Inteligen 1000 3.0.2 Datasheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

InteliGen

1000

Order code: IG31000XBBB

Paralleling gen-set controller for switchgear


Datasheet applications
AirGate 2.0 makes sure that the connection to the controller
Product description is established faster from all around the world, and is more
True RMS measurement is used with Voltage, Current and reliable than ever before.
Power measurement. Internal PLC interpreter with easy to use PLC Editor, for
Comprehensive paralleling Gen-set controller for island or simple and fast creation of specific logic
mains parallel operation Up to 31 characters in texts, parameters, Alarms for system
Cooperation with up to 64 gen-set / mains / tie controllers clarity and easy troubleshooting
Direct communication with ECU Compatibility with ComAp IG/IS/IM-NT line, IG200, IG500
Secure Remote control and monitoring controllers
ENABLE/DISABLE concept of features and protections
Highly flexible yet configurable solution for switchgear
makes the system highly versatile yet simple and easy for
applications
both commissioning engineers and operators

Key features Application overview


Hardware compliant to the latest switchgear market needs
State of the art AC accuracy measurements which allows to
participate on primary frequency control mechanism, grid
balancing and demand response projects
Cybernetic security by design, based on the ANSI/ISA-
62443 standard
Large portion of both local and remote monitoring options,
with high number of at once connected clients split into
“trusted” and “untrusted” zones
Mains parallel operation with support of Grid codes,
compliant to European Grid codes ( Requirements for
Generators, VDE-AR-N 4110:2018, VDE-AR-N 4105:2019,
G99), American IEEE 1547
Multiple Island operation with cooperation up to 64 additional
gen-set/mains/tie controllers
Several load transfer options with possibility of less than
100ms load transfer
Redundant inter-controller line for critical applications like
datacentres, hospitals
Double redundancy of the kW and kVAr sharing
User management allowing to handle up to 30 unique users

| InteliGen 1000 3.0.2 Datasheet | Related HW ver: 1.0.2 | Related SW ver: 3.0.2 | Date of issue: 2/13/2024
Terminals and dimensions

InteliGen 1000 3.0.2 Datasheet 2


Binary inputs
Technical data
Number 12, non-isolated
Power supply Close/Open 0-2 V DC close contact
Power supply range 8-36 V DC indication 6-36 V DC open contact

Power consumption 16 W Configurable Pull-up / Pull-down

RTC battery Replaceable, type CR1632 3V Pulse input Bin 9 and 10 max. 50 Hz

Fusing power 8A Binary outputs


Consumption 2.5 A Controller + 10 x 0.5 A BOUTs @ 8 V
Number 12, non-isolated
Fusing E-STOP 1A
Max. current 0.5 A
Max. Heat Dissipation 16 W
Switching to Positive supply terminal
Operating conditions
Analog inputs
Operating
-40 °C to +70 °C Number 4, switchable (R/U/I)
temperature
Range R = 0-10000 Ω; U = 0-10 V; I = 0-20 mA
Storage temperature -40 ˚C to +80 ˚C
R: 2 % from value for 0-250 Ω
25/55°C, 48hours,95 % non-
Operating humidity R: 4% from value for 250-2500 Ω
condensing
(norm 60068-2-30) Accuracy R: 6 % from value for 5000-10000 Ω
(EN 60068-2-30)
U: 1% from value ±100 mV
Protection degree IP20
I: 1% from value ±200 uA
5-25 Hz, ± 1.6 mm
Vibration
25-100 Hz, a = 4 g Voltage regulator output
2
Shocks a = 500 m/s Protection Reinforced isolation
Surrounding air temperature rating 70 °C. Switchable: U ±10 V, I ±20 mA, PWM: 0 V/5
Type
Suitable for pollution degree 2. V

AC Current measurement U: 1 % from value ±100 mV


Accuracy
I: 1 % from value ±200 uA
3ph Gen current
Measurement inputs
1ph Mains current (Auxiliary current)
Speed governor output
Measurement range 1A/5A
Protection Basic isolation
Maximum continuous
2 A / 10 A Type Switchable: U ±10 V, I ±20 mA, PWM: 0 V/5 V
current
Allowed overload 18 A for 15 sec. U: 1 % from value ±100 mV
Accuracy
±3 mA / ±15 mA for 0.0 to 0.4 A / 0.0 to 2.0 I: 1 % from value ±200 uA
Accuracy A0.75 % of value for 0.4 to 1.0 A / 2.0 to
5.0 A
Magnetic pick-up
Frequency range 40-70 Hz (accuracy 0.002 %) Minimum input 4 V pk-pk to 50 V pk-pk in range 4 Hz to 1 kHz
Input impedance 0.68 MΩ ph-ph , 0.34 MΩ ph-n voltage
Working voltage 6 V pk-pk to 50 V pk-pk in range 4 Hz to 5 kHz
AC Voltage measurement range 10 V pk-pk to 50 V pk-pk in range 4 Hz to 10 kHz

3ph-n Gen voltage Frequency input


Measurement inputs 4 Hz to 10 kHz
3ph-n Mains voltage range

115 V ph-N / 200 V ph-ph Frequency


measurement 0.2 % from range 10 kHz
suitable also for VTs output
Measurement range tolerance
231 V ph-N / 400 V ph-ph
UL, cUL: 346 V ph-N / 600 V ph-ph
Communications
Linear measurement USB Device Basic isolation, USB type B
and protection range 433 V ph-N / 750 V ph-ph RS 485 Basic isolation
(maximal voltage) ETH1
Accuracy 0.25 % ETH2 10/100 Mbit
Frequency range 40-70 Hz (accuracy 0.002 %) ETH3

Input impedance 0.72 MΩ ph-ph , 0.36 MΩ ph-n CAN 1A


CAN 2A Basic isolation, 1000/250/50 kbps
Measurement category CAT III, overvoltage category III
CAN 1B , nominal impedance 120 Ω
E-Stop CAN 2B

Dedicated terminal for safe Emergency Stop input. Weight


Physically disconnects BO 1 & BO 2 from power supply.
Controller 750 g
Package 920 g

Controller handles 300 million records into the History, which represents
roughly 1 record per second during 9,5 years. Shall be the History recording
faster, the controller lifetime will become smaller.

InteliGen 1000 3.0.2 Datasheet 3


Available simulator
Product Order code
InteliGen1000 StarterKit SM4IG1K5BAB

Available plug-in modules (NOT SUPPORTED!)


Product Description Order code

CM-RS232-485 CM223248XBX
CM2-4G-GPS CM24GGPSXBX
NOT SUPPORTED!
CM3-Ethernet CM3ETHERXBX
EM-BIO8-EFCP EM2BIO8EXBX

Note: Controller has 2 slots for plug-in modules.

Available external displays


Product Description Order code

InteliVision 5.2 5" TFT external display with 800x480 px resolution RD2IV5BXBAA
InteliVision 10Touch 10.1" Touchscreen display uni with 1280 x 800 px resolution RD1IV10TBPF
InteliVision 13Touch 13.3" Marine certified display unit with 1920 × 1080 px resolution RD1IV13TBME
InteliVision 18 18.5" Touchscreen display unit with 1366 × 768 px resolution RD31840PBIE

Available CAN modules


Product Description Order code
Inteli AIN8 8 Analog Input Channels and 1 RPM/Impulse Input Module I-AIN8
Inteli AIN8TC 8 Analog Input Channels for termocouples measurement I-AIN8TC

4 Analog Inputs for differential voltage measurement, 4 Analog Input equipment


Inteli AIO9/1 I-AIO9/1
channels, 1 Analog Input for resistance measurement and 1 Analog Output
Inteli IO8/8 16 Configurable Binary Inputs/Outputs and Analog Outputs Module I-IO8/8
IGL-RA15 Remote Annunciator w/ 15 programmable LEDs EM2IGLRABAA
IGS-PTM 4 Analog Inputs, 1 Analog Output, 8 Binary Inputs and 8 Binary Outputs IGS-PTM
I-AOUT8 8 configurable analog outputs I-AOUT8
IS-AIN8 8 configurable analog inputs IS-AIN8
IS-BIN16/8 16 galvanically separated inputs, 8 binary outputs, 2 pulse inputs IS-BIN16/8
InteliFieldbus Gateway Modbus TCP/RTU Communication gateway CM1IFGATBBB

CAN Repeater Module, compatible when using 32C/8C CAN Intercontroller Comm
I-CR I-CR
Mode
Communication gateway with configurable interfaces between Modbus TCP/RTU,
InteliGateway 300 ComAp CAN, WebSupervisor and InteliScada protocols allowing user-defined CM2GW300BAB
interconnection of all attached devices

Functions and protections


Support of functions and protections as defined by ANSI (American National Standards Institute):

ANSI
Description ANSI code Description ANSI code Description
code
Master unit 1 Reverse power 32R Power factor 55
Stopping device 5 Master sequence device 34 Overvoltage 59
Multi-function device 11 Undercurrent 37 Pressure switch 63
Overspeed 12 Excitation loss 40 Liquid level switch 71

E-mail: [email protected]
Web: www.comap-control.com

© ComAp. Features and specification are subject to change without prior notice.
Underspeed 14 Unit sequence starting 44 Alarm relay * 74
Speed and frequency matching
15 Current unbalance 46 Vector shift 78
device
16EFT
Data communications device Voltage unbalance 47 Reclosing relay 79
16SC
Starting-to-running transition
19 Incomplete sequence relay 48 Overfrequency 81H
contractor
Synchronizing-check 25 Temperature monitoring 49T Underfrequency 81U
Thermal relay 26 Overcurrent 50/50TD ROCOF 81R
Undervoltage 27 Earth fault current 50N+64 Auto selective control/transfer 83
Annunciator 30 Overcurrent IDMT 51 Regulating device 90
Overload 32 Earth fault current IDMT 51+64

Load shedding 32P AC circuit breaker 52

* extension module IGL-RA15 required

Certifications and standards


EN 61000-6-2 EN 60068-2-1 (-40 °C/16 h) UL6200 *

EN 61000-6-4 EN 60068-2-2 (70 °C/16 h) UKCA

EN 61010-1 EN 60068-2-6 (2÷25 Hz / ±1,6 mm; 25÷100 Hz / 4,0

EN 60255-1 g)
2
EN 60529 (IP20) EN 60068-2-27 (a=500 m/s ; T=6 ms)

EN 60068-2-30 (25/55 °C, RH 95%, 48 h)


* ULC 6200:2019 Certified (see the NFL File for the FW version with the Witness test if it is required by the certification of the end product)

Grid codes
European Requirements for Generators, 2016/631

German VDE-AR-N 4110:2018 UK ENA EREC G99

American IEEE 1547 Austrian TOR

List of SW Key Features


SW Key Feature Order Code
CAN bus redundancy SKREDCAN201

Hot Swap Redundancy SKHOTSWAP01

PLC package SKPLCPCKG01


Variable Speed Generator SW1VSGXXXXX

E-mail: [email protected]
Web: www.comap-control.com

© ComAp. Features and specification are subject to change without prior notice.
Supplier's Declaration of Conformity
47 CFR § 2.1077 Compliance Information

Unique identifier: IG31000XBBB

Responsible Party:
Kevin Counts
10 N Martingale Rd #400
60173 - Schaumburg, IL
USA

Tel: +1 815 636 2541


E-mail: [email protected]

FCC Compliance Statement


This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.

E-mail: [email protected]
Web: www.comap-control.com

© ComAp. Features and specification are subject to change without prior notice.