CONTRACT NO.

: 725-C03 CONTRACT TITLE: PRIMARY INFRASTRUCTUE IN CONTRACTOR'S DATE: 29/09/2018


MARDUMAH SUBMITTAL NO.

DOCUMENTS NO.: PREPARED BY: MOHAMMED NAGATY CHECKED BY: SAVAD TS

SUBMITTAL TITLE: VOLUME CONTROL DAMPER Page: __1___ OF _6

SPEC. REF. I.E. REMARK (IDENTIFY ANY


MAT'L SOURCE (MFR
SECTION, PAGE, SPECIFICATION REQUIREMENT PROPOSED MATERIAL DEVIATIONS FM SPECS
SUPPLIER) AND JUSTIFY
NO,, ETC

Manufacturer: VOLUME CONTROL DAMPERS 2.11 Proposed Brand: KBE


SPECS. Section: Proposed Model: KACL020
KBE SAUDI ARABIA L.L.C A. General
15820
Contact Name: Mu'men
DUCT Shahwan Fabricate in accordance with SMACNA HVAC Duct .1
.As per SMACNA Standards .1
ACCESSORIES Telephone : 00966-13- Construction Standards Metal and Flexible and as
PART-2.11. A,B,C 8877894 .indicated
Page 19 & 20 of 30 Mobile : 00966-54-5560990 Duct mounted motor operated and manual .2 Duct mounted motor operated and manual .2
Fax : 00966-13-8876563 dampers used for balancing shall be as shown on dampers used for balancing shall be as shown on
Email: the drawings the drawings
. :Drawing No [email protected] COMPLY with RC
725-320-20UC-ME- Damper frames shall be 130 x 25 x 1.52 mm (16 .3 Please see KBE standard construction for HAT .3 specification
220 Supplier: gage) galvanized steel. Blade axles shall be either 13 channel frame & Flat frame as well as the blades
.SAUDI AIRCON CO or 19 mm stainless steel with stainless steel axles. Model No KACL020
P.O Box 11730 .bearings
Jubail Industrial City 31961
Kingdom of Saudi Arabia Linkage Shall be Stainless steel. Sleeve bearing for .4 Linkage are Galvanized Steel. Blades are having .4
Phone: 01-3-340-8700 linkage shall be Stainless steel. Blade Shall be of bronze bearings. Blade Shall be of Galvanized or
Fax: 01-3-340-8549 Galvanized or stainless steel construction stainless steel construction (dependent on duct
(dependent on duct material ) and shall carry blade .material ) and shall carry blade seals
.seals

WE CERTIFY THAT ALL THE REQUIREMENT OF


THIS SPECIFICATION FOR THE PROPOSED
PRODUCT HAVE BEEN COMPARED, AND THE Q.C .Manager: INTIKHAB ALI
DEVIATIONS FROM THE SPECIFICATION HAVE Name Signature
BEEN SPECIALLY IDENTIFIED.
PM : IYAD GHANNAM
CONTRACT NO.: 725-C03 CONTRACT TITLE: PRIMARY INFRASTRUCTUE IN CONTRACTOR'S DATE: 29/09/2018
MARDUMAH SUBMITTAL NO.

DOCUMENTS NO.: PREPARED BY: MOHAMMED NAGATY CHECKED BY: SAVAD TS

SUBMITTAL TITLE: VOLUME CONTROL DAMPER Page: __2___ OF __6

REMARK (IDENTIFY
SPEC. REF. I.E.
MAT'L SOURCE (MFR ANY DEVIATIONS
SECTION, PAGE, SPECIFICATION REQUIREMENT PROPOSED MATERIAL
SUPPLIER) FM SPECS AND
NO,, ETC
JUSTIFY

