McQuay Fan Coil Units
McQuay Fan Coil Units
McQuay Fan Coil Units
Contents
Features ..................................................................................................................... 1 Specifications ............................................................................................................. 3 Unit Selection Procedure ......................................................................................... 11 Cooling Capacity Performance Chart ....................................................................... 14 Heating Capacity Performance Chart ....................................................................... 49 Water Flow Rate Vs Pressure Drop ......................................................................... 66 Correction Factors ................................................................................................... 71 Wiring Diagrams ...................................................................................................... 72 Controllers ............................................................................................................... 85 Blower Performance Curves ..................................................................................... 91 Outlines And Dimensions........................................................................................ 103 General Installation Guide ..................................................................................... 112 General Operation Guide ....................................................................................... 113
Note: Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and experienced with this type of equipment. Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
Warning: Moving machinery and electrical power hazards. May cause severe personal injury or death. Disconnect and lock off power before servicing equipment.
"McQuay" is a registered trademark of McQuay International. All rights reserved throughout the world. 2002 McQuay International "Bulletin illustrations cover the general appearance of McQuay International products at the time of publication and we reserve the right to make changes in design and construction at any time without notice."
Features
Space Saving
Different types of fan coil units are designed to be both versatile and space saving to suit every interior design. Ceiling concealed type for the sophisticated, luxurious floor space saving, all kind of interior decoration; ceiling exposed type for economical and space saving installation; etc.
Zone Control
These fan coil units can be installed in different zones as each unit operates independently. Zone control on energy saving, different comfort requirement; better air distribution needs can therefore be easily achieved.
Specifications
MWM
MODEL
PERFORMANCE High Air Flow (CFM / L/s) Medium Low kcal/hr Nominal Total Cooling Capacity W Btu/hr kcal/hr Sensible Cooling Capacity Nominal Total Heating Capacity (Entering water Temp. : 60C) Water Flow Rate Head Loss (Cooling) Head Loss (Heating) : 60 C COIL Type Tube Fin Connection Number of rows / fin per inch Max. Working Pressure Testing Pressure Surface Area Surface Air Velocity MOTOR Type Power Supply Rated Input power Rated Running Current Poles High Fan Sound Level (dBA) Medium Fan Low Fan Room Temp. Control Condensate Drain Size AIR FILTER WEIGHT DIMENSION (H x W x D) kg mm Air Discharge Operation mm V/Ph/Hz W (50/60Hz) A (50/60Hz) m / ft
2 2
005FW 300 / 510 230 / 390 190 / 320 1210 1410 4800 1179 1375 4680 2772 3220 11000 1.10 / 4.16 0.245 / 1689 0.186 / 1282
007FW 300 / 510 230 / 390 190 / 320 1638 1910 6500 1373 1600 5447 3150 3660 12500 1.54 / 5.83 0.436 / 3006 0.335 / 2310
010FW 270 / 127 230 / 109 190 / 90 2520 2931 10000 1739 2022 6900 4032 4689 16000 2.00 / 7.57 7.77 / 53572 6.09 / 41989
015FW 300 / 142 270 / 127 230 / 109 3024 3517 12000 2026 2356 8040 4536 5275 18000 2.67 / 10.11 12.93 / 89149 10.28 / 70878
020FW 480 / 227 430 / 203 370 / 175 4284 4982 17000 2956 3438 11730 6552 7620 26000 4.22 / 15.97 4.89 / 33715 3.86 / 26614
025FW 580 / 274 485 / 229 380 / 179 5292 6154 21000 3651 4247 14490 8064 9378 32000 5.33 / 20.18 7.40 / 51021 5.86 / 40403
Seamless copper tube mechanically boded to aluminium slit fin. OD 7mm, thickness 0.35 mm. thickness 0.11 mm 1 / 18 (kg/cm2) / (psi) 0.208 / 2.239 0.690 / 135.84 1 / 20 OD 1/2" copper tube 2 / 18 2 / 18 16.4 / 233 30 kg/cm2 for 1 min, leak test : 16 kg/cm2 for 5 min. 0.208 / 2.239 0.198 / 2.131 0.198 / 2.131 0.254 / 2.733 0.690 / 135.84 0.64 / 126.70 0.72 / 140.78 0.89 / 175.63 0.254 / 2.733 1.08 / 212.22 2 / 18 2 / 18
(m/s) / (ft/min)
Permanent split capacitor motor 25 0.11 25 0.11 220 - 240 / 1 / 50 , 208 - 230 / 1 / 60 25 / 26 25 / 26 0.11 / 0.12 4 38 34 30 38 35 31 45 42 39 47 44 42 0.11 / 0.12 53 / 67 0.23 / 0.31 57 / 81 0.24 / 0.38
Micro-computer Controlled Thermostat Automatic Louver (Up & Down) LCD wireless micro-computer remote control 19.05 12 12 Washable Saran Net Filter 12 12 15 15
