DS300H

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

DS300/H Series 3 Plus Compressor Controllers Hardware Specifications

Series 3 Plus
Compressor Controllers
Hardware Specifications

Analog Inputs Eight isolated, floating-ground Discrete Five single-pole relays, each rated
(up to 10 Vdc) inputs. Standard Outputs 1 A atþ28 Vdc, jumper-selectable
combinations include: as normally-open or normally-
• all channels 1-to-5 Vdc closed.
(360 k impedance); Power Supply Power supply automatically adjusts
• all channels 4-to-20 mAdc to a wide range of input voltages:
(100  impedance); • 21 to 32 Vdc, or
Optional Field Termination Assem- • 96 to 264 Vac, 50 to 60 Hz
bly uses all 1-to-5 Vdc inputs. Maximum power consumption is 35
Consult the factory for information Watts, including transmitter power.
on optional custom configurations.
Inrush Current 6 to 22 A – duration of 2 to 6 ms
Analog Outputs One or two analog outputs, each
Power Cable One 14 ft. (4.3 m) cable per pair of
factory-configured for either:
controllers, both ends compatible
• 4-to-20 mAdc, 0 to 750  with selected power supply. AWG
load impedance, or 18 (0.8 mm2) conductors.
• 0-to-5 Vdc, 2 k to 200 k
Transmitter 24.0±1.2 Vdc, 6.0W maximum,
load impedance.
Power isolated and regulated.
Controllers may be configured
for output reliability tracking. Field Wiring Removable back-panel compres-
Terminals sion terminals accept AWG 18 to
Upper and lower limits can be AWG 14 (0.8 to 2.0 mm2) wire.
independently configured at any
0.1 % multiple of full scale. Optional Field Input/Output Module
(see DS300/T) can be mounted up
Serial Ports Two serial ports for communicating to 100 feet from controller.
with other CCC devices.
Power Failure System program and configuration
Two serial ports with optional sup-
Protection parameters stored in non-volatile
port for Modbus communications: EEPROM; process variables stored
• EIA RS-422/485 compatible in RAM with about a five-minute
• asynchronous, bi-directional, five capacitor backup capacity.
line interface: Scan Time 40 milliseconds. Inputs are sam-
RX+, RX–, TX+, TX–, GND pled every 5 milliseconds.
• 4000 ft. (1200 m) maximum cable Program Controller software can be updated
length Updating via serial communications from PC
• up to 32 transceivers per circuit running Download software.
• 4800, 9600, or 19.2k baud Manual Control Output signal(s) and controller set
• 8 data bits, 1 start bit, 1 stop bit points can be set at any 0.1 %
(odd, even, or no parity) multiple of full scale. Bumpless
transfer between automatic and
Discrete Inputs Seven inputs with common return, manual operation or between local
each rated at 30 Vdc (maximum), and remote set point.
2.2 k resistance.
Parameter Front panel swings out to provide
Energized state: +10 to +30 Vdc;
De-energized state: 0 to +2 Vdc. Setting access to configuration parameter
keyboard and 8 character display.
Optional Toolbox software allows
setup from IBM-compatible PC.

August 2015 Page 1 of 2 DS300/H (6.0.4)


Standard Back Panel Dimensions
Top View
CH 1 CH 2 CH 3 CH 4 OUT 1 OUT 2 Pressure Screw
+ – + – + – + – + +
Slide Slide Clamp

2.96
CH 5 CH 6 CH 7 CH 8 CR1 CR2 75.2 2.68
+ – + – + – + – 1 2 1 2 68.1

19.04
CR3 CR4 CR5 DISCRETE IN 484
1 2 1 2 1 2 D1 D2 D D3 D4 D5 1.0
26

Side View
PORT 1 PORT 2
TX/RX TX2 RX2 24VDC DISCRETE
1 + – + – 2 + – + – D6 D7

PORT 3 NOT PORT 4


TX3 RX3 TX4 RX4
+ – 3 + – USED + – 4 + –
6.00 5.50
153 140

PORT 5 96-264 VAC


TX5 RX5
+ – + – 21-32 VDC

TB6
Port 5 - Not Used Front Bezel Power Cord
N GRD H
MADE IN USA
35 W max
þDimensions given in inches and millimeters

Nameplate 0.42 x 2.56 in. (10.7 x 65 mm) label Mounting Cutout Width: 2.70 in. (68.6 mm)
(Optional) that can accommodate one line of Dimensions Tolerance: +0.02 in. (0.5 mm)/–0.00
14-pt type (about 17 characters) or Cutout Height: 5.60 in. (142.2 mm)
two lines of 10-pt type (about 22 Tolerance: +0.03 in. (0.8 mm)/–0.00
characters each).
Cabinet Depth: 22 in. (56 cm) from
Ambient Operating Temperature: front of panel.
Conditions 32 to 122°F (0 to 50°C).
Observed MTBF 395000 hours (45.1 years)
Storage Temperature:
–13 to + 185°F (–25 to +85°C). Electrical Ordinary, non-hazardous areas.
Relative Humidity: 0 to 95% Classifications Approved by CE, CSA, and
(if free from condensation). City of L.A.

Weight 7.5 lb (3.4 kg).

August 2015 Page 2 of 2 DS300/H (6.0.4)

COMPRESSOR CONTROLS CORPORATION


4725 121st Street, Des Moines, IA 50323, USA
Phone: (515) 270-0857 • Fax: (515) 270-1331 • Web: www.cccglobal.com
Printed in U.S.A.

You might also like