NYRY

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

NYR(AL)Y

NYR(AL)Y 11xx(10-800)
(10-800) mm²
mm² 0.6/1
0.6/1 kV kV
Cu / PVC / AWA / PVC
(Copper Conductor, PVC Insulated, Aluminium Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Construction Data
Application :
Nom. Overall Cable Copper Conductor
For installation in the ground, indoors, cable
Cross Diameter Weight trunking and outdoors if increased mechanical PVC Insulation
Section protection is required or where high-pulling
Area approx. approx. stresses may occur during installation or PVC Inner Sheath
mm² mm kg/km operation.
Aluminium Wire Armor
10 14.4 326 Special Features on Request : Non-hygroscopic Tape
• Fire Resistance
16 15.4 402
• Oil Resistance PVC Sheath
25 17.2 541 • UV Resistance
• Flame Retardant Cat. A, B, C
35 18.3 658
• Flame Retardant Non Category
50 20.5 841 • Heat Resistance
• Anti Termite
70 22.5 1,070
• Anti Rodent
95 24.5 1,365 • Low Smoke Zero Halogen
120 26.5 1,662
150 28.5 1,967
Note :
185 31.0 2,406
Conductor Shape
240 34.0 3,071 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor
shape
300 38.0 3,781
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
400 42.0 4,764 25 - 800 sqmm supplied in non compacted circular stranded (rm) or compacted
circular stranded (cm) conductor shape
500 46.5 5,968
630 51.0 7,538 Standard Packing
10 - 300 sqmm supplied in wooden drum @ 1000 m
800 57.0 9,508
400 - 800 sqmm supplied wooden drum on available length
Length Tolerance per drum ± 2%

Electrical Data
Conductor Inductance Current - Carrying Capacity at 30° C * Short
circuit current
Nom. DC AC Trefoil Flat
at
Cross Resistance Resistance formation formation in air in ground in air in ground 1 sec
Sect. at 20°C at 70°C

Max. Max. Max. Max. Max. Max. Max.


(mm²) (Ω/km) (Ω/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA)
10 1.83 2.190 0.442 0.489 73 77 75 79 1.15
16 1.15 1.376 0.412 0.458 96 99 98 102 1.84
25 0.727 0.870 0.386 0.432 127 128 130 131 2.88
35 0.524 0.627 0.367 0.414 154 153 158 157 4.03
50 0.387 0.463 0.351 0.397 187 181 192 186 5.75
70 0.268 0.321 0.333 0.379 234 222 240 227 8.05
95 0.193 0.232 0.322 0.368 286 264 292 269 10.93
120 0.153 0.184 0.315 0.361 331 299 338 304 13.80
150 0.124 0.150 0.309 0.355 376 334 383 338 17.25
185 0.0991 0.120 0.302 0.348 431 375 438 378 21.28
240 0.0754 0.092 0.294 0.340 507 429 511 430 27.60
300 0.0601 0.075 0.293 0.340 573 472 573 468 34.50
400 0.0470 0.060 0.290 0.337 650 522 644 513 41.20
500 0.0366 0.048 0.284 0.330 732 573 719 557 51.50
630 0.0283 0.040 0.275 0.321 820 625 799 602 64.89
800 0.0221 0.033 0.275 0.321 883 651 851 620 82.40
12633-01 Rev. 2.0 / 2009

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYRY
NYRY 22xx(1.5-300)
(1.5-300) mm²
mm² 0.6/1
0.6/1 kV kV
Cu / PVC / SWA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Construction Data
Application :
Nom. Overall Cable Copper Conductor
For installation in the ground, indoors, cable
Cross Diameter Weight trunking and outdoors if increased mechanical PVC Insulation
Section protection is required or where high-pulling
Area approx. approx. stresses may occur during installation or PVC Inner Sheath
mm² mm kg/km operation.
Galvanized Steel Wire Armor
1.5 14.0 347 Special Features on Request :
Non-hygroscopic Tape
• Fire Resistance
2.5 15.0 403
• Oil Resistance PVC Sheath
4 16.9 516 • UV Resistance
• Flame Retardant Cat. A, B, C
6 18.8 701
• Flame Retardant Non Category
10 21.0 874 • Heat Resistance
• Anti Termite
16 23.0 1,082
• Anti Rodent
25 27.0 1,565 • Low Smoke Zero Halogen
35 29.0 1,893
50 32.5 2,293
Note :
70 37.0 3,150
Conductor Shape
95 42.0 4,037 1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
conductor shape
120 45.0 4,725
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
150 50.5 6,041 25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape
185 55.5 7,253
Standard Packing
240 61.5 8,949 1.5 - 70 sqmm supplied in wooden drum @ 1000 m
95 - 300 sqmm will be suplied in wooden drum on available length
300 67.5 10,731
Length Tolerance per drum ± 2%

Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground

Max. Max. Max. Max. Max.


(mm²) (Ω/km) (Ω/km) (mH/km) (A) (A) (kA)
1.5 12.1 14.478 0.328 24 28 0.17
2.5 7.41 8.866 0.304 32 37 0.29
4 4.61 5.516 0.303 42 48 0.46
6 3.08 3.685 0.288 54 61 0.69
10 1.83 2.190 0.269 73 82 1.15
16 1.15 1.376 0.255 97 106 1.84
25 0.727 0.870 0.255 128 137 2.88
35 0.524 0.627 0.246 157 165 4.03
50 0.387 0.464 0.247 188 194 5.75
70 0.268 0.321 0.238 238 240 8.05
95 0.193 0.232 0.238 288 284 10.93
120 0.153 0.184 0.233 333 323 13.80
150 0.124 0.150 0.233 381 363 17.25
185 0.0991 0.121 0.233 433 406 21.28
240 0.0754 0.093 0.232 506 466 27.60
300 0.0601 0.075 0.231 573 520 34.50
12633-02 Rev. 2.0 / 2009

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYRY
NYRY 33xx(1.5-300)
(1.5-300) mm²
mm² 0.6/1
0.6/1 kV kV
Cu / PVC / SWA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Construction Data
Application :
Nom. Overall Cable Copper Conductor
For installation in the ground, indoors, cable
Cross Diameter Weight trunking and outdoors if increased mechanical PVC Insulation
Section protection is required or where high-pulling
Area approx. approx. stresses may occur during installation or PVC Inner Sheath
mm² mm kg/km operation.
Galvanized Steel Wire Armor
1.5 14.5 382 Special Features on Request : Non-hygroscopic Tape
• Fire Resistance
2.5 15.5 448
• Oil Resistance PVC Sheath
4 18.4 678 • UV Resistance
• Flame Retardant Cat. A, B, C
6 19.6 783
• Flame Retardant Non Category
10 22.0 1,006 • Heat Resistance
• Anti Termite
16 24.0 1,276
• Anti Rodent
25 28.0 1,863 • Low Smoke Zero Halogen
35 30.5 2,279
50 33.5 2,644
Note :
70 38.5 3,664
Conductor Shape
95 42.5 4,661 1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
conductor shape
120 45.5 5,487
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
150 51.5 7,040 25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor
185 56.5 8,457
240 62.5 10,579 Standard Packing
1.5 - 70 sqmm supplied in wooden drum @ 1000 m
300 68.0 12,683
95 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground

Max. Max. Max. Max. Max.


(mm²) (Ω/km) (Ω/km) (mH/km) (A) (A) (kA)
1.5 12.1 14.478 0.328 20 24 0.17
2.5 7.41 8.866 0.304 27 32 0.29
4 4.61 5.516 0.303 36 41 0.46
6 3.08 3.685 0.288 46 52 0.69
10 1.83 2.190 0.269 63 69 1.15
16 1.15 1.376 0.255 83 90 1.84
25 0.727 0.870 0.255 110 116 2.88
35 0.524 0.627 0.246 134 140 4.03
50 0.387 0.464 0.247 168 171 5.75
70 0.268 0.321 0.238 212 209 8.05
95 0.193 0.232 0.238 259 250 10.93
120 0.153 0.184 0.233 299 284 13.80
150 0.124 0.150 0.233 342 317 17.25
185 0.0991 0.121 0.233 391 357 21.28
240 0.0754 0.093 0.232 457 409 27.60
300 0.0601 0.075 0.231 519 457 34.50
12633-03 Rev. 2.0 / 2009

