Nyy PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

NYY

NYY 11xx(1.5-800)
(1.5-800) mm
mm 0.6/1
0.6/1 kV kV
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1

Construction Data
Application :
Nom. Overall Cable
Power cable : Indoors, cable trunking, outdoors
Cross Diameter Weight and burried in the ground, for power stations, Copper Conductor
Section industry and switchgear as well as for urban
Area approx. approx. supply networks, if mechanical damage is PVC Insulation
mm mm kg/km unlikely.

1.5 6.1 53 Special Features on Request :


Fire Resistance PVC Sheath
2.5 6.6 67
4 7.6 94 Oil Resistance
UV Resistance
6 8.1 117 Flame Retardant Cat. A, B, C
10 9.1 166 Flame Retardant Non Category
16 10.1 229 Heat Resistance
Anti Termite
25 11.9 345
Anti Rodent
35 13.0 444 Low Smoke Zero Halogen
50 15.0 600 Nylon Coated
70 16.9 815
95 19.1 1,079
120 21.0 1,325 Note :
150 23.0 1,604 Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
185 25.5 2,020
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
240 29.0 2,636 25 - 800 sqmm supplied in non compacted circular stranded (rm) or compacted
300 32.0 3,219 circular stranded (cm) conductor shape
400 35.5 4,087
Standard Packing
500 39.5 5,213 1.5 - 10 sqmm supplied in coil @ 100 m
630 44.0 6,712 16 - 300 sqmm supplied in wooden drum @ 1000 m
800 48.5 8,368 400 - 800 sqmm supplied in wooden drum on available length
Length Tolerance per drum 2%

Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short
circuit current
Nom. DC AC Trefoil Flat
at
Cross Resistance Resistance formation formation in air in ground in air in ground 1 sec
Sect. at 20C at 70C

Max. Max. Max. Max. Max. Max. Max.


(mm) (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA)
1.5 12.1 14.478 0.459 0.505 21 27 21 27 0.17
2.5 7.41 8.866 0.423 0.470 27 35 28 35 0.29
4 4.61 5.516 0.404 0.450 37 46 38 45 0.46
6 3.08 3.685 0.380 0.426 46 57 48 57 0.69
10 1.83 2.190 0.350 0.396 64 76 65 76 1.15
16 1.15 1.376 0.327 0.374 84 98 87 97 1.84
25 0.727 0.870 0.312 0.358 114 127 117 125 2.88
35 0.524 0.627 0.299 0.345 140 152 144 150 4.03
50 0.387 0.464 0.290 0.336 172 180 177 178 5.75
70 0.268 0.321 0.280 0.326 218 220 225 218 8.05
95 0.193 0.232 0.274 0.321 270 264 278 260 10.93
120 0.153 0.184 0.269 0.315 315 300 325 296 13.80
150 0.124 0.150 0.266 0.313 362 336 373 331 17.25
185 0.0991 0.121 0.264 0.310 420 379 433 374 21.28
240 0.0754 0.093 0.261 0.307 503 439 518 432 27.60
300 0.0601 0.075 0.258 0.305 580 494 598 486 34.50
400 0.0470 0.061 0.256 0.302 674 558 695 549 41.20
500 0.0366 0.049 0.252 0.299 781 629 806 618 51.50
630 0.0283 0.041 0.247 0.293 901 704 930 692 64.89
14233-01 Rev. 2.0 / 2009

800 0.0221 0.035 0.242 0.289 1018 775 1052 762 82.40

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYY 2 x (1.5-300) mm 2
0.6/1
NYY 2 x (1.5-300) mm 0.6/1
2
kV kV
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1

Construction Data
Application :
Nom. Overall Cable Copper Conductor
Power cable : Indoors, cable trunking, outdoors
Cross Diameter Weight and burried in the ground, for power stations,
Section industry and switchgear as well as for urban
PVC Insulation
Area approx. approx. supply networks, if mechanical damage is
mm mm kg/km unlikely. PVC Inner Sheath

1.5 12.5 200 Special Features on Request :


Fire Resistance
2.5 13.4 242 PVC Sheath
Oil Resistance
4 15.4 330 UV Resistance
Flame Retardant Cat. A, B, C
6 16.5 399
Flame Retardant Non Category
10 18.4 538 Heat Resistance
Anti Termite
16 20.5 713
Anti Rodent
25 24.0 1,001 Low Smoke Zero Halogen
Nylon Coated
35 26.0 1,274
50 29.5 1,536
70 33.0 2,066
Note :
95 37.5 2,787 Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
120 41.0 3,371
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
150 45.0 4,114 25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape
185 50.0 5,128
Standard Packing
240 56.0 6,581 1.5 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
300 62.0 8,130
Length Tolerance per drum 2%

Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC
at 30C * at
Cross Resistance Resistance 1 sec
Sect. at 20C at 70C in air in ground

Max. Max. Max. Max. Max.


