FCU McQUAY

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Catalog

C: 700-3

McQuay Horizontal Concealed Fan Coil Unit


Model THC (Vintage B) Sizes 200 Through 1200 CFM

Table of Contents
Nomenclature.......................................................... page  Introduction............................................................. page 3 Design Features...................................................page 3-4 Fan coil Construction Illustration .......................... page 3 Performance Data ............................................. pages 5-6 Cooling Capacity (-Pipe) ..................................... page 5 Heating Capacity (-Pipe) ..................................... page 5 General Unit Data (-Pipe) ................................... page 5 Cooling Capacity (4-Pipe) ..................................... page 6 1-Row Heating Capacity (4-Pipe) ......................... page 6 General Unit Data (4-Pipe) ................................... page 6 Dimensional Data ................................................... page 7 Air Volume Capacity Data......................................... page 8 Motor Data ................................................................ page 8 Wiring Diagrams ..................................................... page 9 Engineering Guide Specifications ................. page 10-11

All standard units All custom units

Ratings certified by the Air Conditioning & Refrigeration Institute (ARI)

Nomenclature
Fan Coil Description /Type of Product
THC = Horizontal THC Concealed

F THC 2 H02 A

A 70 A 69 AX 20 A A
SKU Type

A = Stock C = Build to Order

Design Series
1 = A Design 2 = B Design

Power Connection
A = Junction Box

Unit Size

Nominal Cfm H02 = 200 H04 = 400 H03 = 300 H06 = 600 H12 = 1200 A = 115V-60-1 E = 208/230V-60-1 J = 277-265V-60-1 A = 3-Row Coil

H08 = 800 H10 = 1000

17 = Rear Ducted with Plenum, Filter & Duct Collar 20 = No Plenum, Open Return

Return Air

Discharge Controls

AX = Front Discharge with Built in Duct Collar 00 = JBox with Terminal Strip & Wired Motor Leads 69 = LV-3SP JBox, DDC Ready Interface and Toggle Disconnect Switch 70 = Overflow Switch, LV-3SP, DDC Ready Interface and Toggle Disconnect Switch

Power Supply/Motor Voltage

Main Coil (Heating/Cooling) Secondary Coil (Heating)


70 = 1-Row Heating

Hand Orientation

A = Same Hand - Left B = Same Hand Right

Page  of 1 / Catalog 700

Introduction
McQuay fan coils have been widely applied in hotels, apartments, dormitories and military barracks, assisted living facilities and offices. They have earned a reputation for quality - providing years of efficient, reliable, quiet heating and cooling and easy, low-cost installation and maintenance. The Model THC horizontal concealed fan coil unit is a slim, lightweight unit that is ideal for installation in ceilings where height is limited. Units are available in seven sizes from 200 to 1,200 cfm.

Quiet and Efficient Centrifugal Fan-Motor Assembly


With a dynamically balanced centrifugal fan wheel and a high efficiency motor assembly, the THC offers you: 1. Minimized vibration. 2. Low noise operation. 3. Low operating cost. 4. 4 speed tap motor for better speed control.

Design Features
Slim Profile
The highly compact, super lightweight design of the Model THC fan coil unit makes it ideal for inside ceiling installations where height is limited.

Indoor Air Quality Design


1. Coils
All THC water coils feature aluminum blue fins mechanically bonded to seamless copper tubes. The blue fins are covered with an epoxy polymer that causes condensation to drip off more quickly, preventing mold build-up and increasing the coil and fin life expectancy. Hand operated brass air vent, conveniently located over the drain pan, requires no tools for venting, and is supplied with a clear plastic hose to prevent spills.

High Efficiency Coil

Unique coil design promotes the mixture of warm and cold air, resulting in high thermal efficiency and lower operating costs.

