Carrier 7.5TR

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Physical Data – English

ARZ ARD
UNIT 38AR 007 008 012 014 016 024 028
NOMINAL CAPACITY (Tons) 6 7 1/2 10 12 1/2 15 20 25
OPERATING WEIGHT (lb)
Aluminium Coils (Standard) 300 383 430 676 740 764 1279
Copper Coils (Optional) 352 484 531 822 886 904 1532
SHIPPING DIMENSIONS (in) (W X H X D) (59.2X45.5X39) (72.6X44.25X41.7) 96.5×49×54.3
COMPRESSOR Scroll
Qty 1 2
Oil Charge (oz) 88 90 110 60(ea) 85(ea) 110(ea) 111 (ea)
REFRIGERANT TYPE * R22
**
Operating Charge, Typical (lb) 12 20 22 23/circuit 28/circuit 17.9 /circuit
Shipping Charge (lb) 2.0 3.1 3.1
FINISH Gray
CONDENSER FAN Propeller Type
Qty…RPM 2…850 2…1100 2…1075 2...1100
Diameter 22 in 26 in 30
Nominal Air Flow (Total CFM) 5400 6500 11,000 14500
Watts (Total) 341 570 1460 1500
Motor Horsepower, 1/8 1/4 1/4 1/2 1
CONDENSER COIL (Qty) 2
Face Area (sq ft Total)) 29.2 29.2 50.4
Rows…Fins/in. 1…17 2…17 3…15 3... 16
Storage Capacity (lb)*** 17.3 34.2 48 -
CONTROLS
Pressurerestart Settings (psig)
High Cutout 428 ± 10 428 ± 10
Cut-in 320 ± 20 320 ± 20
Low Cutout 27 ± 3 27 ± 4
Cut-in 44 ± 5 44 ± 7
0
DISCHARGE GAS THERMOSTAT ( F)
Cutout 270 ± 9
Cut-in --- 190 ± 13 ---
PRESSURE RELIEF Liquid Line
Location Suction Line 200
Tempreature 200
PIPING CONNECTION
Qty…Suction 1…1 1/8 1…1 1/8 1…1 3/8 2…1 3/8 2…1 3/8
Qty…Liquid 1… 3/8 1… 3/8 1… 1/2 2… 1/2 2… 5/8
Hot Gas Stub 3/8 -

*Unit is factory-supplied with holding charge only.


**Typical operating charge with 25 ft of interconnecting piping.
***Storage capacity of condenser coil with coil 80% full of liquid R-22 at 95 F.

4
Electrical data
VOLTAGE FAN MOTORS
UNIT NOMINAL COMPRESSOR 1 COMPRESSOR 2 POWER SUPPLY
RANGE* (Qty 2)
SIZE VOLTAGE
38AR V-Ph-Hz FLA LRA
MIN MAX RLA LRA RLA LRA MCA MOCP
(ea) (ea)
208/230-3-60 187 254 22.4 170 -- -- 0.9 1.6 29.125 51.3
460-3-60 418 506 9.51 80 -- -- 0.5 0.9 12.5 20
Z007
380-3-60 342 418 9.51 80 -- -- 0.9 1.6 13 20
400-3-50 360 440 9.43 80 -- -- 0.5 0.9 12.4 20
208/230-3-60 187 254 25.6 190 -- -- 1.5 3.1 33.9 55
460-3-60 418 506 13.5 95 -- -- 0.8 1.6 17.9 30
Z008
380-3-60 342 418 16 135 -- -- 1.5 3.1 21.9 30
400-3-50 360 440 13.5 95 -- -- 0.8 1.6 17.9 30
208/230-3-60 187 254 35.7 237 -- -- 1.5 3.1 46.5 80
460-3-60 418 506 20.7 130 -- -- 0.8 1.6 26.9 45
Z012
380-3-60 342 418 21.4 160 -- -- 1.5 3.1 28.6 45
400-3-50 360 440 20.7 130 -- -- 0.8 1.6 26.9 45
208/230-3-60 187 254 22.4 170 22.4 170 3.6 7.5 65 70
460-3-60 418 506 9.51 80 9.51 80 1.9 -- 28.5 35
D014
380-3-60 342 418 9.51 80 9.51 80 3.6 7.5 32.8 35
400-3-50 360 440 9.43 80 9.43 80 1.7 -- 27.8 30
208/230-3-60 187 254 25.6 190 25.6 190 3.6 7.5 73 80
460-3-60 418 506 13.5 95 13.5 95 1.9 -- 38.5 45
D016
380-3-60 342 418 16 135 16 135 3.6 7.5 49 55
400-3-50 360 440 13.5 95 13.5 95 1.7 -- 38 45
208/230-3-60 187 254 35.7 237 35.7 237 3.6 7.5 98.3 125
460-3-60 418 506 20.7 130 20.7 130 1.9 -- 56.5 70
D024
380-3-60 342 418 21.4 160 21.4 160 3.6 -- 62 70
400-3-50 360 440 20.7 130 20.7 130 1.7 7.5 56 70
208/230-3-60 187 254 45.7 255 45.7 255 5.5 - 125.3 150
D028 460-3-60 418 506 22.9 145 22.9 145 2.8 - 62.9 80
380-3-60 342 418 27.1 155 27.1 155 3.9 - 75.6 90

LEGEND NOTES:
FLA — Full Load Amps 1. The MCA and MOCP values are calculated in
kW — Total Fan Motor Input (kilowatts) accordance with theNational Electrical Code (NEC),
LRA — Locked Rotor Amps Article 440.
MCA — Minimum Circuit Amps per NEC, Section 430-24 2. Motor RLA and LRA values are established in
MOCP — Maximum Overcurrent Protection (amps) accordance with Underwriters’ Laboratories (UL),
RLA — Rated Load Amps (compressor) Standard 1995.

*Units are suitable for use on electrical systems where


voltage supplied to the unit terminals is not below or
above the listed limits.

18