(mm) (/km) (/km) (mH/km) (A) (A) (kA)

1.5 12.1 14.478 0.328 23 27 0.17


2.5 7.41 8.866 0.304 30 36 0.29
4 4.61 5.516 0.303 40 47 0.46
6 3.08 3.685 0.288 51 59 0.69
10 1.83 2.190 0.269 70 80 1.15
16 1.15 1.376 0.255 93 104 1.84
25 0.727 0.870 0.255 123 134 2.88
35 0.524 0.627 0.246 151 162 4.03
50 0.387 0.464 0.247 182 191 5.75
70 0.268 0.321 0.238 230 236 8.05
95 0.193 0.232 0.238 280 281 10.93
120 0.153 0.184 0.233 325 321 13.80
150 0.124 0.150 0.233 371 361 17.25
185 0.0991 0.121 0.233 424 406 21.28
240 0.0754 0.093 0.232 501 470 27.60
14233-02 Rev. 2.0 / 2009

300 0.0601 0.075 0.231 572 528 34.50

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYY
NYY 33xx(1.5-400)
(1.5-400) mm
mm 0.6/1
0.6/1 kV kV
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1

Construction Data
Application :
Nom. Overall Cable
Power cable : Indoors, cable trunking, outdoors Copper Conductor
Cross Diameter Weight and burried in the ground, for power stations,
Section industry and switchgear as well as for urban
Area approx. approx. PVC Insulation
supply networks, if mechanical damage is
mm mm kg/km unlikely.
PVC Inner Sheath
1.5 13.0 224 Special Features on Request :
Fire Resistance
2.5 14.0 277 PVC Sheath
Oil Resistance
4 16.1 383 UV Resistance
Flame Retardant Cat. A, B, C
6 17.3 471
Flame Retardant Non Category
10 19.4 649 Heat Resistance
Anti Termite
16 22.0 875
Anti Rodent
25 25.0 1,248 Low Smoke Zero Halogen
Nylon Coated
35 27.5 1,606
50 30.0 1,857
70 34.0 2,556
Note :
95 38.5 3,428 Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
120 41.5 4,152
conductor shape
150 46.0 5,115 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
185 50.5 6,330
50 - 400 sqmm supplied in sector shaped stranded (sm) conductor
240 57.0 8,215
Standard Packing
300 62.5 10,116
1.5 - 95 sqmm supplied in wooden drum @ 1000 m
400 69.0 12,765 120 - 400 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum 2%

Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC at
at 30C *
Cross Resistance Resistance 1 sec
Sect. at 20C at 70C in air in ground

Max. Max. Max. Max. Max.


(mm) (/km) (/km) (mH/km) (A) (A) (kA)
1.5 12.1 14.478 0.328 19 23 0.17
2.5 7.41 8.866 0.304 26 31 0.29
4 4.61 5.516 0.303 34 40 0.46
6 3.08 3.685 0.288 44 50 0.69
10 1.83 2.190 0.269 60 68 1.15
16 1.15 1.376 0.255 79 88 1.84
25 0.727 0.870 0.255 105 114 2.88
35 0.524 0.627 0.246 129 137 4.03
50 0.387 0.464 0.247 162 168 5.75
70 0.268 0.321 0.238 203 206 8.05
95 0.193 0.232 0.238 250 247 10.93
120 0.153 0.184 0.233 289 281 13.80
150 0.124 0.150 0.233 330 315 17.25
185 0.0991 0.121 0.233 381 356 21.28
240 0.0754 0.093 0.232 451 412 27.60
300 0.0601 0.075 0.231 517 464 34.50
14233-03 Rev. 2.0 / 2009

400 0.0470 0.060 0.229 594 524 41.20

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYY
NYY 44xx(1.5-400)
(1.5-400) mm
mm 0.6/1
0.6/1 kV kV
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1

