Siemens Ruggedcom RSG2488 User Guide

Download as pdf or txt
Download as pdf or txt
You are on page 1of 308

Preface

Introduction 1

Using ROS 2
RUGGEDCOM ROS
v4.3 Device Management 3

System Administration 4

Setup and Configuration 5


User Guide
Troubleshooting 6

For RSG2488

07/2016
RC1292-EN-03
RUGGEDCOM ROS
User Guide

Copyright © 2016 Siemens Canada Ltd


All rights reserved. Dissemination or reproduction of this document, or evaluation and communication of its contents, is not authorized
except where expressly permitted. Violations are liable for damages. All rights reserved, particularly for the purposes of patent application or
trademark registration.
This document contains proprietary information, which is protected by copyright. All rights are reserved. No part of this document may be
photocopied, reproduced or translated to another language without the prior written consent of Siemens Canada Ltd.

Disclaimer Of Liability
Siemens has verified the contents of this document against the hardware and/or software described. However, deviations between the product
and the documentation may exist.
Siemens shall not be liable for any errors or omissions contained herein or for consequential damages in connection with the furnishing,
performance, or use of this material.
The information given in this document is reviewed regularly and any necessary corrections will be included in subsequent editions. We
appreciate any suggested improvements. We reserve the right to make technical improvements without notice.

Registered Trademarks
RUGGEDCOM™ and ROS™ are trademarks of Siemens Canada Ltd.
Other designations in this manual might be trademarks whose use by third parties for their own purposes would infringe the rights of the
owner.

Third Party Copyrights


Siemens recognizes the following third party copyrights:
• Copyright © 2004 GoAhead Software, Inc. All Rights Reserved.

Open Source
RUGGEDCOM ROS contains Open Source Software. For license conditions, refer to the associated License Conditions document.

Security Information
Siemens provides products and solutions with industrial security functions that support the secure operation of plants, machines, equipment
and/or networks. They are important components in a holistic industrial security concept. With this in mind, Siemens' products and solutions
undergo continuous development. Siemens recommends strongly that you regularly check for product updates.
For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and
integrate each component into a holistic, state-of-the-art industrial security concept. Third-party products that may be in use should also be
considered. For more information about industrial security, visit http://www.siemens.com/industrialsecurity .
To stay informed about product updates as they occur, sign up for a product-specific newsletter. For more information, visit http://
support.automation.siemens.com .

Warranty
Refer to the License Agreement for the applicable warranty terms and conditions, if any.

ii
RUGGEDCOM ROS  
User Guide Table of Contents

Table of Contents
Preface ............................................................................................................ xv
Conventions ....................................................................................................................................... xv
Related Documents ............................................................................................................................ xvi
System Requirements ......................................................................................................................... xvi
Accessing Documentation .................................................................................................................. xvi
Training ........................................................................................................................................... xvii
Customer Support ............................................................................................................................. xvii

Chapter 1
Introduction ..................................................................................................... 1
1.1  Features and Benefits ................................................................................................................... 1
1.2  Security Recommendations and Considerations ............................................................................... 3
1.2.1  Security Recommendations ................................................................................................. 3
1.2.2  Credential Files .................................................................................................................. 5
1.2.2.1  SSL Certificates ....................................................................................................... 6
1.2.2.2  SSH Key Pairs .......................................................................................................... 8
1.3  Supported Networking Standards ................................................................................................... 9
1.4  Port Numbering Scheme ............................................................................................................. 10
1.5  Available Services by Port ............................................................................................................ 10
1.6  SNMP Management Interface Base (MIB) Support .......................................................................... 12
1.6.1  Supported Standard MIBs ................................................................................................. 12
1.6.2  Supported Proprietary RUGGEDCOM MIBs .......................................................................... 13
1.6.3  Supported Agent Capabilities ............................................................................................ 13
1.7    SNMP Traps ................................................................................................................................ 14
1.8  ModBus Management Support ..................................................................................................... 16
1.8.1  ModBus Function Codes ................................................................................................... 16
1.8.2  ModBus Memory Map ...................................................................................................... 17
1.8.3  ModBus Memory Formats ................................................................................................. 22
1.8.3.1    Text ..................................................................................................................... 22
1.8.3.2    Cmd ..................................................................................................................... 23
1.8.3.3  Uint16 .................................................................................................................. 23
1.8.3.4  Uint32 .................................................................................................................. 23
1.8.3.5  PortCmd ............................................................................................................... 23
1.8.3.6  Alarm ................................................................................................................... 24
1.8.3.7  PSStatusCmd ......................................................................................................... 24

v
  RUGGEDCOM ROS
Table of Contents User Guide

1.8.3.8  TruthValues .......................................................................................................... 25
1.9  SSH and SSL Keys and Certificates ................................................................................................ 26
1.9.1  Certificate and Keys Life Cycle ........................................................................................... 26
1.9.2  Certificate and Key Requirements ...................................................................................... 27
1.10  Removable Memory .................................................................................................................. 28

Chapter 2
Using ROS ....................................................................................................... 31
2.1  Connecting to ROS ...................................................................................................................... 31
2.1.1  Connecting Directly .......................................................................................................... 31
2.1.2  Connecting via the Network ............................................................................................. 32
2.2    Logging In .................................................................................................................................. 34
2.3  Logging Out ............................................................................................................................... 35
2.4  Using the Web Interface .............................................................................................................. 35
2.5  Using the Console Interface ......................................................................................................... 37
2.6  Using the Command Line Interface .............................................................................................. 39
2.6.1  Available CLI Commands .................................................................................................. 39
2.6.2  Tracing Events ................................................................................................................. 42
2.6.3  Executing Commands Remotely via RSH ............................................................................ 43
2.6.4  Using SQL Commands ...................................................................................................... 44
2.6.4.1  Finding the Correct Table ....................................................................................... 44
2.6.4.2  Retrieving Information ........................................................................................... 45
2.6.4.3  Changing Values in a Table .................................................................................... 46
2.6.4.4  Resetting a Table ................................................................................................... 47
2.6.4.5  Using RSH and SQL ............................................................................................... 47
2.7  Selecting Ports in RUGGEDCOM ROS ............................................................................................. 48
2.8  Managing the Flash File System ................................................................................................... 48
2.8.1  Viewing a List of Flash Files .............................................................................................. 48
2.8.2  Viewing Flash File Details ................................................................................................. 49
2.8.3  Defragmenting the Flash File System ................................................................................. 49
2.9  Accessing BIST Mode ................................................................................................................... 50
2.10  Managing SSH Public Keys ......................................................................................................... 51
2.10.1  Adding a Public Key ....................................................................................................... 51
2.10.2  Viewing a List of Public Keys ........................................................................................... 52
2.10.3  Updating a Public Key .................................................................................................... 53
2.10.4  Deleting a Public Key ...................................................................................................... 53
2.11  Accessing the Boot Loader ......................................................................................................... 54

Chapter 3
Device Management ....................................................................................... 55
3.1  Viewing Product Information ....................................................................................................... 55

vi
RUGGEDCOM ROS  
User Guide Table of Contents

3.2  Viewing CPU Diagnostics ............................................................................................................. 57


3.3  Viewing the Status of the Power Supplies ..................................................................................... 58
3.4  Restoring Factory Defaults ........................................................................................................... 59
3.5  Uploading/Downloading Files ....................................................................................................... 60
3.5.1  Uploading/Downloading Files Using XMODEM .................................................................... 61
3.5.2  Uploading/Downloading Files Using a TFTP Client ............................................................... 62
3.5.3  Uploading/Downloading Files Using a TFTP Server .............................................................. 63
3.5.4  Uploading/Downloading Files Using an SFTP Server ............................................................ 63
3.5.5  Uploading/Downloading Files Using the microSD/microSDHC Card ........................................ 64
3.6  Managing Logs ........................................................................................................................... 64
3.6.1  Viewing Local Logs .......................................................................................................... 65
3.6.2  Clearing Local Logs .......................................................................................................... 65
3.6.3  Configuring the Local System Log ..................................................................................... 66
3.6.4  Managing Remote Logging ............................................................................................... 67
3.6.4.1  Configuring the Remote Syslog Client ..................................................................... 67
3.6.4.2  Viewing a List of Remote Syslog Servers .................................................................. 68
3.6.4.3  Adding a Remote Syslog Server .............................................................................. 68
3.6.4.4  Deleting a Remote Syslog Server ............................................................................ 69
3.7  Managing Ethernet Ports ............................................................................................................. 70
3.7.1  Controller Protection Through Link Fault Indication (LFI) ..................................................... 71
3.7.2  Viewing the Status of Ethernet Ports ................................................................................. 72
3.7.3  Viewing Statistics for All Ethernet Ports ............................................................................. 74
3.7.4  Viewing Statistics for Specific Ethernet Ports ...................................................................... 74
3.7.5  Clearing Statistics for Specific Ethernet Ports ...................................................................... 77
3.7.6  Viewing Statistics for the Ethernet Management Port .......................................................... 77
3.7.7  Clearing Statistics for the Ethernet Management Port ......................................................... 80
3.7.8  Managing SFP Transceivers ............................................................................................... 80
3.7.8.1  Configuring an SFP Port ......................................................................................... 81
3.7.8.2  Monitoring an SFP Port .......................................................................................... 81
3.7.8.3  Displaying Information for an SFP Port .................................................................... 82
3.7.9  Configuring an Ethernet Port ............................................................................................ 83
3.7.10  Configuring Port Rate Limiting ........................................................................................ 85
3.7.11  Configuring Port Mirroring .............................................................................................. 87
3.7.12  Configuring Link Detection ............................................................................................. 88
3.7.13  Detecting Cable Faults .................................................................................................... 90
3.7.13.1  Viewing Cable Diagnostics Results ........................................................................ 90
3.7.13.2  Performing Cable Diagnostics ............................................................................... 92
3.7.13.3  Clearing Cable Diagnostics ................................................................................... 94
3.7.13.4  Determining the Estimated Distance To Fault (DTF) ................................................ 94
3.7.14  Resetting Ethernet Ports ................................................................................................. 94

vii
  RUGGEDCOM ROS
Table of Contents User Guide

3.8  Managing IP Interfaces ................................................................................................................ 95


3.8.1  Configuring the Management IP Interface .......................................................................... 95
3.8.2  Managing Switch IP Interfaces .......................................................................................... 97
3.8.2.1  Viewing a List of Switch IP Interfaces ...................................................................... 97
3.8.2.2  Adding a Switch IP Interface .................................................................................. 97
3.8.2.3  Deleting a Switch IP Interface ................................................................................. 99
3.9  Managing IP Gateways .............................................................................................................. 100
3.9.1  Viewing a List of IP Gateways ......................................................................................... 101
3.9.2  Adding an IP Gateway .................................................................................................... 101
3.9.3  Deleting an IP Gateway .................................................................................................. 102
3.10  Configuring IP Services ............................................................................................................ 103
3.11  Managing Remote Monitoring .................................................................................................. 105
3.11.1  Managing RMON History Controls .................................................................................. 106
3.11.1.1  Viewing a List of RMON History Controls ............................................................. 106
3.11.1.2  Adding an RMON History Control ........................................................................ 106
3.11.1.3  Deleting an RMON History Control ...................................................................... 108
3.11.2  Managing RMON Alarms ............................................................................................... 109
3.11.2.1  Viewing a List of RMON Alarms .......................................................................... 110
3.11.2.2  Adding an RMON Alarm ..................................................................................... 111
3.11.2.3  Deleting an RMON Alarm ................................................................................... 113
3.11.3  Managing RMON Events ............................................................................................... 114
3.11.3.1  Viewing a List of RMON Events ........................................................................... 115
3.11.3.2  Adding an RMON Event ..................................................................................... 115
3.11.3.3  Deleting an RMON Event .................................................................................... 117
3.12  Upgrading/Downgrading Firmware ........................................................................................... 117
3.12.1  Upgrading Firmware ..................................................................................................... 118
3.12.2  Downgrading Firmware ................................................................................................ 118
3.13  Resetting the Device ............................................................................................................... 119
3.14  Decommissioning the Device ................................................................................................... 120

Chapter 4
System Administration ................................................................................... 123
4.1  Configuring the System Information ........................................................................................... 123
4.2  Customizing the Login Screen .................................................................................................... 124
4.3  Configuring Passwords .............................................................................................................. 124
4.4  Clearing Private Data ................................................................................................................. 127
4.5  Enabling/Disabling the Web Interface ......................................................................................... 128
4.6  Managing Alarms ...................................................................................................................... 128
4.6.1  Viewing a List of Pre-Configured Alarms ........................................................................... 129
4.6.2  Viewing and Clearing Latched Alarms .............................................................................. 130
4.6.3  Configuring an Alarm ..................................................................................................... 130

viii
RUGGEDCOM ROS  
User Guide Table of Contents

4.6.4  Authentication Related Security Alarms ............................................................................ 133


4.7  Managing the Configuration File ................................................................................................ 135
4.7.1  Configuring Data Encryption ........................................................................................... 135
4.7.2  Updating the Configuration File ...................................................................................... 137
4.8  Managing an Authentication Server ........................................................................................... 137
4.8.1  Managing RADIUS Authentication .................................................................................... 138
4.8.1.1  Configuring the RADIUS Server ............................................................................. 139
4.8.1.2  Configuring the RADIUS Client .............................................................................. 139
4.8.2  Managing TACACS+ Authentication ................................................................................. 141
4.8.2.1  Configuring TACACS+ .......................................................................................... 141
4.8.2.2  Configuring User Privileges .................................................................................. 142

Chapter 5
Setup and Configuration ................................................................................ 145
5.1  Managing Virtual LANs .............................................................................................................. 145
5.1.1  VLAN Concepts .............................................................................................................. 146
5.1.1.1  Tagged vs. Untagged Frames ............................................................................... 146
5.1.1.2  Native VLAN ........................................................................................................ 146
5.1.1.3  The Management VLAN ....................................................................................... 147
5.1.1.4  Edge and Trunk Port Types ................................................................................... 147
5.1.1.5  Ingress and Egress Rules ...................................................................................... 147
5.1.1.6  Forbidden Ports List ............................................................................................. 148
5.1.1.7  VLAN-Aware and VLAN-Unaware Modes ................................................................ 148
5.1.1.8  GARP VLAN Registration Protocol (GVRP) ............................................................... 149
5.1.1.9  PVLAN Edge ........................................................................................................ 150
5.1.1.10  QinQ ................................................................................................................ 150
5.1.1.11  VLAN Advantages .............................................................................................. 152
5.1.2  Viewing a List of VLANs .................................................................................................. 153
5.1.3  Configuring VLANs Globally ............................................................................................ 153
5.1.4  Configuring VLANs for Specific Ethernet Ports .................................................................. 155
5.1.5  Managing Static VLANs ................................................................................................... 157
5.1.5.1  Viewing a List of Static VLANs .............................................................................. 157
5.1.5.2  Adding a Static VLAN ........................................................................................... 157
5.1.5.3  Deleting a Static VLAN ......................................................................................... 159
5.2  Managing Spanning Tree Protocol .............................................................................................. 161
5.2.1  RSTP Operation .............................................................................................................. 161
5.2.1.1  RSTP States and Roles .......................................................................................... 162
5.2.1.2  Edge Ports .......................................................................................................... 163
5.2.1.3  Point-to-Point and Multipoint Links ....................................................................... 164
5.2.1.4  Path and Port Costs ............................................................................................. 164
5.2.1.5  Bridge Diameter .................................................................................................. 165

ix
  RUGGEDCOM ROS
Table of Contents User Guide

5.2.1.6  eRSTP ................................................................................................................. 165


5.2.1.7  Fast Root Failover ................................................................................................ 166
5.2.2  RSTP Applications ........................................................................................................... 166
5.2.2.1  RSTP in Structured Wiring Configurations .............................................................. 167
5.2.2.2  RSTP in Ring Backbone Configurations .................................................................. 168
5.2.2.3  RSTP Port Redundancy ......................................................................................... 170
5.2.3  MSTP Operation ............................................................................................................. 170
5.2.3.1  MSTP Regions and Interoperability ........................................................................ 171
5.2.3.2  MSTP Bridge and Port Roles .................................................................................. 172
5.2.3.3  Benefits of MSTP ................................................................................................. 173
5.2.3.4  Implementing MSTP on a Bridged Network ............................................................ 174
5.2.4  Configuring STP Globally ................................................................................................. 175
5.2.5  Configuring STP for Specific Ethernet Ports ...................................................................... 176
5.2.6  Configuring eRSTP .......................................................................................................... 179
5.2.7  Viewing Global Statistics for STP ..................................................................................... 181
5.2.8  Viewing STP Statistics for Ethernet Ports .......................................................................... 183
5.2.9  Managing Multiple Spanning Tree Instances ..................................................................... 185
5.2.9.1  Viewing Statistics for Global MSTIs ....................................................................... 185
5.2.9.2  Viewing Statistics for Port MSTIs ........................................................................... 187
5.2.9.3  Configuring the MST Region Identifier ................................................................... 188
5.2.9.4  Configuring a Global MSTI ................................................................................... 189
5.2.9.5  Configuring an MSTI for an Ethernet Port .............................................................. 190
5.2.10  Clearing Spanning Tree Protocol Statistics ...................................................................... 192
5.3  Managing Classes of Service ...................................................................................................... 192
5.3.1  Configuring Classes of Service Globally ............................................................................ 193
5.3.2  Configuring Classes of Service for Specific Ethernet Ports .................................................. 194
5.3.3  Configuring Priority to CoS Mapping ................................................................................ 195
5.3.4  Configuring DSCP to CoS Mapping ................................................................................... 196
5.4  Managing MAC Addresses ......................................................................................................... 198
5.4.1  Viewing a List of MAC Addresses ..................................................................................... 198
5.4.2  Configuring MAC Address Learning Options ..................................................................... 199
5.4.3  Configuring MAC Address Flooding Options ..................................................................... 199
5.4.4  Managing Static MAC Addresses ...................................................................................... 201
5.4.4.1  Viewing a List of Static MAC Addresses ................................................................. 201
5.4.4.2  Adding a Static MAC Address ............................................................................... 201
5.4.4.3  Deleting a Static MAC Address .............................................................................. 203
5.4.5  Purging All Dynamic MAC Addresses ................................................................................ 204
5.5  Managing Time Services ............................................................................................................ 204
5.5.1  Configuring the Time and Date ....................................................................................... 205
5.5.2  Configuring IRIG-B .......................................................................................................... 207

x
RUGGEDCOM ROS  
User Guide Table of Contents

5.5.3  Managing the Precision Time Protocol (PTP) ..................................................................... 209


5.5.3.1  Configuring PTP Globally ...................................................................................... 210
5.5.3.2  Configuring an Ordinary or Transparent Clock ........................................................ 213
5.5.3.3  Configuring a Boundary Clock Slave ...................................................................... 215
5.5.3.4  Configuring the PTP Delay Request Interval ........................................................... 217
5.5.3.5  Configuring a VLAN for PTP Traffic ........................................................................ 218
5.5.3.6  Viewing PTP Clock Statistics ................................................................................. 218
5.5.3.7  Viewing Boundary Clock Slave Statistics ................................................................ 219
5.5.3.8  Viewing Peer Delay Statistics ................................................................................ 220
5.5.4  Configuring the Time Source .......................................................................................... 221
5.5.5  Managing NTP ............................................................................................................... 222
5.5.5.1  Enabling/Disabling NTP Service ............................................................................. 222
5.5.5.2  Configuring NTP Servers ...................................................................................... 223
5.5.6  Viewing the Status of Time Synchronization Subsystems ................................................... 224
5.6  Managing SNMP ....................................................................................................................... 227
5.6.1  Managing SNMP Users .................................................................................................... 228
5.6.1.1  Viewing a List of SNMP Users ............................................................................... 228
5.6.1.2  Adding an SNMP User .......................................................................................... 228
5.6.1.3  Deleting an SNMP User ........................................................................................ 231
5.6.2  Managing Security-to-Group Mapping .............................................................................. 232
5.6.2.1  Viewing a List of Security-to-Group Maps .............................................................. 232
5.6.2.2  Adding a Security-to-Group Map ........................................................................... 233
5.6.2.3  Deleting a Security-to-Group Map ......................................................................... 234
5.6.3  Managing SNMP Groups ................................................................................................. 235
5.6.3.1  Viewing a List of SNMP Groups ............................................................................. 236
5.6.3.2  Adding an SNMP Group ....................................................................................... 236
5.6.3.3  Deleting an SNMP Group ..................................................................................... 238
5.7  Managing Network Discovery .................................................................................................... 238
5.7.1  Network Discovery Concepts ........................................................................................... 239
5.7.1.1  Link Layer Discovery Protocol (LLDP) ..................................................................... 239
5.7.1.2   RUGGEDCOM Discovery Protocol (RCDP) ............................................................... 240
5.7.2  Configuring LLDP Globally ............................................................................................... 241
5.7.3  Configuring LLDP for an Ethernet Port ............................................................................. 242
5.7.4  Enabling/Disabling RCDP ................................................................................................. 243
5.7.5  Viewing Global Statistics and Advertised System Information ............................................. 244
5.7.6  Viewing Statistics for LLDP Neighbors .............................................................................. 245
5.7.7  Viewing Statistics for LLDP Ports ...................................................................................... 246
5.8  Managing Multicast Filtering ...................................................................................................... 247
5.8.1  Managing IGMP ............................................................................................................. 247
5.8.1.1  IGMP Concepts .................................................................................................... 247

xi
  RUGGEDCOM ROS
Table of Contents User Guide

5.8.1.2  Viewing a List of Multicast Group Memberships ..................................................... 251


5.8.1.3  Viewing Forwarding Information for Multicast Groups ............................................ 252
5.8.1.4  Configuring IGMP ................................................................................................ 253
5.8.2  Managing GMRP ............................................................................................................ 254
5.8.2.1  GMRP Concepts ................................................................................................... 255
5.8.2.2  Viewing a Summary of Multicast Groups ............................................................... 257
5.8.2.3  Configuring GMRP Globally .................................................................................. 257
5.8.2.4  Configuring GMRP for Specific Ethernet Ports ........................................................ 258
5.8.2.5  Viewing a List of Static Multicast Groups ............................................................... 260
5.8.2.6  Adding a Static Multicast Group ........................................................................... 260
5.8.2.7  Deleting a Static Multicast Group .......................................................................... 261
5.9  Managing DHCP ........................................................................................................................ 262
5.9.1  DHCP Concepts .............................................................................................................. 263
5.9.1.1  DHCP Snooping ................................................................................................... 263
5.9.1.2  Trusted and Untrusted Ports ................................................................................. 263
5.9.1.3  DHCP Binding Table ............................................................................................. 264
5.9.1.4  DHCP Relay Agent (Option 82) ............................................................................. 264
5.9.1.5  Dynamic ARP Inspection ....................................................................................... 264
5.9.1.6  Preventable Network Attacks ................................................................................ 265
5.9.2  Configuring the DHCP Relay Agent .................................................................................. 267
5.9.3  Configuring DHCP Snooping ............................................................................................ 268
5.9.4  Configuring DHCP Port Parameters .................................................................................. 269
5.9.5  Configuring the Static DHCP Binding Table ....................................................................... 270
5.9.6  Viewing the DHCP Binding Table ..................................................................................... 272
5.9.7  Saving the Static DHCP Binding Table .............................................................................. 273
5.9.8  Viewing ARP Inspection Statistics ..................................................................................... 273
5.9.9  Clearing ARP Inspection Statistics .................................................................................... 274
5.10  Managing Port Security ........................................................................................................... 275
5.10.1  Port Security Concepts .................................................................................................. 275
5.10.1.1  Static MAC Address-Based Authentication ............................................................ 276
5.10.1.2  IEEE 802.1x Authentication ................................................................................ 276
5.10.1.3  IEEE 802.1X Authentication with MAC Address-Based Authentication ..................... 277
5.10.1.4  Assigning VLANS with Tunnel Attributes .............................................................. 277
5.10.2  Viewing a List of Authorized MAC Addresses .................................................................. 278
5.10.3  Configuring Port Security .............................................................................................. 279
5.10.4  Configuring IEEE 802.1X ............................................................................................... 281
5.11  Managing Link Aggregation ..................................................................................................... 282
5.11.1  Link Aggregation Concepts ........................................................................................... 283
5.11.1.1  Rules and Limitations ......................................................................................... 284
5.11.1.2  Link Aggregation and Layer 2 Features ................................................................ 284

xii
RUGGEDCOM ROS  
User Guide Table of Contents

5.11.1.3  Link Aggregation and Physical Layer Features ...................................................... 285


5.11.2  Managing Port Trunks .................................................................................................. 285
5.11.2.1  Viewing a List of Port Trunks .............................................................................. 285
5.11.2.2  Adding a Port Trunk ........................................................................................... 286
5.11.2.3  Deleting a Port Trunk ......................................................................................... 287

Chapter 6
Troubleshooting ............................................................................................ 289
6.1    General .................................................................................................................................... 289
6.2  Ethernet Ports ........................................................................................................................... 290
6.3  Spanning Tree .......................................................................................................................... 290
6.4    VLANs ...................................................................................................................................... 291

xiii
  RUGGEDCOM ROS
Table of Contents User Guide

xiv
RUGGEDCOM ROS  
User Guide Preface

Preface
This guide describes v4.3 of ROS (Rugged Operating System) running on the RUGGEDCOM RSG2488. It contains
instructions and guidelines on how to use the software, as well as some general theory.
It is intended for use by network technical support personnel who are familiar with the operation of networks. It is
also recommended for use by network and system planners, system programmers, and line technicians.

IMPORTANT!
Some of the parameters and options described may not be available depending on variations in the
device hardware. While every attempt is made to accurately describe the specific parameters and
options available, this Guide should be used as a companion to the Help text included in the software.

Conventions
This User Guide uses the following conventions to present information clearly and effectively.

Alerts
The following types of alerts are used when necessary to highlight important information.

DANGER!
DANGER alerts describe imminently hazardous situations that, if not avoided, will result in death or
serious injury.

WARNING!
WARNING alerts describe hazardous situations that, if not avoided, may result in serious injury and/or
equipment damage.

CAUTION!
CAUTION alerts describe hazardous situations that, if not avoided, may result in equipment damage.

IMPORTANT!
IMPORTANT alerts provide important information that should be known before performing a procedure
or step, or using a feature.

NOTE
NOTE alerts provide additional information, such as facts, tips and details.

CLI Command Syntax


The syntax of commands used in a Command Line Interface (CLI) is described according to the following
conventions:

Conventions xv
  RUGGEDCOM ROS
Preface User Guide

Example Description

command Commands are in bold.

command parameter Parameters are in plain text.

command parameter1 parameter2 Parameters are listed in the order they must be entered.

command parameter1 parameter2 Parameters in italics must be replaced with a user-defined value.

command [ parameter1 | parameter2 ] Alternative parameters are separated by a vertical bar (|).
Square brackets indicate a required choice between two or more
parameters.

command { parameter3 | parameter4 } Curly brackets indicate an optional parameter(s).

command parameter1 parameter2 { parameter3 | All commands and parameters are presented in the order they must
parameter4 } be entered.

