Guide For The Design and Production of LV Power Factor Correction Cubicles

Download as pdf or txt
Download as pdf or txt
You are on page 1of 76
At a glance
Powered by AI
The document discusses guidelines for the design and production of LV power factor correction cubicles including applicable standards, effects of harmonics, component selection and specifications, installation rules, assembly, inspection, testing, handling, installation, commissioning and maintenance procedures.

The main components discussed include capacitors, detuned reactors, contactors, switching and protection devices, power factor controllers, CT and protection devices.

The factors that need to be considered for the design of LV compensation cubicles include the compensation modules, detuned reactors, ventilation, power factor controller, and the low voltage network characteristics.

Power Factor Correction

Guide for the Design and Production of LV Power Factor Correction Cubicles
Panel Builder Guide 2011

Panel Builder Guide 2011

Contents

CHAPTER 1: General design rules

3 - 11

Applicable standards and definitions Reactive Energy Guidelines Effects of Harmonics

CHAPTER 2: Component Selection Guide


Capacitor Rated Voltage and Current of Capacitor Capacitors selection based on operating conditions Offer overview VarplusCan/VarplusBox

12 - 42
12 - 21

Detuned Reactors
Detuned reactors overview Capacitor Rated Voltage with Detuned Reactors Choice of Detuned Reactor Tuning Frequency Offer overview- Detuned reactors

22 - 27

Contactors Offer overview TeSys D Contactors Parallel Operation of Capacitors and Inrush Current Limiting Varlogic N Power Factor Controller Physical and Electrical control of PFC relay CT and Protection Devices Current Transformer Protection Devices in APFC Panels Switchgear and fuse selection Capacitor General Installation rules Installation rules - VarplusCan and VarplusBox Installation rules - VarplusBox Compact

28 - 30 31 - 32 33 - 37 38 - 42

Switching and Protection Devices Power Factor Controller

CHAPTER 3: Installation Rules


43 - 55
43 - 45

Detuned Reactors

APFC Panels Maximum kvar per step in APFC Panel Installation rules - APFC Panels Ventilation for capacitor banks Protection of panels Cable selection

46 47 - 55

CHAPTER 4: Assembly, Inspection and Testing


Assembly and Inspection The means The tests Packaging and transport Storage and handling

56 - 61

CHAPTER 5: Handling

62 - 64

CHAPTER 6: Installation, Commissioning and Maintenance 65 - 67


Pre-Commissioning check lists Installation guidelines for APFC Panels Commissioning of APFC Panel

ANNEXURE

68 - 70

Annexure 1: Trouble shooting in capacitor Annexure 2: Important analysis formulas

Design of LV compensation cubicle


In addition to the rules and standards, production of electrical switchboards for the LV compensation requires consideration of specific constraints.

1- The compensation modules The VarplusCan and VarplusBox capacitors Their positioning must ensure proper ventilation. Their sizing must take into account ambient conditions (harmonics, temperature, etc) The contactors They must be suited to capacitor control. Schneider Electric has designed and tested specific contactors for this application.Their control voltage must be monitored in order to prevent rapid reclosing.

2- The detuned reactors (DR) They must be chosen according to harmonic stresses and installed in order to avoid, as far as possible, capacitor temperature rise.
The DR temperature sensor must be connected so that the step can be disconnected if the temperature is too high

Key points discussed in the document

3- Ventilation It must be efficient in order to keep operating temperature lower than maximum permissible temperature of components.

4- The power factor controller Its functions must be adapted to the capacitor bank characteristics: number and power of steps, sequence, etc. The time delay must be adapted to capacitor discharge time.

5- Low voltage network Network characteristics, and in particular network harmonic distortion, must absolutely be taken into account when choosing capacitors and detuned reactors (if any). 6- Tests to be done after production of the bank At the end of the manufacturing process, a LV switchboard must undergo various routine inspections and tests in the factory, following an established programme. The switchboard must comply with : the appropriate standards the design file (drawings, diagrams and specific requirements) manufacturer mounting instructions in-house instructions. 7- Maintenance must be done every year One month after energising, check all contactor terminal tightening torques. Annual checks General cleanliness of the equipment Filters and ventilation system Terminal tightening torques Proper working order of switching and protective devices Temperature in the premises: -5 C to +40 c max - for normal designs Capacitor capacitance: Consult us if the capacitance value has changed by more than 10 %.

General Design Rules

Applicable standards and definitions


Applicable Standards
IEC: 61921 (Power Capacitors- Low voltage power factor correction banks) is the international standard applicable for Low Voltage Power Factor Correction Banks and Automatic Power Factor Correction (APFC) equipments intended to be used for power factor correction purposes, equipped with built in switch gears and control gears. The guidelines for design, installation, operation and safety of APFC panels are followed based on this international standard. The design of the Low Voltage Power Factor Correction banks and accessories shall comply with the following standards IEC60831: Part 1 & 2-Shunt power capacitors of the self healing type for a.c systems having rated voltage up to and including 1kV. IEC 60439-3: Low voltage switchgear and control gear assemblies. Particular requirements for low-voltage switchgear and control gear assemblies intended to be installed in places where unskilled persons have access for their use-Distribution boards. IEC 60947: Low Voltage Switchgear Part 2: Molded Case Circuit Breakers & Air circuit Breakers Part 4: Power Contactors Part 4-3: Thyristor Switch IEC 60269: LV Fuses IEC 60076-6 : Reactors IEC 60529: Degree of protection provided by enclosure (IP code) IEC 60044-1: Current transformers. IEC 60664-1 / IEC 61326: Power Factor Controller.

Definitions

The design of the APFC equipment involves the following major parts and the selection of these depends very much on the above system conditions.

Enclosure: protects the APFC system components against the external solid or liquid particles and also provide protection for human beings. PFC Controller: Is the brain of the APFC system, which switches ON / OFF the steps depending on the kvar required in order to maintain the PF close to unity. Bus bars: Bus bar is the electrical conducting path, to which all
the components in the APFC system are connected.

Switchgears: Switchgears are the devices which control the

circuit under faulty and normal conditions. Switchgears protect the APFC system against faulty conditions.

Cables: Cables are used to connect various components

in the steps. Proper cable sizing has to be considered for a particular step depending on the rated current and the operating temperature in order to link the various components of the system. Cables loop the power circuit & control circuit in the system.

General Design Rules

Protection devices: Protection has to be provided to safeguard the capacitors and other components due to abnormalities in the system. The incoming switchgear of the APFC system should be tripped by protective devices. Reactors: Reactors are used in steps as detuned filters and are connected in series with capacitors. It must be designed to withstand fundamental and harmonic currents. Capacitors: Capacitors forms the core component in APFC
equipment and plays a vital role in power factor correction. Proper selection of capacitors is very much necessary to comply with the applications.

Note: The above components are explained further in details

Glossary
SFU SDF ACB MCCB HRC SMC DMC : Switch Fuse Unit : Switch Disconnector and Fuse Unit : Air Circuit Breaker : Molded Case Circuit Breaker : High Rupture Capacity Fuse : Sheet Molding Compound : Dough Molding Compound

General Design Rules

Reactive Energy Guidelines

DE90087.eps

All AC electrical networks consume two types of power: active power (kW) and reactive power (kvar): The active power P (in kW) is the real power transmitted to loads such as motors, lamps, heaters, computers The electrical active power is transformed into mechanical power, heat or light. The reactive power Q (in kvar) is used only to supply the magnetic circuits of machines, motors and transformers. The apparent power S (in kVA) is the vector combination of active and reactive power. In this representation, the Power Factor (P/S) is equal to cos. The circulation of reactive power in the electrical network has major technical and economic consequences. For the same active power P, a higher reactive power means a higher apparent power and thus, a higher current must be supplied. - The circulation of active power over time is resulting in active energy (in kWh). - The circulation of reactive power over time is resulting in reactive energy (kvarh).

Principle of reactive energy management

DE90071_r.eps

- In an electrical circuit, the reactive energy is supplied in addition to the active energy.
Power generation
Active energy

Reactive energy

Transmission network

Active energy

Motor
Reactive energy

Due to this higher supplied current, circulation of reactive energy on distribution networks results in: Overload of transformers, Higher temperature rise of the supply cables, Additional losses, Large voltage drops, Higher energy consumption and cost, Less distributed active power. For these reasons, there is a great advantage to generate reactive energy at the load level in order to prevent the unnecessary circulation of current in the network. This is what is known as Power Factor Correction. This is obtained by the connection of capacitors, which produce reactive energy in opposition to the energy absorbed by loads such as motors. The result is a reduced apparent power, and an improved power factor P/S as illustrated on the diagram on the left. The power generation and transmission networks are partially relieved, reducing power losses and making additional transmission capability available. The reactive power is supplied by capacitors. No billing of reactive power by the energy supplier.

Reactive energy supplied and billed by the energy supplier


Power generation
DE90088.eps

Active energy

Transmission network

Active energy

Motor
Reactive energy

Capacitors

Qc
Active energy Active energy

Power generation

Reactive energy

Transmission network

Motor
Reactive energy

DE90071_r.eps

Power generation

Active energy

Transmission network

Active energy

Motor
Reactive energy

Capacitors

General Design Rules

Benefits of reactive energy management


Optimized management of reactive energy brings economic and technical advantages.

Savings on the electricity bill:


Eliminating penalties on reactive energy and decreasing kVA demand, Reducing power losses generated in the transformers and conductors of the installation. Example: Loss reduction in a 630 kVA transformer PW = 6,500 W with an initial Power Factor = 0.7. With power factor correction, we obtain a final Power Factor = 0.98 The losses become: 3,316 W, i.e. a reduction of 49%.

Increasing available power:


Power factor Increased available power 0.7 0.8 0.85 0.90 0.95 1 0% +14% +21% +28% +36% +43%

A high power factor optimizes an electrical installation by allowing a better usage of the components. The power available at the secondary of an MV/LV transformer can therefore be increased by fitting power factor correction equipment at the low voltage side. The table shows the increased available power at the transformer output by improvement of Power Factor from 0.7 to 1.

Power factor 1 0.80 0.60 0.40

Cable cross-section multiplying factor 1 1.25 1.67 2.50

Reducing the installation size


Installing power factor correction equipment allows the conductors cross-section to be reduced, since less current is absorbed by the compensated installation for the same active power. The table in the left shows the multiplying factor for the conductor cross-section according to the different values of power factor.

Reducing the voltage drops on installation


Installing capacitors allows the voltage drops to be reduced upstream of the point where the power factor correction device is connected. It avoids the overload of the network and allows the diminution of harmonics so that no overrating of the installation is necessary.
Reduction in electricity bill Reduction in kvar Demand Reduction in kVA Demand Reduction in Line Current Reduction in Transformer Rating Reduced Loading on Transformer

Reduction in Switchgear rating Reduction in Line losses / Cable losses Improvement in voltage regulations

General Design Rules

Power Factor Correction guidelines

The selection of the Power Factor Correction equipment can follow a 4-step process:

1. Calculation of the requested reactive energy, 2. Selection of the compensation mode:


Global, for the complete installation, By sectors, For individual loads, such as large motors.

3. Selection of the compensation type:


Fixed, by connection of a fixed-value capacitor bank, Automatic, by connection of different number of steps, allowing the adjustment of the reactive energy to the requested value, Dynamic, for compensation of highly fluctuating loads.

4. Taking account of operating conditions and harmonics

Power Factor Correction guidelines

Calculation of Reactive Energy Based on the Application


Power Factor Correction for Transformer no-load compensation
The transformer works on the principle of Mutual Induction. The transformer will consume reactive power for magnetizing purpose. Following equivalent circuit of transformer provides the details of reactive power demand inside the transformer:
kVA rating of Transformer Upto and including 2000 kVA kvar required for No-Load compensation 2% of kVA rating

Leakage reactance reactive power = Z % x Transformer rating Transformer

Xo1 Xo Ro

Ro1 Load

No Load reactive Power = 2% of Transformer rating

Power Factor Correction where Load and present Power Factor is Known
The objective is to determine the requested reactive power QC (kvar) to be installed, in order to improve the power factor cos and reduce the apparent power S.

DE90088.eps

Qc

For < , well get: cos > cos and tan < tan. This is illustrated on the diagram in the left. QC can be determined from the formula: QC = P. (tan - tan), which is deduced from the diagram. QC : power of the capacitor bank, in kvar P : active power, in kW tan: tangent of the phase angle - before compensation, tan: tangent of the phase angle - after compensation The parameters and tan can be obtained from the billing data, or from direct measurement in the installation. The following table can be used for direct determination.
Before compensation tan cos 1.73 1.02 0.96 0.91 0.86 0.80 0.75 0.70 0.65 0.59 0.54 0.48 0.5 0.7 0.72 0.74 0.76 0.78 0.8 0.82 0.84 0.86 0.88 0.9 Reactive power (kvar) to be installed per kW of load, in order to get the requested tan or cos tan 0.75 0.62 0.48 0.41 0.33 0.23 0.00 cos 0.8 0.85 0.9 0.925 0.95 0.975 1.00 0.98 0.27 0.21 0.16 0.11 0.05 1.11 0.40 0.34 0.29 0.24 0.18 0.13 0.08 0.03 1.25 0.54 0.48 0.42 0.37 0.32 0.27 0.21 0.16 0.11 0.06 1.32 0.61 0.55 0.50 0.44 0.39 0.34 0.29 0.24 0.18 0.13 0.07 1.40 0.69 0.64 0.58 0.53 0.47 0.42 0.37 0.32 0.26 0.21 0.16 1.50 0.79 0.74 0.68 0.63 0.57 0.52 0.47 0.42 0.37 0.31 0.26 1.73 1.02 0.96 0.91 0.86 0.80 0.75 0.70 0.65 0.59 0.54 0.48

Note: It is widely accepted to use a thumb rule that Motor compensation required in kvar is equal to 33% of the Motor Rating in HP. But it is always suggested to check the name plate of a motor and find out the kvar required using the above mentioned method (using the above table) for accurate compensation.