Fan coil Construction Illustration


Top Panels built to keep insulation out of airstream LV-3SP Jbox - Interface Control Junction Box (Optional) Units with Plenum, removable Filter from either side of the unit or bottom

Quiet Centrifugal Fan Assembly Service-friendly Manual Air Vent

High Efficiency Coil

Terminal Box (Basic)

Threaded Piping Connections Extended Positive Slope, Indoor Air Quality Drain Pan

Auxiliary Overflow Drain Connection 3/8" I.D. Main Condensate Drain Connection 1/2" O.D. Smooth

Page 3 of 1 / Catalog 700

2. Drain Pan

Galvanized or stainless steel. Extends past the coil to collect condensation from valve and piping packages. Stamped with no welded corners. Positively sloped to provide proper drainage and minimize microbial growth. Equipped with main condensate and auxiliary drain connections to provide overflow protection. Easily removable. Coated with a thick layer of powder paint and baked for easy cleaning and to help protect against microbial growth and corrosion. Insulated with form-fitted, closed cell insulation to prevent condensation build-up on the exterior of the drain pan. Units are available with or without a return air plenum. Units with a plenum are supplied with a high quality filter, filter guide and 3/4" return air duct collar. Easy filter removal encourages frequent changing, especially when the unit is used with a McQuay T170 thermostat, which has a filter reminder. Aluminum foil faced insulation is used in the return air plenum to prevent glass fibers from entering the air stream, to reduce unit sweating, and to attenuate fan noise. Top and side panels surrounding the coil are also insulated with aluminum foil face to prevent the possibility of condensation forming on the outside of the cabinet.

Electrical Connection - Control Interface


All remote thermostats and controls generally require low voltage control wiring from the thermostat/control device to the unit control box. That is why McQuay provides a full range of control options. See Thermostats and Controls below.

Thermostats and Controls


Wall-mounted thermostats are available for all applications, ranging from a simple thermostat and/or 3-speed switch to a digital, ADA display thermostat with autostage control.
Note: For details on thermostats and wiring refer to ED18513.

Factory installed options include:

3. Return Air Plenum

Basic: A single point power connection junction box that consists of a terminal strip for line-voltage control connection to an Off, Hi, Med, Lo switch, plus a thermostat or a control. DDC ready interface via an LV-3SP control box: For low-voltage applications, it includes three 24 volt relays, a line voltage/24volt transformer, two sets of terminal strips and a toggle disconnect. This interface control can be used with a simple 24 volt thermostat or with building automation systems. This interface is also available as a field installed option.

Interface Control Junction Box

Flexible Coil and Piping Connections

Units are easily converted to opposite-hand orientation without requiring additional parts or a conversion kit. Heating and cooling pipe connections are located on the same end. Four pipe coils are factory installed in the reheat position, but are easily field-converted to the preheat position. Coils can be factory installed in the preheat position as a special request.

Note: For wiring diagram details for Vintage B THC units and the LV-3SP Jbox refer to Certified Drawing FC-THC-H02-H012

Valve Packages

Threaded or Sweat Connections

Coils feature a brass header with 3/4" FPT connections to facilitate quick installation of McQuay threaded or quick-connect, factory built valve packages. A galvanized steel cover plate protects the header and provides additional structural support to facilitate connection of any type of valve package and matched load pumps. If sweat copper tube connections are desired, sets of two (2) 3/4" MPT x 1/2" copper male adapters are provided in the basic units.
Page 4 of 1 / Catalog 700

Two-way and three-way electric valves are available in low- and line-voltage configurations for field installation on 2-pipe and 4-pipe systems. Basic, enhanced and deluxe valve/piping packages are also available with and without quick-connect, threaded connections. Valve/piping packages are available with and without bleed lines. Packages without bleed lines will require thermostats capable of sampling the entering water temperature to sense automatic changeover on two-pipe changeover units. (Refer to valve/piping package Engineering Data documentation).

