En Cat Fancoils 2013 v4
En Cat Fancoils 2013 v4
En Cat Fancoils 2013 v4
YORK Fan Coil Units from Johnson Controls the only names you need to know for a Fan Coil and terminal unit range to suit all applications, that has no limits, ranging from the most simple commercial space up to penthouse office and apartments. And whatever the challenge Johnson Controls has the experience to provide units that will meet your needs. When it comes to fan Coil Units and other HVAC products the reputation and experience of the manufacturer is as important as the product. Our YORK by Johnson Controls products have a well earned reputation for quality, for the benefit of those specifying, installing and servicing HVAC equipment. We dont rest on our merits though. We are constantly improving our products. We analyse every aspect of our products to make them more energy efficient, whilst maintaining reliability and ease of installation and use.
Catalogue contents
Fan Coil Units
YFCN Fan Coil Unit centrifugal fan YFCN-ECM Fan Coil Unit Inverter with centrifugal fan LASER & LOW BODY Fan Coil Units YEFB Hydro Blower YHK Hydro Cassette YHK-ECM Inverter Hydro Cassette YFCC Coanda Hydro Cassette YFCC-ECM Coanda Hydro Cassette Inverter YHVP Hydro High Wall
Page
8 10 18 28 30 32 36 38 44
6/7
An extensive offering
One of the most versatile ranges of fan coils on the market today. Wall and ceiling mounted units, exposed or concealed with centrifugal fan, are included, and with cooling capacities ranging from 0.6 kW to 9.9 kW. Dramatic electrical consumption reduction of up to 40% comparative to previous models. This is achieved thanks to the supply of all YORK Fan Coil Units equipped with centrifugal fans and electric motors, and with 6 speed motors as standard to offer greater flexibility in the selection of products. E nergy saving brushless motor technology option available. Its combination with a dedicated frequency inverter and unit controller to regulate the fan speed enables higher efficiencies, even at low rotational speeds, lower unit noise, constant speed characteristics and an increase in motor lifetime expectancy. In comparison to the traditional units equipped with asynchronous three-speed-motors, units with brushless motors can obtain a considerable energy saving, by reducing the power consumption by up to 70%. A full range of factory fitted Johnson Controls valve and pre-configured control options is offered. This in addition to a patented wireless control option - offering greater flexibility in the installation of units, with the highest precision in monitoring and maintaining the desired comfort conditions. H igh pressure Blower units are also available. They can offer up to 23kw of cooling at External Static Pressures of up to 250Pa, and are complemented with a full range of options and accessories covering items such as electrical heating battery, air inlet/outlet diffusers and condensate pumps.
Iconography
Wired control
Dry mode
Timer
Auto Restart
Sleep mode
Auto Sweep
Ducted Installation
Air Filter
Wired controls
BR Remote three speeds controller TR BR + Electronic thermostat and Summer/Winter switch ATR Automatic TR DTR Digital Automatic Remote controller TMO 503 SV2 Digital Automatic Remote controller to be mounted in the standard light wall box DRC - DI Centralized controller up to 60 terminals
Infrared control
YFCN is a range of Fan Coil Units that continues the YORK tradition based on high reliability and low noise levels. It is the result of great commitment in terms of energy and resouces to offer a more modern product from every angle, while still delivering the convenience of easy access to the filters in all models. Moreover each version has the same internal structure, identical in both horizontal and vertical models, in order to standardise production and guarantee a greater flexibility in distribution and installation.
Features
New casing, improved aesthetics, suitable for any modern indoor ambient Full range for all needs: 9 sizes suitable for horizontal or vertical mounting with or without casing Wireless control option Low noise operation 3 fan speeds (possible choice between 6 fan speeds) Single piece discharge grid Several coil choices. Single: 3 or 4 rows; Dual: 3 rows cooling & 2 rows heating Electrical heater optional Suction and discharge plenum optional Factory fitted valve (on/off or modulating) and controller packages Painted back panel option 4 available versions in all range: VC = Vertical Discharge with Casing VCB = Vertical Discharge with Casing (floor installation) HC = Horizontal Discharge with Casing CD = Concealed unit without Casing
Selection software
8/9
Technical features
Model 140 240 1.81 1.43 1.01 1.38 1.07 0.74 335 265 186 13.9 9.2 4.9 2.2 1.72 1.18 387 303 208 11.6 7.5 3.9 295 220 145 47 40 30 38 31 21 40 0.18 530 770 225 340 2.57 1.89 1.65 1.9 1.38 1.2 475 349 304 11.5 6.7 5.3 3.07 2.23 1.95 540 392 341 9.2 5.4 4.2 385 270 235 49 40 36 40 31 27 49 0.23 530 985 225 440 3.12 2.28 1.83 2.34 1.68 1.34 576 421 339 15.5 9 6.1 3.76 2.72 2.16 666 480 380 12.2 6.9 4.6 485 335 265 47 39 33 38 30 24 57 0.26 530 985 225 540 4.09 3.25 2.19 3.07 2.4 1.6 757 600 404 31.3 20.8 10.4 4.83 3.81 2.53 848 669 444 25.7 17 8.3 650 495 315 48 41 31 39 32 22 640 4.79 3.86 2.83 3.6 2.86 2.07 884 714 523 36.2 24.8 14.4 5.88 4.69 3.39 1 041 826 595 29.3 19.5 11 760 590 415 52 46 37 43 37 28 88 0.39 530 1 200 225 740 5.58 4.64 3.56 4.23 3.47 2.62 1 032 857 657 27.7 20 12.5 6.71 5.55 4.2 1 183 977 738 23.7 16.9 10.3 925 735 535 56 51 42 47 42 33 103 0.47 530 1 415 225 840 6.47 5.73 4.03 5.06 4.43 3.04 1 201 1 061 746 17.5 14.1 7.6 8.43 7.36 5.06 1 508 1 316 900 14.5 11.4 6.2 1 200 1 020 655 60 56 45 51 47 36 130 0.58 530 1 415 255 940 7.6 6.54 4.88 6.05 5.11 3.72 1 410 1 213 903 23.2 17.8 10.6 10.08 8.53 6.22 1 811 1 526 1 108 19.3 14.8 8.7 1 500 1 210 830 64 58 50 55 49 41 176 0.78 530 1 415 255
max
Total cooling capacity [kW] (1) med min
1.23 1.02 0.67 0.97 0.79 0.51 229 189 126 5.6 4 1.9 1.55 1.27 0.82 275 227 144 4.7 3.3 1.5 220 175 105 45 39 32 36 30 23 33 0.16 530 670 225
max
Sensible cooling capacity [kW] (1) med min
max
Water flow in cooling [l/h] (1) med min
max
Pressure drop in cooling [kPa] (1)
(2)
(2)
(2)
med min
max
Sound power level [dB(A)] med min
max
Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Absorbed current [A] Height Dimensions ** Width Depth (3) med min
(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,5 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397 ** Dimensions refer to the units with casing Data shown is for 4 row cooling version, 2 pipe system. For performance of 3 row cooling version and/or 4 pipe system unit please contact your local Johnson Controls sales office
ECM Technology
Running costs. Energy consumption. Life cycle. These are 3 issues that are becoming more and more important in the choice of Fan Coil Units. With these criteria in mind, Johnson Controls offers the ECM range of FCU.
ECM technology comprises a brushless motor combined to a dedicated electronic device (inverter). In comparison to conventional units equipped with asynchronous three-speed motors, the fancoil and cassette units with brushless motors can obtain a considerable energy saving, by reducing power consumption up to 70%. Air ow rate can be varied in continuous by means of a 0-10 V signal generated both by our controls or by independent controls systems. The continuous air ow control improves the acoustic comfort and allows a more punctual reply to the variation of the thermal loads, enhancing the stability of ambient temperature.
Technology
ECM technology consists of a brushless motor combined with an inverter managed by specific regulators. The controller uses a 0-10 VDC modulating signal to regulate the fan speed. The brushless electric motor is composed of a rotor having permanent magnets, whose magnetic fields interact with the ones produced by the stator winding. The transfer of current is no longer by mechanical commutator (sliding contacts) but by an electronic commutation system: one electronic controller (inverter) powers the motors stator and generates rotating magnetic fields, that in turn determine the rotors speed. Brusless motor develop much less heat than the traditional brushed motors and they have much lower mechanical resistance than the standard asynchronous maintenance. The absence of brushes eliminates also the main source of electromagnetic noise.
Features Brushless motor with inverter. 0-10VDC control signal. Low mechanical resistance and heat gain Continuous regulation of the fan speed. Specifically designed electronic and digital regulators, also for BMS systems. Possibility to manually set the desired three fan speeds (MIN/MED/MAX). Available for fan coil and cassette units.
