1.0 SECTION I - INTRODUCTION
1.1 GENERAL INFORMATION
Each section of this manual provides basic information and guidelines toensure the proper
application and maintenance of the system.
This manual contain the general description, initial installation & commissioning, operating
information, maintenance information part list,maintenance log sheet, catalogue
cuts/manufacturers manual. Manufacturer/Supplier address, R.C. Specification and as built
drawings forthe whole system.
1.2.2.01 Potable & Fire Water Distribution System Layout and Key plan713-040-20UC-CE-700
1.2.2.02 Potable & Fire Water Distribution System Layout (Sheet 1 of 3) 713-040-20UC-CE-701
1.2.2.03 Potable & Fire Water Distribution System Layout (Sheet 2 of 3)713-040-20UC-CE-702
1.2.2.04 Potable & Fire Water Distribution System Layout (Sheet 3 of 3)713-040-20UC-CE-703
1.2.2.05 Potable & Fire Water Distribution System Miscellaneous Schedules 713-040-20UC-CE-
705
1.2.2.06 Potable & Fire Water Distribution System Fire hydrant, Gate Valve, Marker Post and
Lot Connection Details 713-040-20UC-CE-706
1.2.2.07 Potable & Fire Water Distribution System Pipe bedding, Pipe Sleeve installation and
Pipe Crossing details 713-040-20UC-CE-707
1.2.2.08 Potable & Fire Water Distribution System Tie-In Details 713-040-20UC-CE-708
1.2.3 Catalogue/Cuts/Manual
1.2.3.01 Reinforced Thermosetting Resin Plastic (RTRP} Pipes
1.2.3.02 uPVC Pipes &Fittings
SECTION 2
GENERAL DESCRIPTIONS
2.0 SECTION 2 - GENERAL DESCRIPTION
Ductile Iron Gate Valves are manufactured by AVK Saudi Valve Manufacturing Co. Ltd. With
nominal diameter ranges from ON 200, ON 150, ON 100 .Each valve are fixed with extension
spindle with elevation average of 1.0m to1. 8 m from the ground surface. Specified nominal
working pressure is 16 bar (1598) KPA for this type of material.
AVK dry barrel fire hydrant, high pressure Model 2700 is manufactured by AVK Saudi Valves
Manufacturing Co. Ltd. It is a compression style hydrant that opens against water flow &incorporates
drain valves is opened. The hydrant feature a safety traffic section for easy reinstallation in the event a
vehicle strikes the hydrant.
A total of 21 units AVK hydrant covering the entire site with buried depth ranges from 1200mm up to
2200mm.
Other Features:
Meets or exceeds AWWA (502 latest revision and UL and FM requirements).
High Pressure 200 Psi.
Ductile Iron Nozzle Section, Barrel Section & Base.
Low Weight.
UV-Resistant Polyester coating above ground, epoxy/bitumen coating below ground
Minimum 5 X value bore for high flow rating.
Hydrant removable under pressure from the main valve and up.
Traffic section for easy reinstallation after being knocked-off.
Extensions available in lengths of 6-60 with 6 increments.
SECTION 3
INSTALLATION & COMMISSIONING
3.0 Section 3 - INSTALLATION & COMMISSIONING
SECTION 4
OPERATING INFORMATION
4.0 SECTION 4-OPERATINGINFORMATION
To operate the buried Gate Valve with extension spindle, just openthe cast iron surface box,
color blue with "W" marking usingfabricated wrench & rotate the valve in clockwise direction to
close &Counter clockwise to open the valve
To operate AVK Fire Hydrant, Removedthe hose cap, connect the firehoseto the nozzle & open
it by rotating the top Operating nut in thecounter clockwise rotation using AVK Operating
Wrench.
SECTION 5
MAINTENANCE INFORMATION
5.0 Section 5 - MAINTENANCE INFORMATION
5.1.1 Visually inspect all valves, pipes &fitting for leaks & physically
Integrity
5.1 .2 For Repair and or maintenance work, simply close the isolationValve the affected area using
fabricated wrench by opening thesurface valve box & rotate the isolation valve box in clockwisedirection.
Always keep valve in clean condition.
5.1.3 Fire Hydrant should be visually inspected & kept in a fully closed
position while not in use
Check all valves, pipe fittings for. leaks &Monthly physical condition.
5.3.1 The system should be maintained I inspected regularly. Incase of possible problems occur:
a) Occurrence of leaks-
Usually leaks occurred in the joint fittings of gate valves & pipe joints.Close the entire isolation valve to
prevent water pressure from reaching/replacement in the affected section of fittings.
Commonly applies to external pipes &fitting valves.
b) Valve Malfunction-
Check the water pressure in the system maybe isolation valves are closed, preventing water pressure from
reaching the vaIve in question, Isolation valves should be always open. Valves are factory tested & no
maintenance is required except the gate valve physical condition has been deteriorated for a long time of
service damaged & requires immediate replacement.
c) Fire Hydrant-
A partially open hydrant will jet water through the drain outlets wash away any soil blocking restraining
the hydrant to themain.AVK Fire hydrant is factory tested & lubricated & should be kept in full closed
position while not in use. To test the drainage is by removing one of the hose cap & fill the hydrant with
water place the palm on one hand over the outlet nozzle opening. As the water drain from the hydrant, it
should create a noticeable suction. If this fails, then the drain valve assembly should be removed &
inspected. If the drain valve is clear may be the drain outlet is plugged from outside the fire hydrant&
clearing the drain outlet.
SECTION 6.0
PART LIST
Section Description Page
6.1 Gate Valve
SECTION 7.0
MAINTENANCE LOG SHEET
SECTION 8.0
CATALOGUE/ CUTS/ MANUAL
Section Description Page
SECTION 8.1
Reinforced Thermosetting Resin Plastic
(RTRP) Pipes
SECTION 8.2
UPVC Pipes & Fittings
SECTION 8.3
Flange Adopter & Coupling
SECTION 8.4
Warning Tape
SECTION 8.5
Fire Hydrants
SECTION 8.6
Gate Valves
SECTION 9.0
Manufacturer I Agent Address
SECTION 10
AS-BULIT Drawings
SECTION 11
Copy of Approval of Material used
SECTION 12
TEST REPORT
Section Description Page
12.1 Factory test report
SECTION 12.1
FACTORY TEST REPORT
SECTION 12.2
SITE TEST REPORT
SECTION 13
TECHNICAL SPECIFICATION