Construction Data
Application :
Nom. Overall Cable
Power cable : Indoors, cable trunking, outdoors Copper Conductor
Cross Diameter Weight and burried in the ground, for power stations,
Section industry and switchgear as well as for urban
Area approx. approx. supply networks, if mechanical damage is
PVC Insulation

mm mm kg/km unlikely.
PVC Inner Sheath
1.5 13.8 259 Special Features on Request :
Fire Resistance
2.5 15.0 324 PVC Sheath
Oil Resistance
4 17.3 453 UV Resistance
Flame Retardant Cat. A, B, C
6 18.7 563
Flame Retardant Non Category
10 21.5 794 Heat Resistance
Anti Termite
16 23.5 1,083
Anti Rodent
25 27.5 1,558 Low Smoke Zero Halogen
Nylon Coated
35 30.0 2,018
50 35.5 2,466
70 39.0 3,334
Note :
95 44.5 4,491 Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
120 48.5 5,504
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
150 54.5 6,787 25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 400 sqmm supplied in sector shaped stranded (sm) conductor
185 59.0 8,392
240 66.0 10,818 Standard Packing
1.5 - 70 sqmm supplied in wooden drum @ 1000 m
300 72.5 13,326
95 - 400 sqmm will be suplied in wooden drum on available length
400 82.5 16,969 Length Tolerance per drum 2%

Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC at
at 30C *
Cross Resistance Resistance 1 sec
Sect. at 20C at 70C in air in ground

Max. Max. Max. Max. Max.


(mm) (/km) (/km) (mH/km) (A) (A) (kA)
1.5 12.1 14.478 0.328 22 27 0.17
2.5 7.41 8.866 0.304 29 35 0.29
4 4.61 5.516 0.303 39 46 0.46
6 3.08 3.685 0.288 50 57 0.69
10 1.83 2.190 0.269 68 77 1.15
16 1.15 1.376 0.255 90 99 1.84
25 0.727 0.870 0.255 121 128 2.88
35 0.524 0.627 0.246 149 154 4.03
50 0.387 0.464 0.247 173 173 5.75
70 0.268 0.321 0.238 215 212 8.05
95 0.193 0.232 0.238 266 255 10.93
120 0.153 0.184 0.233 308 289 13.80
150 0.124 0.150 0.233 357 327 17.25
185 0.0991 0.121 0.233 405 366 21.28
240 0.0754 0.093 0.232 482 425 27.60
300 0.0601 0.075 0.231 552 479 34.50
14233-04 Rev. 2.0 / 2009

400 0.0470 0.060 0.229 643 545 41.20

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYY
NYY 55xx(1.5-50)
(1.5-50) mm
mm 0.6/1
0.6/1 kV kV
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1

Construction Data
Application :
Nom. Overall Cable PVC Filler
Power cable : Indoors, cable trunking, outdoors
Cross Diameter Weight and burried in the ground, for power stations, Copper Conductor
Section industry and switchgear as well as for urban
Area approx. approx. supply networks, if mechanical damage is PVC Insulation
mm mm kg/km unlikely.
PVC Inner Sheath
1.5 14.8 302 Special Features on Request :
Fire Resistance
2.5 16.0 382 Oil Resistance PVC Sheath

4 18.7 541 UV Resistance


Flame Retardant Cat. A, B, C
6 20.5 677 Flame Retardant Non Category
Heat Resistance
10 23.0 954 Anti Termite
16 26.0 1,309 Anti Rodent
Low Smoke Zero Halogen
25 30.0 1,895 Nylon Coated

35 33.0 2,478
50 38.0 3,161
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum 2%

Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC at
at 30C *
Cross Resistance Resistance 1 sec
Sect. at 20C at 70C in air in ground

Max. Max. Max. Max. Max.


(mm) (/km) (/km) (mH/km) (A) (A) (kA)
1.5 12.1 14.478 0.328 23 27 0.17
2.5 7.41 8.866 0.304 30 36 0.29
4 4.61 5.516 0.303 41 47 0.46
6 3.08 3.685 0.288 52 59 0.69
10 1.83 2.190 0.269 71 78 1.15
16 1.15 1.376 0.255 94 101 1.84
25 0.727 0.870 0.255 126 131 2.88
35 0.524 0.627 0.246 155 157 4.03
50 0.387 0.464 0.247 189 185 5.75
14233-05 Rev. 2.0 / 2009