McQuay Fan Coil Units

Download as pdf or txt
Download as pdf or txt
You are on page 1of 116

TM: MCCKCM - W - 2150B

Fan Coil Units


Models: MWM-FW Series MCM-DW Series MCK-AW/BW Series MCC-CW Series MDB-BW Series

Contents
Features ..................................................................................................................... 1 Specifications ............................................................................................................. 3 Unit Selection Procedure ......................................................................................... 11 Cooling Capacity Performance Chart ....................................................................... 14 Heating Capacity Performance Chart ....................................................................... 49 Water Flow Rate Vs Pressure Drop ......................................................................... 66 Correction Factors ................................................................................................... 71 Wiring Diagrams ...................................................................................................... 72 Controllers ............................................................................................................... 85 Blower Performance Curves ..................................................................................... 91 Outlines And Dimensions........................................................................................ 103 General Installation Guide ..................................................................................... 112 General Operation Guide ....................................................................................... 113

Note: Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and experienced with this type of equipment. Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.

Warning: Moving machinery and electrical power hazards. May cause severe personal injury or death. Disconnect and lock off power before servicing equipment.

"McQuay" is a registered trademark of McQuay International. All rights reserved throughout the world. 2002 McQuay International "Bulletin illustrations cover the general appearance of McQuay International products at the time of publication and we reserve the right to make changes in design and construction at any time without notice."

Features
Space Saving
Different types of fan coil units are designed to be both versatile and space saving to suit every interior design. Ceiling concealed type for the sophisticated, luxurious floor space saving, all kind of interior decoration; ceiling exposed type for economical and space saving installation; etc.

Zone Control
These fan coil units can be installed in different zones as each unit operates independently. Zone control on energy saving, different comfort requirement; better air distribution needs can therefore be easily achieved.

Unique Features For MWM-FW Series


Easy Installation The wall mounted fan coil unit is easily installed because of its compact size, slimness and light weight. Slim and short outdoor unit can be easily installed even in a narrow balcony and passageway and yet have a stable profile. Space Saving No space is required on either floor or ceiling. This newly developed super slim design for wall mounting maximises floor space usage and enhance ceiling appearance where ceilings are low. Quiet Operation Cooling comfort is improved by whisper-quiet operation which is achieved by a tangential fan. Excellent Air Distribution Air discharge direction can be adjusted in four directions, manually or automatically by using LCD remote control, coupled with good air flow, the unit provides excellent air distribution. Facilitated Maintenance Ensured The new design cassette filter is slide-out type which can be easily removed at the air inlet grille for cleaning. Maintenance is easy for electrical components, piping and wiring as these are all easily accessible by merely removing front plastic panel. Wireless Remote Control The compact LCD transmitter is able to operate the air conditioner unit within the distance of 9 meters. Fan motor speed can be set at low/medium/high or automatic.Sleep mode automatically increase set temperature since room temperature is lower at night thus achieving comfort surrounding. Air flow direction can be controlled automatically. Room temperature is controlled by electronic thermostat. The unit can be preset to on and off automatically for maximum of 15 hours by using timer on/off. Slit Fin The unique Hydrophilic slit fin has greatly improved the air flow and the contact surfaces with the air thus to boost the cooling capacity.

Unique Features For MCK-AW/BW Series


Built In High Head Drain Pump The unit comes with a built in high head drain pump. Condensate water can be pumped up to 500mm and drain out smoothly. 4-Way Air Discharge And Air Swing These features greatly improve the air distribution in the conditioned space. Wireless And Wired Controller Option Wireless Handset is the standard controller. However if wired controller required, Netware wired controller is a wise choice(optional).

Unique Features For MCM-DW Series


2-Way Air Discharge And Air Swing The 2-way air discharge couple with the air swing function, provide better air distribution in the conditioned space. Easy Maintenance The air filter and components can be easily accessed from the bottom of the unit. This make servicing and maintenance become a simple task. Wireless And Wired Controller Option Wireless Handset is the standard controller. However if wired controller required, Netware wired controller is a wise choice(optional).

Unique Features For MCC-CW Series


Elegance And Prestige As the unit is installed above the ceiling with only the supply and return air grille exposed to view, the air conditioned space will appear as elegant and prestigious as a centralized air conditioned area. Evergreen Design This unit will never become obsolete as the unit is completely concealed away. Interior decoration for maximum aesthetic beauty as well as interior design is easily achieved. Superior Air Distribution As the conditioned air can be distributed to every corner of the area by air duct, this will ensure more pleasant living environment, thus provide extra comfort to the occupants. Optional Duct Accessories The optional duct accessories makes the ducting and installation work so easy. Optional Wired Controller Optional Netware wired controller offers simple and flexibility in controlling the unit.

Unique Features For MDB-BW Series


Superb Air Distribution These units are designed with high air flow and static, enables adequate distribution of air to the desired space. Providing comfort to every corner of the room. Reliability The structures are strong and robust to ensure the product operation life. Versatile Multiple rooms can be cooled together by just using one unit of MDB.

Specifications
MWM

MODEL
PERFORMANCE High Air Flow (CFM / L/s) Medium Low kcal/hr Nominal Total Cooling Capacity W Btu/hr kcal/hr Sensible Cooling Capacity Nominal Total Heating Capacity (Entering water Temp. : 60C) Water Flow Rate Head Loss (Cooling) Head Loss (Heating) : 60 C COIL Type Tube Fin Connection Number of rows / fin per inch Max. Working Pressure Testing Pressure Surface Area Surface Air Velocity MOTOR Type Power Supply Rated Input power Rated Running Current Poles High Fan Sound Level (dBA) Medium Fan Low Fan Room Temp. Control Condensate Drain Size AIR FILTER WEIGHT DIMENSION (H x W x D) kg mm Air Discharge Operation mm V/Ph/Hz W (50/60Hz) A (50/60Hz) m / ft
2 2

005FW 300 / 510 230 / 390 190 / 320 1210 1410 4800 1179 1375 4680 2772 3220 11000 1.10 / 4.16 0.245 / 1689 0.186 / 1282

007FW 300 / 510 230 / 390 190 / 320 1638 1910 6500 1373 1600 5447 3150 3660 12500 1.54 / 5.83 0.436 / 3006 0.335 / 2310

010FW 270 / 127 230 / 109 190 / 90 2520 2931 10000 1739 2022 6900 4032 4689 16000 2.00 / 7.57 7.77 / 53572 6.09 / 41989

015FW 300 / 142 270 / 127 230 / 109 3024 3517 12000 2026 2356 8040 4536 5275 18000 2.67 / 10.11 12.93 / 89149 10.28 / 70878

020FW 480 / 227 430 / 203 370 / 175 4284 4982 17000 2956 3438 11730 6552 7620 26000 4.22 / 15.97 4.89 / 33715 3.86 / 26614

025FW 580 / 274 485 / 229 380 / 179 5292 6154 21000 3651 4247 14490 8064 9378 32000 5.33 / 20.18 7.40 / 51021 5.86 / 40403

W Btu/hr kcal/hr W Btu/hr USGPM / LITRES/M psi / Pa psi / Pa

Seamless copper tube mechanically boded to aluminium slit fin. OD 7mm, thickness 0.35 mm. thickness 0.11 mm 1 / 18 (kg/cm2) / (psi) 0.208 / 2.239 0.690 / 135.84 1 / 20 OD 1/2" copper tube 2 / 18 2 / 18 16.4 / 233 30 kg/cm2 for 1 min, leak test : 16 kg/cm2 for 5 min. 0.208 / 2.239 0.198 / 2.131 0.198 / 2.131 0.254 / 2.733 0.690 / 135.84 0.64 / 126.70 0.72 / 140.78 0.89 / 175.63 0.254 / 2.733 1.08 / 212.22 2 / 18 2 / 18

(m/s) / (ft/min)

Permanent split capacitor motor 25 0.11 25 0.11 220 - 240 / 1 / 50 , 208 - 230 / 1 / 60 25 / 26 25 / 26 0.11 / 0.12 4 38 34 30 38 35 31 45 42 39 47 44 42 0.11 / 0.12 53 / 67 0.23 / 0.31 57 / 81 0.24 / 0.38

Micro-computer Controlled Thermostat Automatic Louver (Up & Down) LCD wireless micro-computer remote control 19.05 12 12 Washable Saran Net Filter 12 12 15 15

