2. Check for PVC adopters are provided for cables and male adapter for all PVC conduits
terminating in the panel board.
3. Check the dressing is complete for all the wires in the panel boards
2. With all the appliance connected or the two ends of the conductors shorted and all Switches
switched ON the reading shown on the megger should be zero. If the reading shows infinity then
there is an open circuit. The fault should be traced and rectified.
3. For cables, the extreme ends of any two phase is shorted and when the test is conducted the
reading should be zero if the meter reads infinity or some value of mega ohms then there is a
fault in the cable and it should be rectified. Same procedure shall be repeated for other 3
conductors of the cable.
FOR WIRES;
With the other ends of the circuit conductor open the value should be infinity for all the test. If
the value is zero there is short circuit or the insulation of the wire is damaged and the wire is
changed accordingly.
FOR CABLES: -
For Cables the Megger range should be 1000V, and both the ends of the cable shall be kept open
and test shall be conducted between phases and neutrals as follows:
neutrals as follows:
i.RtoY
ii.RtoB
iii.YtoB
iv.RtoN
V.YtoN
vi.BtoN
all these reading should be infinity, if otherwise the cable ^ores/phases are faulty and should be
rectified.
The test results shall be recorded in a format for Engineers reference and record. The format
shall be submitted to Consultant for approval in advance prior to perform the megger test
operation.