0.50
1.50
2.50
3.50 kW
10/11
Technical features
Model 230 240 1.88 1.33 0.78 1.44 0.99 0.57 348 245 145 14.8 8 3.2 2.37 1.63 0.94 421 289 165 12.6 6.5 2.6 325 210 115 51 41 30 42 32 21 20.5 530 770 225 430 2.97 2.19 1.42 2.28 1.65 1.04 550 406 262 28.9 17 7.9 3.74 2.7 1.7 665 478 300 23.9 13.8 6.6 2.74 2.11 1.47 238 181 126 13.6 8.5 4.5 515 350 210 51 42 30 42 33 21 25 530 985 225 440 3.19 2.28 1.44 2.41 1.68 1.04 592 421 266 16.1 8.9 4 3.91 2.75 1.7 694 484 298 13.5 7.2 3 505 340 200 51 42 30 42 33 21 25 530 985 225 630 3.99 2.94 1.97 3.11 2.23 1.47 738 544 365 19 11.1 5.5 4.95 3.59 2.35 879 635 415 15.7 9.2 4.5 3.68 2.8 2 317 241 172 4.5 2.8 1.5 735 495 305 54 44 33 45 35 24 32 530 1 200 225 640 4.54 3.2 2.06 3.41 2.35 1.49 839 590 379 33 17.8 8.2 5.6 3.87 2.43 991 681 426 26.9 14.9 6.5 720 475 290 54 44 33 45 35 24 32 530 1 200 225 730 4.98 3.7 2.61 3.84 2.79 1.93 921 684 4.82 32.6 19.4 10.5 6.09 4.47 3.08 1 077 788 542 26.8 16.1 8.4 4.63 3.56 2.65 398 306 228 7.8 4.9 2.9 890 610 400 57 48 37 48 39 28 41 530 1 415 225 740 5.34 3.84 2.62 4.03 2.84 1.91 987 710 484 25.6 14.3 7.3 6.51 4.61 3.09 1 149 812 542 21 11.8 6 875 585 380 57 48 37 48 39 28 41 530 1 415 225 930 6.36 4.86 3.47 5.2 3.83 2.65 1 180 900 642 22.2 13.8 7.6 8.69 6.41 4.45 1 570 1 149 793 18.5 11.4 6.3 5.98 4.62 3.4 514 397 292 12.3 7.8 4.6 1 395 945 605 64 55 44 55 46 35 99 530 1 415 255 940 7.14 5.25 3.61 5.63 4.03 2.71 1 324 972 669 20.8 12.1 6.3 9.39 6.7 4.5 1 685 1 194 796 17 9.9 5.2 1 365 910 575 64 55 44 55 46 35 99 530 1 415 255
max 10v
Total cooling capacity [kW] (1) med 5v min 1v
1.61 1.19 0.74 1.3 0.93 0.56 299 220 137 6.9 4 1.8 2.13 1.53 0.92 383 274 163 5.7 3.4 1.4 1.63 1.23 0.81 140 106 70 4.3 2.6 1.3 330 220 120 51 41 30 42 32 21 20.5 530 770 225
max
Sensible cooling capacity [kW] (1) med min
max
Water flow in cooling [l/h] (1) med min
max
Pressure drop in cooling [kPa] (1)
(2)
(2)
(2)
(3)
(3)
med
min
max
Pressure drop in heating 4 pipes [kPa] (3) med min
max
Air flow [m3/h] med min
max
Sound power level [dB(A)] med min
max
Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Height Dimensions ** Width Depth (4) med min
230 / 1 / 50 + E max mm
mm mm
(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C (4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,5 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397 ** Dimensions refer to the units with casing
Options / Accessories
Compatibility table / Codes
Model Versions Controls for style VC (supplied with separate packaging) Three speed control BL * (1) Three speed control + electronic thermostat and S/W switch TMV-S ** (1) Three speed control + electronic thermostat and centralized S/W - TLC ** (1) Automatic speed control with electronic thermostat and S/W switch ATL ** (1) Controls for style HC/CD (supplied with separate packaging) Remote three speed control BR * (1) Remote three speed control + electronic thermostat CR-T ** (1) Remote three speed control + electronic thermostat and S/W switch TR *** (1) Automatic speed control with electronic thermostat and centralized S/W - ATR *** (1) Automatic remote control with electronic thermostat, S/W swithc and liquid crystall display DTR ** (1) Automatic speed control with electronic thermostat to be mounted in the light wall box TMO-503-S **** (1) Automatic speed control with electronic thermostat to be mounted in the light wall box TMO-503-SV2 **** (1) Electromechanical thermostat T2T (1) YFCN AC motor + Standard control devices VC/VCB mod. - Vertical with casing HC mod. - Horizontal with casing CD mod. - Without casing
Controls accessories for all versions (supplied with separate packaging) Low temperature cut out TME for controls TL, TLC, ATL, ART, TR, DTR Low temperature cut out TMM for controls CR-T, BL, BR, TMV-S Change over 15-25 CH 15-25 Receiving speed selector for centralized control (slave) style VC RECV Receiving speed selectror for centralized control (slave) style HC/CD SEL-CR Receiver (slave) for control DTR RECD Terminal board adaptor kit KIT
Controls for style VC + additional electric resistance (supplied with separate packaging) Three speed control with electronic thermostat and S/W switch TMV-R-IAQ (1) Automatic speed control with electronic thermostat and S/W switch ATL-E ** (1)
9063006 9063004
Controls for style HC/CD + additional electric resistance (supplied with separate packaging) Remote three speed control BR-E * (1) Remote three speed control + electronic thermostat and S/W switch TR-E *** (1) Automatic speed control with electronic thermostat and centralized S/W - ATR-E *** (1) Automatic remote control with electronic thermostat, S/W switch and liquid crystall display DTR ** (1)
WARNING * not to be used with valves ** it can be used with valves and/or low temperature cut-out *** to be used with valves and/or low temperature cut-out. The Winter/Summer switch is manual/centralized in accordance to the position of the J1 Jumper **** low temperature cut-out included (1) denotes JCI TUC0311-2 also suitable for use
Free wireless control system for all YFCN all versions Remote Control FREE-COM Mounted Electronic Board FREE-UPM Not Mounted Electronic Board FREE-UPS Temperature sensor FREE-SEN
12/13
9066332 9066333 9066331E 9066336 9066337 3021203 9066339 9066338 3021293 9025310 9079118 3021290 3021292
MAX 20 m
MAX 20 m
Options / Accessories
Options / Accessories
Compatibility table / Codes
Model Versions Controls accessories for all versions (supplied with separate packaging) Low temperature cut out NTC for controls CR-T-ECM, TMV-T-ECM Change over 15-25 CH 15-25 for controls CR-T-ECM, TMV-T-ECM Model Versions VC/VCB mod. - Vertical with casing Controls for style VC (supplied with separate packaging) Continuous fan speed control with electronic thermostat and S/W switch TMV-T-ECM (1) Controls for style HC/CD (supplied with separate packaging) CR-T-ECM Continuous fan speed control with electronic thermostat and S/W switch (1) UPM-ECM power unit for CR-T-ECM remote control, fitted on the unit (1) UPS-ECM power unit for CR-T-ECM remote control, not fitted on the unit (1) YFCN ECM motor + Standard control devices VC/VCB mod. - Vertical with casing HC mod. - Horizontal with casing CD mod. - Without casing
3021090 9053049
YFCN ECM motor + MB control devices HC mod. - Horizontal with casing CD mod. - Without casing
9060141
Accessories of controls for VC, HC-VCB and CD models (supplied with separate packaging) MB-ECM-M mounted power unit for ECM fan coil (1) MB-ECM-S not mounted power unit for ECM fan coil (1) Wall control T-MB (1) IR remote control and mounted IR receiver RM-RT03 (1) IR remote control and not mounted IR receiver RS-RT03 (1) IR remote control RT03 (1) Mounted IR receiver RM (1) Not mounted IR receiver RS (1) Multifunction wall control up to 60 units PSM-DI (1) T2 sensor (to be used as Change-over or minimum temperature sensor) (1)
9066334 9066335 9066331E 9066336 9066337 3021203 9066339 9066338 3021293 9025310
9066334 9066335 9066331E 9066336 9066337 3021203 9066339 9066338 3021293 9025310
9066334 9066335 9066331E 9066336 9066337 3021203 9066339 9066338 3021293 9025310
Management system for a network of fan coils with MB electronic board Hardware / software supervisory system Net Router S Relay output board SIOS (1) denotes JCI TUC0311-2 also suitable for use
Power input
Power input
Power input
Power input
max 60 Router
max 60 units
MC2 Jumper to be closed Network end
Router-s 03
Power input
Power input
Power input
Power input
max 60 units
MC2 Jumper to be closed Network end
Router-s 02
Power input Outputs for system Power input Outputs for system Power input Outputs for system Power input Outputs for system
max 60 units
MC2 Jumper to be closed Network end
Router-s 01
RS 485
NET
USB-RS 485 converter
14/15
9066560 9060476
-
9060478
330/340
9060484 9060481
730/740 830/840 930/940
9066491E -
130/140
230/240
330/340
430/440
9066611 -
130/140
230/240
330/340
430/440
9060150 6060400 6060402 6060403 6060420 9066535 9060577 9060182 9060192 9066505 9060232 9060103
530/540 630/640
9060151
730/740
9066381 9066441 9066451 9066371 9066361 9066411 9066431 9066421 9066461 9066391 9066401
9066382 9060710 9060720 9066372 9066362 9060750 9060764 9060760 9066462 9060770 9060774
9066383 9060711 9060721 9066373 9066363 9060751 9060765 9060761 9066463 9060771 9060775
9066385 9060712 9060722 9066375 9066365 9060752 9060766 9060762 9066465 9060772 9060776
9066467
9066388 9060714 9060724 9066378 9066368 9060753 9060767 9060763 9066468 9060773 9060777
Options / Accessories
Dimensions
YFCN / YFCN-ECM 130 to 940 (with casing)
VC, VCB and HC models
630
530
All dimensions in mm. Drawings not a scale. Model A B C 130 / 140 670 225 354 230 / 240 770 225 454 330 / 340 985 225 669 430 / 440 985 225 669 530 / 540 1 200 225 884 630 / 640 1 200 225 884 730 / 740 1 415 225 1 099 830 / 840 1 415 255 1 099 930 / 940 1 415 255 1 099
100
100 71 44 125
133
16/17
17 12 A 22 22 12 B 153 10 C
511
12
12 29
All dimensions in mm. Drawings not a scale. Model A B C 130 / 140 374 218 354 230 / 240 474 218 454 330 / 340 689 218 669 430 / 440 689 218 669 530 / 540 904 218 884 630 / 640 904 218 884 730 / 740 1 119 218 1 099 830 / 840 1 119 248 1 099 930 / 940 1 119 248 1 099
71 44
125
133
Dimensions
119
153
153
CML00 (Built in) CMR00 (Wall mounted) Thermostat with manual fan speed and S/W change over
CEL00 (Built in) CER00 (Wall mounted) Thermostat with manual fan speed and automatic change over CEL20 (Built in) CER20 (Wall mounted) Thermostat with auto. fan speed and automatic change over CEL30 (Built in) CER30 (Wall mounted) Thermostat with auto. fan speed and automatic change over for modulating valve
LASER fan coil units are simple and elegant, discreet in their design. High standards of quality and reliability, combined with a wide range of accessories ensure a total solution for all comfort cooling and heating requirements. LOW BODY units are part of the LASER Fan Coils Units family. The reduced height cabinet makes them the ideal solution for new or replacement applications where dimensional limitations apply.
