3.6.1 Busduct (Jis)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 29

SECTION

2.4.1

BUSDUCT
(Japan Industrial Standards)

PMM Bldg. S
Taikisha Philippines, Inc.
Lot 2-A, Phase 1-B, First Philippine Industrial Park (FPIP), Tanauan City, Batangas
Doc. No. : NEB-00000

GENERAL SPECIFICATION OF 600V Insulation Type BUSDUCT NISSIN ELECTRIC(THAILAND)CO.,LTD.

SPECIFICATION BS-08-00010

Rated Voltage AC 600V

Phase 3Ph,3ph+N

600A,800A,1000A,1200A,1350A,1500A,1600A,2000A,2500A,3000A,3200A,3500A,4000A,4500A
Rated Current
5000A,6300A

Insulation Level 2500V ( 1 min. )

Applicable Standard IEC 61439-1 , IEC 61439-6, JIS C 8364

Material Conductor 61% Conductivity Aluminium Busbar , 98% Conductivity Copper Busbar

(JISH 4180 Aluminium and Aluminium Alloy Bus Conductor ,JISH3140 Copper Busbar equivalent )

Duct Galvanized Steel Sheet

Coductor Insulation Class B 130℃ Polyester Film (t=0.25mm. 2 layer)

Surface Conductor Conductor connection surface : Tin plating

treatment Duct Polyester powder painting (5Y7/1).

Thickness of Painting : Indoor Type BD : More than 40 µm(Outside of case)

Outdoor Type BD : More than 70 µm(Outside of case)

Temperature Rise Less than 55℃ (AT out side surface of duct) *Ambient Temperature : 40℃

Degree of Outdoor IP 55

Protection Indoor IP 41 or IP 54

Short circuit current( 1sec) 600A 800A 1000A 1200A 1350A-2000A 2500A-3200A 3500A-6300A

40KA 60KA 80KA 100KA 120KA

Acceptance Visual & dimension All inspection data and specification are compared and confirmed.

Inspection Inspection

Insulation The insulation resistance shall be not less than 100MΩ.

Resistance (1000V Insulation resistance tester)

Withstand The busduct shall withstand the test voltage 2500V one minute.

Voltage test
Busduct Catalog
(Standard Dimension)
( Standard Dimension )

Low-voltage Busduct

NET Nissin Electric (Thailand) Co., Ltd.


60/64 Moo 19 Navanakorn2 Phaholyothin road, Klongluang, Phathumthani,
12120, Thailand. Tel. (662) 5290968-70, (662) 5293314-5 Fax. (662) 9087470
Website : http://www.nissin-thai.com E-mail : [email protected]
Cross Section of Bus duct
Indoor Type

ALUMINIUM CONDUCTOR COPPER CONDUCTOR


AMP. WEIGHT AMP. WEIGHT
CONDUCTOR HI CONDUCTOR HI
RATING (Kg/m.) RATING (Kg/m.)
SIZE (mm.) (mm.) SIZE (mm.) (mm.)
(A) 3W 4W (A) 3W 4W
400A 1-t6x50 115 11 13 800A 1-t6x50 115 17 21
600A 1-t6x50 115 11 13 1000A 1-t6x75 125 21 28
800A 1-t6x75 125 13 16 1200A 1-t6x100 150 26 34
1000A 1-t6x100 150 16 20 1350A 1-t6x125 175 37 41
1200A 1-t6x125 175 18 23 1500A 1-t6x125 175 37 41
1350A 1-t6x165 215 22 34 1600A 1-t6x165 215 42 54
1500A 1-t6x165 215 22 34 2000A 1-t6x175 225 44 57
1600A 1-t6x175 225 28 36 2500A 2-t6x125 330 50 65
2000A 1-t10x175 225 30 38 3000A 2-t6x140 350 60 75
2500A 2-t10x125 330 35 45 3200A 2-t6x140 350 60 75
3000A 2-t10x140 350 40 50 3500A 2-t6x175 440 82 98
3200A 2-t10x140 350 40 50 4000A 2-t6x200 490 94 113
3500A 2-t10x175 440 65 80 4500A 3-t6x165 625 126 162
4000A 2-t10x200 490 74 89 5000A 3-t6x175 655 132 171
4500A 3-t10x165 625 84 108 6300A 4-t6x140 690 140 190
5000A 3-t10x175 655 90 114
6300A 4-t10x140 690 90 120