Performance Data THC Horizontal Concealed (2-Pipe System)


ARI Approved Standard Coil Water Cooling Capacity Ratings1
UNIT SIZE H02 H03 H04 H06 H08 H10 H12 FTHC HORIZONTAL CONCEALED UNIT COOLING CAPACITY1 WATER TOTAL SENSIBLE FLOW BTUH BTUH GPM 8500 11,100 14,500 21,200 22,700 25,300 34,200 6100 8400 10,800 16,100 18,000 20,000 27,000 1.94 2.51 3.26 4.70 5.14 5.70 7.75 WATER P.D. FT. W.C. 5.10 3.26 5.80 12.82 3.68 4.76 8.29

Standard Coil Water Heating Capacity Ratings2


UNIT SIZE H02 H03 H04 H06 H08 H10 H12 FTHC HORIZONTAL CONCEALED UNIT HEATING CAPACITY2 WATER FLOW SENSIBLE BTUH GPM 14,900 0,300 6,800 37,600 4,400 48,300 68,800
o o

WATER P.D. FT. W.C. 5.10 3.6 5.80 1.8 3.68 4.76 8.9
o

1.94 .51 3.6 4.70 5.14 5.70 7.75

Water heating coils at 70 F DB entering air, 140 F entering water, 30 F water temperature drop and high fan speed with standard 115/60/1 motor. For heating coil capacity ratings at conditions other than those listed refer to the RepTools Computer Selection Program or consult your McQuay representative.

General Unit Data


Unit Size H02 Type Number of Fans Number of Rows Type Type Number of Motors Power Supply 50Hz 60Hz Coil Connection Drain Pipe Connections Length Width Height Ship Weight in. in. in. lb. 23.25 32.05 9.88 63.00 6 75 91 109 1 1 1 1 1 H03 H04 H06 Fan Centrifugal Fan (forward-curved galvanized steel fan wheel) 2 2 Coil 3/1 Split Water - (3-Row Chilled Water) (1-Row Hot Water) Motor(s) PSC 1 Watts - High Speed 109 131 171 05 3/4" FPT Main Drain - 3/4" O.D. Smooth / Auxiliary Drain - 3/8" I.D. Smooth Unit with Return Air Plenum and Filter 23.25 38.74 9.88 73.00 23.25 43.86 9.88 88.00 23.25 51.73 9.88 102.00 23.25 61.57 9.88 134.00 23.25 65.51 9.88 143.00 23.25 75.75 9.88 153.00 4 91 49 99 31 385 2 2 2 115/60/1, 08-30/50/60/1, 77/60/1 3 3 4 H08 H10 H12

Conditions:

1 Cooling Capacity: Entering air temp.80oF (DB), 67oF (WB); Entering water temp.45oF, Leaving water temp. 55oF. 2 Heating Capacity: Entering air temp.70oF (DB); Entering water temp.140oF, The same amount of water flow with cooling. Air Flow: Under dry coil conditions, fan speed high. Weight: Includes return air plenum and packing.

Page 5 of 1 / Catalog 700

Performance Data THC Horizontal Concealed (4-Pipe System)


ARI Approved Standard Coil Water Cooling Capacity Ratings1
UNIT SIZE H02 H03 H04 H06 H08 H10 H12 FTHC HORIZONTAL CONCEALED UNIT COOLING CAPACITY1 WATER TOTAL SENSIBLE FLOW BTUH BTUH GPM 8500 11,100 14,500 21,200 22,700 25,300 34,200 6100 8400 10,800 16,100 18,000 20,000 27,000 1.94 2.51 3.26 4.70 5.14 5.70 7.75 WATER P.D. FT. W.C. 5.10 3.26 5.80 12.82 3.68 4.76 8.29

Standard Coil Water 1-Row Heating Capacity Ratings2


UNIT SIZE H02 H03 H04 H06 H08 H10 H12 FTHC HORIZONTAL CONCEALED UNIT 1-ROW HEATING CAPACITY2 WATER FLOW SENSIBLE BTUH GPM 11,500 16,300 0,400 9,600 36,100 40,300 49,800
o o

WATER P.D. FT. W.C. 1.47 .89 5.3 10.7 3.4 4.07 6.45
o

0.64 0.91 1.1 1.65 .00 .4 .76

Water heating coils at 70 F DB entering air, 180 F entering water, 40 F water temperature drop and high fan speed with standard 115/60/1 motor. For heating coil capacity ratings at conditions other than those listed refer to the RepTools Computer Selection Program or consult your McQuay representative.