: Entering air temp. : 26.7 C ( 80 F ) DB, 19.4 C ( 67 F ) WB Entering water temp. : 7.2 C ( 45 F ) Leaving water temp. : 12.8 C ( 55 F ) : Entering air temp. : 21.1 C ( 64 F ) DB Entering water temp. : 60 C ( 140 F ) Leaving water temp. : 55 C ( 131 F )
Heating capacity
Microphone position : 1m in front of the unit & 0.8m below the vertical centre line of the unit. (JIS C 9612)
MODEL PERFORMANCE Air Flow (CFM/CMH) High Medium Low kcal/hr W Btu/hr kcal/hr W Btu/hr kcal/hr W Btu/hr USGPM / LITRES/M psi / Pa psi / Pa
020AW 770 / 1,310 650 / 1,100 630 / 1,070 6,048 7,034 24,000 4,209 4,894 16,700 9,451 10,991 37,500 5.32 / 20.17 2.13 / 14,686 1.70 / 11,721
025AW 810 / 1,380 700 / 1,190 630 / 1,070 6,804 7,913 27,000 4,738 5,510 18,800 10,585 12,309 42,000 6.22 / 23.45 3.16 / 21,774 2.545 / 17,547
MCK 030AW 920 / 1,560 770 / 1,320 700 / 1,190 7,964 9,261 31,600 5,494 6,389 21,800 12,198 14,185 48,400 7.11 / 26.84 4.36 / 30,061 3.55 / 24,476
040AW 1,020 / 1,740 900 / 1,530 790 / 1,340 9,073 10,551 36,000 6,162 7,166 24,450 13,584 15,797 53,900 8.00 / 30.14 7.29 / 50,263 6.07 / 41,851
050AW 1,080 / 1,840 990 / 1,680 910 / 1,540 9,829 11,430 39,000 6,628 7,708 26,300 14,365 16,706 57,000 8.88 / 33.49 10.99 / 75,773 9.20 / 63,459
Sensible Cooling Capacity Nominal Total Heating Capacity (Entering water Temp. : 60 C) Water Flow Rate Head Loss (Cooling) Head Loss (Heating) : 60 C COIL Type Tube Fin Connection Number of rows / fin per inch Max. Working Pressure Testing Pressure Surface Area Surface Air Velocity MOTOR Type Power Supply Rated Input Running Current Poles Control Condensate Drain Size AIR FILTER WEIGHT (Unit + panel) DIMENSION (H x W x D)
Seamless copper tube mechanically bonded to aluminium slit fin OD 9.52 mm, thickness 0.35 mm Thickness 0.11 mm OD 3/4" copper tube 2/12 2/14 2/16 2/16 2/16 16.4 / 233 2 2 30 kg/cm for 1 min, leak test : 16 kg/cm for 5 min 0.459 / 5.022 0.459 / 5.022 0.459 / 5.022 0.459 / 5.022 0.459 / 5.022 0.78 / 153.33 0.82 / 161.29 0.93 / 183.19 1.03 / 203.11 1.09 / 215.05 Permanent split capacitor motor 220 - 240 / 1 / 50, 208 - 230/1/60 151 / 163 164 / 208 192 / 321 0.65 / 0.75 0.69 / 0.98 0.80 / 1.50 6 Micro-computer Controlled Thermostat Automatic Louver (Up & Down) LCD wireless micro-computer remote control 19.05 Washable Saran Net Filter 32 + 4 35 + 4 38 + 4 335 x 820 x 820 ( 363 x 930 x 930 )
21 + 4
40 + 4
: Entering air temp. : 26.7C (80F)DB, 19.4C (67F)WB Entering water temp. : 7.2C (45F) Leaving water temp. : 12.8C (55F) : Entering air temp. : 21.1C (64F)DB Entering water temp. : 60C (140F) Leaving water temp. : 55C (131F)
Heating capacity
MCK
MODEL
PERFORMANCE High Air Flow (CFM / L/s) Medium Low kcal/hr Nominal Total Cooling Capacity W Btu/hr kcal/hr Sensible Cooling Capacity Nominal Total Heating capacity (Entering water Temp. : 60 C) Water Flow Rate Head Loss (Cooling) Head Loss (Heating) : 60 C COIL Type Tube Fin Connection Number of rows / fin per inch Max. Working Pressure Testing Pressure Surface Area Surface Air Velocity MOTOR Type Power Supply Rated Input power Rated Running Current Poles Sound pressure level ( dBA ) High Fan Medium Fan Low Fan Room Temp. Control Condensate Drain Size AIR FILTER WEIGHT (Unit + Panel) DIMENSION - HxWxD ( ) - with panel kg mm Air Discharge Operation mm V/Ph/Hz W (50/60Hz) A (50/60Hz) m2/ft2 (m/s)/(ft/min) (kg/cm 2)/(psi) W Btu/hr kcal/hr W Btu/hr USGPM/LITRES/M psi / Pa psi / Pa
015BW 430 / 203 370 / 175 310 / 146 3150 3660 12500 2331 2708 9250 5292 6150 21000 3.34 / 12.7 0.582 / 4013 0.455 / 3137
020BW 430 / 203 370 / 175 310 / 146 4284 4977 17000 2853 3315 11322 6300 7320 25000 4.44 / 16.8 1.849 / 12749 1.461 / 10074
025BW 500 / 236 450 / 212 390 / 184 5040 5860 20000 3352 3897 13300 7308 8500 29000 5.54 / 21 2.739 / 18885 2.189 / 15093
030BW 607 / 287 537 / 253 475 / 224 5796 6740 23000 3872 4499 15364 8316 9663 33000 6.64 / 25 3.78 / 26063 3.055 / 21064
Seamless copper tube mechanically bonded to aluminium slit fin. OD 9.52 mm, thickness 0.35 mm. thickness 0.11 mm 1 / 18 OD 3/4" copper tube 2 / 14 2 / 14 16.4 / 233 30 kg/cm2 for 1 min, leak test : 16 kg/cm2 for 5 min. 0.431 / 4.637 0.416 / 4.483 0.416 / 4.483 0.416 / 4.483 0.471 / 92.73 0.487 / 95.91 0.567 / 111.53 0.688 / 135.40 2 / 14
Permanent split capacitor motor 72 / 73 0.31 / 0.34 43.7 39 37.5 220 - 240 / 1 / 50 , 208 - 230 / 1 / 60 72 / 73 79 / 88 0.31 / 0.34 6 43.7 39 37.5 Manual Louver LCD wireless micro-computer remote control 19.05 30 + 3 Washable Saran Net Filter 30 + 3 31 + 3 293 x 650 x 650 (363 x 930 x 930) 32 + 3 44 40 38 47 44 40 0.33 / 0.41 108 / 108 0.45 / 0.50
: Entering air temp. : 26.7 C ( 80 F ) DB, 19.4 C ( 67 F ) WB Entering water temp. : 7.2 C ( 45 F ) Leaving water temp. : 12.8 C ( 55 F ) : Entering air temp. : 21.1 C ( 64 F ) DB Entering water temp. : 60 C (140 F) Leaving water temp. : 55 C (131 F)
Heating capacity
Microphone position : MCK015-025B - 1.4m below the facia (JIS C 9612) , MCK030B - 1.5m below the facia (JIS B 8615).
