Spec Sheet Mtu 16v4000 Ds2250 FC
Spec Sheet Mtu 16v4000 Ds2250 FC
Spec Sheet Mtu 16v4000 Ds2250 FC
Product Highlights
// Benefits // Performance Assurance Certification (PAC)
- Low fuel consumption - Engine-generator set tested to ISO 8528-5 for transient
- Optimized system integration ability response
- High reliability - 85% load factor
- High availability of power - Verified product design, quality and performance integrity
- Long maintenance intervals - All engine systems are prototype and factory tested
// Power
Rating // Certifications
- System ratings: 2260 kVA - 2370 kVA - CE certification option
- Accepts rated load in one step per NFPA 110 - Unit certificate acc. to BDEW (German Grid-Code)
- Generator set complies to G3 according to ISO 8528-5
- Generator set exceeds load steps according to ISO 8528-5
2 / // / MTU 16V4000 DS2250 / 50 Hz / 380V - 11kV
Application data
// Engine // Liquid Capacity (Lubrication)
// Fuel Consumption //
Exhaust System
l/hr g/kwh
At 100% of power rating: 452.23 191 Exhaust gas temp. (after turbocharger): C 485
At 75% of power rating: 342.7 193 Exhaust gas volume: m3/s 5.8
At 50% of power rating: 240.3 203 Maximum allowable back pressure: mbar 85
Minimum allowable back pressure: mbar 30
All data refers only to the engine and is based on ISO standard conditions (25C and 100m above sea level).
Values referenced are in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml.
All fuel consumption values refer to rated engine power.
3 / // / MTU 16V4000 DS2250 / 50 Hz / 380V - 11kV
// Engine
// Generator
4 pole three-phase synchronous Short circuit capability 3xIn for 10sec Leroy Somer low voltage generator
generator Winding and bearing RTDs Marathon low voltage generator
Brushless, self-excited, self-regulating, (without monitoring) Oversized generator
self-ventilated Excitation by AREP Medium voltage generator
Digital voltage regulator Mounting of CTs: 2 core CTs Engine output optimized generator
Anti condensation heater Winding pitch: 2/3 winding
Stator winding Y-connected, Voltage setpoint adjustment 10%
accessible neutral (brought out) Meets NEMA MG-1, BS 5000,
Protection IP23 IEC 60034-1, VDE 0530,
Insulation class H, utilization acc. to H DIN EN 12601, AS1359 and ISO 8528
Radio suppression EN55011, requirements
group 1, cl. B
// Control Panel
Pre-wired control cabinet for easy Basler controller Different expansion modules
application of customized controller Deif controller Remote annunciator
(V1+) Complete system metering Daytank control
Island operation (V2) Digital metering Generator winding temperature
Automatic mains failure operation Engine parameters monitoring
with ATS (V3a) Generator Protection Functions Generator bearing temperature
Automatic mains failure operation Engine protection monitoring
incl. control of generator and mains SAE J1939 engine ECU Modbus TCP-IP
breaker (V3b) communications
Island parallel operation of multiple Parametrization software
gensets (V4) Multilingual capability
Automatic mains failure operation Multiple programmable contact inputs
with short (< 10s) mains parallel Multiple contact outputs
overlap synchronization (V5) Event recording
Mains parallel operation of IP 54 front panel rating with
a single genset (V6) integrated gasket
Mains parallel operation of
multiple gensets (V7)
// Power Panel
Available in 600x600 and 600x1000 Supply for anti condensation heating Supply electrical driven radiator
Phase monitoring relay 230V/400V Plug socket cabinet for 230V from 45kW 75kW (PP 600x1000)
Supply for battery charger compatible Euro/USA
Supply for jacket water heater
Flexible fuel connectors mounted to Switchable fuel filter with Fuel cooler integrated into
base frame water separator cooling equipment
Fuel filter with water separator Switchable fuel filter with
Fuel filter with water separator water separator heavy-duty
heavy-duty Seperate fuel cooler
// Starting/Charging System
// Mounting System
Welded base frame Resilient engine and generator Modular base frame design
mounting
// Exhaust System
Exhaust bellows with connection Exhaust silencer with 30 dB(A) sound Y-connection-pipe
flange attenuation
Exhaust silencer with 10 dB(A) sound Exhaust silencer with 40 dB(A) sound
attenuation attenuation
Drawing above for illustration purposes only, based an standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.
Sound data
// Consult your local MTU Onsite Energy distributor for sound data.
Emissions data
// Consult your local MTU Onsite Energy distributor for emissions data.