or meeting the above criteria for an hour.
dAL88 DataCORDER EEPROM A write of a critical DataCORDER item to Persistent Memory Block A
Failure location has failed after a retry.
dAL89 Flash Memory Error An error has been detected in the process of writing daily data to
the non-volatile FLASH memory.
dAL90 Future Expansion This alarm is for future expansion, and is not in use at this time.
dAL91 Alarm List Full The DataCORDER alarm queue is determined to be full (eight alarms).
4–19 T-370
The standard DataCORDER report displays the supply and return air temperatures. The cold treatment report dis-
plays USDA #1, #2, #3 and the supply and return air temperatures. Cold treatment recording is backed up by a bat-
tery so recording can continue if AC power is lost.
USDA/ Message Trip Comment
A special feature in DataLINE allows the user to enter a USDA (or other) message in the header of a data report.
The maximum message length is 78 characters. Only one message will be recorded per day.
4.7.14 USDA Cold Treatment Procedure
If configured for USDA probes, the following is a summary of the steps required to initiate a USDA Cold Treat-
ment. Refer to the DataLINE User manual 62-10629 for more details.
1. Ensure the DataCORDER is configured as follows:
a. DataCORDER is configured for USDA probes, and logging interval set for 60 minutes.
b. Sensor is set to “2 Averaged 3-USDA.”
c. The resolution is set to “Normal.”
Figure 4.7 DataCorder Configuration Screen
2. Calibrate the three USDA probes by ice bathing the probes and performing the calibration function with the
DataLINE. This calibration procedure generates the probe offsets which are stored in the controller and
applied to the USDA sensors for use in generating sensor type reports. See Figure 4.8.
Figure 4.8 DataCorder Probe Calibration Screen
T-370 4–20
3. Pre-cool the container to the treatment temperature or below.
4. Install the DataCORDER module battery pack (if not already installed).
5. Place the three probes. Refer to USDA Treatment Manual for directions on placement of probes in fruit and
probe locations in container.
Sensor 1 Place the first sensor, labeled USDA1, in a box at the top of the stack of the fruit nearest
to the air return intake.
Sensor 2 Place the second sensor, labeled USDA2, slightly aft of the middle of the container,
halfway between the top and bottom of the stack.
Sensor 3 Place the third sensor, labeled USDA3, one pallet stack in from the doors of the
container, halfway between the top and bottom of the stack.
6. To initiate USDA recording, connect the personal computer and Enter ISO header information using the
DataLINE software. See Figure 4.9.
a. Enter ISO header information.
b. Enter a trip comment if desired.
c. Using the System Tools screen in the DataLINE software perform a “trip start.” See Figure 4.10.
4–21 T-370
4.8 Optional Features
4.8.1 Automatic Cold Treatment (ACT) Cd51
Cold Treatment has been employed as an effective post-harvest method for the control of Mediterranean and cer-
tain other tropical fruit flies. Exposing infested fruit to temperatures of 2.2°C (3.6°F) or below for specific time peri-
ods results in the mortality of various life stages for this group of insects.
Automated Cold Treatment (ACT) in the Carrier Transicold unit is a method to simplify the task of completing cold
treatment by automating the process of changing the setpoints. ACT is set up through function code Cd51. Refer to
Function Code table in this manual for Cd51 menu processing and displays.
NOTE
ACT, setup with Cd51, and Automatic Setpoint Change (ASC), setup with Cd53, will not work simulta-
neously. Setting one will deactivate the other.
5. “trEAt" is now displayed in the left display and the right will be flashing the last setting (shown as XX.X°C).
Use the Arrow keys to select the desired cold treatment setpoint and press the ENTER key.
NOTE
"trEAt" is the maximum value that the USDA probes need to remain below, to pass the Cold Treatment
protocol. For instance, if the treat value is set at 35.0°F (1.7°C) then the USDA probe temperatures
must remain below 35.0°F (1.7°C) to pass.
6. "dAyS" is now displayed in the left display and the right will be flashing. Use the Arrow keys to select the
desired days for cold treatment and press the ENTER key.
7. "ProbE" is now displayed in the left display and the right will display the probe numbers that are connected.
Press the ENTER key. For instance, if "1234" is displayed, then all four of the probes are connected.
T-370 4–22
8. "SPnEW" is now displayed in the left display and the right will be flashing. Use the Arrow keys to select the
desired setpoint after the cold treatment process has successfully completed and press the ENTER key.
This would be the final temperature prior to the delivery of the cargo.
9. Cd51 is now displayed in the left display and the right will display days / hours remaining in cold treatment.
10. The unit will start to countdown once all detected USDA probes have reached the specified cold treatment
temperature. The cold treatment process will continue until the specified number of days is reached. During
operation, Cd51 will show the number of days and hours remaining in the cold treatment.
NOTE
Once the cold treatment process has been initiated, setpoint change via the keypad is disabled.
11. While the unit is operating in ACT mode, the left hand display will alternate between "COLd" and setpoint.
The right hand display will alternate between "trEAt" and the cargo temperature. Once the treatment time
has been completed, the setpoint temperature will increase to the "SPnEW" setting chosen in step 8.
12. When the cold treatment process is complete, the "SPnEW" setpoint will be displayed in the left hand dis-
play and cargo temperature in the right hand display, alternating with "COLd" "Done". "COLd" "Done" will
continue to alternate with the setpoint and cargo temperature until ACT is turned off.
4–23 T-370
4. Select the desired number of setpoint changes (nSC) by scrolling through the available “flashing” options (1
– 6) in the right display, then press the ENTER key.
5. Select the initial setpoint: With (SP 0) in the left display, select by scrolling to the desired “flashing” setpoint
in the right display and press ENTER.
6. Select the days desired for initial setpoint (SP 0): With (DAY 0) in the left display, select by scrolling to the
desired “flashing” days (1 to 99) in the right display and press ENTER.
7. Select the next setpoint (SP 1): With (SP 1) in the left display, select by scrolling to the desired “flashing” set-
point in the right display and press ENTER.
8. Continue to select each additional setpoint.
9. Select a final setpoint (SP x): With (SP x) in the left display, select by scrolling to the desired “flashing” set-
point in the right display and press ENTER.
While the unit is operating in ASC mode, the left hand display will alternate between current unit setpoint and
“ASC”. The right hand display will alternate between current control temperature and “ACtvE”. The user can deter-
mine the amount of time left at the current setpoint by selecting Cd53. The amount of time left will be displayed in
the right display (XX (days) / XX (hours). By sequentially pressing ENTER, set parameters can be viewed.
At completion of ASC mode, the left hand display will alternate between current unit setpoint “ASC”. The right hand
display will alternate between current control temperature and “Done”.
The display will remain this way until ASC is turned off. The user can determine the date of completion by selecting
Cd53. With (done) in the left display, the date of completion will be displayed in the right display (Month / Day).
ASC can be manually turned off by selecting Cd53, scrolling to “Off” and pressing the ENTER key.
ACS will be automatically turned off after three days without power, or if a Pre-trip is initiated.
ACS (Cd53) will work independently of Automatic Cold Treatment (ACT) (Cd51). Setting one deactivates the other.
T-370 4–24
Table 4–6 Controller Configuration Variables
Config Title
CnF02 Evaporator Fan Speed
CnF03 Control Sensors
CnF04 Dehumidification Mode
CnF08 Single Phase / 3-Phase Evaporator Fan Motor
CnF09 Refrigerant Selection
CnF11 Defrost “Off” Selection
CnF15 Discharge Temperature Sensor
CnF16 DataCORDER Present
CnF17 Discharge Pressure Sensor
CnF18 Heater
CnF20 Suction Pressure Sensor
CnF22 Economy Mode Option
CnF23 Defrost Interval Timer Save Option
CnF24 Advanced Pre-trip Enhanced Test Series Option
CnF25 Pre-trip Test Points / Results Recording Option
CnF26 Heat Lockout Change Option
CnF27 Suction Temperature Display Option
CnF28 Bulb Mode Option
CnF31 Probe Check Option
CnF32 Single Evaporator Fan Option
CnF33 Snap Freeze Option
CnF34 Degree Celsius Lockout Option
CnF37 Electronic Temperature Recorder
CnF41 Lower DTT Setting
CnF44 eAutoFresh Enabled
CnF45 Low Humidity Enabled
CnF47 Fresh Air Vent Position Sensor
CnF49 DataCORDER Configuration Restore
CnF50 Enhanced Bulb Mode Selection
CnF51 Timed Defrost Disable
CnF52 Oil Return Algorithm
CnF53 Water Cool Oil Return Logic
CnF55 TXV Boost Relay
CnF56 TXV Boost Circuit
CnF59 Electronic Expansion Valve
CnF60 Compressor-Cycle Perishable Cooling
CnF61 ACT ASC Control Enable
CnF62 Extended Temperature Control Enable
CnF63 QUEST Pre-trip / TripWise Default State
4–25 T-370
4.10 Controller Function Codes
NOTICE
If the function is not applicable, the display will read “-----”
Display Only Functions
Cd01 VFD (%) This is the percent capacity that the VFD is currently running at ranging from
0 - 100%. Therefore, this is the speed of the compressor as a percentage.
Cd03 VFD Status This is the current feedback value from the VFD. This code will display output
current (Amperes) by default.
Press the ENTER key to take the interface down into a selection menu.
The arrow keys will allow the operator to cycle forwards and backwards
through the following VFD-related quantities:
“CUr” (current draw in amps): x.x ranging from 0 to 99.9
“PEr” (speed of compressor as %): x ranging from 0 to 100
POW (power draw displayed in kilowatts): x.x ranging from 0.0 to 99.9
Press the ENTER key again to cause the selected quantity to be pulled up as
default, in future code select operations.
Press the CODE SELECT key in this selection menu to cancel the current
selection activity, and ascend into the main code selection menu.
Cd04 Line Current, The current is measured on three legs.
Phase A The current measured is used for control and diagnostic purposes.
For control processing, the highest of the Phase A and B current values is
Cd05 Line Current, used for current limiting purposes.
Phase B Phase C is used for compressor current draw measurement.
For diagnostic processing, the current draws are used to monitor component
generalization.
Cd06 Line Current,
Whenever a heater or a motor is turned ON or OFF, the current draw
Phase C
increase / decrease for that activity is measured.
The current draw is then tested to determine if it falls within the expected
range of values for the component.
Failure of this test will result in a Pre-trip failure or a control alarm indication.
Cd07 Mains Power Voltage The main supply voltage is displayed.
Cd08 Mains Power Frequency The value of the main power frequency is displayed in Hertz. The frequency
displayed will be halved if either fuse F1 or F2 is bad (alarm code AL21).
Cd09 Ambient Air The ambient sensor reading is displayed.
Temperature
Cd10 Evaporator Refrigerant The evaporator temperature of refrigerant measured leaving the evaporator.
Temperature (ETS)
Cd11 Compressor Discharge The compressor discharge temperature is displayed in °C or (°F).
Temperature (CPDS)
Cd12 Compressor Suction Bar (°C) presented with decimal. PSI (°F) no decimal.
Port Pressure (SPT)
Cd13 Flash Tank Pressure Bar (°C) presented with decimal. PSI (°F) no decimal.
(FPT)
Cd14 Compressor Discharge Bar (°C) presented with decimal. PSI (°F) no decimal.
Pressure (DPT)
T-370 4–26
Table 4–7 Controller Function Codes
Code Title Description
Cd15 Unloader The status of the valve is displayed (“OPEn” − “CLOSE”).
Cd16 Compressor Motor Hour This code displays the compressor motor hours. Unit run time can be viewed
Meter, Unit Run Time by pressing the ENTER key while in Cd16. Total hours are recorded in
Hour Meter increments of 10 hours (i.e., 3000 hours is displayed as 300).
Compressor Motor Hour Meter display can be reset to 0 by pressing and
holding the ENTER key for 5 seconds. The Unit Run Time Hour Meter cannot
be reset using this code.
Cd17 Relative Humidity % Humidity Sensor (HS) reading is displayed. This code displays the relative
humidity, as a percent value.
Cd18 Software Revision The software revision number is displayed.
Number
Cd19 Battery Check Request battery test and display results. After selecting Cd19, press the
ENTER key to run the battery test. “——“, “btESt”, “PASS”, “”LOW”, “FAIL”.
Press and hold the ALT key for 2 seconds, then press the ENTER key with
ALT key still held down to clear the “Chargeable Battery Required” flag and
then the test is run. If ENTER is not pressed in 5 seconds, the controller
returns to display the setpoint.
Cd20 Container Unit Model This code displays the model for which the controller is configured. (i.e.,
Number / Configuration 69NT40-601-001 the display will show 01001. The model number for the unit
is listed on the Unit Nameplate, see Figure 2.1.
Cd21 Capacity Mode: Displays the current mode of operation “Unloaded, Standard, Economized,”
Unloaded, Standard, the mode of operation will be displayed as (“unld”, “Std”, “Econ”).
Economized
Cd22 Compressor Run State Displays the current compressor run state (“OFF”, “ON”).
Cd23 Evaporator Fan State Displays the current evaporator fan state (“OFF”, “LO”, “HI”).
Cd25 Time Remaining Until This code displays the time remaining until the unit goes into defrost (in
Defrost tenths of an hour). This value is based on actual accumulated compressor
running time.
Cd26 Defrost Termination Defrost Temperature Sensor reading is displayed.
Sensor Temperature
Configurable Functions
NOTICE
Function codes Cd27 through Cd37 are user-selectable functions. The operator can change the
value of these functions to meet the operational needs of the container.
Cd27 Defrost Interval This is the desired period of time between defrost cycles. “AUTO”, “OFF”, 3,
6, 9, 12, 24 Hours. Factory default is “AUTO”.
Cd28 Standard Temperature This parameter determines the default units (metric or British) for the system.
Unit The opposite units may be temporarily displayed with the C/F key. This
function code will display “—−“ if the controller Degree Celsius Lockout option
is set to F. The factory default value is Celsius units.
4–27 T-370
Table 4–7 Controller Function Codes
Code Title Description
Cd29 User Selectable Failure This is the desired action to be taken should an alarm occur which severely
Response Code limits the capability of the control system. Depending upon what alarm has
occurred, the actual action taken may not be the same as the desired failure
action.
The user selects one of two possible actions as follows:
A - Evaporator Fan Only (Evap fans on high speed, n/a with frozen setpoints.)
d - Full System Shutdown - Factory Default (Shut down every component in
unit.)
Cd30 In-Range Tolerance The in-range tolerance will determine the band of temperatures around the
setpoint which will be designated as in-range. If the control temperature is in-
range, the in-range light will be illuminated. There are four possible values:
1 = +/- 0.5°C (+/- 0.9°F)
2 = +/- 1.0°C (+/- 1.8°F)
3 = +/- 1.5°C (+/- 2.7°F)
4 = +/- 2.0°C (+/- 3.6°F) - Factory Default
Cd32 System Current Limit The highest current draw of 460VAC Line Current Phase A, B, C is compared
to this limit and unit capacity may be reduced to limit current draw if current
limit is exceeded.
The five values for 460 VAC operation are: 15, 17, 19, 21, or 23 amperes.
The factory default setting is 21 amperes.
Cd33 Humidity Setpoint This is the value in percent to which the system will dehumidify.
There are configuration variables that determine whether dehumidification is
installed. In the test mode, the setpoint will be temporarily set to 1%, allowing
the test of dehumidification. After 5 minutes, the normal setpoint is restored.
If Pre-trip is initiated, this value will be set to “OFF” automatically.
Cd35 Bulb Mode The current state of the bulb mode option. “−−−−“, “nOr”, “bULb”
Cd36 Evaporator Fan Speed This is the desired evaporator fan speed for use during the bulb mode option.
“−−−−“, “ALt”, “LOW”, “HI”
Cd37 Variable DTT Setting This is the variable defrost termination thermostat setting to be used with the
optional bulb mode functionality. “—−−“, “nOr”
Display Only Functions
Cd38 Secondary Supply This item is only displayed if the DataCORDER is configured OFF and
configured for a four probe system. Dashes are displayed otherwise.
Cd39 Secondary Return This item is only displayed if the DataCORDER is configured OFF and
configured for a four probe system. Dashes are displayed otherwise.
Cd40 Container ID Cd40 is configured at commissioning to read a valid container identification
number. The reading will not display alpha characters; only the numeric
portion of the number will display. See Section 7.19.3 Controller
Programming Procedure for additional information.
Cd45 Vent Position This function code will be dashed out if not configured for VPS. This function
code displays current vent position in units of 5 CMH (units displayed as
“CM”) or closes CFM (units displayed as “CF”) depending on the selection of
Cd 46 (Airflow display units), Cd 28 (Metric/Imperial) or the pressing of the
deg C/F key.
CFM displayed as “CF”, CMH displayed as “CM”.
Values: 0 to 240 for UPPER / 0 to 225 for LOWER
T-370 4–28
Table 4–7 Controller Function Codes
Code Title Description
Cd46 Air Flow Display Units Selects the airflow units to be displayed by Function Code 45 (Cd 45) if
configured for Vent Position Sensor or displayed by “FLO” under Cd 43 if
configured for Autoslide. CF= Cubic Feet per Minute, CM=Cubic Meters per
Hour, bOth=Displays either CF or CM depending on the setting of Cd 28
(Metric/Imperial) or the pressing of the degree C/F key.
Default − “bOth” If configured for Vent Position Sensor or Autoslide
Cd48 Dehumidification / Bulb Initially Cd48 will display current dehumidification-mode; bUlb - bulb cargo
Cargo Mode Parameter mode, dEhUM - normal dehumidification, or OFF - off. This display is steady.
Selection Press the ENTER key to take the interface down into a hierarchy of
parameter selection menus (mode, setpoint, evaporator speed, DTT setting).
Press the ENTER key in any parameter selection menu to commit to
selection of the currently displayed parameter and cause the interface to
descend into the next parameter selection menu. All parameter selection
menus alternate between a blank display and the current selection in the right
hand display.
Press the CODE SELECT key in a selection menu to cancel the current
selection activity and ascend back up to the next higher selection menu (or
to Cd48 display mode if that is the next higher).
If the operator does not press any key for five seconds, the interface reverts
to normal system display and the current selection menu is canceled, but any
previously committed changes are retained.
Available parameters and parameter ranges are a function of configuration
options and previously selected parameters as indicated above.
Whenever any Pre-trip test is initiated, dehumidification mode goes to OFF.
Whenever dehumidification mode goes to OFF:
• Dehumidification control setpoint goes to 0% RH internally but will
then initialize to 95% RH when dehumidification mode leaves OFF.
• Evaporator speed select goes to Alt for units without PWM Compres-
sor Control (Cnf57 = Out), Evaporator speed select goes to Hi for
units with PWM Compressor Control (Cnf57 = In).
• DTT setting goes to 25.6°C or 18.0°C, depending on Cnf41.
Whenever dehumidification-mode is set to bUlb, DTT setting goes to 18.0°C
if it had been set higher.
Whenever dehumidification-mode is set to dEhUM, DTT setting goes to
25.6°C or 18.0°C, depending on Cnf41.
For units without PWM Compressor Control (Cnf57 = Out):
• Whenever dehumidification control setpoint is set below 65% RH
evaporator speed select goes to LO if it had been set to Hi.
• Whenever dehumidification control setpoint is set above 64% RH
evaporator speed select goes to Alt if it had been set to LO.
For units with PWM Compressor Control (Cnf57 = In):
• Whenever dehumidification control setpoint is below 60% RH, evapo-
rator fan speed is set to LO, the user can set evaporator fan speed to
Hi via the keypad.
• Whenever dehumidification control setpoint is set equal to or above
60% RH, the evaporator fan speed is set to Hi, the user has the ability
to set the evaporator fan speed to LO via the keypad.
4–29 T-370
Table 4–7 Controller Function Codes
Code Title Description
Cd49 Days Since Last Display number of days since last successful completion. Press the ENTER
Successful Pre-trip key for number of days since successful Pre-trip completion for Auto1, Auto2,
and Auto3 in sequence.
Press the CODE SELECT key to step back through list and ultimately exit
CD49 display.
Cd51 Automatic Cold Automatic Cold Treatment (ACT) mode:
Treatment Parameter Cd51 increments of (1 day)_(1hr), Display: default “0_0 “
Selection
“done” mm-dd this will be display is ACT has completed
“ACt” value “On” “OFF” or “----“Display / Select: default “OFF“
“trEAt” value °C / °F on 0.1 degree increments Display / Select: default
“0.0°C“
“DAyS” value “0-99” increments of 1 Display / Select: default “0”
“ProbE” value Probe positions ex ’1 2 _ 4’ ’1 _ 3 _’ Display: default “---- “
“SPnEW” value °C / °F on 0.1° increments Display / Select: default “10.0°C “
Initially Cd51 will display current countdown timer increments of (1
day)_(1hr), default “0_0”.
See Section 4.8.1 for procedure to set ACT using Cd51.
Pressing the ENTER key will take the interface down into a hierarchy of
parameter selection menus (act, treat, days, probe and spnew setting).
Pressing the ENTER key in any of the parameter selection menus commits
to selection of the currently displayed parameter and causes the interface to
descend into the next parameter selection menu. All parameter selection
menus alternate between a blank display and the current selection in the right
hand display.
Pressing the CODE SELECT key in a selection menu cancels the current
selection activity and ascends back up to the next higher selection menu (or
to Cd51 display mode if that is the next higher).
If the operator does not press any key for five seconds, the interface reverts
to normal system display and the current selection menu is cancelled, but
any previously committed changes are retained.
Parameter with the exception of “Act” may not be altered if Cd51 is re-entered
if “Act” is “On”. When ACT has completed including reaching the new setpoint
“done” on the left display and the MONTH DAY of completion on the right
display will be displayed as the second entry in the menu. Turning ACT off
clears this entry. This action also resets Cd51 to initial time remaining. ACT
must then be turned on to view or modify the additional parameters.
Whenever any auto Pre-trip test or Trip Start is initiated, ACT mode goes to
OFF.
T-370 4–30
Table 4–7 Controller Function Codes
Code Title Description
Cd53 Automatic Setpoint Automatic Setpoint Change (ASC) Mode:
Change Mode Cd53 increments of (1 day)_(1hr), Display: default “0_0”
Parameter Selection
“done” mm-dd this will be display is ASC has completed
“ASC” value “On” “OFF” Display / Select: default “OFF“
“nSC” value “1 - 6” (This is the value “n” for the subsequent entries).
“SP (n-1)” value °C / °F on 0.1 degree increments Display / Select: default
“10.0°C“
“DAY (n-1)” value “1 – 99” increments of 1 Display / Select: default “1“
“SP (n)” value °C / °F on 0.1 degree increments Display / Select: default
“10.0°C
Initially Cd53 will display current countdown timer increments of (1
day)_(1hr), default “0_0”.
Pressing the ENTER key will take the interface down into a hierarchy of
parameter selection menus, (mode, act, treat, days, probe and spnew
setting).
Pressing the ENTER key in any of the parameter selection menus selects the
currently displayed parameter and causes the interface to descend into the
next parameter selection menu. All parameter selection menus alternate
between a blank display and the current selection in the right hand display.
Pressing the CODE SELECT key in a selection menu cancels the current
selection activity and ascends back up to the next higher selection menu (or
to Cd53 display mode if that is the next higher).
If the operator does not press any key for five seconds, the interface reverts
to normal system display and the current selection menu is cancelled, but
any previously committed changes are retained.
Available parameters and parameter ranges are a function of configuration
options and previously selected parameters as indicated above.
Parameter with the exception of “ASC” may not be altered if Cd53 is re-
entered if “ASC” is “On”. When ASC has completed including reaching the
last setpoint “done” on the left display and the MONTH DAY of completion on
the right display will be displayed as the second entry in the menu. Turning
ASC off clears this entry. This action also resets Cd53 to initial time
remaining. ASC must then be turned on to view or modify the additional
parameters.
Whenever any auto Pre-trip test or Trip Start is initiated, ASC mode goes to OFF.
Cd54 Superheat Values Evaporator superheat: Evaporator leaving temperature minus suction
saturation temperature as calculated from suction pressure.
Cd55 Discharge Superheat Cd55 will display discharge superheat (discharge temperature minus
discharge saturation temperature as calculated from discharge pressure)
values in C / F as calculated by the discharge temperature minus the
discharge saturation temperature as calculated from discharge pressure. “--
---” will be displayed if selection is not valid.
Cd58 Water Pressure Switch This code is only displayed if the unit is configured for water-cooled
State condenser option. Values for this code are: “----”, “OPEN”, “CLOSE”.
Cd61 VFD Bypass Mode When this code is active it signifies the unit is operating in a LIMP HOME
MODE Condition.
Cd61 is locked out, and should only be activated after the VFD bypass pro-
cedure has been completed (see Section 7.20.2).
Cd68 EEV % Opening Displays the current percent opening of EEV (0-100%).
Cd69 HPXV % Opening Displays the current percent opening of HPXV (0-100%).
4–31 T-370
Figure 4.11 Alarm Troubleshooting Sequence
Start
Troubleshooting
Yes
Did
Evaporator No Check Power Refer to CONNECT POWER
fans start? Supply Section 5.2
Yes
Yes
Yes
See alarm
Active Yes details & Refer to Controller Alarm Indications
Alarms? repair Table 4–8
No
Yes
Unit OK
T-370 4–32
4.11 Controller Alarm Indications
4–33 T-370
AL06 Keypad or Keypad Harness Failure
Cause: Controller has detected continuous activity from one of the keypad keys.
Component Keypad or Harness
Troubleshooting Power cycle the unit.
Corrective Action Resetting the unit may correct problem. Monitor the unit.
If the alarm reappears, replace the keypad and harness.
T-370 4–34
AL15 Loss of Cooling
Cause: Evaporator efficiency monitor has detected a loss of system capacity, likely due to a drop in
refrigerant charge density.
Component Refrigerant Charge
Troubleshooting Check units for leaks, paying careful attention to high side fittings.
Check Pressure Relief Valves (Section 7.7) to see if refrigerant has
been released and replace if necessary.
Check for signs of unit running short of refrigerant: Codes Cd12 and
Cd13 along with high superheat at Cd54 and EEV open more than
standard operation, up to 100% at Cd68.
Corrective Action Rectify refrigerant leaks. Remove refrigerant charge (Section 7.2.5),
evacuate the unit (Section 7.2.7), and recharge the unit to rated charge
(Section 7.2.8).
Component Evaporator
Troubleshooting Check for excessive ice buildup on the coil, T-bar blockages, or fouling.
Corrective Action Defrost the coil.
4–35 T-370
AL19 Discharge Temperature High
Cause: Discharge temperature is above 135°C (275°F).
Component Restrictions in the refrigeration system
Troubleshooting Check the unit for air flow restrictions.
Corrective Action Clean or remove any debris from the coils.
Component Non-condensables in the refrigeration system.
Troubleshooting With the unit off, allow system to stabilize to ambient temperature.
Check system pressure against the Pressure / Temperature Chart for
R744 (Table 7–4). Refer to function codes Cd12, Cd13 and Cd14.
Corrective Action Remove refrigerant charge (Section 7.2.5), evacuate the unit (Section
7.2.7), and recharge the unit (Section 7.2.8).
Component Compressor
Troubleshooting Check VFD Speed (Cd01), Suction Pressure (Cd12), and Flash Tank
Pressure (Cd13). If the compressor speed is greater than 70% and the
Flash Tank pressure is approximately equal to suction pressure with the
High Pressure Expansion Valve (HPXV) controlling at less than 25%
(Cd69), there may be a compressor first stage failure. This condition will
also increase compressor discharge temperature (Cd11) and may also
demonstrate AL03 alarms.
Corrective Action If the alarm persists, it may indicate a failing compressor. Replace the
compressor, refer to Compressor Service (Section 7.3).
Component Refrigerant Charge
Troubleshooting Check unit for leaks, paying careful attention to high side fittings. Unit
over-charge or under-charge may create pressure control problems
related to charge density and compression ratio. Ensure the unit
refrigerant charge is within operational specifications for the model.
Check Pressure Relief Valves (Section 7.7) to see if refrigerant has
been released and replace if necessary.
Check for signs that the unit is running short of refrigerant. Check
Compressor Suction Pressure (Cd12) and Flash Tank Pressure (Cd13).
Check for high superheat (Cd54) and EEV open more than standard
operation, up to 100% (Cd68).
Corrective Action Rectify refrigerant leaks, vacuum and re-charge the system to rated
charge.
T-370 4–36
AL20 Control Contactor Fuse (F3)
Cause: Control power fuse (F3A or F3B) is open.
Component Fuse F3A
Troubleshooting If fuse F3A is open, check PA, PB, and CH coils for short to ground. If a
short is found, the coil is defective. Check ESV coil resistance at TP7 to
TP9, and USV coil resistance at TP1 to TP9. If short to ground, or if
resistance is less than 4 ohms, the coil is defective.
Corrective Action Replace the defective coil.
Replace the fuse.
Component Fuse F3B
Troubleshooting If fuse F3B is open, check contactor coils GF, GS, ES, EF, HR, for a
short to ground. If a short is found, the coil is defective.
Corrective Action Replace the defective coil.
Replace the fuse.
Component Controller
Troubleshooting Check voltage at QC1. If voltage is present, it indicates a defective
microprocessor.
Corrective Action Refer to Controller Service (Section 7.19).
AL22 Evaporator IP
Cause: Evaporator motor internal protector (IP) is open.
Component Evaporator Motor
Troubleshooting Shut down the unit, disconnect power and check evaporator motor IP at
plug connection pins 4 & 6.
Corrective Action Replace the defective evaporator fan motor. Refer to Evaporator Fan
Motor Service (Section 7.13).
4–37 T-370
AL24 Compressor IP
Cause: Compressor internal protector (IP) is open for greater than five seconds.
Component Compressor
Troubleshooting Confirm motor IP is open at KA2 to KB9. Verify the High Pressure Switch
(HPS) is closed.
Corrective Action Monitor the unit. If the alarm remains active or is repetitive, replace the
compressor at the next available opportunity. Refer to Compressor
Service (Section 7.3).
T-370 4–38
AL28 Low Suction Pressure
Cause: Suction pressure is less than 5.5 bar (80 psi), or less than 6.2 bar (90 psi) for 300 seconds.
Component Refrigerant Charge
Troubleshooting Check units for leaks, paying careful attention to high side fittings.
Check Pressure Relief Valves (Section 7.7) to see if refrigerant has
been released and replace if necessary.
Check for signs that the unit is running short of refrigerant. Check
Compressor Suction Pressure (Cd12) and Flash Tank Pressure
(Cd13). Check for high superheat (Cd54) and Electronic Expansion
Valve (EEV) open more than standard operation, up to 100% (Cd68).
Corrective Action Rectify refrigerant leaks, vacuum and re-charge the system to rated
charge.
Component Suction Pressure Transducer (SPT)
Troubleshooting Power cycle the unit.
Corrective Action Resetting the unit may correct the problem. Monitor the unit.
Troubleshooting Confirm accurate SPT pressure readings. Refer to Manifold Gauge Set
procedures (Section 7.2).
Corrective Action Replace SPT if it is defective.
4–39 T-370
AL52 EEPROM Alarm List Full
Cause: Alarm list queue is full.
Component Active Alarms
Troubleshooting Repair any alarms in the queue that are active. These are indicated by
“AA”.
Corrective Action Clear alarms. Refer to the Controller Alarms table (Section 4.5).
T-370 4–40
AL58 Compressor High Pressure Safety (HPS)
Cause: High pressure safety switch has opened and reset within five seconds, triggering a high pressure
shutdown state.
Component High Pressure Switch (HPS)
Troubleshooting Test the HPS. Refer to Checking High Pressure Switch procedure
(Section 7.5.1). Run a P7 test to verify the operation of the HPS.
Corrective Action Replace the HPS if it is defective. Refer to Sensor Replacement
procedure (Section 7.5.2).
Component Refrigeration System
Troubleshooting Measure temperatures before and after all fittings and braze joints
paying careful attention to screen locations. Temperature drops may
indicate internal blockages. Unit over-charge may create pressure
control problems. Ensure unit refrigerant charge is within operational
specifications for the model. Check unit for air flow restrictions.
Corrective Action Clean or remove any debris from coils. Rectify system blockages.
Remove refrigerant charge (Section 7.2.5), evacuate the unit (Section
7.2.7), and recharge the unit (Section 7.2.8).
Component High Pressure Expansion Valve (HPXV)
Troubleshooting Verify that the HPXV coil is fully seated on the stem of the HPXV body
(see Section 7.15.2). Attempt to manually open the valve with magnet.
If this rectifies the problem, replace the stepper motor. Check
resistance of HPXV coils.
Corrective Action Replace the HPXV.
4–41 T-370
AL61 Heater Current Draw Fault
Cause: Improper current draw during heat or defrost mode.
Component Heater(s)
Troubleshooting While in heat or defrost mode, check for proper current draw at the
Heater Contactors (HR). Refer to Electrical Data (Section 3.4).