MODEL PERFORMANCE Air Flow (CFM/CMH) High Medium Low kcal/hr W Btu/hr kcal/hr W Btu/hr kcal/hr W Btu/hr USGPM / LITRES/M psi / Pa psi / Pa
020DW 590 / 1,000 530 / 900 420 / 710 5,040 5,862 20,000 3,528 4,102 14,000 7,560 8,792 30,000 4.44 / 16.75 2.95 / 20,315 2.46 / 16,915
025DW 660 / 1,130 650 / 1,110 580 / 990 5,544 6,448 22,000 3,825 4,448 15,180 8,442 9,818 33,500 4.88 / 18.42 3.52 / 24,250 2.83 / 20,191
MCM 030DW 730 / 1,240 720 / 1,220 680 / 1,160 6,552 7,620 26,000 4,455 5,180 17,680 9,674 11,250 38,385 5.76 / 21.77 3.17 / 21,875 2.64 / 18,215
040DW 1,000 / 1,700 950 / 1,620 930 / 1,580 9,535 11,137 38,000 6,485 7,538 25,730 16,207 18,639 63,600 8.44 / 31.82 5.96 / 41,170 4.98 / 34,279
050DW 1,110 / 1,890 1,070 / 1,820 1,000 / 1,700 12,096 14,068 48,000 7,983 9,282 31,680 17,065 19,846 67,715 10.66 / 40.19 9.19 / 63,330 7.65 / 52,731
Sensible Cooling Capacity Nominal Total Heating Capacity (Entering water Temp. : 60 C) Water Flow Rate Head Loss (Cooling) Head Loss (Heating) : 60 C COIL Type Tube Fin Connection Number of rows / fin per inch Max. Working Pressure Testing Pressure Surface Area Surface Air Velocity MOTOR Type Power Supply Rated Input Running Current Poles Sound pressure level ( H / M / L ) Control Condensate Drain Size AIR FILTER WEIGHT DIMENSION (H x W x D)
Seamless copper tube mechanically bonded to aluminium slit fin OD 9.52 mm, thickness 0.35 mm Thickness 0.11 mm OD 3/4" copper tube 3/12 3/12 3/12 4/12 4/14 16.4 / 233 2 2 30 kg/cm for 1 min, leak test : 16 kg/cm for 5 min 0.217 / 2.338 0.217 / 2.338 0.263 / 2.826 0.406 / 4.361 0.406 / 4.361 1.28 / 252.35 1.43 / 282.29 1.31 / 258.32 1.16 / 229.31 1.29 / 254.53 Permanent split capacitor motor 220 - 240 / 1 / 50, 208 - 230/ 1 / 60 130 / 155 132 / 179 240 / 337 0.58 / 0.70 0.58 / 0.80 1.04 / 1.50 4 54 / 53 / 50 51 / 50 / 48 54 / 53 / 52 Micro-computer Controlled Thermostat Automatic Louver (Up & Down) LCD wireless micro-computer remote control 19.05 Washable Saran Net Filter 43 45 70
249 x 1,214 x 670
43
70
: Entering air temp. : 26.7C (80F)DB, 19.4C (67F)WB Entering water temp. : 7.2C (45F) Leaving water temp. : 12.8C (55F) : Entering air temp. : 21.1C (64F)DB Entering water temp. : 60C (140F) Leaving water temp. : 55C (131F)
Heating capacity
MCC MODEL PERFORMANCE Air Flow (CFM/CMH) High Medium Low kcal/hr W Btu/hr kcal/hr W Btu/hr kcal/hr W Btu/hr USGPM / LITRES/M psi / Pa psi / Pa 010CW 300 / 510 280 / 480 240 / 410 2,520 2,931 10,000 1,789 2,081 7,100 4,032 4,690 16,000 2.22 / 8.40 1.53 / 10550 1.21 / 8340 015CW 430 / 730 310 / 530 270 / 460 3,780 4,397 15,000 2,646 3,078 10,500 6,048 7,034 24,000 3.33 / 12.61 3.48 / 24000 2.8 / 19300 020CW 620 / 1,050 610 / 1,040 500 / 850 4,788 5,569 19,000 3,352 3,898 13,300 7,560 8,793 30,000 4.44 / 16.81 2.92 / 20130 2.34 / 16130 025CW 840 / 1,430 790 / 1,340 640 / 1,090 6,048 7,034 24,000 4,234 4,924 16,800 9,324 10,845 37,000 5.55 / 21.01 4.70 / 32410 3.83 / 26410
Sensible Cooling Capacity Nominal Total Heating Capacity (Entering water Temp. : 60 C) Water Flow Rate Head Loss (Cooling) Head Loss (Heating) : 60 C COIL Type Tube Fin Connection Number of rows / fin per inch Max. Working Pressure Testing Pressure Surface Area Surface Air Velocity MOTOR Type Power Supply Rated Input Running Current Poles Control Condensate Drain Size AIR FILTER WEIGHT DIMENSION (H x W x D)
Seamless copper tube mechanically bonded to aluminium slit fin OD 9.52 mm, thickness 0.35 mm Thickness 0.11 mm OD 3/4" copper tube 3/12 (kg/cm ) / (psi)
2 2
3/12
2
3/12
m / ft (m/s) / (ft/min)
30 kg/cm for 1 min, leak test : 16 kg/cm for 5 min 0.129 / 1.39 0.161 / 1.734 0.197 / 2.128 0.228 / 2.461 1.10 / 215.8 1.26 / 248.0 1.48 / 291.4 1.73 / 341.3 Permanent split capacitor motor 220 - 240 / 1 / 50 , 208 - 230 / 1 / 60 71 / 72 0.30 / 0.33 102 / 114 0.43 / 0.53 148 / 172 0.65 / 0.80 180 / 223 0.74 / 1.01
4 Micro-computer Controlled Thermostat LCD wireless micro-computer remote control 19.05 Washable Saran Net Filter 17 261 x 765 x 411 21 261 x 905 x 411 22 261 x 1,065 x 411 25 261 x 1,200 x 411
: Entering air temp. : 26.7C (80F)DB, 19.4C (67F)WB Entering water temp. : 7.2C (45F) Leaving water temp. : 12.8C (55F) : Entering air temp. : 21.1C (64F)DB Entering water temp. : 60C (140F) Leaving water temp. : 55C (131F)
Heating capacity
MCC
MODEL
PERFORMANCE High Air Flow (CFM/CMH) Medium Low kcal/hr Nominal Total Cooling Capacity W Btu/hr kcal/hr Sensible Cooling Capacity Nominal Total Heating Capacity (Entering water Temp. : 60C) Water Flow Rate Head Loss (Cooling) Head Loss (Heating) : 60 C COIL Type Tube Fin Connection Number of rows / fin per inch Max. Working Pressure Testing Pressure Surface Area Surface Air Velocity MOTOR Type Power Supply Rated Input Running Current Poles Room Temp. Control Condensate Drain Size AIR FILTER WEIGHT DIMENSION (H x W x D) kg mm Air Discharge Operation mm V/Ph/Hz W A m / ft
2 2
028CW 1440/2450 1270/2160 1120/1900 6,804 7,914 27,000 4,695 5,460 18,630 7,056 8,207 28,000 6.16/23.31 2.437/16800 1.952/13460