Related Documents
Other documents that may be of interest include:
• RUGGEDCOM RSG2488 Installation Guide

System Requirements
Each workstation used to connect to the RUGGEDCOM ROS interface must meet the following system
requirements:
• Must have one of the following Web browsers installed:
▫ Microsoft Internet Explorer 8.0 or higher
▫ Mozilla Firefox
▫ Google Chrome
▫ Iceweasel/IceCat (Linux Only)
• Must have a working Ethernet interface compatible with at least one of the port types on the RUGGEDCOM
device
• The ability to configure an IP address and netmask on the computer’s Ethernet interface

Accessing Documentation
The latest user documentation for RUGGEDCOM ROS v4.3 is available online at www.siemens.com/ruggedcom. To
request or inquire about a user document, contact Siemens Customer Support.

xvi Related Documents


RUGGEDCOM ROS  
User Guide Preface

Training
Siemens offers a wide range of educational services ranging from in-house training of standard courses on
networking, Ethernet switches and routers, to on-site customized courses tailored to the customer's needs,
experience and application.
Siemens' Educational Services team thrives on providing our customers with the essential practical skills to make
sure users have the right knowledge and expertise to understand the various technologies associated with critical
communications network infrastructure technologies.
Siemens' unique mix of IT/Telecommunications expertise combined with domain knowledge in the utility,
transportation and industrial markets, allows Siemens to provide training specific to the customer's application.
For more information about training services and course availability, visit www.siemens.com/ruggedcom or
contact a Siemens Sales representative.

Customer Support
Customer support is available 24 hours, 7 days a week for all Siemens customers. For technical support or general
information, contact Siemens Customer Support through any of the following methods:
Online
Visit http://www.siemens.com/automation/support-request to submit a Support Request (SR) or check
on the status of an existing SR.
Telephone
Call a local hotline center to submit a Support Request (SR). To locate a local hotline center, visit http://
www.automation.siemens.com/mcms/aspa-db/en/automation-technology/Pages/default.aspx .

Mobile App
Install the Industry Online Support app by Siemens AG on any Android, Apple iOS or Windows mobile
device and be able to:
• Access Siemens' extensive library of support documentation, including FAQs and manuals
• Submit SRs or check on the status of an existing SR
• Contact a local Siemens representative from Sales, Technical Support, Training, etc.
• Ask questions or share knowledge with fellow Siemens customers and the support community

Training xvii
RUGGEDCOM ROS  
User Guide Preface

Customer Support xviii


RUGGEDCOM ROS Chapter 1
User Guide Introduction

Introduction
Welcome to the RUGGEDCOM ROS v4.3 Software User Guide for the RSG2488. This Guide describes the wide array
of carrier grade features made available by ROS (Rugged Operating System).

CONTENTS
• Section 1.1, “Features and Benefits”
• Section 1.2, “Security Recommendations and Considerations”
• Section 1.3, “Supported Networking Standards”
• Section 1.4, “Port Numbering Scheme”
• Section 1.5, “Available Services by Port”
• Section 1.6, “SNMP Management Interface Base (MIB) Support”
• Section 1.7, “SNMP Traps”
• Section 1.8, “ModBus Management Support”
• Section 1.9, “SSH and SSL Keys and Certificates”
• Section 1.10, “Removable Memory”

Section 1.1

Features and Benefits


The following describes the many features available in RUGGEDCOM ROS and their benefits:
• Cyber Security
Cyber security is an urgent issue in many industries where advanced automation and communications networks
play a crucial role in mission critical applications and where high reliability is of paramount importance. Key
RUGGEDCOM ROS features that address security issues at the local area network level include:
Passwords Multi-level user passwords secures against unauthorized configuration

SSH/SSL Extends capability of password protection to add encryption of passwords and data as they
cross the network

Enable/Disable Ports Capability to disable ports so that traffic cannot pass

802.1Q VLAN Provides the ability to logically segregate traffic between predefined ports on switches

SNMPv3 Encrypted authentication and access security

HTTPS For secure access to the Web interface

• Enhanced Rapid Spanning Tree Protocol (eRSTP)™


Siemens's eRSTP allows the creation of fault-tolerant ring and mesh Ethernet networks that incorporate
redundant links that are pruned to prevent loops. eRSTP implements both STP and RSTP to promote
interoperability with commercial switches, unlike other proprietary ring solutions. The fast root failover feature
of eRSTP provides quick network convergence in case of an RSTP root bridge failure in a mesh topology.

Features and Benefits 1


Chapter 1 RUGGEDCOM ROS
Introduction User Guide

• Quality of Service (IEEE 802.1p)


Some networking applications such as real-time control or VoIP (Voice over IP) require predictable arrival
times for Ethernet frames. Switches can introduce latency in times of heavy network traffic due to the internal
queues that buffer frames and then transmit on a first come first serve basis. RUGGEDCOM ROS supports Class
of Service, which allows time critical traffic to jump to the front of the queue, thus minimizing latency and
reducing jitter to allow such demanding applications to operate correctly. RUGGEDCOM ROS allows priority
classification by port, tags, MAC address, and IP Type of Service (ToS). A configurable weighted fair queuing
algorithm controls how frames are emptied from the queues.
• VLAN (IEEE 802.1Q)
Virtual Local Area Networks (VLAN) allow the segregation of a physical network into separate logical networks
with independent broadcast domains. A measure of security is provided since hosts can only access other hosts
on the same VLAN and traffic storms are isolated. RUGGEDCOM ROS supports 802.1Q tagged Ethernet frames
and VLAN trunks. Port based classification allows legacy devices to be assigned to the correct VLAN. GVRP
support is also provided to simplify the configuration of the switches on the VLAN.
• Simple Network Management Protocol (SNMP)
SNMP provides a standardized method, for network management stations, to interrogate devices from different
vendors. SNMP versions supported by RUGGEDCOM ROS are v1, v2c and v3. SNMPv3 in particular provides
security features (such as authentication, privacy, and access control) not present in earlier SNMP versions.
RUGGEDCOM ROS also supports numerous standard MIBs (Management Information Base) allowing for easy
integration with any Network Management System (NMS). A feature of SNMP is the ability to generate traps
upon system events. RUGGEDCOM NMS, the Siemens management solution, can record traps from multiple
devices providing a powerful network troubleshooting tool. It also provides a graphical visualization of the
network and is fully integrated with all Siemens products.
• Remote Monitoring and Configuration with RUGGEDCOM NMS
RUGGEDCOM NMS (RNMS) is Siemens's Network Management System software for the discovery, monitoring
and management of RUGGEDCOM products and other IP enabled devices on a network. This highly
configurable, full-featured product records and reports on the availability and performance of network
components and services. Device, network and service failures are quickly detected and reported to reduce
downtime.
RNMS is especially suited for remotely monitoring and configuring RUGGEDCOM routers, switches, serial servers
and WiMAX wireless network equipment. For more information, contact a Siemens Sales representative.
• NTP (Network Time Protocol)
NTP automatically synchronizes the internal clock of all RUGGEDCOM ROS devices on the network. This allows
for correlation of time stamped events for troubleshooting.
• Port Rate Limiting
RUGGEDCOM ROS supports configurable rate limiting per port to limit unicast and multicast traffic. This can
be essential to managing precious network bandwidth for service providers. It also provides edge security for
Denial of Service (DoS) attacks.
• Broadcast Storm Filtering
Broadcast storms wreak havoc on a network and can cause attached devices to malfunction. This could be
disastrous on a network with mission critical equipment. RUGGEDCOM ROS limits this by filtering broadcast
frames with a user-defined threshold.
• Port Mirroring
RUGGEDCOM ROS can be configured to duplicate all traffic on one port to a designated mirror port. When
combined with a network analyzer, this can be a powerful troubleshooting tool.
• Port Configuration and Status
RUGGEDCOM ROS allows individual ports to be hard configured for speed, duplex, auto-negotiation, flow
control and more. This allows proper connection with devices that do not negotiate or have unusual settings.
Detailed status of ports with alarm and SNMP trap on link problems aid greatly in system troubleshooting.

2 Features and Benefits


RUGGEDCOM ROS Chapter 1
User Guide Introduction

• Port Statistics and RMON (Remote Monitoring)


RUGGEDCOM ROS provides continuously updating statistics per port that provide both ingress and egress packet
and byte counters, as well as detailed error figures.
Also provided is full support for RMON statistics. RMON allows for very sophisticated data collection, analysis
and detection of traffic patterns.
• Multicast Filtering
RUGGEDCOM ROS supports static multicast groups and the ability to join or leave multicast groups dynamically
using IGMP (Internet Group Management Protocol) or GMRP (GARP Multicast Registration Protocol).
• Event Logging and Alarms
RUGGEDCOM ROS records all significant events to a non-volatile system log allowing forensic troubleshooting.
Events include link failure and recovery, unauthorized access, broadcast storm detection, and self-test
diagnostics among others. Alarms provide a snapshot of recent events that have yet to be acknowledged by
the network administrator. An external hardware relay is de-energized during the presence of critical alarms,
allowing an external controller to react if desired.
• HTML Web Browser User Interface
RUGGEDCOM ROS provides a simple, intuitive user interface for configuration and monitoring via a standard
graphical Web browser or via a standard telcom user interface. All system parameters include detailed
online help to make setup a breeze. RUGGEDCOM ROS presents a common look and feel and standardized
configuration process, allowing easy migration to other managed RUGGEDCOM products.
• Brute Force Attack Prevention
Protection against Brute Force Attacks (BFAs) is standard in RUGGEDCOM ROS. If an external host fails to log in
to the Terminal or Web interfaces after a fixed number of attempts, the service will be blocked for one hour.

Section 1.2

Security Recommendations and Considerations


This section describes important security-related recommendations and suggestions that should be considered
before implementing the RSG2488 on any network.

CONTENTS
• Section 1.2.1, “Security Recommendations”
• Section 1.2.2, “Credential Files”

Section 1.2.1

Security Recommendations
To prevent unauthorized access to the device, note the following security recommendations:

NOTE
Be aware that GPS signals have the potential to be either spoofed or jammed by a malicious third
party.

Authentication
• Replace the default passwords for all user accounts and processes (where applicable) before the device is
deployed.

Security Recommendations and Considerations 3


Chapter 1 RUGGEDCOM ROS
Introduction User Guide

• Use strong passwords with high randomization (i.e. entropy), without repetition of characters. Avoid weak
passwords such as password1, 123456789, abcdefgh, and any dictionary words or proper names in any
combination. For more information about creating strong passwords, refer to the password requirements in
Section 4.3, “Configuring Passwords” .
• Make sure passwords are protected and not shared with unauthorized personnel.
• Passwords should not be re-used across different user names and systems, or after they expire.
• If RADIUS authentication is done remotely, make sure all communications are within the security perimeter or
on a secure channel.

Physical/Remote Access
• Do not connect the device to the Internet. Deploy the device only within a secure network perimeter.
• Restrict physical access to the device to only authorized personnel. A person with malicious intent could extract
critical information, such as certificates, keys, etc. (user passwords are protected by hash codes), or reprogram
the device.
• Control access to the serial console to the same degree as any physical access to the device. Access to the serial
console allows for potential access to the RUGGEDCOM ROS boot loader, which includes tools that may be used
to gain complete access to the device.
• Only enable services that will be used on the device, including physical ports. Unused physical ports could
potentially be used to gain access to the network behind the device.
• If SNMP is enabled, limit the number of IP addresses that can connect to the device and change the community
names. Also configure SNMP to raise a trap upon authentication failures. For more information, refer to
Section 5.6, “Managing SNMP” .
• Avoid using insecure services such as Telnet and TFTP, or disable them completely if possible. These services are
available for historical reasons and are disabled by default.
• Limit the number of simultaneous Web Server, Telnet and SSH sessions allowed.
• Configure remote system logging to forward all logs to a central location. For more information, refer to
Section 3.6, “Managing Logs” .
• Configuration files are provided in the CSV (comma separated values) format for ease of use. Make sure
configuration files are properly protected when they exist outside of the device. For instance, encrypt the files,
store them in a secure place, and do not transfer them via insecure communication channels.
• Management of the configuration file, certificates and keys is the responsibility of the device owner.
Consider using RSA key sizes of at least 2048 bits in length and certificates signed with SHA256 for increased
cryptographic strength. Before returning the device to Siemens for repair, make sure encryption is disabled (to
create a cleartext version of the configuration file) and replace the current certificates and keys with temporary
throwaway certificates and keys that can be destroyed upon the device's return.
• Be aware of any non-secure protocols enabled on the device. While some protocols, such as HTTPS and SSH, are
secure, others, such as Telnet and RSH, were not designed for this purpose. Appropriate safeguards against non-
secure protocols should be taken to prevent unauthorized access to the device/network.
• Configure port security features on access ports to prevent a third-party from launching various attacks that can
harm the network or device. For more information, refer to Section 5.10, “Managing Port Security” .

Hardware/Software
• Make sure the latest firmware version is installed, including all security-related patches. For the latest
information on security patches for Siemens products, visit the Industrial Security website [http://
www.industry.siemens.com/topics/global/en/industrial-security/news-alerts/Pages/alerts.aspx] or the
ProductCERT Security Advisories website [http://www.siemens.com/innovation/en/technology-focus/
siemens-cert/cert-security-advisories.htm] . Updates to Siemens Product Security Advisories can be obtained

4 Security Recommendations
RUGGEDCOM ROS Chapter 1
User Guide Introduction

by subscribing to the RSS feed on the Siemens ProductCERT Security Advisories website, or by following
@ProductCert on Twitter.
• Configure port security features on access ports to prevent a third-party from launching various attacks that can
harm the network or device. For more information, refer to Section 5.10, “Managing Port Security” .
• Enable BPDU Guard on ports where RSTP BPDUs are not expected.
• Use the latest Web browser version compatible with RUGGEDCOM ROS to make sure the most secure Transport
Layer Security (TLS) versions and ciphers available are employed. Additionally, 1/n-1 record splitting is
enabled in the latest web browser versions of Mozilla Firefox, Google Chrome and Internet Explorer, and
mitigates against attacks such as SSL/TLS Protocol Initialization Vector Implementation Information Disclosure
Vulnerability (BEAST) for Non-Controlled (NC) versions of RUGGEDCOM ROS.
• Modbus can be deactivated if not required by the user. If Modbus activation is required, then it is recommended
to follow the security recommendations outlined in this User Guide and to configure the environment according
to defense-in-depth best practices.
• Prevent access to external, untrusted Web pages while accessing the device via a Web browser. This can assist in
preventing potential security threats, such as session hijacking.
• For optimal security, use SNMPv3 whenever possible. Use strong passwords without repetitive strings ( e.g.
abc or abcabc) with this feature. For more information about creating strong passwords, refer to the password
requirements in Section 4.3, “Configuring Passwords” .
• Unless required for a particular network topology, the IP Forward setting should be set to { Disabled } to prevent
the routing of packets.

NOTE
For configuration compatibility reasons, the configured setting will not change when upgrading from
RUGGEDCOM ROS versions older than v4.2.0 to v4.2.0 and newer. This setting is always enabled and
cannot be configured on versions before v4.2.0. For new units with firmware v4.2.0 this setting is
configurable and disabled by default.

Policy
• Periodically audit the device to make sure it complies with these recommendations and/or any internal security
policies.
• Review the user documentation for other Siemens products used in coordination with device for further security
recommendations.

Section 1.2.2

Credential Files
RUGGEDCOM ROS uses security keys to establish secure remote logins (SSH) and Web access (SSL).
It is strongly recommended that a unique SSL certificate and SSH keys be created and provisioned. New
RUGGEDCOM ROS-based units from Siemens will be shipped with a unique certificate and keys preconfigured in
the ssl.crt and ssh.keys flash files.
The default and auto-generated SSL certificates are self-signed. It is recommended to use an SSL certificate that
is either signed by a trusted third-party Certificate Authority (CA) or by an organization's own CA. This technique
is described in the Siemens application note: Creating/Uploading SSH Keys and SSL Certificates to ROS Using
Windows, available from www.siemens.com/ruggedcom.
The sequence of events related to Key Management during an upgrade to RUGGEDCOM ROS v4.3 or later is as
follows:

Credential Files 5
Chapter 1 RUGGEDCOM ROS
Introduction User Guide

NOTE
The auto-generation of SSH keys is not available for Non-Controlled (NC) versions of RUGGEDCOM ROS.

• On first boot, RUGGEDCOM ROS will start the SSH and SSL services using the default keys.
• Immediately after boot, RUGGEDCOM ROS will start to generate a unique SSL certificate and SSH key pair, and
save each one to its corresponding flash file. As each one is created, the corresponding service is immediately
restarted with the new keys.
• At any time during the key generation process, custom keys can be uploaded. The custom keys will take
precedence over both the default and auto-generated keys.
• On subsequent boot, if there is a valid ssl.crt file, the default certificate will not be used for SSL. If there is a
valid ssh.keys file, the default SSH key will not be used.
• At any time, new keys may be uploaded or generated by RUGGEDCOM ROS using the sslkeygen or
sshkeygen CLI commands.

CONTENTS
• Section 1.2.2.1, “SSL Certificates”
• Section 1.2.2.2, “SSH Key Pairs”

Section 1.2.2.1
SSL Certificates
RUGGEDCOM ROS supports SSL certificates that conform to the following specifications:
• X.509 v3 digital certificate format
• PEM format
• For RUGGEDCOM ROS Controlled verions: RSA key pair, 1024, 2048 or 3072 bits; or EC 256, 384 or 521 bits
• For RUGGEDCOM ROS Non-Controlled (NC) verions: RSA key pair, 512 to 2048 bits
The RSA key pair used in the default certificate and in those generated by RUGGEDCOM ROS uses a public key of
1024 bits in length.

NOTE
RSA keys smaller than 2048 bits in length are not recommended. Support is only included here for
compatibility with legacy equipment.

NOTE
The default certificate and keys are common to all RUGGEDCOM ROS versions without a certificate or
key files. That is why it is important to either allow the key auto-generation to complete or to provision
custom keys. In this way, one has at least unique, and at best, traceable and verifiable keys installed
when establishing secure communication with the unit.

NOTE
RSA key generation times increase depending on the key length. 1024 bit RSA keys take less than 5
minutes to generate on a lightly loaded unit, whereas 2048 bit keys may take longer. A typical modern
PC system, however, can generate these keys in seconds.

6 SSL Certificates
RUGGEDCOM ROS Chapter 1
User Guide Introduction

The following (bash) shell script fragment uses the openssl command line utility to generate a self-signed X.509
v3 SSL certificate with a 1024 bit RSA key suitable for use in RUGGEDCOM ROS. Note that two standard PEM files
are required: the SSL certificate and the RSA private key file. These are concatenated into the resulting ssl.crt
file, which may then be uploaded to RUGGEDCOM ROS:

# RSA key size:


BITS=1024
# 20 years validity:
DAYS=7305

# Values that will be stored in the Distinguished Name fields:

COUNTRY_NAME=CA # Two-letter country code


STATE_OR_PROVINCE_NAME=Ontario # State or Province
LOCALITY_NAME=Concord # City
ORGANIZATION=Ruggedcom.com # Your organization's name
ORGANIZATION_CA=${ORGANIZATION}_CA # Your Certificate Authority
COMMON_NAME=RC # The DNS or IP address of the ROS unit
ORGANIZATIONAL_UNIT=ROS # Organizational unit name

# Variables used in the construction of the certificate


REQ_SUBJ="/C=${COUNTRY_NAME}/ST=${STATE_OR_PROVINCE_NAME}/L=${LOCALITY_NAME}/O=${ORGANIZATION}/OU=
${ORGANIZATIONAL_UNIT}/CN=${COMMON_NAME}/"
REQ_SUBJ_CA="/C=${COUNTRY_NAME}/ST=${STATE_OR_PROVINCE_NAME}/L=${LOCALITY_NAME}/O=${ORGANIZATION_CA}/
OU=${ORGANIZATIONAL_UNIT}/"

########################################################################
# Make the self-signed SSL certificate and RSA key pair:

openssl req -x509 -newkey rsa:${BITS} -nodes \


-days ${DAYS} -subj ${REQ_SUBJ} \
-keyout ros_ssl.key \
-out ros_ssl.crt

# Concatenate Cert and Key into a single file suitable for upload to ROS:
# Note that cert must precede the RSA key:
cat ros_ssl.crt ros_ssl.key > ssl.crt

For information on creating SSL certificates for use with RUGGEDCOM ROS in a Microsoft Windows environment,
refer to the following Siemens application note: Creating/Uploading SSH Keys and SSL Certificates to ROS Using
Windows.
The following is an example of a self-signed SSL certificate generated by RUGGEDCOM ROS:

Certificate:
Data:
Version: 3 (0x2)
Serial Number:
ca:01:2d:c0:bf:f9:fd:f2
Signature Algorithm: sha1WithRSAEncryption
Issuer: C=CA, ST=Ontario, L=Concord, O=RuggedCom.com, OU=RC, CN=ROS
Validity
Not Before: Dec 6 00:00:00 2012 GMT
Not After : Dec 7 00:00:00 2037 GMT
Subject: C=CA, ST=Ontario, L=Concord, O=RuggedCom.com, OU=RC, CN=ROS
Subject Public Key Info:
Public Key Algorithm: rsaEncryption
RSA Public Key: (1024 bit)
Modulus (1024 bit):
00:83:e8:1f:02:6b:cd:34:1f:01:6d:3e:b6:d3:45:
b0:18:0a:17:ae:3d:b0:e9:c6:f2:0c:af:b1:3e:e7:
fd:f2:0e:75:8d:6a:49:ce:47:1d:70:e1:6b:1b:e2:
fa:5a:1b:10:ea:cc:51:41:aa:4e:85:7c:01:ea:c3:
1e:9e:98:2a:a9:62:48:d5:27:1e:d3:18:cc:27:7e:
a0:94:29:db:02:5a:e4:03:51:16:03:3a:be:57:7d:

SSL Certificates 7
Chapter 1 RUGGEDCOM ROS
Introduction User Guide

3b:d1:75:47:84:af:b9:81:43:ab:90:fd:6d:08:d3:
e8:5b:80:c5:ca:29:d8:45:58:5f:e4:a3:ed:9f:67:
44:0f:1a:41:c9:d7:62:7f:3f
Exponent: 65537 (0x10001)
X509v3 extensions:
X509v3 Subject Key Identifier:
EC:F3:09:E8:78:92:D6:41:5F:79:4D:4B:7A:73:AD:FD:8D:12:77:88
X509v3 Authority Key Identifier:
keyid:EC:F3:09:E8:78:92:D6:41:5F:79:4D:4B:7A:73:AD:FD:8D:12:77:88
DirName:/C=CA/ST=Ontario/L=Concord/O=RuggedCom.com/OU=RC/CN=ROS
serial:CA:01:2D:C0:BF:F9:FD:F2
X509v3 Basic Constraints:
CA:TRUE
Signature Algorithm: sha1WithRSAEncryption
64:cf:68:6e:9f:19:63:0e:70:49:a6:b2:fd:09:15:6f:96:1d:
4a:7a:52:c3:46:51:06:83:7f:02:8e:42:b2:dd:21:d2:e9:07:
5c:c4:4c:ca:c5:a9:10:49:ba:d4:28:fd:fc:9d:a9:0b:3f:a7:
84:81:37:ca:57:aa:0c:18:3f:c1:b2:45:2a:ed:ad:dd:7f:ad:
00:04:76:1c:f8:d9:c9:5c:67:9e:dd:0e:4f:e5:e3:21:8b:0b:
37:39:8b:01:aa:ca:30:0c:f1:1e:55:7c:9c:1b:43:ae:4f:cd:
e4:69:78:25:5a:a5:f8:98:49:33:39:e3:15:79:44:37:52:da:
28:dd

Section 1.2.2.2
SSH Key Pairs
Controlled versions of RUGGEDCOM ROS support SSH public/private key pairs that conform to the following
specifications:
• PEM format
• DSA key pair, 1024, 2048 or 3072 bits in length; or RSA 1024, 2048 or 3072 bits in length
The DSA key pair used in the default key pair and in those generated by RUGGEDCOM ROS uses a public key of
1024 bits in length.

NOTE
DSA or RSA keys smaller than 2048 bits in length are not recommended, and support is only included
here for compatibility with legacy equipment.

NOTE
DSA/RSA key generation times increase depending on the key length. 1024 bit RSA keys take less than 5
minutes to generate on a lightly loaded unit, whereas 2048 bit keys may take longer. A typical modern
PC system, however, can generate these keys in seconds.

The following (bash) shell script fragment uses the ssh-keygen command line utility to generate a 1024 bit
DSA key suitable for use in RUGGEDCOM ROS. The resulting ssh.keys file, which may then be uploaded to
RUGGEDCOM ROS:

# DSA key size:


BITS=1024

# Make an SSH key pair:


ssh-keygen -t dsa -b 1024 -N '' -f ssh.keys

The following is an example of an SSH key generated by RUGGEDCOM ROS:

Private-Key: (1024 bit)


priv:
00:b2:d3:9d:fa:56:99:a5:7a:ba:1e:91:c5:e1:35:

8 SSH Key Pairs


RUGGEDCOM ROS Chapter 1
User Guide Introduction

77:85:e8:c5:28:36
pub:
6f:f3:9e:af:e6:d6:fd:51:51:b9:fa:d5:f9:0a:b7:
ef:fc:d7:7c:14:59:52:48:52:a6:55:65:b7:cb:38:
2e:84:76:a3:83:62:d0:83:c5:14:b2:6d:7f:cc:f4:
b0:61:0d:12:6d:0f:5a:38:02:67:a4:b7:36:1d:49:
0a:d2:58:e2:ff:4a:0a:54:8e:f2:f4:c3:1c:e0:1f:
9b:1a:ee:16:e0:e9:eb:c8:fe:e8:16:99:e9:61:81:
ed:e4:f2:58:fb:3b:cb:c3:f5:9a:fa:ed:cd:39:51:
47:90:5d:6d:1b:27:d5:04:c5:de:57:7e:a7:a3:03:
e8:fb:0a:d5:32:89:40:12
P:
00:f4:81:c1:9b:5f:1f:eb:ac:43:2e:db:dd:77:51:
6e:1c:62:8d:4e:95:c6:e7:b9:4c:fb:39:9c:9d:da:
60:4b:0f:1f:c6:61:b0:fc:5f:94:e7:45:c3:2b:68:
9d:11:ba:e1:8a:f9:c8:6a:40:95:b9:93:7c:d0:99:
96:bf:05:2e:aa:f5:4e:f0:63:02:00:c7:c2:52:c7:
1a:70:7c:f7:e5:fe:dd:3d:57:02:86:ae:d4:89:20:
ca:4b:46:80:ea:de:a1:30:11:5c:91:e2:40:d4:a3:
82:c5:40:3b:25:8e:d8:b2:85:cc:f5:9f:a9:1d:ea:
0a:ac:77:95:ee:d6:f7:61:e3
Q:
00:d5:db:48:18:bd:ec:69:99:eb:ff:5f:e1:40:af:
20:80:6d:5c:b1:23
G:
01:f9:a1:91:c0:82:12:74:49:8a:d5:13:88:21:3e:
32:ea:f1:74:55:2b:de:61:6c:fd:dd:f5:e1:c5:03:
68:b4:ad:40:48:58:62:6c:79:75:b1:5d:42:e6:a9:
97:86:37:d8:1e:e5:65:09:28:86:2e:6a:d5:3d:62:
50:06:b8:d3:f9:d4:9c:9c:75:84:5b:db:96:46:13:
f0:32:f0:c5:cb:83:01:a8:ae:d1:5a:ac:68:fb:49:
f9:b6:8b:d9:d6:0d:a7:de:ad:16:2b:23:ff:8e:f9:
3c:41:16:04:66:cf:e8:64:9e:e6:42:9a:d5:97:60:
c2:e8:9e:f4:bc:8f:6f:e0

Section 1.3

Supported Networking Standards


The following networking standards are supported by RUGGEDCOM ROS:
Standard 10 Mbps Ports 100 Mbps Ports 1000 Mbps Ports Notes

IEEE 802.3x ü ü ü Full Duplex Operation

IEEE 802.3z ü 1000Base-LX

IEEE 802.3ab ü 1000Base-Tx

IEEE 802.1D ü ü ü MAC Bridges

IEEE 802.1Q ü ü ü VLAN (Virtual LAN)

IEEE 802.1p ü ü ü Priority Levels

Supported Networking Standards 9


Chapter 1 RUGGEDCOM ROS
Introduction User Guide

Section 1.4

Port Numbering Scheme


For quick identification, each port on a RSG2488 device is assigned a number in the form of [slot]/[number]. Slots
and ports along the top row are numbered from left to right. Slots and ports along the bottom row are numbered
from right to left. Therefore, the third port in the first slot would be labeled 1/3, where 1 represents the slot and 3
represents the port number. All port numbers are silk-screened on the device.

1 4 1 4 1 4 1 2

4 1 4 1 4 1 2 1

Figure 1:  RSG2488 Port Numbering (Typical)

Use these numbers to configure applicable features on select ports.

Section 1.5

Available Services by Port


The following table lists the services available under RUGGEDCOM ROS. This table includes the following
information:
• Services
The service supported by the device.
• Port Number
The port number associated with the service.
• Port Open
The port state, whether it is always open and cannot be closed, or open only, but can be configured.

NOTE
In certain cases, the service might be disabled, but the port can still be open (e.g. TFTP).

• Port Default
The default state of the port (i.e. open or closed).
• Access Authorized
Denotes whether the ports/services are authenticated during access.
Service Enabled/
Services Port Number Access Authorized Note
Disabled

Telnet TCP/23 Disabled Yes Only available


through two
management
interfaces.

10 Port Numbering Scheme


RUGGEDCOM ROS Chapter 1
User Guide Introduction

Service Enabled/
Services Port Number Access Authorized Note
Disabled

HTTP TCP/80 Enabled —


(configurable),
redirects to 443

HTTPS TCP/443 Enabled Yes


(configurable)

RSH TCP/512 Disabled Yes Only available


(configurable) through two
management
interfaces.

TFTP UDP/69 Disabled No Only available


(configurable) through two
management
interfaces.

SFTP TCP/22 Enabled Yes Only available


through two
management
interfaces.

SNMP UDP/161 Disabled Yes Only available


(configurable) through two
management
interfaces.

SNTP UDP/123 Enabled No Only available


(configurable) through two
management
interfaces.

SSH TCP/22 Enabled Yes Only available


through two
management
interfaces.

ICMP — Enabled No

TACACS+ TCP/49 Disabled Yes


(configurable) (configurable)

RADIUS UDP/1812 to send Disabled Yes Only available


(configurable), (configurable) through two
opens random port management
to listen to interfaces.

Remote Syslog UDP/514 Disabled No Only available


(configurable) (configurable) through two
management
interfaces.

TCP Modbus (Server) TCP/502 Disabled No Only available


(configurable) through two
management
interfaces.

TCP Modbus (Switch) TCP/502 Disabled No


(configurable)

DHCP, DHCP Agent UDP/67, 68 sending Disabled No


msg if enabled - if (configurable)
received, always
come to CPU,

Available Services by Port 11


Chapter 1 RUGGEDCOM ROS
Introduction User Guide

Service Enabled/
Services Port Number Access Authorized Note
Disabled
dropped if service
not configured

PTP (IEEE 1588) UDP/319 Disabled No


(configurable)
UDP/320

Section 1.6

SNMP Management Interface Base (MIB) Support


RUGGEDCOM ROS supports a variety of standard MIBs, proprietary RUGGEDCOM MIBs and Agent Capabilities MIBs,
all for SNMP (Simple Network Management Protocol).

CONTENTS
• Section 1.6.1, “Supported Standard MIBs”
• Section 1.6.2, “Supported Proprietary RUGGEDCOM MIBs”
• Section 1.6.3, “Supported Agent Capabilities”

Section 1.6.1

Supported Standard MIBs


RUGGEDCOM ROS supports the following standard MIBs:
Standard MIB Name Title

RFC 2578 SNMPv2-SMI Structure of Management Information Version 2

RFC 2579 SNMPv2-TC Textual Convention s for SMIv2

RFC 2580 SNMPv2-CONF Conformance Statements for SMIv2

IANAifType Enumerated Values of the ifType Object Defined ifTable defined in IF-
MIB

RFC 1907 SNMPv2-MIB Management Information Base for SNMPv2

RFC 2011 IP-MIB SNMPv2 Management Information Base for Internet Protocol using
SMIv2

RFC 2012 TCP-MIB SNMPv2 Management Information Base for the Transmission Control
Protocol using SMIv2

RFC 2013 UDP-MIB Management Information Base for the UDP using SMIv2

RFC 2863 IF-MIB The Interface Group MIB

RFC 2819 RMON-MIB Remote Network Monitoring (RMON) management Information base

RFC 4188 BRIDGE-MIB Definitions of Managed Objects for Bridges

RFC 4318 RSTP-MIB Definitions of Managed Objects for Bridges with Rapid Spanning Tree
Protocol

12 SNMP Management Interface Base (MIB) Support


RUGGEDCOM ROS Chapter 1
User Guide Introduction

Standard MIB Name Title

RFC 3411 SNMP-FRAMEWORK-MIB An Architecture for Describing Simple Network Management


Protocol (SNMP) Management Framework

RFC 3414 SNMP-USER-BASED-SM-MIB User-based Security Model (USM) for Version 3 of the Simple
Network Management Protocol (SNMPv3)

RFC 3415 SNMP-VIEW-BASED-ACM-MIB View-bsed Access Control Model (VACM) for the Simple
Management Protocol (SNMP)

IEEE 802.1AB-2005 LLDP-MIB Management Information Base Module for LLDP Configuration,
Statistics, Local System Data and Remote Systems Data Components

RFC 4363 Q-BRIDGE-MIB Definitions of Managed Objects for Bridges with Traffic Classes,
Multicast Filtering, and Virtual LAN Extensions

IEEE C37.238-2011 IEEEC37.238-MIB IEEE Standard Profile for Use of IEEE 1588 Precision Time Protocol in
Power System Applications

Section 1.6.2

Supported Proprietary RUGGEDCOM MIBs


RUGGEDCOM ROS supports the following proprietary RUGGEDCOM MIBs:
File Name MIB Name Description

RUGGEDCOM-MIB.mib RUGGEDCOM-MIB RUGGEDCOM enterprise SMI

RUGGEDCOM-TRAPS-MIB.mib RUGGEDCOM-TRAPS-MIB RUGGEDCOM traps definition

RUGGEDCOM-SYS-INFO-MIB.mib RUGGEDCOM-SYS-INFO-MIB General system information about


RUGGEDCOM device

RUGGEDCOM-STP-MIB.mib RUGGEDCOM-STP-MIB Management for RSTP protocol

RUGGEDCOM-GPS-MIB.mib RUGGEDCOM-GPS-MIB RUGGEDCOM proprietary MIB to control and


monitor GPS module

RUGGEDCOM-IRIGB-MIB.mib RUGGEDCOM-IRIGB-MIB RUGGEDCOM proprietary MIB to control and


monitor IRIG-B module

RUGGEDCOM-NTP-MIB.mib RUGGEDCOM-NTP-MIB RUGGEDCOM proprietary MIB to control and


monitor NTP module

RUGGEDCOM-PTP1588-MIB.mib RUGGEDCOM-PTP1588-MIB RUGGEDCOM proprietary MIB to control and


monitor PTP1588 module

RUGGEDCOM-TIMECONFIG-MIB.mib RUGGEDCOM-TIMECONFIG-MIB RUGGEDCOM proprietary MIB to control and


monitor TIMECONFIG module

Section 1.6.3

Supported Agent Capabilities


RUGGEDCOM ROS supports the following agent capabilities for the SNMP agent:

Supported Proprietary RUGGEDCOM MIBs 13


Chapter 1 RUGGEDCOM ROS
Introduction User Guide

NOTE
For information about agent capabilities for SNMPv2, refer to RFC 2580 [http://tools.ietf.org/html/
rfc2580].

File Name MIB Name Supported MIB

RC-SNMPv2-MIB-AC.mib RC-SNMPv2-MIB-AC SNMPv2-MIB

RC-UDP-MIB-AC.mib RC-UDP-MIB-AC UDP-MIB

RC-TCP-MIB-AC.mib RC-TCP-MIB-AC TCP-MIB

RC-SNMP-USER-BASED-SM-MIB-AC.mib RC-SNMP-USER-BASED-SM-MIB-AC SNMP-USER-BASED-SM-MIB-AC

RC-SNMP-VIEW-BASED-ACM-MIB-AC.mib RC-SNMP-VIEW-BASED-ACM-MIB-AC SNMP-VIEW-BASED-ACM-MIB-AC

RC-IF-MIB-AC.mib RC-IF-MIB-AC IF-MIB

RC-BRIDGE-MIB-AC.mib RC-BRIDGE-MIB-AC BRIDGE-MIB

RC-RMON-MIB-AC.mib RC-RMON-MIB-AC RMON-MIB

RC-Q-BRIDGE-MIB-AC.mib RC-Q-BRIDGE-MIB-AC Q-BRIDGE-MIB

RC-IP-MIB-AC.mib RC-IP-MIB-AC IP-MIB

RC-LLDP-MIB-AC.mib RC-LLDP-MIB-AC LLDP-MIB

RC_RSTP-MIB-AC.mib RC_RSTP-MIB-AC RSTP-MIB

RC-RUGGEDCOM-STP-AC-MIB.mib RC-RUGGEDCOM-STP-AC-MIB RUGGEDCOM-STP-MIB

RC-RUGGEDCOM-SYS-INFO-MIB-AC.mib RC-RUGGEDCOM-SYS-INFO-MIB-AC RUGGEDCOM-SYS-INFO-MIB

RC-RUGGEDCOM-TRAPS-MIB-AC.mib RC-RUGGEDCOM-TRAPS-MIB-AC RUGGEDCOM-TRAPS-MIB

RC-GPS-MIB-AC.mib RC-GPS-MIB-AC GPS-MIB

RC-IRIGB-MIB-AC.mib RC-IRIGB-MIB-AC IRIGB-MIB

RC-NTP-MIB-AC.mib RC-NTP-MIB-AC NTP-MIB

RC-PTP1588-MIB-AC.mib RC-PTP1588-MIB-AC PTP1588-MIB

RC-TIMECONFIG-MIB-AC.mib RC-TIMECONFIG-MIB-AC TIMECONFIG-MIB

Section 1.7

SNMP Traps
The device generates the following standard traps:

Table: Standard Traps

Trap MIB

linkDown IF-MIB

linkUp

authenticationFailure SNMPv2-MIB

coldStart

14 SNMP Traps
RUGGEDCOM ROS Chapter 1
User Guide Introduction

Trap MIB

newRoot BRIDGE-MIB

topologyChage

risingAlarm RMON-MIB

fallingAlarm

lldpRemoteTablesChange LLDP-MIB

The device also generates the following proprietary traps:


Table: Proprietary Traps
Trap MIB

genericTrap RUGGEDCOM-TRAPS-MIB

powerSupplyTrap

swUpgradeTrap

cfgChangeTrap

weakPasswordTrap

defaultKeysTrap

Generic traps carry information about events in their severity and description objects. They are sent at the same
time an alarm is generated for the device. The following are examples of RUGGEDCOM generic traps:

NOTE
Information about generic traps can be retrieved using the CLI command alarms. For more
information about the alarms command, refer to Section 2.6.1, “Available CLI Commands” .

Table: Generic Traps
Trap Severity

heap error Alert

NTP server failure notification

real time clock failure Error

failed password Warning

MAC address not learned by switch fabric Warning

received looped back BPDU Error

received two consecutive confusing BPDUs on port, forcing down Error

The device generates the following traps when specific events occur:
Table: Event-Based Traps
Trap MIB Event

rcRstpNewTopology RUGGEDCOM-STP-MIB This trap is generated when the device


topology becomes stable after a topology
change occurs on a switch port.

rcGpsStatusChange RUGGEDCOM-GPS-MIB.mib This trap is generated if the status of the GPS


module is changed.

SNMP Traps 15
Chapter 1 RUGGEDCOM ROS
Introduction User Guide

Trap MIB Event

rcIrigbStatusChange RUGGEDCOM-IRIGB-MIB.mib This trap is generated if the status of the


IRIG-B module is changed.

ieeeC37238EventOfstExceedLimit IEEEC37-238-MIB.mib This trap is generated if the offset from


Master of the IEEE 1588 Slave exceeds the
configured limit.

ieeeC37238EventChangeOfMaster IEEEC37-238-MIB.mib This trap is generated if new master has


been selected.

ieeeC37238EventMasterStepChange IEEEC37-238-MIB.mib This trap is generated if a step change


occurred in current grandmaster time.

ieeeC37238EventPTPServiceStarted IEEEC37-238-MIB.mib This trap is generated if PTP service has


started.

ieeeC37238EventPTPServiceStopped IEEEC37-238-MIB.mib This trap is generated if PTP service has


stopped.

Section 1.8

ModBus Management Support


Modbus management support in RUGGEDCOM devices provides a simple interface for retrieving basic status
information. ModBus support simplifies the job of SCADA (Supervisory Control and Data Acquisition) system
integrators by providing familiar protocols for retrieving RUGGEDCOM device information. ModBus provides
mostly read-only status information, but there are some writable registers for operator commands.
The ModBus protocol PDU (Protocol Data Unit) format is as follows:
Function Code Data

CONTENTS
• Section 1.8.1, “ModBus Function Codes”
• Section 1.8.2, “ModBus Memory Map”
• Section 1.8.3, “ModBus Memory Formats”

Section 1.8.1

ModBus Function Codes


RUGGEDCOM devices support the following ModBus function codes for device management through ModBus:

NOTE
While RUGGEDCOM devices have a variable number of ports, not all registers and bits apply to all
products.
Registers that are not applicable to a particular device return a zero (0) value. For example, registers
referring to serial ports are not applicable to RUGGEDCOM switch devices.

16 ModBus Management Support


RUGGEDCOM ROS Chapter 1
User Guide Introduction

Read Input Registers or Read Holding Registers — 0x04 or 0x03


Example PDU Request
Function Code 1 Byte 0x04(0x03)

Starting Address 2 Bytes 0x0000 to 0xFFFF (Hexadecimal)


128 to 65535 (Decimal)

Number of Input Registers 2 Bytes Bytes 0x0001 to 0x007D

Example PDU Response


Function Code 1 Byte 0x04(0x03)
a
Byte Count 1 Byte 2xN
a
Number of Input Registers N x 2 Bytes
a
The number of input registers

Write Multiple Registers — 0x10


Example PDU Request
Function Code 1 Byte 0x10

Starting Address 2 Bytes 0x0000 to 0xFFFF

Number of Input Registers 2 Bytes Bytes 0x0001 to 0x0079


b
Byte Count 1 Byte 2xN
b
Registers Value N x 2 Bytes Value of the register
b
The number of input registers

Example PDU Response


Function Code 1 Byte 0x10

Starting Address 2 Bytes 0x0000 to 0xFFFF

Number of Registers 2 Bytes 1 to 121 (0x79)

Section 1.8.2

ModBus Memory Map


The following details how ModBus process variable data is mapped.

Product Info
The following data is mapped to the Productinfo table:
Address #Registers Description (Reference Table in UI) R/W Format

0000 16 Product Identification R Text

0010 32 Firmware Identification R Text

ModBus Memory Map 17


Chapter 1 RUGGEDCOM ROS
Introduction User Guide

Address #Registers Description (Reference Table in UI) R/W Format

0040 1 Number of Ethernet Ports R Uint16

0042 1 Number of Alarms R Uint16

0043 1 Power Supply Status R PSStatusCmd

0044 1 FailSafe Relay Status R TruthValue

0045 1 ErrorAlarm Status R TruthValue

Product Write Register


The following data is mapped to various tables:
Address #Registers Description (Reference Table in UI) R/W Format

0080 1 Clear Alarms W Cmd

0081 2 Reset Ethernet Ports W PortCmd

0083 2 Clear Ethernet Statistics W PortCmd

Alarms
The following data is mapped to the alarms table:
Address #Registers Description (Reference Table in UI) R/W Format

0100 64 Alarm 1 R Alarm

0140 64 Alarm 2 R Alarm

0180 64 Alarm 3 R Alarm

01C0 64 Alarm 4 R Alarm

0200 64 Alarm 5 R Alarm

0240 64 Alarm 6 R Alarm

0280 64 Alarm 7 R Alarm

02C0 64 Alarm 8 R Alarm

Ethernet Port Status


The following data is mapped to the ethPortStats table:
Address #Registers Description (Reference Table in UI) R/W Format

03FE 2 Port Link Status R PortCmd

Ethernet Statistics
The following data is mapped to the rmonStats table:

18 ModBus Memory Map


RUGGEDCOM ROS Chapter 1
User Guide Introduction

Address #Registers Description (Reference Table in UI) R/W Format

0400 2 Port s1/p1 Statistics - Ethernet In Packets R Uinst32

0402 2 Port s1/p2 Statistics - Ethernet In Packets R Uinst32

0404 2 Port s1/p3 Statistics - Ethernet In Packets R Uinst32

0406 2 Port s1/p4 Statistics - Ethernet In Packets R Uinst32

0408 2 Port s2/p1 Statistics - Ethernet In Packets R Uinst32

040A 2 Port s2/p2 Statistics - Ethernet In Packets R Uinst32

040C 2 Port s2/p3 Statistics - Ethernet In Packets R Uinst32

040E 2 Port s2/p4 Statistics - Ethernet In Packets R Uinst32

0410 2 Port s3/p1 Statistics - Ethernet In Packets R Uinst32

0412 2 Port s3/p2 Statistics - Ethernet In Packets R Uinst32

0414 2 Port s3/p3 Statistics - Ethernet In Packets R Uinst32

0416 2 Port s3/p4 Statistics - Ethernet In Packets R Uinst32

0418 2 Port s4/p1 Statistics - Ethernet In Packets R Uinst32

041A 2 Port s4/p2 Statistics - Ethernet In Packets R Uinst32

041C 2 Port s4/p3 Statistics - Ethernet In Packets R Uinst32

041E 2 Port s4/p4 Statistics - Ethernet In Packets R Uinst32

0420 2 Port s5/p1 Statistics - Ethernet In Packets R Uinst32

0422 2 Port s5/p2 Statistics - Ethernet In Packets R Uinst32

0424 2 Port s5/p3 Statistics - Ethernet In Packets R Uinst32

0426 2 Port s5/p4 Statistics - Ethernet In Packets R Uinst32

0428 2 Port s6/p1 Statistics - Ethernet In Packets R Uinst32

042A 2 Port s6/p2 Statistics - Ethernet In Packets R Uinst32

042C 2 Port s6/p3 Statistics - Ethernet In Packets R Uinst32

042E 2 Port s6/p4 Statistics - Ethernet In Packets R Uinst32

0430 2 Port s7/p1 Statistics - Ethernet In Packets R Uinst32

0432 2 Port s7/p2 Statistics - Ethernet In Packets R Uinst32

0434 2 Port s8/p1 Statistics - Ethernet In Packets R Uinst32

0436 2 Port s8/p2 Statistics - Ethernet In Packets R Uinst32

0440 2 Port s1/p1 Statistics - Ethernet Out Packets R Uinst32

0442 2 Port s1/p2 Statistics - Ethernet Out Packets R Uinst32

0444 2 Port s1/p3 Statistics - Ethernet Out Packets R Uinst32

0446 2 Port s1/p4 Statistics - Ethernet Out Packets R Uinst32

0448 2 Port s2/p1 Statistics - Ethernet Out Packets R Uinst32

044A 2 Port s2/p2 Statistics - Ethernet Out Packets R Uinst32

ModBus Memory Map 19


Chapter 1 RUGGEDCOM ROS
Introduction User Guide

Address #Registers Description (Reference Table in UI) R/W Format

044C 2 Port s2/p3 Statistics - Ethernet Out Packets R Uinst32

044E 2 Port s2/p4 Statistics - Ethernet Out Packets R Uinst32

0450 2 Port s3/p1 Statistics - Ethernet Out Packets R Uinst32

0452 2 Port s3/p2 Statistics - Ethernet Out Packets R Uinst32

0454 2 Port s3/p3 Statistics - Ethernet Out Packets R Uinst32

0456 2 Port s3/p4 Statistics - Ethernet Out Packets R Uinst32

0458 2 Port s4/p1 Statistics - Ethernet Out Packets R Uinst32

045A 2 Port s4/p2 Statistics - Ethernet Out Packets R Uinst32

045C 2 Port s4/p3 Statistics - Ethernet Out Packets R Uinst32

045E 2 Port s4/p4 Statistics - Ethernet Out Packets R Uinst32

0460 2 Port s5/p1 Statistics - Ethernet Out Packets R Uinst32

0462 2 Port s5/p2 Statistics - Ethernet Out Packets R Uinst32

0464 2 Port s5/p3 Statistics - Ethernet Out Packets R Uinst32

0466 2 Port s5/p4 Statistics - Ethernet Out Packets R Uinst32

0468 2 Port s6/p1 Statistics - Ethernet Out Packets R Uinst32

046A 2 Port s6/p2 Statistics - Ethernet Out Packets R Uinst32

046C 2 Port s6/p3 Statistics - Ethernet Out Packets R Uinst32

046E 2 Port s6/p4 Statistics - Ethernet Out Packets R Uinst32

0470 2 Port s7/p1 Statistics - Ethernet Out Packets R Uinst32

0472 2 Port s7/p2 Statistics - Ethernet Out Packets R Uinst32

0474 2 Port s8/p1 Statistics - Ethernet Out Packets R Uinst32

0476 2 Port s8/p2 Statistics - Ethernet Out Packets R Uinst32

0480 2 Port s1/p1 Statistics - Ethernet In Packets R Uinst32

0482 2 Port s1/p2 Statistics - Ethernet In Packets R Uinst32

0484 2 Port s1/p3 Statistics - Ethernet In Packets R Uinst32

0486 2 Port s1/p4 Statistics - Ethernet In Packets R Uinst32

0488 2 Port s2/p1 Statistics - Ethernet In Packets R Uinst32

048A 2 Port s2/p2 Statistics - Ethernet In Packets R Uinst32

048C 2 Port s2/p3 Statistics - Ethernet In Packets R Uinst32

048E 2 Port s2/p4 Statistics - Ethernet In Packets R Uinst32

0490 2 Port s3/p1 Statistics - Ethernet In Packets R Uinst32

0492 2 Port s3/p2 Statistics - Ethernet In Packets R Uinst32

0494 2 Port s3/p3 Statistics - Ethernet In Packets R Uinst32

0496 2 Port s3/p4 Statistics - Ethernet In Packets R Uinst32

20 ModBus Memory Map


RUGGEDCOM ROS Chapter 1
User Guide Introduction

Address #Registers Description (Reference Table in UI) R/W Format

0498 2 Port s4/p1 Statistics - Ethernet In Packets R Uinst32

049A 2 Port s4/p2 Statistics - Ethernet In Packets R Uinst32

049C 2 Port s4/p3 Statistics - Ethernet In Packets R Uinst32

049E 2 Port s4/p4 Statistics - Ethernet In Packets R Uinst32

04A0 2 Port s5/p1 Statistics - Ethernet In Packets R Uinst32

04A2 2 Port s5/p2 Statistics - Ethernet In Packets R Uinst32

04A4 2 Port s5/p3 Statistics - Ethernet In Packets R Uinst32

04A6 2 Port s5/p4 Statistics - Ethernet In Packets R Uinst32

04A8 2 Port s6/p1 Statistics - Ethernet In Packets R Uinst32

04AA 2 Port s6/p2 Statistics - Ethernet In Packets R Uinst32

04AC 2 Port s6/p3 Statistics - Ethernet In Packets R Uinst32

04AE 2 Port s6/p4 Statistics - Ethernet In Packets R Uinst32

04B0 2 Port s7/p1 Statistics - Ethernet In Packets R Uinst32

04B2 2 Port s7/p2 Statistics - Ethernet In Packets R Uinst32

04B4 2 Port s8/p1 Statistics - Ethernet In Packets R Uinst32

04B6 2 Port s8/p2 Statistics - Ethernet In Packets R Uinst32

04C0 2 Port s1/p1 Statistics - Ethernet Out Packets R Uinst32

04C2 2 Port s1/p2 Statistics - Ethernet Out Packets R Uinst32

04C4 2 Port s1/p3 Statistics - Ethernet Out Packets R Uinst32

04C6 2 Port s1/p4 Statistics - Ethernet Out Packets R Uinst32

04C8 2 Port s2/p1 Statistics - Ethernet Out Packets R Uinst32

04CA 2 Port s2/p2 Statistics - Ethernet Out Packets R Uinst32

04CC 2 Port s2/p3 Statistics - Ethernet Out Packets R Uinst32

04CE 2 Port s2/p4 Statistics - Ethernet Out Packets R Uinst32

04D0 2 Port s3/p1 Statistics - Ethernet Out Packets R Uinst32

04D2 2 Port s3/p2 Statistics - Ethernet Out Packets R Uinst32

04D4 2 Port s3/p3 Statistics - Ethernet Out Packets R Uinst32

04D6 2 Port s3/p4 Statistics - Ethernet Out Packets R Uinst32

04D8 2 Port s4/p1 Statistics - Ethernet Out Packets R Uinst32

04DA 2 Port s4/p2 Statistics - Ethernet Out Packets R Uinst32

04DC 2 Port s4/p3 Statistics - Ethernet Out Packets R Uinst32

04DE 2 Port s4/p4 Statistics - Ethernet Out Packets R Uinst32

04E0 2 Port s5/p1 Statistics - Ethernet Out Packets R Uinst32

04E2 2 Port s5/p2 Statistics - Ethernet Out Packets R Uinst32

ModBus Memory Map 21


Chapter 1 RUGGEDCOM ROS
Introduction User Guide

Address #Registers Description (Reference Table in UI) R/W Format

04E4 2 Port s5/p3 Statistics - Ethernet Out Packets R Uinst32

04E6 2 Port s5/p4 Statistics - Ethernet Out Packets R Uinst32

04E8 2 Port s6/p1 Statistics - Ethernet Out Packets R Uinst32

04EA 2 Port s6/p2 Statistics - Ethernet Out Packets R Uinst32

04EC 2 Port s6/p3 Statistics - Ethernet Out Packets R Uinst32

04EE 2 Port s6/p4 Statistics - Ethernet Out Packets R Uinst32

04F0 2 Port s7/p1 Statistics - Ethernet Out Packets R Uinst32

04F2 2 Port s7/p2 Statistics - Ethernet Out Packets R Uinst32

04F4 2 Port s8/p1 Statistics - Ethernet Out Packets R Uinst32

04F6 2 Port s8/p2 Statistics - Ethernet Out Packets R Uinst32

Section 1.8.3

ModBus Memory Formats


The following ModBus memory formats are supported by Siemens.

CONTENTS
• Section 1.8.3.1, “Text”
• Section 1.8.3.2, “Cmd”
• Section 1.8.3.3, “Uint16”
• Section 1.8.3.4, “Uint32”
• Section 1.8.3.5, “PortCmd”
• Section 1.8.3.6, “Alarm”
• Section 1.8.3.7, “PSStatusCmd”
• Section 1.8.3.8, “TruthValues”

Section 1.8.3.1
Text
The Text format provides a simple ASCII representation of the information related to the product. The most
significant register byte of an ASCII characters comes first.
For example, consider a Read Multiple Registers request to read Product Identification from location 0x0000.
0x04 0x00 0x00 0x00 0x08

The response may look like:


0x04 0x10 0x53 0x59 0x53 0x54 0x45 0x4D 0x20 0x4E 0x41 0x4D 0x45

0x00 0x00 0x00 0x00 0x00

22 ModBus Memory Formats


RUGGEDCOM ROS Chapter 1
User Guide Introduction

In this example, starting from byte 3 until the end, the response presents an ASCII representation of the characters
for the product identification, which reads as SYSTEM NAME. Since the length of this field is smaller than eight
registers, the rest of the field is filled with zeros (0).

Section 1.8.3.2
Cmd
The Cmd format instructs the device to set the output to either true or false. The most significant byte comes first.
• FF 00 hex requests output to be True
• 00 00 hex requests output to be False
• Any value other than the suggested values does not affect the requested operation
For example, consider a Write Multiple Registers request to clear alarms in the device.
0x10 0x00 0x80 0x00 0x01 2 0xFF 0x00

• FF 00 for register 00 80 clears the system alarms


• 00 00 does not clear any alarms
The response may look like:
0x10 0x00 0x80 0x00 0x01

Section 1.8.3.3
Uint16
The Uint16 format describes a Standard ModBus 16 bit register.

Section 1.8.3.4
Uint32
The Uint32 format describes Standard 2 ModBus 16 bit registers. The first register holds the most significant 16
bits of a 32 bit value. The second register holds the least significant 16 bits of a 32 bit value.

Section 1.8.3.5
PortCmd
The PortCmd format describes a bit layout per port, where 1 indicates the requested action is true, and 0 indicates
the requested action is false.
PortCmd provides a bit layout of a maximum of 32 ports. Therefore, it uses two ModBus regsiters:
• The first ModBus register corresponds to ports 1 – 16
• The second ModBus register corresponds to ports 17 – 32 for a particular action
Bits that do not apply to a particular product are always set to zero (0).
A bit value of 1 indicates that the requested action is true. For example, the port is up.
A bit value of 0 indicates that the requested action is false. For example, the port is down.

Cmd 23
Chapter 1 RUGGEDCOM ROS
Introduction User Guide

Reading Data Using PortCmd


To understand how to read data using PortCmd, consider a ModBus Request to read multiple registers from
locatoin 0x03FE.
0x04 0x03 0xFE 0x00 0x02

The response depends on how many parts are available on the device. For example, if the maximum number of
ports on a connected RUGGEDCOM device is 20, the response would be similar to the following:
0x04 0x04 0xF2 0x76 0x00 0x05

In this example, bytes 3 and 4 refer to register 1 at location 0x03FE, and represent the status of ports 1 – 16. Bytes
5 and 6 refer to register 2 at location 0x03FF, and represent the status of ports 17 – 32. The device only has 20
ports, so byte 6 contains the status for ports 17 – 20 starting from right to left. The rest of the bites in register 2
corresponding to the non-existing ports 21 – 31 are zero (0).

Performing Write Actions Using PortCmd


To understand how data is written using PortCmd, consider a Write Multiple Register request to clear Ethernet port
statistics:
0x10 0x00 0x83 0x00 0x01 2 0x55 0x76 0x00 0x50

A bit value of 1 clears Ethernet statistics on the corresponding port. A bit value of 0 does not clear the Ethernet
statistics.
0x10 0x00 0x81 0x00 0x02

Section 1.8.3.6
Alarm
The Alarm format is another form of text description. Alarm text corresponds to the alarm description from the
table holding all of the alarms. Similar to the Text format, this format returns an ASCII representation of alarms.

NOTE
Alarms are stacked in the device in the sequence of their occurence (i.e. Alarm 1, Alarm 2, Alarm 3,
etc.).

The first eight alarms from the stack can be returned, if they exist. A zero (0) value is returned if an alarm does not
exist.

Section 1.8.3.7
PSStatusCmd
The PSStatusCmd format describes a bit layout for providing the status of available power supplies. Bits 0-4 of the
lower byte of the register are used for this purpose.
• Bits 0-1: Power Supply 1 Status
• Bits 2-3: Power Supply 2 Status
Other bits in the register do not provide any system status information.

24 Alarm
RUGGEDCOM ROS Chapter 1
User Guide Introduction

Bit Value Description

01 Power Supply not present (01 = 1)

10 Power Supply is functional (10 = 2)

11 Power Supply is not functional (11 = 3)

The values used for power supply status are derived from the RUGGEDCOM-specific SNMP MIB.

Reading the Power Supply Status from a Device Using PSStatusCmd


To understand how to read the power supply status from a device using PSStatusCmd, consider a ModBus Request
to read multiple registers from location 0x0043.
0x04 0x00 0x43 0x00 0x01

The response may look like:


0x04 0x02 0x00 0x0A

The lower byte of the register displays the power supply's status. In this example, both power supplies in the unit
are functional.

Section 1.8.3.8
TruthValues
The Truthvalues format represents a true or false status in the device:
• 1 indicates the corresponding status for the device to be true
• 2 indicates the corresponding status for the device to be false

Reading the FailSafe Relay Status From a Device Using TruthValue


To understand how to use the TruthValue format to read the FailSafe Relay status from a device, consider a
ModBus request to read multiple registers from location 0x0044.
0x04 0x00 0x44 0x00 0x01

The response may look like:


0x04 0x02 0x00 0x01

The register's lower byte shows the FailSafe Relay status. In this example, the FailSafe Relay is energized.

Reading the ErrorAlarm Status From a Device Using TruthValue


To understand how to use the TruthValue format to read the ErrorAlarm status from a device, conside a ModBus
request to read mulitple registers from location 0x0045.
0x04 0x00 0x45 0x00 0x01

The response may look like:


0x04 0x02 0x00 0x01

TruthValues 25
Chapter 1 RUGGEDCOM ROS
Introduction User Guide

The register's lower byte shows the ErrorAlarm status. In this example, there is no active ERROR, ALERT or CRITICAL
alarm in the device.

Section 1.9

SSH and SSL Keys and Certificates


The following describes the SSH and SSL keys and certificates in RSG2488, along with the certificate and SSH key
requirements.

CONTENTS
• Section 1.9.1, “Certificate and Keys Life Cycle”
• Section 1.9.2, “Certificate and Key Requirements”

Section 1.9.1

Certificate and Keys Life Cycle


Each RUGGEDCOM ROS device is shipped with an SSL certificate and RSA key pair, and a DSA host key pair for
SSH, that are generated at and provisioned by the factory. The administrator may upload a new certificate and
keys to the system at any time, which will overwrite the existing ones. In addition, CLI commands are available to
regenerate SSL certificate and key pair as well as the SSH host key pair.
There are three types of certificates and keys used in RUGGEDCOM ROS:

NOTE
SSH is not supported in Non-Controlled (NC) versions of RUGGEDCOM ROS.

NOTE
Network exposure to a ROS unit operating with the default keys, although always only temporary
by design, should be avoided. The best way to reduce or eliminate this exposure is to provision user-
created certificate and keys as quickly as possible, and preferably before the unit is placed in network
service.

• Default
A default certificate and SSL/SSH keys are built in to RUGGEDCOM ROS and are common across all RUGGEDCOM
ROS units sharing the same firmware image. In the event that valid SSL certificate or SSL/SSH key files are not
available on the device (as is usually only the case when upgrading from an old ROS version that does not
support user-configurable keys and therefore does was not shipped with unique, factory-generated keys), the
default certificate and keys are put into service *temporarily* so that SSH and SSL (https) sessions can be served
until generated or provisioned keys are available.
• Auto-Generated
If a default SSL certificate and SSL/SSH keys are in use, RUGGEDCOM ROS immediately begins to generate
a unique certificate and SSL/SSH keys for the device in the background. If a custom certificate and keys are
loaded while auto-generated certificates and keys are being generated, the generator will abort and the custom
certificate and keys and will be used.
• User-Generated (Recommended)
Custom certificates and keys are the most secure option. They give the user complete control over certificate
and key management, allow for the provision of certificates signed by a public or local certificate authority,

26 SSH and SSL Keys and Certificates


RUGGEDCOM ROS Chapter 1
User Guide Introduction

enable strictly controlled access to private keys, and allow authoritative distribution of SSL certificates, any CA
certificates, and public SSH keys.

NOTE
The RSA key pair corresponding to the SSL certificate must be appended to the certificate in the
ssl.crt file.

Section 1.9.2

Certificate and Key Requirements


For SSL, controlled versions of RUGGEDCOM ROS require an X.509 certificate in standard PEM format and an RSA
or ECC key pair. The certificate may be self-signed or signed by a separate authority. The RSA key must be 1024,
2048 or 3072 bits in length; the ECC key must be 192, 224, 256, 384 or 521 bits in length.
Non-Controlled (NC) versions of RUGGEDCOM ROS require an X.509 certificate in standard PEM format and an RSA
key pair. The RSA key must be between 512 and 2048 bits in length.
The certificate and keys must be combined in a single ssl.crt file and uploaded to the device.
The following is an example of a combined SSL certificate and key:

-----BEGIN CERTIFICATE-----
MIIC9jCCAl+gAwIBAgIJAJh6rrehMt3iMA0GCSqGSIb3DQEBBQUAMIGuMQswCQYD
VQQGEwJDQTEQMA4GA1UECBMHT250YXJpbzEQMA4GA1UEBxMHQ29uY29yZDESMBAG
A1UEChMJUnVnZ2VkY29tMRkwFwYDVQQLExBDdXN0b21lciBTdXBwb3J0MSYwJAYD
VQQDEx1XUy1NSUxBTkdPVkFOLlJVR0dFRENPTS5MT0NBTDEkMCIGCSqGSIb3DQEJ
ARYVc3VwcG9ydEBydWdnZWRjb20uY29tMB4XDTEyMTAyMzIxMTA1M1oXDTE3MTAy
MjIxMTA1M1owgZwxCzAJBgNVBAYTAlVTMRAwDgYDVQQIEwdPbnRhcmlvMRAwDgYD
VQQHEwdDb25jb3JkMRIwEAYDVQQKEwlSdWdnZWRDb20xGTAXBgNVBAsTEEN1c3Rv
bWVyIFN1cHBvcnQxFDASBgNVBAMTCzE5Mi4xNjguMS4yMSQwIgYJKoZIhvcNAQkB
FhVTdXBwb3J0QHJ1Z2dlZGNvbS5jb20wgZ8wDQYJKoZIhvcNAQEBBQADgY0AMIGJ
AoGBALfE4eh2aY+CE3W5a4Wz1Z1RGRP02COHt153wFFrU8/fFQXNhKlQirlAHbNT
RSwcTR8ZFapivwYDivn0ogOGFXknYP90gv2oIaSVY08FqZkJW77g3kzkv/8Zrw3m
W/cBsZJ8SyKLIDfy401HkHpDOle5NsQFSrziGUPjAOIvvx4rAgMBAAGjLDAqMAkG
A1UdEwQCMAAwHQYDVR0OBBYEFER0utgQOifnrflnDtsqNcnvRB0XMA0GCSqGSIb3
DQEBBQUAA4GBAHtBsNZuh8tB3kdqR7Pn+XidCsD70YnI7w0tiy9yiRRhARmVXH8h
5Q1rOeHceri3JFFIOxIxQt4KgCUYJLu+c9Esk/nXQQar3zR7IQCt0qOABPkviiY8
c3ibVbhJjLpR2vNW4xRAJ+HkNNtBOg1xUlp4vOmJ2syYZR+7XAy/OP/S
-----END CERTIFICATE-----
-----BEGIN RSA PRIVATE KEY-----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-----END RSA PRIVATE KEY-----

For SSH, RUGGEDCOM ROS requires a DSA or RSA host key pair in PEM format. The key must be 1024, 2048 or
3072 bits in length for Controlled versions. The key file is uploaded to the ssh.keys flash file on the device.
The following is an example of a PEM formatted SSH key:

-----BEGIN DSA PRIVATE KEY-----

Certificate and Key Requirements 27


Chapter 1 RUGGEDCOM ROS
Introduction User Guide
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-----END DSA PRIVATE KEY-----

For more information about encryption key management, refer to Section 1.2, “Security Recommendations and
Considerations” .

Section 1.10

Removable Memory
The RSG2488 features a user-accessible memory slot that supports a standard ISO/IEC 9293-compatible FAT16 or
FAT32 (File Allocation Table) file system on a microSD/microSDHC Flash card.
An important advantage of using a FAT-based file system for the removable memory is that its contents may be
modified on any general purpose computer that has a microSD/microSDHC interface.

NOTE
The microSD/microSDHC card will be automatically formatted to the FAT16 or FAT32 file system if any
file system other than FAT16 or FAT32 is loaded on the card.

Figure 2: Memory Slot
1. Access Plate    2. microSD/microSDHC Flash Card

The primary purpose of the removable microSD/microSDHC card is to provide a place to automatically backup
the main firmware image and device configuration database, along with the ability to automatically restore the
firmware image and/or the configuration from the backup. It can also be used to regain access to the device if data
in the internal Flash memory is corrupted.
During normal operation, the device will automatically synchronize the files main.bin and config.csv on the
device and the microSD/microSDHC card. If a valid firmware file (main.bin) exists on the microSD/microSDHC
card, ROS will load and run the firmware from the card.
When the device is rebooted, it will compare the files main.bin and config.csv on the device and the
microSD/microSDHC card. If the files on the device differ from those on the card, the device will upload the files
from the card into its file system and apply them.
Other applications for the removable microSD/microSDHC card include:

28 Removable Memory
RUGGEDCOM ROS Chapter 1
User Guide Introduction

• Quickly recover from a hardware failure in the field


• Backup and restore firmware and configuration data
• Copy the firmware and configuration from one device to another
• Perform an automatic firmware upgrade
• Recover from a failed firmware upgrade or reconfiguration
• Setup the boot security option
• Reset the admin username and password
• Automatically backup syslogs
In addition to being able to automatically backup and restore firmware and configuration using the removable
memory, RUGGEDCOM ROS supports an extended set of command line utilities for manipulating files on the
system. The removable memory card presents a disk paradigm, familiar to users of FAT-based file systems,
complete with CLI (Command Line Interface) commands like dir, copy, and move. For a complete list of available
CLI commands, refer to Section 2.6.1, “Available CLI Commands” .

Removable Memory 29
RUGGEDCOM ROS Chapter 1
User Guide Introduction

Removable Memory 30
RUGGEDCOM ROS Chapter 2
User Guide Using ROS

Using ROS
This chapter describes how to use the RUGGEDCOM ROS interface.

CONTENTS
• Section 2.1, “Connecting to ROS”
• Section 2.2, “Logging In”
• Section 2.3, “Logging Out”
• Section 2.4, “Using the Web Interface”
• Section 2.5, “Using the Console Interface”
• Section 2.6, “Using the Command Line Interface”
• Section 2.7, “Selecting Ports in RUGGEDCOM ROS ”
• Section 2.8, “Managing the Flash File System”
• Section 2.9, “Accessing BIST Mode”
• Section 2.10, “Managing SSH Public Keys”
• Section 2.11, “Accessing the Boot Loader”

Section 2.1

Connecting to ROS
This section describes the various methods for connecting the device.

CONTENTS
• Section 2.1.1, “Connecting Directly”
• Section 2.1.2, “Connecting via the Network”

Section 2.1.1

Connecting Directly
RUGGEDCOM ROS can be accessed through a direct RS-232 serial console or Ethernet connection for management
and troubleshooting purposes. A console connection provides access to the console interface and CLI. An Ethernet
connection provides access to the Web interface.

Using the RS-232 Serial Console Port


To establish a console connection to the device, do the following:

Connecting to ROS 31
Chapter 2 RUGGEDCOM ROS
Using ROS User Guide

1. Connect a workstation (either a terminal or computer running terminal emulation software) to the RS-232
serial console port on the device. For more information about the RS-232 serial console port, refer to the
RSG2488 Installation Guide.
2. Configure the workstation as follows:
• Speed (baud): 57600
• Data Bits: 8
• Parity: None
• Flow Control: Off
• Terminal ID: VT100
• Stop Bit: 1
3. Connect to the device. Once the connection is established, the login form appears. For more information
about logging in to the device, refer to Section 2.2, “Logging In” .

Using an Ethernet Port


To establish a direct Ethernet connection to the device, do the following:
1. On the workstation being used to access the device, configure an Ethernet port to use an IP address falling
within the subnet of the device.
By default, the device has a different IP address and subnet configured for two types of IP interfaces, both of
which are mapped to one or more physical ports:
Port IP Address/Mask

MGMT 10.0.0.1/8

All other Ethernet ports 192.168.0.1/24

For example, to configure the device to connect to one of the available Ethernet ports, assign an IP address to
the Ethernet port on the workstation in the range of 192.168.0.3 to 192.168.0.254.
2. Launch the SSH client on the workstation and connect to admin@{ipaddress}, where {ipaddress} is the IP
address for the port that is connected to the network. The login prompt appears:

Using username "admin".


[email protected]'s password:

3. Log in to ROS. For more information about logging in to ROS, refer to Section 2.2, “Logging In” .

Section 2.1.2

Connecting via the Network


RUGGEDCOM ROS can be accessed over the network either through a Web browser, terminal or a workstation
running terminal emulation software.

Using a Web Browser


Web browsers provide a secure connection to the Web interface for RUGGEDCOM ROS using the SSL (Secure
Socket Layer) communication method. SSL encrypts traffic exchanged with its clients.

32 Connecting via the Network


RUGGEDCOM ROS Chapter 2
User Guide Using ROS

The RUGGEDCOM ROS Web server guarantees that all communications with the client are private. If a client
requests access through an insecure HTTP port, the client is automatically rerouted to the secure port. Access to
the Web server through SSL will only be granted to clients that provide a valid user name and password.
To establish a connection through a Web browser, do the following:
1. On the workstation being used to access the device, configure an Ethernet port to use an IP address falling
within the subnet of the device. The default IP address is 192.168.0.1/24.
By default, the device has a different IP address and subnet configured for two types of IP interfaces, both of
which are mapped to one or more physical ports:
Port IP Address/Mask

MGMT 10.0.0.1/8

All other Ethernet ports 192.168.0.1/24

For example, to configure the device to connect to one of the available Ethernet ports, assign an IP address to
the Ethernet port on the workstation in the range of 192.168.0.3 to 192.168.0.254.
2. Open a Web browser. For a list of recommended Web browsers, refer to the section called “System
Requirements” .

IMPORTANT!
Upon connecting to the device, some Web browsers may report the Web server's certificate cannot
be verified against any known certificates. This is expected behavior, and it is safe to instruct the
browser to accept the certificate. Once the certificate is accepted, all communications with the
Web server through that browser will be secure.

3. In the address bar, type the IP address for the port that is connected to the network. Once the connection is
established, the login screen for the Web interface appears.
For more information about logging in to the device, refer to Section 2.2, “Logging In” . For more information
about the Web interface, refer to Section 2.4, “Using the Web Interface” .

Using a Terminal or Terminal Emulation Software


A terminal or computer running terminal emulation software provides access to the console interface for
RUGGEDCOM ROS through a Telnet, RSH (Remote Shell) or SSH (Secure Shell) service.

NOTE
IP services can be restricted to control access to the device. For more information, refer to Section 3.10,
“Configuring IP Services” .

To establish a connection through a terminal or terminal emulation software, do the following:


1. Select the service (i.e. Telnet, RSH or SSH).
2. Enter the IP address for the port that is connected to the network.
3. Connect to the device. Once the connection is established, the login form appears. For more information
about logging in to the device, refer to Section 2.2, “Logging In” .

Connecting via the Network 33


Chapter 2 RUGGEDCOM ROS
Using ROS User Guide

Section 2.2

Logging In
To log in to the device, do the following:
1. Connect to the device either directly or through a Web browser. For more information about how to connect
to the device, refer to Section 2.1, “Connecting to ROS” .
Once the connection is established, the login form appears.

Figure 3: SSH Login Screen (Console Interface)


1. User Name Box    2. Password Box

1 2

Figure 4: Login Screen (Web Interface)


1. Username Box    2. Password Box    3. Submit Button

NOTE
The following default usernames and passwords are set on the device for each user type:
Guest Operator Admin
Username: guest Username: operator Username: admin
Password: guest Password: operator Password: admin

CAUTION!
To prevent unauthorized access to the device, make sure to change the default guest, operator,
and admin passwords before commissioning the device.
For more information about changing passwords, refer to Section 4.3, “Configuring Passwords” .

2. In the User Name field, type the username for an account setup on the device.
3. In the Password field, typ the password for the account.

34 Logging In
RUGGEDCOM ROS Chapter 2
User Guide Using ROS

4. Click Enter or click Submit (Web interface only).

Section 2.3

Logging Out
To log out of the device, navigate to the main screen and do the following:
• To log out of the Console or secure shell interfaces, press CTRL + X.
• To log out of the Web interface, click Logout.

Figure 5: Web Interface (Example)


1. Logout

NOTE
If any pending configuration changes have not been committed, RUGGEDCOM ROS will request
confirmation before discarding the changes and logging out of the device.

Section 2.4

Using the Web Interface


The Web interface is a Web-based Graphical User Interface (GUI) for displaying important information and controls
in a Web browser. The interface is divided into three frames: the banner, the menu and the main frame.

Logging Out 35
Chapter 2 RUGGEDCOM ROS
Using ROS User Guide

2
3

Figure 6: Web Interface Layout (Example)


1. Top Frame    2. Side Frame    3. Main Frame

Frame Description

Top The top frame displays the system name for the device.

Side The side frame contains a logout option and a collapsible list of links that open various
screens in the main frame. For information about logging out of RUGGEDCOM ROS, refer to
Section 2.3, “Logging Out” .

Main The main frame displays the parameters and/or data related to the selected feature.

Each screen consists of a title, the current user's access level, parameters and/or data (in form or table format),
and controls (e.g. add, delete, refresh, etc.). The title provides access to context-specific Help for the screen that
provides important information about the available parameters and/or data. Click on the link to open the Help
information in a new window.
When an alarm is generated, an alarm notification replaces the current user's access level on each screen until
the alarm is cleared. The notification indicates how many alarms are currently active. For more information about
alarms, refer to Section 4.6, “Managing Alarms” .

36 Using the Web Interface


RUGGEDCOM ROS Chapter 2
User Guide Using ROS

1 3

Figure 7: Elements of a Typical Screen (Example)


1. Title    2. Parameters and/or Data    3. Access Level or Alarm Notification    4. Controls

NOTE
If desired, the web interface can be disabled. For more information, refer to Section 4.5, “Enabling/
Disabling the Web Interface” .

Section 2.5

Using the Console Interface


The Console interface is a Graphical User Interface (GUI) organized as a series of menus. It is primarily accessible
through a serial console connection, but can also be accessed through IP services, such as a Telnet, RSH (Remote
Shell), SSH (Secure Shell) session, or SSH remote command execution.

NOTE
IP services can be restricted to control access to the device. For more information, refer to Section 3.10,
“Configuring IP Services” .

Each screen consists of a system identifier, the name of the current menu, and a command bar. Alarms are also
indicated on each screen in the upper right corner.

Using the Console Interface 37


Chapter 2 RUGGEDCOM ROS
Using ROS User Guide

1 5

Figure 8: Console Interface (Example)


1. System Identification    2. Menus    3. Command Bar    4. Menu Name    5. Alarms Indicator

NOTE
The system identifier is user configurable. For more information about setting the system name, refer
to Section 4.1, “Configuring the System Information” .

Navigating the Interface


Use the following controls to navigate between screens in the Console interface:
Enter Select a menu item and press this Enter to enter the sub-menu or screen beneath.

Esc Press Esc to return to the previous screen.

Configuring Parameters
Use the following controls to select and configure parameters in the Console interface:
Up/Down Arrow Keys Use the up and down arrow keys to select parameters.

Enter Select a parameter and press Enter to start editing a parameter. Press Enter again to commit the change.

Esc When editing a parameter, press Esc to abort all changes.

38 Using the Console Interface


RUGGEDCOM ROS Chapter 2
User Guide Using ROS

Commands
The command bar lists the various commands that can be issued in the Console interface. Some commands are
specific to select screens. The standard commands include the following:
Ctrl + A Commits configuration changes made on the current screen.

NOTE
Before exiting a screen, RUGGEDCOM ROS will automatically prompt the user to save any changes
that have not been committed.

Ctrl + I Inserts a new record.

Ctrl + L Deletes a record.

Ctrl + S Opens the CLI interface.

Ctrl + X Terminates the current session. This command is only available from the main menu.

Ctrl + Z Displays important information about the current screen or selected parameter.

Section 2.6

Using the Command Line Interface


The Command Line Interface (CLI) offers a series of powerful commands for updating ROS, generating certificates/
keys, tracing events, troubleshooting and much more. It is accessed via the Console interface by pressing Ctrl-S.

CONTENTS
• Section 2.6.1, “Available CLI Commands”
• Section 2.6.2, “Tracing Events”
• Section 2.6.3, “Executing Commands Remotely via RSH”
• Section 2.6.4, “Using SQL Commands”

Section 2.6.1

Available CLI Commands


The following commands are available at the command line:
Command Description

A: Changes the working directory to the microSD/microSDHC Flash card.

alarms all Displays a list of available alarms.


Optional and/or required parameters include:
• all displays all available alarms

arp Displays the IP to MAC address resolution table.

attrib filename [ + | - ] [ W | Sets and removes file attributes.


H ]

cd Changes the current working directory on the microSD/microSDHC Flash card (A:).

Using the Command Line Interface 39


Chapter 2 RUGGEDCOM ROS
Using ROS User Guide

Command Description

cdroot Changes the current working directory to the internal Flash drive.

chkdsk Checks the file system for disk errors.

clearalarms Clears all alarms.

clearethstats [ all | port ] Clears Ethernet statistics for one or more ports.
Optional and/or required parameters include:
• all clears statistics for all ports
• port is a comma separated list of port numbers (e.g. 1,3-5,7)

clearlogs Clears the system and crash logs.

clrcblstats [ all | port ] Clears cable diagnostics statistics for one or more ports.
Optional and/or required parameters include:
• all clears statistics for all ports
• port is a comma separated list of port numbers (e.g. 1,3-5,7)

clrstpstats Clears all spanning tree statistics.

cls Clears the screen.

copy Copies a target file to the internal or removable memory.


Examples:
• Copying a file from the removable memory to the internal memory

copy a:\config.csv config.csv


• Copying a file from the internal memory to the removable memory

copy config.csv a:\config.csv

delete filename Deletes the specified file.

dir Prints the directory listing.

exit Terminates the session.

factory Enables factory mode, which includes several factory-level commands used for testing and
troubleshooting. Only available to admin users.

CAUTION!
Misuse of the factory commands may corrupt the operational state of device
and/or may permanently damage the ability to recover the device without
manufacturer intervention.

flashfiles { info filename | A set of diagnostic commands to display information about the Flash filesystem and to
defrag } defragment Flash memory.
Optional and/or required parameters include:
• info filename displays information about the specified file in the Flash file system
• defrag defragments files in the Flash file system
For more information about the flashfiles command, refer to Section 2.8, “Managing
the Flash File System” .

flashleds timeout Flashes the LED indicators on the device for a specified number of seconds.
Optional and/or required parameters include:
• timeout is the number of seconds to flash the LED indicators. To stop the LEDs from
flashing, set the timeout period to 0 (zero).

format disk Formats the specified disk (e.g. A:).

40 Available CLI Commands


RUGGEDCOM ROS Chapter 2
User Guide Using ROS

Command Description

fpgacmd Provides access to the FPGA management tool for troubleshooting time synchronization.

help command Displays a brief description of the specified command. If no command is specified, it displays
a list of all available commands, including a description for each.
Optional and/or required parameters include:
• command is the command name.

ipconfig Displays the current IP address, subnet mask and default gateway.

label disk string Applies a label to the specified disk (e.g. A:).

loaddflts Loads the factory default configuration.

logout Logs out of the shell.

logs Displays syslog entries in CLI shell.

mkdir name Creates a new directory.

move source destination Creates the specified file to a different directory.

ping address { count | Sends an ICMP echo request to a remotely connected device. For each reply received, the
timeout } round trip time is displayed. Use this command to verify connectivity to the next connected
device. It is a useful tool for testing commissioned links. This command also includes the
ability to send a specific number of pings with a specified time for which to wait for a
response.
Optional and/or required parameters include:
• address is the target IP address.
• count is the number of echo requests to send. The default is 4.
• timeout is the time in milliseconds to wait for each reply. The range is 2 to 5000
seconds. The default is 300 milliseconds.

NOTE
The device to be pinged must support ICMP echo. Upon commencing the ping,
an ARP request for the MAC address of the device is issued. If the device to be
pinged is not on the same network as the device pinging the other device, the
default gateway must be programmed.

purgemac Purges the MAC Addrtess table.

random Display seeds or random numbers.

rename source destination Renames the specified file. Add a path to new filename to move the file at the same time.

reset Perform a hard reset of the switch.

resetport { all | ports } Resets one or more Ethernet ports, which may be useful for forcing re-negotiation of speed
and duplex, or in situations where the link partner has latched into an inappropriate state.
Optional and/or required parameters include:
• all resets all ports
• ports is a comma separated list of port numbers (e.g. 1,3-5,7)

rmdir directory Deletes the specified directory.

rmon Displays the names of all RMON alarm eligible objects.

route Displays the gateway configuration.

sql { default | delete | help | Provides an SQL-like interface for manipulating all system configuration and status
info | insert | save | select | parameters. All commands, clauses, table, and column names are case insensitive.
update }
Optional and/or required parameters include:
• default sets all records in a table(s) to factory defaults

Available CLI Commands 41


Chapter 2 RUGGEDCOM ROS
Using ROS User Guide

Command Description
• delete allows for records to be deleted from a table
• help provides a brief description for any SQL command or clause
• info displays a variety of information about the tables in the database
• insert enables new records to be inserted into a table
• save saves the database to non-volatile memory storage
• select queries the dtabase and displays selected records
• update enable existing records in a table to be updated
For more information about the sql command, refer to Section 2.6.4, “Using SQL
Commands” .

sshkeygen keytype N Generates new SSH keys in ssh.keys.


Optional and/or required parameters include:
• keytype is the type of key, either rsa or dsa
• N is the number of bits in length. The allowable sizes are 1024, 2048 or 3072

sshpubkey List, remove and update key entries in sshpub.keys file.

sslkeygen keytype N Generates a new SSL certificate in ssl.crt.


Optional and/or required parameters include:
• keytype is the type of key, either rsa or ecc
• N is the number of bits in length. For RSA keys, the allowable sizes are 1024, 2048 or
3072. For ECC keys, the allowable sizes are 192, 224, 256, 384, or 521.

telnet dest Opens a telnet session. Press Ctrl-C to close the session.
Optional and/or required parameters include:
• dest is the server's IP address

tftp { dest | cmd | fsource Opens a TFTP session. Press Ctrl-C to close the session.
| fdest }
Optional and/or required parameters include:
• dest is the remote TFTP server's IP address
• cmd is either put (upload) or get (download)
• fsource is the source filename
• fdest is the destination filename

trace Starts event tracing. Run trace ? for more help.

type filename Displays the contents of a text file.


Optional and/or required parameters include:
• filename is the name of the file to be read

version Prints the software version.

xmodem { send | receive } Opens an XModem session.


filename
Optional and/or required parameters include:
• send sends the file to the client.
• receive receives the file from the client.
• filename is the name of the file to be read.

Section 2.6.2

Tracing Events
The CLI trace command provides a means to trace the operation of various protocols supported by the device.
Trace provides detailed information, including STP packet decodes, IGMP activity and MAC address displays.

42 Tracing Events
RUGGEDCOM ROS Chapter 2
User Guide Using ROS

NOTE
Tracing has been designed to provide detailed information to expert users. Note that all tracing is
disabled upon device startup.

To trace an event, do the following:


1. Log in to the device as an admin user and access the CLI shell. For more information about accessing the CLI
shell, refer to Section 2.6, “Using the Command Line Interface” .
2. Determine the protocols and associated options available by typing:
trace ?

If an option such as allon or alloff is required, determine which options are available for the desired
protocol by typing:
trace protocol ?

NOTE
If required, expand the trace scope by stringing protocols and their associated options together
using a vertical bar (|).

3. Select the type of trace to run by typing:


trace protocol option

Where:
• protocol is the protocol to trace
• option is the option to use during the trace
Example:

>trace transport allon


TRANSPORT: Logging is enabled

4. Start the trace by typing:


trace

Section 2.6.3

Executing Commands Remotely via RSH


The Remote Shell (RSH) facility can be used from a workstation to cause the product to act upon commands as if
they were entered at the CLI prompt. The syntax of the RSH command is usually of the form:
rsh ipaddr –l auth_token command_string

Where:
• ipaddr is the address or resolved name of the device.
• auth_token is the user name (i.e. guest, operator or admin) and corresponding password separated by a
comma. For example, admin,secret.
• command_string is the RUGGEDCOM ROS CLI command to execute.

Executing Commands Remotely via RSH 43


Chapter 2 RUGGEDCOM ROS
Using ROS User Guide

NOTE
The access level (corresponding to the user name) selected must support the given command.

NOTE
Any output from the command will be returned to the workstation submitting the command.
Commands that start interactive dialogs (such as trace) cannot be used.

Section 2.6.4

Using SQL Commands


RUGGEDCOM ROS provides an SQL-like command facility that allows expert users to perform several operations
not possible under the traditional Web or CLI interface. For instance:
• Restoring the contents of a specific table, but not the whole configuration, to their factory defaults.
• Search tables in the database for specific configurations.
• Make changes to tables predicated upon existing configurations.
When combined with RSH, SQL commands provide a means to query and configure large numbers of devices from
a central location.

NOTE
For a list of parameters available under the sql command, refer to Section 2.6.1, “Available CLI
Commands” .

NOTE
Read/write access to tables containing passwords or shared secrets is unavailable using SQL
commands.

CONTENTS
• Section 2.6.4.1, “Finding the Correct Table”
• Section 2.6.4.2, “Retrieving Information”
• Section 2.6.4.3, “Changing Values in a Table”
• Section 2.6.4.4, “Resetting a Table”
• Section 2.6.4.5, “Using RSH and SQL”

Section 2.6.4.1
Finding the Correct Table
Many SQL commands operate upon specific tables in the database, and require the table name to be specified.
Navigating the menu system in the console interface to the desired menu and pressing Ctrl-Z displays the name of
the table. The menu name and the corresponding database table name will be cited.
Another way to find a table name is to type the following in the CLI:
sql info tables

44 Using SQL Commands


RUGGEDCOM ROS Chapter 2
User Guide Using ROS

This command also displays menu names and their corresponding database table names depending upon the
features supported by the device. For example:

Table Description
-------------------------------------------------------------------------------
alarms Alarms
cpuDiags CPU Diagnostics
ethPortCfg Port Parameters
ethPortStats Ethernet Statistics
ethPortStatus Port Status
ipCfg IP Services

Section 2.6.4.2
Retrieving Information
The following describes various methods for retrieving information about tables and parameters.

Retrieving Information from a Table


Use the following command to display a summary of the parameters within a table, as well as their values:
sql select from table

Where:
• table is the name of the table
Example:

>sql select from ipAddrtable

IP Address Subnet IfIndex IfStats IfTime IfName


172.30.146.88 255.255.224.0 1001 17007888 2994 vlan1

1 records selected

Retrieving Information About a Parameter from a Table


Use the following command to retrieve information about a specific parameter from a table:

NOTE
The parameter name must be the same as it is displayed in the menu system, unless the name contains
spaces (e.g. ip address). Spaces must be replaced with underscores (e.g. ip_address) or the parameter
name must be wrapped in double quotes (e.g. "ip address").

sql select parameter from table

Where:
• parameter is the name of the parameter
• table is the name of the table
Example:

>sql select "ip address" from ipSwitchIfCfg

IP Address

Retrieving Information 45
Chapter 2 RUGGEDCOM ROS
Using ROS User Guide

192.168.0.1

1 records selected

Retrieving Information from a Table Using the Where Clause


Use the following command to display specific parameters from a table that have a specific value:
sql select from table where parameter = value

Where:
• table is the name of the table
• parameter is the name of the parameter
• value is the value of the parameter
Example:

>sql select from ethportcfg where media = 1000T

Port Name ifName Media State AutoN Speed Dupx FlowCtrl LFI Alarm
1/1 Port 1 1/1 1000T Enabled On Auto Auto Off Off On
1/2 Port 2 1/2 1000T Enabled On Auto Auto Off Off On
1/3 Port 3 1/3 1000T Enabled On Auto Auto Off Off On
1/4 Port 4 1/4 1000T Enabled On Auto Auto Off Off On

4 records selected

Further refine the results by using and or or operators:


sql select from table where parameter = value [ { and | or } | parameter | = | value ...]

Where:
• table is the name of the table
• parameter is the name of the parameter
• value is the value of the parameter
Example:

>sql select from ethportcfg where media = 1000T and State = enabled

Port Name ifName Media State AutoN Speed Dupx FlowCtrl LFI Alarm
1/1 Port 1 1/1 1000T Enabled On Auto Auto Off Off on
1/2 Port 2 1/2 1000T Enabled On Auto Auto Off Off On
1/3 Port 3 1/3 1000T Enabled On Auto Auto Off Off On
1/4 Port 4 1/4 1000T Enabled On Auto Auto Off Off On

4 records selected

Section 2.6.4.3
Changing Values in a Table
Use the following command to change the value of parameters in a table:
sql update table set parameter = value

Where:

46 Changing Values in a Table


RUGGEDCOM ROS Chapter 2
User Guide Using ROS

• table is the name of the table


• parameter is the name of the parameter
• value is the value of the parameter
Example:

>sql update iplcfg set IP_Address_Type = static


1 records updated

Conditions can also be included in the command to apply changes only to parameters that meet specific criteria.
In the following example, flow control is enabled on ports that are operating in 100 Mbps full-duplex mode with
flow control disabled:

>sql update ethportcfg set FlowCtrl = Off where ( Media = 100TX and FlowCtrl = On )
2 records updated

Section 2.6.4.4
Resetting a Table
Use the following command to reset a table back to its factory defaults:
sql default into table

Where:
• table is the name of the table

Section 2.6.4.5
Using RSH and SQL
The combination of remote shell scripting and SQL commands offers a means to interrogate and maintain a
large number of devices. Consistency of configuration across sites may be verified by this method. The following
presents a simple example where the devices to interrogate are drawn from the file Devices:

C:> type Devices


10.0.1.1
10.0.1.2

C:\> for /F %i in (devices) do rsh %i -l admin,admin sql select from ipAddrtable

C:\>rsh 10.0.1.1 -l admin,admin sql select from ipAddrtable

IP Address Subnet IfIndex IfStats IfTime IfName


192.168.0.31 255.255.255.0 1001 274409096 2218 vlan1

1 records selected

C:\>rsh 10.0.1.2 -l admin,admin sql select from ipAddrtable


0 records selected
C:\

Resetting a Table 47
Chapter 2 RUGGEDCOM ROS
Using ROS User Guide

Section 2.7

Selecting Ports in RUGGEDCOM ROS


Many features in ROS can be configured for one or more ports on the device. The following describes how to
specify a single port, a range of ports, or a port within a specific slot.
Select a single port by specifying the slot and port number:

1/2

Select a range of ports using a dash (-) between the first port and the last port in the list:

1/1-1/4

Select multiple ports by defining a comma-separated list:

1/1,1/4,1/6,1/9

Only ports within the same slot can be selected in a single range. To select a range of ports from different slots,
define a comma-separated list of ranges:

1/1-1/4,2/1-2/4,3/1-3/3

Use the All option to select all ports in the device, or, if available, use the None option to select none of the
ports.

Section 2.8

Managing the Flash File System


The following section describes how to manage the flash file system.

CONTENTS
• Section 2.8.1, “Viewing a List of Flash Files”
• Section 2.8.2, “Viewing Flash File Details”
• Section 2.8.3, “Defragmenting the Flash File System”

Section 2.8.1

Viewing a List of Flash Files


To view a list of files currently stored in Flash memory, do the following:
1. Log in to the device as an admin user and access the CLI shell. For more information about accessing the CLI
shell, refer to Section 2.6, “Using the Command Line Interface” .
2. Type flashfiles. A list of files currently in Flash memory is displayed, along with their locations and the
amount of memory they consume. For example:

>flashfiles
-----------------------------------------------------------------

48 Selecting Ports in RUGGEDCOM ROS


RUGGEDCOM ROS Chapter 2
User Guide Using ROS

Filename Base Size


-----------------------------------------------------------------
syslog.txt 0xFE100080 0x001BFF80 (1834880)
crashlog.txt 0xFE2C0080 0x0003FF80 (262016)
clksyn.txt 0xFE300080 0x0000067F (1663)
factory.txt 0xFE300780 0x00000278 (632)
ssl.crt 0xFE300A80 0x000006B2 (1714)
ssh.keys 0xFE3011C0 0x00000293 (659)
bootoption.txt 0xFE3014E0 0x00000080 (128)
fpga2488.bin 0xFE3015E0 0x000C400C (802828)
config.csv 0xFE954DA0 0x00004CBE (19646)
main.bin 0xFE959AE0 0x002C5493 (2905235)

Free Space: 19792360


Used Space: 11664720
Fragmented Space: 5830423
-----------------------------------------------------------------

Section 2.8.2

Viewing Flash File Details


To view the details of a file currently stored in Flash memory, do the following:
1. Log in to the device as an admin user and access the CLI shell. For more information about accessing the CLI
shell, refer to Section 2.6, “Using the Command Line Interface” .
2. Display information about a file by typing:
flashfiles info filename

Where:
• filename is the name of the file stored in Flash memory
Details, similar to the following, are displayed.

>flashfiles info main.bin

Flash file information for main.bin:


Header version : 4

Platform : ROS-MPC83
File name : main.bin
Firmware version : v4.3.0
Build date : Sep 27 2014 15:50
File length : 2624659
Board IDs : 3d
Header CRC : 73b4
Header CRC Calc : 73b4
Body CRC : b441
Body CRC Calc : b441

Section 2.8.3

Defragmenting the Flash File System


The flash memory is defragmented automatically whenever there is not enough memory available for a binary
upgrade. However, fragmentation can occur whenever a new file is uploaded to the unit. Fragmentation causes
sectors of available memory to become separated by ones allocated to files. In some cases, the total available
memory might be sufficient for a binary upgrade, but that memory may not be available in one contiguous region.

Viewing Flash File Details 49


Chapter 2 RUGGEDCOM ROS
Using ROS User Guide

To defragment the flash memory, do the following:


1. Log in to the device as an admin user and access the CLI shell. For more information about accessing the CLI
shell, refer to Section 2.6, “Using the Command Line Interface” .
2. Defragment the flash memory by typing:
flashfiles defrag

Section 2.9

Accessing BIST Mode


BIST (Built-In-Self-Test) mode is used by service technicians to test and configure internal functions of the device.
It should only be accessed for troubleshooting purposes.

CAUTION!
Mechanical hazard – risk of damage to the device. Excessive use of BIST functions may cause increase
wear on the device, which may void the warranty. Avoid using BIST functions unless instructed by a
Siemens Customer Support representative.

NOTE
Access to BIST mode is disabled at the factory by default. All console inputs are ignored and users are
directed automatically to the RUGGEDCOM ROS user interface.

To first enable access to BIST mode, do the following:


1. Using a PC/laptop, create a file named bootoption.txt and include the following line in the file:

Security=no

2. Upload the file to the device or insert a microSD/microSDHC card containing the file and reboot the device.

NOTE
Access to BIST and the boot loader can be later revoked by changing no to yes.

To access BIST mode, do the following:

IMPORTANT!
Do not connect the device to the network when it is in BIST mode. The device will generate excess
multicast traffic in this mode.

1. Disconnect the device from the network.


2. Connect to RUGGEDCOM ROS through the RS-232 console connection and a terminal application. For more
information, refer to Section 2.1.1, “Connecting Directly” .
3. Reset the device. For more information, refer to Section 3.13, “Resetting the Device” .
4. During the boot up sequence, press Ctrl-C when prompted. The command prompt for BIST appears.

>

5. Type help to view a list of all available options under BIST.

50 Accessing BIST Mode


RUGGEDCOM ROS Chapter 2
User Guide Using ROS

Section 2.10

Managing SSH Public Keys


RUGGEDCOM ROS allows admin users to list, add and delete SSH public keys. Public keys are added as non-volatile
storage (i.e. flash) files on RUGGEDCOM ROS devices, and are retrieved at the time of SSH client authentication.

CONTENTS
• Section 2.10.1, “Adding a Public Key”
• Section 2.10.2, “Viewing a List of Public Keys”
• Section 2.10.3, “Updating a Public Key”
• Section 2.10.4, “Deleting a Public Key”

Section 2.10.1

Adding a Public Key


Admin users can add one or more public keys to RUGGEDCOM ROS.
Public keys are stored in a flash file, called sshpub.keys. The sshpub.keys file consists of ssh user public key entries.
Similar to the config.csv file, each entry must be separated by an empty line. An entry has two components. They
are, in sequence:
• Header
• Key
The header contains the parameters of the entry, separated by comma. The parameters are, in sequence:
• ID: A number between 0 and 9999
• Entry type: UserKey
• Access Level: (Admin, Operator or Guest)
• Revocation Status: active/inactive (always active for keys)
• User Name: This is the client's user name (not the RUGGEDCOM ROS user name). This will be used by clients to
later SSH into the RUGGEDCOM ROS device.
The key must be in RFC4716 or PEM format, with any of the following header and footer lines:

-----BEGIN PUBLIC KEY-----


-----END PUBLIC KEY-----

-----BEGIN SSH2 PUBLIC KEY-----


-----END SSH2 PUBLIC KEY-----

-----BEGIN RSA PUBLIC KEY-----


-----END RSA PUBLIC KEY-----

The following is an example of a valid entry in the sshpub.keys file in PEM format:

1,userkey,admin,active,alice
---- BEGIN SSH2 PUBLIC KEY ----
AAAAB3NzaC1yc2EAAAABIwAAAQEA4mRrqfk+RKXnmGRvzMyWVDsbq5VwpGGrlLQYCrjVEa
NdbXsphqYKop8V5VUeXFRAUFzOy82yk8TF/5JxGPWq6wRNjhnYR7IY2AiMBq0+K8XeURl/
z5K2XNRjnqTZSFwkhaUVJeduvjGgOlNN4yvgUwF3n0idU9k3E1q/na+LmYIeGhOwzCqoAc
ipHAdR4fhD5u0jbmvjv+gDikTSZIbj9eFJfP09ekImMLHwbBry0SSBpqAKbwVdWEXIKQ47
zz7ao2/rs3rSV16IXSq3Qe8VZh2irah0Md6JFMOX2qm9fo1I62q1DDgheCOsOiGPf4xerH

Managing SSH Public Keys 51


Chapter 2 RUGGEDCOM ROS
Using ROS User Guide

rI2cs6FT31rAdx2JOjvw==
---- END SSH2 PUBLIC KEY ----

The following is an example of a valid entry in the sshpub.keys file in in RFC4716 format:

2,userkey,admin,active,bob
ssh-rsa AAAAB3NzaC1yc2EAAAADAQABAAABAQDH0NivR8zzbTxlecvFPzR/
GR24NrRJa0Lc7scNsWRgi0XulHuGrRLRB5RoQ39+spdig88Y8CqhRI49XJx7uLJe0Su3RvyNYz1jkdSwHq2hSZCpukJxJ6CK95Po/
sVa5Gq2gMaHowiYDSkcx+AJywzK/eM6i/jc125lRxFPdfkj74u+ob3PCvmIWz5z3WAJBrQU1IDPHDets511WMu8O9/
mAPZRwjqrWhRsqmcXZuv5oo54wIopCAZSo20SPzM2VmXFuUsEwDkvYMXLJK1koJPbDjH7yFFC7mwK2eMU/
oMFFn934cbO5N6etsJSvplYQ4pMCw6Ok8Q/bB5cPSOa/rAt bob@work

IMPORTANT!
The content of the sshaddpub.keys file must follow the same syntax as the sshpub.keys file.

RUGGEDCOM ROS allows only 16 user key entries to be stored. Each key entry must meet the following limits:
• Key type must be either RSA 2048 bits or RSA 3072 bits
• Key size must not exceed 4000 base64 encoded characters
• Entry Type in the header must not exceed 8 ASCII characters
• Access Level in the header must not exceed 8 ASCII characters (operator is maximum)
• Revocation status in the header must not exceed 8 ASCII characters (inactive is maximum)
• User Name must not exceed 12 ASCII characters
There are two ways to update sshpub.keys. Users can either upload a locally-created file directly to the
sshpub.keys file, which will replace the content in flash with the uploaded content. Or, users can upload a locally-
created file to the sshaddpub.keys file, which will keep the existing entries in the sshpub.keys file and append the
new entries.
To add keys, do the following:
1. Create a public key file via a host computer.
2. Transfer the public key file to the device using SFTP or Xmodem. For more information about transferring
files, refer to Section 3.5, “Uploading/Downloading Files” .
3. Log in to the device as an admin user and access the CLI shell. For more information about accessing the CLI
shell, refer to Section 2.6, “Using the Command Line Interface” .
4. Check the system log to make sure the files were properly transferred. For more information about viewing
the system log, refer to Section 3.6.1, “Viewing Local Logs” .

Section 2.10.2

Viewing a List of Public Keys


Admin users can view a list of existing public keys on the device.
To view public keys, do the following:
1. Log in to the device as an admin user and access the CLI shell. For more information about accessing the CLI
shell, refer to Section 2.6, “Using the Command Line Interface” .
2. At the CLI prompt, type:
sshpubkey list

52 Viewing a List of Public Keys


RUGGEDCOM ROS Chapter 2
User Guide Using ROS

A list of public keys will appear, including their key ID, access level, revocation status, user name and key
fingerprint.

Section 2.10.3

Updating a Public Key


Admin users can update public keys.
To update public keys, do the following:
1. Log in to the device as an admin user and access the CLI shell. For more information about accessing the CLI
shell, refer to Section 2.6, “Using the Command Line Interface” .
2. At the CLI prompt, type:
sshpubkey list

A list of public keys will appear, including their key ID, access level, revocation status, user name and key
fingerprint.
3. Type the following commands to update the public keys:
Command Description

sshpubkey update_id current_ID Updates the ID of user public key.


new_ID
NOTE
The user public key ID must be a number between 0 and 9999.

• current_ID is the ID currently assigned to the public key


• new_ID is the ID that will be used to identify the public key going forward

sshpubkey update_al AL Updates the access level of a user public key.


• AL is the access level (admin, operator or guest) of the public key to be updated

sshpubkey update_rs RS Updates the revocation status (active, inactive) of a user public key.
• RS is the revocation status of the public key to be updated

sshpubkey update_un UN Updates the user name of a user public key.


• UN is the user name of the public key to be updated

Section 2.10.4

Deleting a Public Key


Admin users can delete one or more public keys.
To delete a public key, do the following:
1. Log in to the device as an admin user and access the CLI shell. For more information about accessing the CLI
shell, refer to Section 2.6, “Using the Command Line Interface” .
2. At the CLI prompt, type:
sshpubkey list

A list of public keys will appear, including access level, revocation status, user name and key fingerprint.

Updating a Public Key 53


Chapter 2 RUGGEDCOM ROS
Using ROS User Guide

3. Type the following commands to delete the public key(s):


Command Description

sshpubkey remove ID Removes a key from the non-volatile storage.


• ID is the ID of the public key to be removed

Section 2.11

Accessing the Boot Loader


RUGGEDCOM ROS uses Uboot to control the boot up sequence of the device. Uboot is a feature-rich and widely
used open source bootloader developed by DENX [http://www.denx.de/wiki/U-Boot].

NOTE
Access to the boot loader is disabled at the factory by default. All console inputs are ignored and users
are directed automatically to the RUGGEDCOM ROS user interface.

To first enable access to the boot loader, do the following:


1. Using a PC/laptop, create a file named bootoption.txt and include the following line in the file:

Security=no

2. Upload the file to the device or insert a microSD/microSDHC card containing the file and reboot the device.

NOTE
Access to BIST and the boot loader can be later revoked by changing no to yes.

To access the boot loader, do the following:


1. Connect to RUGGEDCOM ROS through the RS-232 console connection and a terminal application. For more
information, refer to Section 2.1.1, “Connecting Directly” .
2. Reset the device. For more information, refer to Section 3.13, “Resetting the Device” .
3. As soon as the device starts to boot up, press Ctrl-Z. The command prompt for Uboot appears.

=>

4. Type help to view a list of all available options under Uboot.

54 Accessing the Boot Loader


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Device Management
This chapter describes how to configure and manage the device and its components, such as module interfaces,
logs and files.

NOTE
For information about how to configure the device to work with a network, refer to Chapter 5, Setup
and Configuration .

CONTENTS
• Section 3.1, “Viewing Product Information”
• Section 3.2, “Viewing CPU Diagnostics”
• Section 3.3, “Viewing the Status of the Power Supplies”
• Section 3.4, “Restoring Factory Defaults”
• Section 3.5, “Uploading/Downloading Files”
• Section 3.6, “Managing Logs”
• Section 3.7, “Managing Ethernet Ports”
• Section 3.8, “Managing IP Interfaces”
• Section 3.9, “Managing IP Gateways”
• Section 3.10, “Configuring IP Services”
• Section 3.11, “Managing Remote Monitoring”
• Section 3.12, “Upgrading/Downgrading Firmware”
• Section 3.13, “Resetting the Device”
• Section 3.14, “Decommissioning the Device”

Section 3.1

Viewing Product Information


During troubleshooting or when ordering new devices, Siemens personnel may request specific information about
the device, such as the model, order code or serial number.
To view information about the device, navigate to Diagnostics » View Product Information . The Product
Information form appears.