Corrective Action Replace the heater(s) if it is defective. Refer to Evaporator Coil &
Heater Assembly (Section 7.11).
Component Contactor
Troubleshooting Check voltage at the Heater Contactor (HR) on the heater side.
Corrective Action If no voltage present, replace the Heater Contactor (HR) if it is
defective.
T-370 4–42
AL66 Suction Pressure Transducer (SPT)
Cause: Suction Pressure Transducer (SPT) out of range.
Component Suction Pressure Transducer (SPT)
Troubleshooting Confirm accurate SPT pressure readings. Refer to Manifold Gauge Set
procedures (Section 7.2). Reference Cd12 for transducer values.
Corrective Action Replace SPT if it is defective.
Troubleshooting Monitor the unit.
Corrective Action If the alarm persists, it may indicate a failing compressor. Refer to
Compressor Service (Section 7.3).
4–43 T-370
AL71 Secondary Return Sensor (RRS)
Cause: Secondary Return Sensor (RRS) is out of range.
Component Secondary Return Sensor (RRS)
Troubleshooting Perform Pre-trip P5.
Corrective Action If P5 passes, no further action is required.
If P5 fails, replace the defective sensor as determined by P5. Refer to
Temperature Sensor Service (Section 7.22).
T-370 4–44
AL95 Gas Cooler Outlet Temperature
Cause: Gas Cooler outlet temperature is out of range.
Component Gas Cooler
Troubleshooting Check for dirt, debris and blockage of the Gas Cooler. Check continuity
at connector KH.
Corrective Action Remove any blockage in the Gas Cooler coil.
Component Gas Cooler Temperature Sensor (GCTS)
Troubleshooting Check the operation of the GCTS.
Corrective Action Replace the GCTS if necessary. See Section 7.8.
NOTICE
If the controller is configured for four probes without a DataCORDER, the DataCORDER alarms
AL70 and AL71 will be processed as Controller alarms AL70 and AL71. Refer to Table 4–5.
The controller performs self-check routines. If an internal failure occurs, an “ERR” alarm will appear on the display.
This is an indication the controller needs to be replaced. In the event that a failure occurs and the display cannot be
updated, the status LED will indicate the appropriate ERR code using Morse code as shown below.
4–45 T-370
ERR 2 . .−. .−. . . −−−
Cause: Watchdog time-out
Description The controller program has entered a mode whereby the controller program has
stopped executing.
T-370 4–46
4.12 Controller Pre-Trip Test Codes
NOTICE
“Auto” or “Auto1” menu includes the: P0, P1, P2, P3, P4, P5, P6 and rSLts.
“Auto2” menu includes P0, P1, P2, P3, P4, P5, P6, P7, P8, P9, P10 and rSLts.
“Auto3” menu includes P0, P1, P2, P3, P4, P5, P6, P7 and P8.
P0-0 Pre-trip Initiated Setup: The display shows, in sequence, Container identifier code, software
revision number (Cd18), container unit model number (Cd20), and
configuration database identifier CFMMYYDD.
Next the unit indicates the presence of an RMU according to whether any
RMU inquiry messages have been received since the unit was booted.
Units equipped with Autoslide (Cnf44) will position the vent to closed,
followed by two sequences of opening to 100% and returning to the closed
position. No other Autoslide mode of operation will be available until the two
cycles of opening and closing have completed.
Pass / Fail Criteria: Since the system cannot recognize lights and display
failures, there are no test codes or results associated with this phase of Pre-
trip.
To know if the test passes the operator must visually observe that the LCD
display elements and the indicator lights function.
P1 Tests - Heaters Current Draw: Heater is turned on, then off. Current draw must fall within specified range. No
other system components will change state during this test.
Code Title Description
P1-0 Heaters Turned On Setup: Heater starts in the off condition, current draw is measured, and then
the heater is turned on. After 15 seconds on, the current draw is measured
again. The change in current draw is then recorded.
Pass / Fail Criteria: Test passes if current draw change is within the range
specified.
P1-1 Heaters Turned Off Setup: Heater is then turned off. After 10 seconds the current draw is
measured. The change in current draw is then recorded.
Pass / Fail Criteria: Test passes if current draw change is within the range
specified.
P2 Tests - Gas Cooler Fan Current Draw: Gas Cooler fan is turned on, then off. Current draw must fall within
specified range. No other system components will change state during this test. If the Water Pressure Switch is
open this test will be skipped.
Code Title Description
P2-0 Gas Cooler Fan, Setup: Gas Cooler fan starts in the off condition, current draw is measured,
Low Speed On Test and Gas Cooler low speed fan is then turned on. After 10 seconds the current
draw is measured again. The change in current draw is then recorded. After
the current is measured the Gas Cooler fan is turned off and after 2 seconds
a second off measurement is taken.
Pass / Fail Criteria: Test passes if current draw is in the specified range.
P2-1 Gas Cooler Fan, Setup: Gas Cooler fan starts in the off condition, current draw is measured,
High Speed On Test and Gas Cooler high speed fan is then turned on. After 15 seconds the
current draw is measured again. The change in current draw is then recorded.
After the current is measured the Gas Cooler fan is turned off and after 15
seconds a second off measurement is taken.
Pass / Fail Criteria: Test passes if current draw is in the specified range.
4–47 T-370
P3 Tests - Low Speed Evaporator Fan Current Draw: Low speed evaporator fan is turned on, then off. Current
draw must fall within specified range. No other system components will change state during this test.
Code Title Description
P3-0 Low Speed Setup: Evaporator fans start in the off condition, current draw is measured,
Evaporator Fans On and then low speed evaporator fans will be turned on. After 10 seconds the
Test current draw is measured again. The change in current draw is then recorded.
Pass / Fail Criteria: Test passes if current draw is in the specified range.
P3-1 Low Speed Setup: Low speed evaporator fans are then turned off. After 2 seconds the
Evaporator Fans Off current draw is measured. The change in current draw is then recorded.
Test Pass / Fail Criteria: Test passes if current draw is in the specified range.
P4 Tests - High Speed Evaporator Fan Current Draw: High speed evaporator fans are turned on, then off. Cur-
rent draw must fall within specified range and measured current changes must exceed specified ratios. No other
system components will change state during this test.
Code Title Description
P4-0 High Speed Setup: Evaporator fans start in the off condition, current draw is measured,
Evaporator Fans On and then high speed evaporator fans will be turned on. After 10 seconds the
Test current draw is measured again. The change in current draw is then recorded.
Pass / Fail Criteria: Test passes if current draw is in the range specified.
P4-1 High Speed Setup: High speed evaporator fans are then turned off. After 2 seconds the
Evaporator Fans Off current draw is measured. The change in current draw is then recorded.
Test Pass / Fail Criteria: Test passes if current draw is in the range specified.
P5 Tests - Air Stream Sensor Tests: Tests the validity of the Air Stream Temperature & Humidity Sensors (HS).
Code Title Description
P5-0 Supply/Return Setup: High Speed Evaporator Fan is turned on and run for eight minutes,
Temperature Probe with all other outputs de-energized.
Test Pass / Fail Criteria: A temperature comparison is made between the return
and supply probes.
NOTE:
If this test fails, “P5-0” and “FAIL” will be displayed. If both Probe tests (this
test and the PRIMARY/ SECONDARY) pass, display will read “P5” “PASS.”
P5-1 Primary vs Requirements: For units equipped with secondary supply probe only.
Secondary Supply Pass / Fail Criteria: The temperature difference between Supply
Temperature Test Temperature Sensor (STS) and supply recorder sensor (SRS) probe is
compared.
NOTE:
If this test fails, “P5-1” and “FAIL” will be displayed. If both Probe tests (this
and the SUPPLY/RETURN TEST) pass, because of the multiple tests, the
display will read “P 5” “PASS.”
P5-2 Primary vs Requirements: For units equipped with secondary return probe only.
Secondary Return Pass / Fail Criteria: The temperature difference between Return
Temperature Test Temperature Sensor (RTS) and Return Recorder Sensor (RRS) probe is
compared.
NOTES:
1. If this test fails, “P5-2” and “FAIL” will be displayed. If both Probe tests (this
test and the SUPPLY/RETURN) pass, because of the multiple tests, the
display will read “P 5,” “PASS.”
2. The results of Pre-trip tests 5-0, 5-1 and 5-2 will be used to activate or clear
control probe alarms.
T-370 4–48
Code Title Description
P5-10 Humidity Sensor Setup: This is a Pass / Fail / Skip test of the Humidity Sensor (HS)
Controller configuration.
Configuration Pass / Fail Criteria: Test passes if the controller configuration has Humidity
Verification Test Sensor in. Test fails if the controller configuration has Humidity Sensor out
and Humidity Sensor voltage is greater than 0. This test is skipped if the
controller configuration has the Humidity Sensor out and Vout is less than
0.20 Volts.
P5-11 Humidity Sensor Setup: This is a Pass / Fail test of Humidity Sensor (HS) installation, humidity
Installation sensor is present. Test P5-10 must pass before this test is run.
Verification Test Pass / Fail Criteria: Test passes if Humidity Sensor voltage is greater than
0.20.
Test fails if the voltage is less than 0.20 Volts or if the humidity sensor is
configured in and is not present.
P5-12 Humidity Sensor Setup: This is a Pass / Fail test of the Humidity Sensor (HS) range. Test P5-
Range Check Test 11 must pass before this test is run.
Pass / Fail Criteria: Test passes if Humidity Sensor voltage is between 0.33
Volts and 4 Volts. Otherwise the test fails.
P6 Tests - Refrigerant Probes, Variable Frequency Drive, and Refrigeration Valves: Tests the VFD, EVXV,
HPXV, Unloader Solenoid Valve, Economizer Solenoid Valve, and refrigerant pressure/temperature sensors.
Code Title Description
P6-0 Discharge Pass / Fail Criteria: If AL64 (Discharge Temperature Sensor) is activate, the
Thermistor Test test fails. Otherwise the test passes.
P6-1 Suction Thermistor Pass / Fail Criteria: If the Suction Temperature Sensor (CPSS) is both
Test configured ON and is invalid, the test fails. Otherwise the test passes.
P6-2 Discharge Pressure Pass / Fail Criteria: If AL65 (Discharge Pressure Sensor, DPT) is active any
Sensor Test time during the first 45 second period, the test fails. Otherwise, the test
passes.
P6-3 Suction Pressure Pass / Fail Criteria: If AL66 (Suction Pressure Sensor) is active the test fails.
Sensor Test Otherwise the test passes.
P6-4 Flash Tank Pressure Pass / Fail Criteria: If AL68 (Flash Tank Pressure Transducer Alarm), is
Sensor Test active the test fails. Otherwise the test passes.
NOTE:
After P6-4 is complete, the unit will establish an initial operating condition.
P6-5 Unloader Valve Setup: This test is run after P6-6. During this test, 50 seconds after the initial
(USV) Test run condition USV will close while system pressures are checked. After
meeting certain criteria the USV will be opened and system operating
conditions will again be checked to confirm that USV has opened.
P6-6 Variable Frequency Setup: This test is run before P6-5. During this test, the unit will establish an
Drive Test initial operating condition. After 20 seconds at the initial condition compressor
speed will be increased and system operating conditions will be recorded
after which time the compressor speed will be decreased.
Pass / Fail Criteria: Test passes when a pressure change has been
detected.
P6-7 High Pressure Setup: After P6-6 is complete, the unit will establish an initial operating
Expansion Valve condition. After the initial operating condition the controller will slowly adjust
(HPXV) Test HPXV and monitor discharge pressure.
Pass / Fail Criteria: Test will pass provided an increase in discharge
pressure has been detected.
4–49 T-370
Code Title Description
P6-8 Evaporator Setup: After P6-7 is complete, the unit will establish an initial operating
Expansion Valve condition. After the initial operating condition the controller will slowly adjust
(EEV) Test EEV.
Pass / Fail Criteria: Once pressure difference has been determined, the test
passes.
P6-9 Economizer Setup: Setup: After P6-8 has completed, the unit will establish an initial
Solenoid Valve operating condition. The controller will then energize the Unloader Solenoid
(ESV) Test Valve (USV), followed by the economizer valve ESV. The controller will
monitor system pressures
Pass / Fail Criteria: Test will pass based on the change in pressure.
P6-10 Low Charge Check Pass / Fail Criteria: Test will pass if the unit has adequate charge.
Otherwise, test fails.
NOTICE
P7-0 & P8 are included with “Auto2 & Auto3” only. P9-0 through P10 are included with “Auto2” only.
P7 Tests - High Pressure Tests: Unit is run at full capacity with low condenser fan running to make sure that the
HPS opens and closes properly.
Code Title Description
P7-0 High Pressure When test is running, the right display shows Discharge Pressure if the
Switch Opening sensor is configured and valid, else Discharge Temperature.
Test Setup: The unit will establish an initial operating condition, then will slowly
adjust VFD and HPXV and control system pressure to reach test criteria.
Pre-trip 7 will be skipped if any of the following conditions are met before the
test:
Return Temperature < -17.77°C.
Water Pressure Switch is open (if equipped).
Pass / Fail Criteria: Test passes if HPS opens any time after the compressor
starts.
Test fails if:
HPS fails to open before 900 seconds total test time. Discharge Pressure
greater than 2075 psig. If greater than 2075 psig shutdown compressor, turn
on fans, fail test.
Abort test if:
Evaporator IP alarm.
Compressor IP alarm.
Water Pressure Switch opens (if equipped).
Discharge Temperature exceeds 146.1°C
Both Discharge Pressure and Discharge Temperature go invalid.
Compressor Current exceeds operating parameters.
P7-1 High Pressure Setup: The controller will energize the gas cooler fan, open valves, and stop
Switch Close Test the compressor.
Pass / Fail Criteria: The test passes if the high pressure switch closes within
the 60 seconds.
P8 Tests - Perishable Mode Tests: Pre-trip tests P7-0 and P7-1 must have passed or have been skipped for
these tests to execute.
T-370 4–50
Code Title Description
P8-0 Perishable Mode Setup: If the control temperature is below 15.56°C, the set-point is changed
Heat Test to 15.56°C, and a 180 minute timer is started. The control will then be placed
in the equivalent of normal heating. If the control temperature is above
15.56°C at the start of the test, then the test proceeds immediately to test 8-
1. While in test 8-0 the right display will show the value of the control
temperature.
Pass / Fail Criteria: The test fails if the timer expires before the control
temperature reaches set-point - 0.3°C. If the test fails, it will not auto-repeat.
There is no pass display for this test. Once the control temperature reaches
set-point, the test proceeds to test 8-1.
P8-1 Perishable Mode Requirements: Control temperature must be at least 15.6°C (60°F).
Pulldown Test Setup: Setpoint is changed to 0°C. The system will attempt to pull down the
control temperature to setpoint using the equivalent of normal perishable
cooling. During this test, the control temperature will be displayed on the right
display.
Pass / Fail Criteria: The test passes if the control temperature goes below
the setpoint before the 180 minute timer expires and CO2 sensor calibration
passes or is skipped. Otherwise, the test fails.
P8-2 Perishable Mode Requirements: Test P8-1 must pass for this test to execute. This test is
Maintain skipped if the DataCORDER is not configured or not available.
Temperature Test Setup: 15-minute timer is started. The unit will be required to minimize control
temperature error (supply temp minus setpoint) until timer expires. Control
temperature is sampled at least once each minute starting at the beginning of
P8-2.
Pass / Fail Criteria: If the average recorded temperature is within +/- 1.0°C
(1.8°F) of setpoint, the test passes. If the average temperature is outside of
the tolerance range or if the DataCORDER supply temperature probe is
invalid, the test fails and the control probe temperature will be recorded as -
50.0°C. P8-2 will auto-repeat by starting P8-0 over.
P9 Tests - DTT Close and Open Test: The DTT in this control is not a physical device, with actual metallic con-
tacts, it is a software function that acts similar to a thermostat. Using various temperature inputs, the DTT function
determines whether a thermostat mounted on the Evaporator Coil would have OPEN or CLOSED contacts. Primar-
ily, the DTT function operates based on the temperature reading from the Defrost Termination Sensor.
Code Title Description
P9-0 DTT Closed and Setup: System will run full cool for 30 minutes max while the DTT probe
Open Test temperature is above 10°C. (opening threshold), allowing DTT to become
considered closed. This step may not have to be executed. Once DTT is
considered closed, system simulates defrost by running the heaters for up to
2 hours, or until DTT is considered open (25.6°C/18°C depending on
configuration & defrost options). Successful opening of DTT causes the
Defrost Interval Timer to be reset. Condenser Pressure Control logic should
be used for this test if the controller is configured for it.