038CW 1540/2620 1450/2460 1260/2140 10,550 12,270 41,864 7,490 8,712 29,723 16,872 19,623 66,951 8.36/31.64 4.992/34420 4.084/28160
Seamless copper tube mechanically boded to aluminium slit fin. OD 9.52 mm, thickness 0.35 mm. thickness 0.11 mm OD 3/4" copper tube 3/18 (kg/cm ) / (psi)
2 2
30 kg/cm for 1 min, leak test : 16 kg/cm for 5 min. 0.264/2.844 0.363/3.909 1.14/224.44 Permanent split capacitor motor 220 - 240 / 1 / 50 300 1.30 4 Micro-computer Controlled Thermostat Automatic Louver (Up & Down) LCD wireless micro-computer remote control 19.05 Washable Saran Net Filter 38 290X942X600 41 310X1247X638 563 2.4 1.764/347.16
(m/s) / (ft/min)
: Entering air temp. : 26.7 C ( 80 F ) DB, 19.4 C ( 67 F ) WB Entering water temp. : 7.2 C ( 45 F ) Leaving water temp. : 12.8 C ( 55 F ) : Entering air temp. : 21.1 C ( 64 F ) DB Entering water temp. : 60 C ( 140 F ) Leaving water temp. : 55 C ( 131 F )
Heating capacity
MCC MODEL PERFORMANCE Air Flow (CFM/CMH) High Medium Low kcal/hr W Btu/hr kcal/hr W Btu/hr kcal/hr W Btu/hr USGPM / LITRES/M psi / Pa psi / Pa 030CW 1,030 / 1,750 820 / 1,390 660 / 1,120 7,308 8,500 29,000 5,189 6,035 20,590 11,592 13,483 46,000 6.66 / 25.21 2.11 / 14550 1.68 / 11580 040CW 1,150 / 1,960 1,025 / 1,740 840 / 1,430 9,576 11,138 38,000 6,799 7,908 26,980 15,120 17,586 60,000 8.88 / 33.61 3.78 / 26060 3.06 / 21100 050CW 1,540 / 2,620 1,430 / 2,430 1,300 / 2,210 12,348 14,362 49,000 8,644 10,053 34,300 19,152 22,276 76,000 11.11 / 42.06 6.48 / 44680 5.36 / 36960 060CW 1,990 / 3,380 1,830 / 3,110 1,630 / 2,770 13,608 15,827 54,000 9,798 11,396 38,880 22,680 26,379 90,000 13.33 / 50.46 1.48 / 10205 1.18 / 8140
Sensible Cooling Capacity Nominal Total Heating Capacity (Entering water Temp. : 60 C) Water Flow Rate Head Loss (Cooling) Head Loss (Heating) : 60 C COIL Type Tube Fin Connection Number of rows / fin per inch Max. Working Pressure Testing Pressure Surface Area Surface Air Velocity MOTOR Type Power Supply Rated Input Running Current Poles Control Condensate Drain Size AIR FILTER WEIGHT DIMENSION (H x W x D)
Seamless copper tube mechanically bonded to aluminium slit fin OD 9.52 mm, thickness 0.35 mm Thickness 0.11 mm OD 3/4" copper tube 3/12 (kg/cm ) / (psi)
2 2
3/12
2
3/12
m / ft (m/s) / (ft/min)
30 kg/cm for 1 min, leak test : 16 kg/cm for 5 min 0.31 / 3.44 0.41 / 4.40 0.48 / 5.16 1.70 / 334.30 1.78 / 350.00 1.96 / 385.66 Permanent split capacitor motor 220 - 240 / 1 / 50 , 208 - 230 / 1 / 60
4 Micro-computer Controlled Thermostat LCD wireless micro-computer remote control 19.05 Washable Saran Net Filter 39 378 x 929 x 474 42 378 x 1,045 x 474 54 378 x 1,299 x 474 62 378 x 1,499 x 474
: Entering air temp. : 26.7C (80F)DB, 19.4C (67F)WB Entering water temp. : 7.2C (45F) Leaving water temp. : 12.8C (55F) : Entering air temp. : 21.1C (64F)DB Entering water temp. : 60C (140F) Leaving water temp. : 55C (131F)
Heating capacity
MDB MODEL PERFORMANCE Air Flow (CFM/CMH) Nominal Total Cooling Capacity kcal/hr W Btu/hr kcal/hr W Btu/hr kcal/hr W Btu/hr USGPM / LITRES/M psi / Pa psi / Pa mmAq 075BW 2,500 / 4,250 19,152 22,274 76,000 13,598 15,810 53,960 30,996 36,049 123,000 16.88 / 63.64 8.72 / 60,050 7.26 / 50,000 10 100BW 3,200 / 5,440 24,696 28,722 98,000 18,028 20,961 71,540 40,320 46,700 160,000 21.77 / 82.06 2.65 / 18,230 2.20 / 15,179 10 125BW 4,200 / 7,140 32,760 38,101 130,000 23,587 27,425 93,600 53,734 62,490 213,215 28.88 / 108.86 3.55 / 24,472 2.96 / 20,377 15 150BW 4,600 / 7,820 41,076 47,773 163,000 29,164 33,909 115,730 66,348 77,160 263,270 36.22 / 136.49 2.77 / 19,092 2.31 / 15,897 15
Sensible Cooling Capacity Nominal Total Heating Capacity (Entering water Temp. : 60 C) Water Flow Rate Head Loss (Cooling) Head Loss (Heating) : 60 C Ext. static COIL Type Tube Fin Connection Number of rows / fin per inch Max. Working Pressure Testing Pressure Surface Area Surface Air Velocity MOTOR Type Power Supply Rated Input Running Current Poles Number of motors Sound pressure level Control Condensate Drain Size FAN Type/Drive Number of Fans AIR FILTER (OPTIONAL) Type Length x Height Quantity WEIGHT DIMENSION (H x W x D)
Seamless copper tube mechanically bonded to aluminium slit fin OD 9.52 mm, thickness 0.35 mm Thickness 0.11 mm 3/14
2 (kg/cm ) / (psi)
OD 1 /8" copper tube 4/12 3/14 16.4 / 233 30 kg/cm 2 for 1 min, leak test : 16 kg/cm2 for 5 min 0.54 / 5.82 1.01 / 10.83 2.75 / 550 1.94 / 388
4/14
m / ft (m/s) / (ft/min)
V/Ph/Hz W A
Permanent split capacitor motor 220 - 240 / 1 / 50 , 208 - 230 / 1 / 60 415 / 3 / 50 , 415 / 3 / 60 810 / 1062 3.70 / 5.16 2 62 1008 / 1310 4.22 / 7.04 4 2730 / 1620 3.39 / 5.70 3370 / 1999 3.39 / 5.70 1 67
dBA mm
mm kg mm 2 96
572 x 1,502 x 761
1 145
: Entering air temp. : 26.7C (80F)DB, 19.4C (67F)WB Entering water temp. : 7.2C (45F) Leaving water temp. : 12.8C (55F) : Entering air temp. : 21.1C (64F)DB Entering water temp. : 60C (140F) Leaving water temp. : 55C (131F)
Heating capacity
10
Step 1 Determine type of fan coil units to be used, i.e. ceiling cassette (MCK-AW Series); ceiling exposed (MCM-DW Series); etc.