290 x 815 x 179

306 x 1062 x 202

Condition Cooling capacity

: Entering air temp. : 26.7 C ( 80 F ) DB, 19.4 C ( 67 F ) WB Entering water temp. : 7.2 C ( 45 F ) Leaving water temp. : 12.8 C ( 55 F ) : Entering air temp. : 21.1 C ( 64 F ) DB Entering water temp. : 60 C ( 140 F ) Leaving water temp. : 55 C ( 131 F )

Heating capacity

Microphone position : 1m in front of the unit & 0.8m below the vertical centre line of the unit. (JIS C 9612)

MODEL PERFORMANCE Air Flow (CFM/CMH) High Medium Low kcal/hr W Btu/hr kcal/hr W Btu/hr kcal/hr W Btu/hr USGPM / LITRES/M psi / Pa psi / Pa

020AW 770 / 1,310 650 / 1,100 630 / 1,070 6,048 7,034 24,000 4,209 4,894 16,700 9,451 10,991 37,500 5.32 / 20.17 2.13 / 14,686 1.70 / 11,721

025AW 810 / 1,380 700 / 1,190 630 / 1,070 6,804 7,913 27,000 4,738 5,510 18,800 10,585 12,309 42,000 6.22 / 23.45 3.16 / 21,774 2.545 / 17,547

MCK 030AW 920 / 1,560 770 / 1,320 700 / 1,190 7,964 9,261 31,600 5,494 6,389 21,800 12,198 14,185 48,400 7.11 / 26.84 4.36 / 30,061 3.55 / 24,476

040AW 1,020 / 1,740 900 / 1,530 790 / 1,340 9,073 10,551 36,000 6,162 7,166 24,450 13,584 15,797 53,900 8.00 / 30.14 7.29 / 50,263 6.07 / 41,851

050AW 1,080 / 1,840 990 / 1,680 910 / 1,540 9,829 11,430 39,000 6,628 7,708 26,300 14,365 16,706 57,000 8.88 / 33.49 10.99 / 75,773 9.20 / 63,459

Nominal Total Cooling Capacity

Sensible Cooling Capacity Nominal Total Heating Capacity (Entering water Temp. : 60 C) Water Flow Rate Head Loss (Cooling) Head Loss (Heating) : 60 C COIL Type Tube Fin Connection Number of rows / fin per inch Max. Working Pressure Testing Pressure Surface Area Surface Air Velocity MOTOR Type Power Supply Rated Input Running Current Poles Control Condensate Drain Size AIR FILTER WEIGHT (Unit + panel) DIMENSION (H x W x D)

(kg/cm ) / (psi) m / ft (m/s) / (ft/min)


2 2

Seamless copper tube mechanically bonded to aluminium slit fin OD 9.52 mm, thickness 0.35 mm Thickness 0.11 mm OD 3/4" copper tube 2/12 2/14 2/16 2/16 2/16 16.4 / 233 2 2 30 kg/cm for 1 min, leak test : 16 kg/cm for 5 min 0.459 / 5.022 0.459 / 5.022 0.459 / 5.022 0.459 / 5.022 0.459 / 5.022 0.78 / 153.33 0.82 / 161.29 0.93 / 183.19 1.03 / 203.11 1.09 / 215.05 Permanent split capacitor motor 220 - 240 / 1 / 50, 208 - 230/1/60 151 / 163 164 / 208 192 / 321 0.65 / 0.75 0.69 / 0.98 0.80 / 1.50 6 Micro-computer Controlled Thermostat Automatic Louver (Up & Down) LCD wireless micro-computer remote control 19.05 Washable Saran Net Filter 32 + 4 35 + 4 38 + 4 335 x 820 x 820 ( 363 x 930 x 930 )

V/Ph/Hz W A Room Temp. Air Discharge Operation mm kg mm

127 / 139 0.53 / 0.64

253 / 328 1.08 / 1.50

21 + 4

40 + 4

Condition Cooling capacity

: Entering air temp. : 26.7C (80F)DB, 19.4C (67F)WB Entering water temp. : 7.2C (45F) Leaving water temp. : 12.8C (55F) : Entering air temp. : 21.1C (64F)DB Entering water temp. : 60C (140F) Leaving water temp. : 55C (131F)

Heating capacity

MCK

MODEL
PERFORMANCE High Air Flow (CFM / L/s) Medium Low kcal/hr Nominal Total Cooling Capacity W Btu/hr kcal/hr Sensible Cooling Capacity Nominal Total Heating capacity (Entering water Temp. : 60 C) Water Flow Rate Head Loss (Cooling) Head Loss (Heating) : 60 C COIL Type Tube Fin Connection Number of rows / fin per inch Max. Working Pressure Testing Pressure Surface Area Surface Air Velocity MOTOR Type Power Supply Rated Input power Rated Running Current Poles Sound pressure level ( dBA ) High Fan Medium Fan Low Fan Room Temp. Control Condensate Drain Size AIR FILTER WEIGHT (Unit + Panel) DIMENSION - HxWxD ( ) - with panel kg mm Air Discharge Operation mm V/Ph/Hz W (50/60Hz) A (50/60Hz) m2/ft2 (m/s)/(ft/min) (kg/cm 2)/(psi) W Btu/hr kcal/hr W Btu/hr USGPM/LITRES/M psi / Pa psi / Pa

015BW 430 / 203 370 / 175 310 / 146 3150 3660 12500 2331 2708 9250 5292 6150 21000 3.34 / 12.7 0.582 / 4013 0.455 / 3137

020BW 430 / 203 370 / 175 310 / 146 4284 4977 17000 2853 3315 11322 6300 7320 25000 4.44 / 16.8 1.849 / 12749 1.461 / 10074

025BW 500 / 236 450 / 212 390 / 184 5040 5860 20000 3352 3897 13300 7308 8500 29000 5.54 / 21 2.739 / 18885 2.189 / 15093

030BW 607 / 287 537 / 253 475 / 224 5796 6740 23000 3872 4499 15364 8316 9663 33000 6.64 / 25 3.78 / 26063 3.055 / 21064

Seamless copper tube mechanically bonded to aluminium slit fin. OD 9.52 mm, thickness 0.35 mm. thickness 0.11 mm 1 / 18 OD 3/4" copper tube 2 / 14 2 / 14 16.4 / 233 30 kg/cm2 for 1 min, leak test : 16 kg/cm2 for 5 min. 0.431 / 4.637 0.416 / 4.483 0.416 / 4.483 0.416 / 4.483 0.471 / 92.73 0.487 / 95.91 0.567 / 111.53 0.688 / 135.40 2 / 14

Permanent split capacitor motor 72 / 73 0.31 / 0.34 43.7 39 37.5 220 - 240 / 1 / 50 , 208 - 230 / 1 / 60 72 / 73 79 / 88 0.31 / 0.34 6 43.7 39 37.5 Manual Louver LCD wireless micro-computer remote control 19.05 30 + 3 Washable Saran Net Filter 30 + 3 31 + 3 293 x 650 x 650 (363 x 930 x 930) 32 + 3 44 40 38 47 44 40 0.33 / 0.41 108 / 108 0.45 / 0.50

Micro-computer Controlled Thermostat

Condition Cooling capacity

: Entering air temp. : 26.7 C ( 80 F ) DB, 19.4 C ( 67 F ) WB Entering water temp. : 7.2 C ( 45 F ) Leaving water temp. : 12.8 C ( 55 F ) : Entering air temp. : 21.1 C ( 64 F ) DB Entering water temp. : 60 C (140 F) Leaving water temp. : 55 C (131 F)

Heating capacity

Microphone position : MCK015-025B - 1.4m below the facia (JIS C 9612) , MCK030B - 1.5m below the facia (JIS B 8615).