General Unit Data


Unit Size H02 Type Number of Fans Number of Rows Type Type Number of Motors Power Supply 50Hz 60Hz Coil Connection Drain Pipe Connections Length Width Height Ship Weight in. in. in. lb. 23.25 32.05 9.88 63.00 6 75 91 109 1 1 1 1 1 H03 H04 H06 Fan Centrifugal Fan (forward-curved galvanized steel fan wheel) 2 2 Coil 3/1 Split Water - (3-Row Chilled Water) (1-Row Hot Water) Motor(s) PSC 1 Watts - High Speed 109 131 171 05 3/4" FPT Main Drain - 3/4" O.D. Smooth / Auxiliary Drain - 3/8" I.D. Smooth Unit with Return Air Plenum and Filter 23.25 38.74 9.88 73.00 23.25 43.86 9.88 88.00 23.25 51.73 9.88 102.00 23.25 61.57 9.88 134.00 23.25 65.51 9.88 143.00 23.25 75.75 9.88 153.00 4 91 49 99 31 385 2 2 2 115/60/1, 08-30/50/60/1, 77/60/1 3 3 4 H08 H10 H12

Conditions:

1 Cooling Capacity: Entering air temp.80oF (DB), 67oF (WB); Entering water temp.45oF, Leaving water temp. 55oF. 2 Heating Capacity: Entering air temp.70oF (DB); Entering water temp.180oF. Air Flow: Under dry coil conditions, fan speed high. Weight: Includes return air plenum and packing.

Page 6 of 1 / Catalog 700

Dimensional Data THC Horizontal Concealed, with Plenum Box


Unit Size H02 H03 H04 H06 H08 H10 H12 A 3.05" 38.74" 43.86" 51.73" 61.57" 65.51" 75.75" B 17.64" 4.33" 9.45" 37.3" 47.17" 51.10" 61.34" C 19.17" 5.87" 30.98" 38.86" 48.70" 5.64" 6.87" D 19.96" 6.65" 31.77" 39.65" 49.49" 53.43" 63.66" E 18.46" 5.15" 30.0" 38.07" 47.91" 51.85" 6.09" F 1.13" 7.8" 3.94" 40.8" 50.66" 54.60" 64.83" Filters Size 181/8" x 8" x 1" 47/8" x 8" x 1" 97/8" x 8" x 1" 187/8" x 8" x 1" 33/4" x 8" x 1" 53/4" x 8" x 1" 307/8" x 8" x 1"
6.54" 4.66"

Qty 1 1 1    2

Note: For wiring diagram details for Vintage B THC units and the LV-3SP Jbox refer to Certified Drawing FC-THC-H02-H012

Detail

(Optional) LV-3SP Jbox Interface Control Junction Box

.877"

(Optional) LV-3SP Jbox 7.73"H x 6.54"W x 3.38"D (always located on the end opposite the coil connection)

7.73"
D E

Filter
2- R/A Plenum Mounting Holes 3/8" x 5/8" 4 - Mounting Holes 3/8" x 5/8" Auxiliary Overflow Drain 3/8" I.D. Main Condensate Drain 3/4" O.D.

3.13"

8.75" 2.32" 6.54" 7.36"

3.75" 1  3 4 5 6 7 8 Metal Sheet Terminal Block - Line Voltage Terminal Block - Line Voltage Relays, 4v coil - Line Voltage Contact Terminal Block - Low Voltage Terminal Block, 4v - Line Voltage Transformer, 4v - Line Voltage Divider

1.5" B C A 6.38" 9.75"

Air Vent

2"

TOP VIEW
1.02" 7.73" 5.75" 9.75"

Plenum Back with Filter


Unit with plenums, filter removable from either side or bottom of unit

.88"

FRONT VIEW
Terminal box located at the same side as coil connection 23.25" 1.25" 1.25" 2.75" 9.25" 4.53" 1.73" 12.75"
Terminal Block (Basic Unit Only)

1.40"

Main Condensate Drain 3/4" O.D.

