Relevo

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

R3N

miniature industrial relays

10 A / 250 V AC • Relays of general application • For plug-in sockets: 35 mm rail mount


acc. to PN-EN 60715; on panel mounting • Miniature dimensions •
Cadmium - free contacts • AC and DC coils
• WT (mechanical indicator + lockable front test button) - standard
features of relays. Relays may be provided with the test buttons (no
latching) and plugs - page 10
• Recognitions, certifications, directives: RoHS,

Contact data
Number and type of contacts 3 CO
Contact material AgNi, AgNi/Au 0,2 µm
Rated / max. switching voltage AC 250 V / 440 V
Min. switching voltage 10 V
Rated load (capacity) AC1 10 A / 250 V AC
AC15 3 A / 120 V 1,5 A / 240 V (B300)
AC3 370 W (single-phase motor)
DC1 10 A / 24 V DC (see Fig. 3)
DC13 0,22 A / 120 V 0,1 A / 250 V (R300)
Min. switching current 5 mA
Max. inrush current 20 A
Rated current 10 A
Max. breaking capacity AC1 2 500 VA
Min. breaking capacity 0,3 W
Contact resistance  100 m
Max. operating frequency
• at rated load AC1 1 200 cycles/hour
• no load 18 000 cycles/hour
Coil data
Rated voltage 50/60 Hz AC 6 ... 240 V
DC 5 ... 220 V
Must release voltage AC:  0,2 Un DC:  0,1 Un
Operating range of supply voltage see Tables 1, 2
Rated power consumption AC 1,6 VA
DC 0,9 W
Insulation according to PN-EN 60664-1
Insulation rated voltage 250 V AC
Rated surge voltage 4 000 V 1,2 / 50 µs
Overvoltage category III
Insulation pollution degree 2
Dielectric strength
• between coil and contacts 2 500 V AC type of insulation: basic
• contact clearance 1 500 V AC type of clearance: micro-disconnection
• pole - pole 2 500 V AC type of insulation: basic
Contact - coil distance
• clearance  2,5 mm
• creepage  4 mm
General data
Operating / release time (typical values) AC: 10 ms / 8 ms DC: 13 ms / 3 ms
Electrical life
• resistive AC1 > 105 10 A, 250 V AC
• cos see Fig. 2
Mechanical life (cycles) > 2 x 107
Dimensions (L x W x H) 27,5 x 21,2 x 35,6 mm
Weight 35 g
Ambient temperature • storage -40...+85 oC
• operating AC: -40...+55 oC DC: -40...+70 oC
Cover protection category IP 40 PN-EN 60529
Environmental protection RTI PN-EN 116000-3
14.07.2014

Shock resistance (NO/NC) 10 g / 5 g


Vibration resistance 5 g 10...150 Hz
The data in bold type pertain to the standard versions of the relays.

www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
R3N
miniature industrial relays

Coil data - DC voltage version Table 1

Coil resistance Coil operating range


Rated voltage Acceptable
Coil code at 20 °C V DC
V DC resistance
 min. (at 20 °C) max. (at 55 °C)
1005 5 28 ± 10% 4,0 5,5
1006 6 40 ± 10% 4,8 6,6
1012 12 160 ± 10% 9,6 13,2
1024 24 640 ± 10% 19,2 26,4
1048 48 2 600 ± 10% 38,4 52,8
1060 60 4 000 ± 10% 48,0 66,0
1080 80 7 100 ± 10% 64,0 88,0
1110 110 13 600 ± 10% 88,0 121,0
1125 125 16 000 ± 10% 100,0 137,5
1220 220 54 000 ± 10% 176,0 242,0
The data in bold type pertain to the standard versions of the relays.

Coil data - AC 50/60 Hz voltage version Table 2

Coil resistance Coil operating range


Rated voltage Acceptable
Coil code at 20 °C V AC
V AC resistance
 min. (at 20 °C) max. (at 55 °C)
5006 6 9,8 ± 10% 4,8 6,6
5012 12 39,5 ± 10% 9,6 13,2
5024 24 158 ± 10% 19,2 26,4
5042 42 470 ± 10% 33,6 46,2
5048 48 640 ± 10% 38,4 52,8
5060 60 930 ± 10% 48,0 66,0
5080 80 1 720 ± 10% 64,0 88,0
5110 110 3 450 ± 10% 88,0 121,0
5115 115 3 610 ± 10% 92,0 127,0
5120 120 3 770 ± 10% 96,0 132,0
5127 127 4 000 ± 10% 101,6 139,0
5220 220 15 400 ± 10% 176,0 242,0
5230 230 16 100 ± 10% 184,0 253,0
5240 240 16 800 ± 10% 192,0 264,0
The data in bold type pertain to the standard versions of the relays.

NEW TECHNOLOGY
The new R2N, R3N, R4N relays are modernized versions
of the R2, R3, R4 relays. The modernization covered
the design of the relays and the manufacturing process.
14.07.2014

www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
R3N
miniature industrial relays

Dimensions - plug-in version (WT), Design


with lockable front test button type T

Improvement of the functionality of the mechanical


indicator (W): it is mounted on an insulation base of
the unit of the movable contacts; the changes provide
the appropriate position in the window in the upper side
Dimensions - plug-in version, with test button of the housing irrespectively of the number of operations
(no latching) or with plug (no manual operation)
performed by the relay.

Application of electronics made in the SMD techno-


logy: additional features L (LED diode) and D (diode)
Test buttons R4P-0001 and plugs R4W-0003 need are located on the printed circuit board; the change
to ordered saparately. They substitute buttons type T.
To exchange by Customer themselves. Information
of the position of the LED diode and optimization
on test buttons (no latching) and plugs - page 10. of the quality and intensity of its light provide certainty
that the relay is in operation status when the LED is on.

Connection diagram (pin side view)

Improvement of the efficiency of the electromagnet:


3 CO an innovational technology of connecting elements has
Note: the indicated polarity of the supply refers to the relays been introduced, which guarantees more reliable opera-
14.07.2014

with extra equipment D - surge suppression element (diode) tion of the relay.
- for DC coils only.
Strengthening of the insulation in the area of the
contact plate: polyamide PA66 has been applied; it has
very good mechanical and electrical parameters and best
thermal properties. 3

www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
R3N
miniature industrial relays

Electrical life at AC resistive load. Fig. 1 Electrical life reduction factor Fig. 2
Switching frequency: 1 200 cycles/hour at AC inductive load
N
Number of cycles

Reduction factor
Power factor
N - electrical life
Breaking capacity [kVA] at AC1

Max. DC breaking capacity Mounting


A - resistive load DC1 Fig. 3
B - inductive load L/R = 40 ms Relays R3N are offered in versions for plug-in sockets,
with WT features as standard (W - mechanical indi-
cator + T - lockable front test button). In these relays is
possibility self-exchange of button type T for test
button R4P-0001 (no latching) or on plug R4W-0003
DC current [A]

(no manual operation). The buttons R4P-0001 and the


plugs R4W-0003 need to ordered saparately.
Relays R3N are designed for: • screw terminals plug-
-in sockets GZT3 ❶ and GZM3 ❶ with clip GZT4-0040
or G4 1052, 35 mm rail mount acc. to PN-EN 60715
or on panel mounting with two M3 screws. Signalling /
protecting modules type M... are available with sockets
(see page 7).
❶ Plug-in sockets GZT3, GZM3 may be linked with inter­­­­con­nection strip
type ZGGZ4 (see page 8).

DC voltage [V]

Contact material selection for different load types

• AgNi - for resistive or inductive loads,


• AgNi/Au 0,2 µm - Au protects the contact surface during storage.
14.07.2014

www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
R3N
miniature industrial relays

Ordering codes

Cover protection
category

Type Contact Number and type Connection Coil code Additional


material of contacts mode features

R 3 N — — — —

Contact material
20 - AgNi
21 - AgNi/Au 0,2 µm see Tables 1, 2 page 2

Number and type of contacts


13 - 3 CO

Cover protection category


2 - in cover, IP 40 version

Connection mode
3 - for plug-in sockets

Additional features
without marks - without additional features
WT - mechanical indicator + lockable front test button ❷
WTL - mechanical indicator + lockable front test button + light indicator (LED diode)
WTD - mechanical indicator + lockable front test button + surge suppression element (diode) ❸
WTLD - mechanical indicator + lockable front test button + light indicator (LED diode) + surge suppression element (diode) ❸

❷ WT - standard features of relays


❸ WTD, WTLD - available only in relays with DC coils
Test buttons (no latching) and plugs need to ordered saparately. They substitute buttons type T. To exchange by Customer themselves.
Information on test buttons (no latching) and plugs - page 10.
• Button R4P-0001-A - orange colour (AC coils)
• Button R4P-0001-D - green colour (DC coils)
• Plug R4W-0003-A - orange colour (AC coils)
• Plug R4W-0003-D - green colour (DC coils)

Note:
For relays with additional features D - surge suppression element (diode) (versions WTD and WTLD) - fixed supply
polarity compulsory for the DC load of coils: +A1(13) / -A2(14). The polarity is indicated on the relay cover. For other
versions of the relays with DC coils any polarity is possible.