Example: Consider one 1000kW motor with cos 0.8 (tan = 0.75). In order to get cos= 0.95, it is necessary to install a capacitor bank with a reactive power equal to k x P, i.e. : Qc = 0.42 x 1000 = 420 kvar

Power Factor Correction guidelines

Selection of the compensation mode

Supply Bus

Transformer

The location of low-voltage capacitors in an installation constitutes the mode of compensation, which may be global (one location for the entire installation), by sectors (section-by-section), at load level, or some combination of the latter two. In principle, the ideal compensation is applied at a point of consumption and at the level required at any instant. In practice, technical and economic factors govern the choice. The place for connection of capacitor banks in the electrical network is determined by: Global objective (avoid penalties on reactive energy, relieve of transformer or cables, avoid voltage drops and sags), Operating mode (stable or fluctuating loads), Foreseeable influence of capacitors on the network characteristics, Installation cost.

Circuit breaker

CC

GC IC M M IC IC M

GC IC M

Global compensation
The capacitor bank is connected at the head of the installation to be compensated in order to provide reactive energy for the whole installation. This configuration is convenient for stable and continuous load factor.

CC : Central Compensation GC : Group Compensation IC : Individual Compensation M : Motor Load

Compensation by sectors
The capacitor bank is connected at the head of the feeders supplying one particular sector to be compensated. This configuration is convenient for a wide installation, with workshops having different load factors.

Compensation of individual loads


The capacitor bank is connected right at the inductive load terminals (especially large motors). This configuration is well adapted when the load power is significant compared to the subscribed power. This is the technical ideal configuration, as the reactive energy is produced exactly where it is needed, and adjusted to the demand.

Power Factor Correction guidelines

Selection of the compensation type

Different types of compensation shall be adopted depending on the performance requirements and complexity of control: Fixed, by connection of a fixed-value capacitor bank, Automatic, by connection of different number of steps, allowing the adjustment of the reactive energy to the requested value, Dynamic, for compensation of highly fluctuating loads.

Fixed compensation
This arrangement uses one or more capacitor(s) to provide a constant level of compensation. Control may be: Manual: by circuit-breaker or load-break switch, Semi-automatic: by contactor, Direct connection to an appliance and switched with it. These capacitors are applied: At the terminals of inductive loads (mainly motors), At bus bars supplying numerous small motors and inductive appliances for which individual compensation would be too costly, In cases where the load factor is reasonably constant.

Automatic compensation
This kind of compensation provides automatic control and adapts the quantity of reactive power to the variations of the installation in order to maintain the targeted cos . The equipment is applied at points in an installation where the active-power and/or reactivepower variations are relatively large, for example: At the busbars of a main distribution switch-board, At the terminals of a heavily-loaded feeder cable. Where the kvar rating of the capacitors is less than, or equal to 15% of the supply transformer rating, a fixed value of compensation is appropriate. Above the 15% level, it is advisable to install an automatically-controlled bank of capacitors. Control is usually provided by contactors. For compensation of highly fluctuating loads, fast and highly repetitive connection of capacitors is necessary, and static switches must be used.

Dynamic compensation
This kind of compensation is requested when fluctuating loads are present, and voltage fluctuations should be avoided. The principle of dynamic compensation is to associate a fixed capacitor bank and an electronic var compensator, providing either leading or lagging reactive currents. The result is a continuously varying and fast compensation, perfectly suitable for loads such as lifts, crushers, spot welding

10

Power Factor Correction guidelines

Effects of Harmonics

Harmonics in electrical installations


The presence of harmonics in electrical systems means that current and voltage are distorted and deviate from sinusoidal waveforms. Harmonic currents are currents circulating in the networks and which frequency is an integer multiple of the supply frequency. Harmonic currents are caused by non-linear loads connected to the distribution system. A load is said to be non-linear when the current it draws does not have the same waveform as the supply voltage. The flow of harmonic currents through system impedances in turn creates voltage harmonics, which distort the supply voltage. The most common non-linear loads generating harmonic currents are using power electronics, such as variable speed drives, rectifiers, inverters, etc. Loads such as saturable reactors, welding equipment, arc furnaces, also generate harmonics. Other loads such as inductors, resistors and capacitors are linear loads and do not generate harmonics.

Influence of Harmonics in Capacitors


Capacitors are particularly sensitive to harmonic currents since their impedance decreases proportionally to the order of the harmonics present. This can result in a capacitor overload, shortening steadily its operating life. In some extreme situations, resonance can occur, resulting in an amplification of harmonic currents and a very high voltage distortion. Amplification of Harmonic currents is very high when the natural resonance frequency of the capacitor and the network combined happens to be close to any of the harmonic frequencies present. This situation could result in severe over voltages and overloads which will lead to premature failure of capacitors To ensure a good and proper operation of the electrical installation, the harmonic level must be taken into account in the selection of the power factor correction equipment. A significant parameter is the cumulated power of the non-linear loads generating harmonic currents.
Equipment Motor Transformer Switch gear and cables Capacitors Protective Relays Power electronic equipment Control & instrumentation Electronic equipment Communication equipment / PCs Neutral cable Telecommunication equipment Effect of Harmonics Over heating, production of non-uniform torque,increased vibration Over heating and insulation failure, noise Neutral link failure, increased losses due to skin effect and over heating of cables Life reduces drastically due to harmonic overloading Malfunction and nuisance tripping Misfiring of Thyristors and failure of semiconductor devices Erratic operation followed by nuisance tripping and breakdowns Interference

Higher Neutral current with 3rd harmonic frequency, Neutral over heating and or open neutral condition Telephonic interference, malfunction of sensitive electronics used, failure of telecom hardware

11

Component General Design Rules Selection guide Capacitors

Rated voltage and current of Capacitor


According to IEC 60831-1 standard, the rated voltage (UN) of a capacitor is defined as the continuously admissible operating voltage. The rated current (IN) of a capacitor is the current flowing through the capacitor when the rated voltage (UN) is applied at its terminals, supposing a purely sinusoidal voltage and the exact value of reactive power (kvar) generated. Capacitor units shall be suitable for continuous operation at an r.m.s. current of (1.3 x IN). In order to accept system voltage fluctuations, capacitors are designed to sustain over-voltages of limited duration. For compliance to the standard, capacitors are for example requested to sustain over-voltages equal to 1.1 times UN, 8h per 24h. VarplusCan and VarplusBox capacitors have been designed and tested extensively to operate safely on industrial networks. The design margin allows operation on networks including voltage fluctuations and common disturbances. Capacitors can be selected with their rated voltage corresponding to the network voltage. For different levels of expected disturbances, different technologies are proposed, with larger design margin for capacitors adapted to the most stringent working conditions (HDuty & Energy)
CAUTION: the life expectancy will be reduced if capacitors are used at the maximum level of the working conditions.

12

Component General Design Rules Selection guide Capacitors

Capacitor Selection Based on operating conditions


The operating conditions have a great influence on the life expectancy of capacitors. For this reason, different categories of capacitors, with different withstand levels, must be selected according to operating conditions. Capacitors must be selected in function of the following parameters: Ambient Temperature (C), Expected over-current, related to voltage disturbances, including maximum sustained over voltage, Maximum number of switching operations/year, Requested life expectancy. Capacitors are particularly sensitive to harmonics. Depending on the magnitude of harmonics in the network, different configurations shall be adopted. Different ranges with different levels of ruggedness are proposed: SDuty: Standard duty capacitors for standard operating conditions, and when no significant non-linear loads are present. HDuty: Heavy duty capacitors for difficult operating conditions, particularly voltage disturbances, or when a few non-linear loads are present. The rated current of capacitors must be increased in order to cope with the circulation of harmonic currents. Energy: Specially designed capacitors, for harsh operating conditions, particularly high temperature. Capacitors with detuned reactors: applicable when a significant number of non-linear loads are present. Tuned filters: when non-linear loads are predominant, requesting harmonic mitigation. A special design is generally necessary, based on on-site measurements and computer simulations of the network. Since the harmonics are caused by non-linear loads, an indicator for the magnitude of harmonics is the ratio of the total power of non-linear loads to the supply transformer rating. This ratio is noted NLL, and is also known as Gh/Sn: NLL = Total power of non-linear loads (Gh) Installed transformer rating (Sn)

DB121413.eps

Example: Supply transformer rating: Sn = 630 kVA Total power of non-linear loads: Gh = 150 kVA NLL= (150/630) x 100 = 24%

13

Component General Design Rules Selection guide Capacitors

Capacitor selection taking account of harmonics


Supply transformer Measure THDi, THDu

The percentage of non-linear loads NLL is a first indicator for the magnitude of harmonics. The proposed selection of capacitors depending on the value of NLL is given in the diagram below.
NLL (%)
SDuty HDuty Energy

DE90182.eps

10

20

25

50

Linear loads

Non-linear loads

HDuty Energy (with detuned reactor)

A more detailed estimation of the magnitude of harmonics can be made with measurements. Significant indicators are current harmonic distortion THDi and voltage harmonic distortion THDu, measured at the transformer secondary, with no capacitors connected. According to the measured distortion, different technologies of capacitors shall be selected:
THDi (%)
SDuty HDuty Energy HDuty Energy (with detuned reactor)

10

20

THDu (%)
SDuty HDuty Energy HDuty Energy (with detuned reactor)

Note: The capacitor technology has to be selected according to the most restrictive measurement. Example, a measurement is giving the following results : - THDi = 15 % Harmonic solution. - THDu = 3.5 % HDuty / Energy solution. HDuty or Energy with Detuned Reactor has to be selected.

14

Component General Design Rules Selection guide Capacitors

Solution SDuty

Description Standard capacitor

Recommended use for Networks with non significant non-linear loads Standard over-current Standard operating temperature Normal switching frequency Standard life expectancy Few non-linear loads Significant over-current Standard operating temperature Significant switching frequency Long life expectancy Significant number of non-linear loads (up to 25%) Significant over-current Extreme temperature conditions Very frequent switching Extra long life expectancy High level of non-linear loads (up to 30%) Significant over-current Standard operating temperature Significant switching frequency Long life expectancy High level of non-linear loads (up to 30%) Significant over-current Extreme temperature conditions Very frequent switching Extra long life expectancy

Max. condition NLL 10% 1.5 IN 55C (class D) 5,000/year Up to 100,000 h* NLL 20% 1.8 IN 55C (class D) 7,000/year Up to 130,000 h* NLL 25% 1.5 IN 70C 10,000/year Up to 160,000 h* NLL 30% 1.8 IN 55C (class D) 7,000/year Up to 130,000 h* NLL 30% 2.5 IN 70C (class D) 10,000/year Up to 160,000 h*

HDuty

Heavy-duty capacitor

Energy HDuty + Detuned Reactor

Capacitor for special conditions Heavy-duty, harmonic rated capacitor + detuned reactor Energy, harmonic rated capacitor + detuned reactor

Energy + Detuned Reactor

*The maximum life expectancy is given considering standard operating conditions: service voltage(UN), service current(IN), 35C ambient temperature. WARNING: The life expectancy will be reduced if capacitors are used in maximum working conditions.

15

Component General Design Rules Selection guide Capacitors

Offer Overview VarplusCan


Robustness
Easy installation & maintenance Optimized design for low weight, compactness and reliability to ensure easy installation. Unique termination system that allows maintained tightening. 1 point for mounting and earthing. Vertical and horizontal position in case of Heavy Duty.

Aluminum can capacitors specially designed and engineered to deliver a long working life with low losses in standard, heavy-duty and severe operating conditions. Suitable for Fixed and Automatic PFC, real time compensation, detuned and tuned filters..

Safety
Self-healing. Pressure-sensitive disconnector on all three phases. Discharge resistors fitted. Finger-proof CLAMPTITE terminals to reduce risk of accidental contact and to ensure firm termination (10 to 30 kvar). Special film resistivity and metallization profile for higher thermal efficiency, lower temperature rise and enhanced life expectancy.
PE90131

Compacity
Optimized geometric design (small dimensions and low weight).

Features
High life expectancy up to 160,000 hours. Very high overload capabilities and good thermal and mechanical properties. Economic benefits due to its compact size. Easy maintenance. Unique finger proof termination to ensure tightening.
Construction Voltage range
PE90132

VarplusCan

SDuty 230 V -525 V 1 - 30 kvar Up to 200 x IN

HDuty 230 V -830 V 5 - 50 kvar Up to 250 x IN

Energy 400 V - 525 V 5 -15 kvar Up to 350 x IN

Extruded aluminium can

Power range (three-phase) Peak inrush current Over voltage Over current
PE90130

1.1 x UN 8h every 24 h 1.5 x IN Up to 100,000 h 1.8 x IN Up to 130,000 h 2.5 x IN Up to 160,000 h

PE90131

Mean life expectancy Safety Dielectric

Self-healing + pressure-sensitive disconnector + discharge device (50V/1min) Metallized Polypropylene film with Zn/Al alloy Metallized Polypropylene film with Zn/Al alloy with special profile metallization and wave cut Double metallized paper + Polypropylene film

Impregnation Non-PCB, Non-PCB, sticky Non-PCB, oil Biodegradable (dry) Biodegradable resin resin Ambient temperature Protection Mounting Terminals min -25C to max 55C IP20, indoor Upright Upright, Horizontal Upright Double fast-on + cable ( < 10 kvar) CLAMPTITE - Three-phase terminal with electric shock protection(finger proof) STUD TYPE for more than 30 kvar min -25C to max 70C

16

Component General Design Rules Selection guide Capacitors

VarplusCan
Technical Specifications

General characteristics Standards Frequency Losses (dielectric) Losses (total) Capacitance tolerance Voltage Between terminals test Between terminal & Container Discharge resistor Working Conditions Humidity Altitude Over voltage Switching SDuty Operations HDuty Energy Mean Life expectancy Harmonic SDuty Content HDuty Energy Installation characteristics Mounting SDuty position HDuty Energy Fastening & Earthing Indoor, Upright Indoor, Upright & horizontal Indoor, Upright Threaded M12 stud at the bottom IEC 60831-1/-2 50/60Hz < 0.2W/kvar < 0.5W/ kvar - 5%, +10% 2.15 x UN (AC), 10s < 660V - 3 kV(AC), 10s > 660V - 6kV(AC). 10s Fitted, standard discharge time 60s Discharge time 180s on request

95% 2.000 m above sea level 1.1 xUN 8h in every 24h Up to 5,000 switching operations per year Up to 7,000 switching operations per year Up to 10,000 switching operations per year Up to 1,60,000 hrs NLL < 10 % NLL < 20 % NLL < 25 %

Safety Features Safety Self-healing + Pressure-sensitive disconnector for each phase + Discharge device

17

Component General Design Rules Selection guide Capacitors

Offer Overview VarplusBox


Double metallic protection. Mechanically well suited for stand-alone installations.

VarplusBox capacitors deliver reliable performance in the most severe application conditions, in Fixed & Automatic PFC systems, in networks with frequently switched loads and harmonic disturbances.

Robustness

Safety
Its unique safety feature electrically disconnects the capacitors safely at the end of their useful life. The disconnectors are installed on each phase, which makes the capacitors very safe, in addition to the protective steel enclosure.

PE90135

Flexibility
These capacitors can be easily mounted inside panels or in a standalone configuration. Suitable for flexible bank configuration.

Features
Metal box enclosure. High power ratings up to 100 kvar. Easy repair and maintenance. Up to 70C temperature. High inrush current withstand up to 400 x IN. Stand-alone PFC equipment. Direct connection to a machine, in harsh environmental conditions.
Construction Voltage range Power range (three-phase) Peak inrush current Over voltage Over current
PE90164

VarplusBox

SDuty 380 V - 480 V 7.5 - 100 kvar Up to 200 x IN

HDuty 230 V - 830 V 2.5 - 100 kvar Up to 250 x IN

Energy 380 V - 525 V 7.5 - 100 kvar Up to 350 x IN

Steel sheet enclosure

1.1 x UN 8 h every 24 h 1.5 x IN Up to 100,000 h 1.8 x IN Up to 130,000 h 2.5 x IN Up to 160,000 h

Mean life expectancy Safety


PE90137

Self-healing + pressure-sensitive disconnector + discharge device (50V/1min) Metallized Polypropylene film with Zn/Al alloy Metallized Polypropylene film with Zn/Al alloy with special profile metallization and wave cut Double metallized paper + Polypropylene film

Dielectric

PE90135

Impregnation Non-PCB, Non-PCB, sticky Non-PCB, oil Biodegradable (dry) Biodegradable resin resin Ambient temperature Protection Mounting Terminals min -25C to max 55C IP20 Indoor Upright Upright, Horizontal Upright Terminals designed for large cable termination and direct busbar mounting for banking min -25C to max 70C

18

Component General Design Rules Selection guide Capacitors

VarplusBox

Technical Specifications

General characteristics Standards Frequency Losses (dielectric) Losses (total) Capacitance tolerance Voltage Between terminals test Between terminal & Container Discharge resistor Working Conditions Humidity Altitude Over voltage Switching SDuty Operations HDuty Energy Mean Life expectancy Harmonic SDuty Content HDuty Energy Installation characteristics Mounting SDuty position HDuty Energy Fastening & Earthing Indoor, Upright Indoor, Upright & horizontal Indoor, Upright Threaded M6 mounting screws at the bottom IEC 60831-1/-2 50/60Hz < 0.2W/kvar < 0.5W/ kvar - 5%, +10% 2.15 x UN (AC), 10s < 660V - 3 kV(AC), 10s > 660V - 6kV(AC). 10s Fitted, standard discharge time 60s Discharge time 180s on request

95% 2.000 m above sea level 1.1 xUN 8h in every 24h Up to 5,000 switching operations per year Up to 7,000 switching operations per year Up to 10,000 switching operations per year Up to 1,60,000 hrs NLL < 10 % NLL < 20 % NLL < 25 %

Safety Features Safety Self-healing + Pressure-sensitive disconnector for each phase + Discharge device

19

Component General Design Rules Selection guide Capacitors

Choice of compensation

Customer needs Below table describes typical solutions used in several types of activities. Not adapted Usually (70%) Possibly (20%) Rarely (10%)

In any case, it is recommended to make measurements at site in order to validate the final solution.
SDuty HDuty (upto 20%) Hduty/Energy Energy (upto 25%) + Detuned Reactor
Gh/Sn 15 % 15% < Gh/Sn 25% 25% < Gh/Sn 50%

Pollution rate Industry Food & Beverage Textile Wood Paper - Printing Chemical - Pharmacy Plastic Glass - Ceramic Steel - Metallurgy Automotive Cement - Mines Refinery Micro-electronics Tertiary Supermarkets Hospitals Stadium - Amusement park Hotels - Offices - Bank Insurance Energy & Infrastructures Water Internet farm Wind mills Railways - Subways Airports Harbours Tunnels

20

Component General Design Rules Selection guide Capacitors

Safety Features in VarplusCan and VarplusBox


Pressure Sensitive Disconnector (PSD)
Pressure Sensitive Disconnector (also called tear-off fuse): this is provided in each phase of the capacitor and enables safe disconnection and electrical isolation at the end of the life of the capacitor. Malfunction will cause rising pressure inside the can. Pressure can only lead to vertical expansion by bending lid outwards. Connecting wires break at intended spots. Capacitor is disconnected irreversibly.

DB403284 DB403285

T+12+2

(a) (b)

Self Healing
An electric breakdown is possible in the capacitor films due to electric or mechanical over stress. Due to this a small area of metallization will get evaporated and the capacitor will continue to be in service. Continuation of these phenomena will reduce the capacitance value as well as life of the capacitor over a period of time. Self-healing is a process by which the capacitor restores itself in the event of a fault in the dielectric which can happen during high overloads, voltage transients etc.

Figure 1 - (a) Metal layer - (b) Polypropylene film

Figure 2

When insulation breaks down, a short duration arc is formed (figure 1). The intense heat generated by this arc causes the metallization in the vicinity of the arc to vaporise (figure 2). Simultaneously it re-insulates the electrodes and maintains the operation and integrity of the capacitor (figure 3).

Figure 3

Discharge Resistors
A charged Capacitor must be discharged before re-switching, to prevent premature failure. Built-in discharge resistors are used for discharging the capacitor with a delay of one minute as discharge time.
Caution! Do not touch the Capacitor Terminals before Discharging.

21

Component General Design Rules Selection guide Detuned Reactors

Detuned Reactors Overview

Reactors have to be associated to capacitor banks for Power Factor Correction in systems with significant non-linear loads, generating harmonics. Capacitors and reactors are configured in a series resonant circuit, tuned so that the series resonant frequency is below the lowest harmonic frequency present in the system. For this reason, this configuration is usually called Detuned Capacitor Bank, and the reactors referred as Detuned Reactors. The use of detuned reactors thus prevents harmonic resonance problems, avoids the risk of overloading the capacitors and contributes to reducing voltage harmonic distortion in the network. The tuning frequency can be expressed by the relative impedance of the reactor (in %), or by the tuning order, or directly in Hz. The most common values of relative impedance are 5.7, 7 and 14%. (14% is used with high level of 3rd harmonic voltages).
Relative Tuning order impedance (%) 5.7 7 14 4.2 3.8 2.7 Tuning frequency @50Hz (Hz) 210 190 135 Tuning frequency @60Hz (Hz) 250 230 160

The selection of the tuning frequency of the reactor capacitor depends on multiple factors: Presence of zero-sequence harmonics (3, 9, ), Need for reduction of the harmonic distortion level, Optimization of the capacitor and reactor components. Frequency of ripple control system if any. To prevent disturbances of the remote control installation, the tuning frequency is to be selected at a lower value than the ripple control frequency. In a detuned filter application, the voltage across the capacitors is higher than the nominal system voltage. Then, capacitors must be designed to withstand higher voltages. Depending on the selected tuning frequency, part of the harmonic currents is absorbed by the detuned capacitor bank. Then, capacitors must be designed to withstand higher currents, combining fundamental and harmonic currents.

22

Component General Design Rules Selection guide Detuned Reactors

Working limits
In order to avoid any overload of detuned reactors and capacitors, maximum values of voltage distortion have to be respected. Harmonic voltages and THDu have to be measured at the transformer secondary, with the capacitors connected. The current through the capacitors has to be compared to the rated value. Imp/IN is the ratio of the maximum permissible current to the rated current of the capacitor. The proposed limits are only indicative. In any case, if you have a doubt or if values are higher than the above limits, contact us.
Working THDu Harmonic Voltage Imp / IN limits max. % of the order max SDuty 5 Hduty 7 Harmonic 10 (14% relative impedance) Harmonic 8 (7% relative impedance) Harmonic 6 (5.7% relative impedance) 3 5 7 11 13 3 8 7 3.5 3 0.5 0.5 6 5 5 4 3.5 3.5 3 3 1.5 1.8 1.12 1.19 1.31

23

Component General Design Rules Selection guide Detuned Reactors

Capacitors rated voltage with Detuned Reactor


VarplusCan and VarplusBox capacitors when used along with Detuned Reactors have to be selected with a rated voltage higher than network service voltage (US).
Supply network

US, QS
A C B

The recommended rated voltage of capacitors to be used in detuned filter applications with respect to different network service voltage (US) and relative impedance is given in the table below. These values ensure a safe operation in the most stringent operating conditions. Less conservative values may be adopted, but a case by case analysis is necessary.
Capacitor Rated Voltage (UN) V Relative Impedance (%) 5.7% 7% 14% Network Service Voltage (US) V 50Hz 60Hz 400 690 400 480 600 480 480 830 480 480 575 690

UN , QN

Load

Refer to the picture above and consider the following: Us: system voltage (V), QS: requested reactive power (kvar) UN: capacitor rated voltage (V) QN: capacitor rated power (kvar)

Example of Capacitor Selection with a Detuned Reactor


Case: For a 400V 50Hz system, It is required to connect a VarplusCan HDuty of 25kvar reactive power with a detuned reactor with 7% relative impedance P (Tuning factor = 3.8 ). QS = 25kvar, US = 400V, P = 0.07 Step 1: calculation of the capacitor rated voltage The voltage applied to the capacitor is given by the formula: UC = US / (1 P) UC = 400 / (1 - 0.07) = 430.1 V The Capacitor will be choosen with UN = 480V. ( Less Stringent values can be adopted based on the network conditions ) Step 2: calculation of the capacitor reactive power The reactive power QC of the capacitor (with UC applied) is given by the formula: QC = QS / (1 - P) @ UC QC = 25 / (1- 0.07) = 26.88 kvar @ UC The capacitor kvar rating at UN will be: QN = QC * (UN / UC)2 QN = 26.88 * (480 / 430)2 =33.5 kvar The Capacitor will be choosen for 33.5 kvar at 480V for delivering 25kvar with a 7% reactor in a 400V 50Hz system. Use Reference number BLRCH339A407B48 Combination of Capacitor with Part number BLRCH339A407B48 and Detuned Reactor with part number 52405 will give 25kvar at Point B (Refer Picture above)
24

Component General Design Rules Selection guide Detuned Reactors

Choice of detuned reactor tuning frequency


General The detuned reactors (DR) are designed to protect the capacitors by preventing amplification of the harmonics present on the network. They must be connected in series with the capacitors. The detuned reactors generate an overvoltage at the capacitor terminals. The rated voltage of capacitors has to be increased accordingly. Technical data Choice of tuning: The tuning frequency fr corresponds to the resonance frequency of the L-C assembly. fr = 1 2 LC

DB121411

DB121412

We also speak of tuning order n. For a 50 Hz network: n= fr 50 Hz

The tuning frequency chosen must ensure that the harmonic current spectrum range is outside the resonance frequency. It is essential to ensure that no remote control frequencies are disturbed.
DB121408

The most common tuning orders are 3.8 or 4.3 (2.7 is used for 3rd order harmonics).

The tuning factor (P)


The tuning factor (P) is the ratio of Inductor Impedance to the capacitor Impedance XL fr = = (2 f)2 LC = (2 LC)2 f 2 XC f2 P = fr 2 f fr = P

Curve: impedance module at point A

25

Component General Design Rules Selection guide Detuned Reactors

Offer Overview Detuned reactors


Operating conditions
Use: indoor Storage temperature: - 40C, + 60C Relative humidity in operation: 20-80% Salt spray withstand: 250 hours (for 400 V - 50 Hz range). Operating temperature
Altitude (m) > 1000, 2000 Minimum (C) 0 Maximum (C) 55 50 Highest average over any period of: 1 year 24 hours 50 45 40 35

The detuned reactors (DR) are designed to protect the capacitors by preventing amplification of the harmonics present on the network.

PE90154

1000 0

Technical specifications
General characteristics Description Degree of protection Insulation class Rated voltage Inductance tolerance per phase Insulation level windings and windings/earth Thermal protection Restored on terminal block 250 V AC, 2 A Three-phase, dry, magnetic circuit, impregnated IP00 H 400 to 690 V - 50 Hz 400 to 600 V - 60 Hz Other voltages on request -5, +5 % 1.1 kV

Dielectric test 50/60 Hz between 4 kV, 1 min

Maximum Permanent Current (IMP)

Lets define the service current (IS) as the current absorbed by the capacitor and detuned reactor assembly, when a purely sinusoidal voltage is applied, equal to the network service voltage (US). IS = Q (kvar) / (3 x US) In order to operate safely in real conditions, a detuned reactor must be designed to accept a maximum permanent current (IMP) taking account of harmonic currents and voltage fluctuations. The following table gives the typical percentage of harmonic currents considered for the different tuning orders.
(%) Tuning order 2.7 3.8 4.2 i3 5 3 2 Harmonic currents i5 i7 15 40 63 12 17 i11 5 5 5 2

A 1.1 factor is applied in order to allow long-term operation at a supply voltage up to (1.1 x US). The resulting maximum permanent current (IMP) is given in the following table:
Tuning order 2.7 3.8 4.2 IMP (times IS) 1.12 1.2 1.3

26

Component General Design Rules Selection guide Detuned Reactors

DB114156

Installation
Forced ventilation required Vertical detuned reactor winding for better heat dissipation Electrical connection: > to a screw terminal block for 6.25 and 12.5 kvar detuned reactors > to a drilled pad for 25, 50 and 100 kvar detuned reactors
Note: As the detuned reactor is fitted with thermal protection, it is imperative that the normally closed dry contact be used to disconnect the step in the event of overheating (see drawing at left).

Normally closed dry contact

27

Component Selection guide Contactors

Offer Overview TeSys D Contactors


General Capacitor control is accompanied by transient operating conditions resulting from the capacitor load which, amongst other things, generates a very high overcurrent equivalent to a short-circuit of short duration. The use of standard contactors may compromise the safety of persons and installations. TeSys D contactors for capacitor control The LC1-DK contactors are specially designed for capacitor control. They are fitted with a contact block allowing the current to pass on closing and with damping resistors limiting the current on energisation. (See page no. 30) Personal safety The contactors cannot be operated manually. The contactors are fitted with covers for protection against direct contact. Safety of installations The damping resistors are disconnected after the capacitor current energising peak. A faulty contactor pole therefore does not allow the permanent current to flow through the resistor and prevents it from burning. Simplicity and durability LC1-DK contactors are a ready-to-use solution that does not require the installation of shock coils. Their durability is far greater than that of conventional solutions (300,000 operating cycles at 400 V). Caution If specific contactors cannot be used to control the capacitors, then energising current limiting reactors must be used. Please consult the contactor manufacturer.
Note: LC1D contactors not incorporating damping resistor can be used with detuned reactors. The inductance of the detuned reactor limits the energising current to a value that can be accepted by the contactor.

DB109701

Effect in Network voltage, Capacitor current and Capacitor voltage without using inrush current limiters

28

Component Selection guide Contactors

References and maximum power ratings


Power ratings Instantaneous auxiliary Tightening torque temp. 55 C contacts on end-piece 220 V 400 V 660 V 240 V 440 V 690 V kvar kvar kvar F O Nm 6.5 12.5 18 1 1 1.2 2 1.2 6.5 15 24 1 1 1.7 2 1.7 10 20 30 1 1 1.9 2 1.9 15 25 36 1 1 2.5 2 2.5 20 30 48 1 2 5 25 40 58 1 2 5 40 60 92 1 2 9 Basic reference no. to which the control voltage reference no. should be added (2) Weight (Kg)

LC1-DFK11 LC1-DFK02 LC1-DGK11 LC1-DGK02 LC1-DLK11 LC1-DLK02 LC1-DMK11 LC1-DMK02 LC1-DPK12 LC1-DTK12 LC1-DWK12

0.43 0.43 0.45 0.45 0.6 0.6 0.63 0.63 1.3 1.3 1.65

The power values in the above table are valid for the following conditions:
Prospective peak energising current Maximum operating rate Electrical durability at nominal load LC1-DK LC1-DFK/DGK/DLK/DMK/DPK LC1-DTK/DWK All contactor ratings 200 IN 240 operating cycles/hour 100 operating cycles/hour 3,00,000 operating cycles 2,00,000 operating cycles

400 V 690 V

(2)

Control circuit voltage ():


110 F7 220 M7 230 P7 240 U7 380 Q7 400 V7 415 N7

Tension (V) 50/60 Hz

Other voltages: Contact us.

29

Component Selection guide Switching and protection devices

Parallel operation of capacitor and inrush current limiting capacitors in APFC panels
Power supply

Power supply

Conventional Switching Contactor

Inrush

Conventional Switching Contactor

Capacitors Before Switching After Switching

Capacitor

Conventional single stage capacitor switching

At capacitor switching while one or more capacitors are connected to the system, the switching capacitor will see a high inrush current. This is due to the current flow from the already connected capacitor(s) (which will act as a source) through the least impedance path set by the switched capacitor along with the current from the main source. This means that when the number of capacitors in parallel increases, the amount of inrush current also increases. Inrush current will damage the capacitor as well as the switching device. In order to prevent inrush current, it is required to use current limiting devices such as Capacitor Duty Contactors or Inductor Coil. Pictorial illustration of the conventional switching and switching using a special capacitor duty contactor is shown in the left.

Power supply

Power supply

Conventional Switching Contactor Inrush Capacitors already on After Switching

Conventional Switching Contactor Capacitors switched on

Capacitors already on Before Switching

Capacitors to be switched on

Conventional multi stage capacitor switching with normal power contactor

Power supply

Power supply

Capacitor Switching Contactor Capacitors to be switched on

Capacitor Switching Contactor Limited Inrush Capacitor switched on

Capacitors already on Before Switching

Capacitors already on After Switching Stage 1

Multi Stage Capacitor Switching with Capacitor Duty Contactor Stage 1 - Capacitor is switched through a inrush current limiter

Power supply

Power supply

Capacitor Switching Contactor Limited Inrush Capacitors switched on

Capacitor Switching Contactor Normal Current Capacitors switched on

Capacitors already on After Switching Stage 2

Capacitors already on After Switching Stage 3

Stage 2 - Capacitor is switched through Contactor and inrush current limiter Stage 3 - inrush current limiter is removed from the circuit and Capacitor is completely switched on

30

Component Selection guide Switching and protection devices

Selection of Capacitor Switching and Protection Devices


Use switching and protection devices designed for capacitor switching duty. After switching off a capacitor, a delay of at least 1 minute must be allowed before switching on again to ensure the discharge of individual capacitor step/unit before reconnection. Solid State switching (Thyristor Switches) can be used when fast switching in APFC Panels is needed.

Short Circuit Protection Device


MCCB or HRC fuses are used with the capacitor for Short Circuit Protection. This has to be rated for 1.5 times the rated current of the capacitor. It is recommended to Use Compact NSX/CVS range of MCCBs.

Contactors
Contactors shall be used to switch capacitors in or out of service of each individual step. The contactors shall prevent inrush current to a safe level when the capacitor steps are switched on. There are two types of contactors used for switching each step: Capacitor Duty Contactor Power Contactor Capacitor duty contactors are recommended in APFC equipment to minimize inrush currents experienced during the switching of capacitors. These contactors have special early make contacts with series resistances which dampens the inrush currents. However, when normal Power contactors are used, and when there are no reactors in series, a suitable inductor coil has to be connected in series with the contactor for limiting the inrush currents. Contactors will have to be chosen with care, keeping in mind the following factors which can influence their performance: Contactor shall be re- strike free and adapted for capacitors The rated voltage of the contactor shall be equal to or higher than the maximum network voltage with the power factor correction installation. The contactor shall be designed for continuous current (including harmonics) which can pass the power factor correction installation and/or filter at maximum source voltage, maximum frequency and extreme tolerances of the components, especially capacitors and reactors. Capacitor duty contactors are rated based on nominal reactive power and Power contactors are rated based on the rated operational current. It is recommended to use Special Contactors LC1 D.K which are designed for switching 3 phase Single or Multiple step Capacitor Banks. Capacitor duty contactors are normally rated up to 60kvar. When higher rated steps exist such as 75kvar, 100kvar and above, the following methods can be adopted.

31

Component Selection guide Switching and protection devices


Method 1: for steps up to 120kvar Capacitor Duty Contactors can be used in parallel to switch the Steps. Example: To switch 100kvar step, using capacitor duty contactor, there are two alternatives. Provide two steps of 50kvar each, (having 50kvar switch, and 50kvar reactor and 50kvar capacitors) and the connection of relay in such a way to operate both together. ( refer Fig A) Provide single step using two capacitor duty contactors in parallel with one 100kvar reactor and one 100kvar capacitor (4x25kvar / 2x50kvar) (refer Fig B) In option B, if one contactor malfunctions, the other contactor gets over loaded and there is possibility for damage in second contactor also. However if both contactors are in good conditions and operate exactly at the same moment, theoretically there will be no problem. But the contactor switching may not occur exactly at the same time, and a very small time difference may cause over loading of contactors. Method 2: for steps more than 120kvar Contactors of AC3 Duty can be used in this case but capacitors need to be put in series with inductor coil.
K1 KN

S/P

APFC Relay

K1

KN

Capacitors Fig A

S/P

APFC Relay

Example: To switch 120 kvar step, using AC3 Duty contactor, provide four steps of 30kvar VarplusCan capacitor connected to a inductor coil in series. (see Fig C).

Capacitors Fig B

S/P

APFC Relay

K1

IC

Capacitors Fig C

32

Component Selection guide PF Controller

Power Factor Controller

PF controllers are microprocessor based, which takes real time inputs from the network, calculate the kvar required and switch on /off capacitors. The microprocessor analyzes the current input signal from the load current transformer and the Voltage tapped from the Bus to produce switching commands to control the contactor ON/OFF of the capacitor steps. Intelligent control by PFC controllers ensures an even utilization of capacitor steps, minimized number of switching operations and optimized life cycle. Feasibility for Four quadrant operation for sensing the energy flow direction becomes necessary for certain applications based on system conditions. The controller placed inside the panel shall have the reliability to withstand the operating temperature of at least 50 C or more.

C/k setting:
C/k value is used in the setting of old generation Power Factor Controllers, however it is found rarely to be used in panels now. C/k value is a threshold value for switching On/Off the capacitor steps by the controller. C/k is the value obtained by dividing first step capacitor power Q to the current transformer ratioK. This setting shall be automatic or can be set manually. The main features of the PF controller must include the following: Automatic C/k- value setting, Connection of different capacitor steps. Automatic detection and usage of optimum capacitor steps. Current measuring 10mA-5A, suitable for connecting CT x/1A and x/5A. Programmable capacitor switching delay Indication for over current Indication for low power factor Fan contact Modern day APFC controllers provide various additional functions like electrical data logging, self diagnostics and system health features and are capable of communication using standard protocols. Additional features can be chosen based on specific requirements of end user which are as follows: Four Quadrant operation Automatic phase reversal correction Various automatic trip conditions can be programmed over current, over voltage Single phase measurement Various metering parameters like V, I, THD-V, Hz, kvar, temp, PF etc.,

33

Component Selection guide PF Controller

Technical data General data

Offer overview - Varlogic N power factor controller

Varlogic NR6/NR12

operating temperature: 060 C storage temperature: -20 C60 C colour: RAL 7016 standard: EMC: IEC 61326 electrical: IEC/EN 61010-1. panel mounting mounting on 35 mm DIN rail (EN 50022) protection class in panel mounting: front face: IP41 rear face: IP20. display NR6, NR12 type: backlighted screen 65 x 21 mm NRC12 type: backlighted graphic screen 55 x 28 mm. languages: English, French, German, Portuguese, Spanish alarm contact temperature internal probe separate contact to control fan inside the power factor correction bank access to the history of alarm.

PE90161

Inputs
phase to phase or phase to neutral connection insensitive to CT polarity insensitive to phase rotation polarity current input: NR6, NR12 type: CT X/5 A NRC12 type: CT X/5 A et X/1 A.
PE90156

Outputs
potential free output contacts: AC : 1 A/400 V, 2 A/250 V, 5 A/120 V DC : 0,3 A/110 V, 0,6 A/60 V, 2 A/24 V.

Settings and parameters


target cos setting: 0.85 ind0.9 cap possibility of a dual cos target (type NRC12) manual or automatic parameter setting of the power factor controller choice of different stepping programs: linear normal circular optimal. main step sequences: 1.1.1.1.1.1 1.2.3.3.3.3 1.2.2.2.2.2 1.2.4.4.4.4 1.2.3.4.4.4 1.1.2.3.3.3 1.1.2.2.2.2 1.2.4.8.8.8 personalized sequences for NRC12 type delay between 2 successive switch on of a same step: NR6, NR12 type: 10 600 s NRC12 type: 10 900 s step confi guration programming (fi xed/auto/disconnected) (NRC12 type) 4 quadrant operation for generator application (NRC12 type) manual control for operating test.

Varlogic NRC12

PE90155.eps

Range
Type Number of step output contacts NR6 6 NR12 12 NRC12 12 RT6 6 RT8 8 RT12 12 Accessories Communication RS485 Modbus set for NRC12 Temperature external probe for NRC12 type in addition to internal probe allows measurement at the hottest point inside the capacitork52 Part number 52448 52449 52450 51207 On request On request 52451 52452

34

Component Selection guide PF Controller

Varlogic - Technical characteristics


General characteristics Output relays AC 5 A / 120 V 2 A / 250 V DC 0.3 A / 110 V 0.6 A / 60 V Protection Index Front panel IP41 Rear IP20 Measuring current 0 to 5 A Specific features RT6 NR-6/12 Number of steps 6 6 / 12 Supply voltage (V AC) 88 to 130 50 / 60 Hz 185 to 265 185 to 265 320 to 460 320 to 460 Display 4 digit 7 segment LEDs 65 x 21 mm backlit screen 55 x 28 mm backlit screen Dimensions 143 x 143 x 67 155 x 158 x 70 Flush panel mounting 35 mm DIN rail mounting (EN 50022) Operating temperature 0 C - 55 C 0 C - 60 C Alarm contact Internal temperature probe Separate fan relay contact Alarm history Last 5 alarms Type of connection Phase-to-neutral Phase-to-phase Current input CT 10000/5 A CT 25/5 A 6000/5 A CT 25/1 A 6000/5 A Target cos setting 0.85 ind. 1 0.85 ind. 0.9 cap. Possibility of a dual cos target Accuracy 2 % 5 % Response delay time 10 to 1800 s 10 to 120 s Reconnection delay time 10 to 1800 s 10 to 600 s 10 to 900 s 4-quadrant operation for generator application Communication protocol 1 A / 400 V 2 A / 24 V

NRC12 12 88 to 130 185 to 265 320 to 460

155 x 158 x 80 0 C - 60 C

Last 5 alarms

2 % 10 to 180 s

Modbus

35

Component Selection guide PF Controller

Physical and Electrical Control of PFC Relay


The Varlogic power factor controllers continually measure the reactive power of the system and switch the capacitor steps ON and OFF to obtain the required power factor. Their ten step combinations enable them to control capacitors of different powers. Step combinations 1.1.1.1.1.1 1.2.3.3.3.3 1.1.2.2.2.2 1.2.3.4.4.4 1.1.2.3.3.3 1.2.3.6.6.6 1.1.2.4.4.4 1.2.4.4.4.4 1.2.2.2.2.2 1.2.4.8.8.8 These combinations ensure accurate control by reducing the number of power factor correction modules reduce workmanship for panel assembly Optimising the control in this way generates considerable financial benefits. Explanations Q1 = Power of the first step Q2 = Power of the second step ------------------Qn = Power of the nth step (maximum 12) Examples: 1.1.1.1.1.1: 1.1.2.2.2.2: 1.2.3.4.4.4: 1.2.4.8.8.8: Q2 = Q1, Q3 = Q1, , Qn = Q1 Q2 = Q1, Q3 = 2Q1, Q4 = 2Q1, , Qn = 2Q1 Q2 =2Q1, Q3 = 3Q1, Q4= 4Q1, , Qn = 4Q1 Q2 = 2Q1, Q3 = 4Q1, Q4= 8 Q1, , Qn = 8 Q1

Calculating the number of electrical steps depends on: the number of controller outputs used (e.g. 7) the chosen combination, according to the power of the various steps (e.g. 1.2.2.2).
Combinations 1.1.1.1.1.1 1.1.2.2.2.2 1.2.2.2.2.2 1.1.2.3.3.3 1.2.3.3.3.3 1.1.2.4.4.4 1.2.3.4.4.4 1.2.4.4.4.4 1.2.3.6.6.6 1.2.4.8.8.8 Number of controller outputs used 1 1 1 1 1 1 1 1 1 1 1 2 2 2 3 2 3 2 3 3 3 3 3 3 4 5 4 6 4 6 7 6 7 4 4 6 7 7 9 8 5 5 8 9 6 6 7 7 8 8 9 9 10 11 12 10 11 12

10 12 14 16 18 20 22 11 13 15 17 19 21 23

10 13 16 19 22 25 28 31 12 15 18 21 24 27 30 33 12 16 20 24 28 32 36 40

10 14 18 22 26 30 34 38 42 11 15 19 23 27 31 35 39 43 12 18 24 30 36 42 48 54 60 15 23 31 39 47 55 63 71 79

36

Component Selection guide PF Controller

Practical Example: Consider an APFC System of 250 kvar Solution 1: Electrical control 10 x 25 kvar 25 + 25 + 25 + 25 + 25 + 25 + 25 + 25 + 25 + 25 ; sequence : 1.1.1.1.1.1 10 physical steps 10 contactors Refer Contactor Selection 12-step controller ( Varlogic NR12 ) Refer PFC relays- Varlogic Selection Capacitors- VarplusCan 10 x 25kvar Conclusion High Labor, high cost: non-optimised solution. Possible Power levels (kvar) : 25,50,75,100,125,150,175, 200, 225, 250 Solution 2: Electrical control 10 x 25 kvar 25 + 50 + 75 +100 = 10 x 25 kvar electrical; sequence: 1.2.3.4:4 4 physical steps allowing for 10 different power levels 4 contactors (refer contactor selection) 6-step controller ( Varlogic NR6 - refer PFC relays- Varlogic selection) Capacitors - VarplusCan - 2 x 25kvar + 2 x 50kvar + 1 x 100kvar Conclusion Optimised Solution. Optimisation of compensation cubicle - Possible power levels (kvar) The symbol shows the physical step is On for obtaining the Possible power levels.

Possible power levels (kvar) 25 50 75 100 125 150 175 200 225 250

Physical Steps 25 50 75 100

37

Component Selection guide CT and Protection Devices

Current Transformer

Current transformer (CT) is used in APFC panels for measurement purposes. It steps down load current to a low value (5A) output. The VA rating of CT shall be 5VA or 10VA as the maximum.

DB121445

Where to connect CT
DB121443

Resin Cast CTs or Moulded case CTs are sealed units and have better life than the ordinary tape insulated CTs. Moulded case CTs are usually preferred for lower current ratings and resin cast for higher ratings. Primary current of the CT has to be selected based on the total kvar of the panel. Since CTs and relays are provided in the same panel, the lead wire length will be very short and hence use of 5A secondary is preferred. Ammeter is the only load and considering short distance of wires, 5 to 10VA is selected as a maximum burden. It is recommended to use Class 1 CTs for Commercial measurements

The following aspects shall be considered while selecting CTs:

Current Transformer- Installation recommendations


current transformer must be installed upstream of the installation to be compensated the controller voltage should be set between L2 and L3 and the CT to phase L1 the capacitor bank wiring diagram should be designed to ensure that the time required to discharge the capacitors is observed (minimum 1 minute), for example in the event of a loss of contactor auxiliary voltage if the installation comprises two or more supply transformers, a summing CT that will take all the energy consumed by the installation into account must be provided. The ratio to be used to calculate the C/k is the sum of the ratios of the various measuring CTs if the installation includes a generator set, a contact will disconnect the capacitor bank in the event of generator set operation.The best method in this case is to use it to cut off the supply to the controller

How to connect Controller


DB121446

Connecting controller when summing CT is used


DB121444

CTA CTC CTD

CTB

CTE

CTF

Connecting CTs when more than one supply Transformer is used 38

Component Selection guide CT and Protection Devices

Protection Devices in APFC Panel


The following are the protection schemes provided for APFC panels:

Over voltage
In the event of an over voltage, electrical stress on the capacitor dielectric and the current drawn by the capacitors will increase. The APFC equipment must be switched off in the event of over voltage with suitable over voltage relay.

Under voltage
In the event of under voltage, electrical stress on the capacitor dielectric and the current drawn by the capacitors will decrease. This condition is not harmful. But protection is provided based on customer request to protect system from under voltage.

Over Current
Over current condition is very harmful to all current carrying components. All the switchgears are selected on a higher maximum current carrying capacity. However suitable over current relays with alarm can be used for over current protection.

Short circuit protection


At the incomer level short circuit protection is provided by devices such as MCCB, ACB and SFU suitably. At the step protection level, suitable fuses, MCB, MCCB can be used.

Thermal Overload
It is taken care by thermal overload relay. The APFC controller must be tripped in cases where internal ambient temperature exceeds the limits. Reactors are also provided with thermal switches, to trip in the case of temperature increase.

Earthing
Two earthing points are provided in the APFC panel for connecting to the earth bus. This will ensure the overall safety of operating personnel and equipment protection in case of earth faults.

Earth Leakage Relay


It has to be connected at power incoming side of the panel, Earth leakage relay is provided to safeguard the operator by tripping the incomer.

Timers
Capacitors require a minimum discharge time of approximately 60 seconds after they are switched off before they can be switched on again. This is to be set in the APFC controller. Capacitors are provided with discharge resistors.

39

Component Selection guide CT and Protection Devices

Switchgear and Fuse Selection

Main incomer is used to disconnect the APFC system in case of short circuit, over load and earth fault. The rating of the incomer switchgear will vary depending on rating of the APFC equipment and the required fault current handling capacity. SDF, MCCB or ACB can be used as incomer switchgear depending on the current rating of the APFC equipment and the required fault level. Outgoing protection is provided to protect the individual capacitor step in the APFC equipment. The outgoing protection may be fuses, MCB, MCCB & SDF depending on the rating of the individual capacitor steps, required fault level & customer requirement too. Factor of 1.5 for over loads The factor of 1.5 has arrived by taking into account the combined effects of harmonics, Over Voltage and capacitance tolerance as per standard IEC 60831. 1.5= (1.3 x 1.15 = 1.495) ~ 1.5 where 1.3 - Factor of maximum permissible current of capacitors at rated sinusoidal voltage and rated frequency excluding transients. 1.15- Capacitance tolerance. As per IEC 61921, capacitor current should not be allowed to exceed the above value of 1.5 times hence there is no possibility of increasing the factor. There is no need for reducing the factor since the factors 1.3 and 1.15 are applicable to all types of capacitors. Therefore the safety factor of (1.5 x In) is used for selecting all switchgear.
Other than selecting the rating of the circuit breaker or SDF ,it is essential to protect the capacitor bank by selecting - proper thermal magnetic release setting in case of a circuit breaker - proper fuse rating selection in case of a SDF

40

Component Selection guide CT and Protection Devices

Thermal and Magnetic setting of a Circuit breaker


The rating must be chosen to allow the thermal protection to be set to: 1.5 In for SDuty/HDuty/Energy Capacitors 1.31In for HDuty/Energy with 5.6% Detuned Reactor (Tuning Factor 4.3) 1.19In for HDuty/Energy with 7% Detuned Reactor (Tuning Factor 3.8) 1.12In for HDuty/Energy with 14% Detuned Reactor (Tuning Factor 2.7)
Note: Restrictions in Thermal settings of system with Detuned reactors are due to limitation of IMP (Maximum Permissible current ) of the Detuned reactor. Example 1: Capacitor alone

Example 1: 150kvar/400v 50Hz Capacitor Us = 400V; Qs = 150kvar Un = 400V; Qn = 150kvar In = 150000/4003 = 216A Circuit Breaker Rating = 216 x 1.5 = 324A Select a 400A Circuit Breaker. Circuit Breaker thermal setting = 216 x 1.5 = 324

Individual capacitor protection by fuses

Individual capacitor protection by circuit breaker

Conclusion:- Select a Circuit Breaker of 400A with Thermal Setting at 324A and Magnetic Setting ( Short Circuit ) at 3240A

Example 2: Capacitor with detuned reactors

Example 2: 20kvar/400v 50Hz Harmonic Range with 7% Detuned Reactor Us = 400V; Qs = 20kvar Un = 440V; Qn = 22.51kvar Refer: Selection of capacitor with detuned reactor In = 22510/4403 = 29.9A
Individual capacitor protection by circuit breaker Individual capacitor protection by fuses

Circuit Breaker Rating = 29.9*1.5 = 45A Circuit Breaker thermal setting = 29.9 x 1.19 = 35.6A

Capacitor bank protection by means of a circuit breaker

Conclusion:- Select a Circuit Breaker of 45A ( or next available appropriate range) with Thermal Setting at 35.6A and Magnetic Setting ( Short Circuit ) at 356A

41

Component Selection guide CT and Protection Devices

Fuse Selection
The rating must be chosen to allow the thermal protection to be set to: 1.5 In for SDuty/HDuty/Energy Capacitors 1.35In for HDuty/Energy with 5.7% Detuned Reactor (Tuning Factor 4.3) 1.2In for HDuty/Energy with 7% Detuned Reactor (Tuning Factor 3.8) 1.15In for HDuty/Energy with 14% Detuned Reactor (Tuning Factor 2.7)
Note: Restrictions in Thermal settings of system with Detuned reactors are due to limitation of IMP (Maximum Permissible current ) of the Detuned reactor.
DB114162

Example 1: Capacitor alone

Example 1: 150kvar/400v 50Hz Capacitor Us = 400V; Qs = 150kvar Un = 400V; Qn = 150kvar In = 150000/4003 = 216A SDF Rating = 216*1.5 = 324A Select a SDF of 324A (or next available appropriate range) with

Individual capacitor protection by circuit breaker

Individual capacitor protection by fuses

HRC Fuse Rating = 216 *1.5 = 324A (or next available lower rating )

Example 2: Capacitor with detuned reactors

Example 2: 20kvar/400v 50Hz Harmonic Range with 7% Detuned Reactor Us = 400V; Qs = 20kvar Un = 440V; Qn = 22.51kvar Refer: Selection of capacitor with detuned reactor In = 22510/4403 = 29.9A SDF Rating = 29.9*1.5 = 45A
Individual capacitor protection by circuit braker Individual capacitor protection by fuses

HRC Fuse Rating = 29.9 *1.2 = 36A Conclusion:- Select a SDF of 45A (or next available appropriate range) with HRC Fuse Rating 36A (or next available lower rating )

Capacitor bank protection by means of fuses

42

Installation rules Capacitors

General Installation Rules

General
Indoor installation on firm support in a correctly ventilated local or envelope. Ambient temperature around capacitors must not exceed 35C over one year, 45C over 24hours and 55C max (according to IEC 60831 for -25/D temperature category) (Except for Energy range ( 55C over 24 hours and 70 Max).
PE90130

PE90131

PE90132

Maintain a gap of min. 30mm between capacitor units and min. 30mm between capacitors and panel enclosure for better air circulation Electrical clearance between phases shall be 30mm. For 3ph capacitors keep min. 30mm gap above the top of the capacitor Use capacitor duty contactor or inductor coil in series with two phases in order to limit the inrush current when capacitors are switched in parallel with other energized capacitor units. Please ensure that there is no force by any means on the Pressure Sensitive Disconnector ( PSD) in such a way to affect the operation of PSD when it is required to operate.

PE90164

PE90137

43

PE90135

Installation rules Capacitors

Installation rules VarplusCan and VarplusBox


Terminals
Double Fast-On + Cable For lower ratings Double fast-on terminals with cables are provided ( for rating <=10kvar ) CLAMPTITE terminals The unique finger-proof CLAMPTITE termination is fully integrated with discharge resistors and allows suitable access to tightening and ensures cable termination without any loose connections. Once tightened, the design guarantees that the tightening torque is always maintained. (for rating >10kvar , up to 30kvar) STUD type terminals This type of terminals are used for proper current handling capabilities in capacitors of 40&50kvar

Double Fast-On + Cable

Clamptite

Stud Type

Electrical connection
2.5 NM

10Nm

Select the cable cross section depending on the kvar & voltage rating see cable Selection User is recommended to use a cable of minimum temperature withstand capacity of 90C. ( recommended is 105 C) Remove conductor insulation of the cable only 10mm for connection. Suitable size lugs have to be used with connecting cable to capacitor terminals in order to avoid heat generation due to improper contacts, in case of VarplusBox or Stud type VarplusCan. Insert conductor fully inside without connecting lugs in the CLAMPTITE, no single strand to come out from the slot, in case of CLAMPTITE terminals. Use pneumatic gun to tighten the screw from top of the CLAMPTITE terminal cover. If not possible, please ensure proper tightness when a screw driver is used to avoid loose termination. Apply a torque of 2.5Nm to tighten For Stud type terminals use a pressure of 20Nm to tighten the Terminals after connecting cable using proper sized lugs. For tightening the VarplusBox terminal studs apply a torque of for M6 studs - 4 Nm for M8 studs - 8 Nm for M10 studs - 12 Nm Mounting Varplus capacitors can be mounted alone or in row. Position: SDuty & Energy : upright HDuty : upright or horizontal Capacitor body shall be earthed at bottom. Capacitor shall be installed in dry place away from heat generating source & avoid dusty atmosphere Proved proper cross ventilation for heat conduction Apply a tightening torque of 8Nm to fix the VarplusBox capacitor on the mounting plates. Tightening torque of 10Nm to be applied on Hexagonal mounting nut for VarplusCan(see picture in the left).

Removable screws Top cover Sliding cover Cable entry hole Removable Terminal Nuts and Washers Fixed Washer and Plate

VarplusBox

Installation step1

Installation step2

44

Installation rules Capacitors

Installation rules VarplusBox Compact


Following are the steps for installation of VarplusBox HDuty Compact Capacitors.

Step 1
Unpack the VarplusBox HDuty Compact

Step 2
Mounting of Capacitor

Step 3
Cable Connection and Installation Select the Cable cross section depending on the kvar & Voltage rating see Cable Selection User is recommended to use a cable of minimum Temperature withstand capacity of 90C. ( Recommended is 105 C) Remove conductor insulation of the cable only 10mm for connection. Suitable size lugs has to be used with connecting cable to capacitor terminals in order to avoid heat generation due to improper contacts. For the step ratings where VarplusBox HDuty Compact is put in parellel ensure that Maximum power per step Rule is followed. See Maximum power per step-VarplusBox HDuty Compact Follow the instructions below.

Capacitor and accessories

Ventilation
Capacitors, contactors, fuses and electrical connections generate heat dissipation (about 2,5W/kvar total or 8W/kvar with series reactors). Specific precautions must be taken in order not to exceed temperature values of -25C/D category around the capacitors inside the cubicle (see paragraph .Installation.). The airflow inside the cubicle must go from bottom to top. The cross section of the top air outlet must be at least equal to 1.1 times the cross-section of the bottom air inlet. For power higher than 200kvar in 2m high cubicle forced ventilation is necessary. It is recommended to install forced ventilation with extractor fans on the cubicle roof. In case of detuned reactors use, it is recommended to install them in a column separate from the capacitors. Preferably reactors at the top and Capacitors at bottom.

Installation instructions

Mounting instructions

45

Installation rules Detuned Reactors

Detuned reactors

DB121436

Temperature rise stresses


The preferred architecture of a PFC switch board with detuned reactors is with a separate column, specifically reserved for the reactors. (See picture) Detuned reactors require forced ventilation.
Note: under no circumstances may the detuned reactors be fitted beneath the capacitors.

Example of capacitor banks with Detuned Reactors


DB121428

Location of the detuned reactors


To ensure proper ventilation, the DR windings must be vertical.
DB121427

DB121437

Installation distance
The minimum distances illustrated opposite must be observed for insulation purposes and to prevent overheating.

46

Installation rules APFC Panels

Maximum kvar per step in APFC Panel


For VarplusCan
There are no restrictions in number of VarplusCan capacitors to be put on parallel; the following points have to be taken care before deciding the maximum kvar per step a) Contactor rating. b) VA burden of the relay. c) Ventilation d) Minimum clearances a) Contactor Rating Capacitor duty contactors are normally rated up to 60kvar. Whenever higher rated steps exist such as 75kvar, 100kvar or 120kvar, the contactors are connected in such a way to be operateed by a single contact of the relay. However for rating 120kvar and above AC3 duty contactors can be used along with the suitable inductor coils in series with capacitors in two phases for suppressing the inrush current. (refer to selection of capacitor switching and protection devices - Contactors )

b) VA burden of the relay


The maximum kvar per step also depends on the VA burden of each output contact of the power factor relay. The coil rating of all the contactors in the step should not exceed the VA burden of the relay contact.

c) Ventilation
The maximum ambient temperature on the capacitors is +55C. The capacitors have to be placed in the rack in such a way that temperature should not exceed this limit. So, proper ventilation is very much required.

d) Minimum clearances
For better air circulation, a minimum clearence of 30mm between capacitor units and panel enclosure need to be kept. Also maintain a 30mm gap above the top of the capacitor. These are the points to be considered while deciding the number of capacitors in a rack.

47

Installation rules APFC Panels

Restrictions for VarplusBox HDuty Compact There are restrictions in number of VarplusBox HDuty Compact capacitors to be put in parallel due to the restriction in the mounting of these capacitors. All the 4 points discussed above are valid for VarplusBox HDuty Compact except the mounting restrictions. Maximum acceptable power of the assembly is shown in the below table.
Rated voltage 380/400/415 V 440 V 480/525 V 690 V Maximum quantity Maximum acceptable power of units mechanically of the assembly assembled 4 4 4 4 65 kvar (20kvar is the maximum with single unit) 65 kvar (20kvar is the maximum with single unit) 50 kvar (12.5kvar is the maximum with single unit) 50 kvar (12.5kvar is the maximum with single unit)

* Mentioned is the effective Power at the network voltage with Detuned ReactorRefer Capacitor rated voltage with detuned reactor

Applicable maximum power can be estimated from the figure below.

50/60 Hz

UN < 400V

40 kvar

> 40kvar

50/60 Hz

UN 400V

65 kvar

> 65kvar

48

Installation rules APFC Panels

Installation rules APFC Panels


Enclosure
Enclosure provides protection for the components used in the APFC panel against ingress of external solid or liquid particles. Enclosures are made up of CRCA (Cold Rolled Close Annealed) high carbon steel. The enclosures shall be thoroughly degreased and cleaned and phosphate coated before primer coats & powder coating. Enclosure design shall comply to allow easy access of components inside the APFC Panel. Proper electrical clearances must be maintained inside the panel to ensure safety and ease of maintenance. Utmost care shall be taken for the design of enclosure and layout of all the parts and components in such a manner that it gives easy access for maintenance (Especially the components on the front door for aesthetic appearance). Enclosure must be designed to ensure proper ventilation; necessary louvers shall be made at the required area for proper ventilation. These louvers shall be closed with wire mesh or perforated sheets of required size from inside to achieve the specified IP levels.

Size of enclosure
Selecting the enclosure size is an important aspect, which accommodates most of the components in it and the size of the enclosure should be selected properly after a proper layout of components is made, in order to maintain the electrical clearances, ventilation and safety. The heat generating components should be located in such a manner that the heat generated does not come in contact with other components, especially which are sensitive to heat. A proper air flow has to be planned. Size of the enclosure depends on the following points. Total kvar rating of the APFC system. Type of APFC Panel, normal or harmonic filter panel. Number of physical steps. Type of incomer protection (SDF, MCCB or ACB). Type of outgoing protection (HRC Fuses, MCB or MCCB) Type of capacitors (application & construction based) and number of capacitors in the panel. Cable entry - Bottom or Top. Installation type - Outdoor or Indoor. Bus bar sizing and positioning in panels

49

Installation rules APFC Panels

Ventilation inside the APFC Panel


Proper ventilation is essential to ensure good performance of the installed components in the APFC panel. Care must be taken to ensure that unimpeded airflow is maintained inside the panel. The accumulation of heat in an enclosure will potentially damage the electrical equipments. Overheating can shorten the life expectancy of components, especially the capacitors, which are highly sensitive to temperature and leads to catastrophic failure. Since adequate ventilation is required, sufficient louvers shall be provided at the bottom portion of the panel as inlet for air, and at top portion for exhaust. This gives a natural air flow from bottom to top inside the panel. For high kvar rated panels, this natural air flow has to be assisted by forced ventilation using exhaust fans at the top to have quicker replacement of hot air inside with cool air from outside and maintain the internal ambient temperature of the panel at the desired level.
Note: Providing louvers throughout the height of the panel is not recommended since it doesnt give the ducting effect for air flow.

Selection of Fan
It is better to use a fan with thermal switches. In this case the positioning of the fans should be taken care so as to not place the fans thermal switch close to heat dissipating devices so as to avoid any malfunctioning of thermal switch. The selection of fans shall be based on several parameters: Total watt loss including all components in the panel, IP level of the panel. Total volume of the enclosure, Outside ambient temperature, Desired internal ambient temperature. The cubic meter per hour capacity of the fan and the ambient temperature at which the fan can continuously operate are also to be taken into account for deciding the number of fans. The following are the conditions considered for fan calculation, and applicable only for this design, The design conditions are taken in such a way to take care of even extreme temperature of 50C inside the panel ( As the design is for higher temperature, safety factor will be very high ) External Temperature - (Ambient) - 40C Enclosure Dimension (see table)
User can see the recommended practices for Ventilation in following pages with respect to the application

50

Installation rules APFC Panels

Ventilation for capacitor banks

Ventilation Practices
Normal operating conditions according to IEC61439-1 Maximum temperature in the electrical room: 40C Average temperature over 24hrs in the electrical room: 35C Average annual temperature in the electrical room: 25C Minimum temperature: 5C Maximum altitude: 2000m Other conditions, contact us

The following rules apply to capacitor banks without reactor

Ventilation rules:
Sduty, HDuty & Energy Range Capacitors, contactors, fuses and electrical connections dissipate heat. These losses are roughly 2-3W/kvar. Calculate the losses roughly and use the table mentioned in the next page ("Minimum number of fans required in the panel"). The following ventilation rules must therefore be complied with: The air within the cubicle must flow upwards. It is recommended that extractor fans be fitted on top of the cubicle. The bottom air inlet must be as low as possible for better ventilation The cross-section of the top air outlet must be more than the cross-section of the bottom air inlet The openings must be compatible with the safety rating (IP) There should be at least 100 mm between the fan and the modules or components The air inlet at the bottom air intake grille must not be obstructed or restricted by a component or module Always let a gap of minimum 600 mm between the back of the panel and the wall for a front open panel and a minimum gap of 1000 mm for the rear opened panel. It allows to have a good ventilation Take into account the pressure drops of the air inlet and outlet. As an indication, the real airflow is 0.6 to 0.75 time the airflow announced by the fan manufacturer

51

Installation rules APFC Panels

The following rules apply to Capacitor banks with reactors


DB114165

Ventilation for capacitor banks with detuned reactors


Capacitors, Detuned Reactors, contactors, fuses and electrical connections dissipate heat: These Losses are roughly 8-9W/kvar. Calculate the losses roughly and use the table below with respect to Watt losses. This equipment must always include a forced ventilation system. The DRs must be installed: in a separate enclosure or in the same enclosure as the capacitors, but in a separate compartment, or possibly above the capacitors. The part of the enclosure containing the capacitors must be ventilated according to the standard capacitor bank rules. The part of the enclosure containing the DRs must be ventilated according to the dissipated power. The ventilation rules in the previous page are applicable here also.Ventilation fans are required with respect to Watt losses. (The designs is made based on the assumption of the system as described above. Any special system conditions need consultation of Schneider Electric. It is always preferred to do thermal study before fixing the ventilation in the panel)

Minimum number of fans required in the panel (1) Total losses No. of fans required(2) 0 - 500 W 0 500 - 1500 W 1 1500 - 2400 W 2 2400 - 3000 W 3 3000 - 3500 W 4 3500 - 4500 W 5 4500 - 5000 W 6
(2)

The air throughput of the fans recommended above is 160 m3 / h

Recommended Enclosure sizes


The following table gives the examples for the panel dimensions for better Ventilation
kvar rating 100 150 200 250 300 350
(1)

Total no. of steps 5 6 6 7 8 8

Panel dimension (H x L x W)mm With reactor 1800 x 800 x 800 1800 x 800 x 800 1800 x 800 x 800 2000 x 800 x 800 2000 x 800 x 800 2000 x 800 x 800 2000 x 800 x 800 Without reactor 1800 x 800 x 600 1800 x 800 x 600 1800 x 800 x 600 2000 x 800 x 600 2000 x 800 x 600 2000 x 800 x 600 2000 x 800 x 800

400 8

The number of fans recommended can be followed only if proper ventilation of all the components as per the design rules of the components are implemented with the recommended enclosure sizes and also ensure the recommended mounting distance from the wall.

52

Installation rules APFC Panels

Protection of panels

Protection of panel is to protect both the enclosure and the equipment inside the enclosure, against external influences or conditions such as Mechanical impacts, Corrosion Corrosive solvents Fungus Vermin Solar radiation Icing Moisture (for example, produced by condensation) Explosive atmospheres Protection against contact with hazardous moving parts external to the enclosure (such as fans)

Degree of protection
Degree of protection (IP) is represented by two numerals and two optional characters IP 0-6 0-8 A-D H M S W See standard IEC 60529 Acceptable degree of protection is IP 4X for most of the APFC panels. For dusty environment, a higher level of ingress protection is recommended. A higher IP level gives reduction in cooling and hence special cooling system should be designed (i.e. air conditioning) and better ventilation. When some degree of protection against ingress of water is required, we usually go to IP42. The recommended IP is: IP42

Earthing
Earthing or grounding means literally to make an electrical connection between the ground and a metallic body. The main reason for doing this is safety. The term ground is often used to mean a part of the circuit which has zero volts on it. The main objectives are as follows Provide an alternative path for the fault current to flow so that it will not endanger the user. Ensure that all exposed conductive parts do not reach a dangerous potential. Earthing safety points to be adhered for panels are as follows: Interconnect all earthing points of door mounted metallic components and all non-current carrying parts of control wiring. Connect finally to panel earth bus with suitable cable. Interconnect all earthing points of power circuit components (capacitors, reactors, switches etc). Provide coupling links for connecting the earth bus sections at site. As per standards two earth terminals must be provided for panels. The earth must be designed based on the system fault level at the location.

53

Installation rules APFC Panels

Cable Selection

Cables are used for power circuit and control circuit in APFC system. Choosing a proper and adequate cable is of very much importance. The selection of cable depends on the following points. Voltage Rating. Ampere Capacity. Heating Conditions. Voltage Rating The type and thickness of insulation is determined by the voltage grade. It also helps in determining the minimum size of conductor that is suitable for loads. Ampere Capacity Current carrying capacity of the cable is selected based on the maximum current rating of each step. Heating conditions Include the external thermal conditions which are responsible for determining the temperature increment of a cable. Some important factors to be considered during selection of cables are Ambient temperature Presence of artificial cooling Proximity to heating elements.

Step Power cable selection


Flexible, rigid or semi rigid copper cables are generally used inside the Panel. It shall have a voltage class of 1100V grade. For a working voltage that is less than half the insulation voltage of the cable , i.e < 550V, these cables are considered to be class 2. Therefore they can be flanged directly to metal supports without use of any additional insulating material. The Cable cross section must be compatible with: The current to be carried The ambient temperature around the conductors. Dimensional Rules: The ambient temperature in the electrical room must not exceed 40C The Cables must be appropriate for a current of at least 1.5 times the capacitor current at a temperature of 50C The ambient temperature of the electrical room must not exceed 50C

54

Installation rules APFC Panels

Auxiliary Circuit cable selection


Unless otherwise stated in specifications, the following cable cross sections are recommended for auxiliary wirings. 1.5 mm copper wires for the auxiliary voltage circuits 2.5 mm copper wires for current circuits- CT secondary connection and for earthing It should have a voltage class of 1100/660V grade or more. The cables must be multi strand, single core and PVC insulated.
Note: For CT connection the lug used should be ring type.

Capacitor Bank connection Cable Selection


Power conductors and chosen to carry continuous current of 1.5 times the rated current Power cables are used for interconnection between bus bar, step protection, switches, reactors and capacitors. The maximum permissible conductor temperature is 90C. The cables shall be multi strand, single core and PVC insulated. Minimum of 4 mm power cable is considered for connection capacitor step up to 10kvar Maximum of 35 mm cable is considered for 50 kvar step. And for higher rated steps of 75 or 100kvar, 2 numbers of 35 mm cable are generally used in parallel. Various manufacturers of cables distinguish cables based on cable diameter, current carrying capacity and type. Hence it is necessary to select cables suitably to meet the needs in APFC panels
Note: selection of suitable lugs is very much important in order to achieve a proper joint. Proper crimping of these lugs to the cables should also be ensured. Only 2 lugs are permitted in one hole for termination (i.e. at either sides of the hole and not one above the other).

Recommended size of cables and lugs


kvar rating 2.5 5 7.5 10 12.5 Cable Size in mm2 230V/240V Al 1.5 4 10 16 Cu 1 2.5 6 10 10 400 to 480V Al 1.5 1.5 4 6 6 Cu 1 1 2.5 4 4 >600V Al 1.5 1.5 1.5 2.5 2.5 Cu 1 1 1 1.5 M5/M6/M8 Pin type, fork type or ring type based on the terminal of the components Lug Size

15 10 6 6 4 20 25 30 40 50 75 100 16 10 10 6 25 16 16 10 35 25 16 10 50 35 25 16 50 35 35 25 250 250 235 250 225 235 216 225

M5/M6/M8 fork type or Ring based

**The above details/specifications will vary from manufacture to manufacture. Calculations are based on standard operating conditions.

55

Assembly, Inspection and Testing

Assembly and Inspection

Layout of various components in APFC panels


Components layout is prepared based on the arrangements of switchgears, capacitors, reactors and other components to be installed in the APFC panel. The others also include Bus bars, incomer cable entry whether at bottom or top, fans, etc. Usually capacitors, switch gears and reactors are provided at separate locations, however between capacitors and reactors a complete partition should be provided. Capacitors are mounted vertically on a separate metal channel, tightened by the mounting screw to avoid dislocation. Capacitors are transposed and placed when arranged one below the other in racks. This arrangement gives better cooling to all capacitors equally. Capacitors are sensitive to high temperature and hence proper care will have to be taken while locating them. Reactors operate at much higher temperature than capacitors. Placing reactors adjacent to capacitors or below them will harm capacitors. Capacitors will be subjected to reactors heat and the operating performance will be affected. Hence capacitors and rectors are not assembled together and a complete partition is required between them. The cables connecting the components run in cable alleys, properly numbered for respective steps.

Inspection- Applicable tests and procedure for conducting in APFC panels


Tests according to IEC 61921 to validate the APFC design is conducted A. Type Tests B. Routine Test A. Verificaton of type tests Temperature rise test Dielectric properties Short circuit withstand strength Effectiveness of the protection circuit Clearance and creepage distances Mechanical operation Degree of protection B. Routine Test Inspection of assembly including inspection of wiring and if necessary electrical operation test Dielectric test Checking of protective measures and of the electrical continuity of protective circuit Verification of insulation resistance

56

Assembly, Inspection and Testing

The means

Principle

Practical rules At the end of the manufacturing process, a LV switchboard must undergo various routine inspections and tests in the factory, following an established programme. The switchboard must comply with: the appropriate standards the design file (drawings, diagrams and specific requirements) manufacturer mounting instructions in-house instructions. Test conditions Tests must be carried out in a clearly defined area, in compliance with applicable legislation or regulations, by qualified personnel. Inspection is carried out in a special area refered to as the test platform which is set aside for final testing. All inspectors must first attend a special training course and must be qualified for working in the proximity of live parts. Inspection means The necessary parts should be suitable for the purpose, correctly calibrated and in good working order: dielectric test station megohmmeter multimeter capacitance meter torque wrench controller test bench
Megohmmeter.

DD382359-65

The reference documents The main international standards are: IEC 60439-1, IEC 60529, IEC 60831-1&2 and IEC 61921. In addition to those items which are specific to the switchboard: drawings, diagrams and specific specifications, quality inspectors should refer to up-to-date documents, integrating revisions and updates: to technical files to in-house rules, etc keeping track of changes in standards in order to have the most recent version at all times

57

Assembly, Inspection and Testing

The tests
Inspections and tests - Standards:IEC 60439

Practical rules
Carry out all the compulsory inspections and tests and in particular the three routine tests specified by the IEC 60439-1 standards. They complement any type tests which may have been carried out previously by the manufacturer. Standard IEC 60439-1 defines 10 tests to be carried out on electrical switchboards: 7 type tests 3 routine tests. The 7 type tests must be carried out in laboratories and test platforms on cubicles, using real working configurations: complete cubicles fitted with standard components and equipped with VarplusCan and VarplusBox capacitors. The assembly instructions and the 3 routine tests (described below) provide the necessary proof that the switchboard is of the Type Tested Assembly (TTA) or Partially Tested Assembly (PTA) type, and in compliance with standards.

1st routine test


Inspection of the assembly, including inspection of wiring and, if necessary, an electrical operation test. Conformity conformity of the finished switchboard to the drawings, part lists and diagrams: number, type and rating of devices conformity of cabling: auxiliary and power circuit connections quality of cables: conductor cross-section, crimping and tightness marking of conductors and devices. Visual inspection check clearances and creepage distances at connections or part of busbars check the degree of protection. Presence of protective elements, according to requirements (canopy, gasket, front plate, etc.). No enclosure infractions (cut-outs, holes, etc.) that might compromise the original degree of protection check the presence of a name plate or technical documentation showing the manufacturers name, the project identity number and all the technical specifications relevant to the LV correction switchboard (kvar, voltage, frequency, etc.) Electrical operation Inspect the cables and check the proper operation of the LV correction switchboard, preferably using a controller test bench (attached diagram). Capacitance measurement : Check the capacitance of each step. One measurement between two capacitor terminals is sufficient: Refer annexure 2, formula 4 for Q value (in kvar) analysis from capacitance measured.
58

Assembly, Inspection and Testing

DD382356-69

2nd routing test : Insulation testing


Dielectric test: All devices must be connected, with the exception of those incapable of withstanding the test voltage (disconnect the controller). Tests must be done with all the contactors closed. For a switchboard with voltage rated up 690 V, apply a test voltage of 2500 V - 50 Hz for 1 second minimum, between all the live parts and the interconnected frames of the assembly.
Note: due to capacitor presence, the test must be performed between the 3 shortcircuited phases and the earth.

Dielectrometer
DD382361-69

The tests are satisfactory if there is neither puncture nor flashover between the various parts being tested. Alternative solution: If the switchboard is not subjected to a dielectric test, an insulation measurement must be taken using an insulation tester, with a voltage of at least 500 V (DC). The minimum insulation resistance value must be higher than 1000 ohms/V.

3rd routine test : Protective measures

Check for the presence of barriers to protect against direct and indirect contacts with live parts. Visually check that: Contact washers have been used on all assemblies Earthing wires have been fitted to doors The PE conductor is present and must be connected. Finishing Clean the inside of the switchboard Check presence of switchboard identification markers Check external appearance: scratches, paintwork, etc. Reports Create a non quality input document used to quantify faults, evaluate their importance and assign them to relevant department that must take the necessary action to ensure conformity of the electrical switchboard.

Multimeter

Practical rules
Conformity of production: Draw up a list of missing items Draw up a list of equipment which will be dispatched separately from the switchboard. Conformity of operation: Issue a test report This report notes any anomalies detected and the required corrective measures Establish with the customer, a check list of all the points to be checked (example enclosed) Issue a test report that remains in the panel-builders possession but that can be supplied on request this report certifies that all the tests have been carried out and avoids repeating all tests a second time once on site. Each panel-builder has his own test documents.
59

Assembly, Inspection and Testing

Pre despatch factory inspections report model

Customer: .................................. Project no: ..................................

Cust. order no: .................................. Workpost: .............................

Inspection performed by: .......................................... Signatures: .................................. Q.I: ........................................................................ Device: .............................................................................................................................. kvar V Hz Comments Q.I

Inspection operations 1- dielectric test test 2500 V - 50 Hz - 1 second minimum insulation measurement at 500 V CC 2a- conformity Capacitor (kvar) conform not conform Fuse (A) conform not conform Contactor (type) conform not conform DR (mH) conform not conform DR (A) conform not conform Cable cross-section conform not conform Busbar cross-section conform not conform Connection pads conform not conform Earth circuit conform not conform Component identification conform not conform Conductor identification conform not conform Rating plate conform not conform Documentation conform not conform Frame continuity conform not conform Degree of protection conform not conform Locking conform not conform Presentation, appearance conform not conform Inspection

Steps no. Comments Q.I

operations 1 2 3 4 5 6 7 8 9 10 11 12 2b- operation Contactor OK OK OK OK OK OK OK OK OK OK OK OK Controller conform not conform Indication OK OK OK OK OK OK OK OK OK OK OK OK 2c- capacitance measurement C between (mF) Capacitor no. reading

Observations : ................................................................................................................................................................................................... ............................................................................................................................................................................................................................ ............................................................................................................................................................................................................................ ............................................................................................................................................................................................................................ ............................................................................................................................................................................................................................ ............................................................................................................................................................................................................................

no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no :

60

Assembly, Inspection and Testing

Final inspection report model

Customer: ............................................................................................... Customer order no: .......................................................................... Project no: ............................................................................................... List of equipment Workpost number: ................................................................................... Description: ...................................................................................... Inspection performed 1- Conformity inspection Enclosures Switchgear Conductors : ..........................................................................................................................................................................

: ........................................................................................................................................................................... : ...........................................................................................................................................................................

2- Mechanical checks :.............................................................................................................................................................................. 3- Electrical continuity of mechanical frames Resistance value : ...................................................... m Visual : ........................... Electrical : ......................

4- Dielectric tests (2500 V - 50 Hz - 1 second minimum) : ......................................................................................................................... 5- Insulation resistance monitoring (500 V DC) : ..................................................................................................................................... Resistance value : ...................................................... m

6- Electrical operating tests : ..................................................................................................................................................................... Observations : .................................................................................................................................................................................................. ............................................................................................................................................................................................................................ ............................................................................................................................................................................................................................ ............................................................................................................................................................................................................................ ............................................................................................................................................................................................................................ Conclusion : equipment accepted without reservations. equipment accepted with reservations. Customer inspection Acceptance test organisation Inspector Q.I manager equipment refused, to be presented for re-inspection.

Date: ......................................... Date: ......................................... Signature: ................................. Signature: ...................................

Date: ......................................... Signature: ...................................

61

Handling

Packaging and Transport

Packing design is carried out with due consideration to the mode of transport. The packing design shall be based on the following The panel outer dimension. Total weight of the panel. Position of components/ equipments mounted on the front Panel Position of heavy components placed inside the enclosure Place of delivery Mode of transport Type of loading and unloading Storage conditions at site The panels are provided with the following Proper lifting arrangement - for the panel and the complete assembly Protection against rain, spillage of water or liquids by properly covering the entire enclosure. Protection for meters display and instruments on the front panel Desiccants to ensure removal of moisture during transportation and storage. Packing Sequence Application of Hessian cloth against shocks Thermo Cole to protect instruments , meters - refer Fig 1 Application of stretch film & bubble film on the panel Placement of kurlon spacer on the panel to act as spacer between panel and side/top /rear shocks Inclusion of silica gel bags Printing / labels / Signs to indicate upright position - refer Fig 2 Handling of packed Panels Road Transport During Transport it is necessary to protect the panel from vibration & jolting by proper anchoring in the truck bed. While loading and unloading the panel onto or from the truck, use a crane or fork lift, depending on the weight and size of the panel, especially a loading platform is preferable DO not push the panel up or down a ramp. Alternatively, the crate can be lifted vertically by sling and pulley hook, to ensure safety to the panel and personnel. It is also necessary to instruct the site/ commissioning personnel to handle the packing for movement of the panel to erection site by using crane/ trolley truck to avoid physical damage. Sea Transport Steps should be taken to protect the equipment from corrosion, humidity and rain. Suitable marks and indications should be given on the crate for applying slings for lifting on to the ship deck. While shipping, it is necessary for the shipping agency to properly anchor the panel package to prevent roll over during transit
62

Fig 1

Fig 2

Handling

The following are the figures referring to Dos and Donts

Wrong!

Wrong!


Right!

63

Handling

Storage and Handling

The APFC Panel builder must, in all contracts, provide the user with a manual on proper procedures to be adopted during the stages of installation, commissioning and maintenance. This is particularly important when customers own staff undertakes erection and commissioning. The manual covers, as a minimum, the following subjects:Unloading, inspection and storage of packed panels. Unpacking and visual inspection of panel. Installation and cabling at final location. Setting of APFC relay. Live checks and observations to be made with supply ON, precautions needed during this phase. Recommendation for routine checks to be made after commissioning. In all cases, copies of operating instruction manual of major components, such as APFC controller and protective relays, published by the respective manufacturers, should be provided to the user for use during installation.

Unpacking
While unpacking, care should be taken to see that no sharp tools hits / hampers the surface of the panel and creates dents and damage the powder coated finish of the enclosure. A copy of this Instruction Manual along with a copy of the schematic drawing of the panel is also put in the panel. The same shall be read carefully and followed for the installation, commissioning, and operation of the equipment by the concerned officials at site. If any damage in transit or loss of components is observed during unpacking, this has to be intimated immediately to the concerned. Two panel keys are also supplied along with the panel.

Handling
Attach ropes to the lifting hooks of the panel for handling. Never use hard tools like crowbars which can damage the panel while handling. As far as possible cranes should be used to lift and move the panels. Do not push and give jerks to the panel, and thereby jerks to the internal components. Keep the panel on a flat, firm, surface in the normal upright position. Do not keep it on side wise or upside down. Do not use the operating handles of MCCB, Switches, etc; for holding while handling.

Storage
Do not store the panel uncovered even for a short period. Keep it covered at least with a polyethylene sheet. If it is not to be erected / commissioned for a longer period, keep the panel with the polyethylene sheet and store in a cool, dry, well ventilated, place, well protected from dust and corrosion, wet atmosphere.

64

Installation, Commissioning and Maintenance

Installation, Commissioning and Maintenance


Installation and Commissioning
The panel can be grouted directly on the floor of the switchboard room, provided that proper trench for cabling has been made and the floor is leveled properly. No specific foundation is required.

Pre-commissioning check lists


Check list - 1 The following points should be verified before charging capacitor banks installed in APFC panel. Capacitor voltage rating is equal to or more than the maximum voltage recorded in the installation Capacitor is mounted and installed as per mounting and installation guidelines in this document The plant has the facility to trip the capacitor under over voltage conditions.(10%) Ensure each capacitor bank is provided with suitable protection devices. Suitable inrush current device is connected in series with contactor to limit the inrush current or capacitor duty contactor is connected. Capacitor is installed in the area free from entry of dust, chemical fumes and rain water. PF Controller provided in the panel should be set for 60 seconds On-delay. (Not applicable for capacitors used with the fast switching devices - Static Switched ) The capacitor with detuned reactor banks are provided with MCCB for protection apart from above points. Use the switchgear selection guidelines for selection of breaker Check list - 2 Following points are required to be verified before charging APFC panel. All the electrical connection is checked for loose termination in the panel. The CT is located before the cable connection of APFC panel towards source / main breaker of installation. Ensure the CTs are connected to the PF Controller. It is suggested to mount measurement C.T of the APFC Relay on the Highest current carrying phase ( Eg: R ) and the Voltage input for the relay is taken from other two phases ( Eg: YB ) . This is not applicable for a three phase sensing APFC relays. Neutral cable is connected to the panel. Current carrying capacity of cable in the APFC panel is rated equal to incomer switch current rating. Capacitor terminals are checked for any loose connection. Earthing bus is connected to the panel. All the control fuses are intact. If MCBs are used for step protection make sure they are switched on. Emergency push button is released. Panel are installed in the area free from entry of dust, chemical fumes and rain water.
65

Installation, Commissioning and Maintenance

Check list - 3 Verify the following points in the installation before commissioning capacitor with detuned reactor banks. Capacitor banks without reactor should not be permitted on the secondary side of transformer circuit which is having capacitor + Detuned reactor banks connected. In this case please remove capacitors without reactors from the same network. Capacitors used with reactors are always of higher voltage than network voltage. Please do not use normal capacitor rated for network voltage. Earthing should be done at capacitors and reactors separately. Make sure all the cable and termination guidelines are followed. Forced cross ventilation should be provided in the installation area. If the filter banks are installed inside the panel the fans need to be provided. Detuned reactors are provided with thermal protection, the Normally Closed (NC) dry contact must be used to disconnect the step in the event of overheating.

Shift the panel to the location where it is required to be installed. a. Position the panel on the foundation and lock the panel base frame with the foundation bolts for free standing panels, by using spirit level and plumber block for achieving horizontal and vertical leveling. b. Position the panel on the wall or structure and fix with wall mounting brackets provided along with the panel. Leveling should be done here also as explained above. Connect the earth conductor to the panel terminal provided on either side of the panel. Use the key provided to open the door of the panel and make sure that electrical connection of all equipments are intact. This is particularly important since vibration in transportation sometimes may have resulted in loose connections. The cable rated for current capacity equivalent to main incomer of panel should be used. Use suitable size lugs for connecting the power cables. Connect the cable to the terminals provided for the power supply. Make sure that the correct phase identification is maintained while connecting the incoming terminals to the panel with respect to phases of supply line, as any mistake will lead to the malfunctioning of relay. Connect the APFC relay as mentioned in the checklists. Check the preset values of the CT secondary current of the relay. It should match with the CT used.

Installation guidelines for APFC panel

Commissioning of APFC panel


Connect the 3-phase incoming cable to the Incoming terminal of the Incomer Switch / Circuit breaker of the APFC panel. If the APFC controller / relay are programmable type, program the various settings as per instructions given in the respective instruction manual. Ensure that the CT shorting links are removed after the CT secondary connections are made properly.
66

Installation, Commissioning and Maintenance

Keep the Auto /off / Manual selector switch in the Auto position. Ensure that the power supply to the Incomer switch is ON from the glowing of the indicating lamps R, Y, and B. Cross check the system voltage. Switch ON the Incomer SFU / MCCB / ACB of the APFC Panel. The APFC relay will be energized and displays the present power factor, when R-Phase load CT connections and phase sequence of voltage (Y & B) are correct.
Note: Before interchanging the C.T. secondary wires, ensure that the terminals of the C.T. are shorted by a small wire, which should be removed after the inter change.

Periodic Maintenance

The following periodic checks are recommended to be conducted Visual check of components and current carrying parts, especially bus bar. Check tightness of all electrical connections. Check current drawn by the individual capacitor steps. Check the operation of contactors manually by switching of the APFC equipment Visually check for rust and corrosions in bolts, nuts and other accessories Visually check for the sparks and burn outs in the panels.

67

Annexures

Annexure I

Trouble Shooting in Capacitor


Symptoms Capacitor terminal over heating Cause 1. Proper size for lug is not used 2. Loose connection 3. Rating of cable is not adequate 4. Capacitor drawing over current Remedial Action 1. Check the size of lugs used and replace with suitable size 2. Tighten the loose connections 3. Check the cable current carrying capacity and change if required 4. Check the harmonics in Supply voltage 1. Ensure the ventilation for the installation area 2. Check for the harmonic presence 3. Check the system voltage and capacitor rated voltage. If required replace with capacitor of proper rated voltage 1. Voltage to be maintained 2. Should be checked if the capacitors are installed and operated as per the guideline given 3. Incase of elements failure due to excessive harmonic currents, capacitor should be replaced with reactor and higher rated capacitor. 1. Check the connections of the capacitors 2. Transformer should be provided with fixed compensation 3. Do the proper selection of capacitor as per the guidelines given. 1. Do proper selection/ setting of short circuit device 2. Use special capacitor duty contactors for inrush current limiting in case of parallel switching 3. if it is harmonic overload, capacitor should be replaced with reactor and suitable capacitor.

Over heating of capacitor unit

1. Poor ventilation 2. Drawing excessive current 3. Over voltage

Capacitor drawing less current

1. Low voltage 2. Failure of capacitor elements

Power factor is not improved

1. Capacitor installed is not operated. 2. Supply transformer fixed compensation is not provided 3. Capacitors are not selected properly 1. Short circuit rating/setting is improper 2. Harmonic over loading

Short circuit device operating frequently

68

Annexures

Annexure II

Important analysis formulas

Formula -1 The kvar of capacitor will not be same if voltage applied to the capacitor and frequency changes. The example given below shows how to calculate capacitor power in kvar from the measured values at site and name plate details. QM =( fM / fN ) ( UM / UN )2 QN
UN = Rated Voltage fN = Rated Frequency Rated power QN = UM = Measured voltage Measured frequency fM = QM = Available power in kvar

Example: 1. Name plate details 15kvar, 3 phases, 440V, 50Hz capacitor. Measured voltage - 425V Measured frequency - 48.5Hz QM =( fM / fN ) ( UM / UN )2 QN QM = (48.5/50) (425 / 440 )2 15 = 13.57kvar. 2. Name plate details 25kvar, 3 phases, 480V, 60Hz capacitor. Measured voltage - 464V Measured frequency - 59.5Hz QM =( fM / fN ) ( UM / UN )2 QN QM = (59.5/60) x (464/480 )2 x 15 = 23.16kvar.

Formula - 2

The current of capacitor will not be same if voltage applied to the capacitor and frequency changes. The example given below shows how to calculate capacitor current from the measured value at site. IM = IR

( )
U M x fM U R x fR

UN = Rated Voltage fN = Rated Frequency IN = Rated Current UM = Measured Voltage fM = Measured frequency IM = Capacitor Current

Example: Consider a capacitor of 15 kvar, 440V, 50 Hz, 3 Phase Capacitor Rated Current from name plate = 19.68A Measured Values are: Voltage : 425V , Frequency : 49.5 Hz, IM = 19.68

= 18.43A

425 x 48.5 440 x 50

Note:Please ensure that the measurement is done using true RMS clamp meter 69

Annexures

Formula - 3

Formula for calculating rated current of capacitor with rated supply voltage and frequency. IN = kvar x 103 / (3 x UN) Example 1. 50 kvar , 3 phase, 400V, 50Hz capacitor. IN = kvar x 103 / (3 x UN) IN = (50 1000) / (1.732 400) IN = 72.16 A 2. 37.7 kvar, 3 phases, 525V, 50Hz capacitor. IN = kvar 103 / (3 UN) IN= (37.7 1000) / (1.732 525) IN = 41.45 A

Formula - 4

The capacitance value of a capacitor can be calculated using following formulae for delta connected 3ph capacitor. Assume that capacitance of the three delta connected capacitors are C as shown in the figure. C C C = QN 109 / (4fNUN2) for 3 phase capacitor. Example 1. 15 kvar, 3 phases, 415V, 50Hz capacitor C = 15 109 / ( 4 x 3.142 50 (415 415)) = 138.62F 2. 15 kvar, 3 phases, 440V, 50Hz capacitor C = 15 x 109 / ( 4 x 3.142 x 50 x (440 x440)) = 123.31F

kvar calculation from the measured capacitance value of a capacitor. QM = 2/3 (Ca + Cb + Cc) UN2 (2fN )/ 109 - for three phase capacitor Example 1: Consider you have measured a capacitor rated for 440volts, 50Hz where in measured capacitance value is as follows. 1. 197f ( between R & Y phase ) -Ca 2. 196f ( between B & Y phase ) -Cb 3. 200f ( between R & B phase ) -Cc QM = 2/3 (Ca + Cb + Cc) UN2 (2fN )/ 109 QM = 2/3 (197+196+200)(4402 )23.1450 / 109 = 24.04kvar 2: Consider you have measured a capacitor rated for 480V ,60Hz where in measured capacitance value is as follows. 4. 236f ( between R & Y phase ) - Ca 5. 238f ( between B & Y phase ) - Cb 5. 237f ( between R & B phase ) - Cc QM = 2/3 (Ca + Cb + Cc) UN2 (2fN )/ 109 QM = 2/3(236+238+237)(4802)23.1460/109 = 41.19kvar
The tolerance of capacitance of a capacitor is -5% t0 +10% of capacitor as specified in the IEC Standards.

Formula - 5

70

Notes

Schneider Electric Industries SAS


Head Office 35, rue Joseph Monier CS 3032392506 Rueil-Malmaison www.schneider-electric.com

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper. Design: Schneider Electric Photos: Schneider Electric 10/2011

PFCED111008EN

2011 - Schneider Electric Industries SAS - All rights reserved

You might also like