Pass / Fail Criteria: The test fails if: the DTT is not considered closed after
the 30 minutes of full cooling, HTT opens when DTT is considered closed or
if return air temperature rises above 49°C (120°F). The test passes if the DTT
is considered open within the 2 hour heat cycle time limit.
-----
4–51 T-370
P10 Tests - Frozen Mode Tests:
Code Title Description
P10-0 Frozen Mode Heat Setup: If the container temperature is below 7.2°C, the setpoint is changed
Test to 7.2°C., and a 180 Minute timer is started. The control will then be placed in
the equivalent of normal heating. If the container temperature is above 7.2C.
at the start of the test, then the test proceeds immediately to test 10-1. During
this test, the control temperature will be shown on the right display.
Pass / Fail Criteria: The test fails if the 180 Minute timer expires before the
control temperature reaches setpoint - 0.3°C. If the test fails, it will not auto-
repeat. There is no pass display for this test. Once the control temperature
reaches setpoint, the test proceeds to test 10-1.
P10-1 Frozen Mode Requirements: Control temperature must be at least 7.2°C (45°F)
Pulldown Test Setup: The setpoint is changed to -17.8°C. The system will then attempt to
pull down the control temperature to setpoint using normal frozen mode
cooling. During this test, the control temperature will be shown on the right
display.
Pass / Fail Criteria: The test passes if the control temperature reaches
setpoint minus 0.3°C before the 180 minute timer expires. Otherwise, the test
fails. Upon failure and when initiated by an automatic Pre-trip sequence, P10-
1 will auto-repeat once by starting P10-0 over again.
P10-2 Frozen Mode Requirements: Test P10-1 must pass for this test to execute.
Maintain Setup: Same as test 8-2 except control temperature is return probe.
Temperature Test
Pass / Fail Criteria: The average error must be +/-1.6°C. If the
DataCORDER supply temperature probe is invalid, the test fails and the
control probe temperature will be recorded as -50°C. Upon failure and when
initiated by an automatic Pre-trip sequence, P10-2 will auto-repeat by starting
P10-0 over again.
-----
T-370 4–52
Table 4–9 DataCORDER Function Code Assignments
NOTE:
Inapplicable Functions display “-----”
To Access: Press the ALT.MODE key then CODE SELECT key
Code Title Description
dC26,27 S/N, Left 4, Right 4 The DataCORDER serial number consists of eight characters. Function code
dC26 contains the first four characters. Function code dC27 contains the last
four characters. (This serial number is the same as the controller serial
number.)
dC28 Minimum Days Left An approximation of the number of logging days remaining until the
DataCORDER starts to overwrite the existing data.
dC29 Days Stored Number of days of data that are currently stored in the DataCORDER.
dC30 Date of Last Trip The date when a Trip Start was initiated by the user. In addition, if the system
start goes without power for seven continuous days or longer, a trip start will
automatically be generated on the next AC power up. Press and hold
“ENTER” key for five seconds to initiate a “Trip Start.”
dC31 Battery Test Shows the current status of the optional battery pack.
PASS: Battery pack is fully charged.
FAIL: Battery pack voltage is low.
dC32 Time: Hour, Minute Current time on the real time clock (RTC) in the DataCORDER.
dC33 Date: Month, Day Current date (month and day) on the RTC in the DataCORDER.
dC34 Date: Year Current year on the RTC in the DataCORDER.
dC35 Cargo Probe 4 Current calibration value for the Cargo Probe. This value is an input via the
Calibration interrogation program.
4–53 T-370
Table 4–10 DataCORDER Pre-Trip Result Records
Test Title Data
P5-12 Humidity Sensor Range Pass / Fail / Skip.
P6-0 Discharge Thermistor Test Pass / Fail / Skip.
P6-1 Suction Thermistor Test Pass / Fail / Skip.
P6-2 Discharge Pressure Sensor Test Pass / Fail / Skip.
P6-3 Suction Pressure Sensor Test Pass / Fail / Skip.
P6-4 Flash Tank Pressure Sensor Test Pass / Fail / Skip.
P6-5 USV Test Pass / Fail / Skip.
P6-6 VFD Test Pass / Fail / Skip.
P6-7 HPXV Test Pass / Fail / Skip.
P6-8 EEV Test Pass / Fail / Skip.
P6-9 ESV Test Pass / Fail / Skip.
P6-10 Low Charge Check Pass / Fail / Skip.
P7-0 High Pressure Switch Open Pass / Fail / Skip.
P7-1 High Pressure Switch Close Pass / Fail / Skip.
P8-0 Perishable Mode Heat Test Pass / Fail / Skip Result, STS, time it takes to heat to 16°C (60°F).
P8-1 Perishable Mode Pulldown Test Pass / Fail / Skip Result, STS, time it takes to pull down to 0°C
(32°F).
P8-2 Perishable Mode Maintain Test Pass / Fail / Skip Result, Averaged DataCORDER supply
temperature (SRS) over last recording interval.
P9-0 DTT Open / Close Test Pass / Fail / Skip Result, DTS reading at end of test, line voltage,
line frequency, time in defrost.
P10-0 Frozen Mode Heat Test Pass / Fail / Skip Result, STS, time unit is in heat.
P10-1 Frozen Mode Pulldown Test Pass / Fail / Skip Result, STS, time to pull down unit to -17.8°C
(0°F).
P10-2 Frozen Mode Maintain Test Pass / Fail / Skip Result, Averaged DataCORDER return
temperature (RRS) over last recording interval.
T-370 4–54
SECTION 5
OPERATION
5.1 Introduction
! WARNING
Beware of unannounced starting of the evaporator and gas cooler fans. The unit may cycle the
fans and compressor unexpectedly as control requirements dictate.
! WARNING
Do not attempt to remove power plug(s) before turning OFF Start-Stop switch (ST), unit circuit
breaker(s) and external power source.
! WARNING
Make sure the power plugs are clean and dry before connecting to power receptacle.
5–1 T-370
5.3.1 Upper Fresh Air Makeup Vent
Two slots and a stop are designed into the Upper Fresh Air disc for air flow adjustments. The first slot allows for a 0
to 30% air flow; the second slot allows for a 30 to 100% air flow. To adjust the percentage of air flow, loosen the
wing nut and rotate the disc until the desired percentage of air flow matches with the arrow. Tighten the wing nut.
To clear the gap between the slots, loosen the wing nut until the disc clears the stop.
Figure 5.1 gives air exchange values for an empty container. Higher values can be expected for a fully loaded con-
tainer.
TBAR TBAR
250 1 1/2”
200 1 1/2”
TBAR TBAR
200 2 5/8”
2 5/8”
150 TBAR 3” TBAR 3”
150
100
100
50
50
0 0
0 10 20 30 40 50 60 70 80 90 100 0 10 20 30 40 50 60 70 80 90 100
PERCENT OPEN PERCENT OPEN
NOTICE
The user has four minutes to make necessary adjustments to the vent setting. This time calcu-
lation begins on the initial movement of the sensor. The vent can be moved to any position
within the four minutes. On completion of the first four minutes, the vent is required to remain
stable for the next four minutes. If vent position changes are detected during the four minute
stability period, an alarm will be generated. This provides the user with the ability to change
the vent setting without generating multiple events in the DataCORDER.
T-370 5–2
Operational Parameters
FLO indicates the opening to which the slide will move based on the stored value in CMH (in increments of 5) or
CFM depending on the selection of Cd46 (Airflow display units), Cd28 (Metric/Imperial) or the pressing of the deg
C/F key. CFM is displayed as CF, CMH is displayed as CM.
tIM is the time delay prior to the door opening. The time range is from 1 to 72 hrs in 1 hr increments.
CO2LM is the maximum level of carbon dioxide that is allowed for the cargo. The range is from 0% to 19% in 1%
increments, the default setting is 10.
O2LM is the minimum level of O2 that is allowed for the cargo. The range is from 2% to 20% in 1% increments, the
default setting is 10.
Rtn is an offset value used to expand the return air temperature value in order to compensate for fresh air entering
the container. The allowable range is 0.6°C - 2.8°C or 1.0°F - 5.0°F in 0.1 degree increments, default setting is
2.8°C (5°F).
Circuit Function
Sockets B to A Energizes remote cool light
Sockets C to A Energizes remote defrost light
Sockets D to A Energizes remote in-range light
! WARNING
Make sure that the unit circuit breaker CB-1 and the Start-Stop switch (ST) are in the “O” (OFF)
position before connecting to any electrical power source.
NOTICE
The electronic phase detection system will check for proper phase rotation within the first 5
seconds. If rotation is not correct, the phase will be reversed.
2. The Controller Function Codes for the container ID (Cd40), software version (Cd18) and unit model number
(Cd20) will be displayed in sequence.
3. Continue with Start Up Inspection, Section 5.6.
5–3 T-370
5.6 Start-Up Inspections
5.6.1 Physical Inspection
Check rotation of gas cooler and evaporator fans.
! CAUTION
Pre-trip diagnostics should not be performed with critical temperature cargoes in the container.
! CAUTION
When the PRE-TRIP key is pressed, economy, dehumidification and bulb mode will be deacti-
vated. At the completion of Pre-Trip activity, economy, dehumidification and bulb mode must
be reactivated.
Pre-trip diagnosis provides automatic testing of the unit components using internal measurements and comparison
logic. The program will provide a “PASS” or “FAIL” display to indicate test results.
The testing begins with access to a Pre-trip selection menu. The user may have the option of selecting one of two
automatic tests. These tests will automatically perform a series of individual Pre-trip tests. The user may also scroll
down to select any of the individual tests. When only the short sequence is configured, it will appear as “AUtO” in the
display. Otherwise “AUtO1” will indicate the short sequence and “AUtO2” will indicate the long sequence. The test
short sequence will run tests P0 through P6. The long test sequence will run tests P0 through P10.
A detailed description of the Pre-trip test codes is listed in Section 4.12. If no selection is made, the Pre-trip menu
selection process will terminate automatically. However, dehumidification and bulb mode must be reactivated man-
ually if required.
Scrolling down to the “r SLts” code and pressing the ENTER key will allow the user to scroll through the results of
the last Pre-trip testing run. If no Pre-test has been run (or an individual test has not been run) since the unit was
powered up, “−−−−” will be displayed.
T-370 5–4
Prior to Starting a Trip Test verify the following:
• Voltage (Cd 07) is within tolerance and unit amperage draw (Cd 04, Cd 05, Cd 06) are within expected limits.
Otherwise, tests may fail incorrectly.
• All alarms are rectified and cleared.
NOTE
While making a selection, failure to press either an Arrow key or ENTER for 5 seconds will return the
system to its default display, and normal operating mode.
2. To Run an Automatic Test: Scroll through the selections by pressing the Up or Down Arrow keys to display
AUtO, AUtO 1, AUtO 2 or AUtO 3 as desired, then press the ENTER key.
• The unit will execute the series of tests without any need for direct user interface. These tests vary in
length, depending on the component under test.
• While tests are running, “P#-#” will appear on the left display; the #’s indicate the test number and sub-
test. The right display will show a countdown time in minutes and seconds, indicating the amount of time
remaining in the test.
! CAUTION
When a failure occurs during automatic testing, the unit will suspend operation awaiting oper-
ator intervention.
! CAUTION
When Pre-trip test Auto2 runs to completion without being interrupted, the unit will terminate
Pre-trip and display “Auto2 end”. The unit will suspend operation until the user presses the
ENTER key.
When Pre-trip test Auto1 runs to completion without a failure, the unit will exit the pre-trip mode
and return to normal control operation. However, dehumidification and bulb mode must be reacti-
vated manually if required.
3. When an automatic test fails, it will be repeated once. A repeated test failure will cause “FAIL” to be shown
on the right display, with the corresponding test number to the left. The user may then press the Down Arrow
key to repeat the test, the Up Arrow key to skip to the next test or the PRE-TRIP key to terminate testing.
The unit will wait indefinitely or until the user manually enters a command.
4. To Run an Individual Test: Scroll through the selections by pressing the Up or Down Arrow keys to display
an individual test code. Press the ENTER key when the desired test code is displayed.
• Individually selected tests, other than the LED / Display test, will perform the operations necessary to ver-
ify the operation of the component. At the conclusion, “PASS” or “FAIL” will be displayed. This message
will remain displayed for up to three minutes, during which time a user may select another test. If the
three minute time period expires, the unit will terminate Pre-trip and return to control mode operation.
• While the tests are being executed, the user may terminate the Pre-trip diagnostics by pressing and hold-
ing the PRE-TRIP key. The unit will then resume normal operation. If the user decides to terminate a test
but remain at the test selection menu, the user may press the Up Arrow key. When this is done, all test
outputs will be de-energized and the test selection menu will be displayed.
• Throughout the duration of any Pre-trip test (except the P-7 high pressure switch tests), the current and
pressure limiting processes are active. The current limiting process only is active for P-7.
5–5 T-370
5.7.2 Displaying Pre-Trip Results
1. Press the PRE-TRIP key to access the Pre-trip test selection menu. “SELCt PrtrP” will be displayed.
NOTE
While making a selection, failure to press either an Arrow key or ENTER for 5 seconds will return the
system to its default display, and normal operating mode.
3. Press the ENTER key. The results for all Pre-trip sub tests are available from this menu (i.e., 1-0, 1-1, etc).
The results will be displayed as “PASS” or “FAIL” for all the tests run to completion since power up. If a test
has not been run since power up, “-----” will be displayed.
Once all Pre-test activity is completed, dehumidification and bulb mode must be reactivated manually if
required.
T-370 5–6
SECTION 6
TROUBLESHOOTING
6–1 T-370
6.3 Unit Runs But Has Insufficient Cooling
Condition Possible Cause Remedy / Reference
Refrigeration system Pressures abnormal Section 6.7
Temperatures abnormal Section 6.13
Currents abnormal Section 6.14
Controller malfunction Section 6.9
Evaporator fan or motor defective Section 7.13
Electronic Expansion Valve (EEV) Replace
T-370 6–2
6.6 Unit Will Not Defrost Properly
Condition Possible Cause Remedy / Reference
Will not initiate defrost Defrost timer malfunction (Cd27) Table 4–7
automatically
Terminal connections loose Tighten
Wiring defective Replace
Defrost Temperature Sensor (DTS) defective or Replace
Heat Termination Thermostat (HTT) open
Heater contactor or coil defective Replace
Will not initiate defrost Manual defrost switch defective Replace
manually
Keypad defective Replace
Defrost Temperature Sensor (DTS) open Replace
Initiates but relay DR drops out Low line voltage Section 3.4
Initiates but does not defrost Heater contactor or coil defective Replace
Heater(s) burned out Section 7.11
6–3 T-370
6.9 Microprocessor Malfunction
Condition Possible Cause Remedy / Reference
Will not control Software incorrect and/or controller Check
configuration incorrect
Sensor defective Section 7.22
Wiring defective Check
Refrigerant charge low Section 7.2.6
T-370 6–4
6.12 High Pressure Expansion Valve (HPXV) Malfunction
Condition Possible Cause Remedy / Reference
High discharge pressure High Pressure Expansion Valve (HPXV) coil not Section 7.15.2
seated properly, loose, or not fully engaged.
Software incorrect or controller configuration Check
incorrect
Discharge Pressure Transducer (DPT) failed Replace
Filter drier restriction Section 7.10
Gas Cooler Temperature Sensor (GCTS) loose or Check
insufficiently clamped
Gas cooler coil dirty Section 7.8
Gas cooler fan rotating backwards Section 7.9
Gas cooler fan inoperative Section 7.9
HPXV control malfunction Replace
HPXV failed Replace
6–5 T-370
SECTION 7
SERVICE
! CAUTION
Never use air or gases containing oxygen for leak testing or operating refrigerant compres-
sors. Pressurized mixtures of air or gases containing oxygen can lead to explosion.
1 2
3 4
7–1 T-370
! DANGER
Only use manifold gauge sets designed and manufactured for R-744 (CO2) on these units.
NOTE
To completely open the system the Economizer Solenoid Valve (ESV), Unloader Solenoid Valve
(USV), and High Pressure Expansion Valve (HPXV) must be opened. See Section 7.2.4 for
procedure.
T-370 7–2
7.2.3 Removing Service Gauges
NOTE
As the coupling knobs of the connector valves are being closed, a small pocket of CO2 refrigerant is
isolated inside the connector which makes it difficult to remove. On the last turn of the valve, a vent
opens which releases this trapped refrigerant.
4. With both service couplings closed, connect a hose to the center port of the manifold gauge set.
5. Make sure the open end of the hose is pointed in a safe direction, and slowly open the manifold gauge set
high and low side hand valves to allow the hose pressure to be released.
7.2.4 Manually Opening Solenoid Valves and High Pressure Expansion Valve
During system evacuation and refrigerant charging, both solenoid valves (ESV, USV) and the High Pressure
Expansion Valve (HPXV) must be open. This ensures the removal of pockets of refrigerant throughout the system,
and allows a complete system evacuation and dehydration. All valves will be reset upon system start up.
For location of the ESV, USV, and HPXV, see Section 3.1.4.
! CAUTION
Opening the Manifold Gauge Valve wide open quickly can cause excessive noise and possible
loss of the system oil charge.
7–3 T-370
To service any component that is part of the pressurized system, it is required to first remove the refrigerant charge.
To completely open the system the Economizer Solenoid Valve (ESV), Unloader Solenoid Valve (USV), and High
Pressure Expansion Valve (HPXV) must be opened. See Section 7.2.4.
1. Connect the service gauge, by following the procedure for Connecting Service Gauges. See Section 7.2.2.
The gauge will show the system pressure.
2. Once the manifold gauge set is properly connected and open to the system, connect the utility hose to the
center port of the manifold gauge set if not already connected.
3. Secure the utility hose and point in a safe direction.
4. Slowly open the low side and high side of the gauge set to release the refrigerant through the utility hose.
5. After all of the R-744 refrigerant charge has been released from the system and the gauges read 0 psi,
close the manifold gauge set hand valves.
! WARNING
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors.
Pressurized mixtures of air or gases containing oxygen can lead to explosion.
NOTICE
Use only R-744 refrigerant to pressurize the system. Any other gas or vapor will contaminate
the system, and require additional purging and evacuation of the system.
1. If the system is without refrigerant, charge the system with R-744 to full charge on the nameplate. See
Section 7.2.8 for adding refrigerant.
2. Leak-check connections using an R-744 electronic leak detector (part # 07-00529-00). If AR-GLO dye has
been added to the system, a UV torch can also be used to check for signs of leaks.
3. After identifying the leak location, remove the refrigerant charge. See Section 7.2.5.
4. Repair any leaks that were found.
5. Evacuate and dehydrate the unit. See Section 7.2.7. If the unit fails to pull down or maintain a vacuum,
inspect the repair again.
6. Charge the unit. See Section 7.2.8.
7. After the repair is made to the unit (threaded joint or brazed), the joint MUST be leak tested using the R-744
electronic leak tester.
T-370 7–4
6. Test the evacuation setup for any connection leaks by closing the low side and high side service fittings and
drawing a deep vacuum with the vacuum pump and gauge valves open. Shut off the pump and check to see
if the vacuum holds. Repair leaks if necessary.
7. Open the low side and high side service fittings.
8. Start the vacuum pump. Evacuate the unit until the electronic vacuum gauge indicates 2000 microns. Close
the electronic vacuum gauge and vacuum pump valves. Shut off the vacuum pump. Wait a few minutes to
be sure the vacuum holds.
9. Break the vacuum with clean dry CO2 (R-744) refrigerant. Raise system pressure to roughly 0.14 bar (2
psig), monitoring it with the compound gauge.
10. Evacuate unit to 500 microns.
11. Close the electronic vacuum gauge and vacuum pump valves. Shut off the vacuum pump. Wait five minutes
to see if vacuum holds. This procedure checks for residual moisture and/or leaks.
12. With a vacuum still in the unit, the refrigerant charge may be drawn into the system from a refrigerant
container on a weight scale.
7.2.8 Charging, Vapor Method
NOTICE
Only use Refrigerant R-744 with a Purity level of 99.9% CO2. Refer to nameplate for required charge.
NOTE
In cold ambient temperatures it may be necessary to raise the bottle pressure by warming the cylinder.
This is accomplished by using a cylinder warmer or by moving the cylinder into warm ambient conditions.
NOTE
To completely open the system the Economizer Solenoid Valve (ESV), Unloader Solenoid Valve
(USV), and High Pressure Expansion Valve (HPXV) must be opened. See Section 7.2.4.
1. Evacuate the unit and leave in a deep vacuum. See Section 7.2.7.
2. Place the R-744 cylinder on a scale and connect the utility hose from the service gauge to the pressure
regulator. See Figure 7.2, Figure 7.3 for Evacuation diagram.
3. With the supply valve closed on the regulator, open the valve on the cylinder. The gauge on the regulator will
now show the R-744 cylinder pressure.
4. Purge the utility hose by partially unthreading the hose on the manifold gauge set and opening the supply on
the regulator. Tighten the hose on the gauge and close the supply line.
5. Zero out the scale or note the starting weight.
6. Open the low side and high side hand valves by turning the knobs counterclockwise. See Figure 7.2,
Figure 7.3 for evacuation diagram.
7. Allow the R-744 refrigerant to flow into the unit until the correct weight of refrigerant has been added as
indicated by the scale.
8. If you are unable to get the full charge into the unit based on ambient conditions, the following additional
steps should be taken:
a. Remove magnets and refit coils to ESV, USV and HPXV.
b. Close the high side hand valve on the manifold gauge set.
c. Turn the unit on. The suction side pressure will reduce and the unit will start to draw the remaining refrig-
erant into the system.
9. Close the low side service connection by turning the knob clockwise once desired charge is reached.
10. Close the valve on the R-744 cylinder and bleed out remaining pressure in the utility line by partially
unthreading the hose.
11. Start the unit in cooling mode. Run for approximately 10 minutes to make sure the unit is cooling properly.
12. Remove the gauge set. See Section 7.2.3.
7–5 T-370
Figure 7.2 Refrigeration Evacuation & Charging Diagram - PIDs lower than NT5010
16 15
14
5
1
7 3
8 4
10
2 6
13
11 9 12
T-370 7–6
Figure 7.3 Refrigeration Evacuation & Charging Diagram - PIDs NT5010 and higher
5
16 15
14
7 3
8 9 4
10
2 6
9 12 13
11
7–7 T-370
7.3 Compressor
! WARNING
Make sure power to the unit is OFF and power plug disconnected before replacing the compressor.
! WARNING
Before disassembly of the compressor, be sure to relieve the internal pressure very carefully by
slightly loosening the couplings to break the seal.
NOTICE
Compressor is shipped without oil in the compressor.
3 6 7
NOTE
The service replacement of the compressor is sold without terminal box and cover, service connection,
and Suction Pressure Transducer. The customer should retain these components for use on
replacement compressor.
1. Turn the unit Start-Stop switch (ST) and unit Circuit Breaker (CB-1) Off.
2. Disconnect power to the unit.
3. Remove all refrigerant from the unit. See Section 7.2.5.
4. Locate the compressor terminal box. Tag and disconnect the wiring from the compressor terminals and
remove the compressor terminal box. The terminal box will be used on the new compressor.
5. Loosen the compressor flange mounting bolts, break the seal and then remove the bolts.
6. Remove the compressor mounting bolts.
T-370 7–8
7. Remove the compressor and mounting plate (if compressor has a plate). See Section 3.2 for weight of
compressor.
8. Remove the Suction Pressure Transducer (SPT) from compressor and check operation of switch. See
Section 7.5.1. The SPT will be used on the new compressor.
9. Remove service fittings from the compressor. The service fittings will be used on the new compressor.
10. Place the compressor in a position where it will be convenient to drain the oil. Remove the oil drain plug (see
Figure 7.4) and allow the oil to drain out slowly. The compressor will need to be angled to remove all the oil.
11. Measure the amount of oil drained from the compressor.
12. Add four mls. of AR-GLO 5E dye to the new replacement compressor oil.
13. Pour the equivalent amount of new oil into the suction side flange of the new compressor. See Figure 7.4.
The compressor suction side may need to be elevated for better angle to pour oil in.
NOTICE
When installing service fittings and the Suction Pressure Transducer, a new O-ring must be
installed with each. See Section 7.4 for instructions on installing the O-rings.
14. Install the service fittings with new O-rings on the replacement compressor and torque to 27 Nm (20 ft-lb).
15. Install the SPT with a new O-ring on the replacement compressor and torque to 27 Nm (20 ft-lb).
16. Install the replacement compressor in the unit.
17. Install the compressor mounting bolts and torque to 22.6 Nm (16.67 ft-lb).
18. If replacement compressor has mounting plate, install the compressor plate mounting bolts and torque to
22.6 Nm (16.67 ft-lb).
19. Connect the junction box to the replacement compressor and use the terminal wiring kit to rewire the
compressor. Follow the instructions included with the kit.
20. Install the junction box cover.
21. Install the compressor flanges with new metal gaskets.
22. Install the flange mounting bolts and torque to 36.61 Nm (27 ft-lb).
23. Connect the high side and low side service gauges to the discharge and suction service fittings. See
Section 7.2.2.
24. Dehydrate and evacuate the system to 500 microns (75.9 cm Hg vacuum = 29.90 inches Hg vacuum). See
Section 7.2.7.
25. Charge the unit with refrigerant. See Section 7.2.8.
26. After the unit has been fully charged, remove the service gauges. See Section 7.2.3.
27. Start the unit and check operation.
28. If the compressor is equipped with a sight glass, the oil level should be between 1/4 and 3/4 of the sight
glass while operating.
29. Clean the area below the foot of the compressor with local cleaner and install the icing label on the frame in
front of the compressor (part # 62-66170-00).
7–9 T-370
7.4 O-Ring Installation
7.4.1 Installation
This procedure is intended for all O-ring installations for this unit. A Pressure Relief Valve (PRV) is used for
illustration purposes in this procedure.
1. Place electrical tape around the threads of the component to protect the O-ring from damage during
installation. See Figure 7.5.
2. Apply a small amount of Super O-lube to the O-ring, making sure to coat the entire surface. See Figure 7.6.
3. Slide the O-ring over the tape and onto the component. See Figure 7.7.
4. Remove electrical tape. See Figure 7.8.
Figure 7.5 O-Ring - Electrical Tape Figure 7.7 O-Ring - Slide On O-Ring
T-370 7–10
Figure 7.9 Loctite 55 - Twist Cord Figure 7.12 Loctite 55 - Wrap Cord
3rd 6th
7–11 T-370
7.6 Pressure Transducer
7.6.1 Replacing a Pressure Transducer
For location of the pressure transducers, see Section 3.1.4.
1. Remove the refrigerant charge from the unit. See Section 7.2.5.
2. Disconnect wiring from the pressure transducer.
3. Remove the pressure transducer by turning the assembly counterclockwise.
4. See Section 7.4 for installation of the O-ring on the pressure transducer.
5. Install a new pressure transducer.
6. Evacuate and dehydrate the system. See Section 7.2.7.
7. Recharge the system. See Section 7.2.8.
8. Start the unit, and then verify refrigeration charge.
NOTE
The transducer should be used within 48 hours after cord wrapping.
! DANGER
There are no serviceable parts on a pressure relief valve (PRV). Attempting to repair or alter the
PRV is not permitted. If the PRV has released pressure, the entire PRV must be replaced.
1. Remove the refrigerant charge from the unit. See Section 7.2.5.
2. Remove the pressure relief valve.
3. Verify no contaminants have entered into the orifice.
4. See Section 7.4 for installation of an O-ring on the pressure relief valve.
5. Install a new pressure relief valve using correct torque. Wrench on 1-1/8” hexagon flats only, do not wrench
on round surfaces. See Section 3.3 for torque requirements.
6. Evacuate and dehydrate the system. See Section 7.2.7.
7. Recharge the system. See Section 7.2.8.
8. Start the unit, and then verify refrigeration charge.
NOTE
Use low water pressure when cleaning coils to avoid damage.
! WARNING
Do not open the Gas Cooler fan grille before turning power OFF and disconnecting power plug.
1. Remove the refrigerant charge from the unit. See Section 7.2.5.
2. Remove the Gas Cooler fan grille and side panels.
T-370 7–12
3. Unsolder the (2) Intercooler and (2) Gas Cooler lines.
4. Remove the coil mounting hardware and remove the coil assembly.
5. Install the replacement coil and mounting hardware.
6. Solder the Intercooler and Gas Cooler connections.
7. Leak-check the unit coil connections. See Section 7.2.6.
8. Evacuate and dehydrate the system. See Section 7.2.7.
9. Recharge the system. See Section 7.2.8.
10. Secure fan grille and any panels that may have been removed.
! WARNING
Do not open Gas Cooler fan grille before turning power OFF and disconnecting power plug
The Gas Cooler fan rotates counterclockwise as viewed from front of unit. The fan pulls air through the coil, and
discharges air horizontally through the front of the unit. To replace the motor assembly:
1. Remove the Gas Cooler fan grille.
2. Loosen the two set screws on fan. (Thread sealer has been applied to set screws at installation.)
NOTICE
Do not pull or pry from the outer edge of the fan as this may damage the fan.
3. Remove the fan assembly.
4. Unplug the wiring connector.
5. Mark the location of the fan motor and keep the hardware in the same location for reassembly.
6. Remove motor mounting hardware and replace the motor. It is recommended that new locknuts be used
when replacing the motor.
7. Connect the wiring connector.
8. Install the fan loosely on the motor shaft (hub side in). DO NOT USE FORCE. If necessary, tap the hub only,
not the hub nuts or bolts. Apply “Loctite H” to the (2) fan set screws. Adjust the fan within the venturi so that
the outer edge of the fan is within 2.0 +/- 0.07 mm (0.08” +/- 0.03”) from the outside of the orifice opening.
Spin the fan by hand to check clearance.
9. Secure the fan grille and any panels that may have been removed.
! CAUTION
Do not touch the Filter Drier to check for temperature difference while the unit is operating.
Refer to troubleshooting for when to replace the Filter Drier due to restriction.
NOTE
The Filter Drier should be replaced any time the system is opened up for service.
7–13 T-370
7.11 Evaporator Coil Assembly
The evaporator section, including the coil, should be cleaned regularly. Restrictions in the evaporator coil restrict air
flow through the coil and reduce heat transfer. The preferred cleaning fluid is fresh water or steam. Another
recommended cleaner is Oakite 202 or similar, following manufacturer’s instructions.
The two drain pan hoses are routed behind the Gas Cooler fan motor and compressor. The drain pan line(s) must be
open to ensure adequate drainage.
2
1
T-370 7–14
7.12.2 Megger Testing the Heaters
! WARNING
Always turn OFF the unit circuit breakers, disconnect the main power supply, and perform Lock Out
/ Tag Out before working on moving parts.
All of the checks performed during this procedure should be carried out using a 500v Meg-ohm tester.
1. Connect the ground wire from the insulation tester to a fixed ground point, preferably the ground plate in the
control box.
2. At the load side of the heater contactor, check the insulation resistance to ground.
If readings are > 2 Mohm, then the heaters are operating properly and no action is needed.
If readings are < 1 Mohm, then the faulty heater needs to be identified. Proceed to step 3 for units with a
heater access panel or step 4 for units without a heater access panel.
If readings are between 1 and 2 Mohm, then the heaters need to be re-tested with the following steps:
a. Reconnect the unit to power and power the unit on.
b. Set the unit set point to a minimum of 10°C higher than the current temperature of the container. Allow
the unit to go into heat mode, reach the temperature set point and maintain for 10-15 minutes.
c. Power the unit off. Allow the unit to cool to ambient temperature.
d. Connect the ground wire from the insulation tester to a fixed ground point, preferably the ground plate in
the control box.
e. At the load side of the heater contactor, check the insulation resistance to ground.
If readings are > 1 Mohm, then the heaters are operating properly and no action is needed.
If readings are < 1 Mohm, then the faulty heater needs to be identified. Proceed to step 3 for units with a
heater access panel or step 4 for units without a heater access panel.
3. Identify the faulty heater(s) for units with a heater access panel:
a. Open the access panel and cut out all wire splices to isolate all heaters inside of the unit.
b. Repeat the Megger test on each individual heater. Connect the ground clip to the outer metal sheath of
the heater and the test clip to one of the wires from the same heater.
c. Replace any heater where the readings are < 1 Mohm.
4. Identify the faulty heater(s) for units without a heater access panel:
a. Remove all six connections from the Heater (HR) contactor load side, which splits the six heaters into
three separate pairs.
b. Identify the following three wires: DHTL, DHML, DHBL. There is one from each load connection.
c. Repeat the Megger test on each pair of heaters to identify the faulty heater pair. Connect the ground clip
from the insulation tester to a fixed ground point on the unit, preferably the ground plate in the control
box. Connect the test clip to one of the wires stated above.
d. Test all three wires and replace any heater pair that has readings < 1 Mohm.
5. If the unit is loaded, and the heater can not be immediately replaced, perform the following steps:
a. Identify the wire at the opposite end of the faulty heater pair: DHTL - DHTR, DHML - DHMR, DHBL -
DHBR.
b. Isolate the two wires.
c. Reconnect the remaining good wiring pairs to their original connections.
d. The unit will fail the PTI test P1-0 at the next pre-trip inspection. Repair action can be taken at that time.
6. If the unit is empty, replace the faulty heater:
7–15 T-370
! WARNING
Always turn OFF the unit circuit breakers, disconnect the main power supply, and perform Lock Out
/ Tag Out before working on moving parts.
a. With the heater pair identified, remove the upper back panel inside the container.
b. Identify the center point connection for the heater pair (black wiring from heaters) either against the unit
back wall or in the wiring loom.
c. Cut the splice to separate the two heaters.
d. Carry out a Megger check on the two heaters in the same way as for units with heater panel. Replace
any heater where the Megger readings are < 1 Mohms.
NOTE
If all heaters are above the acceptable limit with the wiring disconnected, then this indicates that the
fault was in one or more of the wire splices that were removed.
e. Remove the hold-down clamp securing the heater(s) to the coil.
f. Verify that the heaters are not hot before handling them.
g. Lift the bent end of the heater (with the opposite end down and away from the coil). Move the heater to
the side enough to clear the heater end support and remove.
h. To install heater, reverse steps.
i. Reconnect all wiring using new splices and heat shrink where needed. The heat shrink MUST have a
'melt-able' liner to ensure that the connections are properly sealed when shrunk. This can be seen as a
'Ring' of melt liner pushed from under the heat shrink at each end of the shrink tube.
NOTE
Failure to use melt liner heat shrink allows moisture to 'wick' up under the heat shrink and cause a
leakage path.
T-370 7–16
Figure 7.16 Evaporator Fan Assembly
4
2
5
3
! WARNING
Always turn OFF the unit circuit breakers, disconnect the main power supply, and perform Lock Out
/ Tag Out before working on moving parts.
1. Remove the upper access panel (see Figure 3.2) by removing mounting bolts and TIR locking device.
Reach inside of unit and remove the Ty-Rap securing the wire harness loop. Disconnect the connector by
twisting to unlock and pulling to separate.
2. Loosen four 1/4-20 clamp bolts that are located on the underside of the fan deck at the sides of the fan
assembly. Slide the loosened clamps back from the fan assembly.
3. Slide the fan assembly out from the unit and place on a sturdy work surface.
7–17 T-370
7.13.3 Assemble the Evaporator Fan Assembly
1. Assemble the motor and plastic spacer onto the stator.
NOTICE
When removing the black nylon evaporator fan blade, care must be taken to assure that the
blade is not damaged. In the past, it was a common practice to insert a screwdriver between
the fan blades to keep it from turning. This practice can no longer be used, as the blade is
made up of a material that will be damaged. It is recommended that an impact wrench be used
when removing the blade. Do not use the impact wrench when reinstalling, as galling of the
stainless steel shaft can occur.
2. Apply Loctite to the 1/4-20 x 3/4 long bolts and torque to 7.9Nm (70 in-lb).
3. Place one 5/8 flat washer on the shoulder of the fan motor shaft. Insert the key in the keyway and lubricate
the fan motor shaft and threads with a graphite-oil solution (such as Never-seez).
4. Install the fan onto the motor shaft. Place one 5/8 flat washer with a 5/8-18 locknut onto the motor shaft and
torque to 40 foot-pounds.
5. Install the evaporator fan assembly in reverse order of removal. Torque the four 1/4-20 clamp bolts to 7.9Nm
(70 in-lb). Connect the wiring connector.
6. Replace access panel making sure that panel does not leak. Make sure that the TIR locking device is
lockwired.
T-370 7–18
Cleaning Procedure:
1. Remove the upper evaporator access panel inside of the unit.
2. Spray the surface with water before applying the cleaning solution. This helps the cleaner work better.
3. Liberally apply the prepared cleaner solution (5 parts water and 1 part cleaner).
4. Allow the cleaner to soak in for 5 to 7 minutes.
5. Assess area for rinsing. Follow all local regulations regarding disposal of waste water.
6. Thoroughly rinse the cleaner and surrounding area, floor, etc. When rinsing where heavy foaming solution is
present, it is very important to take the time to thoroughly rinse the equipment and surroundings.
7. Always rinse the empty coil cleaner bottle, cap tightly and dispose of properly.
7–19 T-370
5. Apply the blue dot on the unit side wall next to the coil indicating that the coil has been inspected and is
seated correctly on the valve body.
6. If a coil is seated incorrectly on a loaded unit once it has been seated properly, power cycle the unit. This
enables the controller to reset the valve to 0% to ensure proper operation going forward.
7. Replace the Filter Drier. See Section 7.10.
8. Evacuate and dehydrate the system. See Section 7.2.7.
9. Recharge the system. See Section 7.2.8.
10. Check unit operation by running Pre-trip. See Section 4.7.
This procedure is to be performed in an effort to ease the troubleshooting of the humidity sensor. When performing
this procedure and while working on the unit, always follow the proper lockout/tagout procedures.
Items Required:
• One 7/16” socket wrench or nut driver.
• One 1/4” socket wrench or nut driver.
• One clean, clear water bottle with a minimum 6 cm (2.5 in) opening and capacity to hold 500 ml (16.9 oz).
• 100 ml (3.4 oz) of fresh water - distilled if available.
• 50 gm of Salt (NaCl).
Procedure:
1. Remove the left Upper Fresh Air Makeup Vent panel.
2. Remove the humidity sensor from the mounting hardware and bring to the front of the access panel.
3. Disconnect the humidity sensor from the harness.
4. Drill a 3 cm (1.25 in) hole in the cap of a bottle.
5. Pour approximately 100 ml (3.4 oz) of water into the empty clean bottle.
6. Add salt to the water until it is present at the bottom of the bottle.
7. Cap the bottle and tape over the drilled hole.
8. Shake the bottle until the salt dissolves and water is saturated.
NOTE
To ensure saturation, add additional salt until it settles at the bottom without dissolving while shaking.
9. Remove the cap and insert the humidity sensor into the bottle through the bottle opening and pull the connector
back through the drilled hole in the cap. Then, secure the cap and seal the wire going through the cap.
T-370 7–20
NOTE
Make sure that the sensor is not at all in contact with the salt water.
Humidity Sensor
10. Allow the saturated salt mixture to settle for approximately ten minutes.
11. Reconnect the humidity sensor to the harness and power the reefer unit on.
12. Press the CODE SELECT key on the keypad.
13. Use the Arrow keys until “Cd17” is displayed then press the ENTER key.
14. This displays the humidity sensor reading. Verify the reading is between 60% and 85% relative humidity.
15. If the humidity sensor display is outside of this range, reconfirm the salt mixture and retest. If not in range,
replace the sensor at the next opportunity.
16. Wipe clean and reinstall the humidity sensor and access panel. Torque the access panel hardware to 69 kg-
cm (60 in.-lbs.) using a crossing pattern similar to the numbering below.
17. If the panel gasket is damaged and needs to be replaced, use the following part numbers:
• 42-00296-01: Standard Panel Gasket
• 42-00823-00: XtendFRESH Panel Gasket
7–21 T-370
7.17.1 Removing / Replacing the ESV or USV Coil
1. Remove the valve coil from the valve. See Figure 7.19.
2. Cut the cable approximately 3 inches (75 mm) from the coil.
3. Connect the new coil wires using butt-splices and heat-shrink tubing.
4. Replace the coil on the valve, make sure that the coil is fully seated.
Solenoid Coil
O-Ring
Solenoid
4. VALVE REMOVAL: The preferred method of removing the solenoid valve is to cut the connection between
the brazed section and the valve, using a small tube cutter. The valve can also be removed by un-brazing
the connection. Then remove the valve. Remove valve.
5. Fit the new solenoid valve into position and braze. Use a wet rag to keep valve cool whenever brazing.
6. Install the O-ring on the valve stem (provided). See Figure 7.19.
7. Press the coil onto the valve stem ensuring that it is pressed all the way down, engaging with the O-ring.
! DANGER
There are no serviceable parts on the flash tank. Attempting to repair the flash tank or welding
on the flash tank vessel is not permitted. If the flash tank should be damaged in any way the
entire flash tank must be replaced.
T-370 7–22
Removing the Flash Tank:
1. Turn unit power off and remove power from the unit.
2. Remove the refrigerant charge from the unit. See Section 7.2.5.
3. Remove flash tank pressure relief valve.
4. Un-braze the tube connections.
5. Remove the bolts securing the flash tank to the unit (4 places).
6. Take out flash tank.
7.19 Controller
NOTICE
The NaturaLINE platform must use the green label controller only (part number 12-55011).
! CAUTION
Do not remove wire harnesses from module unless you are grounded to the unit frame with a
static safe wrist strap.
! CAUTION
Unplug all module connectors before performing arc welding on any part of the container.
The guidelines and cautions provided herein should be followed when handling the modules. These precautions and
procedures should be implemented when replacing a module, when doing any arc welding on the unit, or when
service to the refrigeration unit requires handling and removal of a module.
1. Obtain a grounding wrist strap (Carrier Transicold part number 07-00304-00) and a static dissipation mat
(Carrier Transicold part number 07-00277-00). The wrist strap, when properly grounded, will dissipate any
potential buildup on the body. The dissipation mat will provide a static-free work surface on which to place
and/or service the modules.
2. Disconnect and secure power to the unit.
3. Place strap on wrist and attach the ground end to any exposed unpainted metal area on the refrigeration
unit frame (bolts, screws, etc.).
4. Carefully remove the module. Do not touch any of the electrical connections if possible. Place the module
on the static mat.
5. The strap should be worn during any service work on a module, even when it is placed on the mat.
7–23 T-370
7.19.2 Controller Troubleshooting
A group of test points, TP1 - TP10, are provided on the controller for troubleshooting electrical circuits. See Figure
7.20 and schematic diagram in Section 8.
NOTICE
Use a digital voltmeter to measure AC voltage between TP’s and ground (TP9), except for TP8.
T-370 7–24
7.19.3 Controller Programming Procedure
! CAUTION
The unit must be OFF whenever a programming card is inserted or removed from the controller
programming port.
7–25 T-370
9. Press the Up or Down Arrow key until the display reads the desired model number.
10. Press the ENTER key.
11. When software loading has successfully completed, the display will show the message “COnFG donE”.
If the display has blinking message “Pro FAIL” or “bad 12V”, then a problem has occurred while
loading the software. Place the Start-Stop switch (ST) to “0” to turn unit power off and remove the
card.
12. Place the Start-Stop switch (ST) to “0” to turn unit power off.
13. Remove the PCMCIA card from the programming slot.
14. Place the Start-Stop switch (ST) to “I” to return the unit to normal operation.
15. To confirm the correct model configuration was loaded, use the keypad to bring up function code Cd20. The
model displayed should match the last five digits of the model number listed on the unit nameplate (see
Figure 2.1).
NOTE
The characters will be preset to the container ID already on the controller. If none exist, the default will
be AAAA0000000.
T-370 7–26
3. Place the Start-Stop switch (ST) to “I” to turn unit power on.
4. The display will display the message “SEt UP”.
5. Press the ENTER key on the keypad.
6. The display will read “ruN COnFG”.
7. Press the Up or Down Arrow key until display reads “SEt Id”.
8. Press the ENTER key.
9. The display will show the first letter of the container ID.
10. Press the Up or Down Arrow key to increase or decrease the values. Press ENTER to confirm a value for
the current field and move to the next value. Press CODE SELECT to modify a previous value.
11. When the last value is entered, press the ENTER key to enter the information to the controller. The display
will return to “SEt Id”.
12. Place the Start-Stop switch (ST) to “0” to turn power off.
13. Remove the PCMCIA card from the programming slot.
14. Place the Start-Stop switch (ST) to “I” to return the unit to normal operation.
15. To confirm that the correct container ID was loaded, use the keypad to bring up function code Cd40.
! CAUTION
Use care when cutting wire ties to avoid nicking or cutting wires.
Standard Battery Location (Rechargeable Cells):
1. Turn unit power OFF and disconnect power supply.
2. Disconnect battery wire connector from control box.
3. Slide out and remove old battery and bracket. See Figure 3.5, Item 8.
4. Slide new battery pack and bracket into the control box slot.
5. Reconnect battery wire connector to control box and replace wire ties that were removed.
7–27 T-370
Secure Battery Option (Rechargeable Cells Only):
1. Turn unit power OFF and disconnect power supply.
2. Open control box door and remove both the high voltage shield and clear plastic rain shield (if installed).
3. Disconnect the battery wires from the “KA” plug positions 14, 13, 11.
4. Using Driver Bit, Carrier Transicold part number 07-00418-00, remove the 4 screws securing the display
module to the control box. Disconnect the ribbon cable and set the display module aside.
NOTICE
The battery wires must face toward the right.
5. Remove the old battery from the bracket and clean bracket surface. Remove the protective backing from the
new battery and assemble to the bracket. Secure battery by inserting the wire tie from the back of the
bracket around the battery, and back through the bracket.
6. Reconnect the ribbon cable to display and re-install the display.
7. Route the battery wires from the battery along the display harness and connect the red battery wire and one
end of the red jumper to “KA14,” the other end of the red jumper wire to “KA11,” and the black wire to “KA13.”
8. Replace wire ties that were removed.
Wire
4. Remove the grille and fan assembly. While removing, rotate the fan assembly to in order to expose the
wires. See Figure 7.22.
5. Cut the exposed VFD fan wires and remove the fan assembly.
6. Feed the cut wires through the opening at the back of the fan housing, this is where the new fan wires will be
spliced to the existing wires.
T-370 7–28
3. Rotate the fan assembly and place it back into the fan housing so that the wires are located on top and
completely tucked in behind the fan housing.
4. Place the grille over the fan and secure the fan assembly and grille with the (4) mounting screws.
5. Replace the VFD cover and secure in place with the (8) mounting screws.
6. Restore power to the unit and check the operation of the VFD fan.
! CAUTION
Variable Frequency Drive Electrical Hazard. After disconnecting from power supply, wait seven
(7) minutes before servicing to allow capacitors to completely discharge.
If the VFD fails, the following procedure will bypass VFD control allowing the compressor to operate at one speed.
This will restore limited unit functionality until the VFD can be repaired or replaced.
1. Turn the unit off and disconnect the power cord.
2. Wait a minimum of 7 minutes before servicing the VFD.
3. Remove the (8) screws that secure the VFD cover and remove the cover. The VFD Phase wiring will be
visible in the lower right corner of the box. See Figure 7.23.
Figure 7.23 VFD Phase Wiring
VFU
VFW
VFV
L3
L2
L1
Clamps
7–29 T-370
5. Disconnect the VFD input and output phase wires, leaving the ground wire attached.
Output Power
Input Power
6. Cut the barrels off of the wires using wire cutters and strip back the insulation approximately 0.25”
(6.35mm).
L1 VFU-CP1
L2 VFW-CP2
L3 VFV-CP3
8. Position the heat shrink and crimp the electrical splice connector for all 6 wires mentioned above.
T-370 7–30
9. Locate the following wires to prepare for a two-to-one butt splice electrical connection.
VFV-CP5
VFW-CP4
VFU-CP6
10. Using a hot air gun, shrink the heat shrink tube to insulate all of the electrical butt splice joints.
11. While heating the heat shrink tube for a two-to-one butt splice electrical connection, use a needle-nosed
plier to crimp the heat shrink tube while heating.
7–31 T-370
12. Install wire harness clamps and secure the wires using best practice to prevent damage.
13. Be sure that all the wires are within the VFD and replace the cover and secure with the eight (8) screws.
14. Power up the unit and go to Cd61 to activate the VFD Bypass mode.
15. While Cd61 is visible on the display, press and hold the ALT key for 2 seconds, then press ENTER with the
ALT key still held down. This will lock the code. Press an arrow key to change from ‘OFF’ to ‘Act iV’ and
press ENTER. Press ENTER a second time to lock and activate the limp home mode. Power cycle the unit
to engage limp home mode. To unlock or reset to normal operation the same procedure must be followed.
Cd61 will remain on the display until a valid selection is made, or is manually exited. If the state of limp
home mode is modified, Cd61 will restart the unit after a 30 second hold off.
T-370 7–32
Procedure:
1. Prepare a mixture of clean ice using distilled water in a clean insulated container. If possible, the person
handling should be wearing latex gloves.
a. Crush or chip the ice to completely fill the container. The finer the ice particles, the more accurate the
mixture.
b. Add enough pre-cooled distilled water to fill the container.
c. Stir the mixture for a minimum of 2 minutes to ensure water is completely cooled and good mixing has
occurred.
d. The mixture should generally contain about 85% ice with the distilled water occupying the rest of the
space.
e. Add more ice as the ice melts.
2. Stir the ice water slurry mixture to maintain a temperature of 0°C (32°F).
3. Constantly monitor the temperature of the ice water slurry with your reference thermometer. Ensure that the
temperature of the bath has stabilized. The criterion for stability generally is to take two readings at 1 minute
intervals, and the two readings should be 0°C (32°F).
7–33 T-370
Table 7–2 Sensor Resistance - AMBS, DTS, ETS, RRS, RTS, SRS, STS
°C °F OHMS °C °F OHMS
-40 -40 336,500 6 42.8 24,173
-39 -38.2 314,773 7 44.6 23,017
-38 -36.4 294,600 8 46.4 21,922
-37 -34.6 275,836 9 48.2 20,886
-36 -32.8 258,336 10 50 19,900
-35 -31 242,850 11 51.8 18,975
-34 -29.2 228,382 12 53.6 18,093
-33 -27.4 214,164 13 55.4 17,258
-32 -25.6 200,909 14 57.2 16,466
-31 -23.8 188,545 15 59 15,715
-30 -22.0 177,000 16 60.8 15,002
-29 -20.2 166,360 17 62.6 14,325
-28 -18.4 156,426 18 64.4 13,683
-27 -16.6 147,148 19 66.2 13,073
-26 -14.8 138,478 20 68 12,494
-25 -13 130,374 21 69.8 11,944
-24 -11.2 122,794 22 71.6 11,420
-23 -9.4 115,702 23 73.4 10,923
-22 -7.6 109,063 24 75.2 10,450
-21 -5.8 102,846 25 77 10,000
-20 -4 97,022 26 78.8 9,572
-19 -2.2 91,563 27 80.6 9,164
-18 -0.4 86,445 28 82.4 8,777
-17 1.4 81,644 29 84.2 8,407
-16 3.2 77,139 30 86 8,055
-15 5 72,910 31 87.8 7,720
-14 6.8 68,938 32 89.6 7,401
-13 8.6 65,206 33 91.4 7,096
-12 10.4 61,699 34 93.2 6,806
-11 12.2 58,401 35 95 6,529
-10 14 55,330 36 96.8 6,265
-9 15.8 52,381 37 98.6 6,013
-8 17.6 49,634 38 100.4 5,772
-7 19.4 47,047 39 102.2 5,543
-6 21.2 44,610 40 104.0 5,323
-5 23 42,314 41 105.8 5,114
-4 24.8 40,149 42 107.6 4,914
-3 26.6 38,108 43 109.4 4,723
-2 28.4 36,182 44 111.2 4,540
-1 30.2 34,365 45 113 4,365
0 32 32,650 46 114.8 4,198
1 33.8 31,030 47 116.6 4,038
2 35.6 29,500 48 118.4 3,885
3 37.4 28,054 49 120.2 3,739
4 39.2 26,688 50 122 3,599
5 41 25,396
T-370 7–34
Table 7–3 Sensor Resistance - CPDS
°C °F OHMS °C °F OHMS
-40 -40 849,822 18 64.4 136,705
-38 -36.4 834,450 20 68.0 124,876
-36 -32.8 819,079 22 71.6 114,101
-34 -29.2 803,707 24 75.2 104,352
-32 -25.6 788,336 25 77 100,000
-30 -22.0 772,964 26 78.8 95,585
-28 -18.4 757,593 28 82.4 87,619
-26 -14.8 742,221 30 83.0 80,447
-24 -11.2 726,849 32 89.6 73,931
-22 -7.6 711,478 34 93.2 68,000
-20 -4.0 696,106 36 96.8 62,599
-18 -0.4 680,735 38 100.4 57,657
-16 3.2 665,363 40 104.0 53,200
-14 6.8 649,992 42 107.6 49,117
-12 10.4 620,224 44 111.2 45,367
-10 14.0 563,722 46 114.8 41,965
-8 17.6 507,219 48 118.4 38,840
-6 21.2 450,717 50 122.0 35,991
-4 24.8 403,140 52 125.6 33,369
-2 28.4 365,427 54 129.2 30,967
0 32.0 327,715 56 132.8 28,753
2 35.6 295,834 58 136.4 26,733
4 39.2 267,922 60 140.0 24,867
6 42.8 241,618 62 143.6 23,152
8 46.4 219,659 64 147.2 21,570
10 50.0 198,927 66 150.8 20,827
12 53.6 180,987 68 154.4 20,112
14 57.2 164,687 70 158.0 18,768
16 60.8 149,680 72 161.6 16,375
This procedure explains how to perform a GDP calibration of the supply (STS/SRS) and return (RTS/RRS) sensors
using DataLINE software version 3.1 or higher. The calibration procedure should be conducted in pairs (STS/SRS,
or RTS/RRS) and it is recommended to calibrate before the full pre-trip inspection.
7–35 T-370
! WARNING
Before removing the Supply or Return air sensors from the unit, turn the ON/OFF switch and circuit
breaker to the OFF position. Disconnect the power plug from the unit. Follow proper lockout/tagout
procedures to ensure the power cannot inadvertently be energized. It is important that all
dismantling work is done and tools and personnel are away from the unit before powering on the
unit for calibration.
! WARNING
When performing the Return Air Sensor calibration, disconnect both evaporator motors.
NOTE
Before proceeding with the calibration procedure, ensure that controller software version is up to date
(57xx) and DataLINE version 3.1 or higher is installed onto the download device. Only the latest
DataLINE and controller software will allow users to carry out Good Distribution Practice (GDP)
calibration. Do not downgrade the software after installing the latest software.
NOTE
Before proceeding with the calibration procedure, it is recommended to check the sensors by running
pre-trip P5-0. This test checks the sensor values. If the test fails, identify and correct the faulty sensor
and rerun the test.
Tools Required:
• Socket screwdrivers set
• Phillips screwdriver
• Standard hand tools
• Interrogator cable
• Laptop with DataLINE 3.1 or above installed
• Clean insulated container for distilled water and ice
• A regularly calibrated reference thermometer, recommended to be of accuracy up to 2 decimal places
T-370 7–36
! WARNING
Before powering on the unit, it is important to ensure that all dismantling work is done and tools are
away and service personnel are not working on the unit at the time of power on.
2. Open DataLINE version 3.1 or above. From the DataLINE launch pad, click on the Probe Calibration button
to go to the Probe Calibration screen. A pop-up window will appear reminding the user to ensure proper ice
bath temperature. Click OK to acknowledge.
3. On the Probe Calibration screen, click on the Calibrate Supply sensors or Calibrate Return sensors button.
4. A Location of Service pop-up window will appear. In the appropriate fields, enter the Service Center Name
and Service Center Location where the calibration is being performed. Then, click the Save button. A pop-
up window will appear reminding the user to ensure proper ice bath temperature. Click OK to acknowledge
and remember to maintain the Ice bath at 0°C (32°F).
7–37 T-370
Figure 7.26 DataLINE - Enter Service Information
5. Prepare the ice bath. Refer to the Ice Bath Preparation procedure.
Ensure that the set-up (i.e. ice bath, sensors, reference thermometer) has reached a stable state before
beginning the calibration process. Ensure that the set-up is clean and the reference thermometer is
regularly maintained and calibrated.
6. Place the ice bath in a location near sensors. For Return Sensors, place the ice bath on an elevated
platform (ladder) of appropriate height.
7. Once temperature stability is ensured, submerge the sensors in the ice water slurry. Make certain that the
sensors do not contact the container sides or bottom, or each other. Continuously stir the slurry mixture
during calibration.
8. Ensure that the Ice bath is at 0°C (32°F) using the calibrated reference thermometer. Confirm that the
sensor readings have stabilized and the sensors are within +/- 0.3°C (0.5°F). The readings can be taken
from the Uncal column in the Current Probe Offset Temperatures table.
9. Then, after confirming the sensor readings have stabilized, click on the Start Cal button. After clicking Start
Cal, the process begins automatically and will complete in less than 5 minutes. Continue to stir the ice bath
during testing. Calibration will fail if the stability cannot be achieved or the sensor offset is greater than 0.3°C
(0.5°F).
T-370 7–38
Figure 7.28 DataLINE - Start Cal Button
10. Once the calibration has completed, a pop-up will appear with the message Calibrate Complete. Click OK to
acknowledge and the results will then be displayed on the screen in the Results column.
Calibration will fail if the stability cannot be achieved or the sensor offset is greater than 0.3°C (0.5°F).
The validity of a sensor can be checked by hand warming the sensors to see if there are changes in the
readings on the DataLINE screen. If calibration will not complete, replace and recalibrate the sensors.
Refer to the Sensor Replacement procedure.
11. After completing the calibration event, download a DCX file and check that all of the following information is
captured: service center name, location, the results of the calibration and the offset applied. Ensure that all
the information is captured and the event is considered a success when all the intended sensors in
calibration have passed.
NOTE
If there is “uncal” in the download, it means that the calibration process was not completed.
12. After the completion of the calibration, restore the unit to its original state.
7–39 T-370
7.22.4 Sensor Replacement
1. Turn unit power OFF and disconnect power supply.
NOTICE
Include white date code label when cutting out and removing defective sensors. The label
could be required for warranty returns.
2. Cut cable. Slide the cap and grommet off a bulb type sensor and save for reuse. Do not cut the grommet.
3. Cut one wire of existing cable 40 mm (1-1/2 inches) shorter than the other wire.
4. Cut replacement sensor wires (opposite colors) back 40 mm (1-1/2 inches). See Figure 7.30.
5. Strip back insulation on all wiring 6.3 mm (1/4 inch).
40 mm (1 1/2 in),
Sensor 2 or 3 wires as required
6. Slide a large piece of heat shrink tubing over the cable, and place the two small pieces of heat shrink tubing,
one over each wire, before adding crimp fittings as shown in Figure 7.31.
3 4
! CAUTION
Do not allow moisture to enter wire splice area as this may affect the sensor resistance.
T-370 7–40
12. Slide large heat shrink tubing over both splices and shrink.
13. Position the sensor in unit as shown in Figure 7.31 and re-check sensor resistance.
14. Reinstall the sensor. See Section 7.22.5.
NOTICE
The P5 Pre-Trip test must be run to inactivate probe alarms. See Section 5.8.
1
4
6
3
6 mm (1/4 inch)
7–41 T-370
Figure 7.33 Return Sensor Positioning
1
2 1.50 in.
(38.1cm)
1.00 in.
(25.4cm)
T-370 7–42
1. Remove the refrigerant charge from the unit. See Section 7.2.5.
2. Disconnect wiring from defective transducer.
NOTICE
When removing or installing a transducer from the unit, always use a deep well socket or box
end wrench to prevent crushing of the transducer. Never use an open end wrench (see Figure
7.35). Using an open end wrench will concentrate pressure on only two sides of the transducer
housing which can potentially crush the transducer.
Do NOT Use
Open End!
3. Using a deep well socket or box end wrench, turn the transducer assembly counterclockwise to loosen and
remove the defective transducer.
4. Using a deep well socket or box end wrench, install the new transducer. The torque values for each
transducer are listed below:
• SPT: 25.7-28.5 Nm (19-21 ft-lb)
• DPT and FPT: 9.5-12.2 Nm (7-8 ft-lb)
5. Reconnect the wiring to the new Transducer.
6. Evacuate and dehydrate the system. See Section 7.2.7.
7. Recharge the system. See Section 7.2.8.
8. Start the unit, verify refrigeration charge. See Section 3.6.
! WARNING
Installation requires wiring to the main unit circuit breaker, CB-1. Make sure the power to the unit is
off and power plug disconnected before beginning installation.
1. CB-1 is connected to the power system, see wiring schematic. Ensure that the unit power is off AND that the
unit power plug is disconnected.
2. Open control box and remove low voltage shield. See Figure 7.36. Open the high voltage shield.
3. If using factory provisioned wiring, remove the circuit breaker panel, with circuit breaker, from the control
box. Locate, wires CB21/CIA3, CB22/CIA5 and CB23/CIA7 that have been tied back in the wire harness.
Remove the protective heat shrink from the ends of the wires.
4. Refit the circuit breaker panel.
5. Fit the new CIM into the unit.
6. Attach three wires CB21/CIA3, CB22/CIA5 and CB23/CIA7 to the CIM at connection CIA.
7. Locate connectors CIA and CIB, remove plugs if required, and attach to the module.
8. Replace the low voltage shield.
7–43 T-370
Figure 7.36 Communications Interface Installation
1 2
T-370 7–44
Table 7–4 R-744 Temperature - Pressure Chart
Temp Pressure Temp Pressure
°F °C psig °C °F bar
-18 -27.8 208.3 -29 -20.2 13.76
-16 -26.7 216.5 -28 -18.4 14.26
-14 -25.6 225.0 -27 -16.6 14.77
-12 -24.4 233.8 -26 -14.8 15.29
-10 -23.3 242.7 -25 -13.0 15.83
-8 -22.2 251.9 -24 -11.2 16.38
-6 -21.1 261.3 -23 -9.4 16.94
-4 -20.0 271.0 -22 -7.6 17.51
-2 -18.9 280.9 -21 -5.8 18.10
0 -17.8 291.0 -20 -4.0 18.70
2 -16.7 301.5 -19 -2.2 19.31
4 -15.6 312.1 -18 -0.4 19.94
6 -14.4 323.1 -17 1.4 20.58
8 -13.3 334.2 -16 3.2 21.24
10 -12.2 345.7 -15 5.0 21.91
12 -11.1 357.4 -14 6.8 22.59
14 -10.0 369.5 -13 8.6 23.29
16 -8.9 381.8 -12 10.4 24.01
18 -7.8 394.3 -11 12.2 24.74
20 -6.7 407.2 -10 14.0 25.49
22 -5.6 420.4 -9 15.8 26.25
24 -4.4 433.8 -8 17.6 27.03
26 -3.3 447.6 -7 19.4 27.82
28 -2.2 461.7 -6 21.2 28.63
30 -1.1 476.1 -5 23.0 29.46
32 0.0 490.8 -4 24.8 30.30
34 1.1 505.8 -3 26.6 31.16
36 2.2 521.2 -2 28.4 32.04
38 3.3 536.9 -1 30.2 32.94
40 4.4 552.9 0 32.0 33.85
42 5.6 569.3 1 33.8 34.78
44 6.7 586.0 2 35.6 35.73
46 7.8 603.1 3 37.4 36.70
48 8.9 620.5 4 39.2 37.69
50 10.0 638.3 5 41.0 38.70
52 11.1 656.5 6 42.8 39.72
54 12.2 675.0 7 44.6 40.77
56 13.3 694.0 8 46.4 41.83
58 14.4 713.3 9 48.2 42.92
7–45 T-370
Table 7–4 R-744 Temperature - Pressure Chart
Temp Pressure Temp Pressure
°F °C psig °C °F bar
60 15.6 733.1 10 50.0 44.02
62 16.7 753.2 11 51.8 45.15
64 17.8 773.8 12 53.6 46.30
66 18.9 794.8 13 55.4 47.47
68 20.0 816.2 14 57.2 48.66
70 21.1 838.1 15 59.0 49.87
72 22.2 860.5 16 60.8 51.11
74 23.3 883.3 17 62.6 52.37
76 24.4 906.7 18 64.4 53.65
78 25.6 930.5 19 66.2 54.96
80 26.7 954.9 20 68.0 56.29
82 27.8 979.8 21 69.8 57.65
84 28.9 1005.4 22 71.6 59.03
86 30.0 1031.6 23 73.4 60.44
88 31.1 ** 24 75.2 61.88
25 77.0 63.34
26 78.8 64.84
27 80.6 66.36
28 82.4 67.92
29 84.2 69.51
30 86.0 71.14
31 87.8 71.80
32 89.6 ****
** 87.8°F is the Critical point of CO2, Pressure 1056.2psig. Distinct liquid and vapor states do not exist.
**** 31.1°C is the Critical point of CO2, Pressure 72.82Bar. Distinct liquid and vapor states do not exist.
T-370 7–46
7.27 Bolt Torque Values
Table 7–5 Recommended Bolt Torque Values (Dry, Non-Lubricated for 18-8 Stainless Steel)
Bolt Diameter Threads In-Lb Ft-Lb Nm
Free Spinning
#4 40 5.2 0.4 0.6
#6 32 9.6 0.8 1.1
#8 32 20 1.7 2.3
#10 24 23 1.9 2.6
1/4 20 75 6.3 8.5
5/16 18 132 11 14.9
3/8 16 240 20 27.1
7/16 14 372 31 42
1/2 13 516 43 58.3
9/16 12 684 57 77.3
5/8 11 1104 92 124.7
3/4 10 1488 124 168.1
Non Free Spinning (Locknuts etc.)