MODEL PERFORMANCE Air Flow (CFM/CMH) High Medium Low kcal/hr W Btu/hr kcal/hr W Btu/hr kcal/hr W Btu/hr USGPM / LITRES/M psi / Pa psi / Pa

020DW 590 / 1,000 530 / 900 420 / 710 5,040 5,862 20,000 3,528 4,102 14,000 7,560 8,792 30,000 4.44 / 16.75 2.95 / 20,315 2.46 / 16,915

025DW 660 / 1,130 650 / 1,110 580 / 990 5,544 6,448 22,000 3,825 4,448 15,180 8,442 9,818 33,500 4.88 / 18.42 3.52 / 24,250 2.83 / 20,191

MCM 030DW 730 / 1,240 720 / 1,220 680 / 1,160 6,552 7,620 26,000 4,455 5,180 17,680 9,674 11,250 38,385 5.76 / 21.77 3.17 / 21,875 2.64 / 18,215

040DW 1,000 / 1,700 950 / 1,620 930 / 1,580 9,535 11,137 38,000 6,485 7,538 25,730 16,207 18,639 63,600 8.44 / 31.82 5.96 / 41,170 4.98 / 34,279

050DW 1,110 / 1,890 1,070 / 1,820 1,000 / 1,700 12,096 14,068 48,000 7,983 9,282 31,680 17,065 19,846 67,715 10.66 / 40.19 9.19 / 63,330 7.65 / 52,731

Nominal Total Cooling Capacity

Sensible Cooling Capacity Nominal Total Heating Capacity (Entering water Temp. : 60 C) Water Flow Rate Head Loss (Cooling) Head Loss (Heating) : 60 C COIL Type Tube Fin Connection Number of rows / fin per inch Max. Working Pressure Testing Pressure Surface Area Surface Air Velocity MOTOR Type Power Supply Rated Input Running Current Poles Sound pressure level ( H / M / L ) Control Condensate Drain Size AIR FILTER WEIGHT DIMENSION (H x W x D)

(kg/cm ) / (psi) m / ft (m/s) / (ft/min)


2 2

Seamless copper tube mechanically bonded to aluminium slit fin OD 9.52 mm, thickness 0.35 mm Thickness 0.11 mm OD 3/4" copper tube 3/12 3/12 3/12 4/12 4/14 16.4 / 233 2 2 30 kg/cm for 1 min, leak test : 16 kg/cm for 5 min 0.217 / 2.338 0.217 / 2.338 0.263 / 2.826 0.406 / 4.361 0.406 / 4.361 1.28 / 252.35 1.43 / 282.29 1.31 / 258.32 1.16 / 229.31 1.29 / 254.53 Permanent split capacitor motor 220 - 240 / 1 / 50, 208 - 230/ 1 / 60 130 / 155 132 / 179 240 / 337 0.58 / 0.70 0.58 / 0.80 1.04 / 1.50 4 54 / 53 / 50 51 / 50 / 48 54 / 53 / 52 Micro-computer Controlled Thermostat Automatic Louver (Up & Down) LCD wireless micro-computer remote control 19.05 Washable Saran Net Filter 43 45 70
249 x 1,214 x 670

V/Ph/Hz W A dBA Room Temp. Air Discharge Operation mm kg mm

96 / 114 0.40 / 0.50 50 / 47 / 40

240 / 337 1.04 / 1.50 54 / 53 / 52

43

70

214 X 1,214 X 670

249 X 1,714 X 670

Condition Cooling capacity

: Entering air temp. : 26.7C (80F)DB, 19.4C (67F)WB Entering water temp. : 7.2C (45F) Leaving water temp. : 12.8C (55F) : Entering air temp. : 21.1C (64F)DB Entering water temp. : 60C (140F) Leaving water temp. : 55C (131F)

Heating capacity

MCC MODEL PERFORMANCE Air Flow (CFM/CMH) High Medium Low kcal/hr W Btu/hr kcal/hr W Btu/hr kcal/hr W Btu/hr USGPM / LITRES/M psi / Pa psi / Pa 010CW 300 / 510 280 / 480 240 / 410 2,520 2,931 10,000 1,789 2,081 7,100 4,032 4,690 16,000 2.22 / 8.40 1.53 / 10550 1.21 / 8340 015CW 430 / 730 310 / 530 270 / 460 3,780 4,397 15,000 2,646 3,078 10,500 6,048 7,034 24,000 3.33 / 12.61 3.48 / 24000 2.8 / 19300 020CW 620 / 1,050 610 / 1,040 500 / 850 4,788 5,569 19,000 3,352 3,898 13,300 7,560 8,793 30,000 4.44 / 16.81 2.92 / 20130 2.34 / 16130 025CW 840 / 1,430 790 / 1,340 640 / 1,090 6,048 7,034 24,000 4,234 4,924 16,800 9,324 10,845 37,000 5.55 / 21.01 4.70 / 32410 3.83 / 26410

Nominal Total Cooling Capacity

Sensible Cooling Capacity Nominal Total Heating Capacity (Entering water Temp. : 60 C) Water Flow Rate Head Loss (Cooling) Head Loss (Heating) : 60 C COIL Type Tube Fin Connection Number of rows / fin per inch Max. Working Pressure Testing Pressure Surface Area Surface Air Velocity MOTOR Type Power Supply Rated Input Running Current Poles Control Condensate Drain Size AIR FILTER WEIGHT DIMENSION (H x W x D)

Seamless copper tube mechanically bonded to aluminium slit fin OD 9.52 mm, thickness 0.35 mm Thickness 0.11 mm OD 3/4" copper tube 3/12 (kg/cm ) / (psi)
2 2

3/14 16.4 / 233

3/12
2

3/12

m / ft (m/s) / (ft/min)

30 kg/cm for 1 min, leak test : 16 kg/cm for 5 min 0.129 / 1.39 0.161 / 1.734 0.197 / 2.128 0.228 / 2.461 1.10 / 215.8 1.26 / 248.0 1.48 / 291.4 1.73 / 341.3 Permanent split capacitor motor 220 - 240 / 1 / 50 , 208 - 230 / 1 / 60 71 / 72 0.30 / 0.33 102 / 114 0.43 / 0.53 148 / 172 0.65 / 0.80 180 / 223 0.74 / 1.01

V/Ph/Hz W A Room Temp. Operation mm kg mm

4 Micro-computer Controlled Thermostat LCD wireless micro-computer remote control 19.05 Washable Saran Net Filter 17 261 x 765 x 411 21 261 x 905 x 411 22 261 x 1,065 x 411 25 261 x 1,200 x 411

Condition Cooling capacity

: Entering air temp. : 26.7C (80F)DB, 19.4C (67F)WB Entering water temp. : 7.2C (45F) Leaving water temp. : 12.8C (55F) : Entering air temp. : 21.1C (64F)DB Entering water temp. : 60C (140F) Leaving water temp. : 55C (131F)

Heating capacity

MCC

MODEL
PERFORMANCE High Air Flow (CFM/CMH) Medium Low kcal/hr Nominal Total Cooling Capacity W Btu/hr kcal/hr Sensible Cooling Capacity Nominal Total Heating Capacity (Entering water Temp. : 60C) Water Flow Rate Head Loss (Cooling) Head Loss (Heating) : 60 C COIL Type Tube Fin Connection Number of rows / fin per inch Max. Working Pressure Testing Pressure Surface Area Surface Air Velocity MOTOR Type Power Supply Rated Input Running Current Poles Room Temp. Control Condensate Drain Size AIR FILTER WEIGHT DIMENSION (H x W x D) kg mm Air Discharge Operation mm V/Ph/Hz W A m / ft
2 2

028CW 1440/2450 1270/2160 1120/1900 6,804 7,914 27,000 4,695 5,460 18,630 7,056 8,207 28,000 6.16/23.31 2.437/16800 1.952/13460

038CW 1540/2620 1450/2460 1260/2140 10,550 12,270 41,864 7,490 8,712 29,723 16,872 19,623 66,951 8.36/31.64 4.992/34420 4.084/28160

W Btu/hr kcal/hr W Btu/hr USGPM / LITRES/M psi / Pa psi / Pa

Seamless copper tube mechanically boded to aluminium slit fin. OD 9.52 mm, thickness 0.35 mm. thickness 0.11 mm OD 3/4" copper tube 3/18 (kg/cm ) / (psi)
2 2

3/14 16.4 / 233


2

30 kg/cm for 1 min, leak test : 16 kg/cm for 5 min. 0.264/2.844 0.363/3.909 1.14/224.44 Permanent split capacitor motor 220 - 240 / 1 / 50 300 1.30 4 Micro-computer Controlled Thermostat Automatic Louver (Up & Down) LCD wireless micro-computer remote control 19.05 Washable Saran Net Filter 38 290X942X600 41 310X1247X638 563 2.4 1.764/347.16

(m/s) / (ft/min)

Condition Cooling capacity

: Entering air temp. : 26.7 C ( 80 F ) DB, 19.4 C ( 67 F ) WB Entering water temp. : 7.2 C ( 45 F ) Leaving water temp. : 12.8 C ( 55 F ) : Entering air temp. : 21.1 C ( 64 F ) DB Entering water temp. : 60 C ( 140 F ) Leaving water temp. : 55 C ( 131 F )

