MTU 20V4000 DS2750: Diesel Generator Set
MTU 20V4000 DS2750: Diesel Generator Set
MTU 20V4000 DS2750: Diesel Generator Set
Product Highlights
// Benefits // Performance Assurance Certification (PAC)
- Low fuel consumption - Engine-generator set tested to ISO 8528-5 for transient
- Optimized system integration ability response
- High reliability - 75% load factor
- High availability of power - Verified product design, quality and performance integrity
- Long maintenance intervals - All engine systems are prototype and factory tested
// MTU Onsite Energy is a single-source supplier // Complete range of accessories available
- Control panel
// Support - Power panel
- Global product support offered - Circuit breaker/power distribution
- Fuel system
// Standards - Fuel connections with shut-off valve mounted to base frame
- Engine-generator set is designed and manufactured in - Starting/charging system
facilities certified to standards ISO 2008:9001 and - Exhaust system
ISO 2004:14001 - Mechanical and electrical driven radiators
- Generator set complies to ISO 8528 - Medium and oversized voltage alternators
- Generator meets NEMA MG1, BS5000, ISO, DIN EN and
IEC standards // Emissions
- NFPA 110 - Fuel consumption optimized
// Power
Rating // Certifications
- System ratings: 2620 kVA - 2660 kVA - CE certification option
- Accepts rated load in one step per NFPA 110 - Unit certificate acc. to BDEW (German Grid-Code)
- Generator set complies to G3 according to ISO 8528-5
- Generator set exceeds load steps according to ISO 8528-5
2 / // / MTU 20V4000 DS2750 / 50 Hz / 380V - 11kV
Application data➀
// Engine // Liquid Capacity (Lubrication)
// Fuel Consumption➁ //
Exhaust System
l/hr g/kwh
At 100% of power rating: 508.9 192 Exhaust gas temp. (after turbocharger): °C 580
At 75% of power rating: 387.7 195 Exhaust gas volume: m3/s 6.5
At 50% of power rating: 279.6 211 Maximum allowable back pressure: mbar 85
Minimum allowable back pressure: mbar 30
➀ All data refers only to the engine and is based on ISO standard conditions (25°C and 100m above sea level).
➁ Values referenced are in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml.
All fuel consumption values refer to rated engine power.
3 / // / MTU 20V4000 DS2750 / 50 Hz / 380V - 11kV
// Engine
// Generator
■ 4 pole three-phase synchronous ■ Short circuit capability 3xIn for 10sec ■ Leroy Somer low voltage generator
generator ■ Winding and bearing RTDs Marathon low voltage generator
■ Brushless, self-excited, self-regulating, (without monitoring) Oversized generator
self-ventilated ■ Excitation by AREP Medium voltage generator
■ Digital voltage regulator ■ Mounting of CT´s: 2 core CT´s
■ Anti condensation heater ■ Winding pitch: 2/3 winding
■ Stator winding Y-connected, ■ Voltage setpoint adjustment ± 10%
accessible neutral (brought out) ■ Meets NEMA MG-1, BS 5000,
■ Protection IP23 IEC 60034-1, VDE 0530,
■ Insulation class H, utilization acc. to H DIN EN 12601, AS1359 and ISO 8528
■ Radio suppression EN55011, requirements
group 1, cl. B
■ Pre-wired control cabinet for easy Basler controller Different expansion modules
application of customized controller Deif controller Remote annunciator
(V1+) ■ Complete system metering Daytank control
Island operation (V2) ■ Digital metering Generator winding temperature
Automatic mains failure operation ■ Engine parameters monitoring
with ATS (V3a) ■ Generator protection functions Generator bearing temperature
Automatic mains failure operation ■ Engine protection monitoring
incl. control of generator and mains ■ SAE J1939 engine ECU Modbus TCP-IP
breaker (V3b) communications
Island parallel operation of multiple ■ Parametrization software
gensets (V4) ■ Multilingual capability
Automatic mains failure operation ■ Multiple programmable contact inputs
with short (< 10s) mains parallel ■ Multiple contact outputs
overlap synchronization (V5) ■ Event recording
Mains parallel operation of ■ IP 54 front panel rating with
a single genset (V6) integrated gasket
Mains parallel operation of
multiple gensets (V7)
Available in 600x600 and 600x1000 Supply for anti condensation heating Supply electrical driven radiator
Phase monitoring relay 230V/400V Plug socket cabinet for 230V from 45kW – 75kW (PP 600x1000)
Supply for battery charger compatible Euro/USA
Supply for jacket water heater
■ Flexible fuel connectors mounted to Switchable fuel filter with Fuel cooler integrated into
base frame water separator cooling equipment
Fuel filter with water separator Switchable fuel filter with
Fuel filter with water separator water separator heavy-duty
heavy-duty Seperate fuel cooler
■ Welded base frame ■ Resilient engine and generator ■ Modular base frame design
mounting
Exhaust bellows with connection Exhaust silencer with 30 dB(A) sound Y-connection-pipe
flange attenuation
Exhaust silencer with 10 dB(A) sound Exhaust silencer with 40 dB(A) sound
attenuation attenuation
Drawing above for illustration purposes only, based an standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.
Sound data
// Consult your local MTU Onsite Energy distributor for sound data.
Emissions data
// Consult your local MTU Onsite Energy distributor for emissions data.
www.mtuonsiteenergy.com