S.No Particulars 24 Core X 1.5 sq mm 1 Name of Manufacturer POLYCAB INDIA LTD. 2 Type of Cable Overall Screened 3 No of Elements X Size in mm² 24C X 1.5 4 Voltage Grade (V) 300/500 5 Conductor a) Material Plain Stranded Copper (Class-2) as per IS: 8130/2013 b) Maximum d.c. resistance of conductor at 20° C (Ω/km) 12.10 c) Shape of conductor Stranded Circular 6 Insulation a) Material PVC Type A as per IS:5831 b) Minimum Thickness mm 0.44 c) Core identification All cores Grey with number printing on core 7 Collective Screen a) Material Aluminium mylar tape b) Nominal Thickness mm 0.018 c) Material of Drain Wire Flexible ATC d) Size of Drain Wire (Approx.) 0.5 mm²(16/0.2 mm) 8 Inner sheath a) Material Extruded PVC Type ST1 to IS: 5831 Latest b) Minimum Thickness mm 0.3 9 Armouring a) Material Galvanised Steel b) Type of armouring Flat Strip c) Nominal size of armour (mm) 4.0 x 0.8 d) Tolerance on armour dimensions ± 10% 10 Outer sheath a) Material Extruded FR-LSH PVC Type ST1 to IS: 5831, Latest b) Thickness mm 1.40 (Min.) c) colour of sheath Blue Maximum conductor temperature under normal 11 70 operating conditions °C 12 Minimum bending radius 12 times Overall diameter 13 Electrical Parameters a) Mutual capacitance nf/km <250 b) Insulation resistance MΩ/km 10 c) Inductance to resistance ratio (L/R) µH/Ω <40 d) Dielectric strength for 1 minute (H.V Test) kV 2.0 Max. tensile strength for Cables pulled with stocking 14 9 x D², D is the cable OD in mm (Newtons) 15 Approximate Overall diameter of cable mm 21.5 ± 2.0 16 Applicable Standard Generally as per IS 1554 Part I/88 & BS EN 50288-7 17 Standard Drum Length (Mtr.) 1000 ± 5% Maximum 5% of order quantity and Min Individual Non- 18 Non-Standard Drum Length (Mtr.) Standard Drum 200 meters 19 Embossing POLYCAB 300/500 VOLTS GRADE FR-LSH YEAR POLYCAB 300/500 VOLTS GRADE FR-LSH CABLE SIZE 20 Printing SCREENED with SEQUENTIAL LENGTH MARKING at every one meter interval. 21 FR-LSH PROPERTIES a) Oxygen Index Min. 29% as per ASTM D- 2863 b) Temperature Index Min. 250 Deg.C as per ASTM D- 2863 c) Smoke Density Rating Max. 60% as per ASTM D- 2843 d) Acid Gas Generation Max. 20% as per IEC- 754- 1 e) Flammability Test As per IEC:332-I Note:-The values given above are subject to tolerances as per the relevant standards. Incase of any Typographical error /Descrepancy, relevent standards shall be prevailed.