Viewing Product Information 55


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Figure 9: Product Information Form


1. MAC Address Box    2. Order Code Box    3. Classification Box    4. Serial Number Box    5. Main Version Box    6. Hardware ID Box   
7. Reload Button

This screen displays the following information:

Parameter Description

MAC Address Synopsis:   ##-##-##-##-##-## where ## ranges 0 to FF


Shows the unique MAC address of the device.

Order Code Synopsis:   Any 57 characters


Shows the order code of the device.

Classification Synopsis:   Any 15 characters


Provides system classification.
The value Controlled indicates the main firmware is a Controlled
release. The value Non-Controlled indicates the main firmware is a
Non-Controlled release. The Controlled main firmware can run on
Controlled units, but it can not run on Non-Controlled units. The
Non-Controlled main firmware can run on both Controlled and Non-
Controlled units.

Serial Number Synopsis:   Any 31 characters


Shows the serial number of the device.

Main Version Synopsis:   Any 47 characters


Shows the version and build date of the main operating system
software.

Hardware ID Synopsis:   { RSG2488, RSG2488 v2 }


Shows the type, part number, and revision level of the hardware.

56 Viewing Product Information


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Section 3.2

Viewing CPU Diagnostics


To view CPU diagnostic information useful for troubleshooting hardware and software performance, navigate to
Diagnostics » View CPU Diagnostics . The CPU Diagnostics form appears.

10
11

Figure 10: CPU Diagnostics Form


1. Running Time Box    2. CPU Usage Box    3. RAM Total Box    4. RAM Free Box    5. RAM Low Watermark Box    6. DMA RAM Free Box   
7. DMA RAM Low Watermark Box    8. Temperature Box    9. Free Rx Bufs Box    10. Free Tx Bufs Box    11. Reload Button

This screen displays the following information:

Parameter Description

Running Time Synopsis:   DDDD days, HH:MM:SS


The amount of time since the device was last powered on.

CPU Usage Synopsis:   0.0 to 100.0%


The percentage of available CPU cycles used for device operation as
measured over the last second.

RAM Total Synopsis:   0 to 4294967295


The total size of RAM in the system.

RAM Free Synopsis:   0 to 4294967295


The total size of RAM still available.

RAM Low Watermark Synopsis:   0 to 4294967295


The size of RAM that have never been used during the system
runtime.

DMA RAM Free Synopsis:   0 to 4294967295


The total size of DMA RAM still available.

DMA RAM Low Watermark Synopsis:   0 to 4294967295

Viewing CPU Diagnostics 57


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Parameter Description
The size of DMA RAM that have never been used during the system
runtime.

Temperature Synopsis:   -32768 to 32767 C


The temperature on CPU board.

Free Rx Bufs Synopsis:   0 to 4294967295


Free Rx Buffers.

Free Tx Bufs Synopsis:   0 to 4294967295


Free Tx Buffers.

Section 3.3

Viewing the Status of the Power Supplies


To view the current status of the power supplies, navigate to Diagnostics » Power Supply Status . The Power
Supply Status table appears.

Figure 11: Power Supply Status Table

This table displays the following information:

Parameter Description

ID Synopsis:   1 to 2

Voltage Synopsis:   0 to 4294967295 mV


The millivolt output voltage.

Current Synopsis:   0 to 4294967295 mA


The milliampere output current.

Temperature Synopsis:   -32768 to 32767 C


The temperature of the power supply.

InStatus Synopsis:   { ----, Out of range , Good }


Specifies whether or not the power supply input voltage is in range.
For dual DC/DC power supplies, the input voltage range is between
36 and 72 V.
For dual AC/DC power supplies, the input voltage range for AC is
between 85 and 264 VAC and, for DC, 95 and 300 VDC.

OutStatus Synopsis:   { ----, Out of range , Good }

58 Viewing the Status of the Power Supplies


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Parameter Description
Specifies whether or not the power supply output voltage is in
range. The output voltage range is 12 V +/- 1%.

Section 3.4

Restoring Factory Defaults


The device can be completely or partially restored to its original factory default settings. Excluding groups of
parameters from the factory reset, such as those that affect basic connectivity and SNMP management, is useful
when communication with the device is still required during the reset.
The following categories are not affected by a selective configuration reset:
• IP Interfaces
• IP Gateways
• SNMP Users
• SNMP Security to Group Maps
• SNMP Access
In addition, the following categories are not affected by a full or selective configuration reset:
• Time Zone
• DST Offset
• DST Rule
To restore factory defaults, do the following:
1. Navigate to Diagnostics » Load Factory Defaults . The Load Factory Defaults form appears.

2 3

Figure 12: Load Factory Defaults Form


1. Defaults Choice List    2. Apply Button    3. Reload

2. Configure the following parameter(s) as required:

NOTE
If the VLAN ID for the Management IP interface is not 1, setting Defaults Choice to Selected will
automatically set it to 1.

Parameter Description

Defaults Choice Synopsis:   { None, Selected, All }

Restoring Factory Defaults 59


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Parameter Description
Setting some records like IP Interfaces management interface,
default gateway, SNMP settings to default value would cause
switch not to be accessible with management applications. This
parameter allows user to choose to load defaults to Selected
tables, which would preserve configuration for tables that are
critical for switch management applications, or to force All tables
to default settings.

3. Click Apply.

Section 3.5

Uploading/Downloading Files
Files can be transferred between the device and a host computer using any of the following methods:
• Xmodem using the CLI shell over a Telnet or RS-232 console session
• TFTP client using the CLI shell in a console session and a remote TFTP server
• TFTP server from a remote TFTP client
• SFTP (secure FTP over SSH) from a remote SFTP client
• microSD/microSDHC card

IMPORTANT!
Scripts can be used to automate the management of files on the device. However, depending on the
size of the target file(s), a delay between any concurrent write and read commands may be required,
as the file may not have been fully saved before the read command is issued. A general delay of five
seconds is recommended, but testing is encouraged to optimize the delay for the target file(s) and
operating environment.

NOTE
The contents of the internal file system are fixed. New files and directories cannot be created, and
existing files cannot be deleted. Only the files that can be uploaded to the device can be overwritten.

Files that may need to be uploaded or downloaded include:


• main.bin – the main RUGGEDCOM ROS application firmware image
• fpga2488.bin – the FPGA firmware binary image
• config.csv – the complete configuration database, in the form of a comma-delimited ASCII text file
• factory.txt – Contains the MAC address, order code and serial number. Factory data must be signed.
• banner.txt – contains text that appears on the login screen
• bootoption.txt – controls access to the bootloader and BIST interfaces

60 Uploading/Downloading Files
RUGGEDCOM ROS Chapter 3
User Guide Device Management

NOTE
Multiple versions of the standard files can be saved on the microSD/microSDHC card. However, if any
file resides in the root directory of the microSD/microSDHC card and has the same filename as a file in
the internal memory, RUGGEDCOM ROS will automatically load the file during the next boot up.

CONTENTS
• Section 3.5.1, “Uploading/Downloading Files Using XMODEM”
• Section 3.5.2, “Uploading/Downloading Files Using a TFTP Client”
• Section 3.5.3, “Uploading/Downloading Files Using a TFTP Server”
• Section 3.5.4, “Uploading/Downloading Files Using an SFTP Server”
• Section 3.5.5, “Uploading/Downloading Files Using the microSD/microSDHC Card”

Section 3.5.1

Uploading/Downloading Files Using XMODEM


To updload or download a file using XMODEM, do the following:

NOTE
This method requires a host computer that has terminal emulation or Telnet software installed and the
ability to perform XMODEM transfers.

NOTE
Xmodem transfers can only be performed through the serial console, which is authenticated during
login.

1. Establish a direct connection between the device and the host computer. For more information, refer to
Section 2.1.1, “Connecting Directly” .
2. Log in to the device as an admin user and access the CLI shell. For more information about accessing the CLI
shell, refer to Section 2.6, “Using the Command Line Interface” .

NOTE
The send option sends files to the host computer, while the receive option pulls files from the
host computer.

3. At the CLI prompt, type:


xmodem [ send | receive ] filename

Where:
• filename is the name of the file (i.e. main.bin)

NOTE
If available in the terminal emulation or Telnet software, select the XModem 1K protocol for
transmission over the standard XModem option.

4. When the device responds with


Press Ctrl-X to cancel

Uploading/Downloading Files Using XMODEM 61


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

, launch the XMODEM transfer from the host computer. The device will indicate when the transfer is
complete.
The following is an example from the CLI shell of a successful XMODEM file transfer:

>xmodem receive main.bin


Press Ctrl-X to cancel
Receiving data now ...C
Received 1428480 bytes. Closing file main.bin ...
main.bin transferred successfully

Section 3.5.2

Uploading/Downloading Files Using a TFTP Client


To updload or download a file using a TFTP client, do the following:

IMPORTANT!
TFTP does not define an authentication scheme. Any use of the TFTP client or server is considered
highly insecure.

NOTE
This method requires a TFTP server that is accessible over the network.

1. Identify the IP address of the computer running the TFTP server.


2. Establish a direct connection between the device and a host computer. For more information, refer to
Section 2.1.1, “Connecting Directly” .
3. Log in to the device as an admin user and access the CLI shell. For more information about accessing the CLI
shell, refer to Section 2.6, “Using the Command Line Interface” .
4. At the CLI prompt, type:
tftp address [ get | put ] source-filename destination-filename

Where:
• get copies files from the host computer to the device
• put copies files from the device to the host computer
• address is the IP address of the computer running the TFTP server
• source-filename is the name of the file to be transferred
• destination-filename is the name of the file (on the device or the TFTP server) that will be replaced
during the transfer
The following is an example of a successful TFTP client file transfer:

>tftp 10.0.0.1 get ROS-CF52_Main_v3.7.0.bin main.bin


TFTP CMD: main.bin transfer ok. Please wait, closing file ...
TFTP CMD: main.bin loading succesful.

62 Uploading/Downloading Files Using a TFTP Client


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Section 3.5.3

Uploading/Downloading Files Using a TFTP Server


To updload or download a file using a TFTP server, do the following:

IMPORTANT!
TFTP does not define an authentication scheme. Any use of the TFTP client or server is considered
highly insecure.

NOTE
This method requires a host computer that has TFTP server software installed.

IMPORTANT!
Interaction with TFTP servers is strictly controlled within the device to prevent unauthorized access.
Make sure the device is configured to accept the TFTP connection. For more information, refer to
Section 3.10, “Configuring IP Services” .

1. Establish a direct connection between the device and the host computer. For more information, refer to
Section 2.1.1, “Connecting Directly” .
2. Initialize the TFTP server on the host computer and launch the TFTP transfer. The server will indicate when the
transfer is complete.
The following is an example of a successful TFTP server exchange:

C:\>tftp -i 10.1.0.1 put C:\files\ROD-CF52_Main_v3.7.0.bin main.bin


Transfer successful: 1428480 bytes in 4 seconds, 375617 bytes/s

Section 3.5.4

Uploading/Downloading Files Using an SFTP Server


SFTP (Secure File Transfer Protocol) is a file transfer mechanism that uses SSH to encrypt every aspect of file
transfer between a networked client and server.

NOTE
The device does not have an SFTP client and, therefore, can only receive SFTP files from an external
source. SFTP requires authentication for the file transfer.

To updload or download a file using an SFTP server, do the following:

NOTE
This method requires a host computer that has SFTP client software installed.

1. Establish an SFTP connection between the device and the host computer.
2. Launch the SFTP transfer. The client will indicate when the transfer is complete.
The following is an example of a successful SFTP server exchange:

user@host$ sftp admin@ros_ip


Connecting to ros_ip...
admin@ros_ip's password:
sftp> put ROS-CF52_Main_v3-7-0.bin main.bin

Uploading/Downloading Files Using a TFTP Server 63


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Uploading ROS-CF52_Main_v3-7-0.bin to /main.bin


ROS-CF52_Main_v3-7-0.bin 100% 2139KB 48.6KB/s 00:44
sftp>

Section 3.5.5

Uploading/Downloading Files Using the microSD/microSDHC


Card
The removable microSD/microSDHC card can be used to transfer files between the device, a host computer, and/or
another device for a variety of purposes. For more information about the removable microSD/microSDHC card and
its uses, refer to Section 1.10, “Removable Memory” .

IMPORTANT!
Before sharing an encrypted configuration file with another device, make sure both devices share the
same password/passphrase for deciphering encrypted configuration files. For more information on how
to enable data encryption, refer to Section 4.7.1, “Configuring Data Encryption” .

IMPORTANT!
After uploading or downloading a file, allow at least twenty seconds before removing the microSD/
microSDHC card to ensure the data has been fully transferred.

NOTE
The files on the microSD/microSDHC card and the device can be renamed during the transfer. This is
useful, for instance, when multiple versions of the firmware binary file are available on the microSD/
microSDHC card. The correct version can be transferred to the device and renamed main.bin to
replace the version currently on the device.

To upload a file from the card to the device, log in to the CLI shell and type:
copy a:\sourceFile destinationFile

To download a file from the device to the card, type:


copy sourceFile a:\destinationFile

Section 3.6

Managing Logs
The crash (crashlog.txt) and system (syslog.txt) log files contain historical information about events that
have occurred during the operation of the device.
The crash log contains debugging information related to problems that might have resulted in unplanned restarts
of the device or which may effect the operation of the device. A file size of 0 bytes indicates that no unexpected
events have occurred.
The system log contains a record of significant events including startups, configuration changes, firmware
upgrades and database re-initializations due to feature additions. The system log will accumulate information until
it is full, holding approximately 2 MB of data.

Uploading/Downloading Files Using the microSD/


64 microSDHC Card
RUGGEDCOM ROS Chapter 3
User Guide Device Management

NOTE
Syslog files backed up to the microSD/microSDHC card are timestamped in the format of year, month
and date (e.g. syslog.txt.20140101). This allows for multiple syslog files to be saved on the same card.

CONTENTS
• Section 3.6.1, “Viewing Local Logs”
• Section 3.6.2, “Clearing Local Logs”
• Section 3.6.3, “Configuring the Local System Log”
• Section 3.6.4, “Managing Remote Logging”

Section 3.6.1

Viewing Local Logs


The local crash and system logs can both be downloaded from the device and viewed in a text editor. For more
information about downloading log files, refer to Section 3.5, “Uploading/Downloading Files” .
To view the system log through the Web interface, navigate to Diagnostics » View System Log . The syslog.txt
form appears.

Figure 13: syslog.txt Form

Section 3.6.2

Clearing Local Logs


To clear both the local crash and system logs, log in to the CLI shell and type:
clearlogs

To clear only the local system log, log in to the Web interface and do the following:
1. Navigate to Diagnostics » Clear System Log . The Clear System Log form appears.

Viewing Local Logs 65


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Figure 14: Clear System Log Form


1. Confirm Button

2. Click Confirm.

Section 3.6.3

Configuring the Local System Log


To configure the severity level for the local system log, do the following:

NOTE
For maximum reliability, use remote logging. For more information, refer to Section 3.6.4, “Managing
Remote Logging” .

1. Navigate to Administration » Configure Syslog » Configure Local Syslog . The Local Syslog form appears.

2 3

Figure 15: Local Syslog Form


1. Local Syslog Level    2. Apply Button    3. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

Local Syslog Level Synopsis:   { EMERGENCY, ALERT, CRITICAL, ERROR, WARNING,


NOTICE, INFORMATIONAL, DEBUGGING }
Default:   INFORMATIONAL
The severity of the message that has been generated. Note that
the severity level selected is considered the minimum severity
level for the system. For example, if ERROR is selected, the system
sends any syslog messages generated by Error, Critical, Alert and
Emergency.

3. Click Apply.

66 Configuring the Local System Log


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Section 3.6.4

Managing Remote Logging


In addition to the local system log maintained on the device, a remote system log can be configured as well to
collect important event messages. The syslog client resides on the device and supports up to 5 collectors (or syslog
servers).
The remote syslog protocol, defined in RFC 3164, is a UDP/IP-based transport that enables the device to send event
notification messages across IP networks to event message collectors, also known as syslog servers. The protocol
is designed to simply transport these event messages from the generating device to the collector(s).

CONTENTS
• Section 3.6.4.1, “Configuring the Remote Syslog Client”
• Section 3.6.4.2, “Viewing a List of Remote Syslog Servers”
• Section 3.6.4.3, “Adding a Remote Syslog Server”
• Section 3.6.4.4, “Deleting a Remote Syslog Server”

Section 3.6.4.1
Configuring the Remote Syslog Client
To configure the remote syslog client, do the following:
1. Navigate to Administration » Configure Syslog » Configure Remote Syslog Client . The Remote Syslog
Client form appears.

2 3

Figure 16: Remote Syslog Client Form


1. UDP Port    2. Apply Button    3. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

UDP Port Synopsis:   1025 to 65535 or { 514 }


Default:   514
The local UDP port through which the client sends information to
the server(s).

3. Click Apply.

Managing Remote Logging 67


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Section 3.6.4.2
Viewing a List of Remote Syslog Servers
To view a list of known remote syslog servers, navigate to Administration » Configure Syslog » Configure
Remote Syslog Server . The Remote Syslog Server table appears.

Figure 17: Remote Syslog Server Table

If remote syslog servers have not been configured, add the servers as needed. For more information, refer to
Section 3.6.4.3, “Adding a Remote Syslog Server” .

Section 3.6.4.3
Adding a Remote Syslog Server
RUGGEDCOM ROS supports up to 5 remote syslog servers (or collectors). Similar to the local system log, a remote
system log server can be configured to log information at a specific severity level. Only messages of a severity
level equal to or greater than the specified severity level are written to the log.
To add a remote syslog server to the list of known servers, do the following:
1. Navigate to Administration » Configure Syslog » Configure Remote Syslog Server . The Remote Syslog
Server table appears.

Figure 18: Remote Syslog Server Table


1. InsertRecord

2. Click InsertRecord. The Remote Syslog Server form appears.

68 Viewing a List of Remote Syslog Servers


RUGGEDCOM ROS Chapter 3
User Guide Device Management

5 7

Figure 19: Remote Syslog Server Form


1. IP Address Box    2. UDP Port Box    3. Facility Box    4. Severity Box    5. Apply Button    6. Delete Button    7. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

IP Address Synopsis:   ###.###.###.### where ### ranges from 0 to 255


Syslog server IP Address.

UDP Port Synopsis:   1025 to 65535 or { 514 }


Default:   514
The UDP port number on which the remote server listens.

Facility Synopsis:   { USER, LOCAL0, LOCAL1, LOCAL2, LOCAL3, LOCAL4,


LOCAL5, LOCAL6, LOCAL7 }
Default:   LOCAL7
Syslog Facility is one information field associated with a syslog
message. The syslog facility is the application or operating system
component that generates a log message. ROS map all syslog
logging information onto a single facility which is configurable by
user to facilitate remote syslog server.

Severity Synopsis:   { EMERGENCY, ALERT, CRITICAL, ERROR, WARNING,


NOTICE, INFORMATIONAL, DEBUGGING }
Default:   DEBUGGING
The severity level is the severity of the message that has been
generated. Please note that the severity level user select is
accepted as the minimum severity level for the system. For
example, if user selects the severity level as 'Error' then the system
send any syslog message originated by Error, Critical, Alert and
Emergency.

4. Click Apply.

Section 3.6.4.4
Deleting a Remote Syslog Server
To delete a remote syslog server from the list of known servers, do the following:

Deleting a Remote Syslog Server 69


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

1. Navigate to Administration » Configure Syslog » Configure Remote Syslog Server . The Remote Syslog
Server table appears.

Figure 20: Remote Syslog Server Table

2. Select the server from the table. The Remote Syslog Server form appears.

5 7

Figure 21: Remote Syslog Server Form


1. IP Address Box    2. UDP Port Box    3. Facility Box    4. Severity Box    5. Apply Button    6. Delete Button    7. Reload Button

3. Click Delete.

Section 3.7

Managing Ethernet Ports


The following section describes how to set up and manage Ethernet ports.

NOTE
For information about configuring remote monitoring for Ethernet ports, refer to Section 3.11,
“Managing Remote Monitoring” .

CONTENTS
• Section 3.7.1, “Controller Protection Through Link Fault Indication (LFI)”

70 Managing Ethernet Ports


RUGGEDCOM ROS Chapter 3
User Guide Device Management

• Section 3.7.2, “Viewing the Status of Ethernet Ports”


• Section 3.7.3, “Viewing Statistics for All Ethernet Ports”
• Section 3.7.4, “Viewing Statistics for Specific Ethernet Ports”
• Section 3.7.5, “Clearing Statistics for Specific Ethernet Ports”
• Section 3.7.6, “Viewing Statistics for the Ethernet Management Port”
• Section 3.7.7, “Clearing Statistics for the Ethernet Management Port”
• Section 3.7.8, “Managing SFP Transceivers”
• Section 3.7.9, “Configuring an Ethernet Port”
• Section 3.7.10, “Configuring Port Rate Limiting”
• Section 3.7.11, “Configuring Port Mirroring”
• Section 3.7.12, “Configuring Link Detection”
• Section 3.7.13, “Detecting Cable Faults”
• Section 3.7.14, “Resetting Ethernet Ports”

Section 3.7.1

Controller Protection Through Link Fault Indication (LFI)


Modern industrial controllers often feature backup Ethernet ports used in the event of a link failure. When these
interfaces are supported by media (such as fiber) that employ separate transmit and receive paths, the interface
can be vulnerable to failures that occur in only one of the two paths.
Consider for instance two switches (A and B) connected to a controller. Switch A is connected to the main port on
the controller, while Switch B is connected to the backup port, which is shut down by the controller while the link
with Switch A is active. Switch B must forward frames to the controller through Switch A.

1 2

3 4

Figure 22: Example
1. Switch A    2. Switch B    3. Main Transmit Path    4. Backup Transmit Path    5. Controller

If the transmit path from the controller to Switch A fails, Switch A still generates a link signal to the controller
through the receive path. The controller still detects the link with Switch A and does not failover to the backup
port.
This situation illustrates the need for a notification method that tells a link partner when the link integrity signal
has stopped. Such a method natively exists in some link media, but not all.
100Base-TX, 1000Base-T, 1000Base-X Includes a built-in auto-negotiation feature (i.e. a special flag called Remote Fault Indication
is set in the transmitted auto-negotation signal).

Controller Protection Through Link Fault Indication (LFI) 71


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

100Base-FX Links Includes a standard Far-End-Fault-Indication (FEFI) feature defined by the IEEE 802.3
standard for this link type. This feature includes:
• Transmitting FEFI
Transmits a modified link integrity signal in case a link failure is detected (i.e. no link signal
is received from the link partner)
• Detecting FEFI
Indicates link loss in case an FEFI signal is received from the link partner

10Base-FL LInks No standard support.

10Base-FL links do not have a native link partner notification mechanism and FEFI support in 100Base-FX links is
optional according to the IEEE 802.3 standard, which means that some links partners may not support it.
Siemens offers an advanced Link-Fault-Indication (LFI) feature for the links that do not have a native link partner
notification mechanism. With LFI enabled, the device bases the generation of a link integrity signal upon its
reception of a link signal. In the example described previously, if switch A fails to receive a link signal from the
controller, it will stop generating a link signal. The controller will detect the link failure and failover to the backkup
port.

IMPORTANT!
If both link partners have the LFI feature, it must not be enabled on both sides of the link. If it is
enabled on both sides, the link will never be established, as each link partner will be waiting for the
other to transmit a link signal.

The switch can also be configured to flush the MAC address table for the controller port. Frames destined for the
controller will be flooded to Switch B where they will be forwarded to the controller (after the controller transmits
its first frame).

Section 3.7.2

Viewing the Status of Ethernet Ports


To view the current status of each Ethernet port, navigate to Ethernet Ports » View Port Status . The Port Status
table appears.

72 Viewing the Status of Ethernet Ports


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Figure 23: Port Status Table

This table displays the following information:

Parameter Description

Port Synopsis:   1/1 to maximum port number


The port number as seen on the front plate silkscreen of the switch.

Name Synopsis:   Any 15 characters


A descriptive name that may be used to identify the device conected
on that port.

Link Synopsis:   { ----, ----, Down, Up }


The port's link status.

Speed Synopsis:   { ---, 10M, 100M, 1G, 10G }


The port's current speed.

Duplex Synopsis:   { ----, Half, Full }


The port's current duplex status.

Viewing the Status of Ethernet Ports 73


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Section 3.7.3

Viewing Statistics for All Ethernet Ports


To view statistics collected for all Ethernet ports, navigate to Ethernet Stats » View Ethernet Statistics . The
Ethernet Statistics table appears.

Figure 24: Ethernet Statistics Table

This table displays the following information:

Parameter Description

Port Synopsis:   1/1 to maximum port number


The port number as seen on the front plate silkscreen of the switch.

State Synopsis:   { ----, ----, Down, Up }

InOctets Synopsis:   0 to 4294967295


The number of octets in received good packets (Unicast+Multicast
+Broadcast) and dropped packets.

OutOctets Synopsis:   0 to 4294967295


The number of octets in transmitted good packets.

InPkts Synopsis:   0 to 4294967295


The number of received good packets (Unicast+Multicast+Broadcast)
and dropped packets.

OutPkts Synopsis:   0 to 4294967295


The number of transmitted good packets.

ErrorPkts Synopsis:   0 to 4294967295


The number of any type of erroneous packet.

Section 3.7.4

Viewing Statistics for Specific Ethernet Ports


To view statistics collected for specific Ethernet ports, navigate to Ethernet Stats » View Ethernet Port Statistics
. The Ethernet Port Statistics table appears.

74 Viewing Statistics for All Ethernet Ports


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Figure 25: Ethernet Port Statistics Table

This table displays the following information:

Parameter Description

Port Synopsis:   1/1 to maximum port number


The port number as seen on the front plate silkscreen of the switch.

InOctets Synopsis:   0 to 18446744073709551615


The number of octets in received good packets (Unicast+Multicast
+Broadcast) and dropped packets.

OutOctets Synopsis:   0 to 18446744073709551615


The number of octets in transmitted good packets.

InPkts Synopsis:   0 to 18446744073709551615


The number of received good packets (Unicast+Multicast+Broadcast)
and dropped packets.

OutPkts Synopsis:   0 to 18446744073709551615


The number of transmitted good packets.

TotalInOctets Synopsis:   0 to 18446744073709551615


The total number of octets of all received packets. This includes data
octets of rejected and local packets which are not forwarded to the
switching core for transmission. It should reflect all the data octets
received on the line.

TotalInPkts Synopsis:   0 to 18446744073709551615


The number of received packets. This includes rejected, dropped
local, and packets which are not forwarded to the switching core for
transmission. It should reflect all packets received ont the line.

InBroadcasts Synopsis:   0 to 18446744073709551615


The number of good Broadcast packets received.

InMulticasts Synopsis:   0 to 18446744073709551615


The number of good Multicast packets received.

