OE Spec DP01500D5S 12V FC TB 50Hz 2 14
OE Spec DP01500D5S 12V FC TB 50Hz 2 14
OE Spec DP01500D5S 12V FC TB 50Hz 2 14
DP01500D5S
380V – 11 kV/50 Hz/Prime/Fuel Consumption Optimized
MTU 12V4000G23/Water Charge Air Cooling
PRODUCT HIGHLIGHTS
// Benefits // Performance Assurance Certification (PAC)
- Low fuel consumtion - Engine-generator set tested to ISO 8528-5 for transient
- Optimized system integration ability response
- High reliability - 75% load factor
- High availability of power - Verified product design, quality and performance integrity
- Long maintenance intervals - All engine systems are prototype and factory tested
APPLICATION DATA➀
// Engine // Liquid Capacity (Lubrication)
➀ All data refers only to the engine and is based on ISO standard conditions (25°C and 100m above sea level).
➁ Values referenced are in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml.
All fuel consumption values refer to rated engine power.
3 / // / DP01500D5S / 50 Hz / 380V - 11kV
// Engine
// Generator
■ NEMA MG1, BS5000, ISO, DIN EN and ■ No load to full load regulation ■ Marathon low voltage generator
IEC standards ■ ±0,25% voltage regulation no load to Leroy Somer generator
■ Self-ventilated full load (please contact your local MTU Onsite
■ Superior voltage waveform ■ Brushless alternator with brushless Energy distribution partner for system
■ Solid state, volts-per-Hertz regulator pilot exciter ratings)
■ 4 pole, rotating field Oversized generator
■ Sustained short circuit current of up Medium voltage generator
to 250% of the rated current for up
to 10 seconds (marathon generator)
Sustained short circuit current of up
to 300% of the rated current for up to
10 seconds (Leroy Somer generator)
// Control Panel
■ Pre-wired control cabinet for easy Basler controller Different expansion modules
application of customized controller Deif controller Remote annunciator
(V1+) ■ Complete system metering Daytank control
Island operation (V2) ■ Digital metering Generator winding temperature
Automatic mains failure operation ■ Engine parameters monitoring
with ATS (V3a) ■ Generator Protection Functions Generator bearing temperature
Automatic mains failure operation ■ Engine protection monitoring
incl. control of generator and mains ■ SAE J1939 engine ECU Differential protection with
breaker (V3b) communications multi-finction protection relay
Island parallel operation of multiple ■ Parametrization software Modbus RTU-TCP gateway
gensets (V4) ■ Multilingual capability
Automatic mains failure operation ■ Multiple programmable contact inputs
with short (< 10s) mains parallel ■ Multiple contact outputs
overlap synchronization (V5) ■ Event recording
Mains parallel operation of a single ■ IP 54 front panel rating with
genset (V6) integrated gasket
Mains parallel operation of multiple
gensets (V7)
// Fuel System
// Mounting System
■ Welded base frame ■ Resilient engine and generator ■ Modular base frame design
mounting
// Exhaust System
Drawing above for illustration purposes only, based an standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.
SOUND DATA
// Consult your local MTU Onsite Energy distributor for sound data.
EMISSIONS DATA
// Consult your local MTU Onsite Energy distributor for emissions data.
www.mtuonsiteenergy.com