Heating capacity

MCC MODEL PERFORMANCE Air Flow (CFM/CMH) High Medium Low kcal/hr W Btu/hr kcal/hr W Btu/hr kcal/hr W Btu/hr USGPM / LITRES/M psi / Pa psi / Pa 030CW 1,030 / 1,750 820 / 1,390 660 / 1,120 7,308 8,500 29,000 5,189 6,035 20,590 11,592 13,483 46,000 6.66 / 25.21 2.11 / 14550 1.68 / 11580 040CW 1,150 / 1,960 1,025 / 1,740 840 / 1,430 9,576 11,138 38,000 6,799 7,908 26,980 15,120 17,586 60,000 8.88 / 33.61 3.78 / 26060 3.06 / 21100 050CW 1,540 / 2,620 1,430 / 2,430 1,300 / 2,210 12,348 14,362 49,000 8,644 10,053 34,300 19,152 22,276 76,000 11.11 / 42.06 6.48 / 44680 5.36 / 36960 060CW 1,990 / 3,380 1,830 / 3,110 1,630 / 2,770 13,608 15,827 54,000 9,798 11,396 38,880 22,680 26,379 90,000 13.33 / 50.46 1.48 / 10205 1.18 / 8140

Nominal Total Cooling Capacity

Sensible Cooling Capacity Nominal Total Heating Capacity (Entering water Temp. : 60 C) Water Flow Rate Head Loss (Cooling) Head Loss (Heating) : 60 C COIL Type Tube Fin Connection Number of rows / fin per inch Max. Working Pressure Testing Pressure Surface Area Surface Air Velocity MOTOR Type Power Supply Rated Input Running Current Poles Control Condensate Drain Size AIR FILTER WEIGHT DIMENSION (H x W x D)

Seamless copper tube mechanically bonded to aluminium slit fin OD 9.52 mm, thickness 0.35 mm Thickness 0.11 mm OD 3/4" copper tube 3/12 (kg/cm ) / (psi)
2 2

3/12 16.4 / 233

3/12
2

3/12

m / ft (m/s) / (ft/min)

0.37 / 3.98 1.31 / 258.78

30 kg/cm for 1 min, leak test : 16 kg/cm for 5 min 0.31 / 3.44 0.41 / 4.40 0.48 / 5.16 1.70 / 334.30 1.78 / 350.00 1.96 / 385.66 Permanent split capacitor motor 220 - 240 / 1 / 50 , 208 - 230 / 1 / 60

V/Ph/Hz W A Room Temp. Operation mm kg mm

421 / 486 1.90 / 2.40

550 / 661 2.60 / 3.40

670 / 767 2.90 / 3.70

748 / 804 3.20 / 3.70

4 Micro-computer Controlled Thermostat LCD wireless micro-computer remote control 19.05 Washable Saran Net Filter 39 378 x 929 x 474 42 378 x 1,045 x 474 54 378 x 1,299 x 474 62 378 x 1,499 x 474

Condition Cooling capacity

: Entering air temp. : 26.7C (80F)DB, 19.4C (67F)WB Entering water temp. : 7.2C (45F) Leaving water temp. : 12.8C (55F) : Entering air temp. : 21.1C (64F)DB Entering water temp. : 60C (140F) Leaving water temp. : 55C (131F)

Heating capacity

MDB MODEL PERFORMANCE Air Flow (CFM/CMH) Nominal Total Cooling Capacity kcal/hr W Btu/hr kcal/hr W Btu/hr kcal/hr W Btu/hr USGPM / LITRES/M psi / Pa psi / Pa mmAq 075BW 2,500 / 4,250 19,152 22,274 76,000 13,598 15,810 53,960 30,996 36,049 123,000 16.88 / 63.64 8.72 / 60,050 7.26 / 50,000 10 100BW 3,200 / 5,440 24,696 28,722 98,000 18,028 20,961 71,540 40,320 46,700 160,000 21.77 / 82.06 2.65 / 18,230 2.20 / 15,179 10 125BW 4,200 / 7,140 32,760 38,101 130,000 23,587 27,425 93,600 53,734 62,490 213,215 28.88 / 108.86 3.55 / 24,472 2.96 / 20,377 15 150BW 4,600 / 7,820 41,076 47,773 163,000 29,164 33,909 115,730 66,348 77,160 263,270 36.22 / 136.49 2.77 / 19,092 2.31 / 15,897 15

Sensible Cooling Capacity Nominal Total Heating Capacity (Entering water Temp. : 60 C) Water Flow Rate Head Loss (Cooling) Head Loss (Heating) : 60 C Ext. static COIL Type Tube Fin Connection Number of rows / fin per inch Max. Working Pressure Testing Pressure Surface Area Surface Air Velocity MOTOR Type Power Supply Rated Input Running Current Poles Number of motors Sound pressure level Control Condensate Drain Size FAN Type/Drive Number of Fans AIR FILTER (OPTIONAL) Type Length x Height Quantity WEIGHT DIMENSION (H x W x D)

Seamless copper tube mechanically bonded to aluminium slit fin OD 9.52 mm, thickness 0.35 mm Thickness 0.11 mm 3/14
2 (kg/cm ) / (psi)

OD 1 /8" copper tube 4/12 3/14 16.4 / 233 30 kg/cm 2 for 1 min, leak test : 16 kg/cm2 for 5 min 0.54 / 5.82 1.01 / 10.83 2.75 / 550 1.94 / 388

4/14

m / ft (m/s) / (ft/min)

0.54 / 5.82 2.15 / 430

1.01 / 10.83 2.12 / 425

V/Ph/Hz W A

Permanent split capacitor motor 220 - 240 / 1 / 50 , 208 - 230 / 1 / 60 415 / 3 / 50 , 415 / 3 / 60 810 / 1062 3.70 / 5.16 2 62 1008 / 1310 4.22 / 7.04 4 2730 / 1620 3.39 / 5.70 3370 / 1999 3.39 / 5.70 1 67

dBA mm

2 1 64 63 LCD wireless micro-computer remote control 25.4

Centrifugal fan (forward curved) / Direct 2 2

Centrifugal fan (forward curved) / Belt Driven 1 1

mm kg mm 2 96
572 x 1,502 x 761

Washable Saran Net Filter 622 x 433 2 100 1 140


885 x 1,640 x 1,040

1 145

Condition Cooling capacity

: Entering air temp. : 26.7C (80F)DB, 19.4C (67F)WB Entering water temp. : 7.2C (45F) Leaving water temp. : 12.8C (55F) : Entering air temp. : 21.1C (64F)DB Entering water temp. : 60C (140F) Leaving water temp. : 55C (131F)

Heating capacity

10

Unit Selection Procedure


The cooling and heating capacities of the fan coil units can be determined by the Cooling Capacity Performance Chart and Heating Capacity Performance Chart in the following pages based on nominal air flow at standard water temperature. The total and sensible capacities must be adjusted as variables come in. A sample of selection procedure is given as below:

Step 1 Determine type of fan coil units to be used, i.e. ceiling cassette (MCK-AW Series); ceiling exposed (MCM-DW Series); etc.

Step 2 Select a tentative unit size based on cooling capacities at nominal air flow. Design entering air temperatures and required water flows from cooling capacities chart (Page 14 - 35) or the nominal capacities ratings (Page 3 - 10) from standard specification.

Step 3 Determine the nominal unit cooling capacities for the unit selected. If the cooling capacities chart must be used, the following information must be known :a) Design water temperature rise b) Design entering water temperature c) Design entering air dry bulb temperature d) Design entering air wet bulb temperature Example of how to read the cooling performance chart.

MCK050AW

Total Cooling Capacity Sensible Capacity

11

Step 4 If air flow value is different from the nominal value(high speed), then refer to specification from Page 3 to 10 for the air flow required(medium or low speed). Determine the total and sensible correction factor from Air Flow Capacity Correction Factor (Page 57). Step 5 If the unit is to operate at an altitude above sea level, multiply the capacity correction factors by an Altitude Correction Factors. Refer to Page 57.

