Moeller Datasheet DILET11-M-A 048886
Moeller Datasheet DILET11-M-A 048886
Moeller Datasheet DILET11-M-A 048886
Ordering information
Description Timing relays, On−delayed
Rated operational current AC−11
220 V 230 V 240 V Ie A 3
380 V 400 V 440 V Ie A 3
Conventional thermal current Ith A 6
0.15 – 3 s
0.5 – 10 s
3 – 60 s
u0.15 – 3 min
Time range 0.5 – 10 min
3 – 60 min
0.15 – 3 h
0.5 – 10 h
3 – 60 h
fixed
Function
11, On−delayed
1
Notes concerning the product group
Accessories Page
Time functions Engineering
Sealable shroud 010482
Potentiometer 229491
Screw adapter 095853
Blade terminals 059904
General
IEC/EN 60947, VDE 0660,
Standards UL, CSA
IEC/EN 60255, VDE 0435
Lifespan, mechanical
AC operated Operations × 106 30
DC operated Operations × 106 30
Damp heat, constant, to IEC
60068−2−78;
Climatic proofing
Damp heat, cyclic, to IEC
60068−2−30
Ambient temperature
Open °C –20...60
Enclosed °C –20...45
Mounting position As required
2
Mechanical shock resistance (IEC/EN
60068−2−27)
Half−sinusoidal shock, 20 ms
Make contact g 4
Degree of protection
Terminals IP 20
Weight kg 0,09
Terminal capacities
1 × (0.75 – 2.5)
Solid mm2
2 × (0.75 – 2.5)
1 × (0.75 – 1.5)
Flexible with ferrule mm2
2 × (0.75 – 1.5)
Solid or stranded AWG 1 × (18 – 14)
Contacts
Rated impulse withstand voltage Uimp V AC 6000
Overvoltage category/pollution
III/2
degree
Rated insulation voltage Ui V AC 600
Rated operational voltage Ue V AC 440
Safe isolation to VDE 0106 Part 101
and Part 101/A1
between coil and auxiliary contacts V AC 250
between the auxiliary contacts V AC 250
Making capacity
AC−14 cos = 0.3 440 V A 48
AC−15 cos = 0.3 220 V A 50
DC−11 L/R – 40 ms × Ie 1,1
Breaking capacity
AC−14 cos = 0.3 440 V A 3
AC−15 cos = 0.3 220 V A 3
DC−11 L/R – 40 ms × Ie 1,1
Rated operational current
AC–−14
440 V Ie A 3
AC−15
220 V Ie A 3
DC–11
L/R max. 15 ms
24 V Ie A 1,5
L/R max. 50 ms A 1,2
3
Conv. thermal current Ith A 6
Short−circuit rating without welding
A
Max. fuse, make contacts 6
gG/gL
A
Max. fuse, break contacts 6
gG/gL
Magnet systems
Power consumption
Pick−up AC VA 2
Sealing AC VA 2
Pick−up DC W 1,8
Sealing DC W 1,8
Duty factor % DF 100
Maximum operating frequency Ops/h 4000
Minimum command time
AC ms 50
DC ms 30
Repetition accuracy (deviation) % 0,5
Recovery time (after 100% time
ms 70
delay)
Notes
Making and breaking
conditions to DC−13, time
constant as stated
When supplied directly from
Notes
mains or transformer > 1000
VA
Not DILET...−W
ETR4−51: 50 ms
Dimensions
DILET...
4
Dimensions
DILET... + HDILE
Electronic timing relay with sealable shroud
Characteristic curve