23WT25 CS en
23WT25 CS en
23WT25 CS en
Modem 23WT25
RTU560 product line
Application, characteristics and technical data have to Output and input impedance can be chosen between
be taken from the hardware data sheet: 600 Ω and infinity.
23WT25 Data sheet 1KGT 150 591 Input filter characteristic can be switched between:
The total load of a subrack power supply unit can • Option to set the optimum predistortion through
be controlled via the selection of the version; i.e. the integrated test function with result displayed via
allocation of the loads to 24 V DC and 5 V DC. LED (LEDs = EQZ, RxD)
Carrier disconnection:
The 23WT25 modem is plug-compatible with the
23WT22 modem. • through RTS in half-duplex mode
• after a period of time (2 to 16 seconds) which is
Processing Functions dependent on the bit rate
The 23WT25 modem has the following characteristics Optional monitoring of the received signal for
(see also table 2): isochronous distortion with display (LED=SQL; SQL
alarm).
VFT channels in the CCITT grid for different bit rates
(bps - bits per second) rates: Carrier monitoring (DCD alarm) as a function of the bit
rate.
• 24 channels 50 bps R.35
• 12 channels 100 bps R.37 Alarm relay can optionally be set to:
• 6 channels 200 bps R.38A • DCD alarm directly
• 2 channels 600 bps • DCD alarm delayed as a function of the bit rate
• 1 channel 1200 bps V.23 • DCD alarm delayed or SQL alarm
• 1 channel 2400 bps
Free assignment of the polarity of the V.24 signals, and
Operating modes: also of the zero position of the receiver (RxD) (+ ΔF or -
ΔF).
• two-wire or four-wire link
• point-to-point connection or Output of the received eye sensitivity signal to the
• multi-drop line with staggering transmitter output for testing in the test mode.
• duplex or half-duplex mode on two-wire or four-
wire links
Settings
The transmission level can be set as a function of:
The 23WT25 modem is configured by means of the
• the bit rate according to CCITT jumper rows X2 to X8. The jumper rows X2 to X5 are
• the occupied channels read and evaluated by the digital signal processor
• additional stepping up by 6 dB (DSP). The analog part is configured with X6. The
Setting receiver sensitivity in four steps (6, 10, 14 or 26 signal level definitions are assigned to the V.24 lines
dB) using X7.
• Raising the detection level by 15 dB for noisy lines • X2 = transmitter bit rate and channel
is possible • X3 = receiver bit rate and channel
• X4 = transmission level, predistortion channels with a low bit rate are to be separated at
• X5 = additional functions least by one low-bit-rate channel from the higher bit
• X6 = line connection analog part rate.
• X7 = V.24 signal level definitions
If there are adjacent channels with the same bit
• X8 = power supply
rate (applies only to the range 50-200 bps), the level
The arrangement of the jumpers on the module is
difference may not exceed 17 dB.
shown in figure 3.
Quality Check
The 23WT25 modem allows the received signal to be
monitored for excessive isochronous distortion during
operation. If a threshold value is exceeded, the modem
indicates this via the LED SQL (SQL= signal quality
level) and activates the alarm relay (k1).
• +5 V DC (R0001) or
• +24 V DC (R0002)
The necessary further supply voltages are generated
by DC/DC converters on the circuit board. In addition,
the respective supply voltage can either be supplied
by the power supply unit of the subrack or from an
external source (ext.). For this purpose, the jumper X8
is to be set accordingly (see figure 3). The negative
pole of the external voltage source is to be connected
to the negative pole of the subrack supply (see
connection and setting description for 23TP22 and
23ET24 or table 12).
NF2a b30
500LTD01
600Ω two-wire-
NF2b z30 transmission line
end to end
17 16 15 14 13 12 11 10 9 8 7 6 5
NF1a b32 X6
600Ω
z32
NF1b
end to end
17 16 15 14 13 12 11 10 9 8 7 6 5
NF1a b32 X6
600Ω
z32
NF1b
NF2a b30
500LTD01
600Ω Receive
NF2b z30
four-wire-
transmission line 17 16 15 14 13 12 11 10 9 8 7 6 5
NF1a b32 X6
500LTD01 Transmit
600Ω
z32
NF1b
Two-wire-
NF2a b30 transmission line
500LTD01
X6- 13
NF2b z30
Receive
Transmit
17 16 15 14 13 12 11 10 9 8 7 6 5
NF1a b32 X6
X6- 10
z32
NF1b
NF2a b30
500LTD01 Two-wire-
X6- 13
transmission
NF2b z30
line
Receive 17 16 15 14 13 12 11 10 9 8 7 6 5
Transmit X6
NF1a b32
X6- 10
z32
NF1b
NF2a b30
500LTD01
600Ω Receive
NF2b z30
four-wire-
transmission line 17 16 15 14 13 12 11 10 9 8 7 6 5
NF1a b32 X6
500LTD01 Transmit
600Ω
z32
NF1b
four-wire- 17 16 15 14 13 12 11 10 9 8 7 6 5
transmission line
NF1a b32 X6
500LTD01
600Ω
z32
Transmit
NF1b
NF2a b30 A1 A1
600Ω Line
NF2b z30 E1 E1 A
600Ω S P
A2 A2
E2 E2
600Ω
23WT25
600Ω
Line 17 16 15 14 13 12 11 10 9 8 7 6 5
B
NF1a b32 A1 A1 X6
600Ω
z32 E1 E1
NF1b 600Ω S P
A2 A2
E2 E2
600Ω
Line
C
600Ω
ABB Power Grids Germany AG We reserve the right to make technical We reserve all rights in this document and in
changes or modify the contents of this the subject matter and illustrations contained
1KGT 150 592 V005 1
P.O. Box 10 01 64 document without prior notice. With therein. Any reproduction, disclosure to third
68128 Mannheim, Germany regard to purchase orders, the agreed parties or utilization of its contents – in whole
Tel. +49 621 381-3000 particulars shall prevail. ABB Power or in parts – is forbidden without prior written
Grids Germany AG does not accept any consent of ABB Power Grids Germany AG.
responsibility whatsoever for potential Copyright© 2020 ABB Power Grids Germany AG
errors or possible lack of information in All rights reserved
www.abb.com/remote-terminal-units this document.