Step 6 Calculate the actual cooling capacity by multiply the nominal capacity (from Step 3) with Air Flow Capacity Correction Factor from Step 4 and the Altitude Correction Factor from Step 5. Actual Capacity, W = Nominal capacity (Step 3) x Air Flow Capacity Correction Factor (Step 4) x Altitude Correction Factor (Step 5) Step 7 Water flow rate can be determined by: Litres/Min = Total Cooling Capacity, W 70 x Water Temperature Rise C

USGPM

Total Cooling Capacity, Btu/H 500 x Water Temperature Rise F

Step 8 Heating Capacities at nominal air flow (Page 36 to 51 - Heating Performance Chart) are based on standard condition of 60C EWT and 21C EAT. The actual heating capacity can be obtained by using the Heating Capacity Correction Factor (Page 57) and Altitude Correction Factor as per Step 5. Hence Actual Heating Capacity, W = Nominal Capacity (Page 36 to 51) x Heating Capacity Correction Factor (Page 57) x Air Flow Capacity Correction Factor (Step 4) x Altitude Correction Factor (Step 5)

Step 9 Water Pressure Drop Tables are on Page 52 to 56. EXAMPLE Select a ceiling cassette type fan coil unit at the following design specification: Room design condition Room Cooling Load Room Heating Load Entering water temperature Water temperature rise Air Volume Altitude : 26.7C DB / 19C WB : 7 kW sensible capacity / 10 kW total capacity : 10 kW : 7C cooling / 54C heating : 5C : 1700 cmh : 600 m

SOLUTION Step 1 Based on the type of fan coil required and the design conditions, tentatively select MCK050AW. From the cooling capacity performance chart (Page 15), at 26.7C DB / 19C WB air temperature, 7C entering water temperature and with 5C water temperature rise, the cooling capacity for this unit is 11 kW total capacity and 7.6 kW sensible

12

Step 2 From page 57, the air flow correction factor table, at high speed, the air volume is 1840 cmh and medium speed is 1680 cmh, hence high speed is selected. And the correction factor is hence 1.0. If lower air flow required, then use the medium and low fan speed. The correction factor can be determined by getting the ratio of air flow (i.e. medium or low speed / high speed). Step 3 As the unit is operating at 600m above sea level, the Altitude correction factor is 0.98 total and 0.93 sensible. Step 4 Multiply the cooling capacities obtained from step 1 (as per specification and design condition) by correction factors from (2) and (3) Actual total cooling capacity Actual sensible cooling capacity Step 5 Water flow rate = 11 x 1.0 x 0.98 kW = 7.6 x 1.0 x 0.93 kW = 10.78 kW = 7.068 kW

= Litres/M

10780 W 70 x 5

30.8

Step 6 From Heating Capacity Performance Chart (Page 40), determine the heating capacity at the nominal air

MCK050AW

volume by using the flow rate calculated in Step 5. The heating capacity is at 16.18 kW. Step 7 From Heating Capacity Correction Factor Tables at 54.4C water entering temperature and 26.7C entering air temperature, the correction factor is 0.717, Actual Heating Capacity Step 8 Water Pressure Drop can be estimated from water Pressure Drop Table (Page 52 to 56) using interpolate method: At flow rate of 30.8 Litres/Min, the nominal pressure drop is 68,322 Pa Pressure drop correction factor = 1.2947 - 0.0021 x (EWTC x 1.8 + 32) = 1.0234 Hence the actual pressure drop = nominal pressure drop x correction factor = 69,921 Pa. 13 = 16.18 x 0.98 x 0.717 = 11.37 kW

Cooling Capacity Performance Chart

MWM005FW

14

MWM007FW

15

MWM010FW

16

MWM015FW

17

MWM020FW

18

MWM025FW

19

MCK020AW

20

MCK025AW

21

MCK030AW

22

MCK040AW

23

MCK050AW

24

MCK015BW

25

MCK015BWN

26

MCK020BW

27

MCK025BW

28

MCK030BW

29

MCM020DW

30

MCM025DW

31

MCM030DW

32

MCM040DW

33

MCM050DW

34

MCC010CW

35

MCC015CW

36

MCC020CW

37

MCC025CW

38

MCC030CW

39

MCC040CW

40

MCC050CW

41

MCC060CW

42

MCC028CW

43

MCC038CW

44

MDB075BW

45

MDB100BW

46

MDB125BW

47

MDB150BW

48

Heating Capacity Performance Chart


Wall Mounted Type MWM010FW AWM10FW
84.00

HEATING CAPACITY - W

82.00

80.00

78.00

76.00

74.00

72.00 4.50

5.50

6.50

7.50

8.50

9.50

10.50

WATER FLOWRATE - LITRE/MIN

MWM015FW AWM15FW
92.00 91.00

HEATING CAPACITY- W

90.00 89.00 88.00 87.00 86.00 85.00 84.00 83.00 82.00 6.00

7.00

8.00

9.00

10.00

11.00

12.00

13.00

14.00

15.00

WATER FLOWRATE - LITRE/MIN

49

MWM020FW AWM20FW
134.00

132.00

HEATING CAPACITY - W

130.00

128.00

126.00

124.00

122.00

120.00

118.00 9.00

10.00

11.00

12.00

13.00

14.00

15.00

16.00

17.00

18.00

19.00

20.00

21.00

22.00

23.00

WATER FLOWRATE - LITRE/MIN

MWM025FW AWM25FW
166.00 164.00

HEATING CAPACITY- W

162.00 160.00 158.00 156.00 154.00 152.00 150.00 148.00 146.00 11.00

13.00

15.00

17.00

19.00

21.00

23.00

25.00

27.00

29.00

WATER FLOWRATE - LITRE/MIN

50

Ceiling Cassette Type

MCK020AW

MCK025AW

51

MCK030AW

MCK040AW

52

MCK050AW

53

MCK015BW
108.00 106.00

104.00

HEATING CAPACITY - W

102.00

100.00

98.00

96.00

94.00

92.00 7.00

8.00

9.00

10.00

11.00

12.00

13.00

14.00

15.00

16.00

17.00

18.00

WATER FLOWRATE - LITRE/MIN

MCK020BW
130.00 129.00 128.00 127.00 126.00 HEATING CAPACITY- W 125.00 124.00 123.00 122.00 121.00 120.00 119.00 118.00 117.00 116.00 10.00

12.00

14.00

16.00

18.00

20.00

22.00

24.00

WATER FLOWRATE - LITRE/MIN

54

MCK025BW
144.00

142.00

140.00 HEATING CAPACITY - W

138.00

136.00

134.00

132.00

130.00 12.00

13.00

14.00

15.00

16.00

17.00

18.00

19.00

20.00

21.00

22.00

23.00

24.00

25.00

26.00

27.00

28.00

29.00

30.00

WATER FLOWRATE - LITRE/MIN

MCK030BW
156.00

154.00

HEATING CAPACITY- W

152.00

150.00

148.00

146.00

144.00 15.00

20.00

25.00 WATER FLOWRATE - LITRE/MIN

30.00

35.00

55

Ceiling Suspended Type

MCM020DW

MCM025DW

56

MCM030DW

MCM040DW

57

MCM050DW

58

Ceiling Concealed Type

MCC010CW

MCC015CW

59

MCC020CW

MCC025CW

60

MCC030CW

MCC040CW

61

MCC028CW
13800

13300

HEATING CAPACITY - W

12800

12300

11800 10 15 20 25 30 35 WATER FLOW RATE - LITRES/M

MCC038CW
20500

20000

HEATING CAPACITY - W

19500

19000

18500

18000

17500 15 20 25 30 35 40 45 50 WATER FLOW RATE - LITRES/M

62

MCC050CW

MCC060CW

63

Ducted Blower Split Type

MDB075BW

MDB100BW

64

MDB125BW

MDB150BW

65

Water Flow Rate Vs Pressure Drop


MODELS MWM010FW FLOW RATE LITRES / M USGPM 4.54 1.20 6.06 1.60 7.57 2.00 9.08 2.40 10.60 2.80 6.06 1.60 8.06 2.13 10.11 2.67 12.11 3.20 14.12 3.73 9.58 2.53 12.76 3.37 15.97 4.22 19.15 5.06 22.33 5.90 12.07 3.19 16.12 4.26 20.17 5.33 24.19 6.39 28.24 7.46 WATER PRESSURE DROP Pa PSI 3.67 0.533 6.08 0.882 9.01 1.308 12.55 1.822 16.57 2.405 6.08 0.883 10.15 1.473 15.22 2.209 21.11 3.064 27.90 4.049 2.29 0.333 3.80 0.551 5.69 0.826 7.88 1.144 10.40 1.510 3.45 0.501 5.80 0.842 8.67 1.258 12.04 1.747 15.95 2.315

MWM015FW

MWM020FW

MWM025FW

Note : a. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * ( EWTC * 1.8 + 32 ) b. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * EWTF

66

MODELS MCK020AW

FLOW RATE LITRES / M USGPM


10.07 13.44 16.81 20.17 26.55 12.60 16.81 23.45 25.21 29.41 15.10 20.14 26.84 30.14 35.28 20.14 26.87 30.14 33.61 40.31 25.21 33.49 42.06 50.42 58.86 2.66 3.55 4.44 5.32 7.02 3.33 4.44 6.22 6.66 7.77 3.99 5.32 7.11 7.97 9.32 5.32 7.10 8.00 8.88 10.65 6.66 8.88 11.11 13.32 15.55