Filter Rail

Chilled Water Connections 3/4" FPT

Water Return Connection 3/4" FPT

23.25" 1.25" 1.25" 5.82" 9.25" 8.94" (Unit w/o Plenum)


Terminal Block

Basic terminal box located at the same side as the coil connection

9.88" 3.46" 1/2" Auxiliary Overflow Drain 3/8" I.D. 8.82" (Unit w/o Plenum)

9.88"

4.72"

8.125"

2"
Hot Water Connection 3/4" FPT

9.53"
Water Supply Connection 3/4" FPT

9.53"
Main Drain Connection 3/4" O.D.

18.35" (Unit w/o Plenum)

4-Pipe System - Right Hand Unit*


*Factory supplied left hand units also available

2-Pipe System - Right Hand Unit*


Page 7 of 1 / Catalog 700

Air Volume Capacity Data


Air volume versus external static pressure
Unit Size Air Flow cfm RPM Air Flow cfm RPM Air Flow cfm RPM Air Flow cfm RPM Air Flow cfm RPM Air Flow cfm RPM Air Flow cfm RPM Fan Motor Speed High Medium External Static Pressure (inches of water) External Static Pressure (inches of water) .00 .05 .10 .15 .20 .25 .30 .00 .05 .10 .15 .20 .25 .30 311 93 76 58 40 3 03 31 11 195 178 164 15 134 1070 1130 1170 100 130 16 191 869 899 966 101 1051 1104 114 43 391 368 344 319 97 70 96 77 6 44 9 13 197 1143 117 10 16 155 18 1313 838 890 945 99 1043 1097 1144 507 47 444 416 386 359 36 349 37 310 88 68 47 7 11 1165 101 11 158 185 1314 788 851 903 964 1043 1093 1156 798 770 74 714 688 654 67 581 555 530 508 483 456 43 195 1311 1333 1361 138 1399 1416 990 1017 1060 110 1151 118 130 949 915 874 88 775 730 690 740 701 65 615 57 58 490 117 119 11 159 186 130 1341 931 1003 107 107 114 1167 119 103 981 93 881 836 71 716 775 73 688 631 58 533 493 151 179 1303 1331 1344 1386 141 984 1037 1068 1115 1169 145 155 148 1380 1334 187 19 1173 1114 1067 10 976 97 875 833 781 1344 1367 1389 1408 845 886 146 1039 106 1106 1149 119 135 177 Low External Static Pressure (inches of water) .00 .05 .10 .15 .20 .25 .30 181 157 139 15 111 94 87 704 773 86 887 965 103 1091 34 0 179 161 144 1 113 714 756 833 886 953 103 1081 78 41 14 19 171 145 134 678 737 811 891 957 108 1091 518 497 471 444 45 406 376 894 937 994 1049 1086 1141 1181 66 60 580 535 490 44 400 89 935 956 1014 1070 111 1174 697 643 60 538 496 463 410 90 969 1001 106 113 1161 104 960 91 877 86 788 806 705 958 1003 1043 1095 1141 1178 14

H02 H03 H04 H06 H08 H10 H12

Note: Based on 115V operation, and dry coils.

Motor Data
Fan Motor Speed High Medium Low Unit Size H02 H03 H04 H06 H08 H10 H12 Amps Watts RPM Amps Watts RPM Amps Watts RPM Amps Watts RPM Amps Watts RPM Amps Watts RPM Amps Watts RPM 0.7 0.6 0.5 75 61 53 1043 869 704 1.0 0.7 0.6 109 73 63 1143 838 714 1. 0.9 0.8 131 93 83 11 788 678 1.8 1.4 1.3 115/60/1 05 195 155 990 145 894 .6 .0 1.9 91 9 11 117 931 89 .7 .0 1.9 99 5 11 151 984 90 3.5 .7 .5 385 305 79 1344 1039 958.

Note: Based on 115V operation, dry coil, and 0.0 ESP

Page 8 of 1 / Catalog 700

Wiring Diagrams
FAN SPEED SWITCH L M H LF MF HF SHF BLACK POWER WHITE SOURCE G/Y MAIN SWITCH NOTE: FIELD WIRING M: FAN MOTOR G/Y: GREEN/YELLOW LF: FAN SPEED LOW L N G

For Models: THCH02, THCH03, THCH04, and THCH06 (Basic Unit Only) Wiring (115V/1P/60Hz)(208-230V/1P/60Hz)(265/277V/1P/60Hz) WIRING (115V/1P/60Hz)(208-230V/1P/60Hz) Wiring (220V/1P/50Hz) WIRING (220V/1P/50Hz)
FAN SPEED SWITCH ORANGE BROWN YELLOW RED G/Y M BLACK BLACK L M H LF MF HF SHF BLACK POWER WHITE SOURCE MAIN SWITCH G/Y NOTE: FIELD WIRING MF: FAN SPEED MEDIUM HF: FAN SPEED HIGH SHF: FAN SPEED SUPER HIGH M: FAN MOTOR G/Y: GREEN/YELLOW LF: FAN SPEED LOW MF: FAN SPEED MEDIUM HF: FAN SPEED HIGH SHF: FAN SPEED SUPER HIGH G/Y L N BLUE ORANGE BROWN YELLOW RED G/Y M BLACK BLACK

BLUE

For Models: THCH08, THCH10, THCH12 (Basic Unit Only) WIRING (115V/1P/60Hz)(208-230/1P/60Hz)
FAN SPEED SWITCH L M H LF MF HF SHF L N G BLUE ORANGE BROWN YELLOW RED ORANGE BROWN G/Y YELLOW RED G/Y M2 BLACK G/Y M1 BLACK BLACK

WIRING (220V/1P/50Hz)
FAN SPEED SWITCH L M H LF MF HF SHF BLACK WHITE MAIN SWITCH G/Y NOTE: FIELD WIRING L N BLUE ORANGE BROWN YELLOW RED ORANGE BROWN YELLOW RED G/Y M2 BLACK G/Y M1 BLACK BLACK

POWER SOURCE

BLACK WHITE G/Y MAIN SWITCH

BLACK POWER SOURCE

BLACK

NOTE: FIELD WIRING M1,M2: FAN MOTOR G/Y: GREEN/YELLOW LF: FAN SPEED LOW

MF: FAN SPEED MEDIUM HF: FAN SPEED HIGH SHF: FAN SPEED SUPER HIGH

M1,M2: FAN MOTOR G/Y: GREEN/YELLOW LF: FAN SPEED LOW

MF: FAN SPEED MEDIUM HF: FAN SPEED HIGH SHF: FAN SPEED SUPER HIGH

Page 9 of 1 / Catalog 700

McQuay THC Horizontal Concealed Fan Coil


Engineering Guide Specifications
Furnish and install where shown on the plans and specifications, McQuay THC Horizontal Concealed Fan-Coil Units. Types, sizes and performance are as tabulated in the schedule. Unit performance is substantiated by computer generated output data. Each unit is ARI certified and consists of and complies with the following:

Construction

General Basic unit consist of a chassis, hydronic coil(s), drain pan, junction box, motor, centrifugal fan assembly. Top and side panels surrounding the coil are insulated with aluminum foil face to prevent condensation. The casing, fabricated of heavy gauge galvanized steel with four-sided one inch duct collar for an easy connections to discharge duct work. Units are available with or without return air plenum. Units with return air plenum have a filter frame with 3/4" return air duct collar. Plenum is fully insulated with foil faced, thermal and acoustical insulation to prevent glass fibers in the air stream, unit sweating, and to attenuate fan noise. Mounting holes are to be provided on all four corners to allow the units to be suspended from the ceiling with threaded rods. Selectable either as 2 or 4-pipe systems with coil pipe connections located on the same side. Units are tested in accordance with ARI 440. The units comply with NFPA 90A and are ETL listed in the U.S. and Canada. Top panel and drain pan is easily removed to allow coil access. Coils All THC water coils feature aluminum blue fins mechanically bonded to seamless copper tubes. The blue fins are covered with an epoxy polymer that causes condensation to drip off more quickly, preventing mold build-up and increasing the coil and fin life expectancy. All water coils are 12 fins per inch. Factory burst tested at 425 psig (2930kPa) and leak tested at 225 psig (1552 kPa). Maximum main coil working pressure is 300 psig (2,069 kPa). Maximum entering water temperature is 200F (93C). Cooling coil (2-Pipe) or combination cooling and heating coils (4-Pipe) are available. Heating coils are factory installed in the reheat position with same hand coil connection. Heating coils are capable to be field converted to preheat position. Coils are provided with a brass header, 3/4" FPT coil connections, and a hand operated brass manual air vent, conveniently located over the drain pan, and supplied with a clear plastic hose to prevent spills. The 3/4" FPT connections facilitate the field installation of McQuay threaded, quick-connect factory built valve package. Coil brass headers are protected with a galvanized steel cover plate and held in position with holding screws thus providing additional structural support to thread piping-valve package and matched load pumps. On Basic units optional sets of two (2) 3/4" MPT x 1/2" copper male adapters are provided if sweat copper tube connections are desirable. Note: Units provided with factory installed LV-3SP interface board (with or without plenum) are provided with sets of two (2) 3/4" MPT x 1/2" piping elbow adapter to be used with McQuay threaded, quick-connect valve packages. Fan Assembly Aluminum fan wheels are dynamically balanced, forward curved, double-width, inside double-inlet scroll centrifugal type housings constructed of galvanized steel for corrosion resistance. The rest of the assembly is made with a heavier gauge galvanized steel which provides additional strength and rigidity resulting in smoother, quieter operation. Sound Units shall have published sound power level data tested in accordance with ARI 350. (For more information contact your local Mcquay Sales Representative). Motors 4 speed, permanently lubricated sleeve bearing, permanent split capacitor motors, (115/60/1) (208-230/60/1) (265/60/1) with UL listed automatic reset integral thermal overload protection. Maximum ambient operating temperature of 104F. Run tested in assembled units. Motors are resiliently mounted to assure quiet, vibration free operation.

Page 10 of 1 / Catalog 700

Drain Pan Stamped with no welded corners. The galvanized steel drain pans are cleaned, phosphatized before they are coated with a thick layer of powder paint. Insulated with form-fitted closed cell insulation the drain pan is positively sloped and easily removable for cleaning. Extended out 6" beyond the coil connections for valve/piping packages. Vintage B drain pans include a auxiliary drain connection. Optional stainless steel drain pan is also available with the same features as above, excluding the backed powder paint. Insulation Hideaway return air plenum is fully insulated with foil faced, thermal and acoustical insulation to prevent glass fibers entering the air stream, unit sweating, and to attenuate fan noise. Filters Standard filter is 1" nominal throwaway type. Design vintage B filters are removable from the sides or bottom. Electrical THC fan-coils are made available with the following factory installed options: - Basic: Unit is furnished with single point power connection junction box that includes a terminal strip for line voltage control connection. - DDC ready interface: LV-3SP control box includes (3) - 24 volt relays, line voltage/24volt transformer, 4 sets of terminal strips and toggle disconnect (See Notes below). Piping Packages - All THC units are available with factory-built piping package options for field installation. Basic, enhanced and deluxe piping package options are available with a variety of control valve options: 2 or 3-way 1/2" control valve 2-position or modulating. Basic piping package consists of a quick-connect union, shutoff ball valve with memory stop and control valve on the supply and quick-connect union, shutoff ball valve with memory stop on the return. Enhanced piping package consists of a quick-connect union, shutoff ball valve, control valve on the supply; quickconnect union, shutoff ball valve and manual circuit setter balancing valve on the return. Deluxe piping package has one quick-connect union, shutoff ball valve, control valve and a strainer on the supply; quick-connect union, shutoff ball valve, manual circuit setter balancing valve on the return. Valve packages for sweat connection are also available. Notes: Units with the LV-3SP junction box are provided with a set of two (2) 3/4" MPT x 1/2" piping elbow adapters to be used with McQuay quick-connect, threaded valve packages.

Page 11 of 1 / Catalog 700

This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.

2007 McQuay International www.mcquay.com 1.800.432.1342

Catalog 700-3 / Page 12 of 12 (11-07)