Guide For The Design and Production of LV Power Factor Correction Cubicles
Guide For The Design and Production of LV Power Factor Correction Cubicles
Guide For The Design and Production of LV Power Factor Correction Cubicles
Guide for the Design and Production of LV Power Factor Correction Cubicles
Panel Builder Guide 2011
Contents
3 - 11
Capacitor Rated Voltage and Current of Capacitor Capacitors selection based on operating conditions Offer overview VarplusCan/VarplusBox
12 - 42
12 - 21
Detuned Reactors
Detuned reactors overview Capacitor Rated Voltage with Detuned Reactors Choice of Detuned Reactor Tuning Frequency Offer overview- Detuned reactors
22 - 27
Contactors Offer overview TeSys D Contactors Parallel Operation of Capacitors and Inrush Current Limiting Varlogic N Power Factor Controller Physical and Electrical control of PFC relay CT and Protection Devices Current Transformer Protection Devices in APFC Panels Switchgear and fuse selection Capacitor General Installation rules Installation rules - VarplusCan and VarplusBox Installation rules - VarplusBox Compact
28 - 30 31 - 32 33 - 37 38 - 42
43 - 55
43 - 45
Detuned Reactors
APFC Panels Maximum kvar per step in APFC Panel Installation rules - APFC Panels Ventilation for capacitor banks Protection of panels Cable selection
46 47 - 55
56 - 61
CHAPTER 5: Handling
62 - 64
ANNEXURE
68 - 70
1- The compensation modules The VarplusCan and VarplusBox capacitors Their positioning must ensure proper ventilation. Their sizing must take into account ambient conditions (harmonics, temperature, etc) The contactors They must be suited to capacitor control. Schneider Electric has designed and tested specific contactors for this application.Their control voltage must be monitored in order to prevent rapid reclosing.
2- The detuned reactors (DR) They must be chosen according to harmonic stresses and installed in order to avoid, as far as possible, capacitor temperature rise.
The DR temperature sensor must be connected so that the step can be disconnected if the temperature is too high
3- Ventilation It must be efficient in order to keep operating temperature lower than maximum permissible temperature of components.
4- The power factor controller Its functions must be adapted to the capacitor bank characteristics: number and power of steps, sequence, etc. The time delay must be adapted to capacitor discharge time.
5- Low voltage network Network characteristics, and in particular network harmonic distortion, must absolutely be taken into account when choosing capacitors and detuned reactors (if any). 6- Tests to be done after production of the bank At the end of the manufacturing process, a LV switchboard must undergo various routine inspections and tests in the factory, following an established programme. The switchboard must comply with : the appropriate standards the design file (drawings, diagrams and specific requirements) manufacturer mounting instructions in-house instructions. 7- Maintenance must be done every year One month after energising, check all contactor terminal tightening torques. Annual checks General cleanliness of the equipment Filters and ventilation system Terminal tightening torques Proper working order of switching and protective devices Temperature in the premises: -5 C to +40 c max - for normal designs Capacitor capacitance: Consult us if the capacitance value has changed by more than 10 %.
Definitions
The design of the APFC equipment involves the following major parts and the selection of these depends very much on the above system conditions.
Enclosure: protects the APFC system components against the external solid or liquid particles and also provide protection for human beings. PFC Controller: Is the brain of the APFC system, which switches ON / OFF the steps depending on the kvar required in order to maintain the PF close to unity. Bus bars: Bus bar is the electrical conducting path, to which all
the components in the APFC system are connected.
circuit under faulty and normal conditions. Switchgears protect the APFC system against faulty conditions.
in the steps. Proper cable sizing has to be considered for a particular step depending on the rated current and the operating temperature in order to link the various components of the system. Cables loop the power circuit & control circuit in the system.
Protection devices: Protection has to be provided to safeguard the capacitors and other components due to abnormalities in the system. The incoming switchgear of the APFC system should be tripped by protective devices. Reactors: Reactors are used in steps as detuned filters and are connected in series with capacitors. It must be designed to withstand fundamental and harmonic currents. Capacitors: Capacitors forms the core component in APFC
equipment and plays a vital role in power factor correction. Proper selection of capacitors is very much necessary to comply with the applications.
Glossary
SFU SDF ACB MCCB HRC SMC DMC : Switch Fuse Unit : Switch Disconnector and Fuse Unit : Air Circuit Breaker : Molded Case Circuit Breaker : High Rupture Capacity Fuse : Sheet Molding Compound : Dough Molding Compound
DE90087.eps
All AC electrical networks consume two types of power: active power (kW) and reactive power (kvar): The active power P (in kW) is the real power transmitted to loads such as motors, lamps, heaters, computers The electrical active power is transformed into mechanical power, heat or light. The reactive power Q (in kvar) is used only to supply the magnetic circuits of machines, motors and transformers. The apparent power S (in kVA) is the vector combination of active and reactive power. In this representation, the Power Factor (P/S) is equal to cos. The circulation of reactive power in the electrical network has major technical and economic consequences. For the same active power P, a higher reactive power means a higher apparent power and thus, a higher current must be supplied. - The circulation of active power over time is resulting in active energy (in kWh). - The circulation of reactive power over time is resulting in reactive energy (kvarh).
DE90071_r.eps
- In an electrical circuit, the reactive energy is supplied in addition to the active energy.
Power generation
Active energy
Reactive energy
Transmission network
Active energy
Motor
Reactive energy
Due to this higher supplied current, circulation of reactive energy on distribution networks results in: Overload of transformers, Higher temperature rise of the supply cables, Additional losses, Large voltage drops, Higher energy consumption and cost, Less distributed active power. For these reasons, there is a great advantage to generate reactive energy at the load level in order to prevent the unnecessary circulation of current in the network. This is what is known as Power Factor Correction. This is obtained by the connection of capacitors, which produce reactive energy in opposition to the energy absorbed by loads such as motors. The result is a reduced apparent power, and an improved power factor P/S as illustrated on the diagram on the left. The power generation and transmission networks are partially relieved, reducing power losses and making additional transmission capability available. The reactive power is supplied by capacitors. No billing of reactive power by the energy supplier.
Active energy
Transmission network
Active energy
Motor
Reactive energy
Capacitors
Qc
Active energy Active energy
Power generation
Reactive energy
Transmission network
Motor
Reactive energy
DE90071_r.eps
Power generation
Active energy
Transmission network
Active energy
Motor
Reactive energy
Capacitors
A high power factor optimizes an electrical installation by allowing a better usage of the components. The power available at the secondary of an MV/LV transformer can therefore be increased by fitting power factor correction equipment at the low voltage side. The table shows the increased available power at the transformer output by improvement of Power Factor from 0.7 to 1.
Reduction in Switchgear rating Reduction in Line losses / Cable losses Improvement in voltage regulations
The selection of the Power Factor Correction equipment can follow a 4-step process:
Xo1 Xo Ro
Ro1 Load
Power Factor Correction where Load and present Power Factor is Known
The objective is to determine the requested reactive power QC (kvar) to be installed, in order to improve the power factor cos and reduce the apparent power S.
DE90088.eps
Qc
For < , well get: cos > cos and tan < tan. This is illustrated on the diagram in the left. QC can be determined from the formula: QC = P. (tan - tan), which is deduced from the diagram. QC : power of the capacitor bank, in kvar P : active power, in kW tan: tangent of the phase angle - before compensation, tan: tangent of the phase angle - after compensation The parameters and tan can be obtained from the billing data, or from direct measurement in the installation. The following table can be used for direct determination.
Before compensation tan cos 1.73 1.02 0.96 0.91 0.86 0.80 0.75 0.70 0.65 0.59 0.54 0.48 0.5 0.7 0.72 0.74 0.76 0.78 0.8 0.82 0.84 0.86 0.88 0.9 Reactive power (kvar) to be installed per kW of load, in order to get the requested tan or cos tan 0.75 0.62 0.48 0.41 0.33 0.23 0.00 cos 0.8 0.85 0.9 0.925 0.95 0.975 1.00 0.98 0.27 0.21 0.16 0.11 0.05 1.11 0.40 0.34 0.29 0.24 0.18 0.13 0.08 0.03 1.25 0.54 0.48 0.42 0.37 0.32 0.27 0.21 0.16 0.11 0.06 1.32 0.61 0.55 0.50 0.44 0.39 0.34 0.29 0.24 0.18 0.13 0.07 1.40 0.69 0.64 0.58 0.53 0.47 0.42 0.37 0.32 0.26 0.21 0.16 1.50 0.79 0.74 0.68 0.63 0.57 0.52 0.47 0.42 0.37 0.31 0.26 1.73 1.02 0.96 0.91 0.86 0.80 0.75 0.70 0.65 0.59 0.54 0.48
Note: It is widely accepted to use a thumb rule that Motor compensation required in kvar is equal to 33% of the Motor Rating in HP. But it is always suggested to check the name plate of a motor and find out the kvar required using the above mentioned method (using the above table) for accurate compensation.
