InteliGen GSC C Datasheet v3

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

InteliGen

GSC-C

Order code: IG2GSCCXBAB

Gen-set controller compliant to the latest


Datasheet world Grid Codes requirements

Plug&Play support of ComAp InteliVision display family.


Product description
Event-based History allows easy troubleshooting.
The InteliGen GSC-C is a powerful controller for complex
Tier IV Final and Stage V engines support.
paralelling applications requiring the latest grid codes
standards with extension in external communication Supporting wide range of applications:
capabilities. Pre-configured gen-set functions, scalable and From single to multiple paralleling, from island to network
configurable I/Os, communication capabilities and in-built PLC paralleling operation.
Editor for maximal flexibility.
Hybrid installations support
Key features Generator controller only (engine management can be
Compliant to the latest world grid codes standards: disabled)

Europan Union - EU 631/2016 Requirements for Grid codes requirements interpreteur - synchronizer for
Generators 3rd party control units

Germany - VDE-AR-N 4110:2018, VDE-AR-N 4105:2018


Application overview
(Component certification)
United Kingdom - G99

USA - IEEE 1547-2018

Others
Predefined, adjustable functions for gen-set control allows
easy and fast gen-set commissioning.
Built-in PLC interpreter allows flexible and easy adaptation to
customer needs without extra effort.
Support of wide range applications – from single to multiple,
from island to network parallel operation.
Support of wide range of electrical engines, ECUs.
Powerful power management function optimizing number of
running gen-sets.
Automatic Load and Var sharing over CAN line (requires HW
dongle).

| InteliGen GSC-C Datasheet | Related HW ver: 2.2.0 | Related SW ver: 1.0.0 | Date of issue: 10/15/2020
Technical data
Power supply Binary outputs
Power supply Number 12 non-isolated
8-36 V DC
range Max current 0.5 A (2 A per group)
0.4 A / 8 V DC Switching to Negative/positive supply terminal
Power consumption 0.15 A / 24 V DC
0.1 A / 36 V DC Analog inputs
10 years Number 3 non-isolated
RTC battery
(replaceable by official service) Switchable (Voltage, Resistance,
Type
Fusing 2 A (without BOUT consumption) Current)
Max. Power Resolution 10 bits, max 4 decimals
16 W
Dissipation Range 0-5 V DC / 0-2500 Ω / 0-20 mA

Operating conditions Input impedance >100 kΩ / >100 kΩ / 180 Ω


±1 % of meas. value ±5 mV
Operating
-40 ˚C to +70 ˚C Accuracy ±2 % of meas value ±2 Ω
temperature
±1 % of meas value ±0.5 mA
Storage
-40 ˚C to +80 ˚C
temperature Magnetic pick-up
2000 m above sea level Voltage input range 2 Vpk-pk to 50 Veff
Max. operating
4000 m above sea level for
altitude Frequency input
max Ph-Ph voltage 400V AC 4 Hz to 15 kHz
range
Operating humidity 95 % w/o condensation
Frequency
5-25 Hz, ±1.6 mm measurement 0.2 %
Vibration
25-100 Hz, a = 4 g tolerance
Shocks a=200 m/s2
Voltage regulator output
Heat radiation 16 W
5 V TTL PWM / ± 10 VDC with
Voltage measurement Type
IG-AVRi interface
Measurement 3 ph-n Gen voltage
Speed governor output
inputs 3 ph-n Mains voltage/Bus voltage
Measurement range 110 V / 277 V Voltage output ±10 V DC / max.10 mA

Max allowed Voltage output via ±10 V DC via 10 kΩ resistor / max . 1


125 % ph-n resistor mA
voltage
Accuracy 1 % of 110 V / 277 V PWM 500÷3000 Hz / 5 V / max. 10mA

Frequency range
40-70 Hz (accuracy 0.1 Hz) Communications
45-65 Hz (accuracy <0.01 Hz)
RS232 Direct/Modbus, non-isolated
Input impedance 0.6 MΩ ph-ph, 0.3 MΩ ph-n
RS485 Direct/Modbus, isolated
Current measurement non-isolated RS485, only terminal
Display port
3 ph Gen current connection
Measurement inputs
1 ph Mains current USB port Direct, isolated

Measurement range 1 A / 5 A LAN/Internet, Modbus TCP, SNMP,


Ethernet port
Max allowed AirGate
200 % / 200 %
continuous current External modules
CAN1
Accuracy 2 % of 1 A / 5 A 250 kbps, max 200 m, Isolated

Input impedance <0.1 Ω Intercontroller and comm


extensions
CAN2
Binary inputs 250 / 50kbps, max 200 / 1000m,

Number 12 non-isolated Isolated

Input resistance 4.7 kΩ


Close/Open 0-2 V DC close contact
indication >4 V DC open contact

InteliGen GSC-C Datasheet 2


Dimensions, terminals and mounting

Panel door mounting DIN-rail mounting Panel door mounting


with InteliVision 5 with InteliVision 8

① InteliVision5
② InteliGen GSC-C
③ DIN-rail
④ InteliVision 8

InteliGen GSC-C Datasheet 3


Available extension modules
Product Description Order code
Inteli IO8/8 8 Binary inputs, 8 Binary outputs and 2 Analog outputs in a small unit (HW switchable to IO16/0) I-IO8/8
Inteli IO8/8 HW switchableto IO16/0 - 16 Binary inputs packed in a small unit I-IO8/8
Inteli AIN8 8 Analog inputs (R, I, V) and 1 pulse/frequency input in a small unit I-AIN8
Inteli AIN8TC 8 Thermocouple Analog inputs in a small unit I-AIN8TC
Inteli AIO9/1 9 Analog inputs (4x DC, 4x thermocouples, 1x R) in a small unit I-AIO9/1
IS-AIN8 8 Analog inputs packed in a rugged metal unit IS-AIN8
IGS-PTM 8 Binary inputs, 8 Binary outputs, 4 Analog inputs and 1 Analog output in a unit IGS-PTM
IGL-RA15 15 Binary LED output (3 colors) packed in a rugged metal unit IGL-RA15
I-AOUT8 8 Analog outputs packed in a rugged metal unit I-AOUT8
InternetBridge-NT Multiple Internet connections (PC and Modbus) to all controllers on CAN2 or RS485 IB-NT
I-LB+ Direct connection (PC) to all controllers on CAN2 or RS485 I-LB+

Related products
Product Description Order code
InteliVision 5 Color 5.6" display for monitoring and control INTELIVISION 5
InteliVision 8 Color 8" display for advanced monitoring, control & trending, USB capable INTELIVISION 8
InteliVision 12Touch Color 12" touch display for advanced monitoring, control & trending, USB capable RD1IV12TBZH
Color 18“ touchscreen display designed for complete monitoring and control of multiple
InteliVision 18Touch RD31840PBIE
controllers or cogeneration installation.

Functions and protections


ANSI ANSI ANSI ANSI
Description Description Description Description
code code code code
Synchronism Earth fault
25 Excitation loss 40 51N+64 Overfrequency 81H
check current IDMT
Undervoltage 27 Current unbalance 46 Power Factor 55 Underfrequency 81L
Volatage assymetry and Rate of Change of
Overload 32 47 Overvoltage 59 81R
Phase Rotation Frquency
Reverse power 32R Overcurrent 50+51 Fuel 71
Undercurrent 37 Earth Faul Current 50N+64 Vectorshidt 78

Certificates and standards


This product is CE compliant. This product is compliant to:
EN 60068-2-6 ed.2:2008 European Requirements for Generators
EN 60068-2-27 ed.2:2010 VDE-AR-N-4105:2018, VDE-AR-N-4110:2018
EN 60068-2-30, May 2000 G99
EN 61010-1:2003 IEEE 1547-2018