Example of ordering code:


R3N-2013-23-1024-WT relay R3N, for plug-in sockets, three changeover contacts, contact material AgNi, coil
voltage 24 V DC, with mechanical indicator and lockable front test button, in cover IP 40
14.07.2014

www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
Plug-in sockets and accessories

GZT3 Connection diagram Dimensions


For R3N
NO
Screw terminals
Max. tightening moment NC
for the terminal: 0,7 Nm
35 mm rail mount ZGGZ4
acc. to PN-EN 60715
or on panel mounting
76,3 x 27 x 42,5(80) mm ❷
Three poles
10 A, 300 V AC COIL

COM
GZT4-0040 G4 1052

Accessories ❶ GZT4-0035 Module type M...

GZM3 Connection diagram Dimensions


For R3N
COM
Screw terminals NO
Max. tightening moment
for the terminal: 0,7 Nm NC
35 mm rail mount ZGGZ4
acc. to PN-EN 60715
or on panel mounting
75 x 27 x 61(82) mm ❷
Three poles
10 A, 300 V AC
COIL
GZT4-0040 G4 1052

Accessories ❶ GZT4-0035 Module type M...

❶ Mounting and sub-assemblies of accessories in the socket - see page 6. Signalling / protecting modules type M... - see page 7.
❷ In the bracket the height of socket with retainer / retractor clip is shown.

Mounting and sub-assemblies of the relay and accessories in the socket

Signalling / protecting module Electromagnetic


type M... relay

Removing the relay from the socket


with a retrainer / retractor clip
Retainer / retractor clip

Description plate
14.07.2014

Screw terminals
plug-in socket

www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
Signalling / protecting modules type M...

For sockets type:


GZT80, GZM80, GZS80, GZMB80, GZT92, GZM92, GZS92, ES 32,
GZT2, GZM2, GZMB2, GZT3, GZM3, GZT4, GZM4, GZMB4

Modules type M... are parallely connected with relay coil.


Polarity P: -A1/+A2. Polarity N: +A1/-A2.

Modules type M... Layout Voltage Type of module ❶ ❷


Module D (polarization P) 6/230 V DC M21P
It limits overvoltage on DC coils.

Module D (polarization N) 6/230 V DC M21N


It limits overvoltage on DC coils.

Module LD (polarization P) 6/24 V DC M31R, M31G


It limits overvoltage on DC coils. 24/60 V DC M32R, M32G
Coil energizing indication. 110/230 V DC M33R, M33G
Module LD (polarization N) 6/24 V DC M41R, M41G
It limits overvoltage on DC coils. 24/60 V DC M42R, M42G
Coil energizing indication. 110/230 V DC M43R, M43G
Module RC 6/24 V AC M51
It protects against EMC disturbance. 24/60 V AC M52
It limits overvoltage. 110/240 V AC M53
Module L 6/24 V AC/DC M61R, M61G
Coil energizing indication. 24/60 V AC/DC M62R, M62G
110/230 V AC/DC M63R, M63G
Module LV 6/24 V AC/DC M91R, M91G
It limits overvoltage on AC and DC coils. 24/60 V AC/DC M92R, M92G
Coil energizing indication. 110/230 V AC/DC M93R, M93G
Module V 24 V AC M71
It limits overvoltage on AC and DC coils. 130 V AC M72
No indication. 230 V AC M73
Module R 110/230 V AC M103
It limits overvoltage on AC coils.

❶ M...R - LED red, M...G - LED green


❷ When ordering modules indicate their color: gray or black.

MODULE type M...

LED red
– M...R

LED green
– M...G
14.07.2014

PRECAUTIONS:
1. Ensure that the parameters of the product described in its specification provide a safety margin for the appropriate operation of the device or system and never use
the product in circumstances which exceed the parameters of the product. 2. Never touch any live parts of the device. 3. Ensure that the product has been connected
correctly. An incorrect connection may cause malfunction, excessive heating or risk of fire. 4. In case of any risk of any serious material loss or death or injuries
of humans or animals, the devices or systems shall be designed so to equip them with double safety system to guarantee their reliable operation.

www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
Interconnection strips ZGGZ4

PIR2-...-00L.
(R2N + GZM2)

ZGGZ4

ZGGZ4 for: Plug-in Relays Interface


sockets for plug-in sockets relays ❸
GZT2 R2N PIR2-...-00L. (R2N + GZM2)
GZM2 PIR3-...-00L. (R3N + GZM3)
GZT3 R3N PIR4-...-00L. (R4N + GZM4)
GZM3
GZT4 R4N
GZM4
❸ Interface relay PIR2 (PIR3, PIR4) is offered as a set: plug-in socket GZM2 (GZM3, GZM4) + miniature
industrial relay R2N (R3N, R4N) + signalling / protecting module type M... + retainer / retractor clip GZT4-0040
+ description plate GZT4-0035.

Interconnection strip ZGGZ4


• designed for the co-operation with plug-in sockets
of miniature industrial relays and with interface relays
PIR2, PIR3 and PIR4, which are equipped with screw
terminals; sockets and relays are mounted on 35 mm
rail mount acc. to PN-EN 60715,
• bridges common input signals (coil terminals
A1 or A2) or output signals - see photo at the top,
• maximum permissible current is 10 A / 250 V AC,
• possibility of connection of 6 sockets or relays,
14.07.2014

• colours of strips: ZGGZ4-1 grey, ZGGZ4-2 black.

www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
Additional features for industrial relays

Industrial relays for plug-in sockets: R2N, R3N, R4N, R15 - 2 CO ❺, R15 - 3 CO ❺ with WT features as stan-
dard (W - mechanical indicator + T - lockable front test button). Detailed information on additional features
of individual relays can be found in the data sheets on the side of ”Ordering codes”.

Type ❹ Description For industrial relays


W mechanical indicator R2N, R3N, R4N,
(R15 - 2 CO, 3 CO ❺)

T lockable front test button, R2N, R3N, R4N,


orange colour - AC coils, (R15 - 2 CO, 3 CO ❺)
green colour - DC coils

L light indicator (LED diode), R2N, R3N, R4N, RY2,


located inside the relay (R15 - 2 CO, 3 CO, 4 CO ❺)
RUC, RUC-M

D surge suppression element (diode) R2N, R3N, R4N, RY2,


- only for DC coils (R15 - 2 CO, 3 CO, 4 CO ❺)

V surge suppression element (varistor) (R15 - 2 CO, 3 CO ❺)


- only for AC coils

K test button without block function (R15 - 4 CO ❺),


RUC

❹ Available combinations:
WT, WTL, WTD, WTLD - in relays R2N, R3N, R4N for plug-in sockets
L, D, LD - in relays RY2 for plug-in sockets
WT, WTL, WTD, WTLD, WTV, WTLV - in relays R15 - 2 CO, 3 CO for plug-in sockets
K, L, D, KL, KD, LD, KLD - in relays R15 - 4 CO for plug-in sockets
K, L, KL - in relays RUC
L - in relays RUC-M
❺ Voltage versions, in covers

Test buttons type T R2N, R3N, R4N

orange
– AC coils

green
– DC coils
14.07.2014

www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
Test buttons (no latching) and plugs

Test buttons (no latching) are recommended for R2N...WT, R3N...WT, R4N...WT, R15...WT 2 CO, R15...WT 3 CO
relays - for appli­cations that do not allow permanent contact latching. By manual operation (pressing the button)
relay contacts can get switched for as long time as long the button is pressed. Contacts return to initial position as soon
as pressure is released from the button. Those operations can be done while the coil is deenergized.

Button R4P-0001 or R15-M404 can be easily inserted by


the Customer after removal of button type T (see Fig. 2).
Button type T can be removed with screwdriver as shown
on Fig. 1.

Fig. 1 Fig. 2

Dimensions - test button R4P-0001 Dimensions - test button R15-M404


for R2N...WT, R3N...WT, R4N...WT for R15...WT 2 CO, R15...WT 3 CO

Types of buttons: Types of buttons:


R4P-0001-A - orange colour (AC coils) R15-M404-A - orange colour (AC coils)
R4P-0001-D - green colour (DC coils) R15-M404-D - green colour (DC coils)

Plugs R4W-0003 or R15-M203 can substitute button type T if manual operation (latching and testing) is not
allowed. Changing button type T for plug can be done by Customer themselves in the same way as changing button
type T for button (no latching).

Dimensions - plug R4W-0003 Dimensions - plug R15-M203


for R2N...WT, R3N...WT, R4N...WT for R15...WT 2 CO, R15...WT 3 CO
14.07.2014

Types of plugs: Types of plugs:


R4W-0003-A - orange colour (AC coils) R15-M203-A - orange colour (AC coils)
R4W-0003-D - green colour (DC coils) R15-M203-D - green colour (DC coils)

10

www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]