Step 2 Select a tentative unit size based on cooling capacities at nominal air flow. Design entering air temperatures and required water flows from cooling capacities chart (Page 14 - 35) or the nominal capacities ratings (Page 3 - 10) from standard specification.
Step 3 Determine the nominal unit cooling capacities for the unit selected. If the cooling capacities chart must be used, the following information must be known :a) Design water temperature rise b) Design entering water temperature c) Design entering air dry bulb temperature d) Design entering air wet bulb temperature Example of how to read the cooling performance chart.
MCK050AW
11
Step 4 If air flow value is different from the nominal value(high speed), then refer to specification from Page 3 to 10 for the air flow required(medium or low speed). Determine the total and sensible correction factor from Air Flow Capacity Correction Factor (Page 57). Step 5 If the unit is to operate at an altitude above sea level, multiply the capacity correction factors by an Altitude Correction Factors. Refer to Page 57.
Step 6 Calculate the actual cooling capacity by multiply the nominal capacity (from Step 3) with Air Flow Capacity Correction Factor from Step 4 and the Altitude Correction Factor from Step 5. Actual Capacity, W = Nominal capacity (Step 3) x Air Flow Capacity Correction Factor (Step 4) x Altitude Correction Factor (Step 5) Step 7 Water flow rate can be determined by: Litres/Min = Total Cooling Capacity, W 70 x Water Temperature Rise C
USGPM
Step 8 Heating Capacities at nominal air flow (Page 36 to 51 - Heating Performance Chart) are based on standard condition of 60C EWT and 21C EAT. The actual heating capacity can be obtained by using the Heating Capacity Correction Factor (Page 57) and Altitude Correction Factor as per Step 5. Hence Actual Heating Capacity, W = Nominal Capacity (Page 36 to 51) x Heating Capacity Correction Factor (Page 57) x Air Flow Capacity Correction Factor (Step 4) x Altitude Correction Factor (Step 5)
Step 9 Water Pressure Drop Tables are on Page 52 to 56. EXAMPLE Select a ceiling cassette type fan coil unit at the following design specification: Room design condition Room Cooling Load Room Heating Load Entering water temperature Water temperature rise Air Volume Altitude : 26.7C DB / 19C WB : 7 kW sensible capacity / 10 kW total capacity : 10 kW : 7C cooling / 54C heating : 5C : 1700 cmh : 600 m
SOLUTION Step 1 Based on the type of fan coil required and the design conditions, tentatively select MCK050AW. From the cooling capacity performance chart (Page 15), at 26.7C DB / 19C WB air temperature, 7C entering water temperature and with 5C water temperature rise, the cooling capacity for this unit is 11 kW total capacity and 7.6 kW sensible
12
Step 2 From page 57, the air flow correction factor table, at high speed, the air volume is 1840 cmh and medium speed is 1680 cmh, hence high speed is selected. And the correction factor is hence 1.0. If lower air flow required, then use the medium and low fan speed. The correction factor can be determined by getting the ratio of air flow (i.e. medium or low speed / high speed). Step 3 As the unit is operating at 600m above sea level, the Altitude correction factor is 0.98 total and 0.93 sensible. Step 4 Multiply the cooling capacities obtained from step 1 (as per specification and design condition) by correction factors from (2) and (3) Actual total cooling capacity Actual sensible cooling capacity Step 5 Water flow rate = 11 x 1.0 x 0.98 kW = 7.6 x 1.0 x 0.93 kW = 10.78 kW = 7.068 kW
= Litres/M
10780 W 70 x 5
30.8
Step 6 From Heating Capacity Performance Chart (Page 40), determine the heating capacity at the nominal air
MCK050AW
volume by using the flow rate calculated in Step 5. The heating capacity is at 16.18 kW. Step 7 From Heating Capacity Correction Factor Tables at 54.4C water entering temperature and 26.7C entering air temperature, the correction factor is 0.717, Actual Heating Capacity Step 8 Water Pressure Drop can be estimated from water Pressure Drop Table (Page 52 to 56) using interpolate method: At flow rate of 30.8 Litres/Min, the nominal pressure drop is 68,322 Pa Pressure drop correction factor = 1.2947 - 0.0021 x (EWTC x 1.8 + 32) = 1.0234 Hence the actual pressure drop = nominal pressure drop x correction factor = 69,921 Pa. 13 = 16.18 x 0.98 x 0.717 = 11.37 kW
MWM005FW
14
MWM007FW
15
MWM010FW
16
MWM015FW
17
MWM020FW
18
MWM025FW
19
MCK020AW
20
MCK025AW
21
MCK030AW
22
MCK040AW
23
MCK050AW
24
MCK015BW
25
MCK015BWN
26
MCK020BW
27
MCK025BW
28
MCK030BW
29
MCM020DW
30
MCM025DW
31
MCM030DW
32
MCM040DW
33
MCM050DW
34
MCC010CW
35
MCC015CW
36
MCC020CW
37
MCC025CW
38
MCC030CW
39
MCC040CW
40
MCC050CW
41
MCC060CW
42
MCC028CW
43
MCC038CW
44
MDB075BW
45
MDB100BW
46
MDB125BW
47
MDB150BW
48
HEATING CAPACITY - W
82.00
80.00
78.00
76.00
74.00
72.00 4.50
5.50
6.50
7.50
8.50
9.50
10.50
MWM015FW AWM15FW
92.00 91.00
HEATING CAPACITY- W
90.00 89.00 88.00 87.00 86.00 85.00 84.00 83.00 82.00 6.00
7.00
8.00
9.00
10.00
11.00
12.00
13.00
