N2XSB(AL)Y

N2XSB(AL)Y 11x x(25-630)


(25-630) mm
mm 3.6/6
3.6/6 kV kV
Cu / XLPE/ CTS / PVC / ATA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Aluminium Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Construction Data
Application :
Nom. Overall Cable
For installation indoor, in ground direct burried,
Cross Diameter Weight for power station and switchgear, if there is a
Section risk that low mechanical damage may occur.
Area approx. approx.
mm mm kg/km Special Features on Request
Fire Resistance
25 21.5 729 Oil Resistance
35 22.5 856 UV Resistance
Flame Retardant Cat. A, B, C
50 23.5 998 Flame Retardant Non Category
70 25.5 1,244 Anti Termite
Anti Rodent
95 27.0 1,531
Low Smoke Zero Halogen
120 28.5 1,804
150 30.0 2,058
185 32.0 2,451 Note :
240 35.0 3,077 Conductor Shape
25 - 630 sqmm supplied in compacted circular stranded (cm) conductor shape
300 37.5 3,720
400 41.0 4,554 Standard Packing
500 45.5 5,715 25 - 300 sqmm supplied in wooden drum @ 1000 m
400 - 630 sqmm will be suplied in wooden drum on available length
630 49.0 7,136 Length Tolerance per drum 2%

Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short circuit
Trefoil Flat current at 1 sec
Nom. DC AC
Cross Resistance Resistance formation formation in air in ground in air in ground Conductor Screen
Sect. at 20C at 90C

Max. Max. Max. Max. Max. Max. Max. Max.


(mm) (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
25 0.727 0.927 0.437 0.484 164 153 168 157 3.58 1.14
35 0.524 0.668 0.415 0.461 199 183 204 188 5.01 1.14
50 0.387 0.494 0.398 0.444 237 216 243 221 7.15 1.14
70 0.268 0.342 0.374 0.421 296 264 304 270 10.01 1.14
95 0.193 0.247 0.358 0.404 360 316 369 323 13.59 1.14
120 0.153 0.196 0.346 0.392 416 358 426 366 17.16 1.14
150 0.124 0.159 0.334 0.380 473 402 484 410 21.45 1.14
185 0.0991 0.128 0.325 0.371 541 453 554 462 26.46 1.14
240 0.0754 0.098 0.316 0.362 639 523 654 533 34.32 1.14
300 0.0601 0.079 0.309 0.356 733 588 748 598 42.90 1.14
400 0.0470 0.063 0.300 0.346 851 667 868 677 57.20 1.14
500 0.0366 0.051 0.294 0.341 979 751 997 760 71.50 1.14
630 0.0283 0.041 0.286 0.332 1120 840 1136 848 90.09 1.14
17133-01 Rev. 2.0 / 2009

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
N2XSB(AL)Y
N2XSB(AL)Y 11x x(25-630)
(25-630) mm
mm 6/106/10
kV kV
Cu / XLPE/ CTS / PVC / ATA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Aluminium Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Construction Data
Application :
Nom. Overall Cable
For installation indoor, in ground direct burried,
Cross Diameter Weight for power station and switchgear, if there is a risk
Section that low mechanical damage may occur.
Area approx. approx.
mm mm kg/km Special Features on Request
Fire Resistance
25 23.5 812 Oil Resistance
35 24.5 941 UV Resistance
Flame Retardant Cat. A, B, C
50 25.5 1,086 Flame Retardant Non Category
70 27.0 1,337 Anti Termite
Anti Rodent
95 29.0 1,641 Low Smoke Zero Halogen
120 30.5 1,862
150 32.0 2,175
Note :
185 34.0 2,589
Conductor Shape
240 36.5 3,196 25 - 630 sqmm supplied in compacted circular stranded (cm) conductor shape
300 39.0 3,762
Standard Packing
400 42.0 4,631 25 - 300 sqmm supplied in wooden drum @ 1000 m
400 - 630 sqmm will be suplied in wooden drum on available length
500 46.0 5,767
Length Tolerance per drum 2%
630 49.5 7,192

Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short circuit
Trefoil Flat current at 1 sec
Nom. DC AC
Cross Resistance Resistance formation formation in air in ground in air in ground Conductor Screen
Sect. at 20C at 90C

Max. Max. Max. Max. Max. Max. Max. Max.


(mm) (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
25 0.727 0.927 0.454 0.500 166 153 170 156 3.58 1.14
35 0.524 0.668 0.431 0.477 201 183 206 187 5.01 1.14
50 0.387 0.494 0.413 0.459 240 216 246 221 7.15 1.14
70 0.268 0.342 0.389 0.435 299 264 307 270 10.01 1.14
95 0.193 0.247 0.373 0.419 363 315 372 322 13.59 1.14
120 0.153 0.196 0.358 0.404 418 358 428 365 17.16 1.14
150 0.124 0.159 0.347 0.393 476 401 487 410 21.45 1.14
185 0.0991 0.128 0.338 0.385 545 452 557 461 26.46 1.14
240 0.0754 0.098 0.326 0.372 642 523 657 532 34.32 1.14
300 0.0601 0.079 0.316 0.362 734 588 750 598 42.90 1.14
400 0.0470 0.063 0.305 0.351 852 666 869 677 57.20 1.14
500 0.0366 0.051 0.297 0.343 980 750 997 760 71.50 1.14
630 0.0283 0.041 0.289 0.335 1120 840 1137 848 90.09 1.14
17133-02 Rev. 2.0 / 2009

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
N2XSB(AL)Y
N2XSB(AL)Y 11x x(25-630)
(25-630) mm
mm 8.7/15
8.7/15 kV kV
Cu / XLPE/ CTS / PVC / ATA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Aluminium Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Construction Data
Application :
Nom. Overall Cable
For installation indoor, in ground direct burried,
Cross Diameter Weight for power station and switchgear, if there is a
Section risk that low mechanical damage may occur.
Area approx. approx.
mm mm kg/km Special Features on Request
Oil Resistance
25 25.5 919 UV Resistance
35 26.5 1,052 Flame Retardant Cat. A, B, C
Flame Retardant Non Category
50 27.5 1,200 Anti Termite
70 29.5 1,428 Anti Rodent
Low Smoke Zero Halogen
95 31.0 1,722
120 33.0 2,033
150 34.5 2,339
185 36.5 2,745 Note :
240 39.0 3,303 Conductor Shape
25 - 630 sqmm supplied in compacted circular stranded (cm) conductor shape
300 41.0 3,913
400 45.0 4,834 Standard Packing
500 48.5 5,942 25 - 300 sqmm supplied in wooden drum @ 1000 m
400 - 630 sqmm will be suplied in wooden drum on available length
630 52.0 7,379 Length Tolerance per drum 2%

Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short circuit
Trefoil Flat current at 1 sec
Nom. DC AC
Cross Resistance Resistance formation formation in air in ground in air in ground Conductor Screen
Sect. at 20C at 90C

Max. Max. Max. Max. Max. Max. Max. Max.


(mm) (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
25 0.727 0.927 0.473 0.519 168 153 172 156 3.58 1.14
35 0.524 0.668 0.448 0.495 203 183 208 187 5.01 1.14
50 0.387 0.494 0.430 0.476 242 216 248 220 7.15 1.14
70 0.268 0.342 0.405 0.451 302 263 309 269 10.01 1.14
95 0.193 0.247 0.387 0.433 366 315 374 321 13.59 1.14
120 0.153 0.196 0.376 0.422 422 357 431 364 17.16 1.14
150 0.124 0.159 0.363 0.409 479 401 490 409 21.45 1.14
185 0.0991 0.128 0.352 0.399 548 452 560 460 26.46 1.14
240 0.0754 0.098 0.338 0.385 645 522 659 532 34.32 1.14
300 0.0601 0.079 0.327 0.374 738 588 753 598 42.90 1.14
400 0.0470 0.063 0.317 0.363 855 667 871 676 57.20 1.14
500 0.0366 0.050 0.307 0.353 984 752 1000 761 71.50 1.14
630 0.0283 0.041 0.297 0.344 1125 842 1141 850 90.09 1.14
17133-03 Rev. 2.0 / 2009

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
N2XSB(AL)Y
N2XSB(AL)Y 11x x(35-630)
(35-630)
mmmm
2
2
12/20
12/20 kV kV
Cu / XLPE/ CTS / PVC / ATA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Aluminium Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Construction Data
Application :
Nom. Overall Cable
For installation indoor, in ground direct burried,
Cross Diameter Weight for power station and switchgear, if there is a risk
Section that low mechanical damage may occur.
Area approx. approx.
mm mm kg/km Special Features on Request
Oil Resistance
35 29.0 1,172 UV Resistance
50 30.0 1,281 Flame Retardant Cat. A, B, C
Flame Retardant Non Category
70 31.5 1,554 Anti Termite
95 33.5 1,884 Anti Rodent
Low Smoke Zero Halogen
120 35.5 2,173
150 37.0 2,483
185 38.5 2,839
Note :
240 41.0 3,441
Conductor Shape
300 43.5 4,076 35 - 630 sqmm supplied in compacted circular stranded (cm) conductor shape
400 47.0 5,011
Standard Packing
500 50.5 6,131 35 - 240 sqmm supplied in wooden drum @ 1000 m
300 - 630 sqmm will be suplied in wooden drum on available length
630 54.0 7,580
Length Tolerance per drum 2%

Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short circuit
Trefoil Flat current at 1 sec
Nom. DC AC
Cross Resistance Resistance formation formation in air in ground in air in ground Conductor Screen
Sect. at 20C at 90C

Max. Max. Max. Max. Max. Max. Max. Max.


(mm) (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
35 0.524 0.668 0.465 0.511 205 183 210 187 5.01 1.14
50 0.387 0.494 0.445 0.491 244 215 249 220 7.15 1.14
70 0.268 0.342 0.420 0.466 304 263 311 269 10.01 1.14
95 0.193 0.247 0.404 0.450 368 314 376 320 13.59 1.14
120 0.153 0.196 0.389 0.435 424 357 433 364 17.16 1.14
150 0.124 0.159 0.376 0.422 482 400 492 408 21.45 1.14
185 0.0991 0.127 0.364 0.410 550 451 562 460 26.46 1.14
240 0.0754 0.098 0.349 0.395 648 522 661 532 34.32 1.14
300 0.0601 0.079 0.338 0.384 740 588 755 597 42.90 1.14
400 0.0470 0.063 0.327 0.373 858 667 873 676 57.20 1.14
500 0.0366 0.050 0.316 0.362 986 752 1002 761 71.50 1.14
630 0.0283 0.041 0.306 0.352 1128 843 1143 850 90.09 1.14
17133-04 Rev. 2.0 / 2009

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
N2XSB(AL)Y
N2XSB(AL)Y 11x x(50-630)
(50-630) mm
mm 18/30
18/30 kV kV
Cu / XLPE/ CTS / PVC / ATA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Aluminium Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Construction Data
Application :
Nom. Overall Cable
For installation indoor, in ground direct burried,
Cross Diameter Weight for power station and switchgear, if there is a
Section risk that low mechanical damage may occur.
Area approx. approx.
mm mm kg/km Special Features on Request
Oil Resistance
50 35.5 1,639 UV Resistance
70 37.5 1,913 Flame Retardant Cat. A, B, C
Flame Retardant Non Category
95 39.0 2,185 Anti Termite
120 40.5 2,467 Anti Rodent
Low Smoke Zero Halogen
150 42.5 2,806
Nylon Coated
185 44.5 3,252
240 47.0 3,895
300 49.5 4,553 Note :
400 52.5 5,475 Conductor Shape
50 - 630 sqmm supplied in compacted circular stranded (cm) conductor shape
500 56.0 6,623
630 60.0 8,158 Standard Packing
50 - 240 sqmm supplied in wooden drum @ 1000 m
300 - 630 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum 2%

Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 C * Short circuit
Trefoil Flat current at 1 sec
Nom. DC AC
Cross Resistance Resistance formation formation in air in ground in air in ground Conductor Screen
Sect. at 20C at 90C

Max. Max. Max. Max. Max. Max. Max. Max.


(mm) (/km) (/km) (mH/km) (mH/km) (A) (A) (A) (A) (kA) (kA)
50 0.387 0.494 0.481 0.528 248 214 253 219 7.15 1.14
70 0.268 0.342 0.453 0.500 308 262 314 268 10.01 1.14
95 0.193 0.247 0.434 0.480 372 313 380 319 13.59 1.14
120 0.153 0.196 0.417 0.463 428 356 437 363 17.16 1.14
150 0.124 0.159 0.403 0.449 486 399 496 407 21.45 1.14
185 0.0991 0.127 0.391 0.438 554 450 565 459 26.46 1.14
240 0.0754 0.098 0.376 0.422 652 521 664 530 34.32 1.14
300 0.0601 0.078 0.364 0.410 744 587 757 596 42.90 1.14
400 0.0470 0.062 0.349 0.395 861 666 876 676 57.20 1.14
500 0.0366 0.050 0.337 0.383 990 753 1005 761 71.50 1.14
630 0.0283 0.040 0.327 0.373 1132 845 1145 852 90.09 1.14
17133-05 Rev. 2.0 / 2009