Features
6 speed fan Cabinet factory fitted Valve factory fitted Electrical heater factory fitted Thermal or modulating valve Service valve Option front air intake (LASER) Optional plenum (LASER) ECM inverter option available
Selection software
18/19
Technical features
Model Sizes 110 112 1.64 1.35 1.1 1.37 1.09 0.86 300 244 197 7.1 5 3.4 2.16 1.73 1.35 LASER: YLV, YLV-AF, YLH, YLH-AF, YLIV, YLIV-AF, YLIH, YLIH-AF 114 2.41 2.1 1.75 1.96 1.68 1.36 394 345 284 5.8 4.6 3.3 3.05 2.43 2 216 3.36 2.72 2.24 2.73 2.17 1.74 596 487 398 11.3 9.5 6.5 4.11 3.44 2.75 218 3.58 3.05 2.5 3.14 2.57 2.04 654 553 452 13.6 9.8 6.7 4.95 4.16 3.35 220 4.53 3.75 2.99 3.62 2.91 2.25 802 687 567 24.1 17.4 11.6 5.71 4.65 3.61 222 5.63 4.86 4.24 4.54 3.83 3.27 958 863 741 28.4 21.8 17.2 7.19 6.08 5.25 224 6.57 5.87 4.7 5.2 4.56 3.53 1167 1074 842 18.8 15.5 10.5 7.83 6.94 5.45 226 7.41 6.81 5.61 5.86 5.32 4.26 1306 1224 977 21 18.1 12.8 9.33 8.51 6.86 228 9.50 7.75 6.18 7.71 6.08 4.69 1715 1286 1008 36.9 25.8 17.3 11.80 9.48 7.43
max
Total cooling capacity [kW] (1) med min
1.16 0.99 0.79 0.98 0.82 0.64 201 173 140 3.4 2.8 2 1.57 1.28 1
max
Sensible cooling capacity [kW] (1) med min
max
Water flow in cooling [l/h] (1) med min
max
Pressure drop in cooling [kPa] (1)
(2)
med min
max
(2)
med min
Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397 2.7 2.3 1.7 1.12 1.02 0.79 100 86 71 2 1.6 1.07 239 192 143 48 42 36 38 33 28 46 0.22 538 648 224 6.1 4.7 3.1 1.52 1.31 1.1 163 134 110 4.4 3.4 2.4 328 246 185 50 45 38 40 35 29 48 0.23 538 773 224 4.8 3.7 2.8 2.25 2.06 1.68 199 176 147 8.83 7 6.27 409 336 263 54 49 42 42 38 32 57 0.27 538 898 224 11.9 8.5 5.7 3.38 2.98 2.5 307 259 214 19.3 15.2 11.4 659 495 378 53 48 44 41 36 29 81 0.39 538 1023 224 12.5 9.1 6.3 3.64 3.19 2.7 346 294 241 6.3 5 3.5 780 610 459 56 51 43 43 39 32 86 0.41 538 1148 224 20 14.3 9.5 4.92 4.16 3.38 445 382 318 13 9.7 6.7 906 727 559 54 48 40 41 35 29 107 0.48 614 1273 254 23.5 18 14.2 5.53 4.92 4.36 499 449 386 14.5 11.9 9.6 1117 956 768 60 56 50 47 42 38 156 0.52 614 1273 254 15.5 12.7 8.7 6.92 6.3 5.16 608 562 448 34.1 28.8 20.3 1219 1086 786 58 55 47 45 44 37 147 0.66 614 1523 254 20.5 17.6 12.4 7.18 6.8 5.71 642 604 489 40 36.4 26.8 1374 1253 924 63 60 53 50 47 41 162 0.68 614 1523 254 30.4 21.3 14.3 9.05 7.73 6.34 839 654 525 53.6 40.7 28.6 1795 1210 886 67 60 55 53 45 36 211 0.87 614 1773 254
max
Pressure drop in heating 2 pipes [kPa] (2)
(3)
(3)
(3)
med min
max
Air flow [m3/h] med min
max
Sound power level [dB(A)] med min
max
Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Absorbed current [A] Height Dimensions Width Depth (4) med min
(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C. (4) Sound pressure level in a 100 m3 room, at 1.5 m distance and riverberating time of 0.3 s.
Technical features
Model Sizes 110 112 1.46 1.22 0.97 1.19 0.97 0.75 251 211 168 4 2.9 1.9 2.01 1.69 1.28 LOW BODY: YLVR, YLIVR 114 2.11 1.77 1.42 1.69 1.38 1.09 364 305 246 12.6 9.3 6.3 2.83 2.32 1.83 216 2.72 2.37 1.95 2.16 1.86 1.5 467 409 336 6.9 5.5 3.9 3.64 3.13 2.52 218 3.37 2.95 2.58 2.64 2.29 1.97 580 509 444 18.4 14.6 11.5 4.43 3.83 3.30
max
Total cooling capacity [kW] (1) med min
0.94 0.84 0.69 0.83 0.72 0.57 162 145 119 2.1 1.7 1.2 1.39 1.23 0.98
max
Sensible cooling capacity [kW] (1) med min
max
Water flow in cooling [l/h] (1) med min
max
Pressure drop in cooling [kPa] (1)
(2)
med min
max
(2)
med min
Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397 1.7 1.4 1.0 1.15 1.02 0.83 101 90 73 2.2 1.7 1.2 243 203 149 50 44 37 40 34 27 46 0.22 430 648 254 3.2 2.4 1.6 1.83 1.53 1.22 161 134 107 4.6 3.3 2.2 321 246 178 51 46 39 41 36 29 48 0.23 430 773 254 4.3 3 2 2.43 2.03 1.64 213 177 144 10.5 7.6 5.2 446 343 253 54 49 43 44 39 33 5.6 4.4 3.1 3.27 2.85 2.34 286 250 205 18.9 14.9 10.5 574 470 356 54 48 41 44 38 31 81 0.39 430 1023 254 14.9 11.9 9.3 3.65 3.2 2.8 320 280 245 5.7 4.5 3.6 691 570 470 56 51 44 46 41 34 86 0.42 430 1148 224
max
Pressure drop in heating 2 pipes [kPa] (2)
(3)
(3)
(3)
med min
max
Air flow [m3/h] med min
max
Sound power level [dB(A)] med min
max
Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Absorbed current [A] Height Dimensions Width Depth (4) med min
(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C. (4) Sound pressure level in a 100 m3 room, at 1.5 m distance and riverberating time of 0.3 s.
20/21
LASER 110 2/3/4 rows 2/3/4 rows 2/3 rows 2/3/4 rows 2/3/4 rows 2/3 rows
l l l l l l l l l l l l l l l l l l l l l l l l
112
l l
114
l l
216
l l
218
l l
220
l l
224
l l
226
l l
228
l l
110
112
114
216
218
l l
l l
l l
l l
l l
l l
l l
l l
l l
l l
l l
l l
l l
l l
l l
l l
CBL20 CBL30 J3A2 (2p) J3A2 (4p) J3AM (2p) J3AM (4p) DT (2p) DT (4p) PC WS TM
l l
l l
l l
l l l l l
CSR00 / M9000-PF CMR00 / T125BAC-JS0-E (2 pipes) T125FAC-JS0-E (4 pipes) CER00 CER20 CER30
l l l l
l l l l
l l l l
l l l l
l l l l
l l l l
l l l l
l l l l
l l l l
l l l l
(1) for check compatibility with the models of FCU see compatibility table
Options / Accessories
114 898 624 224 233 174 100 40 280 101 85 538 266 113 48 87 355 50 117 90 47 28 195 219 205 109 20 23 24
216 1023 749 224 233 174 100 40 280 101 85 538 266 113 48 87 355 50 117 90 47 28 195 219 205 109 20 28 30
218 1148 874 224 233 174 100 40 280 101 85 538 266 113 48 87 355 50 117 90 47 28 195 219 205 109 20 31 32
220 1273 999 254 263 174 100 40 356 101 85 614 299 138 53 87 409 50 135 116 47 28 238 252 235 122 20 41 43
222 1273 999 254 263 174 100 40 356 101 85 614 299 138 53 87 409 50 135 116 47 28 238 252 235 122 20 44 46
224 1523 1249 254 263 174 100 40 356 101 85 614 299 138 53 87 409 50 135 116 47 28 238 252 235 122 20 52 54
226 1523 1249 254 263 174 100 40 356 101 85 614 299 138 53 87 409 50 135 116 47 28 238 252 235 122 20 52 54
228 1773 1499 254 263 174 100 40 356 101 85 614 299 138 53 87 409 50 135 116 47 28 238 252 235 122 20 58 61
Q R S T U V V1 W X Y Z kg1 kg2
Dim A B C D E G H J N O P Q R S T U V W X Z kg
110 648 374 254 174 100 170 101 430 245 154 31 47 304 88 87 65 47 84 214 109 20 15
112 773 499 254 174 100 170 101 430 245 154 31 47 304 88 87 65 47 84 214 109 20 17
114 898 624 254 174 100 170 101 430 245 154 31 47 304 88 87 65 47 84 214 109 20 22
216 1023 749 254 174 100 170 101 430 245 154 31 47 304 88 87 65 47 84 214 109 20 23
218 1148 874 254 174 100 170 101 430 245 154 31 47 304 88 87 65 47 84 214 109 20 26
22/23
YLIV-AF & YLIH-AF AF= front air intake V= vertical H= horizontal I= without cabinet
Dim A A1 B C D D1 E F G H I J K L M N O P Q R S T U V V1 W X Y Z kg
110 555 574 374 215 109 128 72 40 280 101 85 505 110 55 349 266 113 48 87 355 50 117 90 47 28 195 219 200 109 20 10
112 680 699 499 215 109 128 72 40 280 101 85 505 110 55 474 266 113 48 87 355 50 117 90 47 28 195 219 200 109 20 13
114 805 824 624 215 109 128 72 40 280 101 85 505 110 55 599 266 113 48 87 355 50 117 90 47 28 195 219 200 109 20 16
216 930 949 749 215 109 128 72 40 280 101 85 505 110 55 724 266 113 48 87 355 50 117 90 47 28 195 219 200 109 20 19
218 1055 1074 874 215 109 128 72 40 280 101 85 505 110 55 849 266 113 48 87 355 50 117 90 47 28 195 219 200 109 20 22
220 1180 1199 999 245 109 128 72 40 356 101 85 581 125 60 974 299 138 53 87 409 50 135 116 47 28 238 252 230 122 20 29
222 1180 1199 999 245 109 128 72 40 356 101 85 581 125 60 974 299 138 53 87 409 50 135 116 47 28 238 252 230 122 20 31
224 1430 1449 1249 245 109 128 72 40 356 101 85 581 125 60 1224 299 138 53 87 409 50 135 116 47 28 238 252 230 122 20 38
226 1430 1449 1249 245 109 128 72 40 356 101 85 581 125 60 1224 299 138 53 87 409 50 135 116 47 28 238 252 230 122 20 38
228 1680 1699 1499 245 109 128 72 40 356 101 85 581 125 60 1474 299 138 53 87 409 50 135 116 47 28 238 252 230 122 20 42
Dim A B C D E G H J K L M N O P Q R S T U V W X Y Z kg
110 555 374 230 108 73 170 101 395 61 349 127 245 154 31 47 304 88 87 65 47 84 214 201 109 20 9
112 680 499 230 108 73 170 101 395 61 474 127 245 154 31 47 304 88 87 65 47 84 214 201 109 20 11
114 805 624 230 108 73 170 101 395 61 599 127 245 154 31 47 304 88 87 65 47 84 214 201 109 20 14
216 930 749 230 108 73 170 101 395 61 724 127 245 154 31 47 304 88 87 65 47 84 214 201 109 20 16
218 1055 874 230 108 73 170 101 395 61 849 127 245 154 31 47 304 88 87 65 47 84 214 201 109 20 19
Features CEL/CER
Dead band for change over 5C or 2C (factory set 2C) Manual fan speeds or automatic (models 20 and 30) Thermostated fan control or continuous fan running Option water sensor WS for change over on coil (for 2 pipes) Led indicated status summer, winter or dead band Temperature setting for 7 to 30C (comfort 20-25C) Plastic pins for limiting temperature range Input for window contact Input for Economy/ occupancy mode Output for remote alarm Filter alarm 600 or 1200 running hours (factory set 1200 hours) With electrical heater post ventilation With Air sensor in the air intake destratification function (CEL only)
CML00 (Built in) CMR00 (Wall mounted) Thermostat with manual fan speed and S/W change over
CEL00 (Built in) CER00 (Wall mounted) Thermostat with manual fan speed and automatic change over CEL20 (Built in) CER20 (Wall mounted) Thermostat with auto. fan speed and automatic change over CEL30 (Built in) CER30 (Wall mounted) Thermostat with auto. fan speed and automatic change over for modulating valve
Compatibility table Thermostats / Valves / Heaters / Parallel connection / Water sensor / Minimum temperature thermostat
Factory fitted thermostat (built in) CSL00 CML00 CEL00 CEL20 CEL30 Fan speed selector Thermostat with manual fan speed and S/W change over Thermostat with manual fan speed, dead band, automatic change over Thermostat with automatic fan speed, dead band, automatic change over Thermostat with automatic fan speed, dead band, automatic change over for modulating valve
l l
Heaters KREL
Water sensor WS
Remote controllers and thermostats (wall mounted) CSR00 / M9000-PF Fan speed selector
l l l l
CMR00 / with manual fan speed and S/W T125BAC-JS0-E (2 pipes) Thermostat T125FAC-JS0-E (4 pipes) change over CER00 CER20 CER30
l
Thermostat with manual fan speed, dead band, automatic change over Thermostat with automatic fan speed, dead band, automatic change over Thermostat with automatic fan speed, dead band, automatic change over for modulating valve Not compatible
Compatible
24/25
Coils and heaters** BA1** KREL** Additional 1 row heating Kit electrical heater with safety thermostat and relay
l l l l l l l l l l l l l l l l l l
Factory fitted thermostat (built in) CSL00 CML00 CEL00 CEL20 CEL30 CBL20 CBL30 Fan speed selector (buit in) Thermostat with manual fan speed and S/W change over Thermostat with manual fan speed, dead band, automatic change over Thermostat with automatic fan speed, dead band, automatic change over Thermostat with automatic fan speed, dead band, automatic change over for modulating valves Parallel connection for ON/OFF valve Parallel connection for modulating valve
l l l l l l l
l l
l l
l l
l l
l l
l l
l l
l l
l l
l l
Remote controllers and thermostats (wall mounted) CSR00 / M9000-PF CMR00 / T125BAC-JS0-E (2 pipes) & T125FAC-JS0-E (4 pipes) CER00 CER20 CER30 Fan speed selector (wall mounted)
l l l l l l l l l l
Thermostat with manual fan speed and S/W change over Thermostat with manual fan speed, dead band, automatic change over Thermostat with automatic fan speed, dead band, automatic change over Thermostat with automatic fan speed, dead band, automatic change over for modulating valves
Valves / Condensate pump / Water sensor / Minimum temperature thermostat (Factory fitted) J3A2 (2p) J3A2 (4p) J3AM (2p) J3AM (4p) DT (2p) DT (4p) PC WS TM 3-way 4-ports on/off valves for 2-pipe systems 3-way 4-ports on/off valves for 4-pipe systems 3-way 4-ports modulating valves for 2-pipe systems 3-way 4-ports modulating valves for 4-pipe systems Shut-off valves for 2-pipe systems (in addition to J3A2/J3AM valves) Shut-off valves for 4-pipe systems (in addition to J3A2/J3AM valves) Condensate pump Water sensor Minimum temperature thermostat
l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l
Feet and panels CP1 ZL1 PPV1 PPH1 Set of painted feet Set of feet + frontal socle Vertical painted back panel Horizontal painted back panel
l l l l l l l l l
Air intake plenum Air intake plenum collars 90 air intake plenum Air intake duct fitting Air delivery plenum with collars 90 air delivery plenum
l l
l l l l l l l l l l l l
Compatible Compatible with conditions Not compatible ** Maximum of rows is indicated in the documentation, the maximum number of rows includes the heating row or electrical heater.
Technical features
Model Sizes 112 114 2.93 2.17 1.04 2.40 1.76 0.84 492 369 180 8.4 4.7 1.6 4.09 2.71 1.27 216 3.86 2.86 1.55 2.92 2.07 1.08 641 498 268 18.1 13.1 5.4 4.80 3.58 1.82 LASER ECM 220 5.06 3.79 2.00 4.08 2.94 1.52 862 642 341 28.3 17.4 5.6 6.41 4.76 2.44 222 6.08 4.48 2.60 5.34 3.84 2.02 1010 760 440 39.2 21.3 7.8 8.55 6.02 3.28 224 7.58 5.32 3.05 6.11 4.11 2.27 1291 910 524 23.0 12.9 4.3 9.10 6.27 3.50 228 (5) 8.10 7.37 4.34 5.96 5.45 3.03 1379 1256 740 29.8 25.0 10.2 9.70 8.28 5.36 112 1.72 1.30 0.62 1.17 1.11 0.47 295 224 106 5.6 3.2 0.9 2.06 1.81 0.80 LOW BODY ECM 114 2.41 1.89 0.93 1.96 1.54 0.74 396 324 160 14.7 10.2 2.9 3.22 2.55 1.20 216 2.98 2.25 1.17 2.44 1.87 0.96 504 387 195 7.8 4.8 1.4 3.98 3.08 1.67
max 9v
Total cooling capacity [kW] (1) med 6v min 3v
2.00 1.52 0.79 1.60 1.21 0.58 343 256 113 8.9 6.0 1.9 2.65 2.02 0.88
max
Sensible cooling capacity [kW] (1) med min
max
Water flow in cooling [l/h] (1) med min
max
Pressure drop in cooling [kPa] (1)
(2)
(2)
Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397 7.3 3.5 1.5 3.13 2.06 1.11 230 180 97 12.7 7.4 2.9 583 379 172 57 46 34 50 40 28 46 623 898 224 13.2 8.7 3.4 3.51 2.80 1.74 315 244 151 23.5 15.8 7.1 710 475 223 53 45 33 47 39 27 40 623 1023 224 23.3 17.6 4.4 5.59 4.20 2.32 482 365 227 15.8 9.7 4.0 1010 675 323 57 46 30 50 40 23 47 699 1273 254 38.4 18.2 6.4 6.47 4.87 2.93 563 424 265 19.0 11.5 5.0 1355 903 420 62 52 37 56 46 31 108 699 1273 254 22.0 10.7 3.5 7.78 5.77 3.49 690 503 307 46.7 24.0 10.2 1504 969 450 63 53 40 56 47 34 103 699 1523 254 30.0 23.0 8.7 8.75 7.90 5.19 752 687 450 48.4 41.0 19.8 1560 1330 620 62 58 44 56 52 38 111 699 1773 254 4.5 2.6 0.7 1.81 1.65 0.84 159 145 74 4.7 3.7 1.1 432 286 128 53 44 34 47 38 28 31 395 680 230 12.0 8.3 2.3 2.66 2.24 1.20 230 195 105 11.5 8.8 2.9 583 379 172 57 46 34 50 40 28 46 395 805 230 6.4 2.9 1.1 3.74 3.00 1.90 330 253 167 23.0 15.8 6.7 710 475 223 53 45 33 47 39 27 40 395 930 230
(2)
(3)
(3)
(3)
med min
max
Air flow [m3/h] med min
max
Sound power level [dB(A)] med min
max
Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Height Dimensions Width Depth (4) med min
230 / 1 / 50 + E max mm
mm mm
(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C. (4) Sound pressure level in a 100 m3 room, at 1.5 m distance and riverberating time of 0.3 s. (5) Max speed 7V instead of 9V
26/27
Designation
YLV
YLH
YLV-AF YLH-AF
Factory fitted thermostat (built in) EDCL OBV11-ODC711 OBV11-ODC211 Microprocessor control for ECM units Omnibus control for ECM units + Analogue Plus console Omnibus control for ECM units + Display console
l l l l l l l l l l l l l l l l l l
Remote controllers and thermostats (wall mounted) TUC0311-2 + TM2100 Microprocessor control for ECM units, for wall installation TUC0311-2 + TM2100 BMS control for ECM units + Remote Analogue Plus console TUC0311-2 + RS-1100 BMS control for ECM units + Remote Display console
l l l l l l l l l l
Valves / Condensate pump / Water sensor / Minimum temperature thermostat (Factory fitted) J3A2 (2p) J3A2 (4p) J3AM (2p) J3AM (4p) DT (2p) DT (4p) PC WS Feet and panels CP1 ZL1 PPV1 PPH1 Set of painted feet Set of feet + frontal socle Vertical painted back panel Horizontal painted back panel
l l l l l l l l l
3-way 4-ports on/off valves for 2-pipe systems 3-way 4-ports on/off valves for 4-pipe systems 3-way 4-ports modulating valves for 2-pipe systems 3-way 4-ports modulating valves for 4-pipe systems Shut-off valves for 2-pipe systems (in addition to J3A2/J3AM valves) Shut-off valves for 4-pipe systems (in addition to J3A2/J3AM valves) Condensate pump Water sensor
l l l l
l l l l
l l l l
l l l l
l l l l
l l l l
l l l l
l l l l
l l l l
l l l l
Air intake plenum Air intake plenum collars 90 air intake plenum Air intake duct fitting Air delivery plenum with collars 90 air delivery plenum
l l
l l l l l l l l l l l l
Compatible Compatible with conditions Not compatible ** Maximum of rows is indicated in the documentation, the maximum number of rows includes the heating row or electrical heater.
CMR00 (Wall mounted) Thermostat with manual fan speed and S/W change over
CER00 (Wall mounted) Thermostat with manual fan speed and automatic change over CER20 (Wall mounted) Thermostat with auto. fan speed and automatic change over CER30 (Wall mounted) Thermostat with auto. fan speed and automatic change over for modulating valve
YEFB Blower units are available in 4 sizes for horizontal concealed installations: thanks to their high ESP fans that can handle up to 250Pa, they are the ideal solution for air conditioning large spaces.
Features
4 unit sizes for horizontal mounting Handles high external static pressure up to 250Pa Choice of 2 or 4 pipe systems Twin centrifugal fans Horizontal air return Air distribution plenum Electric heater option Optional paint finish F5 grade filter option
Selection software
28/29
max
Total cooling capacity [kW]
6.01 5.13 3.22 4.72 3.95 2.38 1 033 882 554 6.3 27.4 12.1 7.89 6.61 3.96
(1)
(1)
(1)
(1)
(2)
(2)
med min
Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397 29.4 22.2 9.8 13.19 10.98 6.5 1 154 961 568 33.1 24 9.5 1 153 916 494 67 62 52 57 52 43 186 0.81 331 989.6 800 26.8 12.3 5.0 13.19 10.98 6.5 1 130 898 484 67 62 52 57 52 43 186 0.81 331 989.6 800 57.6 41.1 30 21 16.57 13.37 1 836 1 449 1 169 75 49.4 33.9 2 158 1 553 1 174 71 65 60 61 56 50 419 1.95 331 989.6 800 35.6 24.4 17.2 21 16.57 13.37 2 116 1 523 1 151 71 65 60 61 56 50 36.6 27.1 18.3 25.7 20.96 16.17 2 247 1 833 1 414 45 31.5 19.9 2 639 1 994 1 422 71 65 59 62 56 50 32.2 22.9 14.7 25.7 20.96 16.17 2 587 1 955 1 394 71 65 59 62 56 50 569 2.59 350 1 239.6 900 19.9 16.9 13.5 41.1 36.66 31.58 3 596 3 205 2 761 24.8 20.2 15.4 4 129 3 505 2 853 78 75 70 69 66 61 984 4.45 439.3 1 633 900 18.4 15.2 11.8 41.1 36.66 31.58 4 048 3 436 2 797 78 75 70 69 66 61 984 4.45 439.3 1 633 900
max
Pressure drop in heating 2 pipes [kPa]
(2)
(3)
(3)
(3)
Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Absorbed current [A]
(4)
230 / 1 / 50
419 1.95 331 989.6 800 569 2.59 350 1 239.6 900
mm mm mm
(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C (4) Sound pressure level in a 100 m3 room, at 1.5 m distance and riverberating time of 0.3 s. 4 pipe system not available with 4R coil
Wired controls
BR Remote three speeds controller TR BR + Electronic thermostat and Summer/Winter switch ATR Automatic TR DTR Digital Automatic Remote controller TMO 503 SV2 Digital Automatic Remote controller to be mounted in the standard light wall box DRC - DI Centralized controller up to 60 terminals
Infrared control
YHK Hydro Cassette units are simple and elegant, discreet in their design. High standards of quality and reliability, combined with a wide range of accessories ensure a total solution for all comfort cooling and heating requirements.
Features
Cooling duty from 1.3 to 11.1 kW 2 & 4 pipes systems in all range 2 sizes: 600 x 600 & 800 x 800 Possible choice between 6 fan speeds Condensate pump integrated in all range 2/3 way valves fitted or supplied loose in all range Coloured versions, possible to change the colour of the grill and the frame Possible to select a complete range of controls Electric heater fitted as an option for all range (2 pipe only) All metal parts insulated to avoid condensations
Selection software
30/31
Technical features
Model -2 pipes
max
Total cooling capacity 2 Pipes [kW] Sensible cooling capacity 2 Pipes [kW] Water flow in cooling 2 Pipes [l/h] Pressure drop in cooling 2 Pipes [kPa] Heating capacity 2 pipes [kW] Water flow in heating 2 pipes [l/h] * Pressure drop in heating 2 pipes [kPa] Heating capacity 2 pipes [kW] Water flow in heating 2 pipes [l/h] Pressure drop in heating 2 pipes [kPa] Model -4 pipes (1) (1) (1) (1) (2) (2) (2) (3) (3) (3) med min
max
med min
max
med min
max med min max med min max med min max med min max med min max med
min
max
med min
YHK 20-2 2.0 1.6 1.3 1.6 1.3 1.0 340 280 219 10 7 4.5 2.6 2.1 1.6 340 280 219 9 6 4 4.6 3.7 2.8 393 315 240 9.9 6.5 4 YHK 20-4 2.3 2.0 1.5 1.9 1.6 1.2 401 337 260 13.5 10 6 3.0 2.5 2.0 261 219 169 14.5 10.5 6.5 610 420 310 49 40 33 40 31 24 57 0.27 8.0 275 575 575
YHK 25-2 2.7 2.3 1.8 2.0 1.8 1.4 461 402 316 9.7 7.6 4.9 3.4 2.9 2.2 461 402 316 8.2 6.3 4.1 5.7 4.9 4.2 488 422 360 8.4 6.4 4.8 YHK 25-4 2.7 2.4 1.9 2.0 1.7 1.3 464 406 318 8.8 6.9 4.6 3.5 3.0 2.4 298 260 209 10.8 8.5 5.7 520 420 310 45 40 33 36 31 24 44 0.20 1.4 275 575 575
YHK 40-2 4.3 3.3 2.3 3.2 2.4 1.6 745 574 387 15.1 9.4 4.6 5.2 3.9 2.6 745 574 387 11.4 7.3 3.5 9.3 7 4.9 795 598 415 12.5 7.6 4 YHK 40-4 3.3 2.7 1.9 2.6 2.0 1.3 574 456 318 13.4 8.8 4.6 4.4 3.5 2.4 378 298 209 16.6 10.8 5.7 710 500 320 53 45 33 44 36 24 68 0.32 2.1 275 575 575
YHK 50-2 5.0 3.9 2.9 3.7 2.8 2.1 863 667 506 19.7 12.4 7.5 6.2 4.6 3.4 863 667 506 17.7 11.2 6.7 10.6 8.3 6.1 914 709 524 16 10 5.9 YHK 50-4 3.8 3.0 2.4 3.0 2.3 1.8 655 519 406 17 11.2 7.2 5.0 4.0 3.1 426 341 267 20.5 13.8 8.8 880 610 430 59 49 41 50 40 32
YHK 65-2 6.2 4.9 4.2 4.6 3.6 3.0 1 060 845 724 21.6 14.3 10.9 7.8 6.0 5.1 1 060 845 724 15.1 9.9 6.7 13.1 10.7 8.6 1 130 874 741 17.5 11.3 8.4 YHK 65-4 6.3 5.0 4.1 4.7 3.7 3.0 1 090 865 712 18.9 12.5 8.8 9.1 7.2 5.9 783 618 508 21.4 14 9.8 1140 820 630 48 40 33 39 31 24 77 0.36 3.0 303 820 820
YHK 95-2 9.5 6.8 5.3 6.5 4.5 3.5 1 636 1 166 913 26.9 14.7 9.4 10.71 7.34 5.61 1 636 1 166 913 23 12.4 7.9 19.8 13.4 10.3 1 699 1 155 882 20.9 10.6 6.7 YHK 95-4 7.7 5.7 4.5 5.8 4.2 3.3 1 326 974 777 26.9 15.4 10.3 11.0 8.1 6.5 946 697 555 29.9 17.4 11.5 1500 970 710 53 40 34 44 31 25 120 0.53 4.0 303 820 820
YHK 110-2 11.1 8.5 5.3 8.3 6.1 3.7 1 909 1 453 913 35.6 21.8 9.4 14.0 10.3 6.1 1 909 1 453 913 30.6 18.6 7.9 23.7 17.3 10.3 2 037 1 484 882 28.9 16 6.7 YHK 110-4 8.9 6.9 4.5 6.8 5.2 3.3 1 529 1 192 777 34.7 22.1 10.3 12.7 10.0 6.5 1 092 858 555 38.8 25.3 11.5 1 820 1 280 710 58 48 34 49 39 25 170 0.74 4.0 303 820 820
max
Total cooling capacity 4 Pipes [kW] Sensible cooling capacity 4 Pipes [kW] Water flow in cooling 4 pipes [l/h] Pressure drop in cooling 4 pipes [kPa] Heating capacity 4 pipes [kW] Water flow in heating 4 pipes [l/h] Pressure drop in heating 4 pipes [kPa] Air flow [m3/h] Sound power level [dB(A)] Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Absorbed current [A] Water content (2 pipes) [l] Dimensions Height Width Depth (4) (1) (1) (1) (1) (3) (3) (3) med min
max
med min
max
med min
max med min max med min max med min max med min max med min max med
min
max med
min
max max mm mm mm
230V/1ph/50hZ
90 0.45 2.1 275 575 575
(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C (4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397
Wired control
T-MB Wall control with display that allows controlling one or more units in Master/Slave mode. The control is equipped with internal sensor to detect the room temperature, which can be defined as a priority compared to the return air sensor on the fan coil.
Infrared control
YHK ECM water cassette is the result of significant technical and design research focused on providing an avant-garde product in terms of performance, low noise and control flexibility. YHK ECM series uses an innovative brushless electric motor controlled by an inverter card that varies the air flow continuously by means of a 0-10 V signal. The extreme efficiency, also at a low speed, makes it possible to greatly reduce electrical consumption (more than 75% less in comparison to a traditional motor) with absorption values, under normal operating conditions, that are no greater than 10 Watt in the entire range.
Features
Cooling duty from 1.8 to 10.8 kW YHKH: models with infrared control (standard) YHKY: models with wired control (accessory) 2 (-2) & 4 (-4 or -6) pipes systems 2 sizes: 600 x 600 & 800 x 800 Condensate pump integrated in all range 2/3 way valves fitted or supplied loose in all range Coloured versions, possible to change the colour of the grid and the frame All metal parts insulated to avoid condensations Inverter fan motor for a very quiet operation Electrical consumption reduced by up to 75% Specific range of controllers with master-slave function
Selection software
32/33
Technical features
Model -2 pipes
max
Total cooling capacity 2 Pipes [kW] Sensible cooling capacity 2 Pipes [kW] Water flow in cooling 2 Pipes [l/h] Pressure drop in cooling 2 Pipes [kPa] Heating capacity 2 pipes [kW] Pressure drop in heating 2 pipes [kPa] Model -4 pipes (1) (1) (1) (1) (2) (2) med min
max
med min
max
med min
max med min max med min max med min max
YHK-ECM 25-2 2.8 2.2 1.8 2.1 1.6 1.4 473 373 317 10.1 6.6 4.9 3.4 2.7 2.2 8.7 5.5 4.0 YHK-ECM 25-4 2.8 2.2 1.9 2.1 1.6 1.3 476 375 318 9.5 6.2 4.6 3.6 2.9 2.4 311 245 209 11.7 7.6 5.7 535 380 310 47 39 33 38 30 24 16 1.4 275 575 575
YHK-ECM 40-2 4.3 3.1 2.2 3.2 2.2 1.6 744 524 385 15.1 9.4 4.6 5.2 3.6 2.6 13.1 6.6 3.6 YHK-ECM 40-6 3.9 2.8 2.1 3.0 2.0 1.5 676 483 359 10.5 5.7 3.5 3.4 2.5 2.0 288 217 170 9.0 5.5 3.5 710 445 310 54 43 33 45 34 24 31 2.1 275 575 575
YHK-ECM 50-2 5.0 3.9 2.6 3.7 2.8 1.8 864 666 441 19.7 12.4 5.9 6.2 4.6 3.0 17.7 10.5 4.7 YHK-ECM 50-6 4.5 3.5 2.4 3.5 2.6 1.7 779 608 409 13.1 8.4 4.1 3.8 3.1 2.2 326 263 189 11.0 7.5 4.5 880 610 360 60 50 37 51 41 28
YHK-ECM 65-2 6.3 5.2 4.2 4.7 3.8 3.0 1 089 885 723 22.7 15.6 10.9 8.0 6.4 5.1 19.5 12.8 8.7 YHK-ECM 65-4 6.5 5.3 4.3 4.8 3.8 3.1 1 120 908 740 19.8 13.6 9.4 9.4 7.5 6.1 805 649 528 22.5 15.5 10.5 1 165 870 630 48 39 33 39 30 24 33 3.0 303 820 820
YHK-ECM 95-2 10.8 7.7 5.3 7.9 5.5 3.7 1 848 1 328 909 33.6 18.5 9.4 12.7 8.8 5.9 28.8 14.9 7.2 YHK-ECM 95-6 9.9 7.2 5.0 7.4 5.2 3.5 1 697 1 233 856 30.1 17.0 8.8 9.5 7.2 5.2 818 616 449 18.0 11.0 6.5 1 770 1 130 710 57 47 34 48 38 25 108 4.0 303 820 820
Total cooling capacity 4 Pipes [kW] Sensible cooling capacity 4 Pipes [kW] Water flow in cooling 4 pipes [l/h] Pressure drop in cooling 4 pipes [kPa] Heating capacity 4 pipes [kW] Water flow in heating 4 pipes [l/h] Pressure drop in heating 4 pipes [kPa] Air flow [m3/h] Sound power level [dB(A)] Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Water content (2 pipes) [l] Dimensions
med min
max
med min
max
med min
max med min max med min max med min max med min max med min max med
min
(4)
max med
min
max
Height Width Depth
230V/1ph/50hZ
62 2.1 275 575 575
mm mm mm
(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C (4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397
Outer casing as an option to integrate the water cassette into any enviroment
2 pipe system 4 pipe system 2 pipe system 4 pipe system 2 pipe system 2 pipe system 2 pipe system 4 pipe system 2 pipe system 4 pipe system 2 pipe system 4 pipe system 2 pipe system 2 pipe system AKPA 600 AKPA 800
YHKY 25 0079000K 0079010K 0079171K 0079181K 0079060K 0079191K 0079020K 0079030K YHKY 25 0079801K 0079811K 0079911K 0079921K 0079841K 0079901K
YHKY 40 0079001K 0079011K 0079172K 0079182K 0079061K 0079192K 0079021K 0079031K YHKY 40 0079802K 0079812K 0079912K 0079922K 0079842K 0079902K
YHKY 50 0079002K 0079012K 0079173K 0079183K 0079062K 0079193K 0079022K 0079032K YHKY 50 0079803K 0079813K 0079913K 0079923K 0079843K 0079903K
YHKY 65 0079003K 0079013K 0079174K 0079184K 0079063K 0079194K 0079023K 0079033K YHKY 65 0079804K 0079814K 0079914K 0079924K 0079844K 0079904K
YHKY 95 0079004K 0079014K 0079175K 0079185K 0079064K 0079195K 0079024K 0079034K YHKY 95 0079805K 0079815K 0079915K 0079925K 0079845K 0079905K
YHKY 110 0079005K 0079015K 0079176K 0079186K 0079065K 0079196K 0079025K 0079035K -
l l l l l
l l l l l l
34/35
YHKY 65
YHKY 95
YHKY 110
UPS-ECM power unit for CR-T-ECM remote control, 9066340 not fitted on the unit (1) NTC Low temperature cut-out for control CR-T-ECM (1) 3021090 Change-over 15-25 for CR-T-ECM (1) 9053049 CONTROLS for YHKY-MP-ECM (ECM motor) Wall control T-MB (1) 9066331E Wire, receiver and IR remote control kit RCS-RT03 (1) 9079117 Infra red remote control RT-03 (1) 3021203 Wire and receiver kit RCS (1) 9079116 Receiver for IR remote control for metal grid MD600 RS (1) 9066338 Multifunction control PSM-DI (1) 3021293 T2 sensor (to be used as change over or min.temp. sensor) T2 (1) 9025310 Management system for a network of fan coils with MB electronic board Hardware / software supervisory system Net 9079118 Router S 3021290 Relay output board SIOS 3021292 (1) denotes JCI TUC0311-2 also suitable for use
l l l
l l l l l l l
l l l
Dimensions
Sizes 20 to 50 (Version 600x600)
Wired controls
BR Remote three speeds controller TR BR + Electronic thermostat and Summer/Winter switch ATR Automatic TR DTR Digital Automatic Remote controller TMO 503 SV2 Digital Automatic Remote controller to be mounted in the standard light wall box DRC - DI Centralized controller up to 60 terminals
Infrared control
Thanks to its unique diffuser, YFCC cassette units generate an airflow with a coanda effect. The unit is suitable for installation in a suspended ceiling. Air intake is from the bottom while the air is supplied parallel to the ceiling. The resulting coanda effect creates excellent draft free distribution of the air inside the room. Units can be supplied with 1 coil (2 pipe system) with optional electric heating element, or with 2 coils (4 pipe system) with one or two rows.
Features
Coanda effect units, allowing easier and cheaper installation Cooling duty from 0.9 to 4.0 kW 2 & 4 pipes systems in all range 3 sizes: 600 x 600, 600 x 1000 & 600 x 1200 2/3 way valves fitted or supplied loose in all range Left and right hand (optional) water connections 6 fan speeds (3 pre-wired) Air throw till 7.6m (cooling) and 9.5m (heating)
Selection software
Coanda effect
36/37
Technical features
Model -2 pipes
max
Total cooling capacity 2 Pipes [kW] (1) med min
max
Sensible cooling capacity 2 Pipes [kW] (1) med min
(1)
(2)
(2)
max med min max med min max med min max med min max med
min
Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Dimensions
(4)
max med
min
YFCC 130 1.5 1.06 0.88 1.18 0.81 0.66 6.1 3.3 2.4 1.93 1.33 1.08 4.9 2.6 1.8 280 180 140 52 41 35 43 32 26 49 309 592 592
YFCC 140 1.74 1.19 0.97 1.31 0.88 0.71 12.9 6.7 4.7 2.1 1.4 1.1 10.7 5.4 3.7 280 180 140 52 41 35 43 32 26 49 309 592 592
YFCC 230 2.37 1.62 1.37 1.77 1.19 1.0 7.6 3.9 2.9 2.86 1.91 1.6 6.3 3.1 2.3 380 240 200 48 36 33 39 27 24 44 309 592 970
YFCC 240 2.57 1.72 1.44 1.88 1.24 1.04 12.1 6.0 4.4 3.1 2.0 1.7 10.2 4.8 3.5 380 240 200 48 36 33 39 27 24 44 309 592 970
YFCC 330 3.34 2.84 1.97 2.51 2.11 1.44 16.2 12.1 6.4 4.02 3.37 2.3 13.4 9.8 5.2 540 440 290 52 46 35 43 37 26 59 309 592 1 192
YFCC 340 4.02 3.56 2.5 2.98 2.63 1.81 15.5 12.6 6.7 4.77 4.2 2.9 12.6 10.0 5.5 620 540 360 55 52 41 46 43 32 72 309 592 1 192
230V/1ph/50Hz
Height Width Depth
max mm mm mm
Model -4 pipes
max
Total cooling capacity 4 Pipes [kW] (1) med min
max
Sensible cooling capacity 4 Pipes [kW] (1) med min
(1)
(3)
(3)
max med min max med min max med min max med min max med
min
Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Dimensions
(4)
max med
min
YFCC 130+1 1.5 1.06 0.88 1.18 0.81 0.66 6.1 3.3 2.4 1.47 1.08 0.92 3.6 2.1 1.6 280 180 140 52 41 35 43 32 26 49 309 592 592
YFCC 230+1 2.37 1.62 1.37 1.77 1.19 1.0 7.6 3.9 2.9 2.35 1.71 1.49 2.0 1.2 0.9 380 240 200 48 36 33 39 27 24
YFCC 330+1 3.34 2.84 1.97 2.51 2.11 1.44 16.2 12.1 6.4 3.3 2.87 2.12 4.3 3.4 2.0 540 440 290 52 46 35 43 37 26 59 309 592 1 192
230V/1ph/50Hz
Height Width Depth
max mm mm mm
(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C (4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397
Wired controls
CR-T-ECM Continuous fan speed control with electronic thermostat and s/w switch
T-MB Wall control with display that allows controlling one or more units in Master/Slave mode. The control is equipped with internal sensor to detect the room temperature, which can be defined as a priority compared to the return air sensor on the fan coil.
Infrared control
Thanks to its unique diffuser, YFCC cassette units generate an airflow with a coanda effect. The unit is suitable for installation in a suspended ceiling. Air intake is from the bottom while the air is supplied parallel to the ceiling. The resulting coanda effect creates excellent draft free distribution of the air inside the room. Units can be supplied with 1 coil (2 pipe system) with optional electric heating element, or with 2 coils (4 pipe system) with one or two rows.
Features
Coanda effect units, allowing easier and cheaper installation Cooling duty from 0.8 to 4.0 kW 2 & 4 pipes systems in all range 3 sizes: 600 x 600, 600 x 1000 & 600 x 1200 2/3 way valves fitted or supplied loose in all range Left and right hand (optional) water connections 6 fan speeds (3 pre-wired) Air throw till 7.6m (cooling) and 9.5m (heating) ECM variable speed motor
Selection software
Coanda effect
38/39
Technical features
Model -2 pipes
max 10v
Total cooling capacity 2 Pipes [kW] (1) med 5v min 1v
max
Sensible cooling capacity 2 Pipes [kW] (1) med min
(1)
(2)
(2)
max med min max med min max med min max med min max med
min
Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Dimensions
(4)
max med
min
YFCC-ECM 130 1.56 1.18 0.82 1.24 0.91 0.62 6.5 4 2.1 2.02 1.5 1.02 5.3 3.3 1.7 295 205 130 55 46 35 46 37 26 29 309 592 592
YFCC-ECM 140 1.81 1.34 0.91 1.38 0.99 0.66 13.9 8.1 4.1 2.2 1.6 1.07 11.6 6.6 3.3 295 205 130 55 46 35 46 37 26 29 309 592 592
YFCC-ECM 230 3.16 2.31 1.46 2.41 1.73 1.07 12.6 7.3 3.2 3.85 2.79 1.72 10.4 6 2.6 540 370 215 56 46 34 47 37 25 37 309 592 970
YFCC-ECM 240 3.5 2.51 1.55 2.6 1.84 1.11 20.8 11.6 5 4.32 3.03 1.82 17.1 9.4 4.1 540 370 215 56 46 34 47 37 25 37 309 592 970
YFCC-ECM 330 3.75 2.78 1.87 2.83 2.06 1.37 19.8 11.8 5.8 4.54 3.3 2.19 16.6 9.4 4.7 620 430 275 58 48 36 49 39 27 42 309 592 1 192
YFCC-ECM 340 4.02 2.94 1.95 2.98 2.15 1.41 15.5 8.9 4.3 4.78 3.44 2.25 13 7.4 3.5 620 430 275 58 48 36 49 39 27 42 309 592 1 192
230V/1ph/50Hz
Height Width Depth
Model -4 pipes Total cooling capacity 4 Pipes [kW] (1) med 5v min 1v
max
Sensible cooling capacity 4 Pipes [kW] (1) med min
(1)
(3)
(3)
max med min max med min max med min max med min max med
min
Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Dimensions
(4)
max med
min
YFCC-ECM 130+1 1.56 1.18 0.82 1.24 0.91 0.62 6.5 4 2.1 1.52 1.18 0.87 3.8 2.5 1.4 295 205 130 55 46 35 46 37 26 29 309 592 592
YFCC-ECM 230+1 3.16 2.31 1.46 2.41 1.73 1.07 12.6 7.3 3.2 3.01 2.31 1.58 3.1 2 1 540 370 215 56 46 34 47 37 25
YFCC-ECM 330+1 3.75 2.78 1.87 2.83 2.06 1.37 19.8 11.7 5.8 3.64 2.82 2.04 5.1 3.3 1.8 620 430 275 58 48 36 49 39 27 42 309 592 1 192
230V/1ph/50Hz
Height Width Depth
max mm mm mm
(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C (4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397
YFCC 130 2 pipe system 4 pipe system (+1) 4 pipe system (+2) 0064001K 0064021K 0064041K
0064212K 0064232K
-
0064213K 0064233K
-
Contact Johnson Controls 9060471 9060472 9060476 9060476 9066571 9060483 9060484 9060477
9060474 9060475
9060478 9060478 9066570 9060480 Contact Johnson Controls 9064051 9064031 9064052 9064032 6060402 6060403 6060420 9064010 9064011 6064191 6064192
9060479
9060481
9064053 9064033
40/41
9060541 / T125BAC-JS0-E (2 pipes) & T125FAC-JS0-E (4 pipes) 9060542 9060521 / T5200-TB-9JS0-E (2 pipes with LCD display) & T5200-FB-9JS0-E (4 pipes with LCD display) 9060170 9060172 9060174 9079110 9060139 3021091 9053048
9053049
WARNING * not to be used with valves ** it can be used with valves and/or low temperature cut-out *** to be used with valves and/or low temperature cut-out. The Winter/Summer switch is manual/centralized in accordance to the position of the J1 Jumper **** low temperature cut-out included (1) denotes JCI TUC0311-2 also suitable for use Note: Electric heaters must be factory supplied only - in ECM range the above controls can control the electric heater only if there is no hot water supply to the exchanger.
Air Throw
C1 - Heating C2 - Cooling
L
YFCC 1 Model Air throw L (m) C1 C2 1 3.8 3 2 4.5 3.6 3 5.8 4.6 4 6.3 5 5 6.8 5.4 6 7.2 5.7 1 4 3.2 2 5 4 YFCC 2 3 6.1 4.8 4 7 5.6 5 8 6.4 6 9 7.2 1 4.5 3.6
L
YFCC 3 2 5.2 4.1 3 6.3 5 4 7.5 6 5 8.8 7 6 9.5 7.6
Features
TR. Wired Control Remote three speeds controller, electronic thermostat and Summer/Winter switch ATR. Wired Control Automatic TR
Available with standard AC motors or low energy EC motors Wired control or infrared control Automatic air sweep Choice of 2 or 3 way valves fitted Condensate collection tray Air filter included Heat exchange coil
Electronic Infrared Control 2 Way Valve ON/OFF with thermoelectric actuator. Suitable for the connection with 12 mm pipes
42/43
Technical features
Model
max
Total cooling capacity [kW] (1) med min
max
Sensible cooling capacity [kW] (1) med min
(2)
Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Dimensions
(3)
max med
min
YHVP 1 1.87 1.5 1.24 1.46 1.19 0.92 2.57 2 1.6 375 270 205 48 41 35 39 32 26 18 322 880 212
YHVP 2 2.18 1.84 1.43 1.75 1.43 1.07 3.16 2.58 1.92 480 365 250 53 47 39 44 38 30
YHVP 3 3.03 2.32 1.89 2.27 1.69 1.35 3.99 2.9 2.3 545 375 280 48 40 35 39 31 26
YHVP 4 3.81 3.26 2.62 2.98 2.47 1.93 5.2 4.3 3.33 790 610 440 57 51 43 48 42 34 48 322 1 185 212
230V/1ph/50Hz
Height Width Depth
max mm mm mm
(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397
Dimensions
COIL CONNECTIONS ON THE LEFT
Dim A
YHVP 1 880
YHVP 2 880
YHVP 3 1 185
YHVP 4 1 185
Controls
Wall control T-MB (to be used with M B board only) 9066331E
44/45
Controls
Wall control T-MB (to be used with M B board only) 9066331E
Lighting - Corridor Lighting - Window Sun Blinds Presence Detector Window Contact Air Quality Luminosity Cooling Heating Ventilation Temperature Energy Metering
46/47
The Integrated Room Control Solution provides the control of the heating, cooling, lighting and sunblinds within an occupied space, such as an office or small conference room, in one coordinated control system with a single point of control interface for the occupant. The AD-IRC Integrated Room Controller is a LonWorks network compatible device that is the master device in the system. The AD-IRC provides direct digital control of terminal unit applications with heating and/or cooling coils, an electric heater, air quality devices and a three-speed or variable speed fan. These applications include radiators, close control units, fan coil units, unit ventilators and chilled beams or chilled ceiling beam installations. It is mounted within the unit or other protective enclosure. One or two zones of lighting in the space and optionally sunblinds are controlled by AD-IRL, AD-IRS and AD-ILS slave modules that can be mounted directly in the ceiling void. The space comfort set point, occupancy mode and fan speed may be adjusted from the wide range of room sensor modules with options for a digital display and IR remote command. From the RJ connected digital modules the occupant can switch and adjust the lighting level and operate the sunblinds. The controller complies with the LonMark interoperability guidelines for sharing data with other network sensors and devices. Operating data can be monitored and controlled from a LonWorks compatible supervisory system, including the Metasys NCM Network Control Module and NAE Network Automation Engine that connect the integrated room control system into a facility-wide building management network.
AD-RLC
AD-LCD
AD-IPL
AD-RIR Accessories
AD-IRM
TM 2160
YMWA / YMRA Water-Cooled, remote condenser and heat pump scroll compressor chiller Cooling Capacities: 20-190 kW - R410A
YLAE-HP Reverse Cycle Air to Water Heat Pump Scroll Compressor Chiller Cooling: 182-297 kW - Heating: 187-323 kW - R410A
YCSE / YCRE Water-Cooled or Remote Air-Cooled Screw Compressor Chiller Cooling Capacities: 134-320 kW - R407C
48/49
YCWL / YCRL Water-Cooled or Remote Air-Cooled Scroll Compressor Chiller Cooling Capacities: 188-580 kW - R410A
YNWS/RS Water-Cooled or Remote Air-Cooled Screw Compressor Chiller Cooling Capacities: 470-1790 kW - R717
YLCS Water-Cooled or Remote Air-Cooled Screw Compressor Chiller Cooling Capacities: 336-1090 kW - R134a
YVWA Water-Cooled Variable Speed Screw Chiller Cooling Capacities: 703-1055 kW - R134a
YMA Custom Air Handling Units Air Volume Range 0.25 m3/s to 60 m3/s
www.johnsoncontrols.co.uk
Johnson Controls public website is the home for all news related to Johnson Controls and its products and services. Within the website you will have access to product information for all of Johnson Controls business units. Within the Building Efficiency business unit portal you will find relevant technical information for all of our product offerings, including, but not limited to HVAC, Controls, and Industrial Refrigeration.
www.johnsoncontrols.com
Printed on recycled paper
PUBL-7200