14.00
15.00
49
MWM020FW AWM20FW
134.00
132.00
HEATING CAPACITY - W
130.00
128.00
126.00
124.00
122.00
120.00
118.00 9.00
10.00
11.00
12.00
13.00
14.00
15.00
16.00
17.00
18.00
19.00
20.00
21.00
22.00
23.00
MWM025FW AWM25FW
166.00 164.00
HEATING CAPACITY- W
162.00 160.00 158.00 156.00 154.00 152.00 150.00 148.00 146.00 11.00
13.00
15.00
17.00
19.00
21.00
23.00
25.00
27.00
29.00
50
MCK020AW
MCK025AW
51
MCK030AW
MCK040AW
52
MCK050AW
53
MCK015BW
108.00 106.00
104.00
HEATING CAPACITY - W
102.00
100.00
98.00
96.00
94.00
92.00 7.00
8.00
9.00
10.00
11.00
12.00
13.00
14.00
15.00
16.00
17.00
18.00
MCK020BW
130.00 129.00 128.00 127.00 126.00 HEATING CAPACITY- W 125.00 124.00 123.00 122.00 121.00 120.00 119.00 118.00 117.00 116.00 10.00
12.00
14.00
16.00
18.00
20.00
22.00
24.00
54
MCK025BW
144.00
142.00
138.00
136.00
134.00
132.00
130.00 12.00
13.00
14.00
15.00
16.00
17.00
18.00
19.00
20.00
21.00
22.00
23.00
24.00
25.00
26.00
27.00
28.00
29.00
30.00
MCK030BW
156.00
154.00
HEATING CAPACITY- W
152.00
150.00
148.00
146.00
144.00 15.00
20.00
30.00
35.00
55
MCM020DW
MCM025DW
56
MCM030DW
MCM040DW
57
MCM050DW
58
MCC010CW
MCC015CW
59
MCC020CW
MCC025CW
60
MCC030CW
MCC040CW
61
MCC028CW
13800
13300
HEATING CAPACITY - W
12800
12300
MCC038CW
20500
20000
HEATING CAPACITY - W
19500
19000
18500
18000
62
MCC050CW
MCC060CW
63
MDB075BW
MDB100BW
64
MDB125BW
MDB150BW
65
MWM015FW
MWM020FW
MWM025FW
Note : a. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * ( EWTC * 1.8 + 32 ) b. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * EWTF
66
MODELS MCK020AW
MCK025AW
MCK030AW
MCK040AW
MCK050AW
MODELS MCK015BW
MCK020BW
MCK025BW
MCK030BW
FLOW RATE LITRES / M USGPM 7.53 1.99 10.07 2.66 12.60 3.33 15.10 3.99 17.64 4.66 10.07 2.66 13.44 3.55 16.81 4.44 20.14 5.32 23.50 6.21 12.60 3.33 16.81 4.44 21.01 5.55 25.21 6.66 29.41 7.77 15.10 3.99 20.14 5.32 25.21 6.66 30.24 7.99 35.28 9.32
WATER PRESSURE DROP Pa PSI 1.26 0.183 2.09 0.304 3.13 0.455 4.33 0.628 5.73 0.831 4.02 0.583 6.74 0.978 10.07 1.461 13.96 2.026 18.31 2.658 5.98 0.868 10.07 1.462 15.08 2.189 21.04 3.053 28.10 4.078 8.32 1.208 15.22 2.209 21.04 3.054 29.59 4.295 39.36 5.713
Note : a. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * ( EWTC * 1.8 + 32 ) b. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * EWTF
67
MODELS MCM020DW
MCM025DW
MCM030DW
MCM040DW
MCM050DW
Note : a. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * ( EWTC * 1.8 + 32 ) b. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * EWTF
68
MODELS MCC010CW
MCC015CW
MCC020CW
MCC025CW
MCC028CW
MCC030CW
MCC038CW
MCC040CW
MCC050CW
MCC060CW
Note : a. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * ( EWTC * 1.8 + 32 ) b. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * EWTF
69
MODELS MDB075BW
MDB100BW
MDB125BW
MDB150BW
Note : a. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * ( EWTC * 1.8 + 32 ) b. PRESSURE DROP CORRECTION FACTOR = 1.2947 0.0021 * EWTF
70
Correction Factors
ALTITUDE CORRECTION FACTORS Elevation, m Total Capacity 0 1.00 300 0.99 600 0.98 900 0.97 1200 0.96 1500 0.94 1800 0.93
HEATING CAPACITY CORRECTION FACTORS ENTERING TEMPERATURE, C EAT C 37.8 43.3 45.0 48.8 54.4 60.0 65.5 71.1 4.4 0.838 0.980 1.021 1.122 1.265 1.406 1.552 1.698 7.2 0.771 0.913 0.954 1.055 1.198 1.379 1.485 1.631 10.0 0.700 0.843 0.885 0.986 0.130 1.272 1.417 1.563 12.7 0.631 0.773 0.817 0.918 1.062 1.205 1.349 1.495 15.5 0.562 0.705 0.748 0.848 0.992 1.137 1.281 1.427 18.3 0.493 0.636 0.679 0.779 0.923 1.070 1.212 1.358 21.1 0.424 0.567 0.610 0.711 0.855 1.000 1.146 1.290 23.9 0.354 0.498 0.541 0.642 0.786 0.932 1.078 1.222 26.7 0.284 0.428 0.471 0.573 0.717 0.863 1.008 1.155
76.7 1.845 1.778 1.710 1.639 1.572 1.504 1.438 1.369 1.302
82.2 1.988 1.920 1.853 1.786 1.719 1.650 1.583 1.515 1.449
87.7 2.134 2.067 2.000 1.931 1.865 1.799 1.730 1.664 1.597
Notes : Adjusted capacity, W (@ Nominal air flow) = base heating capacity (@ nominal 60C EWT, 21.1C EAT) x Heating Capacity Correction Factor
71
Wiring Diagrams
Model : MWM005/007/010/015FW (G6 Controller)
72
73
74
75
76
77
78
Model : MCK015/020/025/030BW
79
80
Model : MCM020/025/030/040/050DWN
81
Model : MCC010/015/020/025CWN
Model : MCC028/030/038/040/050/060CW
82
Model : MCC028/030/038/040/050/060CWN
83
84
Controllers
TYPE OF CONTROLLER VS TYPE OF FAN COIL MODELS
MCK020~050AW MCM020~050DW MCC010~060CW MDB075~150BW
STANDARD CONTROLLER
G6 WIRELESS CONTROL G6 WIRELESS CONTROL NETWARE 2 CW (WIRED CONTROLLER) WITHOUT CONTROLLER
OPTIONAL CONTROLLER
NETWARE 2 CW (WIRED CONTROLLER) NETWARE 2 CW (WIRED CONTROLLER) -
SELF DIAGNOSIS TABLE Wireless Power LED Other LEDs Blinks 4 times Fan blinks Blinks 4 times Sleep blinks Blinks 1 time Cool blinks Blinks 2 times Cool & Fan blinks OPERATION GUIDE FOR G6 Wired 7 Segment Display E1 Blinking E2 Blinking E4 Blinking E6 Blinking Operation / Faulty Indication Room sensor contact loose / short Indoor coil sensor contact loose / short Pipe water temperature fault Pump faulty
7
FAN SPEED AND VENTILATION MODE SELECTION Press the button until the desired fan speed is achieved.