Example: Consider one 1000kW motor with cos 0.8 (tan = 0.75). In order to get cos= 0.95, it is necessary to install a capacitor bank with a reactive power equal to k x P, i.e. : Qc = 0.42 x 1000 = 420 kvar
Supply Bus
Transformer
The location of low-voltage capacitors in an installation constitutes the mode of compensation, which may be global (one location for the entire installation), by sectors (section-by-section), at load level, or some combination of the latter two. In principle, the ideal compensation is applied at a point of consumption and at the level required at any instant. In practice, technical and economic factors govern the choice. The place for connection of capacitor banks in the electrical network is determined by: Global objective (avoid penalties on reactive energy, relieve of transformer or cables, avoid voltage drops and sags), Operating mode (stable or fluctuating loads), Foreseeable influence of capacitors on the network characteristics, Installation cost.
Circuit breaker
CC
GC IC M M IC IC M
GC IC M
Global compensation
The capacitor bank is connected at the head of the installation to be compensated in order to provide reactive energy for the whole installation. This configuration is convenient for stable and continuous load factor.
Compensation by sectors
The capacitor bank is connected at the head of the feeders supplying one particular sector to be compensated. This configuration is convenient for a wide installation, with workshops having different load factors.
Different types of compensation shall be adopted depending on the performance requirements and complexity of control: Fixed, by connection of a fixed-value capacitor bank, Automatic, by connection of different number of steps, allowing the adjustment of the reactive energy to the requested value, Dynamic, for compensation of highly fluctuating loads.
Fixed compensation
This arrangement uses one or more capacitor(s) to provide a constant level of compensation. Control may be: Manual: by circuit-breaker or load-break switch, Semi-automatic: by contactor, Direct connection to an appliance and switched with it. These capacitors are applied: At the terminals of inductive loads (mainly motors), At bus bars supplying numerous small motors and inductive appliances for which individual compensation would be too costly, In cases where the load factor is reasonably constant.
Automatic compensation
This kind of compensation provides automatic control and adapts the quantity of reactive power to the variations of the installation in order to maintain the targeted cos . The equipment is applied at points in an installation where the active-power and/or reactivepower variations are relatively large, for example: At the busbars of a main distribution switch-board, At the terminals of a heavily-loaded feeder cable. Where the kvar rating of the capacitors is less than, or equal to 15% of the supply transformer rating, a fixed value of compensation is appropriate. Above the 15% level, it is advisable to install an automatically-controlled bank of capacitors. Control is usually provided by contactors. For compensation of highly fluctuating loads, fast and highly repetitive connection of capacitors is necessary, and static switches must be used.
Dynamic compensation
This kind of compensation is requested when fluctuating loads are present, and voltage fluctuations should be avoided. The principle of dynamic compensation is to associate a fixed capacitor bank and an electronic var compensator, providing either leading or lagging reactive currents. The result is a continuously varying and fast compensation, perfectly suitable for loads such as lifts, crushers, spot welding
10
Effects of Harmonics
Higher Neutral current with 3rd harmonic frequency, Neutral over heating and or open neutral condition Telephonic interference, malfunction of sensitive electronics used, failure of telecom hardware
11
12
DB121413.eps
Example: Supply transformer rating: Sn = 630 kVA Total power of non-linear loads: Gh = 150 kVA NLL= (150/630) x 100 = 24%
13
The percentage of non-linear loads NLL is a first indicator for the magnitude of harmonics. The proposed selection of capacitors depending on the value of NLL is given in the diagram below.
NLL (%)
SDuty HDuty Energy
DE90182.eps
10
20
25
50
Linear loads
Non-linear loads
A more detailed estimation of the magnitude of harmonics can be made with measurements. Significant indicators are current harmonic distortion THDi and voltage harmonic distortion THDu, measured at the transformer secondary, with no capacitors connected. According to the measured distortion, different technologies of capacitors shall be selected:
THDi (%)
SDuty HDuty Energy HDuty Energy (with detuned reactor)
10
20
THDu (%)
SDuty HDuty Energy HDuty Energy (with detuned reactor)
Note: The capacitor technology has to be selected according to the most restrictive measurement. Example, a measurement is giving the following results : - THDi = 15 % Harmonic solution. - THDu = 3.5 % HDuty / Energy solution. HDuty or Energy with Detuned Reactor has to be selected.
14
Solution SDuty
Recommended use for Networks with non significant non-linear loads Standard over-current Standard operating temperature Normal switching frequency Standard life expectancy Few non-linear loads Significant over-current Standard operating temperature Significant switching frequency Long life expectancy Significant number of non-linear loads (up to 25%) Significant over-current Extreme temperature conditions Very frequent switching Extra long life expectancy High level of non-linear loads (up to 30%) Significant over-current Standard operating temperature Significant switching frequency Long life expectancy High level of non-linear loads (up to 30%) Significant over-current Extreme temperature conditions Very frequent switching Extra long life expectancy
Max. condition NLL 10% 1.5 IN 55C (class D) 5,000/year Up to 100,000 h* NLL 20% 1.8 IN 55C (class D) 7,000/year Up to 130,000 h* NLL 25% 1.5 IN 70C 10,000/year Up to 160,000 h* NLL 30% 1.8 IN 55C (class D) 7,000/year Up to 130,000 h* NLL 30% 2.5 IN 70C (class D) 10,000/year Up to 160,000 h*
HDuty
Heavy-duty capacitor
Capacitor for special conditions Heavy-duty, harmonic rated capacitor + detuned reactor Energy, harmonic rated capacitor + detuned reactor
*The maximum life expectancy is given considering standard operating conditions: service voltage(UN), service current(IN), 35C ambient temperature. WARNING: The life expectancy will be reduced if capacitors are used in maximum working conditions.
15
Aluminum can capacitors specially designed and engineered to deliver a long working life with low losses in standard, heavy-duty and severe operating conditions. Suitable for Fixed and Automatic PFC, real time compensation, detuned and tuned filters..
Safety
Self-healing. Pressure-sensitive disconnector on all three phases. Discharge resistors fitted. Finger-proof CLAMPTITE terminals to reduce risk of accidental contact and to ensure firm termination (10 to 30 kvar). Special film resistivity and metallization profile for higher thermal efficiency, lower temperature rise and enhanced life expectancy.
PE90131
Compacity
Optimized geometric design (small dimensions and low weight).
Features
High life expectancy up to 160,000 hours. Very high overload capabilities and good thermal and mechanical properties. Economic benefits due to its compact size. Easy maintenance. Unique finger proof termination to ensure tightening.
Construction Voltage range
PE90132
VarplusCan
Power range (three-phase) Peak inrush current Over voltage Over current
PE90130
PE90131
Self-healing + pressure-sensitive disconnector + discharge device (50V/1min) Metallized Polypropylene film with Zn/Al alloy Metallized Polypropylene film with Zn/Al alloy with special profile metallization and wave cut Double metallized paper + Polypropylene film
Impregnation Non-PCB, Non-PCB, sticky Non-PCB, oil Biodegradable (dry) Biodegradable resin resin Ambient temperature Protection Mounting Terminals min -25C to max 55C IP20, indoor Upright Upright, Horizontal Upright Double fast-on + cable ( < 10 kvar) CLAMPTITE - Three-phase terminal with electric shock protection(finger proof) STUD TYPE for more than 30 kvar min -25C to max 70C
16
VarplusCan
Technical Specifications
General characteristics Standards Frequency Losses (dielectric) Losses (total) Capacitance tolerance Voltage Between terminals test Between terminal & Container Discharge resistor Working Conditions Humidity Altitude Over voltage Switching SDuty Operations HDuty Energy Mean Life expectancy Harmonic SDuty Content HDuty Energy Installation characteristics Mounting SDuty position HDuty Energy Fastening & Earthing Indoor, Upright Indoor, Upright & horizontal Indoor, Upright Threaded M12 stud at the bottom IEC 60831-1/-2 50/60Hz < 0.2W/kvar < 0.5W/ kvar - 5%, +10% 2.15 x UN (AC), 10s < 660V - 3 kV(AC), 10s > 660V - 6kV(AC). 10s Fitted, standard discharge time 60s Discharge time 180s on request
95% 2.000 m above sea level 1.1 xUN 8h in every 24h Up to 5,000 switching operations per year Up to 7,000 switching operations per year Up to 10,000 switching operations per year Up to 1,60,000 hrs NLL < 10 % NLL < 20 % NLL < 25 %
Safety Features Safety Self-healing + Pressure-sensitive disconnector for each phase + Discharge device
17
VarplusBox capacitors deliver reliable performance in the most severe application conditions, in Fixed & Automatic PFC systems, in networks with frequently switched loads and harmonic disturbances.
Robustness
Safety
Its unique safety feature electrically disconnects the capacitors safely at the end of their useful life. The disconnectors are installed on each phase, which makes the capacitors very safe, in addition to the protective steel enclosure.
PE90135
Flexibility
These capacitors can be easily mounted inside panels or in a standalone configuration. Suitable for flexible bank configuration.
Features
Metal box enclosure. High power ratings up to 100 kvar. Easy repair and maintenance. Up to 70C temperature. High inrush current withstand up to 400 x IN. Stand-alone PFC equipment. Direct connection to a machine, in harsh environmental conditions.
Construction Voltage range Power range (three-phase) Peak inrush current Over voltage Over current
PE90164
VarplusBox
Self-healing + pressure-sensitive disconnector + discharge device (50V/1min) Metallized Polypropylene film with Zn/Al alloy Metallized Polypropylene film with Zn/Al alloy with special profile metallization and wave cut Double metallized paper + Polypropylene film
Dielectric
PE90135
Impregnation Non-PCB, Non-PCB, sticky Non-PCB, oil Biodegradable (dry) Biodegradable resin resin Ambient temperature Protection Mounting Terminals min -25C to max 55C IP20 Indoor Upright Upright, Horizontal Upright Terminals designed for large cable termination and direct busbar mounting for banking min -25C to max 70C
18
VarplusBox
Technical Specifications
General characteristics Standards Frequency Losses (dielectric) Losses (total) Capacitance tolerance Voltage Between terminals test Between terminal & Container Discharge resistor Working Conditions Humidity Altitude Over voltage Switching SDuty Operations HDuty Energy Mean Life expectancy Harmonic SDuty Content HDuty Energy Installation characteristics Mounting SDuty position HDuty Energy Fastening & Earthing Indoor, Upright Indoor, Upright & horizontal Indoor, Upright Threaded M6 mounting screws at the bottom IEC 60831-1/-2 50/60Hz < 0.2W/kvar < 0.5W/ kvar - 5%, +10% 2.15 x UN (AC), 10s < 660V - 3 kV(AC), 10s > 660V - 6kV(AC). 10s Fitted, standard discharge time 60s Discharge time 180s on request
95% 2.000 m above sea level 1.1 xUN 8h in every 24h Up to 5,000 switching operations per year Up to 7,000 switching operations per year Up to 10,000 switching operations per year Up to 1,60,000 hrs NLL < 10 % NLL < 20 % NLL < 25 %
Safety Features Safety Self-healing + Pressure-sensitive disconnector for each phase + Discharge device
19
Choice of compensation
Customer needs Below table describes typical solutions used in several types of activities. Not adapted Usually (70%) Possibly (20%) Rarely (10%)
In any case, it is recommended to make measurements at site in order to validate the final solution.
SDuty HDuty (upto 20%) Hduty/Energy Energy (upto 25%) + Detuned Reactor
Gh/Sn 15 % 15% < Gh/Sn 25% 25% < Gh/Sn 50%
Pollution rate Industry Food & Beverage Textile Wood Paper - Printing Chemical - Pharmacy Plastic Glass - Ceramic Steel - Metallurgy Automotive Cement - Mines Refinery Micro-electronics Tertiary Supermarkets Hospitals Stadium - Amusement park Hotels - Offices - Bank Insurance Energy & Infrastructures Water Internet farm Wind mills Railways - Subways Airports Harbours Tunnels
20
DB403284 DB403285
T+12+2
(a) (b)
Self Healing
An electric breakdown is possible in the capacitor films due to electric or mechanical over stress. Due to this a small area of metallization will get evaporated and the capacitor will continue to be in service. Continuation of these phenomena will reduce the capacitance value as well as life of the capacitor over a period of time. Self-healing is a process by which the capacitor restores itself in the event of a fault in the dielectric which can happen during high overloads, voltage transients etc.
Figure 2
When insulation breaks down, a short duration arc is formed (figure 1). The intense heat generated by this arc causes the metallization in the vicinity of the arc to vaporise (figure 2). Simultaneously it re-insulates the electrodes and maintains the operation and integrity of the capacitor (figure 3).
Figure 3
Discharge Resistors
A charged Capacitor must be discharged before re-switching, to prevent premature failure. Built-in discharge resistors are used for discharging the capacitor with a delay of one minute as discharge time.
Caution! Do not touch the Capacitor Terminals before Discharging.
21
Reactors have to be associated to capacitor banks for Power Factor Correction in systems with significant non-linear loads, generating harmonics. Capacitors and reactors are configured in a series resonant circuit, tuned so that the series resonant frequency is below the lowest harmonic frequency present in the system. For this reason, this configuration is usually called Detuned Capacitor Bank, and the reactors referred as Detuned Reactors. The use of detuned reactors thus prevents harmonic resonance problems, avoids the risk of overloading the capacitors and contributes to reducing voltage harmonic distortion in the network. The tuning frequency can be expressed by the relative impedance of the reactor (in %), or by the tuning order, or directly in Hz. The most common values of relative impedance are 5.7, 7 and 14%. (14% is used with high level of 3rd harmonic voltages).
Relative Tuning order impedance (%) 5.7 7 14 4.2 3.8 2.7 Tuning frequency @50Hz (Hz) 210 190 135 Tuning frequency @60Hz (Hz) 250 230 160
The selection of the tuning frequency of the reactor capacitor depends on multiple factors: Presence of zero-sequence harmonics (3, 9, ), Need for reduction of the harmonic distortion level, Optimization of the capacitor and reactor components. Frequency of ripple control system if any. To prevent disturbances of the remote control installation, the tuning frequency is to be selected at a lower value than the ripple control frequency. In a detuned filter application, the voltage across the capacitors is higher than the nominal system voltage. Then, capacitors must be designed to withstand higher voltages. Depending on the selected tuning frequency, part of the harmonic currents is absorbed by the detuned capacitor bank. Then, capacitors must be designed to withstand higher currents, combining fundamental and harmonic currents.
22
Working limits
In order to avoid any overload of detuned reactors and capacitors, maximum values of voltage distortion have to be respected. Harmonic voltages and THDu have to be measured at the transformer secondary, with the capacitors connected. The current through the capacitors has to be compared to the rated value. Imp/IN is the ratio of the maximum permissible current to the rated current of the capacitor. The proposed limits are only indicative. In any case, if you have a doubt or if values are higher than the above limits, contact us.
Working THDu Harmonic Voltage Imp / IN limits max. % of the order max SDuty 5 Hduty 7 Harmonic 10 (14% relative impedance) Harmonic 8 (7% relative impedance) Harmonic 6 (5.7% relative impedance) 3 5 7 11 13 3 8 7 3.5 3 0.5 0.5 6 5 5 4 3.5 3.5 3 3 1.5 1.8 1.12 1.19 1.31
23
US, QS
A C B
The recommended rated voltage of capacitors to be used in detuned filter applications with respect to different network service voltage (US) and relative impedance is given in the table below. These values ensure a safe operation in the most stringent operating conditions. Less conservative values may be adopted, but a case by case analysis is necessary.
Capacitor Rated Voltage (UN) V Relative Impedance (%) 5.7% 7% 14% Network Service Voltage (US) V 50Hz 60Hz 400 690 400 480 600 480 480 830 480 480 575 690
UN , QN
Load
Refer to the picture above and consider the following: Us: system voltage (V), QS: requested reactive power (kvar) UN: capacitor rated voltage (V) QN: capacitor rated power (kvar)
DB121411
DB121412
The tuning frequency chosen must ensure that the harmonic current spectrum range is outside the resonance frequency. It is essential to ensure that no remote control frequencies are disturbed.
DB121408
The most common tuning orders are 3.8 or 4.3 (2.7 is used for 3rd order harmonics).
25
The detuned reactors (DR) are designed to protect the capacitors by preventing amplification of the harmonics present on the network.
PE90154
1000 0
Technical specifications
General characteristics Description Degree of protection Insulation class Rated voltage Inductance tolerance per phase Insulation level windings and windings/earth Thermal protection Restored on terminal block 250 V AC, 2 A Three-phase, dry, magnetic circuit, impregnated IP00 H 400 to 690 V - 50 Hz 400 to 600 V - 60 Hz Other voltages on request -5, +5 % 1.1 kV
Lets define the service current (IS) as the current absorbed by the capacitor and detuned reactor assembly, when a purely sinusoidal voltage is applied, equal to the network service voltage (US). IS = Q (kvar) / (3 x US) In order to operate safely in real conditions, a detuned reactor must be designed to accept a maximum permanent current (IMP) taking account of harmonic currents and voltage fluctuations. The following table gives the typical percentage of harmonic currents considered for the different tuning orders.
(%) Tuning order 2.7 3.8 4.2 i3 5 3 2 Harmonic currents i5 i7 15 40 63 12 17 i11 5 5 5 2
A 1.1 factor is applied in order to allow long-term operation at a supply voltage up to (1.1 x US). The resulting maximum permanent current (IMP) is given in the following table:
Tuning order 2.7 3.8 4.2 IMP (times IS) 1.12 1.2 1.3
26
DB114156
Installation
Forced ventilation required Vertical detuned reactor winding for better heat dissipation Electrical connection: > to a screw terminal block for 6.25 and 12.5 kvar detuned reactors > to a drilled pad for 25, 50 and 100 kvar detuned reactors
Note: As the detuned reactor is fitted with thermal protection, it is imperative that the normally closed dry contact be used to disconnect the step in the event of overheating (see drawing at left).
27
DB109701
Effect in Network voltage, Capacitor current and Capacitor voltage without using inrush current limiters
28
LC1-DFK11 LC1-DFK02 LC1-DGK11 LC1-DGK02 LC1-DLK11 LC1-DLK02 LC1-DMK11 LC1-DMK02 LC1-DPK12 LC1-DTK12 LC1-DWK12
0.43 0.43 0.45 0.45 0.6 0.6 0.63 0.63 1.3 1.3 1.65
The power values in the above table are valid for the following conditions:
Prospective peak energising current Maximum operating rate Electrical durability at nominal load LC1-DK LC1-DFK/DGK/DLK/DMK/DPK LC1-DTK/DWK All contactor ratings 200 IN 240 operating cycles/hour 100 operating cycles/hour 3,00,000 operating cycles 2,00,000 operating cycles
400 V 690 V
(2)
29
Parallel operation of capacitor and inrush current limiting capacitors in APFC panels
Power supply
Power supply
Inrush
Capacitor
At capacitor switching while one or more capacitors are connected to the system, the switching capacitor will see a high inrush current. This is due to the current flow from the already connected capacitor(s) (which will act as a source) through the least impedance path set by the switched capacitor along with the current from the main source. This means that when the number of capacitors in parallel increases, the amount of inrush current also increases. Inrush current will damage the capacitor as well as the switching device. In order to prevent inrush current, it is required to use current limiting devices such as Capacitor Duty Contactors or Inductor Coil. Pictorial illustration of the conventional switching and switching using a special capacitor duty contactor is shown in the left.
Power supply
Power supply
Capacitors to be switched on
Power supply
Power supply
Multi Stage Capacitor Switching with Capacitor Duty Contactor Stage 1 - Capacitor is switched through a inrush current limiter
Power supply
Power supply
Stage 2 - Capacitor is switched through Contactor and inrush current limiter Stage 3 - inrush current limiter is removed from the circuit and Capacitor is completely switched on
30
Contactors
Contactors shall be used to switch capacitors in or out of service of each individual step. The contactors shall prevent inrush current to a safe level when the capacitor steps are switched on. There are two types of contactors used for switching each step: Capacitor Duty Contactor Power Contactor Capacitor duty contactors are recommended in APFC equipment to minimize inrush currents experienced during the switching of capacitors. These contactors have special early make contacts with series resistances which dampens the inrush currents. However, when normal Power contactors are used, and when there are no reactors in series, a suitable inductor coil has to be connected in series with the contactor for limiting the inrush currents. Contactors will have to be chosen with care, keeping in mind the following factors which can influence their performance: Contactor shall be re- strike free and adapted for capacitors The rated voltage of the contactor shall be equal to or higher than the maximum network voltage with the power factor correction installation. The contactor shall be designed for continuous current (including harmonics) which can pass the power factor correction installation and/or filter at maximum source voltage, maximum frequency and extreme tolerances of the components, especially capacitors and reactors. Capacitor duty contactors are rated based on nominal reactive power and Power contactors are rated based on the rated operational current. It is recommended to use Special Contactors LC1 D.K which are designed for switching 3 phase Single or Multiple step Capacitor Banks. Capacitor duty contactors are normally rated up to 60kvar. When higher rated steps exist such as 75kvar, 100kvar and above, the following methods can be adopted.
31
S/P
APFC Relay
K1
KN
Capacitors Fig A
S/P
APFC Relay
Example: To switch 120 kvar step, using AC3 Duty contactor, provide four steps of 30kvar VarplusCan capacitor connected to a inductor coil in series. (see Fig C).
Capacitors Fig B
S/P
APFC Relay
K1
IC
Capacitors Fig C
32
PF controllers are microprocessor based, which takes real time inputs from the network, calculate the kvar required and switch on /off capacitors. The microprocessor analyzes the current input signal from the load current transformer and the Voltage tapped from the Bus to produce switching commands to control the contactor ON/OFF of the capacitor steps. Intelligent control by PFC controllers ensures an even utilization of capacitor steps, minimized number of switching operations and optimized life cycle. Feasibility for Four quadrant operation for sensing the energy flow direction becomes necessary for certain applications based on system conditions. The controller placed inside the panel shall have the reliability to withstand the operating temperature of at least 50 C or more.
C/k setting:
C/k value is used in the setting of old generation Power Factor Controllers, however it is found rarely to be used in panels now. C/k value is a threshold value for switching On/Off the capacitor steps by the controller. C/k is the value obtained by dividing first step capacitor power Q to the current transformer ratioK. This setting shall be automatic or can be set manually. The main features of the PF controller must include the following: Automatic C/k- value setting, Connection of different capacitor steps. Automatic detection and usage of optimum capacitor steps. Current measuring 10mA-5A, suitable for connecting CT x/1A and x/5A. Programmable capacitor switching delay Indication for over current Indication for low power factor Fan contact Modern day APFC controllers provide various additional functions like electrical data logging, self diagnostics and system health features and are capable of communication using standard protocols. Additional features can be chosen based on specific requirements of end user which are as follows: Four Quadrant operation Automatic phase reversal correction Various automatic trip conditions can be programmed over current, over voltage Single phase measurement Various metering parameters like V, I, THD-V, Hz, kvar, temp, PF etc.,
33
Varlogic NR6/NR12
operating temperature: 060 C storage temperature: -20 C60 C colour: RAL 7016 standard: EMC: IEC 61326 electrical: IEC/EN 61010-1. panel mounting mounting on 35 mm DIN rail (EN 50022) protection class in panel mounting: front face: IP41 rear face: IP20. display NR6, NR12 type: backlighted screen 65 x 21 mm NRC12 type: backlighted graphic screen 55 x 28 mm. languages: English, French, German, Portuguese, Spanish alarm contact temperature internal probe separate contact to control fan inside the power factor correction bank access to the history of alarm.
PE90161
Inputs
phase to phase or phase to neutral connection insensitive to CT polarity insensitive to phase rotation polarity current input: NR6, NR12 type: CT X/5 A NRC12 type: CT X/5 A et X/1 A.
PE90156
Outputs
potential free output contacts: AC : 1 A/400 V, 2 A/250 V, 5 A/120 V DC : 0,3 A/110 V, 0,6 A/60 V, 2 A/24 V.
Varlogic NRC12
PE90155.eps
Range
Type Number of step output contacts NR6 6 NR12 12 NRC12 12 RT6 6 RT8 8 RT12 12 Accessories Communication RS485 Modbus set for NRC12 Temperature external probe for NRC12 type in addition to internal probe allows measurement at the hottest point inside the capacitork52 Part number 52448 52449 52450 51207 On request On request 52451 52452
34
155 x 158 x 80 0 C - 60 C
Last 5 alarms
2 % 10 to 180 s
Modbus
35
Calculating the number of electrical steps depends on: the number of controller outputs used (e.g. 7) the chosen combination, according to the power of the various steps (e.g. 1.2.2.2).
Combinations 1.1.1.1.1.1 1.1.2.2.2.2 1.2.2.2.2.2 1.1.2.3.3.3 1.2.3.3.3.3 1.1.2.4.4.4 1.2.3.4.4.4 1.2.4.4.4.4 1.2.3.6.6.6 1.2.4.8.8.8 Number of controller outputs used 1 1 1 1 1 1 1 1 1 1 1 2 2 2 3 2 3 2 3 3 3 3 3 3 4 5 4 6 4 6 7 6 7 4 4 6 7 7 9 8 5 5 8 9 6 6 7 7 8 8 9 9 10 11 12 10 11 12
10 12 14 16 18 20 22 11 13 15 17 19 21 23
10 13 16 19 22 25 28 31 12 15 18 21 24 27 30 33 12 16 20 24 28 32 36 40
10 14 18 22 26 30 34 38 42 11 15 19 23 27 31 35 39 43 12 18 24 30 36 42 48 54 60 15 23 31 39 47 55 63 71 79
36
Practical Example: Consider an APFC System of 250 kvar Solution 1: Electrical control 10 x 25 kvar 25 + 25 + 25 + 25 + 25 + 25 + 25 + 25 + 25 + 25 ; sequence : 1.1.1.1.1.1 10 physical steps 10 contactors Refer Contactor Selection 12-step controller ( Varlogic NR12 ) Refer PFC relays- Varlogic Selection Capacitors- VarplusCan 10 x 25kvar Conclusion High Labor, high cost: non-optimised solution. Possible Power levels (kvar) : 25,50,75,100,125,150,175, 200, 225, 250 Solution 2: Electrical control 10 x 25 kvar 25 + 50 + 75 +100 = 10 x 25 kvar electrical; sequence: 1.2.3.4:4 4 physical steps allowing for 10 different power levels 4 contactors (refer contactor selection) 6-step controller ( Varlogic NR6 - refer PFC relays- Varlogic selection) Capacitors - VarplusCan - 2 x 25kvar + 2 x 50kvar + 1 x 100kvar Conclusion Optimised Solution. Optimisation of compensation cubicle - Possible power levels (kvar) The symbol shows the physical step is On for obtaining the Possible power levels.
Possible power levels (kvar) 25 50 75 100 125 150 175 200 225 250
37
Current Transformer
Current transformer (CT) is used in APFC panels for measurement purposes. It steps down load current to a low value (5A) output. The VA rating of CT shall be 5VA or 10VA as the maximum.
DB121445
Where to connect CT
DB121443
Resin Cast CTs or Moulded case CTs are sealed units and have better life than the ordinary tape insulated CTs. Moulded case CTs are usually preferred for lower current ratings and resin cast for higher ratings. Primary current of the CT has to be selected based on the total kvar of the panel. Since CTs and relays are provided in the same panel, the lead wire length will be very short and hence use of 5A secondary is preferred. Ammeter is the only load and considering short distance of wires, 5 to 10VA is selected as a maximum burden. It is recommended to use Class 1 CTs for Commercial measurements
CTB
CTE
CTF
Over voltage
In the event of an over voltage, electrical stress on the capacitor dielectric and the current drawn by the capacitors will increase. The APFC equipment must be switched off in the event of over voltage with suitable over voltage relay.
Under voltage
In the event of under voltage, electrical stress on the capacitor dielectric and the current drawn by the capacitors will decrease. This condition is not harmful. But protection is provided based on customer request to protect system from under voltage.
Over Current
Over current condition is very harmful to all current carrying components. All the switchgears are selected on a higher maximum current carrying capacity. However suitable over current relays with alarm can be used for over current protection.
Thermal Overload
It is taken care by thermal overload relay. The APFC controller must be tripped in cases where internal ambient temperature exceeds the limits. Reactors are also provided with thermal switches, to trip in the case of temperature increase.
Earthing
Two earthing points are provided in the APFC panel for connecting to the earth bus. This will ensure the overall safety of operating personnel and equipment protection in case of earth faults.
Timers
Capacitors require a minimum discharge time of approximately 60 seconds after they are switched off before they can be switched on again. This is to be set in the APFC controller. Capacitors are provided with discharge resistors.
39
Main incomer is used to disconnect the APFC system in case of short circuit, over load and earth fault. The rating of the incomer switchgear will vary depending on rating of the APFC equipment and the required fault current handling capacity. SDF, MCCB or ACB can be used as incomer switchgear depending on the current rating of the APFC equipment and the required fault level. Outgoing protection is provided to protect the individual capacitor step in the APFC equipment. The outgoing protection may be fuses, MCB, MCCB & SDF depending on the rating of the individual capacitor steps, required fault level & customer requirement too. Factor of 1.5 for over loads The factor of 1.5 has arrived by taking into account the combined effects of harmonics, Over Voltage and capacitance tolerance as per standard IEC 60831. 1.5= (1.3 x 1.15 = 1.495) ~ 1.5 where 1.3 - Factor of maximum permissible current of capacitors at rated sinusoidal voltage and rated frequency excluding transients. 1.15- Capacitance tolerance. As per IEC 61921, capacitor current should not be allowed to exceed the above value of 1.5 times hence there is no possibility of increasing the factor. There is no need for reducing the factor since the factors 1.3 and 1.15 are applicable to all types of capacitors. Therefore the safety factor of (1.5 x In) is used for selecting all switchgear.
Other than selecting the rating of the circuit breaker or SDF ,it is essential to protect the capacitor bank by selecting - proper thermal magnetic release setting in case of a circuit breaker - proper fuse rating selection in case of a SDF
40
Example 1: 150kvar/400v 50Hz Capacitor Us = 400V; Qs = 150kvar Un = 400V; Qn = 150kvar In = 150000/4003 = 216A Circuit Breaker Rating = 216 x 1.5 = 324A Select a 400A Circuit Breaker. Circuit Breaker thermal setting = 216 x 1.5 = 324
Conclusion:- Select a Circuit Breaker of 400A with Thermal Setting at 324A and Magnetic Setting ( Short Circuit ) at 3240A
Example 2: 20kvar/400v 50Hz Harmonic Range with 7% Detuned Reactor Us = 400V; Qs = 20kvar Un = 440V; Qn = 22.51kvar Refer: Selection of capacitor with detuned reactor In = 22510/4403 = 29.9A
Individual capacitor protection by circuit breaker Individual capacitor protection by fuses
Circuit Breaker Rating = 29.9*1.5 = 45A Circuit Breaker thermal setting = 29.9 x 1.19 = 35.6A
Conclusion:- Select a Circuit Breaker of 45A ( or next available appropriate range) with Thermal Setting at 35.6A and Magnetic Setting ( Short Circuit ) at 356A
41
Fuse Selection
The rating must be chosen to allow the thermal protection to be set to: 1.5 In for SDuty/HDuty/Energy Capacitors 1.35In for HDuty/Energy with 5.7% Detuned Reactor (Tuning Factor 4.3) 1.2In for HDuty/Energy with 7% Detuned Reactor (Tuning Factor 3.8) 1.15In for HDuty/Energy with 14% Detuned Reactor (Tuning Factor 2.7)
Note: Restrictions in Thermal settings of system with Detuned reactors are due to limitation of IMP (Maximum Permissible current ) of the Detuned reactor.
DB114162
Example 1: 150kvar/400v 50Hz Capacitor Us = 400V; Qs = 150kvar Un = 400V; Qn = 150kvar In = 150000/4003 = 216A SDF Rating = 216*1.5 = 324A Select a SDF of 324A (or next available appropriate range) with
HRC Fuse Rating = 216 *1.5 = 324A (or next available lower rating )
Example 2: 20kvar/400v 50Hz Harmonic Range with 7% Detuned Reactor Us = 400V; Qs = 20kvar Un = 440V; Qn = 22.51kvar Refer: Selection of capacitor with detuned reactor In = 22510/4403 = 29.9A SDF Rating = 29.9*1.5 = 45A
Individual capacitor protection by circuit braker Individual capacitor protection by fuses
HRC Fuse Rating = 29.9 *1.2 = 36A Conclusion:- Select a SDF of 45A (or next available appropriate range) with HRC Fuse Rating 36A (or next available lower rating )
42
General
Indoor installation on firm support in a correctly ventilated local or envelope. Ambient temperature around capacitors must not exceed 35C over one year, 45C over 24hours and 55C max (according to IEC 60831 for -25/D temperature category) (Except for Energy range ( 55C over 24 hours and 70 Max).
PE90130
PE90131
PE90132
Maintain a gap of min. 30mm between capacitor units and min. 30mm between capacitors and panel enclosure for better air circulation Electrical clearance between phases shall be 30mm. For 3ph capacitors keep min. 30mm gap above the top of the capacitor Use capacitor duty contactor or inductor coil in series with two phases in order to limit the inrush current when capacitors are switched in parallel with other energized capacitor units. Please ensure that there is no force by any means on the Pressure Sensitive Disconnector ( PSD) in such a way to affect the operation of PSD when it is required to operate.
PE90164
PE90137
43
PE90135
Clamptite
Stud Type
Electrical connection
2.5 NM
10Nm
Select the cable cross section depending on the kvar & voltage rating see cable Selection User is recommended to use a cable of minimum temperature withstand capacity of 90C. ( recommended is 105 C) Remove conductor insulation of the cable only 10mm for connection. Suitable size lugs have to be used with connecting cable to capacitor terminals in order to avoid heat generation due to improper contacts, in case of VarplusBox or Stud type VarplusCan. Insert conductor fully inside without connecting lugs in the CLAMPTITE, no single strand to come out from the slot, in case of CLAMPTITE terminals. Use pneumatic gun to tighten the screw from top of the CLAMPTITE terminal cover. If not possible, please ensure proper tightness when a screw driver is used to avoid loose termination. Apply a torque of 2.5Nm to tighten For Stud type terminals use a pressure of 20Nm to tighten the Terminals after connecting cable using proper sized lugs. For tightening the VarplusBox terminal studs apply a torque of for M6 studs - 4 Nm for M8 studs - 8 Nm for M10 studs - 12 Nm Mounting Varplus capacitors can be mounted alone or in row. Position: SDuty & Energy : upright HDuty : upright or horizontal Capacitor body shall be earthed at bottom. Capacitor shall be installed in dry place away from heat generating source & avoid dusty atmosphere Proved proper cross ventilation for heat conduction Apply a tightening torque of 8Nm to fix the VarplusBox capacitor on the mounting plates. Tightening torque of 10Nm to be applied on Hexagonal mounting nut for VarplusCan(see picture in the left).
Removable screws Top cover Sliding cover Cable entry hole Removable Terminal Nuts and Washers Fixed Washer and Plate
VarplusBox
Installation step1
Installation step2
44
Step 1
Unpack the VarplusBox HDuty Compact
Step 2
Mounting of Capacitor
Step 3
Cable Connection and Installation Select the Cable cross section depending on the kvar & Voltage rating see Cable Selection User is recommended to use a cable of minimum Temperature withstand capacity of 90C. ( Recommended is 105 C) Remove conductor insulation of the cable only 10mm for connection. Suitable size lugs has to be used with connecting cable to capacitor terminals in order to avoid heat generation due to improper contacts. For the step ratings where VarplusBox HDuty Compact is put in parellel ensure that Maximum power per step Rule is followed. See Maximum power per step-VarplusBox HDuty Compact Follow the instructions below.
Ventilation
Capacitors, contactors, fuses and electrical connections generate heat dissipation (about 2,5W/kvar total or 8W/kvar with series reactors). Specific precautions must be taken in order not to exceed temperature values of -25C/D category around the capacitors inside the cubicle (see paragraph .Installation.). The airflow inside the cubicle must go from bottom to top. The cross section of the top air outlet must be at least equal to 1.1 times the cross-section of the bottom air inlet. For power higher than 200kvar in 2m high cubicle forced ventilation is necessary. It is recommended to install forced ventilation with extractor fans on the cubicle roof. In case of detuned reactors use, it is recommended to install them in a column separate from the capacitors. Preferably reactors at the top and Capacitors at bottom.
Installation instructions
Mounting instructions
45
Detuned reactors
DB121436
DB121437
Installation distance
The minimum distances illustrated opposite must be observed for insulation purposes and to prevent overheating.
46
c) Ventilation
The maximum ambient temperature on the capacitors is +55C. The capacitors have to be placed in the rack in such a way that temperature should not exceed this limit. So, proper ventilation is very much required.
d) Minimum clearances
For better air circulation, a minimum clearence of 30mm between capacitor units and panel enclosure need to be kept. Also maintain a 30mm gap above the top of the capacitor. These are the points to be considered while deciding the number of capacitors in a rack.
47
Restrictions for VarplusBox HDuty Compact There are restrictions in number of VarplusBox HDuty Compact capacitors to be put in parallel due to the restriction in the mounting of these capacitors. All the 4 points discussed above are valid for VarplusBox HDuty Compact except the mounting restrictions. Maximum acceptable power of the assembly is shown in the below table.
Rated voltage 380/400/415 V 440 V 480/525 V 690 V Maximum quantity Maximum acceptable power of units mechanically of the assembly assembled 4 4 4 4 65 kvar (20kvar is the maximum with single unit) 65 kvar (20kvar is the maximum with single unit) 50 kvar (12.5kvar is the maximum with single unit) 50 kvar (12.5kvar is the maximum with single unit)
* Mentioned is the effective Power at the network voltage with Detuned ReactorRefer Capacitor rated voltage with detuned reactor
50/60 Hz
UN < 400V
40 kvar
> 40kvar
50/60 Hz
UN 400V
65 kvar
> 65kvar
48
Size of enclosure
Selecting the enclosure size is an important aspect, which accommodates most of the components in it and the size of the enclosure should be selected properly after a proper layout of components is made, in order to maintain the electrical clearances, ventilation and safety. The heat generating components should be located in such a manner that the heat generated does not come in contact with other components, especially which are sensitive to heat. A proper air flow has to be planned. Size of the enclosure depends on the following points. Total kvar rating of the APFC system. Type of APFC Panel, normal or harmonic filter panel. Number of physical steps. Type of incomer protection (SDF, MCCB or ACB). Type of outgoing protection (HRC Fuses, MCB or MCCB) Type of capacitors (application & construction based) and number of capacitors in the panel. Cable entry - Bottom or Top. Installation type - Outdoor or Indoor. Bus bar sizing and positioning in panels
49
Selection of Fan
It is better to use a fan with thermal switches. In this case the positioning of the fans should be taken care so as to not place the fans thermal switch close to heat dissipating devices so as to avoid any malfunctioning of thermal switch. The selection of fans shall be based on several parameters: Total watt loss including all components in the panel, IP level of the panel. Total volume of the enclosure, Outside ambient temperature, Desired internal ambient temperature. The cubic meter per hour capacity of the fan and the ambient temperature at which the fan can continuously operate are also to be taken into account for deciding the number of fans. The following are the conditions considered for fan calculation, and applicable only for this design, The design conditions are taken in such a way to take care of even extreme temperature of 50C inside the panel ( As the design is for higher temperature, safety factor will be very high ) External Temperature - (Ambient) - 40C Enclosure Dimension (see table)
User can see the recommended practices for Ventilation in following pages with respect to the application
50
Ventilation Practices
Normal operating conditions according to IEC61439-1 Maximum temperature in the electrical room: 40C Average temperature over 24hrs in the electrical room: 35C Average annual temperature in the electrical room: 25C Minimum temperature: 5C Maximum altitude: 2000m Other conditions, contact us
Ventilation rules:
Sduty, HDuty & Energy Range Capacitors, contactors, fuses and electrical connections dissipate heat. These losses are roughly 2-3W/kvar. Calculate the losses roughly and use the table mentioned in the next page ("Minimum number of fans required in the panel"). The following ventilation rules must therefore be complied with: The air within the cubicle must flow upwards. It is recommended that extractor fans be fitted on top of the cubicle. The bottom air inlet must be as low as possible for better ventilation The cross-section of the top air outlet must be more than the cross-section of the bottom air inlet The openings must be compatible with the safety rating (IP) There should be at least 100 mm between the fan and the modules or components The air inlet at the bottom air intake grille must not be obstructed or restricted by a component or module Always let a gap of minimum 600 mm between the back of the panel and the wall for a front open panel and a minimum gap of 1000 mm for the rear opened panel. It allows to have a good ventilation Take into account the pressure drops of the air inlet and outlet. As an indication, the real airflow is 0.6 to 0.75 time the airflow announced by the fan manufacturer
51
Minimum number of fans required in the panel (1) Total losses No. of fans required(2) 0 - 500 W 0 500 - 1500 W 1 1500 - 2400 W 2 2400 - 3000 W 3 3000 - 3500 W 4 3500 - 4500 W 5 4500 - 5000 W 6
(2)
Panel dimension (H x L x W)mm With reactor 1800 x 800 x 800 1800 x 800 x 800 1800 x 800 x 800 2000 x 800 x 800 2000 x 800 x 800 2000 x 800 x 800 2000 x 800 x 800 Without reactor 1800 x 800 x 600 1800 x 800 x 600 1800 x 800 x 600 2000 x 800 x 600 2000 x 800 x 600 2000 x 800 x 600 2000 x 800 x 800
400 8
The number of fans recommended can be followed only if proper ventilation of all the components as per the design rules of the components are implemented with the recommended enclosure sizes and also ensure the recommended mounting distance from the wall.
52
Protection of panels
Protection of panel is to protect both the enclosure and the equipment inside the enclosure, against external influences or conditions such as Mechanical impacts, Corrosion Corrosive solvents Fungus Vermin Solar radiation Icing Moisture (for example, produced by condensation) Explosive atmospheres Protection against contact with hazardous moving parts external to the enclosure (such as fans)
Degree of protection
Degree of protection (IP) is represented by two numerals and two optional characters IP 0-6 0-8 A-D H M S W See standard IEC 60529 Acceptable degree of protection is IP 4X for most of the APFC panels. For dusty environment, a higher level of ingress protection is recommended. A higher IP level gives reduction in cooling and hence special cooling system should be designed (i.e. air conditioning) and better ventilation. When some degree of protection against ingress of water is required, we usually go to IP42. The recommended IP is: IP42
Earthing
Earthing or grounding means literally to make an electrical connection between the ground and a metallic body. The main reason for doing this is safety. The term ground is often used to mean a part of the circuit which has zero volts on it. The main objectives are as follows Provide an alternative path for the fault current to flow so that it will not endanger the user. Ensure that all exposed conductive parts do not reach a dangerous potential. Earthing safety points to be adhered for panels are as follows: Interconnect all earthing points of door mounted metallic components and all non-current carrying parts of control wiring. Connect finally to panel earth bus with suitable cable. Interconnect all earthing points of power circuit components (capacitors, reactors, switches etc). Provide coupling links for connecting the earth bus sections at site. As per standards two earth terminals must be provided for panels. The earth must be designed based on the system fault level at the location.
53
Cable Selection
Cables are used for power circuit and control circuit in APFC system. Choosing a proper and adequate cable is of very much importance. The selection of cable depends on the following points. Voltage Rating. Ampere Capacity. Heating Conditions. Voltage Rating The type and thickness of insulation is determined by the voltage grade. It also helps in determining the minimum size of conductor that is suitable for loads. Ampere Capacity Current carrying capacity of the cable is selected based on the maximum current rating of each step. Heating conditions Include the external thermal conditions which are responsible for determining the temperature increment of a cable. Some important factors to be considered during selection of cables are Ambient temperature Presence of artificial cooling Proximity to heating elements.
54
**The above details/specifications will vary from manufacture to manufacture. Calculations are based on standard operating conditions.
55
56
The means
Principle
Practical rules At the end of the manufacturing process, a LV switchboard must undergo various routine inspections and tests in the factory, following an established programme. The switchboard must comply with: the appropriate standards the design file (drawings, diagrams and specific requirements) manufacturer mounting instructions in-house instructions. Test conditions Tests must be carried out in a clearly defined area, in compliance with applicable legislation or regulations, by qualified personnel. Inspection is carried out in a special area refered to as the test platform which is set aside for final testing. All inspectors must first attend a special training course and must be qualified for working in the proximity of live parts. Inspection means The necessary parts should be suitable for the purpose, correctly calibrated and in good working order: dielectric test station megohmmeter multimeter capacitance meter torque wrench controller test bench
Megohmmeter.
DD382359-65
The reference documents The main international standards are: IEC 60439-1, IEC 60529, IEC 60831-1&2 and IEC 61921. In addition to those items which are specific to the switchboard: drawings, diagrams and specific specifications, quality inspectors should refer to up-to-date documents, integrating revisions and updates: to technical files to in-house rules, etc keeping track of changes in standards in order to have the most recent version at all times
57
The tests
Inspections and tests - Standards:IEC 60439
Practical rules
Carry out all the compulsory inspections and tests and in particular the three routine tests specified by the IEC 60439-1 standards. They complement any type tests which may have been carried out previously by the manufacturer. Standard IEC 60439-1 defines 10 tests to be carried out on electrical switchboards: 7 type tests 3 routine tests. The 7 type tests must be carried out in laboratories and test platforms on cubicles, using real working configurations: complete cubicles fitted with standard components and equipped with VarplusCan and VarplusBox capacitors. The assembly instructions and the 3 routine tests (described below) provide the necessary proof that the switchboard is of the Type Tested Assembly (TTA) or Partially Tested Assembly (PTA) type, and in compliance with standards.
DD382356-69
Dielectrometer
DD382361-69
The tests are satisfactory if there is neither puncture nor flashover between the various parts being tested. Alternative solution: If the switchboard is not subjected to a dielectric test, an insulation measurement must be taken using an insulation tester, with a voltage of at least 500 V (DC). The minimum insulation resistance value must be higher than 1000 ohms/V.
Check for the presence of barriers to protect against direct and indirect contacts with live parts. Visually check that: Contact washers have been used on all assemblies Earthing wires have been fitted to doors The PE conductor is present and must be connected. Finishing Clean the inside of the switchboard Check presence of switchboard identification markers Check external appearance: scratches, paintwork, etc. Reports Create a non quality input document used to quantify faults, evaluate their importance and assign them to relevant department that must take the necessary action to ensure conformity of the electrical switchboard.
Multimeter
Practical rules
Conformity of production: Draw up a list of missing items Draw up a list of equipment which will be dispatched separately from the switchboard. Conformity of operation: Issue a test report This report notes any anomalies detected and the required corrective measures Establish with the customer, a check list of all the points to be checked (example enclosed) Issue a test report that remains in the panel-builders possession but that can be supplied on request this report certifies that all the tests have been carried out and avoids repeating all tests a second time once on site. Each panel-builder has his own test documents.
59
Inspection performed by: .......................................... Signatures: .................................. Q.I: ........................................................................ Device: .............................................................................................................................. kvar V Hz Comments Q.I
Inspection operations 1- dielectric test test 2500 V - 50 Hz - 1 second minimum insulation measurement at 500 V CC 2a- conformity Capacitor (kvar) conform not conform Fuse (A) conform not conform Contactor (type) conform not conform DR (mH) conform not conform DR (A) conform not conform Cable cross-section conform not conform Busbar cross-section conform not conform Connection pads conform not conform Earth circuit conform not conform Component identification conform not conform Conductor identification conform not conform Rating plate conform not conform Documentation conform not conform Frame continuity conform not conform Degree of protection conform not conform Locking conform not conform Presentation, appearance conform not conform Inspection
operations 1 2 3 4 5 6 7 8 9 10 11 12 2b- operation Contactor OK OK OK OK OK OK OK OK OK OK OK OK Controller conform not conform Indication OK OK OK OK OK OK OK OK OK OK OK OK 2c- capacitance measurement C between (mF) Capacitor no. reading
no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no : no :
60
Customer: ............................................................................................... Customer order no: .......................................................................... Project no: ............................................................................................... List of equipment Workpost number: ................................................................................... Description: ...................................................................................... Inspection performed 1- Conformity inspection Enclosures Switchgear Conductors : ..........................................................................................................................................................................
: ........................................................................................................................................................................... : ...........................................................................................................................................................................
2- Mechanical checks :.............................................................................................................................................................................. 3- Electrical continuity of mechanical frames Resistance value : ...................................................... m Visual : ........................... Electrical : ......................
4- Dielectric tests (2500 V - 50 Hz - 1 second minimum) : ......................................................................................................................... 5- Insulation resistance monitoring (500 V DC) : ..................................................................................................................................... Resistance value : ...................................................... m
6- Electrical operating tests : ..................................................................................................................................................................... Observations : .................................................................................................................................................................................................. ............................................................................................................................................................................................................................ ............................................................................................................................................................................................................................ ............................................................................................................................................................................................................................ ............................................................................................................................................................................................................................ Conclusion : equipment accepted without reservations. equipment accepted with reservations. Customer inspection Acceptance test organisation Inspector Q.I manager equipment refused, to be presented for re-inspection.
61
Handling
Packing design is carried out with due consideration to the mode of transport. The packing design shall be based on the following The panel outer dimension. Total weight of the panel. Position of components/ equipments mounted on the front Panel Position of heavy components placed inside the enclosure Place of delivery Mode of transport Type of loading and unloading Storage conditions at site The panels are provided with the following Proper lifting arrangement - for the panel and the complete assembly Protection against rain, spillage of water or liquids by properly covering the entire enclosure. Protection for meters display and instruments on the front panel Desiccants to ensure removal of moisture during transportation and storage. Packing Sequence Application of Hessian cloth against shocks Thermo Cole to protect instruments , meters - refer Fig 1 Application of stretch film & bubble film on the panel Placement of kurlon spacer on the panel to act as spacer between panel and side/top /rear shocks Inclusion of silica gel bags Printing / labels / Signs to indicate upright position - refer Fig 2 Handling of packed Panels Road Transport During Transport it is necessary to protect the panel from vibration & jolting by proper anchoring in the truck bed. While loading and unloading the panel onto or from the truck, use a crane or fork lift, depending on the weight and size of the panel, especially a loading platform is preferable DO not push the panel up or down a ramp. Alternatively, the crate can be lifted vertically by sling and pulley hook, to ensure safety to the panel and personnel. It is also necessary to instruct the site/ commissioning personnel to handle the packing for movement of the panel to erection site by using crane/ trolley truck to avoid physical damage. Sea Transport Steps should be taken to protect the equipment from corrosion, humidity and rain. Suitable marks and indications should be given on the crate for applying slings for lifting on to the ship deck. While shipping, it is necessary for the shipping agency to properly anchor the panel package to prevent roll over during transit
62
Fig 1
Fig 2
Handling
Wrong!
Wrong!
Right!
63
Handling
The APFC Panel builder must, in all contracts, provide the user with a manual on proper procedures to be adopted during the stages of installation, commissioning and maintenance. This is particularly important when customers own staff undertakes erection and commissioning. The manual covers, as a minimum, the following subjects:Unloading, inspection and storage of packed panels. Unpacking and visual inspection of panel. Installation and cabling at final location. Setting of APFC relay. Live checks and observations to be made with supply ON, precautions needed during this phase. Recommendation for routine checks to be made after commissioning. In all cases, copies of operating instruction manual of major components, such as APFC controller and protective relays, published by the respective manufacturers, should be provided to the user for use during installation.
Unpacking
While unpacking, care should be taken to see that no sharp tools hits / hampers the surface of the panel and creates dents and damage the powder coated finish of the enclosure. A copy of this Instruction Manual along with a copy of the schematic drawing of the panel is also put in the panel. The same shall be read carefully and followed for the installation, commissioning, and operation of the equipment by the concerned officials at site. If any damage in transit or loss of components is observed during unpacking, this has to be intimated immediately to the concerned. Two panel keys are also supplied along with the panel.
Handling
Attach ropes to the lifting hooks of the panel for handling. Never use hard tools like crowbars which can damage the panel while handling. As far as possible cranes should be used to lift and move the panels. Do not push and give jerks to the panel, and thereby jerks to the internal components. Keep the panel on a flat, firm, surface in the normal upright position. Do not keep it on side wise or upside down. Do not use the operating handles of MCCB, Switches, etc; for holding while handling.
Storage
Do not store the panel uncovered even for a short period. Keep it covered at least with a polyethylene sheet. If it is not to be erected / commissioned for a longer period, keep the panel with the polyethylene sheet and store in a cool, dry, well ventilated, place, well protected from dust and corrosion, wet atmosphere.
64
Check list - 3 Verify the following points in the installation before commissioning capacitor with detuned reactor banks. Capacitor banks without reactor should not be permitted on the secondary side of transformer circuit which is having capacitor + Detuned reactor banks connected. In this case please remove capacitors without reactors from the same network. Capacitors used with reactors are always of higher voltage than network voltage. Please do not use normal capacitor rated for network voltage. Earthing should be done at capacitors and reactors separately. Make sure all the cable and termination guidelines are followed. Forced cross ventilation should be provided in the installation area. If the filter banks are installed inside the panel the fans need to be provided. Detuned reactors are provided with thermal protection, the Normally Closed (NC) dry contact must be used to disconnect the step in the event of overheating.
Shift the panel to the location where it is required to be installed. a. Position the panel on the foundation and lock the panel base frame with the foundation bolts for free standing panels, by using spirit level and plumber block for achieving horizontal and vertical leveling. b. Position the panel on the wall or structure and fix with wall mounting brackets provided along with the panel. Leveling should be done here also as explained above. Connect the earth conductor to the panel terminal provided on either side of the panel. Use the key provided to open the door of the panel and make sure that electrical connection of all equipments are intact. This is particularly important since vibration in transportation sometimes may have resulted in loose connections. The cable rated for current capacity equivalent to main incomer of panel should be used. Use suitable size lugs for connecting the power cables. Connect the cable to the terminals provided for the power supply. Make sure that the correct phase identification is maintained while connecting the incoming terminals to the panel with respect to phases of supply line, as any mistake will lead to the malfunctioning of relay. Connect the APFC relay as mentioned in the checklists. Check the preset values of the CT secondary current of the relay. It should match with the CT used.
Keep the Auto /off / Manual selector switch in the Auto position. Ensure that the power supply to the Incomer switch is ON from the glowing of the indicating lamps R, Y, and B. Cross check the system voltage. Switch ON the Incomer SFU / MCCB / ACB of the APFC Panel. The APFC relay will be energized and displays the present power factor, when R-Phase load CT connections and phase sequence of voltage (Y & B) are correct.
Note: Before interchanging the C.T. secondary wires, ensure that the terminals of the C.T. are shorted by a small wire, which should be removed after the inter change.
Periodic Maintenance
The following periodic checks are recommended to be conducted Visual check of components and current carrying parts, especially bus bar. Check tightness of all electrical connections. Check current drawn by the individual capacitor steps. Check the operation of contactors manually by switching of the APFC equipment Visually check for rust and corrosions in bolts, nuts and other accessories Visually check for the sparks and burn outs in the panels.
67
Annexures
Annexure I
1. Capacitor installed is not operated. 2. Supply transformer fixed compensation is not provided 3. Capacitors are not selected properly 1. Short circuit rating/setting is improper 2. Harmonic over loading
68
Annexures
Annexure II
Formula -1 The kvar of capacitor will not be same if voltage applied to the capacitor and frequency changes. The example given below shows how to calculate capacitor power in kvar from the measured values at site and name plate details. QM =( fM / fN ) ( UM / UN )2 QN
UN = Rated Voltage fN = Rated Frequency Rated power QN = UM = Measured voltage Measured frequency fM = QM = Available power in kvar
Example: 1. Name plate details 15kvar, 3 phases, 440V, 50Hz capacitor. Measured voltage - 425V Measured frequency - 48.5Hz QM =( fM / fN ) ( UM / UN )2 QN QM = (48.5/50) (425 / 440 )2 15 = 13.57kvar. 2. Name plate details 25kvar, 3 phases, 480V, 60Hz capacitor. Measured voltage - 464V Measured frequency - 59.5Hz QM =( fM / fN ) ( UM / UN )2 QN QM = (59.5/60) x (464/480 )2 x 15 = 23.16kvar.
Formula - 2
The current of capacitor will not be same if voltage applied to the capacitor and frequency changes. The example given below shows how to calculate capacitor current from the measured value at site. IM = IR
( )
U M x fM U R x fR
UN = Rated Voltage fN = Rated Frequency IN = Rated Current UM = Measured Voltage fM = Measured frequency IM = Capacitor Current
Example: Consider a capacitor of 15 kvar, 440V, 50 Hz, 3 Phase Capacitor Rated Current from name plate = 19.68A Measured Values are: Voltage : 425V , Frequency : 49.5 Hz, IM = 19.68
= 18.43A
Note:Please ensure that the measurement is done using true RMS clamp meter 69
Annexures
Formula - 3
Formula for calculating rated current of capacitor with rated supply voltage and frequency. IN = kvar x 103 / (3 x UN) Example 1. 50 kvar , 3 phase, 400V, 50Hz capacitor. IN = kvar x 103 / (3 x UN) IN = (50 1000) / (1.732 400) IN = 72.16 A 2. 37.7 kvar, 3 phases, 525V, 50Hz capacitor. IN = kvar 103 / (3 UN) IN= (37.7 1000) / (1.732 525) IN = 41.45 A
Formula - 4
The capacitance value of a capacitor can be calculated using following formulae for delta connected 3ph capacitor. Assume that capacitance of the three delta connected capacitors are C as shown in the figure. C C C = QN 109 / (4fNUN2) for 3 phase capacitor. Example 1. 15 kvar, 3 phases, 415V, 50Hz capacitor C = 15 109 / ( 4 x 3.142 50 (415 415)) = 138.62F 2. 15 kvar, 3 phases, 440V, 50Hz capacitor C = 15 x 109 / ( 4 x 3.142 x 50 x (440 x440)) = 123.31F
kvar calculation from the measured capacitance value of a capacitor. QM = 2/3 (Ca + Cb + Cc) UN2 (2fN )/ 109 - for three phase capacitor Example 1: Consider you have measured a capacitor rated for 440volts, 50Hz where in measured capacitance value is as follows. 1. 197f ( between R & Y phase ) -Ca 2. 196f ( between B & Y phase ) -Cb 3. 200f ( between R & B phase ) -Cc QM = 2/3 (Ca + Cb + Cc) UN2 (2fN )/ 109 QM = 2/3 (197+196+200)(4402 )23.1450 / 109 = 24.04kvar 2: Consider you have measured a capacitor rated for 480V ,60Hz where in measured capacitance value is as follows. 4. 236f ( between R & Y phase ) - Ca 5. 238f ( between B & Y phase ) - Cb 5. 237f ( between R & B phase ) - Cc QM = 2/3 (Ca + Cb + Cc) UN2 (2fN )/ 109 QM = 2/3(236+238+237)(4802)23.1460/109 = 41.19kvar
The tolerance of capacitance of a capacitor is -5% t0 +10% of capacitor as specified in the IEC Standards.
Formula - 5
70
Notes
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper. Design: Schneider Electric Photos: Schneider Electric 10/2011
PFCED111008EN