CRCAlignErrors Synopsis:   0 to 4294967295


The number of packets received which meet all the following
conditions:
• Packet data length is between 64 and 1536 octets inclusive.
• Packet has invalid CRC.
• Collision Event has not been detected.
• Late Collision Event has not been detected.

OversizePkts Synopsis:   0 to 4294967295

Viewing Statistics for Specific Ethernet Ports 75


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Parameter Description
The number of packets received with data length greater than 1536
octets and valid CRC.

Fragments Synopsis:   0 to 4294967295


The number of packets received which meet all the following
conditions:
• Packet data length is less than 64 octets, or packet without SFD
and is less than 64 octets in length.
• Collision Event has not been detected.
• Late Collision Event has not been detected.
• Packet has invalid CRC.

Jabbers Synopsis:   0 to 4294967295


The number of packets which meet all the following conditions:
• Packet data length is greater that 1536 octets.
• Packet has invalid CRC.

Collisions Synopsis:   0 to 4294967295


The number of received packets for which Collision Event has been
detected.

LateCollisions Synopsis:   0 to 4294967295


The number of received packets for which Late Collision Event has
been detected.

Pkt64Octets Synopsis:   0 to 4294967295


The number of received and transmitted packets with size of 64
octets. This includes received and transmitted packets as well as
dropped and local received packets. This does not include rejected
received packets.

Pkt65to127Octets Synopsis:   0 to 4294967295


The number of received and transmitted packets with size of 65 to
127 octets. This includes received and transmitted packets as well as
dropped and local received packets. This does not include rejected
received packets.

Pkt128to255Octets Synopsis:   0 to 4294967295


The number of received and transmitted packets with size of 128 to
257 octets. This includes received and transmitted packets as well as
dropped and local received packets. This does not include rejected
received packets.

Pkt256to511Octets Synopsis:   0 to 4294967295


The number of received and transmitted packets with size of 256 to
511 octets. This includes received and transmitted packets as well as
dropped and local received packets. This does not include rejected
received packets.

Pkt512to1023Octets Synopsis:   0 to 4294967295


The number of received and transmitted packets with size of 512 to
1023 octets. This includes received and transmitted packets as well
as dropped and local received packets. This does not include rejected
received packets.

Pkt1024to1536Octets Synopsis:   0 to 4294967295


The number of received and transmitted packets with size of 1024 to
1536 octets. This includes received and transmitted packets as well
as dropped and local received packets. This does not include rejected
received packets.

76 Viewing Statistics for Specific Ethernet Ports


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Parameter Description

DropEvents Synopsis:   0 to 4294967295


The number of received packets that are droped due to lack of
receive buffers.

OutMulticasts Synopsis:   0 to 18446744073709551615


The number of transmitted Multicast packets. This does not include
Broadcast packets.

OutBroadcasts Synopsis:   0 to 18446744073709551615


The number of transmitted Broadcast packets.

UndersizePkts Synopsis:   0 to 4294967295


The number of received packets which meet all the following
conditions:
• Packet data length is less than 64 octets.
• Collision Event has not been detected.
• Late Collision Event has not been detected.
• Packet has valid CRC.

Section 3.7.5

Clearing Statistics for Specific Ethernet Ports


To clear the statistics collected for one or more Ethernet ports, do the following:
1. Navigate to Ethernet Stats » Clear Ethernet Port Statistics . The Clear Ethernet Port Statistics form
appears.

1
2

Figure 26: Clear Ethernet Port Statistics Form (Typical)


1. Port Check Boxes    2. Confirm Button

2. Select one or more Ethernet ports.


3. Click Confirm.

Section 3.7.6

Viewing Statistics for the Ethernet Management Port


To view statistics collected for the Ethernet Management port, navigate to Ethernet Stats » View Ethernet
MgmtPort Statistics . The Ethernet Management Port Statistics table appears.

Clearing Statistics for Specific Ethernet Ports 77


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Figure 27: Ethernet Management Port Statistics Table

This table displays the following information:

Parameter Description

InOctets Synopsis:   0 to 18446744073709551615


The number of octets in received good packets (Unicast+Multicast
+Broadcast) and dropped packets.

OutOctets Synopsis:   0 to 18446744073709551615


The number of octets in transmitted good packets.

InPkts Synopsis:   0 to 18446744073709551615


The number of received good packets (Unicast+Multicast+Broadcast)
and dropped packets.

OutPkts Synopsis:   0 to 18446744073709551615


The number of transmitted good packets.

InBroadcasts Synopsis:   0 to 18446744073709551615


The number of good Broadcast packets received.

InMulticasts Synopsis:   0 to 18446744073709551615


The number of good Multicast packets received.

CRCAlignErrors Synopsis:   0 to 4294967295


The number of packets received which meet all the following
conditions:
• Packet data length is between 64 and 1536 octets inclusive.

78 Viewing Statistics for the Ethernet Management Port


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Parameter Description
• Packet has invalid CRC.
• Collision Event has not been detected.
• Late Collision Event has not been detected.

OversizePkts Synopsis:   0 to 4294967295


The number of packets received with data length greater than 1536
octets and valid CRC.

Fragments Synopsis:   0 to 4294967295


The number of packets received which meet all the following
conditions:
• Packet data length is less than 64 octets, or packet without SFD
and is less than 64 octets in length.
• Collision Event has not been detected.
• Late Collision Event has not been detected.
• Packet has invalid CRC.

Jabbers Synopsis:   0 to 4294967295


The number of packets which meet all the following conditions:
• Packet data length is greater that 1536 octets.
• Packet has invalid CRC.

Pkt64Octets Synopsis:   0 to 4294967295


The number of received and transmitted packets with size of 64
octets. This includes received and transmitted packets as well as
dropped and local received packets. This does not include rejected
received packets.

Pkt65to127Octets Synopsis:   0 to 4294967295


The number of received and transmitted packets with size of 65 to
127 octets. This includes received and transmitted packets as well as
dropped and local received packets. This does not include rejected
received packets.

Pkt128to255Octets Synopsis:   0 to 4294967295


The number of received and transmitted packets with size of 128 to
257 octets. This includes received and transmitted packets as well as
dropped and local received packets. This does not include rejected
received packets.

Pkt256to511Octets Synopsis:   0 to 4294967295


The number of received and transmitted packets with size of 256 to
511 octets. This includes received and transmitted packets as well as
dropped and local received packets. This does not include rejected
received packets.

Pkt512to1023Octets Synopsis:   0 to 4294967295


The number of received and transmitted packets with size of 512 to
1023 octets. This includes received and transmitted packets as well
as dropped and local received packets. This does not include rejected
received packets.

Pkt1024to1536Octets Synopsis:   0 to 4294967295


The number of received and transmitted packets with size of 1024 to
1536 octets. This includes received and transmitted packets as well
as dropped and local received packets. This does not include rejected
received packets.

DropEvents Synopsis:   0 to 4294967295

Viewing Statistics for the Ethernet Management Port 79


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Parameter Description
The number of received packets that are droped due to lack of
receive buffers.

OutMulticasts Synopsis:   0 to 18446744073709551615


The number of transmitted Multicast packets. This does not include
Broadcast packets.

OutBroadcasts Synopsis:   0 to 18446744073709551615


The number of transmitted Broadcast packets.

UndersizePkts Synopsis:   0 to 4294967295


The number of received packets which meet all the following
conditions:
• Packet data length is less than 64 octets.
• Collision Event has not been detected.
• Late Collision Event has not been detected.
• Packet has valid CRC.

Section 3.7.7

Clearing Statistics for the Ethernet Management Port


To clear the statistics collected for the Ethernet Management port, do the following:
1. Navigate to Ethernet Stats » Clear Ethernet MgmtPort Statistics . The Clear Ethernet Management Port
Statistics form appears.

Figure 28: Clear Ethernet Management Port Statistics Form (Typical)


1. Confirm Button

2. Click Confirm.

Section 3.7.8

Managing SFP Transceivers


RUGGEDCOM ROS supports Small Form Factor Pluggable (SFP) transceivers to provide a 1000Base-X, 100Base-FX,
1000Base-T or 100Base-TX link.

NOTE
Since 1000Base-X fiber SFP transceivers are standardized, RUGGEDCOM ROS supports any model of
this type. It is strongly recommended to use SFP transceiver models offered by Siemens only. Siemens
performs extensive testing on the transceivers in harsh conditions. If a different SFP transceiver model
is used, it is the user’s responsibility to verify it meets environmental and usage requirements.

80 Clearing Statistics for the Ethernet Management Port


RUGGEDCOM ROS Chapter 3
User Guide Device Management

1000Base-T copper SFP transceivers are not standardized. RUGGEDCOM ROS supports only selected
models of this type.

NOTE
SFP transceivers are hot swappable.
When an SFP transceiver is inserted in to the SFP cage, the speed and auto-negotiation settings for
the port are automatically adjusted to the appropriate values. For example, if a 1 G SFP transceiver is
installed, the speed of the port is automatically changed to 1 G and auto-negotiation is set to On.

NOTE
Due to the uncertain latency introduced by the built-in PHY, the time accuracy of IEEE 1588 may be
significantly degraded on a copper SFP port.

CONTENTS
• Section 3.7.8.1, “Configuring an SFP Port”
• Section 3.7.8.2, “Monitoring an SFP Port”
• Section 3.7.8.3, “Displaying Information for an SFP Port”

Section 3.7.8.1
Configuring an SFP Port
Depending on the required link media type, an SFP port may require some explicit configuration:
• For 1000Base-X or 1000Base-T links, the speed of the SFP port must be set to 1 Gbps.
• For 100Base-FX or 100Base-TX links, the speed must be set to 100 Mbps.
• Auto-negotiation can be configured to On when the port speed is set to 1 Gbps, or to Off when the port speed is
set to 100 Mbps.
• Duplex mode cannot be configured on an SFP port and is always forced to full duplex.
For more information about configuring SFP transceiver ports and other Ethernet ports on the device, refer to
Section 3.7.9, “Configuring an Ethernet Port” .

Section 3.7.8.2
Monitoring an SFP Port
RUGGEDCOM ROS supports hot-swapping of SFP transceivers on SFP ports and will automatically detect when an
SFP transceiver is removed or installed.
When RUGGEDCOM ROS detects that an SFP transceiver is plugged into an SFP port, it reads the transceiver
information and determines the transceiver type. This decision results in RUGGEDCOM ROS either accepting,
accepting and reconfiguring, or rejecting the SFP port.
The following table shows in which cases an SFP transceiver is accepted or accepted and reconfigured.
Configured Speed Detected SFP Type: 1000Base-X Detected SFP Type: 100Base-FX Detected SFP Type: 1000Base-T

Accept and automatically set


1 Gbps Accept the speed to 100 Mbps and Accept
set auto-negotiation to Off

Configuring an SFP Port 81


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Configured Speed Detected SFP Type: 1000Base-X Detected SFP Type: 100Base-FX Detected SFP Type: 1000Base-T

Compare the transceiver model


against a list of supported
Accept and automatically
models. Accept if it is in the
100 Mbps set the speed to 1 Gbps and Accept
list. Otherwise, automatically
set auto-negotiation to On
set the speed to 1 Gbps and
set auto-negotiation to On.

If the transceiver is accepted, the Media parameter under Ethernet Ports » Configure Port Parameters shows
detailed information about the SFP transceiver, including Gigabit Ethernet Compliance Code, transmission media,
connector type, and link length. For example:

SFP 1000LX SM LC 10 km
SFP 1000T 100 m

If the transceiver is not recognized, it is rejected. An alarm is also generated and the port is blocked so that no link
can be established until the transceiver is replaced. The Media parameter shows the rejected SFP transceiver is
unidentified. For example:

SFP Unidentified

If no transceiver is installed on an SFP port, the Media parameter shows the SFP transceiver is unplugged:

SFP Unplugged

Section 3.7.8.3
Displaying Information for an SFP Port
To display detailed information about an SFP port, do the following:
1. Log in to the device and access the CLI shell. For more information about accessing the CLI shell, refer to
Section 2.6, “Using the Command Line Interface” .
2. Type the following command:
sfp port

Where:
• port is the port number
Information about the SFP port is displayed. For example:

>sfp
1/1

ID: SFP
Extended ID: GBIC/SFP function is defined by serial ID only
Connector: LC
Transceiver:
Gigabit Ethernet Compliance Codes:
1000LX
Fibre Channel link length:
Long Distance (L)
Fibre Channel transmitter technology:
Longwave laser (LC)
Fibre Channel transmission media:
Single Mode (SM)
Fibre Channel speed:
100 MBytes/Sec
Baud Rate, nominal: 1300 MBits/sec

82 Displaying Information for an SFP Port


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Encoding type: 8B10B


Length(9um): 10 km
Length(9um): 10000 m
Length(50um): 550 m
Length(62.5um): 550 m
Length(Copper): Not specified
Vendor: xxxxxxx
IEEE company ID: xxxxxxx
Part number: xxxxxxxxxx
Revision: 0000
Laser wavelength: 1310 nm
>

Section 3.7.9

Configuring an Ethernet Port


To configure an Ethernet port, do the following:

NOTE
Depending on the required link media type, an SFP port may require some explicit configuration.
Before configuring an SFP port, refer to Section 3.7.8.1, “Configuring an SFP Port” .

1. Navigate to Ethernet Ports » Configure Port Parameters . The Port Parameters table appears.

Figure 29: Port Parameters Table

2. Select an Ethernet port. The Port Parameters form appears.

Configuring an Ethernet Port 83


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

10 8

11

Figure 30: Port Parameters Form


1. Port Box    2. Name Box    3. Media Box    4. State Box    5. AutoN Box    6. Speed Box    7. Dupx Box    8. FlowCtrl Box    9. LFI
Box    10. Alarm Box    11. Apply Button    12. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Port Synopsis:   1/1 to maximum port number


Default:   1/1
The port number as seen on the front plate silkscreen of the
switch.

Name Synopsis:   Any 15 characters


Default:   Port x
A descriptive name that may be used to identify the device
connected on that port.

Media Synopsis:   { 100TX, 10FL, 100FX, 1000X, 1000T, 802.11g,


EoVDSL, 100TX Only, 10FL/100SX, 10GX }
Default:   100TX
The type of the port media.

State Synopsis:   { Disabled, Enabled }


Default:   Enabled
Disabling a port will prevent all frames from being sent and
received on that port. Also, when disabled link integrity signal
is not sent so that the link/activity LED will never be lit. You may
want to disable a port for troubleshooting or to secure it from
unauthorized connections.

NOTE
Disabling a port whose media type is set to 802.11g
disables the corresponding wireless module.

AutoN Synopsis:   { Off, On }


Default:   On
Enable or disable IEEE 802.3 auto-negotiation. Enabling auto-
negotiation results in speed and duplex being negotiated upon
link detection; both end devices must be auto-negotiation

84 Configuring an Ethernet Port


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Parameter Description
compliant for the best possible results. 10Mbps and 100Mbps
fiber optic media do not support auto-negotiation so these media
must be explicitly configured to either half or full duplex. Full
duplex operation requires that both ends are configured as such
or else severe frame loss will occur during heavy network traffic.

Speed Synopsis:   { Auto, 10M, 100M, 1G }


Default:   Auto
Speed (in Megabit-per-second or Gigabit-per-second). If auto-
negotiation is enabled, this is the speed capability advertised by
the auto-negotiation process. If auto-negotiation is disabled, the
port is explicitly forced to this speed mode.
AUTO means advertise all supported speed modes.

Dupx Synopsis:   { Auto, Half, Full }


Default:   Auto
Duplex mode. If auto-negotiation is enabled, this is the duplex
capability advertised by the auto-negotiation process. If auto-
negotiation is disabled, the port is explicitly forced to this duplex
mode.
AUTO means advertise all supported duplex modes.

LFI Synopsis:   { Off, On }


Default:   Off
Enabling Link-Fault-Indication (LFI) inhibits transmitting link
integrity signal when the receive link has failed. This allows the
device at far end to detect link failure under all circumstances.

NOTE
This feature must not be enabled at both ends of a
fiber link.

Alarm Synopsis:   { On, Off }


Default:   On
Disabling link state alarms will prevent alarms and LinkUp and
LinkDown SNMP traps from being sent for that port.

NOTE
If one end of the link is fixed to a specific speed and duplex type and the peer auto-negotiates,
there is a strong possibility that the link will either fail to raise, or raise with the wrong settings on
the auto-negotiating side. The auto-negotiating peer will fall back to half-duplex operation, even
when the fixed side is full duplex. Full-duplex operation requires that both ends are configured
as such or else severe frame loss will occur during heavy network traffic. At lower traffic volumes
the link may display few, if any, errors. As the traffic volume rises, the fixed negotiation side will
begin to experience dropped packets, while the auto-negotiating side will experience excessive
collisions. Ultimately, as traffic load approaches 100%, the link will become entirely unusable.
These problems can be avoided by always configuring ports to the appropriate fixed values.

4. Click Apply.

Section 3.7.10

Configuring Port Rate Limiting


To configure port rate limiting, do the following:

Configuring Port Rate Limiting 85


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

1. Navigate to Ethernet Ports » Configure Port Rate Limiting . The Port Rate Limiting table appears.

Figure 31: Port Rate Limiting Table

2. Select an Ethernet port. The Port Rate Limiting form appears.

5 6

Figure 32: Port Rate Limiting Form


1. Port Box    2. Ingress Limit Box    3. Ingress Frames List    4. Egress Limit Box    5. Apply Button    6. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Port Synopsis:   1/1 to maximum port number


Default:   1/1
The port number as seen on the front plate silkscreen of the
switch.

Ingress Limit Synopsis:   64 to 1000000 Kbps or { Disabled }


Default:   1000 Kbps
The rate after which received frames (of the type described by the
ingress frames parameter) will be discarded by the switch.

Ingress Frames Synopsis:   { Broadcast, Multicast, Mcast&FloodUcast,


Bcast&FloodUcast, FloodUcast, Bcast&Mcast,
Bcast&Mcast&FloodUcast, All }
Default:   Broadcast
This parameter specifies the types of frames to be rate-limited on
this port. It applies only to received frames:
• Broadcast - only broadcast frames
• Multicast - only multicast frames
• Bcast&Mcast - broadcast and multicast frames
• Bcast&FloodUcast - broadcast and flooded unicast frames

86 Configuring Port Rate Limiting


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Parameter Description
• Mcast&FloodUcast - multicast and flooded unicast frames
• FloodUcast - only flooded unicast frames

Egress Limit Synopsis:   64 to 1000000 Kbps or { Disabled }


Default:   Disabled
The maximum rate at which the switch will transmit (multicast,
broadcast and unicast) frames on this port. The switch will discard
frames in order to meet this rate if required.

4. Click Apply.

Section 3.7.11

Configuring Port Mirroring


Port mirroring is a troubleshooting tool that copies, or mirrors, all traffic received or transmitted on a designated
port to specified mirror port. If a protocol analyzer is attached to the target port, the traffic stream of valid frames
on any source port is made available for analysis.
Select a target port that has a higher speed than the source port. Mirroring a 100 Mbps port onto a 10 Mbps port
may result in an improperly mirrored stream.
Frames will be dropped if the full-duplex rate of frames on the source port exceeds the transmission speed of the
target port. Since both transmitted and received frames on the source port are mirrored to the target port, frames
will be discarded if the sum traffic exceeds the target port’s transmission rate. This problem reaches its extreme in
the case where traffic on a 100 Mbps full-duplex port is mirrored onto a 10 Mbps half-duplex port.

NOTE
Invalid frames received on the source port will not be mirrored. These include CRC errors, oversize and
undersize packets, fragments, jabbers, collisions, late collisions and dropped events.

IMPORTANT!
Before configuring port mirroring, note the following limitations:
• Traffic will be mirrored onto the target port irrespective of its VLAN membership. It could be the same
as or different from the source port's membership
• Network management frames (such as RSTP, GVRP etc.) may not be mirrored
• Switch management frames generated by the switch (such as Telnet, HTTP, SNMP, etc.) may not be
mirrored

To configure port mirroring, do the following:


1. Navigate to Ethernet Ports » Configure Port Mirroring . The Port Mirroring form appears.

Configuring Port Mirroring 87


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

4
5 6

Figure 33: Port Mirroring Form


1. Port Mirroring Box    2. Source Port Box    3. Target Port Box    4. Apply Button    5. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

Port Mirroring Synopsis:   { Disabled, Enabled }


Default:   Disabled
Enabling port mirroring causes all frames received and
transmitted by the source port(s) to be transmitted out of the
target port.

Source Port Synopsis:   Any combination of numbers valid for this parameter
The port(s) being monitored.

Source Direction Synopsis:   Egress and Ingress, Egress Only


Default:   Egress and Ingress
Specifies monitoring whether both egress and ingress traffics or
only egress traffic of the source port.

Target Port Synopsis:   1/1 to maximum port number


Default:   1/1
The port where a monitoring device should be connected.

3. Click Apply.

Section 3.7.12

Configuring Link Detection


To configure link detection, do the following:
1. Navigate to Ethernet Ports » Configure Link Detection . The Link Detection form appears.

88 Configuring Link Detection


RUGGEDCOM ROS Chapter 3
User Guide Device Management

3 4

Figure 34: Link Detection Form


1. Fast Link Detection Box    2. Link Detection Time Box    3. Apply Button    4. Reload Button

2. Configure the following parameter(s) as required:

NOTE
When Fast Link Detection is enabled, the system prevents link state change processing from
consuming all available CPU resources. However, if Port Guard is not used, it is possible for almost
all available CPU time to be consumed by frequent link state changes, which could have a negative
impact on overall system responsiveness.

Parameter Description

Fast Link Detection Synopsis:   { Off, On, On_withPortGuard }


Default:   On_withPortGuard
This parameter provides protection against faulty end devices
generating an improper link integrity signal. When a faulty end
device or a mis-matching fiber port is connected to the unit, a
large number of continuous link state changes could be reported
in a short period of time. These large number of bogus link state
changes could render the system unresponsive as most, if not
all, of the system resources are used to process the link state
changes. This could in turn cause a serious network problem as
the unit's RSTP process may not be able to run, thus allowing
network loop to form.
Three different settings are available for this parameter:
• ON_withPortGuard - This is the recommended setting. With this
setting, an extended period (~2 minutes) of excessive link state
changes reported by a port will prompt Port Guard feature to
disable FAST LINK DETECTION on that port and raise an alarm.
By disabling FAST LINK DETECTION on the problematic port,
excessive link state changes can no longer consume substantial
amount of system resources. However if FAST LINK DETECTION
is disabled, the port will need a longer time to detect a link
failure. This may result in a longer network recovery time of
up to 2s. Once Port Guard disables FAST LINK DETECTION of a
particular port, user can re-enable FAST LINK DETECTION on the
port by clearing the alarm.
• ON - In certain special cases where a prolonged excessive link
state changes constitute a legitimate link operation, using
this setting can prevent Port Guard from disabling FAST LINK
DETECTION on the port in question. If excessive link state
changes persist for more than 2 minutes, an alarm will be
generated to warn user about the observed bouncing link. If
the excessive link state changes condition is resolved later on,
the alarm will be cleared automatically. Since this option does
not disable FAST LINK DETECTION, a persistent bouncing link

Configuring Link Detection 89


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Parameter Description
could continue affect the system in terms of response time. This
setting should be used with caution.
• OFF - Turning this parameter OFF will disable FAST LINK
DETECTION completely. The switch will need a longer time to
detect a link failure. This will result in a longer network recovery
time of up to 2s.

Link Detection Time Synopsis:   100 ms to 1000 ms


Default:   100 ms
The time that the link has to continuously stay up before the "link
up" decision is made by the device.
(The device performs de-bouncing of Ethernet link detection
to avoid multiple responses to an occasional link bouncing
event, e.g. when a cable is shaking while being plugged-in or
unplugged).

3. Click Apply.

Section 3.7.13

Detecting Cable Faults


Connectivity issues can sometimes be attributed to faults in Ethernet cables. To help detect cable faults, short
circuits, open cables or cables that are too long, ROS includes a built-in cable diagnostics utility.

CONTENTS
• Section 3.7.13.1, “Viewing Cable Diagnostics Results”
• Section 3.7.13.2, “Performing Cable Diagnostics”
• Section 3.7.13.3, “Clearing Cable Diagnostics”
• Section 3.7.13.4, “Determining the Estimated Distance To Fault (DTF)”

Section 3.7.13.1
Viewing Cable Diagnostics Results
To view the results of previous diagnostic tests, navigate to Ethernet Ports » Configure/View Cable Diagnostics
Parameters . The Cable Diagnostics Parameters table appears.

NOTE
For information about how to start a diagnostic test, refer to Section 3.7.13.2, “Performing Cable
Diagnostics” .

90 Detecting Cable Faults


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Figure 35: Cable Diagnostics Parameters Table

This table displays the following information:

Parameter Description

Port Synopsis:   1/1 to maximum port number


The port number as seen on the front plate silkscreen of the switch.

State Synopsis:   { Stopped, Started }


Control the start/stop of the cable diagnostics on the selected port.
If a port does not support cable diagnostics, State will be reported as
N/A.

Runs Synopsis:   0 to 65535


The total number of times cable diagnostics to be performed on the
selected port. If this number is set to 0, cable diagnostics will be
performed forever on the selected port.

Calib. Synopsis:   -100.0 to 100.0 m


This calibration value can be used to adjust or calibrate the estimated
distance to fault. User can take following steps to calibrate the cable
diagnostics estimated distance to fault:
• Pick a particular port which calibration is needed
• Connect an Ethernet cable with a known length (e.g. 50m) to the
port
• DO NOT connect the other end of the cable to any link partner
• Run cable diagnostics a few times on the port. OPEN fault should
be detected
• Find the average distance to the OPEN fault recorded in the log
and compare it to the known length of the cable. The difference
can be used as the calibration value
• Enter the calibration value and run cable diagnostics a few more
times
• The distance to OPEN fault should now be at similar distance as
the cable length
• Distance to fault for the selected port is now calibrated

Good Synopsis:   0 to 65535


The number of times GOOD TERMINATION (no fault) is detected on
the cable pairs of the selected port.

Open Synopsis:   0 to 65535


The number of times OPEN is detected on the cable pairs of the
selected port.

Short Synopsis:   0 to 65535

Viewing Cable Diagnostics Results 91


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Parameter Description
The number of times SHORT is detected on the cable pairs of the
selected port.

Imped Synopsis:   0 to 65535


The number of times IMPEDANCE MISMATCH is detected on the
cable pairs of the selected port.

Pass /Fail /Total Synopsis:   Any 19 characters


This field summarizes the results of the cable diagnostics performed
so far.
Pass - number of times cable diagnostics successfully completed on
the selected port.
Fail - number of times cable diagnostics failed to complete on the
selected port.
Total - total number of times cable diagnostics have been attempted
on the selected port.

NOTE
For each successful diagnostic test, the values for Good, Open, Short or Imped will increment based
on the number of cable pairs connected to the port. For a 100Base-T port, which has two cable pairs,
the number will increase by two. For a 1000Base-T port, which has four cable pairs, the number will
increase by four.

NOTE
When a cable fault is detected, an estimated distance-to-fault is calculated and recorded in the system
log. The log lists the cable pair, the fault that was detected, and the distance-to-fault value. For more
information about the system log, refer to Section 3.6.1, “Viewing Local Logs” .