8
SIGNAL TRANSMISSION INDICATION Blink to confirm the last setting has been send to the unit.
2
TEMPERATURE SETTING Set the desire room temperature. Press button to increase or decrease the set temperature. Setting range are between 16C to 30C setting (60F to 80F)(Optional setting from 20C to 30C). Press or button simultaneously will toggle the temperature setting between C and F.
6
OPERATION MODES Press the mode button for select the type of operating mode. Cooling only unit: CoolDryFan. Heating cycles: CoolDryHeatFan.
1 5
TIMER SETTING Press set button to activate the timer setting (from 1 hour to 15 hour) of the air conditioning unit. It will be in "On" or "Off" condition after the set time depending to the current condition (either from "On" to Off" or vise versa) To cancel the timer setting, press the button continuously until the timer display goes off. ON / OFF switch Press to start the air conditioner unit. Press again to stop the unit.
4
SLEEP MODE Press the button to activate sleep mode.
This mode can only be activated while in cooling or heating mode operation. If it is activated in COOL mode, the set temperature will be increase 0.5C after 30 minutes, 1C after 1 hour and 2C after 2 hours.
3
AUTOMATIC AIR SWING Press the button to activate the automatic air swing function. The swing angle ranging from horizontal to 25 to bottom.
85
Netware 2
D A B C E
F G
Display
A : Fan Speed Display Displays the fan speed setting (Auto/High/Medium/Low) B : Operation Mode Display Displays the current mode of operation. C : Sleep Display Display the sleep / energy saving status. D : Error Display E : Swing Display Display the aur swing status. F : Key Lock Display Display indicates when key lock function is activated. G : C or F Display Display the temperature in C or F. H : Current Time Start / Stop Time Display Display the current time as well as the start and stop time programmed. I : On / Off Status Lamp Display J : Set Temperature or Room Temperature Display Display the set or room temperature. Other functions Last state memory using battery back up. For 7-days programmable time option, battery back up is used to retain the last state data. Units without battery back up will depend on the EEPROM on the main board. Error Indicator Error code will be shown for any abnormal condition detected. Refer to main board error codes for detail.
86
L P Q N M
Operation
K : Operating Lamp L : On / Off Starting operation : When the unit is off, press the ON/OFF button. The operation LED lights and the unit will be turned on. Stopping operation : When the unit is on, press the ON/OFF button. The operation LED is extinguished and controls are turned off. M : Set Temperature Press this button to set the temperature. By pressing up or down once, temperature changes by 1C (or 1F). The temperature range is16C to 30C (60F to 85F). In FAN mode, temperature can not be set. Pressing up and down buttons simultaneously will toggle the temperature unit between C and F. When set temperature button is pressed, the set temperature will be displayed for 5 seconds. After that, room temperature will be displayed. N : Mode Press MODE button to select operation mode from Cool, Heat, Auto, Dry and Fan. The display will show the selected mode. O : Fan Press FAN button to select Auto, High, Medium or Low fan speed. P : Swing Press SWING button to activate the air sweep function. Q : Sleep Press SLEEP button to activate the sleep or energy saving mode.
87
S R
R : Timer Hold / Resume Display S : Current Time Display T : Operating Lamp U : Key Lock This feature protects the controls from being tampered with by children or unauthorized persons. To activate, press the MINUTE button three times consecutively. KEY LOCK symbol will appear on the LCD display. During this time, ON/OFF button and FAN button can be used. To cancel this feature, press the MINUTE button again three times consecutively. V : Minute When the control is in set clock or set timer mode, pressing the HOUR button will change the set hour. W : Hour When the control is in set clock or set timer mode, pressing the HOUR button will change the set hour. X : Day When the control is in set clock or set timer mode, pressing the DAY button will change the set day. Y : Clock Press button once to set the clock mode. Press button again to disable the clock mode. When the clock mode is activated, the time and date can be set or changed by pressing the DAY, HOUR or MINUTE buttons. Z : Timer Hold / Resume If 7-days timer is set, the word TIMER ACTIVE is displayed. To clear the timer setting, press and hold the HOLD button for 2 to 3 seconds until the word TIMER ACTIVE is no longer displayed. To resume the timer setting after the timer has been placed on hold, press and hold the HOLD button again for 2 to 3 seconds until the word TIMER ACTIVE is displayed.
88
10
9
SENSOR ON/OFF
4 4
FAN ON/OFF
1 2
AUTO
2 5
TEMP
3 7
SWING
TEMP
6
SLEEP
TIMER
6 5
TIMER MODE
SLM
AC5300 (OPTIONAL)
1. ON/OFF switch Press to start the air conditioner unit. Press again to stop the unit. 2. Temperature setting Set the desired room temperature. Press button to increase or decrease the set temperature. Setting range are between o o o o 16 C to 30 C (60 F to 80 F). 3. Operation Modes Press the mode button for select the type of operating mode. - Cooling Only : COOL, DRY, FAN - Heat Pump : AUTO, COOL, DRY, HEAT, FAN (AUTO mode is represented by both COOL and HEAT LED light on) 4. Fan Speed selection. Press the button until the desired fan speed is achieved. 5. Timer. Press the set button to select the switch timer of the air conditioner unit (the setting range is between 1 to 10 hours).