1
Outdoor Type

ALUMINIUM CONDUCTOR COPPER CONDUCTOR


WEIGHT WEIGHT
AMP. CONDUCTOR HO AMP. CONDUCTOR HO
(Kg/m.) (Kg/m.)
RATING (A) SIZE (mm.) (mm.) RATING (A) SIZE (mm.) (mm.)
3W 4W 3W 4W
400A 1-t6x50 165 23 26 800A 1-t6x50 165 29 34
600A 1-t6x50 165 23 26 1000A 1-t6x75 175 33 42
800A 1-t6x75 175 25 30 1200A 1-t6x100 200 39 48
1000A 1-t6x100 200 29 34 1350A 1-t6x125 225 51 56
1200A 1-t6x125 225 32 38 1500A 1-t6x125 225 51 56
1350A 1-t6x165 265 37 50 1600A 1-t6x165 265 57 70
1500A 1-t6x165 265 37 50 2000A 1-t6x175 275 60 73
1600A 1-t6x175 275 44 52 2500A 2-t6x125 380 90 105
2000A 1-t10x175 275 46 54 3000A 2-t6x140 400 100 115
2500A 2-t10x125 380 70 90 3200A 2-t6x140 400 100 115
3000A 2-t10x140 400 80 100 3500A 2-t6x175 490 114 131
3200A 2-t10x140 400 80 100 4000A 2-t6x200 540 128 148
3500A 2-t10x175 490 97 113 4500A 3-t6x165 675 171 210
4000A 2-t10x200 540 108 124 5000A 3-t6x175 705 180 219
4500A 3-t10x165 675 132 156 6300A 4-t6x140 740 190 230
5000A 3-t10x175 705 138 162
6300A 4-t10x140 740 150 200

2
Straight Indoor (S)

A (mm.) L1 (mm.)
CONDUCTOR AMP. RATING (A)
3W 4W STANDARD MINIMUM
ALUMINIUM 400 - 6300
100 130 3000 ,4000 ,5000 500
COPPER 800 - 6300

Vertical Elbow (EL)

A (mm.) L1 (mm.)
CONDUCTOR AMP. RATING (A)
3W 4W STANDARD MINIMUM
400 - 3200 500 450
ALUMINIUM
3500 - 6300 700 650
100 130
800 - 3200 500 450
COPPER
3500 - 6300 700 650

Horizontal Elbow (FL)

A (mm.) L1 (mm.)
CONDUCTOR AMP. RATING (A)
3W 4W STANDARD MINIMUM
ALUMINIUM 400 - 6300
100 130 500 350
COPPER 800 - 6300

3
Vertical Tee (ET)

A (mm.)
AMP. RATING
CONDUCTOR L1 (mm.)
(A) 3W 4W
ALUMINIUM 400 - 5000
100 130 750
COPPER 800 - 6300

Horizontal Elbow (FT)

A (mm.)
AMP. RATING
CONDUCTOR L1 (mm.)
(A) 3W 4W
ALUMINIUM 400 - 5000
100 130 750
COPPER 800 - 6300

Edgewise Offset Elbow (EZ)

AMP. RATING A (mm.) L1 (mm.)


CONDUCTOR
(A) 3W 4W STANDARD MINIMUM
400 - 5000 500 350
ALUMINIUM
6300 700 650
100 130
800 - 5000 500 450
COPPER
6300 700 650

4
Flat wise Offset Elbow (FZ)

A (mm.) L1 (mm.)
CONDUCTOR AMP. RATING (A)
3W 4W STANDARD MINIMUM
400 - 3200 500 450
ALUMINIUM
3500 - 6300 700 650
100 130
800 - 3200 500 450
COPPER
3500 - 6300 700 650

Flat wise + Edgewise Elbow (FL+EL)

CONDUCTO AMP. RATING A (mm.) L1 (mm.) L2 (mm.)


R (A) 3W 4W STANDARD MINIMUM STANDARD MINIMUM
400 - 3200 500 450 500 350
ALUMINIUM
3500 - 6300 700 650 700 550
100 130
800 - 3200 500 450 500 350
COPPER
3500 - 6300 700 650 700 550

5
Expansion 3W (EXP)

Expansion 4W (EXP)

AMP. RATING A (mm.) W1 (mm.)


CONDUCTOR L1 (mm.)
(A) 3W 4W 3W 4W
400 - 3200 245 295
ALUMINIUM
1600 - 6300 100 130 2000 345 425
COPPER 800 - 6300 245 295

3w Plug-in Bus duct (PI) *** Maximum 6 plug-in unit per Busduct 3 meter.

4w Plug-in Bus duct (PI) *** Maximum 6 plug-in unit per Busduct 3 meter.

6
3W Tap-off *** Maximum Tap-off unit per Busduct 3 meter.

4W Tap-off *** Maximum Tap-off unit per Busduct 3 meter.