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYRY
NYRY 44xx(1.5-300)
(1.5-300) mm²
mm² 0.6/1
0.6/1 kV kV
Cu / PVC / SWA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Construction Data
Application :
Nom. Overall Cable Copper Conductor
For installation in the ground, indoors, cable
Cross Diameter Weight trunking and outdoors if increased mechanical PVC Insulation
Section protection is required or where high-pulling
Area approx. approx. stresses may occur during installation or PVC Inner Sheath
mm² mm kg/km operation.
Galvanized Steel Wire Armor
1.5 15.4 425 Special Features on Request :
Non-hygroscopic Tape
• Fire Resistance
2.5 16.5 509
• Oil Resistance PVC Sheath
4 19.6 767 • UV Resistance
• Flame Retardant Cat. A, B, C
6 21.0 904
• Flame Retardant Non Category
10 23.5 1,179 • Heat Resistance
• Anti Termite
16 27.0 1,657
• Anti Rodent
25 30.5 2,236 • Low Smoke Zero Halogen
35 33.5 2,768
50 40.0 3,639
Note :
70 43.0 4,592
Conductor Shape
95 50.0 6,338 1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
conductor shape
120 54.0 7,547
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
150 60.5 9,073 25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor
185 65.0 10,835
240 72.0 13,543 Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
300 78.0 16,333
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground

Max. Max. Max. Max. Max.


(mm²) (Ω/km) (Ω/km) (mH/km) (A) (A) (kA)
1.5 12.1 14.478 0.328 23 28 0.17
2.5 7.41 8.866 0.304 31 36 0.29
4 4.61 5.516 0.303 42 48 0.46
6 3.08 3.685 0.288 53 59 0.69
10 1.83 2.190 0.269 72 79 1.15
16 1.15 1.376 0.255 96 102 1.84
25 0.727 0.870 0.255 128 132 2.88
35 0.524 0.627 0.246 156 157 4.03
50 0.387 0.464 0.247 180 176 5.75
70 0.268 0.321 0.238 224 215 8.05
95 0.193 0.232 0.238 277 258 10.93
120 0.153 0.184 0.233 318 292 13.80
150 0.124 0.150 0.233 366 328 17.25
185 0.0991 0.121 0.233 413 365 21.28
240 0.0754 0.093 0.232 485 420 27.60
300 0.0601 0.075 0.231 550 468 34.50
12633-04 Rev. 2.0 / 2009

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYRY
NYRY 55xx(1.5-50)
(1.5-50) mm²
mm² 0.6/1
0.6/1 kV kV
Cu / PVC / SWA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Construction Data
Application : PVC Filler
Nom. Overall Cable
For installation in the ground, indoors, cable Copper Conductor
Cross Diameter Weight trunking and outdoors if increased mechanical
Section PVC Insulation
protection is required or where high-pulling
Area approx. approx. stresses may occur during installation or PVC Inner Sheath
mm² mm kg/km operation.
Galvanized Steel Wire Armor
1.5 16.3 482 Special Features on Request : Non-hygroscopic Tape
• Fire Resistance
2.5 17.6 581 • Oil Resistance PVC Sheath
4 21.0 882 • UV Resistance
• Flame Retardant Cat. A, B, C
6 22.5 1,055 • Flame Retardant Non Category
• Heat Resistance
10 26.0 1,515 • Anti Termite
16 29.0 1,945 • Anti Rodent
• Low Smoke Zero Halogen
25 33.0 2,649
35 37.5 3,538
50 42.5 4,437 Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 35 sqmm supplied in wooden drum @ 1000 m
50 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground

Max. Max. Max. Max. Max.


(mm²) (Ω/km) (Ω/km) (mH/km) (A) (A) (kA)

1.5 12.1 14.478 0.328 24 28 0.17


2.5 7.41 8.866 0.304 32 37 0.29
4 4.61 5.516 0.303 43 49 0.46
6 3.08 3.685 0.288 55 60 0.69
10 1.83 2.190 0.269 75 80 1.15
16 1.15 1.376 0.255 99 104 1.84
25 0.727 0.870 0.255 132 133 2.88
35 0.524 0.627 0.246 163 160 4.03
50 0.387 0.464 0.247 197 188 5.75
12633-05 Rev. 2.0 / 2009

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification