NA2XSY 1 X (25-630) MM 3.6/6 KV

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

NA2XSY

NA2XSY 11xx(25-630)
(25-630) mm²
mm² 3.6/6
3.6/6 kV kV
Al / XLPE/ CTS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-2

Construction Data
Application :
Nom. Overall Cable
For power stations and switchgear as well
Cross Diameter Weight as stations because of small bending radii
Section in confined spaces indoors. As underground
Area approx. approx. because of light weight where installation
mm� mm kg/km conditions are difficult.

25 16.9 374 Special Features on Request


35 18.1 431 • Oil Resistance
• UV Resistance
50 19.1 492 • Flame Retardant Cat. A, B, C
70 21.0 593 • Flame Retardant Non Category
• Anti Termite
95 23.0 706
• Anti Rodent
120 24.5 807 • Low Smoke Zero Halogen
150 25.5 867 • Nylon Coated

185 27.5 1,018


240 30.0 1,243
Note :
300 32.5 1,474
Conductor Shape
400 36.5 1,777 25 - 630 sqmm supplied in compacted circular stranded (cm) conductor shape
500 40.0 2,178
Standard Packing
630 45.0 2,700 25 - 630 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Electrical Data
Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit
Nom. DC AC Trefoil Flat current at 1 sec
Cross Resistance Resistance formation formation in air in ground in air in ground Conductor Screen
Sect. at 20°C at 90°C

Max. Max. Max. Max. Max. Max. Max. Max.


(mm²) (Ω/km) (Ω/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
25 1.20 1.539 0.399 0.445 120 117 123 121 2.35 1.14
35 0.868 1.113 0.376 0.422 147 141 151 145 3.29 1.14
50 0.641 0.822 0.360 0.407 176 166 181 171 4.70 1.14
70 0.443 0.568 0.339 0.385 222 204 228 210 6.58 1.14
95 0.320 0.411 0.324 0.370 271 244 278 251 8.93 1.14
120 0.253 0.325 0.313 0.359 313 278 322 285 11.28 1.14
150 0.206 0.265 0.303 0.350 355 311 365 319 14.10 1.14
185 0.164 0.211 0.295 0.341 412 353 423 362 17.39 1.14
240 0.125 0.162 0.288 0.335 489 409 502 419 22.56 1.14
300 0.100 0.130 0.283 0.330 563 461 579 473 28.20 1.14
400 0.0778 0.102 0.277 0.323 665 529 684 542 37.60 1.14
500 0.0605 0.081 0.273 0.319 774 603 796 618 47.00 1.14
630 0.0469 0.064 0.264 0.310 914 690 939 706 59.22 1.14
24633-01 Rev. 2.0 / 2009
NA2XSY
NA2XSY 11xx(25-630)
(25-630) mm²
mm² 6/10
6/10 kV kV
Al / XLPE/ CTS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-2

Construction Data
Application :
Nom. Overall Cable
For power stations and switchgear as well
Cross Diameter Weight as stations because of small bending radii
Section in confined spaces indoors. As underground
Area approx. approx. because of light weight where installation
mm� mm kg/km conditions are difficult.

25 18.7 437 Special Features on Request


35 19.9 497 • Oil Resistance
• UV Resistance
50 21.0 561 • Flame Retardant Cat. A, B, C
70 23.0 666 • Flame Retardant Non Category
• Anti Termite
95 24.5 744 • Anti Rodent
120 26.0 847 • Low Smoke Zero Halogen
• Nylon Coated
150 27.5 961
185 29.5 1,104
240 31.5 1,326 Note :
Conductor Shape
300 34.0 1,500
25 - 630 sqmm supplied in compacted circular stranded (cm) conductor shape
400 37.5 1,824
Standard Packing
500 40.5 2,204
25 - 630 sqmm supplied in wooden drum @ 1000 m
630 45.0 2,728 Length Tolerance per drum ± 2%

Electrical Data
Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit
Nom. DC AC Trefoil Flat current at 1 sec
Cross Resistance Resistance formation formation in air in ground in air in ground Conductor Screen
Sect. at 20°C at 90°C

Max. Max. Max. Max. Max. Max. Max. Max.


(mm²) (Ω/km) (Ω/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
25 1.20 1.539 0.419 0.466 123 118 126 121 2.35 1.14
35 0.868 1.113 0.395 0.441 150 141 153 144 3.29 1.14
50 0.641 0.822 0.379 0.425 179 166 183 170 4.70 1.14
70 0.443 0.568 0.355 0.402 225 204 231 209 6.58 1.14
95 0.320 0.411 0.338 0.384 273 244 281 250 8.93 1.14
120 0.253 0.325 0.327 0.373 316 278 325 285 11.28 1.14
150 0.206 0.265 0.319 0.365 360 311 369 318 14.10 1.14
185 0.164 0.211 0.308 0.354 416 353 427 361 17.39 1.14
240 0.125 0.162 0.299 0.345 492 409 506 419 22.56 1.14
300 0.100 0.130 0.291 0.337 565 461 581 472 28.20 1.14
400 0.0778 0.102 0.281 0.327 667 530 686 542 37.60 1.14
500 0.0605 0.081 0.275 0.321 775 603 797 618 47.00 1.14
630 0.0469 0.064 0.265 0.312 915 690 940 706 59.22 1.14
24633-02 Rev. 2.0 / 2009
NA2XSY
NA2XSY 11xx(25-630)
(25-630) mm²
mm² 8.7/15
8.7/15 kV kV
Al / XLPE/ CTS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-2

Construction Data
Application :
Nom. Overall Cable
For power stations and switchgear as well
Cross Diameter Weight as stations because of small bending radii
Section in confined spaces indoors. As underground
Area approx. approx. because of light weight where installation
mm� mm kg/km conditions are difficult.

25 21.0 520 Special Features on Request


35 22.5 584 • Oil Resistance
• UV Resistance
50 23.5 651 • Flame Retardant Cat. A, B, C
70 25.0 722 • Flame Retardant Non Category
• Anti Termite
95 27.0 853
• Anti Rodent
120 28.5 961 • Low Smoke Zero Halogen
150 30.0 1,081 • Nylon Coated

185 32.0 1,231


240 34.0 1,406
Note :
300 36.5 1,640
Conductor Shape
400 40.0 1,977 25 - 630 sqmm supplied in compacted circular stranded (cm) conductor shape
500 42.5 2,368
Standard Packing
630 47.5 2,910 25 - 630 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Electrical Data
Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit
Nom. DC AC Trefoil Flat current at 1 sec
Cross Resistance Resistance formation formation in air in ground in air in ground Conductor Screen
Sect. at 20°C at 90°C

Max. Max. Max. Max. Max. Max. Max. Max.


(mm²) (Ω/km) (Ω/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
25 1.20 1.539 0.442 0.488 125 118 128 120 2.35 1.14
35 0.868 1.113 0.416 0.463 152 141 156 144 3.29 1.14
50 0.641 0.822 0.399 0.445 182 166 186 170 4.70 1.14
70 0.443 0.568 0.373 0.419 228 204 234 209 6.58 1.14
95 0.320 0.411 0.357 0.404 277 244 285 250 8.93 1.14
120 0.253 0.325 0.345 0.391 321 277 329 284 11.28 1.14
150 0.206 0.265 0.336 0.383 364 310 373 318 14.10 1.14
185 0.164 0.211 0.325 0.371 420 352 431 361 17.39 1.14
240 0.125 0.161 0.313 0.360 496 408 509 418 22.56 1.14
300 0.100 0.130 0.305 0.352 569 461 584 472 28.20 1.14
400 0.0778 0.102 0.294 0.340 671 530 689 542 37.60 1.14
500 0.0605 0.080 0.287 0.333 779 603 800 618 47.00 1.14
630 0.0469 0.064 0.276 0.322 919 691 943 707 59.22 1.14
24633-03 Rev. 2.0 / 2009
NA2XSY
NA2XSY 11xx(35-630)
(35-630) mm²
mm² 12/20
12/20 kV kV
Al / XLPE/ CTS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-2

Construction Data
Application :
Nom. Overall Cable
For power stations and switchgear as well
Cross Diameter Weight as stations because of small bending radii
Section in confined spaces indoors. As underground
Area approx. approx. because of light weight where installation
mm� mm kg/km conditions are difficult.

35 24.5 669 Special Features on Request


50 25.5 698 • Oil Resistance
• UV Resistance
70 27.5 824 • Flame Retardant Cat. A, B, C
95 29.0 948 • Flame Retardant Non Category
• Anti Termite
120 30.5 1,074 • Anti Rodent
150 32.0 1,185 • Low Smoke Zero Halogen
• Nylon Coated
185 34.0 1,300
240 36.5 1,535
300 38.5 1,759 Note :
Conductor Shape
400 42.0 2,107
25 - 630 sqmm supplied in compacted circular stranded (cm) conductor shape
500 45.0 2,506
Standard Packing
630 49.5 3,063 25 - 630 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Electrical Data
Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit
Nom. DC AC Trefoil Flat current at 1 sec
Cross Resistance Resistance formation formation in air in ground in air in ground Conductor Screen
Sect. at 20°C at 90°C

Max. Max. Max. Max. Max. Max. Max. Max.


(mm²) (Ω/km) (Ω/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
35 0.868 1.113 0.434 0.480 154 141 158 144 3.29 1.14
50 0.641 0.822 0.415 0.461 184 166 188 170 4.70 1.14
70 0.443 0.568 0.390 0.437 230 204 236 209 6.58 1.14
95 0.320 0.411 0.372 0.418 280 244 287 249 8.93 1.14
120 0.253 0.325 0.360 0.407 324 277 332 284 11.28 1.14
150 0.206 0.265 0.350 0.396 367 310 376 318 14.10 1.14
185 0.164 0.211 0.337 0.384 422 352 433 360 17.39 1.14
240 0.125 0.161 0.326 0.372 499 408 512 418 22.56 1.14
300 0.100 0.130 0.316 0.363 572 461 587 472 28.20 1.14
400 0.0778 0.102 0.304 0.350 674 530 692 542 37.60 1.14
500 0.0605 0.080 0.296 0.342 782 604 802 618 47.00 1.14
630 0.0469 0.064 0.285 0.331 921 692 945 708 59.22 1.14
24633-04 Rev. 2.0 / 2009
NA2XSY
NA2XSY 11xx(50-630)
(50-630) mm²
mm² 18/30
18/30 kV kV
Al / XLPE/ CTS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-2

Construction Data
Application :
Nom. Overall Cable
For power stations and switchgear as well
Cross Diameter Weight as stations because of small bending radii
Section in confined spaces indoors. As underground
Area approx. approx. because of light weight where installation
mm� mm kg/km conditions are difficult.

50 31.0 963 Special Features on Request


70 33.0 1,105 • Oil Resistance
• UV Resistance
95 34.5 1,187 • Flame Retardant Cat. A, B, C
120 36.0 1,324 • Flame Retardant Non Category
• Anti Termite
150 37.5 1,443
• Anti Rodent
185 39.5 1,628 • Low Smoke Zero Halogen
240 41.5 1,863 • Nylon Coated

300 44.0 2,123


400 47.5 2,500
Note :
500 50.5 2,923 Conductor Shape
630 55.0 3,520 50 - 630 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
50 - 400 sqmm supplied in wooden drum @ 1000 m
500 - 630 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Electrical Data
Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit
Nom. DC AC Trefoil Flat current at 1 sec
Cross Resistance Resistance formation formation in air in ground in air in ground Conductor Screen
Sect. at 20°C at 90°C

Max. Max. Max. Max. Max. Max. Max. Max.


(mm²) (Ω/km) (Ω/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
50 0.641 0.822 0.455 0.501 188 166 192 169 4.70 1.14
70 0.443 0.568 0.428 0.474 235 203 241 208 6.58 1.14
95 0.320 0.411 0.406 0.453 285 243 292 249 8.93 1.14
120 0.253 0.325 0.393 0.439 328 277 336 283 11.28 1.14
150 0.206 0.265 0.381 0.427 372 310 381 317 14.10 1.14
185 0.164 0.211 0.368 0.414 428 351 438 360 17.39 1.14
240 0.125 0.161 0.354 0.400 504 408 516 417 22.56 1.14
300 0.100 0.129 0.344 0.390 577 460 592 471 28.20 1.14
400 0.0778 0.101 0.329 0.375 679 530 695 542 37.60 1.14
500 0.0605 0.080 0.320 0.366 787 604 806 618 47.00 1.14
630 0.0469 0.063 0.306 0.352 925 693 948 708 59.22 1.14