Manufacturer: Dampers shall be finished with either hand operated .5 Dampers are finished with Hand Operated quadrant .5
SPECS. Section:
.quadrant or crank lever .or crank lever
15820
KBE SAUDI ARABIA L.L.C
DUCT
Contact Name: Mu'men
ACCESSORIES Shahwan
PART-2.11. A,B,C Telephone : 00966-13- Volume dampers for supply, return and fresh air intake .6 Volume dampers for supply, return and fresh air .6
Page 19 & 20 of 8877894 shall be factory made, opposed blade interlocking type, intake shall be factory made, opposed blade
30 Mobile : 00966-54- multi-blade for duct height 300 mm (12 in.) and larger, interlocking type, multi-blade for duct height 300 mm
5560990 single blade for duct height under 300 mm (12 in.). (12 in.) and larger, single blade for duct height under COMPLY with RC
Fax : 00966-13-8876563 Blades shall be not less than 1.52 mm (16 gage) 300 mm (12 in.). Blades are 1.5 mm (16 gage) galvanized specification
. :Drawing No Email: galvanized steel, maximum 1220 mm (4 ft.) length and steel, maximum 1220 mm (4 ft.) length and 150 mm (6
725-320-20UC- [email protected] 150 mm (6 in.) width, supported on shafts with self in.) width, supported on shafts with self-lubricating
ME-220 lubricating bearings. Frame shall be minimum 3.42 mm bearings. Frame will be minimum 1.5 mm galvanized
(10 gage) galvanized steel. Dampers shall be carefully steel. Dampers shall be carefully fitted and controlled by
Supplier:
.fitted and controlled by locking quadrants .locking quadrants
.SAUDI AIRCON CO
P.O Box 11730
Jubail Industrial City
31961
Kingdom of Saudi Arabia
Phone: 01-3-340-8700
Fax: 01-3-340-8549

WE CERTIFY THAT ALL THE REQUIREMENT


OF THIS SPECIFICATION FOR THE
PROPOSED PRODUCT HAVE BEEN Q.C .Manager: INTIKHAB ALI DATE:
COMPARED, AND THE DEVIATIONS FROM Name Signature
THE SPECIFICATION HAVE BEEN SPECIALLY
IDENTIFIED.
Project Manager: IYAD GHANNAM DATE:
CONTRACT NO.: 725-C03 CONTRACT TITLE: PRIMARY INFRASTRUCTUE IN CONTRACTOR'S DATE: 29/09/2018
MARDUMAH SUBMITTAL NO.

DOCUMENTS NO.: PREPARED BY: MOHAMMED NAGATY CHECKED BY: SAVAD TS

SUBMITTAL TITLE: VOLUME CONTROL DAMPER Page: __3___ OF _6_

REMARK (IDENTIFY
SPEC. REF. I.E.
MAT'L SOURCE (MFR ANY DEVIATIONS
SECTION, PAGE, SPECIFICATION REQUIREMENT PROPOSED MATERIAL
SUPPLIER) FM SPECS AND
NO,, ETC
JUSTIFY

Manufacturer: Dampers used to isolate areas protected by FM 200 .7 Dampers used to isolate areas protected by FM 200 .7
SPECS. Section:
systems or Clean Agent Fire Extinguisher System systems or Clean Agent Fire Extinguisher System
15820 (including but not limited to under floor dampers, return (including but not limited to under floor dampers,
KBE SAUDI ARABIA L.L.C
DUCT Contact Name: Mu'men air duct dampers, supply air dampers, pressurization return air duct dampers, supply air dampers,
ACCESSORIES Shahwan control dampers) shall comply with UL-555S, Leakage pressurization control dampers) shall comply with UL-
PART-2.11. A,B,C Telephone : 00966-13- Class I requirements. When damper is in close position it 555S, Leakage Class I requirements. When damper is in
Page 19 & 20 of 8877894 shall not leak more than 20.23 L/s/m2 at 25 mm wg. and close position it shall not leak more than 20.23 L/s/m2
30 Mobile : 00966-54- not more than 40.48 L/s/m² at 100 mm wg at 25 mm wg. and not more than 40.48 L/s/m² at 100
5560990 mm wg
Fax : 00966-13-8876563 COMPLY with RC
. :Drawing No Email: specification
725-320-20UC- [email protected] B. Single Blade Dampers B. Single Blade Dampers
ME-220 .Fabricate for duct sizes up to 150 x 760 mm (6 x 30 in.) .1 Single Blade will be up 300 height and 1200 mm .1
.width as per SMACNA std
Supplier:
C. Multi-Blade Dampers
Fabricate of opposed blade pattern with maximum .1 Multi-Blade Dampers
.SAUDI AIRCON CO
blade sizes 200 x 1825 mm. Assemble center and edge 1. Fabricate of opposed blade pattern with maximum
P.O Box 11730
crimped blades in prime coated or galvanized channel blade sizes 300 x 1200 mm. Assemble center and edge
Jubail Industrial City
.frame with suitable hardware crimped blades in prime coated or galvanized channel
31961
frame with suitable hardware
Kingdom of Saudi Arabia
Phone: 01-3-340-8700
Fax: 01-3-340-8549

WE CERTIFY THAT ALL THE REQUIREMENT


OF THIS SPECIFICATION FOR THE
PROPOSED PRODUCT HAVE BEEN Q.C .Manager: INTIKHAB ALI DATE:
COMPARED, AND THE DEVIATIONS FROM Name Signature
THE SPECIFICATION HAVE BEEN SPECIALLY
IDENTIFIED.
Project Manager: IYAD GHANNAM DATE:
CONTRACT NO.: 725-C03 CONTRACT TITLE: PRIMARY INFRASTRUCTUE IN CONTRACTOR'S DATE: 29/09/2018
MARDUMAH SUBMITTAL NO.

