InteliGen 1000 2 2 2 Datasheet - 2
InteliGen 1000 2 2 2 Datasheet - 2
InteliGen 1000 2 2 2 Datasheet - 2
1000
Highly flexible yet configurable solution for switchgear AirGate 2.0 makes sure that the connection to the
| InteliGen 1000 2.2.2 Datasheet | Related HW ver: 1.0.2 | Related SW ver: 2.2.2 | Date of issue: 6/23/2022
Dimensions, terminals and mounting
Binary inputs
Power supply
Number 12, non-isolated
Power supply range 8-36 V DC
Close/Open 0-2 V DC close contact
Power consumption 16 W
indication 6-36 V DC open contact
RTC battery Replaceable, type CR1632 3V
Configurable Pull-up / Pull-down
Fusing power 8A
Pulse input Bin 9 and 10 max. 50 Hz
Consumption 2.5 A Controller + 10 x 0.5 A BOUTs
Fusing ESTOP 1.2 A Binary outputs
Max. Heat Dissipation 16 W Number 12, non-isolated
Max. current 0.5 A
D+
Switching to Positive supply terminal
Max. excitation
250 mA
current Analog inputs
Charging fail Number 4, switchable (R/U/I)
80 % of Usupply
threshold
Range R = 0-10000 Ω; U = 0-10 V; I = 0-20 mA
Operating conditions R: 2 % from value for 0-250 Ω
R: 4% from value for 250-2500 Ω
Operating
-40 °C to +70 °C Accuracy R: 6 % from value for 5000-10000 Ω
temperature
U: 1% from value ±100 mV
Storage temperature -40 ˚C to +80 ˚C
I: 1% from value ±200 uA
Operating humidity 25/55°C, RH 95%, 48hours,
(norm 60068-2-30) without condensation Voltage regulator output
Protection degree IP20 Protection Reinforced isolation
5-25 Hz, ± 1.6 mm Switchable: U ±10 V, I ±20 mA, PWM: 0 V/5
Vibration Type
25-100 Hz, a = 4 g V
2
Shocks a = 500 m/s
U: 1 % from value ±100 mV
Surrounding air temperature rating 70 °C. Accuracy
I: 1 % from value ±200 uA
Suitable for pollution degree 2.
Speed governor output
AC Current measurement
Protection Basic isolation
3ph Gen current
Type Switchable: U ±10 V, I ±20 mA, PWM: 0 V/5 V
Measurement inputs 3ph Mains current
1ph Auxiliary current U: 1 % from value ±100 mV
Accuracy
Measurement range 1A/5A I: 1 % from value ±200 uA
Maximum continuous
current
2 A / 10 A Magnetic pick-up
Allowed overload 18 A for 15 sec. Minimum input 4 V pk-pk to 50 V pk-pk in range 4 Hz to 1 kHz
voltage
±3 mA / ±15 mA for 0.0 to 0.4 A / 0.0 to 2.0
A Working voltage 6 V pk-pk to 50 V pk-pk in range 4 Hz to 5 kHz
Accuracy
0.75 % of value for 0.4 to 1.0 A / 2.0 to 5.0 range 10 V pk-pk to 50 V pk-pk in range 4 Hz to 10 kHz
A Frequency input
4 Hz to 10 kHz
Frequency range 40-70 Hz (accuracy 0.002 %) range
CAN Repeater Module, compatible when using 32C/8C CAN Intercontroller Comm
I-CR I-CR
Mode
ANSI
Description ANSI code Description ANSI code Description
code
Master unit 1 Load shedding 32P AC circuit breaker 52
Stopping device 5 Reverse power 32R Power factor 55
Multi-function device 11 Master sequence device 34 Overvoltage 59
Overspeed 12 Undercurrent 37 Pressure switch 63
Underspeed 14 Excitation loss 40 Liquid level switch 71
Speed and frequency matching
15 Unit sequence starting 44 Alarm relay * 74
device
16EFT
Data communications device Current unbalance 46 Vector shift 78
16SC
Starting-to-running transition
19 Voltage unbalance 47 Reclosing relay 79
contractor
Distance relay 21 Incomplete sequence relay 48 Overfrequency 81H
Synchronizing-check 25 Temperature monitoring 49T Underfrequency 81U
Thermal relay 26 Overcurrent 50/50TD ROCOF 81R
E-mail: [email protected]
Web: www.comap-control.com
© ComAp. Features and specification are subject to change without prior notice.
Undervoltage 27 Earth fault current 50N+64 Auto selective control/transfer 83
Annunciator 30 Overcurrent IDMT 51 Regulating device 90
Overload 32 Earth fault current IDMT 51+64
Grid codes
European Requirements for Generators, 2016/631
Responsible Party:
10 N Martingale Rd #400
60173 - Schaumburg, IL
USA
E-mail: [email protected]
Web: www.comap-control.com
© ComAp. Features and specification are subject to change without prior notice.