1/4 20 82.5 6.9 9.3
5/16 18 145.2 12.1 16.4
3/8 16 264 22.0 29.8
7/16 14 409.2 34.1 46.2
1/2 13 567.6 47.3 64.1
9/16 12 752.4 62.7 85
5/8 11 1214.4 101.2 137.2
3/4 10 1636.8 136.4 184.9
7–47 T-370
SECTION 8
ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS
Figure 8.1 Schematic Legend
8–1 T-370
Figure 8.2 Schematic Diagram - Standard Unit Configuration
T-370 8–2
Figure 8.3 Unit Wiring Diagram - Standard Unit Configuration Sheet 1 of 2
8–3 T-370
Figure 8.4 Unit Wiring Diagram -Standard Unit Configuration - Sheet 2 of 2
T-370 8–4
SECTION 9
EU DECLARATION OF CONFORMITY
EU Declaration of Conformity
EU-Konformitätserklärung / EU Overensstemmelseserklæring
Declare, under our sole responsibility, that the NaturaLINE Container Unit:
Erklären, eigenverantwortlich, dass die NaturaLINE Container-Einheit / Erklærer, som eneansvarlige, at Natu-
raLINE Container enhed:
This PED assembly contains the following equipment which was subject to its own CE Marking:
Diese PED-Baugruppe enthält die folgenden Geräte, die ihrer eigenen CE-Kennzeichnung unterliegen / Denne
PED-montering indeholder følgende udstyr, der er underkastet egen CE-mærkning:
9–1 T-370
The following Harmonized Standards were applied for this equipment:
Folgende harmonisierte Normen wurden für diese Geräte angewendet/ Følgende harmoniserede standarder
blev anvendt til dette udstyr:
Machinery Directive EMC Directive RED Directive / RED Richtlinie PED Directive
Maschinenrichtlinie / EMV Richtlinie / EMC (with select options / Mit bestimmten Aus- Druckgeräte-Richt-
Maskindirektiv direktiv wahlmoeglichkeiten // med valgmuligheder) linie / PED-direktiv
EN ISO 12100:2010 EN 61000-6-4:2007 EN/IEC 60950:2011, EN 62311:2008 EN 378-2:2016
EN 60204-1:2006 EN 61000-6-2:2005 EN 300 328 v2.1.1, EN 300 440 v2.1.1
EN 13857:2008 EN 55011:2009 EN 301 511 v12.5.1, EN 301 908-1 v11.1.1
EN 301 489-1 v2.1.1, EN 301 489-3 v2.1.1
EN 301 489-17 v3.1.1, EN 301 489-52 v1.1.0
The following technical standard was applied for this equipment / Folgende technische Norm wurde für diese
Geräte angewendet// Følgende Tekniske standarder blev anvendt til dette udstyr: ISO 1496-2:2008
Shaun Bretherton
Service Engineering Manager of CTL Rotterdam
Pittsburgstraat 21 3047 BL Rotterdam, Netherlands
Carrier Transicold Division, Carrier Corporation Part no. / Teilenr: 62-10144-114 Rev F
P.O. Box 4805 Syracuse, New York 13221 USA English / Deutsch / Dansk
China RoHS per SJ/T 11364-2014
产品中有害物质的名称及含量
有害物质
铅 汞 镉 六价铬 多溴联苯 多溴二苯醚
部件名称 (Pb) (Hg) (Cd) (Cr (VI)) (PBB) (PBDE)
金属板部件 O O O O O O
塑料部件 O O O O O O
盘管组件 X O O O O O
加热部件 O O O O O O
马达,压缩机与风扇组件 O O O O O O
温度控制微处理器系统 X O O O O O
断路器与接触器 O O O O O O
变压器 O O O O O O
传感器 X O O O O O
通讯组件 O O O O O O
阀组件 X O O O O O
电缆线/电源 O O O O O O
电池 O O X O O O
标签与绝缘材料 O O O O O O
玻璃部件 X O O O O O
本表格依据 SJ/T 11364 的规定编制。
O:表示该有害物质在该部件所有均质材料中的含量均在 GB/T 26572 规定的限量要求以下。
X:表示该有害物质至少在该部件的某一均质材料中的含量超出 GB/T 26572 规定的限量要求。
62-66122-00, Rev A
T-370
INDEX
Index–1 T-370
E Feature Descriptions 2–3
Filter Drier Location 3–1
Economized Mode Overview 3–13
Filter Drier Service 7–13
Economized Mode Refrigeration Circuit 3–12 First Aid 1–1
Economizer Solenoid Valve (ESV) Coil Remove and Re- First Stage Discharge Port & Suction Port 3–13
place 7–22
Flash Gas 3–13
Economizer Solenoid Valve (ESV) Economized Mode 3–
13 Flash Tank Component Location 3–1
Economizer Solenoid Valve (ESV) Electrical Data 3–11 Flash Tank Description 2–3
Economizer Solenoid Valve (ESV) Frozen Mode Cooling Flash Tank Pressure Relief Valve (PRV) Location 3–3,
4–8 3–4
Economizer Solenoid Valve (ESV) Location 3–3, 3–4 Flash Tank Refrigeration Circuit 3–12
Economizer Solenoid Valve (ESV) Refrigeration Circuit Flash Tank Remove and Replace 7–22
3–12 Flash Tank Section Components 3–6
Economizer Solenoid Valve (ESV) Remove and Replace Fresh Air Makeup Vent 3–1
7–22 Fresh Air Makeup Vent Adjustment 5–1
Economizer Solenoid Valve (ESV) Service 7–21 Fresh Air Makeup Vent Panel Location 3–1
Electrical Data 3–10 Frozen Mode Cooling Sequence of Operation 4–8
Electronic Expansion Valve (EEV) Location 3–2 Frozen Mode Overview and Temperature Control 4–7
Electronic Expansion Valve (EEV) Nominal Resistance Fuses 3–11
3–11
Electronic Expansion Valve (EEV) Operation 3–13 G
Electronic Expansion Valve (EEV) Refrigeration Circuit
3–12 Gas Cooler / Intercooler Coil 2–3, 7–12
Electronic Expansion Valve (EEV) Service 7–19 Gas Cooler / Intercooler Coil Cleaning 7–12
Electronic Expansion Valve (EEV) Stepper Motor 3–13 Gas Cooler / Intercooler Coil Replacement 7–12
Electronic Expansion Valve (EEV) Superheat 3–8 Gas Cooler / Intercooler Description and Location 3–6
Electronic Leak Detector 7–4 Gas Cooler / Intercooler Fan Motor 4–8
Evacuation and Dehydration 7–4 Gas Cooler / Intercooler Grille 2–4
Evaporator Cleaning 7–18 Gas Cooler Fan And Motor Assembly 7–13
Evaporator Coil and Coil Heaters Location 3–2 Gas Cooler Fan Location 3–1
Evaporator Coil Assembly 7–14 Gas Cooler Fan Motor Electrical Data 3–10
Evaporator Coil Heater Remove and Replace 7–14 Gas Cooler Temperature Sensor (GCTS) Location 3–3,
3–4
Evaporator Coil Heaters 7–14
General Description 3–1
Evaporator Coil Heaters Electrical Data 3–10
General Safety Notices 1–1
Evaporator Coil Remove and Replace 7–14
Evaporator Description 2–3 Generator Protection 4–11
Evaporator Fan And Motor Assembly 7–16
Evaporator Fan Assembly Procedure 7–18 H
Evaporator Fan Disassembly Procedure 7–17 Handles 2–4
Evaporator Fan Motors (EM) 4–8 Handling Modules 7–23
Evaporator Fan Motors (MS) Electrical Data 3–11 Heater Termination Thermostat (HTT) Electrical Data 3–
Evaporator Fan Motors Location 3–2 8
Evaporator Flow Problems 6–4 Heater Termination Thermostat (HTT) Location 3–2
Evaporator Heaters Megger Testing 7–15 High Pressure Expansion Valve (HPXV) Location 3–3,
Evaporator Refrigeration Circuit 3–12 3–4, 7–5
Evaporator Section Components 3–2 High Pressure Expansion Valve (HPXV) Refrigeration
Evaporator Temperature Sensor (ETS1) Location 3–2 Circuit 3–12
Evaporator Temperature Sensor (ETS1) Re-installing 7– High Pressure Expansion Valve (HPXV) Refrigeration
42 Data 3–8
High Pressure Expansion Valve (HPXV) Stepper Motor
3–13
F
High Pressure Switch (HPS) Checking the Switch 7–11
F1, F2, F3A, F3B 3–11 High Pressure Switch (HPS) Location 3–3, 3–4
Failure Action Cd29 4–10 High Pressure Switch (HPS) Refrigeration Data 3–8
T-370 Index–2
High Pressure Switch (HPS) Replacing the Switch 7–11 Pressure Relief Valves (PRV) High Side Location 3–3,
High Pressure Switch (HPS) Service 7–11 3–4
High Speed Contactor (GF) 4–8 Pressure Relief Valves (PRV) Low Side Location 3–3, 3–
Humidity Sensor (HS) Electrical Data 3–11 4
Humidity Sensor (HS) Location 3–2 Pressure Relief Valves (PRV) Service 7–12
Humidity Sensor (HS) Troubleshooting 7–20 Pressure Transducer 7–12
Pre-Trip Diagnosis 5–4
I Pre-Trip Diagnostics 4–12
Pre-Trip Terminating 4–13
Inspect Inside Unit 5–1 Pre-Trip Test Codes 4–47
Interrogator 2–3 Probe Diagnostic Logic 5–6
Interrogator Connector Location 3–2 Protection Modes Of Operation 4–10
Introduction 2–1, 9–1
R
K
R-744 3–9
Keypad 4–1 Refrigerant Charging (Vapor) 7–5
Refrigerant Description 2–1
L Refrigerant Leak Checking 7–4
Labels 2–4 Refrigerant Removing Charge 7–3
Loading Configuration Software 7–25 Refrigerant Service Gauge Set 7–1
Loading Operational Software 7–25 Refrigerant, Charge for R-744 3–9
Lockout / Tagout (LO/TO) 1–6 Refrigeration Circuit Overview 3–12
Refrigeration Circuit Schematic (Air-Cooled) 3–14, 3–15
Refrigeration Circuit Schematic (Water-Cooled) 3–16, 3–
M 17
Maintenance Of Painted Surfaces 7–44 Refrigeration Data 3–8
Maintenance Precautions 1–1 Refrigeration Unit Front Section 3–1
Manifold Gauge Valve 7–3 Remote Monitoring 2–4
Manual Test Operation 4–13 Removing Service Gauges 7–3
Manually Opening Solenoid / Expansion Valves 7–3 Results Reporting 4–13
Micro-Link 3 Controller 4–3 Return Recorder Sensor (RRS) Location 3–2
ML3 Controller 4–3 Return Recorder Sensor (RRS) Re-installing 7–41
Return Temperature Sensor (RTS) DTS Failure 4–10
O Return Temperature Sensor (RTS) Location 3–2
Return Temperature Sensor (RTS) Re-installing 7–41
Observe Unit Operation 5–6
Operating Precautions 1–1
S
Operation Checks 5–1
Operational Software (Cd Function Codes) 4–4 Safety and Protective Devices 3–12
Option Descriptions 2–4 Safety, First Aid 1–1
Optional Features 4–22 Safety, Maintenance Precautions 1–1
Safety, Operating Precautions 1–1
P Sensor Checkout Procedure 7–33
Sensor Replacement 7–40
Perishable Mode Cooling Sequence of Operation 4–5
Service Gauge Set 7–1
Perishable Mode Dehumidification 4–6
Setting the Container ID 7–26
Perishable Mode Dehumidification - Bulb Mode 4–7
Setting the Date and Time 7–26
Perishable Mode Heating Sequence of Operation 4–6
Specific Warning And Caution Statements 1–1
Perishable Mode Overview of Temperature Control 4–5
Standard Mode Overview 3–12
Plate Set 2–3
Standard Mode Refrigeration Circuit 3–12
Power 2–1
Starting the Unit 5–3
Power Cable and Plug 2–4
Start-Stop Switch 5–1, 7–3
Pressure Readout 2–3
Start-Up Inspections, Check Controller Function Codes
Pressure Relief Valves (PRV) Charge Requirements 3–9 5–4
Index–3 T-370
Start-Up Inspections, Complete Inspection 5–4 and Suction 3–13
Start-Up Inspections, DataCORDER Inspection 5–4 Unloader Solenoid Valve (USV) Location 3–1
Start-Up Inspections, Physical Inspection 5–4 Unloader Solenoid Valve (USV) Refrigeration Circuit 3–
Stopping the Unit 5–3 12
Suction (Low) Side Connection 7–1 Unloader Solenoid Valve (USV) Remove and Replace
Suction Pressure Gauge 7–1 7–22
Suction Pressure Transducer (SPT) Location 3–5 Unloader Solenoid Valve (USV) Service 7–21
Suction Pressure Valve 7–1 Upper Fresh Air Makeup Vent 5–2
Supply Recorder Sensor (SRS) Location 3–3, 3–4 USDA Probes Locations 3–2
Supply Recorder Sensor (SRS) Re-installing 7–41 USDA Probes Option Description 2–4
Supply Temperature Sensor (STS) Location 3–3, 3–4 Utility Connection 7–1
Supply Temperature Sensor (STS) Re-installing 7–41
System Start Up 4–5 V
Variable Frequency Drive (VFD) Bypass 7–29
T Variable Frequency Drive (VFD) Cooling Fan Remove
and Replace 7–28
Temperature Control Microprocessor System 4–1
Variable Frequency Drive (VFD) Description 2–3
Temperature Readout, Air 2–3
Variable Frequency Drive (VFD) Electrical Data 3–11
Temperature Readout, Refrigerant 2–3
Variable Frequency Drive (VFD) Fan Remove 7–28
Temperature Sensor Service 7–32
Variable Frequency Drive (VFD) Fan Replace 7–28
Test Point Descriptions 7–24
Variable Frequency Drive (VFD) Location 3–1
Thermometer Port 2–4
Variable Frequency Drive (VFD) Service 7–28
Torque Requirements 3–9
Vent Position Sensor (VPS) Description 2–4
Transducer Service 7–42
Vent Position Sensor (VPS) Electrical Data 3–11
Troubleshooting Abnormal Currents 6–5
Vent Position Sensor (VPS) Location 3–1
Troubleshooting Abnormal Noise Or Vibrations 6–3
Vent Position Sensor (VPS) Operation 5–2
Troubleshooting Abnormal Pressures 6–3
Vent Position Sensor (VPS) Service 7–32
Troubleshooting Abnormal Temperatures 6–5
Troubleshooting Electronic Expansion Valve (EEV) 6–4
Troubleshooting High Pressure Expansion Valve
W
(HPXV) 6–5 Water Pressure Switch (WP) 3–9
Troubleshooting Microprocessor Malfunction 6–4 Water-Cooled Condenser (WCC) Connection 5–3
Troubleshooting No Evaporator Air Flow Or Restricted Water-Cooled Condenser (WCC) Section 3–8
Air Flow 6–4 Wire Harness Connectors 4–3
Troubleshooting Unit Operates Long Or Continuously In
Cooling 6–1
Troubleshooting Unit Runs But Has Insufficient Cooling
6–2
Troubleshooting Unit Will Not Defrost Properly 6–3
Troubleshooting Unit Will Not Heat Or Has Insufficient
Heating 6–2
Troubleshooting Unit Will Not Start Or Starts Then Stops
6–1
Troubleshooting Unit Will Not Terminate Heating 6–2
U
Unit Model Number 2–1
Unit Weight 3–9
Unloaded Mode Overview 3–13
Unloaded Mode Refrigeration Circuit 3–12
Unloader Solenoid Valve (USV) Coil Remove and Repla-
cel 7–22
Unloader Solenoid Valve (USV) Electrical Data 3–11
Unloader Solenoid Valve (USV) First Stage Discharge
T-370 Index–4
Carrier Transicold Division,
Carrier Corporation
P.O. Box 4805
Syracuse, NY 13221 USA
https://www.carrier.com/container-refrigeration