6. Sleep mode Press button to activate the sleep function. This function can only be activated under cool or heating mode operation. When it is activated under cool mode operation, the o set temperature will increase 0.5 C after 30 o o minutes, 1 C after 1 hour and 2 C after 2 hours. If it is activated under HEAT mode operation, the set temperature will be decreased 0.5 C after 30 minutes, 1 C after 1 hour and 2 C after 2 hours. 7. Air Swing Press button to activate the automatic air swing function. 8. Sensor Infra red sensor to receive signals from wireless controller. 9. LED display To display the set temperature (in C) and timer delay setting (in hours). 10. Transmission source To transmit signals to the air conditioner.
89
Dip switch setting for model selection Pin JH & JD Function RESERVE COOL, DRY, FAN COOL, DRY, FAN, HEAT COOL, DRY, FAN HEAT, AUTO NO REAL TIME CLOCK REAL TIME CLOCK WITHOUT DRY FUNCTION DRY FUNCTION Remarks JH-OFF, JD-OFF JH-OFF, JD-ON JH-ON, JD-OFF JH-ON, JD-ON RTC-OFF RTC-ON NO DRY-ON NO DRY-OFF
RTC NO DRY
90
91
92
93
94
95
96
97
98
99
100
101
Model : MDB125/150BW
102
Note : Dimension in mm
Note : Dimension in mm
103
Model :
MCK020/025/030/040/050AW MCK015/020/025/030BW
C D F H
A 820 650
B 820 650
C 363 345
D 335 323
E 28 22
F 930 727
G 930 727
H 624 489
I 622 489
J I G
J 555 444 K 555 444
104
A
1174 1674 1674
B
75 75 75
C
1082 1582 1582
D
68 68 68
E
58 93 93
F
156 156 156
G
1214 1714 1714
H
57 57 57
I
670 670 670
J
216 216 216
K
319 319 319
L
879 1379 1379
M
517 517 517
105
Model : MCC010CW
Model : MCC015/020/025CW
A
31 31 31
B
881 1041 1176
C
841 1002 1137
D
802 962 1097
E
10 10 10
F
905 1005 1200
G
72 72 72
H
261 261 261
I
411 411 411
J
349 349 349
K
225 225 225
L
261 261 261
M
171 174 171
N
118 128 118
O
77 55 77
P
54 55 54
106
107
Model : MCC030CW
Model : MCC040CW
108
Model : MCC050CW
Model : MCC060CW
109
Model : MDB075/100BW
Model
MDB075BW MDB100BW
A
72 94
B
301.8 289.1
Model : MDB125BW
110
Model : MDB150BW
111
Mounting
For ceiling mounted models, locate a position where piping and ducting work can be kept to a minimum. Ensure that overhead supports are strong enough to hold the unit's weight. Position hanger rods and check for alignment with the unit. Check that hangers are secure and that the base of fan coil unit is level in two horizontal positions.
Piping
Drain and water piping must be accurately connected. Please refer to "Specification Sheet" for piping sizes.
Piping Support
All water mains must be adequately supported to carry the necessary weight involved, provisions must be made by the installing contractor to allow for adequate free movement of all vertical and horizontal risers and run outs. Due to the fact that cold water will be circulated through the water mains, a sizeable movement of the water mains can be expected due to contraction. If for example, the piping is rigidly supported with no provision for movement, it is very possible that the tubing of fitting may be broken causing water leakage in the conditioned spaces throughout the building.
Coil Venting
Each standard basic unit coil is equipped with a manually operated air vent which is installed at the end of a small copper line leading into the highest point of the coil. By means of this valve, air may be vented manually, from the coil to keep it operating at full capacity. When water is first introduced into a coil, air is sometimes trapped in the coil tubing. This trapped air will reduce cooling capacity and create "Bubbling" or "Clanking" noise within the units. To release air trapped in the coil, press the air vent head to allow air to flow out of the air vent opening. Release when a steady stream of water appear.
Electrical Connection
As wiring regulations differ from country to country, please refer to your LOCAL ELECTRICAL CODES for field wiring regulations and ensure that they are complied with. Besides, take note of the following general precaution: 1) Ensure that the rated voltage of the unit corresponds to the name plate before commencing wiring work. 2) Provide a power outlet to be used exclusively for each unit and a power supply disconnect and a circuitbreaker for over-current protection should be provided in the exclusive line. 3) The unit must be EARTH to prevent possible hazards due to insulation failure. 4) All wiring must be firmly connected.
112
Air Filters
The function of the air filters is to remove foreign matter such as dirt, soot, pollen and certain other impurities from the air passing through it. A clogged or dirty filter not only fails to do the job for which it is designed, but restricts the flow of air over the coil. The importance of cleaning the filter before it becomes clogged must be greatly stressed. The frequency with which a filter should be cleaned will depend upon the amount of dust and foreign material that enters a unit, and this depends upon location and situation. The washable viledon or saranet filter may be cleaned by tapping the filter on a solid surface to dislodge heavy particles. Wash under stream of warm water, with detergent if necessary. Dry it thoroughly before replacing.
Fan Motor
The fan motor is prelubricated and sealed at the factory. Therefore, no lubricating maintenance is required.
Coils
Clean coil unit by brushing between fins with a nylon brush. Brushing should be followed by cleaning with a vacuum cleaner. The coil may also be cleaned by using a high pressure air hose and nozzle if a compressed air source is available. It should be pointed out that if suitable air filter is used and taken care of properly, the coils need no cleaning.
Drain Pipe
The drain pipe should be checked before operation of unit is begun. If it is clogged, steps should be taken to clean the debris so that condensate will flow out easily.
Replacement Of Parts
Replacement of parts are available through your local dealers. When ordering parts, you must supply 1) Model name of the unit. 2) Serial number of the unit. 3) Part name and number.
113
DOP :
Americas - 13600 Industrial Park Boulevard, P.O. Box 1551, Minneapolis, MINI 55440 USA (612) 553-5330 Asia - Jalan Pengapit 15/19, P.O. Box 7072, 40702 Shah Alam, Selangor Darul Eshan, Malaysia - Tel: 6-03-5594922 - Fax: 6-03-5506980 - Telex: MA 38521 Europe - 42 Cours Jean Jaurs - 17800 Pons - France - Tl: (33) 46 92 33 33 - Tlex: 790 536 F - Tlecopie: (33) 46 91 38 33