End Feed-in 3W *** See bus bar holing as per ( page 17)

End Feed-in 4W *** See bus bar holing as per (page 17)

7
ALUMINIUM CONDUCTOR COPPER CONDUCTOR
RATING A RATING A
B C D B C D
(A) 3W 4W (A) 3W 4W
400 115 50 800 115 50
600 115 50 1000 125 75
800 125 75 270 1200 150 100 270
1000 150 100 1350 100 130 175 125
1200 100 130 175 125 1500 175 125
1350 215 165 1600 215 165
1500 215 165 320
320 2000 225 175
1600 215 165
2000 225 175

Center Feed-in

ALUMINIUM CONDUCTOR
RATING A E
B C D F t
(A) 3W 4W 3W 4W
400 115 50
600 115 50
800 125 75 450 350 450 80
1000 150 100 6
1200 100 130 175 125
1350 215 165
1500 215 165
500 400 500 100
1600 215 165
10
2000 225 175

COPPER CONDUCTOR
RATING A E
B C D F t
(A) 3W 4W 3W 4W
800 115 50
1000 125 75
1200 150 100 450 350 450 80
1350 100 130 175 125 6
1500 175 125
1600 215 165
500 400 500 100
2000 225 175

8
Plug-in Switch Unit
3W 4W

BREAKER 3W (mm.) 4W (mm.)


FRAME (AF) A B C A B C
32 ,63
125 200 560 190 250 640 190
250
400 250 680 230 300 740 290
630 250 680 230 300 740 290

Tap-off Switch Unit


3W 4W

BREAKER 3W (mm.) 4W (mm.)


FRAME (AF) A B C A B C
800 320 1000 155 400 1000 165
1000 320 1200 210 400 1200 210

9
Hanger (Edgewise)

WIRE A B C D
3W 100 150 220 260
4W 130 180 250 290

Hanger (Flatwise)

AMP. COPPER CONDUCTOR


RATING A B C D
(A) AMP.
RATING A B C D
400 115 164 235 275
(A)
600 115 164 235 275
800 125 174 245 285 800 115 164 235 275
1000 150 199 270 310 1000 125 174 245 285
1200 175 224 295 335 1200 150 199 270 310
1350 215 264 335 375 1350 175 224 295 335
1500 215 264 335 375 1500 175 224 295 335
1600 215 264 335 375 1600 215 264 335 375
2000 225 274 345 385 2000 225 274 345 385
2500 330 379 450 490 2500 330 379 450 490
3000 350 399 470 510 3000 350 399 470 510
3200 350 399 470 510 3200 350 399 470 510
3500 440 489 560 600 3500 440 489 560 600
4000 490 539 610 650 4000 490 539 610 650
4500 540 589 660 700 4500 540 589 660 700
5000 650 699 770 810 5000 650 699 770 810
6300 690 739 810 850 6300 690 739 810 850

10
Floor Support
Spring type

ALUMINIUM CONDUCTOR
AMP. 3W 4W
RATING D E
A B C A B C
(A)
400 118 178
600 118 178
800 128 188
1000 153 213
1200 178 238
1350 218 278
200 100 74 230 130 104
1500 218 278
1600 218 278
2000 228 288
2500 334 394
3000 354 414
3200 354 414

COPPER CONDUCTOR
AMP. 3W 4W
RATING D E
A B C A B C
(A)
800 118 178
1000 128 188
1200 153 213
1350 178 238
1500 178 238
200 100 74 230 130 104
1600 218 278
2000 228 288
2500 334 394
3000 354 414
3200 354 414

11
Floor Support
Fix type

AMP. 3W (AL) 4W (AL)


RATING (A) A B C D F A B C D F
600A 124 184 124 184
800A 134 194 134 194
1000A 159 219 159 219
1200A 184 244 184 244
1350A 224 284 224 284
1500A 224 180 284 240 72 224 210 284 270 102
1600A 224 284 224 284
2000A 234 294 234 294
2500A 340 400 340 400
3000A 360 420 360 420
3200A 360 420 360 420

AMP. 3W (CU) 4W (CU)


RATING (A) A B C D F A B C D F
800A 124 184 124 184
1000A 134 194 134 194
1200A 159 219 159 219
1350A 184 244 184 244
1500A 184 244 184 244
180 240 72 210 170 102
1600A 224 284 224 284
2000A 234 294 234 294
2500A 340 400 340 400
3000A 360 420 360 420
3200A 360 420 360 420

12
3W Flanged End

13
14
4W Flanged End

15
ALUMINIUM CONDUCTOR COPPER CONDUCTOR
AMP. AMP.
RATING A B C W W1 W2 t RATING A B C W W1 W2 t
(A) (A)
400 185 155 - 50 - - 800 185 155 - 50 - -
600 185 155 - 50 - - 1000 195 165 - 75 - -
800 195 165 - 75 - - 1200 220 190 - 100 - -
1000 220 190 - 100 - - 6 1350 245 215 - 125 - -
1200 245 215 - 125 - - 1500 245 215 - 125 - -
1350 285 255 - 165 - - 1600 285 255 - 165 - -
1500 285 255 - 165 - - 2000 295 265 - 175 - -
1600 285 255 - 165 - - 2500 400 125 120 125 30 - 6
2000 295 265 - 175 - 3000 420 130 130 140 20 -
2500 400 125 120 125 30 - 3200 420 130 130 140 20 -
3000 420 130 130 140 20 - 3500 510 160 160 175 40 -
3200 420 130 130 140 20 - 4000 560 175 180 200 40 -
10
3500 510 160 160 175 40 - 4500 695 220 225 165 40 -
4000 560 175 180 200 40 - 5000 725 230 235 175 40 -
4500 695 220 225 165 40 - 6300 760 182.5 182.5 140 40 20
5000 725 230 235 175 40 -
6300 760 182.5 182.5 140 40 20

16
Bus Bar Holing

ALUMINIUM CONDUCTOR COPPER CONDUCTOR


AMP. AMP.
PIC PIC
RATING W W1 W2 F RATING W W1 W2 F
TURE TURE
(A) (A)
400 50 - - - 800 50 - - - 1
1
600 50 - - - 1000 75 - - 40
2
800 75 - - 40 1200 100 - - 50
2
1000 100 - - 50 1350 125 - - 40
3
1200 125 - - 40 3 1500 125 - - 40
1350 165 - - 50 1600 165 - - 50
4
1500 165 - - 50 2000 175 - - 50
4
1600 165 - - 50 2500 125 30 - 50 5
2000 175 - - 50 3000 140 20 - 50 6
2500 125 30 - 50 5 3200 140 20 - 50 6
3000 140 20 - 50 6 3500 175 40 - 50 7
3200 140 20 - 50 6 4000 200 40 - 50 8
3500 175 40 - 50 7 4500 165 40 - 50 9
4000 200 40 - 50 8 5000 175 40 - 50 10
4500 165 40 - 50 9 6300 140 40 20 50 11
5000 175 40 - 50 10
6300 140 40 20 50 11

17
Minimum Installation Space Between Bus duct
Feeder Bus duct

Plug-in Bus duct

INSTALLATION X S INSTALLATION S
HORIZONTAL RUN 120 HORIZONTAL RUN
W+X A2 + 50
VERTICAL RUN 170 VERTICAL RUN

Expantion Bus duct

INSTALLATION S
HORIZONTAL RUN
A1/2 + W2 + 100
VERTICAL RUN

***Dimension W : refer to dimension table of Cross Section of Bus duct (page 1-2)

***Dimension A1 ,A2 : refer to drawing of Expension Bus duct (page 6) Plug-in Switch (page 6)

18
CL

CL
CL

CL
CL
CL

CL

CL

CL

CL
CL
CL

CL

CL

1 SECOND FLOOR PRODUCTION AREA PLAN

PROJECT TITLE: OWNER : REV. NO. DESCRIPTION CADD DATE SHEET CONTENT/S: SHEET NO.
CADD BY: A. RANCUDO
DATE:
MICHAEL DG BASCOS
PROFESSIONAL ELECTRICAL ENGINEER
MURATA FACTORY-S AND PHILIPPINE MANUFACTURING CO. CHECKED BY: G. VILLAPANDO SECOND FLOOR PRODUCTION E-03
PRC NO: 4253 PTR NO: 25769650
RELATED BUILDING OF MURATA INC. DATE:
AREA PLAN

TAIKISHA PHILIPPINES INC. TIN NO: 304-608-897 ISSUED AT: STO TOMAS MR. MIKITO YAMADA APPROVED BY: M. UCHIDA REV. DATE:

ISSUED ON: 01.08.2020 LOT 2-A, PH1B, FIRST PHILIPPINE INDUSTRIAL PARK (FPIP), TANAUAN CITY, BATANGAS GENERAL MANAGER DATE: FOR CONSTRUCTION
FILE PATH: C:\USERS\ALFIE RANCUDO\DESKTOP\FROM USB\3. REVISED FOR ENGINEER KRISTINE\9. SEPTEMBER 28,2020\CAD\E-03 SECOND FLOOR PRODUCTION AREA_WITH PIPE RACK LAYOUT; PLOT: 10/13/2020 9:57:02 am LAST SAVED: Alfie