WATER PRESSURE DROP Pa PSI


8,681 14,614 21,869 30,385 40,589 13,043 21,890 40,614 46,204 61,479 18,079 30,440 52,258 64,794 86,339 30,468 52,075 64,821 78,911 110,901 46,287 78,925 120,093 169,129 228,341 1.26 2.12 3.17 4.41 5.89 1.89 3.18 5.89 6.71 8.92 2.62 4.42 7.58 9.40 12.53 4.42 7.56 9.41 11.45 16.10 6.72 11.46 17.43 24.55 33.14

MCK025AW

MCK030AW

MCK040AW

MCK050AW

MODELS MCK015BW

MCK020BW

MCK025BW

MCK030BW

FLOW RATE LITRES / M USGPM 7.53 1.99 10.07 2.66 12.60 3.33 15.10 3.99 17.64 4.66 10.07 2.66 13.44 3.55 16.81 4.44 20.14 5.32 23.50 6.21 12.60 3.33 16.81 4.44 21.01 5.55 25.21 6.66 29.41 7.77 15.10 3.99 20.14 5.32 25.21 6.66 30.24 7.99 35.28 9.32

WATER PRESSURE DROP Pa PSI 1.26 0.183 2.09 0.304 3.13 0.455 4.33 0.628 5.73 0.831 4.02 0.583 6.74 0.978 10.07 1.461 13.96 2.026 18.31 2.658 5.98 0.868 10.07 1.462 15.08 2.189 21.04 3.053 28.10 4.078 8.32 1.208 15.22 2.209 21.04 3.054 29.59 4.295 39.36 5.713

Note : a. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * ( EWTC * 1.8 + 32 ) b. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * EWTF

67

MODELS MCM020DW

FLOW RATE LITRES / M USGPM


10.07 13.44 16.75 20.14 23.50 12.60 16.81 18.42 25.21 29.41 15.10 21.77 25.21 30.24 35.28 20.14 26.87 31.82 40.31 47.05 25.21 33.61 40.19 42.06 50.45 58.86 2.66 3.55 4.44 5.32 6.21 3.33 4.44 4.88 6.66 7.77 3.99 5.76 6.66 7.99 9.32 5.32 7.10 8.44 10.65 12.43 6.66 8.88 10.66 11.11 13.33 15.55

WATER PRESSURE DROP Pa PSI


6,704 11,293 16,915 23,509 31,418 10,080 16,929 20,191 35,766 47,603 9,329 18,215 23,578 33,141 44,075 14,800 24,900 34,279 52,681 70,195 22,186 37,688 52,731 56,987 79,986 106,726 0.97 1.64 2.46 3.41 4.56 1.46 2.46 2.83 5.19 6.91 1.35 2.64 3.42 4.81 6.40 2.15 3.61 4.98 7.65 10.19 3.22 5.47 7.65 8.27 11.61 15.49

MCM025DW

MCM030DW

MCM040DW

MCM050DW

Note : a. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * ( EWTC * 1.8 + 32 ) b. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * EWTF

68

MODELS MCC010CW

FLOW RATE LITRES / M USGPM


5.03 6.70 8.40 10.07 11.73 7.53 10.07 12.61 13.45 15.10 17.64 10.07 13.44 16.75 20.14 23.50 12.60 16.81 20.10 25.21 29.41 14.01 18.55 23.47 28.01 32.55 15.10 20.14 24.28 30.24 35.28 18.93 24.98 31.80 37.85 44.29 20.14 26.87 31.82 40.31 47.05 25.21 33.61 41.03 42.05 50.45 58.86 30.24 40.31 49.41 60.52 70.63 1.33 1.77 2.22 2.66 3.10 1.99 2.66 3.33 3.55 3.99 4.66 2.66 3.55 4.44 5.32 6.21 3.33 4.44 5.33 6.66 7.77 3.7 4.9 6.2 7.4 8.6 3.99 5.32 6.44 7.99 9.32 5.0 6.6 8.4 10.0 11.7 5.32 7.10 8.44 10.65 12.43 6.66 8.88 10.89 11.11 13.33 15.55 7.99 10.65 13.11 15.99 18.66

WATER PRESSURE DROP Pa PSI


10,266 17,204 25,900 35,993 47,954 23,702 40,086 60,894 68,612 85,119 113,685 14,331 24,129 36,500 50,972 67,942 10,459 17,556 24,455 37,082 49,346 5594 9273 13999 19528 25703 4,603 7,717 10,852 16,067 21,269 11568 19062 29289 40957 54784 8,358 14,035 19,194 29,565 39,335 14,476 24,356 35,408 36,930 51,730 68,914 22,296 37,929 55,316 80,413 107,394 1.49 2.50 3.76 5.22 6.96 3.44 5.82 8.84 9.96 12.35 16.50 2.08 3.50 5.30 7.40 9.86 1.52 2.55 3.55 5.38 7.16 0.78 1.29 1.95 2.72 3.58 0.67 1.12 1.58 2.33 3.09 1.61 2.66 4.08 5.71 7.64 1.21 2.04 2.79 4.29 5.71 2.10 3.54 5.14 5.36 7.51 10.00 3.24 5.51 8.03 11.67 15.59

MCC015CW

MCC020CW

MCC025CW

MCC028CW

MCC030CW

MCC038CW

MCC040CW

MCC050CW

MCC060CW

Note : a. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * ( EWTC * 1.8 + 32 ) b. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * EWTF

69

MODELS MDB075BW

FLOW RATE LITRES / M USGPM


37.81 50.42 63.64 75.66 88.27 50.45 67.26 82.06 100.91 117.71 63.06 84.06 108.86 126.12 17.12 75.66 100.91 136.49 151.36 176.61 9.99 13.32 16.88 19.99 23.32 13.33 17.77 21.77 26.67 31.11 16.66 22.22 28.88 33.33 38.88 20.00 26.67 36.22 40.00 46.67

WATER PRESSURE DROP Pa PSI


19,499 32,900 50,000 70,154 93,601 6,304 10,549 15,179 22,206 29,503 7,648 12,822 20,377 27,036 35,945 5,567 9,357 15,897 19,499 26,037 2.83 4.78 7.26 10.18 13.59 0.92 1.53 2.20 3.22 4.28 1.11 1.86 2.96 3.92 5.22 0.81 1.36 2.31 2.83 3.78

MDB100BW

MDB125BW

MDB150BW

Note : a. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * ( EWTC * 1.8 + 32 ) b. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * EWTF

70

Correction Factors

ALTITUDE CORRECTION FACTORS Elevation, m Total Capacity 0 1.00 300 0.99 600 0.98 900 0.97 1200 0.96 1500 0.94 1800 0.93

Sensible Capacity 1.00 0.96 0.93 0.90 0.86 0.83 0.80

HEATING CAPACITY CORRECTION FACTORS ENTERING TEMPERATURE, C EAT C 37.8 43.3 45.0 48.8 54.4 60.0 65.5 71.1 4.4 0.838 0.980 1.021 1.122 1.265 1.406 1.552 1.698 7.2 0.771 0.913 0.954 1.055 1.198 1.379 1.485 1.631 10.0 0.700 0.843 0.885 0.986 0.130 1.272 1.417 1.563 12.7 0.631 0.773 0.817 0.918 1.062 1.205 1.349 1.495 15.5 0.562 0.705 0.748 0.848 0.992 1.137 1.281 1.427 18.3 0.493 0.636 0.679 0.779 0.923 1.070 1.212 1.358 21.1 0.424 0.567 0.610 0.711 0.855 1.000 1.146 1.290 23.9 0.354 0.498 0.541 0.642 0.786 0.932 1.078 1.222 26.7 0.284 0.428 0.471 0.573 0.717 0.863 1.008 1.155

76.7 1.845 1.778 1.710 1.639 1.572 1.504 1.438 1.369 1.302

82.2 1.988 1.920 1.853 1.786 1.719 1.650 1.583 1.515 1.449

87.7 2.134 2.067 2.000 1.931 1.865 1.799 1.730 1.664 1.597

Notes : Adjusted capacity, W (@ Nominal air flow) = base heating capacity (@ nominal 60C EWT, 21.1C EAT) x Heating Capacity Correction Factor

71

Wiring Diagrams
Model : MWM005/007/010/015FW (G6 Controller)

Model : MWM005/007/010/015FW (SLM-3)

72

Model : MWM005/007/010/015FW (Netware 2)

Model : MWM005/007/010/015FWN (G6 Controller)

73

Model : MWM005/007/010/015FWN (SLM-3)

Model : MWM005/007/010/015FWN (Netware 2)

74

Model : MWM020/025FW (G6 Controller)

Model : MWM020/025FW (SLM-3)

75

Model : MWM020/025FW (Netware 2)

Model : MWM020/025FWN (G6 Controller)

76

Model : MWM020/025FWN (SLM-3)

Model : MWM020/025FWN (Netware 2)

77

Model : MCK020/025/030/040/050AW C/W G6 Controller Or Netware-1 CW Wired Controller

Model : MCK020/025/030/040/050AWN (With W1V3 Controller Without Valve)

78

Model : MCK015/020/025/030BW

Model : MCK015/020/025/030BWN (W1V3 Valveless)

79

Model : MCM020/025/030/040/050DW (G6 CONTROLLER)

Model : MCM020/025/030/040/050DW (NETWARE 2)

80

Model : MCM020/025/030/040/050DWN

Model : MCC010/015/020/025CW (Netware 2 / SLM-3)

81

Model : MCC010/015/020/025CWN

Model : MCC028/030/038/040/050/060CW

82

Model : MCC028/030/038/040/050/060CWN

83

Model : MDB075/100BW - WITHOUT CONTROLLER

Model : MDB125/150BW - WITHOUT CONTROLLER

84

Controllers
TYPE OF CONTROLLER VS TYPE OF FAN COIL MODELS
MCK020~050AW MCM020~050DW MCC010~060CW MDB075~150BW

STANDARD CONTROLLER
G6 WIRELESS CONTROL G6 WIRELESS CONTROL NETWARE 2 CW (WIRED CONTROLLER) WITHOUT CONTROLLER

OPTIONAL CONTROLLER
NETWARE 2 CW (WIRED CONTROLLER) NETWARE 2 CW (WIRED CONTROLLER) -

SELF DIAGNOSIS TABLE Wireless Power LED Other LEDs Blinks 4 times Fan blinks Blinks 4 times Sleep blinks Blinks 1 time Cool blinks Blinks 2 times Cool & Fan blinks OPERATION GUIDE FOR G6 Wired 7 Segment Display E1 Blinking E2 Blinking E4 Blinking E6 Blinking Operation / Faulty Indication Room sensor contact loose / short Indoor coil sensor contact loose / short Pipe water temperature fault Pump faulty

7
FAN SPEED AND VENTILATION MODE SELECTION Press the button until the desired fan speed is achieved.

8
SIGNAL TRANSMISSION INDICATION Blink to confirm the last setting has been send to the unit.

2
TEMPERATURE SETTING Set the desire room temperature. Press button to increase or decrease the set temperature. Setting range are between 16C to 30C setting (60F to 80F)(Optional setting from 20C to 30C). Press  or  button simultaneously will toggle the temperature setting between C and F.

6
OPERATION MODES Press the mode button for select the type of operating mode. Cooling only unit: CoolDryFan. Heating cycles: CoolDryHeatFan.

1 5
TIMER SETTING Press set button to activate the timer setting (from 1 hour to 15 hour) of the air conditioning unit. It will be in "On" or "Off" condition after the set time depending to the current condition (either from "On" to Off" or vise versa) To cancel the timer setting, press the button continuously until the timer display goes off. ON / OFF switch Press to start the air conditioner unit. Press again to stop the unit.

4
SLEEP MODE Press the button to activate sleep mode.
This mode can only be activated while in cooling or heating mode operation. If it is activated in COOL mode, the set temperature will be increase 0.5C after 30 minutes, 1C after 1 hour and 2C after 2 hours.

3
AUTOMATIC AIR SWING Press the button to activate the automatic air swing function. The swing angle ranging from horizontal to 25 to bottom.

85

Netware 2
D A B C E

F G

Display
A : Fan Speed Display Displays the fan speed setting (Auto/High/Medium/Low) B : Operation Mode Display Displays the current mode of operation. C : Sleep Display Display the sleep / energy saving status. D : Error Display E : Swing Display Display the aur swing status. F : Key Lock Display Display indicates when key lock function is activated. G : C or F Display Display the temperature in C or F. H : Current Time Start / Stop Time Display Display the current time as well as the start and stop time programmed. I : On / Off Status Lamp Display J : Set Temperature or Room Temperature Display Display the set or room temperature. Other functions Last state memory using battery back up. For 7-days programmable time option, battery back up is used to retain the last state data. Units without battery back up will depend on the EEPROM on the main board. Error Indicator Error code will be shown for any abnormal condition detected. Refer to main board error codes for detail.

86

L P Q N M

Operation
K : Operating Lamp L : On / Off Starting operation : When the unit is off, press the ON/OFF button. The operation LED lights and the unit will be turned on. Stopping operation : When the unit is on, press the ON/OFF button. The operation LED is extinguished and controls are turned off. M : Set Temperature Press this button to set the temperature. By pressing up or down once, temperature changes by 1C (or 1F). The temperature range is16C to 30C (60F to 85F). In FAN mode, temperature can not be set. Pressing up and down buttons simultaneously will toggle the temperature unit between C and F. When set temperature button is pressed, the set temperature will be displayed for 5 seconds. After that, room temperature will be displayed. N : Mode Press MODE button to select operation mode from Cool, Heat, Auto, Dry and Fan. The display will show the selected mode. O : Fan Press FAN button to select Auto, High, Medium or Low fan speed. P : Swing Press SWING button to activate the air sweep function. Q : Sleep Press SLEEP button to activate the sleep or energy saving mode.

87

S R

R : Timer Hold / Resume Display S : Current Time Display T : Operating Lamp U : Key Lock This feature protects the controls from being tampered with by children or unauthorized persons. To activate, press the MINUTE button three times consecutively. KEY LOCK symbol will appear on the LCD display. During this time, ON/OFF button and FAN button can be used. To cancel this feature, press the MINUTE button again three times consecutively. V : Minute When the control is in set clock or set timer mode, pressing the HOUR button will change the set hour. W : Hour When the control is in set clock or set timer mode, pressing the HOUR button will change the set hour. X : Day When the control is in set clock or set timer mode, pressing the DAY button will change the set day. Y : Clock Press button once to set the clock mode. Press button again to disable the clock mode. When the clock mode is activated, the time and date can be set or changed by pressing the DAY, HOUR or MINUTE buttons. Z : Timer Hold / Resume If 7-days timer is set, the word TIMER ACTIVE is displayed. To clear the timer setting, press and hold the HOLD button for 2 to 3 seconds until the word TIMER ACTIVE is no longer displayed. To resume the timer setting after the timer has been placed on hold, press and hold the HOLD button again for 2 to 3 seconds until the word TIMER ACTIVE is displayed.

88

SLM 3 WIRED CONTROLLER

10

9
SENSOR ON/OFF

4 4
FAN ON/OFF

1 2

AUTO

COOL FAN DRY HEAT FAN SWING SLEEP MODE

2 5

TEMP

HIGH MED LOW

3 7
SWING

TEMP

6
SLEEP

TIMER

6 5
TIMER MODE

SLM

AC5300 (OPTIONAL)

1. ON/OFF switch Press to start the air conditioner unit. Press again to stop the unit. 2. Temperature setting Set the desired room temperature. Press button to increase or decrease the set temperature. Setting range are between o o o o 16 C to 30 C (60 F to 80 F). 3. Operation Modes Press the mode button for select the type of operating mode. - Cooling Only : COOL, DRY, FAN - Heat Pump : AUTO, COOL, DRY, HEAT, FAN (AUTO mode is represented by both COOL and HEAT LED light on) 4. Fan Speed selection. Press the button until the desired fan speed is achieved. 5. Timer. Press the set button to select the switch timer of the air conditioner unit (the setting range is between 1 to 10 hours).

6. Sleep mode Press button to activate the sleep function. This function can only be activated under cool or heating mode operation. When it is activated under cool mode operation, the o set temperature will increase 0.5 C after 30 o o minutes, 1 C after 1 hour and 2 C after 2 hours. If it is activated under HEAT mode operation, the set temperature will be decreased 0.5 C after 30 minutes, 1 C after 1 hour and 2 C after 2 hours. 7. Air Swing Press button to activate the automatic air swing function. 8. Sensor Infra red sensor to receive signals from wireless controller. 9. LED display To display the set temperature (in C) and timer delay setting (in hours). 10. Transmission source To transmit signals to the air conditioner.

89

Installation Of LCD Remote Controller


Step-By-Step Guide i) First, open up the casing of the LCD remote controller into its top and bottom case using a screwdriver. To do this, insert the screwdriver into the lower slot and slide it in the outward direction. ii) Fix the bottom case onto the wall with the 2 wooden screws provided. Then, insert the 4 connecting wires (from the main board) through the slot on the lower center of the case as shown below. iii) Connect one end in each of the 3 wires to the terminal block behind the top case as illustrated. iv) To select cooling only model or heatpump model, some adjustment required in the dip switch setting. v) Fasten back the top and bottom case into place. Hook the two upper claws into their respective slots and snap the lower part shut.

Dip switch setting for model selection Pin JH & JD Function RESERVE COOL, DRY, FAN COOL, DRY, FAN, HEAT COOL, DRY, FAN HEAT, AUTO NO REAL TIME CLOCK REAL TIME CLOCK WITHOUT DRY FUNCTION DRY FUNCTION Remarks JH-OFF, JD-OFF JH-OFF, JD-ON JH-ON, JD-OFF JH-ON, JD-ON RTC-OFF RTC-ON NO DRY-ON NO DRY-OFF

RTC NO DRY

90

Blower Performance Curves


BLOWER PERFORMANCE CURVE MCC 010CW

91

BLOWER PERFORMANCE CURVE MCC 015CW

92

BLOWER PERFORMANCE CURVE MCC 020CW

93

BLOWER PERFORMANCE CURVE MCC 025CW

94

BLOWER PERFORMANCE CURVE MCC 028CW

95

BLOWER PERFORMANCE CURVE MCC 030CW

96

BLOWER PERFORMANCE CURVE MCC 038CW

97

BLOWER PERFORMANCE CURVE MCC 040CW

98

BLOWER PERFORMANCE CURVE MCC 050CW

99

BLOWER PERFORMANCE CURVE MCC 060CW

100

Model : MDB075BW (Double Blowers)

Model : MDB100BW (Double Blowers)

101

Model : MDB125/150BW

102

Outlines And Dimensions


Indoor Unit Model: MWM 010F W / 015FW

Note : Dimension in mm

Indoor Unit Model : MWM 020FW / 025FW

Note : Dimension in mm

103

Model :

MCK020/025/030/040/050AW MCK015/020/025/030BW
C D F H

MODEL MCK-AW MCK-BW

A 820 650

B 820 650

C 363 345

D 335 323

E 28 22

F 930 727

G 930 727

H 624 489

I 622 489

J I G
J 555 444 K 555 444

104

Model : MCM 020/025DW

Model : MCM 030/040/050DW

Model MCM030DW MCM040DW MCM050DW

A
1174 1674 1674

B
75 75 75

C
1082 1582 1582

D
68 68 68

E
58 93 93

F
156 156 156

G
1214 1714 1714

H
57 57 57

I
670 670 670

J
216 216 216

K
319 319 319

L
879 1379 1379

M
517 517 517

105

Model : MCC010CW

Model : MCC015/020/025CW

Model MCC015CW MCC020CW MCC025CW

A
31 31 31

B
881 1041 1176

C
841 1002 1137

D
802 962 1097

E
10 10 10

F
905 1005 1200

G
72 72 72

H
261 261 261

I
411 411 411

J
349 349 349

K
225 225 225

L
261 261 261

M
171 174 171

N
118 128 118

O
77 55 77

P
54 55 54

106

Model : MCC 028CW

Model : MCC 038CW

107

Model : MCC030CW

Model : MCC040CW

108

Model : MCC050CW

Model : MCC060CW

109

Model : MDB075/100BW
Model
MDB075BW MDB100BW

A
72 94

B
301.8 289.1

Model : MDB125BW

110

Model : MDB150BW

111

General Installation Guide


Preliminary Site Survey
Electrical supply and installation is to conform to LOCAL AUTHORITY's (e.g. National Electricity Board) CODES and REGULATIONS. Voltage supply fluctuation must not exceed 10% of rated voltage. Electricity supply lines must be independent of welding transformers which can cause supply fluctuation. Ensure that the location is convenient for wiring and piping.

Mounting
For ceiling mounted models, locate a position where piping and ducting work can be kept to a minimum. Ensure that overhead supports are strong enough to hold the unit's weight. Position hanger rods and check for alignment with the unit. Check that hangers are secure and that the base of fan coil unit is level in two horizontal positions.

Piping
Drain and water piping must be accurately connected. Please refer to "Specification Sheet" for piping sizes.

Piping Support
All water mains must be adequately supported to carry the necessary weight involved, provisions must be made by the installing contractor to allow for adequate free movement of all vertical and horizontal risers and run outs. Due to the fact that cold water will be circulated through the water mains, a sizeable movement of the water mains can be expected due to contraction. If for example, the piping is rigidly supported with no provision for movement, it is very possible that the tubing of fitting may be broken causing water leakage in the conditioned spaces throughout the building.

Coil Venting
Each standard basic unit coil is equipped with a manually operated air vent which is installed at the end of a small copper line leading into the highest point of the coil. By means of this valve, air may be vented manually, from the coil to keep it operating at full capacity. When water is first introduced into a coil, air is sometimes trapped in the coil tubing. This trapped air will reduce cooling capacity and create "Bubbling" or "Clanking" noise within the units. To release air trapped in the coil, press the air vent head to allow air to flow out of the air vent opening. Release when a steady stream of water appear.

Electrical Connection
As wiring regulations differ from country to country, please refer to your LOCAL ELECTRICAL CODES for field wiring regulations and ensure that they are complied with. Besides, take note of the following general precaution: 1) Ensure that the rated voltage of the unit corresponds to the name plate before commencing wiring work. 2) Provide a power outlet to be used exclusively for each unit and a power supply disconnect and a circuitbreaker for over-current protection should be provided in the exclusive line. 3) The unit must be EARTH to prevent possible hazards due to insulation failure. 4) All wiring must be firmly connected.

112

General Operation Guide


Start-Up
The following procedure must be completed before any attempts is made to put the entire system Into operation: 1) 2) 3) 4) 5) 6) 7) 8) Piping connections completed. Electrical connections completed. Duct connections completed. Auxiliary drain pans in position where required. Drain line draining into drain pans. Filters correctly installed and free of construction debris. Motor-blower assembly rotates freely. Unit Hydrostatically tested and air vented.

Starting The Fan Coil Unit


1) Turn on the switch of water pump. 2) Start water chiller. 3) Operate the fan coil unit by turning on the fan and set the control switch to get the desired speed. 4) Inspect the duct and piping condition and rectify problem (e.g. vibration, noise, etc.) if exist.

Servicing And Maintenance


Fan coil units are designed to operate continuosly with minor routine maintenance. Since fan coil units cool the discharging forced air, the efficiency with which the units operate is directly related to the amount of air passing through the coil.

Air Filters
The function of the air filters is to remove foreign matter such as dirt, soot, pollen and certain other impurities from the air passing through it. A clogged or dirty filter not only fails to do the job for which it is designed, but restricts the flow of air over the coil. The importance of cleaning the filter before it becomes clogged must be greatly stressed. The frequency with which a filter should be cleaned will depend upon the amount of dust and foreign material that enters a unit, and this depends upon location and situation. The washable viledon or saranet filter may be cleaned by tapping the filter on a solid surface to dislodge heavy particles. Wash under stream of warm water, with detergent if necessary. Dry it thoroughly before replacing.

Fan Motor
The fan motor is prelubricated and sealed at the factory. Therefore, no lubricating maintenance is required.

Coils
Clean coil unit by brushing between fins with a nylon brush. Brushing should be followed by cleaning with a vacuum cleaner. The coil may also be cleaned by using a high pressure air hose and nozzle if a compressed air source is available. It should be pointed out that if suitable air filter is used and taken care of properly, the coils need no cleaning.

Drain Pipe
The drain pipe should be checked before operation of unit is begun. If it is clogged, steps should be taken to clean the debris so that condensate will flow out easily.

Replacement Of Parts
Replacement of parts are available through your local dealers. When ordering parts, you must supply 1) Model name of the unit. 2) Serial number of the unit. 3) Part name and number.

113

DOP :
Americas - 13600 Industrial Park Boulevard, P.O. Box 1551, Minneapolis, MINI 55440 USA (612) 553-5330 Asia - Jalan Pengapit 15/19, P.O. Box 7072, 40702 Shah Alam, Selangor Darul Eshan, Malaysia - Tel: 6-03-5594922 - Fax: 6-03-5506980 - Telex: MA 38521 Europe - 42 Cours Jean Jaurs - 17800 Pons - France - Tl: (33) 46 92 33 33 - Tlex: 790 536 F - Tlecopie: (33) 46 91 38 33