DOCUMENTS NO.: PREPARED BY: MOHAMMED NAGATY CHECKED BY: SAVAD TS

SUBMITTAL TITLE: VOLUME CONTROL DAMPER Page: __4___ OF __6_

REMARK (IDENTIFY
SPEC. REF. I.E.
MAT'L SOURCE (MFR ANY DEVIATIONS
SECTION, PAGE, SPECIFICATION REQUIREMENT PROPOSED MATERIAL
SUPPLIER) FM SPECS AND
NO,, ETC
JUSTIFY

Manufacturer: Configuration .2
SPECS. Section:
KBE SAUDI ARABIA L.L.C a) Manually operated dampers shall be the opposed
15820 Manually Operated dampers are Opposed blade Type.
Contact Name: Mu'men blade type. Where required, dampers shall be fabricated
DUCT Where required, dampers shall be fabricated with
Shahwan with blades parallel to the longest side of the ductwork in
blades parallel to the longest side of the ductwork in
ACCESSORIES Telephone : 00966-13- .which they are installed
.which they are installed
PART-2.11. A,B,C 8877894
Page 19 & 20 of Mobile : 00966-54- Frames .3
30 5560990 a) Frame shall be fabricated of 760 mm wide by 1.21 mm
Fax : 00966-13-8876563 (18 gage) (minimum) roll-formed galvanized steel or 50
Please see KBE standard construction for Flat Frame for
Email: by 12.7 mm (2 by ½ in.) (Minimum) reinforcing ribs and COMPLY with RC
.your references Model : KACLO20F
. :Drawing No [email protected] .mounting flanges for ease of installation specification
725-320-20UC-
ME-220 Supplier: Blades .4
a) Blades shall be fabricated in accordance with SMACNA
.SAUDI AIRCON CO .recommendation
As per SMACNA recommendation
P.O Box 11730
Jubail Industrial City
31961
Kingdom of Saudi Arabia
Phone: 01-3-340-8700
Fax: 01-3-340-8549

WE CERTIFY THAT ALL THE REQUIREMENT


OF THIS SPECIFICATION FOR THE
PROPOSED PRODUCT HAVE BEEN Q.C .Manager: INTIKHAB ALI DATE:
COMPARED, AND THE DEVIATIONS FROM Name Signature
THE SPECIFICATION HAVE BEEN SPECIALLY
IDENTIFIED.
Project Manager: IYAD GHANNAM DATE:
CONTRACT NO.: 725-C03 CONTRACT TITLE: PRIMARY INFRASTRUCTUE IN CONTRACTOR'S DATE: 29/09/2018
MARDUMAH SUBMITTAL NO.

DOCUMENTS NO.: PREPARED BY: MOHAMMED NAGATY CHECKED BY: SAVAD TS

SUBMITTAL TITLE: VOLUME CONTROL DAMPER Page: __5___ OF __6_

REMARK (IDENTIFY
SPEC. REF. I.E.
MAT'L SOURCE (MFR ANY DEVIATIONS
SECTION, PAGE, SPECIFICATION REQUIREMENT PROPOSED MATERIAL
SUPPLIER) FM SPECS AND
NO,, ETC
JUSTIFY

Manufacturer: Blade Shafts and Bearings .5 Blade Shafts and Bearings


SPECS. Section:
a) Blade shafts shall be 12.7 mm (½ in.) round, hex, or a) Blade shafts shall be 12 mm (0.47 in.) round, square,
15820 square, cadmium plated steel and shall operate in oil or hex, zinc plated steel and shall operate in oil
KBE SAUDI ARABIA L.L.C
DUCT Contact Name: Mu'men impregnated bronze bearings mounted in the damper impregnated bronze bearings mounted in the damper
ACCESSORIES Shahwan frame. Round blade shafts are to be thru-bolted or thru- frame. Round blade shafts are to be thru-bolted or thru-
PART-2.11. A,B,C Telephone : 00966-13- .pinned to the damper blades .pinned to the damper blades
Page 19 & 20 of 8877894
30 Mobile : 00966-54- Linkage .6 Linkage
5560990 a) Linkage shall be cadmium plated steel assembly of a) Linkage shall be cadmium plated steel assembly of
Fax : 00966-13-8876563 interconnecting crack-arms attached to the shaft of each interconnecting crack-arms attached to the shaft of COMPLY with RC
:Drawing No Email: damper blade. This linkage is to be mounted external to each damper blade. This linkage is to be mounted specification
725-320-20UC- [email protected] .the air stream .external to the air stream
ME-220
Seals .7
Supplier:
a) Dampers shall be provided with flexible metal or
.SAUDI AIRCON CO
elastomeric jamb seals. Additionally, an extruded vinyl or Noted –Elastomeric jamb seals
P.O Box 11730
elastomeric edge is required along the length of each
Jubail Industrial City
.blade
31961
Kingdom of Saudi Arabia
Phone: 01-3-340-8700
Fax: 01-3-340-8549

WE CERTIFY THAT ALL THE REQUIREMENT


OF THIS SPECIFICATION FOR THE
PROPOSED PRODUCT HAVE BEEN Q.C .Manager: INTIKHAB ALI DATE:
COMPARED, AND THE DEVIATIONS FROM Name Signature
THE SPECIFICATION HAVE BEEN SPECIALLY
IDENTIFIED.
Project Manager: IYAD GHANNAM DATE:
CONTRACT NO.: 725-C03 CONTRACT TITLE: PRIMARY INFRASTRUCTUE IN CONTRACTOR'S DATE: 29/09/2018
MARDUMAH SUBMITTAL NO.

DOCUMENTS NO.: PREPARED BY: MOHAMMED NAGATY CHECKED BY: SAVAD TS

SUBMITTAL TITLE: VOLUME CONTROL DAMPER Page: __6__ OF __6_

REMARK (IDENTIFY
SPEC. REF. I.E.
MAT'L SOURCE (MFR ANY DEVIATIONS
SECTION, PAGE, SPECIFICATION REQUIREMENT PROPOSED MATERIAL
SUPPLIER) FM SPECS AND
NO,, ETC
JUSTIFY

Manufacturer: Accessories .8 Accessories .8


SPECS. Section:
KBE SAUDI ARABIA L.L.C a) Each damper shall be furnished with a shaft extension, a) Each damper furnished with a shaft extension,
15820 .manual lever and locking quadrant .manual lever and locking quadrant
Contact Name: Mu'men
DUCT Shahwan
ACCESSORIES Telephone : 00966-13- E. End Bearings
PART-2.11. A,B,C 8877894 Except in round ducts 300 mm (12 in.) and smaller, .1
Page 19 & 20 of Mobile : 00966-54- provide end bearings. On multiple blade dampers, Sintered Bronze Bearings
30 5560990 provide oil-impregnated nylon or sintered bronze
Fax : 00966-13-8876563 .bearings
Email: F. Quadrants COMPLY with RC
:Drawing No [email protected] F. Quadrants Provide locking, indicating quadrant regulators on .1 specification
725-320-20UC- Provide locking, indicating quadrant regulators on .1 .single and multi-blade dampers
ME-220 Supplier: .single and multi-blade dampers On insulated ducts, mount quadrant regulators on .2
.SAUDI AIRCON CO On insulated ducts, mount quadrant regulators on .2 .stand-off mounting brackets, bases, or adapters
P.O Box 11730 .stand-off mounting brackets, bases, or adapters 3. Where rod lengths exceed 750 mm (30 in.), provide
Jubail Industrial City Where rod lengths exceed 750 mm (30 in.), provide .3 regulator at both ends.
31961 .regulator at both ends
Kingdom of Saudi Arabia
Phone: 01-3-340-8700
Fax: 01-3-340-8549

WE CERTIFY THAT ALL THE REQUIREMENT


OF THIS SPECIFICATION FOR THE
PROPOSED PRODUCT HAVE BEEN Q.C .Manager: INTIKHAB ALI DATE:
COMPARED, AND THE DEVIATIONS FROM Name Signature
THE SPECIFICATION HAVE BEEN SPECIALLY
IDENTIFIED.
Project Manager: IYAD GHANNAM DATE: