2.) PERMACORD CABLE 600V 60°C (LATEST)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Permacord Cable, 600V 60°C

PVC insulation Copper


conductor
(fine strands)
Features
Highly flexible conductor construction
PVC insulated and jacketed
Flame retardant
Oil and gasoline resistant
Conductor identification by standard color-
PVC jacket code system

Specifications Applications
PNS 163 Multi-stranded copper conductor for use in
UL 62 portable and movable electrical devices
ASTM B-173, ASTM B-174 such as tools, motors, polishers, sanders,
service power cord extensions, etc.
Voltage Rating Voltage as specified.
600 Volts (Heavy duty)

Conductor Wall thickness


Approximate AC
construction (nominal) Cable
Size resistance Reactance
Cable Cable ampacity
No. of Diameter Insulation Jacket @ 60°C
diameter weight
strand
AWG mm mm mm mm kg / km A* Ω / km Ω / km
Two Conductor (2/C)
18 16 0.254 0.76 1.52 8.4 91 10 25.1 0.357
16 26 0.254 0.76 1.52 9.1 111 13 15.4 0.331
14 41 0.254 1.14 2.03 12.4 202 18 9.80 0.349
12 65 0.254 1.14 2.41 14.1 271 25 6.18 0.325
10 104 0.254 1.14 2.41 15.3 343 30 3.86 0.304
8 7 x 24 0.254 1.52 2.79 20.2 581 40 2.44 0.334
6 7 x 28 0.254 1.52 3.18 23.2 800 55 1.54 0.306
4 7 x 60 0.254 1.52 3.56 26.8 1,113 70 0.975 0.288
2 19 x 35 0.254 1.52 3.94 31.2 1,573 95 0.622 0.276
Three Conductor (3/C)
18 16 0.254 0.76 1.52 8.8 105 7 25.1 0.357
16 26 0.254 0.76 1.52 9.5 131 10 15.4 0.331
14 41 0.254 1.14 2.03 13.0 235 15 9.80 0.349
12 65 0.254 1.14 2.41 14.8 319 20 6.18 0.325
10 104 0.254 1.14 2.41 16.2 412 25 3.86 0.304
8 7 x 24 0.254 1.52 2.79 21.4 696 35 2.44 0.334
6 7 x 28 0.254 1.52 3.18 24.6 968 45 1.54 0.306
4 7 x 60 0.254 1.52 3.56 28.3 1,362 60 0.975 0.288
2 19 x 35 0.254 1.52 3.94 33.1 1,943 80 0.622 0.276
Four Conductor (4/C)
18 16 0.254 0.76 1.52 9.5 124 6 25.1 0.380
16 26 0.254 0.76 1.52 10.3 156 8 15.4 0.354
14 41 0.254 1.14 2.03 14.1 280 12 9.80 0.373
12 65 0.254 1.14 2.41 16.0 381 16 6.18 0.349
10 104 0.254 1.14 2.41 17.5 498 20 3.86 0.327
8 7 x 24 0.254 1.52 3.18 24.1 882 28 2.44 0.357
6 7 x 28 0.254 1.52 3.56 27.5 1,222 36 1.54 0.329
4 7 x 60 0.254 1.52 3.94 31.6 1,718 48 0.975 0.311
2 19 x 35 0.254 1.52 4.32 36.8 2,451 64 0.622 0.300
*Ampacity is based from NEC 2011 Table 400.5(A)(1) Allowable Ampacity for Flexible Cords and Cables [Based on Ambient
Temperature of 30°C (86°F). See 400.13 and Table 400.4.]

Executive office: Manufacturing Plant: Customer Approval


2297 2/F BCS Prime Bldg. Pasong Luisita Industrial Park Name
Tamo Ext. Makati City, Philippines San Miguel, Tarlac City Philippines
Tel (02) 8813-2529 Tel (045) 985-1089 to 91 Date
Fax (02) 8812-0798 Fax (045) 985-0076 Sign