Section 3.7.13.2
Performing Cable Diagnostics
To perform a cable diagnostic test on one or more Ethernet ports, do the following:
1. Connect a CAT-5 (or better quality) Ethernet cable to the selected Ethernet port.

IMPORTANT!
Both the selected Ethernet port and its partner port can be configured to run in Enabled mode
with auto-negotiation, or in Disabled mode. Other modes are not recommended, as they may
interfere with the cable diagnostics procedure.

2. Connect the other end of the cable to a similar network port. For example, connect a 100Base-T port to a
100Base-T port, or a 1000Base-T port to a 1000Base-T port.
3. In ROS, navigate to Ethernet Ports » Configure/View Cable Diagnostics Parameters . The Cable
Diagnostics Parameters table appears.

92 Performing Cable Diagnostics


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Figure 36: Cable Diagnostics Parameters Table

4. Select an Ethernet port. The Cable Diagnostics Parameters form appears.

10 11

Figure 37: Cable Diagnostics Parameters Form


1. Port Box    2. State Options    3. Runs Box    4. Calib. Box    5. Good Box    6. Open Box    7. Short Box    8. Imped Box    9. Pass /
Fail /Total Box    10. Apply Button    11. Reload Button

5. Under Runs, enter the number of consecutive diagnostic tests to perform. A value of 0 indicates the test will
run continuously until stopped by the user.
6. Under Calib., enter the estimated Distance To Fault (DTF) value. For information about how to determine the
DTF value, refer to Section 3.7.13.4, “Determining the Estimated Distance To Fault (DTF)” .
7. Select Started.

IMPORTANT!
A diagnostic test can be stopped by selecting Stopped and clicking Apply. However, if the test is
stopped in the middle of a diagnostic run, the test will run to completion.

8. Click Apply. The state of the Ethernet port will automatically change to Stopped when the test is complete.
For information about how to monitor the test and view the results, refer to Section 3.7.13.1, “Viewing Cable
Diagnostics Results” .

Performing Cable Diagnostics 93


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Section 3.7.13.3
Clearing Cable Diagnostics
To clear the cable diagnostic results, do the following:
1. Navigate to Ethernet Ports » Clear Cable Diagnostics Statistics . The Clear Cable Diagnostics Statistics
form appears.

Figure 38: Clear Cable Diagnostics Statistics Form


1. Port Check Boxes    2. Apply Button

2. Select one or more Ethernet ports.


3. Click Apply.

Section 3.7.13.4
Determining the Estimated Distance To Fault (DTF)
To determine the estimate Distance To Fault (DTF), do the following:
1. Connect a CAT-5 (or better quality) Ethernet cable with a known length to the device. Do not connect the
other end of the cable to another port.
2. Configure the cable diagnostic utility to run a few times on the selected Ethernet port and start the test. For
more information, refer to Section 3.7.13.2, “Performing Cable Diagnostics” . Open faults should be detected
and recorded in the system log.
3. Review the errors recorded in the system log and determine the average distance of the open faults. For more
information about the system log, refer to Section 3.6.1, “Viewing Local Logs” .
4. Subtract the average distance from the cable length to determine the calibration value.
5. Configure the cable diagnostic utility to run a few times with the new calibration value. The distance to the
open fault should now be the same as the actual length of the cable. The Distance To Fault (DTF) is now
calibrated for the selected Ethernet port.

Section 3.7.14

Resetting Ethernet Ports


At times, it may be necessary to reset a specific Ethernet port, such as when the link partner has latched into an
inappropriate state. This is also useful for forcing a re-negotiation of the speed and duplex modes.
To reset a specific Ethernet port(s), do the following:
1. Navigate to Ethernet Ports » Reset Port(s) . The Reset Port(s) form appears.

94 Clearing Cable Diagnostics


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Figure 39: Reset Port(s) Form


1. Ports    2. Apply Button

2. Select one or more Ethernet ports to reset.


3. Click Apply. The selected Ethernet ports are reset.

Section 3.8

Managing IP Interfaces
Two types of IP interfaces can be configured in RUGGEDCOM ROS:
• Management IP interfaces
• Switch IP Interfaces
The management IP interface represents the management port on the device. Only one management IP interface
can be configured.
Switch IP interfaces represent the VLAN interfaces where each interface must be assigned an IP address with
a unique subnet. Only one VLAN interface can be marked as the management interface which can be used by
management applications, such as WebServer, SSH, etc.

CONTENTS
• Section 3.8.1, “Configuring the Management IP Interface”
• Section 3.8.2, “Managing Switch IP Interfaces”

Section 3.8.1

Configuring the Management IP Interface


To configure the management IP interface, do the following:
1. Navigate to Administration » Configure IP Interfaces » Configure Mgmt IP Interfaces . The Mgmt IP
Interfaces form appears.

Managing IP Interfaces 95
Chapter 3 RUGGEDCOM ROS
Device Management User Guide

4 6

Figure 40: Mgmt IP Interface Form


1. IP Address Type Box    2. IP Address Box    3. Subnet Box    4. Apply Button    5. Delete Button    6. Reload Button

2. Configure the following parameter(s) as required:

NOTE
The IP address and mask configured for the management VLAN are not changed when resetting all
configuration parameters to defaults and will be assigned a default VLAN ID of 1. Changes to the
IP address take effect immediately. All IP connections in place at the time of an IP address change
will be lost.

Parameter Description

IP Address Type Synopsis:   { Static, Dynamic, DHCP, BOOTP }


Default:   Static
Specifies whether the IP address is static or dynamically assigned
via DHCP or BOOTP. Option DYNAMIC is a common case of
dynamically assigned IP address. It switches between BOOTP and
DHCP until it gets the response from the relevant server.Must be
static for non management interfaces

IP Address Synopsis:   ###.###.###.### where ### ranges from 0 to 255


Default:   10.0.0.1
Specifies the IP address of this device. An IP address is a 32-bit
number that is notated by using four numbers from 0 through
255, separated by periods. Only a unicast IP address is allowed,
which ranges from 1.0.0.0 to 233.255.255.255.

Subnet Synopsis:   ###.###.###.### where ### ranges from 0 to 255


Default:   255.0.0.0
Specifies the IP subnet mask of this device. An IP subnet mask
is a 32-bit number that is notated by using four numbers from
0 through 255, separated by periods. Typically, subnet mask
numbers use either 0 or 255 as values (e.g. 255.255.255.0) but
other numbers can appear.

IMPORTANT!
Each IP interface must have a unique network
address.

3. Click Apply.

96 Configuring the Management IP Interface


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Section 3.8.2

Managing Switch IP Interfaces


CAUTION!
Configuration hazard – risk of communication disruption. Changing the ID for the management VLAN
will break any active Raw Socket TCP connections. If this occurs, reset all serial ports.

The following section describes how to set up and manage switch IP interfaces.

CONTENTS
• Section 3.8.2.1, “Viewing a List of Switch IP Interfaces”
• Section 3.8.2.2, “Adding a Switch IP Interface”
• Section 3.8.2.3, “Deleting a Switch IP Interface”

Section 3.8.2.1
Viewing a List of Switch IP Interfaces
To view a list of switch IP interfaces configured on the device, navigate to Administration » Configure IP
Interfaces » Configure Switch IP Interfaces . The Switch IP Interfaces table appears.

Figure 41:  Switch IP Interfaces Table

If switch IP interfaces have not been configured, add IP interfaces as needed. For more information, refer to
Section 3.8.2.2, “Adding a Switch IP Interface” .

Section 3.8.2.2
Adding a Switch IP Interface
To add a switch IP interface, do the following:
1. Navigate to Administration » Configure IP Interfaces » Configure Switch IP Interfaces . The Switch IP
Interfaces table appears.

Managing Switch IP Interfaces 97


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Figure 42:  Switch IP Interfaces Table


1. InsertRecord

2. Click InsertRecord. The Switch IP Interfaces form appears.

7 9

Figure 43:  Switch IP Interfaces Form


1. IP Address Type Box    2. IP Address Box    3. Subnet Box    4. Apply Button    5. Delete Button    6. Reload Button

3. Configure the following parameter(s) as required:

NOTE
The IP address and mask configured for the management VLAN are not changed when resetting all
configuration parameters to defaults and will be assigned a default VLAN ID of 1. Changes to the
IP address take effect immediately. All IP connections in place at the time of an IP address change
will be lost.

Parameter Description

Type Synopsis:   { VLAN }


Default:   VLAN
Specifies the type of the interface for which this IP interface is
created.

ID Synopsis:   1 to 4094
Default:   1

98 Adding a Switch IP Interface


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Parameter Description
Specifies the ID of the interface for which this IP interface is
created. If the interface type is VLAN, this represents the VLAN ID.

IP Address Type Synopsis:   { Static, Dynamic, DHCP, BOOTP }


Default:   Static
Specifies whether the IP address is static or dynamically assigned
via DHCP or BOOTP. Option DYNAMIC is a common case of
dynamically assigned IP address. It switches between BOOTP and
DHCP until it gets the response from the relevant server.Must be
static for non management interfaces

Mgmt Synopsis:   { No, Yes }


Default:   No
Specifies whether the IP interface is the device management
interface.

IP Address Synopsis:   ###.###.###.### where ### ranges from 0 to 255


Default:   192.168.0.1
Specifies the IP address of this device. An IP address is a 32-bit
number that is notated by using four numbers from 0 through
255, separated by periods. Only a unicast IP address is allowed,
which ranges from 1.0.0.0 to 233.255.255.255.

Subnet Synopsis:   ###.###.###.### where ### ranges from 0 to 255


Default:   255.255.255.0
Specifies the IP subnet mask of this device. An IP subnet mask
is a 32-bit number that is notated by using four numbers from
0 through 255, separated by periods. Typically, subnet mask
numbers use either 0 or 255 as values (e.g. 255.255.255.0) but
other numbers can appear.

IMPORTANT!
Each IP interface must have a unique network
address.

4. Click Apply.

Section 3.8.2.3
Deleting a Switch IP Interface
To delete a switch IP interface configured on the device, do the following:
1. Navigate to Administration » Configure IP Interfaces » Configure Switch IP Interfaces . The Switch IP
Interfaces table appears.

Deleting a Switch IP Interface 99


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Figure 44:  Switch IP Interfaces Table

2. Select the IP interface from the table. The Switch IP Interfaces form appears.

7 9

Figure 45:  Switch IP Interfaces Form


1. IP Address Type Box    2. IP Address Box    3. Subnet Box    4. Apply Button    5. Delete Button    6. Reload Button

3. Click Delete.

Section 3.9

Managing IP Gateways
RUGGEDCOM ROS allows up to ten IP gateways to be configured. When both the Destination and Subnet
parameters are blank, the gateway is considered to be a default gateway.

IMPORTANT!
The default gateway will not be changed if the selected factory default configuration is reloaded.

CONTENTS
• Section 3.9.1, “Viewing a List of IP Gateways”

100 Managing IP Gateways


RUGGEDCOM ROS Chapter 3
User Guide Device Management

• Section 3.9.2, “Adding an IP Gateway”


• Section 3.9.3, “Deleting an IP Gateway”

Section 3.9.1

Viewing a List of IP Gateways


To view a list of IP gateways configured on the device, navigate to Administration » Configure IP Gateways .
The IP Gateways table appears.

Figure 46: IP Gateways Table

If IP gateways have not been configured, add IP gateways as needed. For more information, refer to
Section 3.9.2, “Adding an IP Gateway” .

Section 3.9.2

Adding an IP Gateway
To add an IP gateway, do the following:
1. Navigate to Administration » Configure IP Gateways . The IP Gateways table appears.

Figure 47: IP Gateways Table


1. InsertRecord

2. Click InsertRecord. The IP Gateways form appears.

Viewing a List of IP Gateways 101


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

4 6

Figure 48: IP Gateways
1. Destination Box    2. Subnet Box    3. Gateway Box    4. Apply Button    5. Delete Button    6. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Destination Synopsis:   ###.###.###.### where ### ranges from 0 to 255


Specifies the IP address of destination network or host. For default
gateway, both the destination and subnet are 0.

Subnet Synopsis:   ###.###.###.### where ### ranges from 0 to 255


Specifies the destination IP subnet mask. For default gateway,
both the destination and subnet are 0.

Gateway Synopsis:   ###.###.###.### where ### ranges from 0 to 255


Specifies the gateway to be used to reach the destination.

4. Click Apply.

Section 3.9.3

Deleting an IP Gateway
To delete an IP gateway configured on the device, do the following:
1. Navigate to Administration » Configure IP Gateways . The IP Gateways table appears.

Figure 49: IP Gateways Table

102 Deleting an IP Gateway


RUGGEDCOM ROS Chapter 3
User Guide Device Management

2. Select the IP gateway from the table. The IP Gateways form appears.

4 6

Figure 50: IP Gateways Form


1. Destination Box    2. Subnet Box    3. Gateway Box    4. Apply Button    5. Delete Button    6. Reload Button

3. Click Delete.

Section 3.10

Configuring IP Services
To configure the IP services provided by the device, do the following:
1. Navigate to Administration » Configure IP Services . The IP Services form appears.

Configuring IP Services 103


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

10

11

12 13

Figure 51: IP Services Form


1. Inactivity Timeout Box    2. Telnet Sessions Allowed Box    3. Web Server Users Allowed Box    4. TFTP Server Box    5. Modbus
Address Box    6. SSH Sessions Allowed Box    7. RSH Server Options    8. IP Forward Options    9. Max Failed Attempts Box   
10. Failed Attempts Window Box    11. Lockout Time Box    12. Apply Button    13. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

Inactivity Timeout Synopsis:   1 to 60 or { Disabled }


Default:   5 min
Specifies when the console will timeout and display the login
screen if there is no user activity. A value of zero disables
timeouts. For Web Server users maximum timeout value is limited
to 30 minutes.

Telnet Sessions Allowed Synopsis:   1 to 4 or { Disabled }


Default:   Disabled
Limits the number of Telnet sessions. A value of zero prevents any
Telnet access.

Web Server Users Allowed Synopsis:   1 to 4 or { Disabled }


Default:   4
Limits the number of simultaneous web server users.

TFTP Server Synopsis:   { Disabled, Get Only, Enabled }


Default:   Disabled
As TFTP is a very insecure protocol, this parameter allows user to
limit or disable TFTP Server access..
DISABLED - disables read and write access to TFTP Server
GET ONLY - only allows reading of files via TFTP Server
ENABLED - allows reading and writing of files via TFTP Server

ModBus Address Synopsis:   1 to 255 or { Disabled }


Default:   Disabled

104 Configuring IP Services


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Parameter Description
Determines the Modbus address to be used for Management
through Modbus.

SSH Sessions Allowed (Controlled Version Only) Synopsis:   1 to 4


Default:   4
Limits the number of SSH sessions.

RSH Server Synopsis:   { Disabled, Enabled }


Default:   Disabled (controlled version) or Enabled (non-
controlled version)
Disables/enables Remote Shell access.

IP Forward Synopsis:   { Disabled, Enabled }


Controls the ability of IP Forwarding between VLANs in Serial
Server or IP segments.

Max Failed Attempts Synopsis:   1 to 20


Default:   10
Maximum number of consecutive failed access attempts on
service within Failed Attempts Window before blocking the
service.

Failed Attempts Window Synopsis:   1 to 30 min


Default:   5 min
The time in minutes (min) in which the maximum number
of failed login attempts must be exceeded before a service is
blocked. The counter of failed attempts resets to 0 when the timer
expires.

Lockout Time Synopsis:   1 to 120 min


Default:   60 min
The time in minutes (min) the service remains locked out after the
maximum number of failed access attempts has been reached.

3. Click Apply.

Section 3.11

Managing Remote Monitoring


Remote Monitoring (RMON) is used to collect and view historical statistics related to the performance and
operation of Ethernet ports. It can also record a log entry and/or generate an SNMP trap when the rate of
occurrence of a specified event is exceeded.

CONTENTS
• Section 3.11.1, “Managing RMON History Controls”
• Section 3.11.2, “Managing RMON Alarms”

Managing Remote Monitoring 105


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

• Section 3.11.3, “Managing RMON Events”

Section 3.11.1

Managing RMON History Controls


The history controls for Remote Monitoring take samples of the RMON-MIB history statistics of an Ethernet port at
regular intervals.

CONTENTS
• Section 3.11.1.1, “Viewing a List of RMON History Controls”
• Section 3.11.1.2, “Adding an RMON History Control”
• Section 3.11.1.3, “Deleting an RMON History Control”

Section 3.11.1.1
Viewing a List of RMON History Controls
To view a list of RMON history controls, navigate to Ethernet Stats » Configure RMON History Controls . The
RMON History Controls table appears.

Figure 52: RMON History Controls Table

If history controls have not been configured, add controls as needed. For more information, refer to
Section 3.11.1.2, “Adding an RMON History Control” .

Section 3.11.1.2
Adding an RMON History Control
To add an RMON history control, do the following:
1. Navigate to Ethernet Stats » Configure RMON History Controls . The RMON History Controls table
appears.

106 Managing RMON History Controls


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Figure 53: RMON History Controls Table


1. InsertRecord

2. Click InsertRecord. The RMON History Controls form appears.

7 6

Figure 54: RMON History Controls Form


1. Index Box    2. Port Box    3. Requested Buckets Box    4. Granted Buckets Box    5. Interval Box    6. Owner Box    7. Apply Button   
8. Delete Button    9. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Index Synopsis:   1 to 65535


Default:   1
The index of this RMON History Contol record.

Port Synopsis:   1/1 to maximum port number


Default:   1/1
The port number as seen on the front plate silkscreen of the
switch.

Requested Buckets Synopsis:   1 to 4000


Default:   50
The maximum number of buckets requested for this RMON
collection history group of statistics. The range is 1 to 4000. The
default is 50.

Granted Buckets Synopsis:   0 to 65535

Adding an RMON History Control 107


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Parameter Description
The number of buckets granted for this RMON collection history.
This field is not editable.

Interval Synopsis:   1 to 3600


Default:   1800
The number of seconds in over which the data is sampled for each
bucket. The range is 1 to 3600. The default is 1800.

Owner Synopsis:   Any 127 characters


Default:   Monitor
The owner of this record. It is suggested to start this string
withword 'monitor'.

4. Click Apply.

Section 3.11.1.3
Deleting an RMON History Control
To delete an RMON history control, do the following:
1. Navigate to Ethernet Stats » Configure RMON History Controls . The RMON History Controls table
appears.

Figure 55: RMON History Controls Table

2. Select the history control from the table. The RMON History Controls form appears.

108 Deleting an RMON History Control


RUGGEDCOM ROS Chapter 3
User Guide Device Management

7 6

Figure 56: RMON History Controls Form


1. Index Box    2. Port Box    3. Requested Buckets Box    4. Granted Buckets Box    5. Interval Box    6. Owner Box    7. Apply Button   
8. Delete Button    9. Reload Button

3. Click Delete.

Section 3.11.2

Managing RMON Alarms


When Remote Monitoring (RMON) alarms are configured, RUGGEDCOM ROS examines the state of a specific
statistical variable.
Remote Monitoring (RMON) alarms define upper and lower thresholds for legal values of specific statistical
variables in a given interval. This allows RUGGEDCOM ROS to detect events as they occur more quickly than a
specified maximum rate or less quckly than a minimum rate.
When the rate of change for a statistics value exceeds its limits, an internal INFO alarm is always generated. For
information about viewing alarms, refer to Section 4.6.2, “Viewing and Clearing Latched Alarms” .
Additionally, a statistic threshold crossing can result in further activity. An RMON alarm can be configured to point
to a particular RMON event, which can generate an SNMP trap, an entry in the event log, or both. The RMON event
can also direct alarms towards different users defined for SNMP.
The alarm can point to a different event for each of the thresholds. Therefore, combinations such as trap on rising
threshold or trap on rising threshold, log and trap on falling threshold are possible.
Each RMON alarm may be configured such that its first instance occurs only for rising, falling, or all thresholds that
exceed their limits.
The ability to configure upper and lower thresholds on the value of a measured statistic provides for the ability to
add hysteresis to the alarm generation process.
If the value of the measured statistic over time is compared to a single threshold, alarms will be generated each
time the statistic crosses the threshold. If the statistic’s value fluctuates around the threshold, an alarm can be
generated every measurement period. Programming different upper and lower thresholds eliminates spurious
alarms. The statistic value must travel between the thresholds before alarms can be generated. The following
illustrates the very different patterns of alarm generation resulting from a statistic sample and the same sample
with hysteresis applied.

Managing RMON Alarms 109


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Figure 57: The Alarm Process

There are two methods to evaluate a statistic in order to determine when to generate an event: delta and
absolute.
For most statistics, such as line errors, it is appropriate to generate an alarm when a rate is exceeded. The
alarm defaults to the delta measurement method, which examines changes in a statistic at the end of each
measurement period.
It may be desirable to alarm when the total, or absolute, number of events crosses a threshold. In this case, set the
measurement period type to absolute.

CONTENTS
• Section 3.11.2.1, “Viewing a List of RMON Alarms”
• Section 3.11.2.2, “Adding an RMON Alarm”
• Section 3.11.2.3, “Deleting an RMON Alarm”

Section 3.11.2.1
Viewing a List of RMON Alarms
To view a list of RMON alarms, navigate to Ethernet Stats » Configure RMON Alarms . The RMON Alarms table
appears.

Figure 58: RMON Alarms Table

If alarms have not been configured, add alarms as needed. For more information, refer to Section 3.11.2.2,
“Adding an RMON Alarm” .

110 Viewing a List of RMON Alarms


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Section 3.11.2.2
Adding an RMON Alarm
To add an RMON alarm, do the following:
1. Navigate to Ethernet Stats » Configure RMON Alarms . The RMON Alarms table appears.

Figure 59: RMON Alarms Table


1. InsertRecord

2. Click InsertRecord. The RMON Alarms form appears.

10

11

12 14

13

Figure 60: RMON Alarms Form


1. Index Box    2. Variable Box    3. Rising Thr Box    4. Falling Thr Box    5. Value Box    6. Type Options    7. Interval Box    8. Startup
Alarm List    9. Rising Event Box    10. Falling Event Box    11. Owner Box    12. Apply Button    13. Delete Button    14. Reload Button

3. Configure the following parameter(s) as required:

Adding an RMON Alarm 111


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Parameter Description

Index Synopsis:   1 to 65535


Default:   1
The index of this RMON Alarm record.

Variable Synopsis:   SNMP Object Identifier - up to 39 characters


The SNMP object identifier (OID) of the particular variable to
be sampled. Only variables that resolve to an ASN.1 primitive
type INTEGER (INTEGER, Integer32,Counter32, Counter64,
Gauge, or TimeTicks) may be sampled. A list of objects can
be printed using shell command 'rmon'. The OID format:
objectName.index1.index2... where index format depends on
index object type.

Rising Thr Synopsis:   -2147483647 to 2147483647


Default:   0
A threshold for the sampled variable. When the current sampled
variable value is greater than or equal to this threshold, and the
value at the last sampling interval was less than this threshold,
a single event will be generated. A single event will also be
generated if the first sample after this record is created is greater
than or equal to this threshold and the associated startup alarm
ils equal to 'rising'.After rising alarm is generated, another such
event will not be generated until the sampled value falls below
this threshold and reaches the value of FallingThreshold.

Falling Thr Synopsis:   -2147483647 to 2147483647


Default:   0
A threshold for the sampled variable. When the current sampled
variable value is less than or equal to this threshold, and the value
at the last sampling interval was greater than this threshold,
a single event will be generated. A single event will also be
generated if the first sample after this record is created is less
than or equal to this threshold and the associated startup alarm
ils equal to 'falling'.After falling alarm is generated, another such
event will not be generated until the sampled value rises above
this threshold and reaches the value of RisingThreshold.

Value Synopsis:   -2147483647 to 2147483647


The value of monitoring object during the last sampling period.
The presentation of value depends of sample type ('absolute' or
'delta').

Type Synopsis:   { absolute, delta }


Default:   delta
The method of sampling the selected variable and calculating the
value to be compared against the thresholds. The value of sample
type can be 'absolute' or 'delta'.

Interval Synopsis:   0 to 2147483647


Default:   60
The number of seconds in over which the data is sampled and
compared with the rising and falling thresholds.

Startup Alarm Synopsis:   { rising, falling, risingOrFalling }


Default:   risingOrFalling
The alarm that may be sent when this record is first created if
condition for raising alarm is met. The value of startup alarm can
be 'rising', 'falling' or 'risingOrFalling'.

Rising Event Synopsis:   0 to 65535


Default:   0

112 Adding an RMON Alarm


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Parameter Description
The index of the event that is used when a falling threshold is
crossed. If there is no corresponding entryl in the Event Table,
then no association exists. In particular, if this value is zero, no
associated event will be generated.

Falling Event Synopsis:   0 to 65535


Default:   0
The index of the event that is used when a rising threshold is
crossed. If there is no corresponding entryl in the Event Table,
then no association exists. In particular, if this value is zero, no
associated event will be generated.

Owner Synopsis:   Any 127 characters


Default:   Monitor
The owner of this record. It is suggested to start this string
withword 'monitor'.

4. Click Apply.

Section 3.11.2.3
Deleting an RMON Alarm
To delete an RMON alarm, do the following:
1. Navigate to Ethernet Stats » Configure RMON Alarms . The RMON Alarms table appears.

Figure 61: RMON Alarms Table

2. Select the alarm from the table. The RMON Alarms form appears.

Deleting an RMON Alarm 113


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

10

11

12 14

13

Figure 62: RMON Alarms Form


1. Index Box    2. Variable Box    3. Rising Thr Box    4. Falling Thr Box    5. Value Box    6. Type Options    7. Interval Box    8. Startup
Alarm List    9. Rising Event Box    10. Falling Event Box    11. Owner Box    12. Apply Button    13. Delete Button    14. Reload Button

3. Click Delete.

Section 3.11.3

Managing RMON Events


Remote Monitoring (RMON) events define behavior profiles used in event logging. These profiles are used by
RMON alarms to send traps and log events.
Each alarm may specify that a log entry be created on its behalf whenever the event occurs. Each entry may also
specify that a notification should occur by way of SNMP trap messages. In this case, the user for the trap message
is specified as the Community.
Two traps are defined: risingAlarm and fallingAlarm.

CONTENTS
• Section 3.11.3.1, “Viewing a List of RMON Events”
• Section 3.11.3.2, “Adding an RMON Event”

114 Managing RMON Events


RUGGEDCOM ROS Chapter 3
User Guide Device Management

• Section 3.11.3.3, “Deleting an RMON Event”

Section 3.11.3.1
Viewing a List of RMON Events
To view a list of RMON events, navigate to Ethernet Stats » Configure RMON Events . The RMON Events table
appears.

Figure 63: RMON Events Table

If events have not been configured, add events as needed. For more information, refer to Section 3.11.3.2,
“Adding an RMON Event” .

Section 3.11.3.2
Adding an RMON Event
To add an RMON alarm, do the following:
1. Navigate to Ethernet Stats » Configure RMON Events . The RMON Events table appears.

Figure 64: RMON Events Table


1. InsertRecord

2. Click InsertRecord. The RMON Events form appears.

Viewing a List of RMON Events 115


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

7 9

Figure 65: RMON Events Form


1. Index Box    2. Type List    3. Community Box    4. Last Time Sent Box    5. Description Box    6. Owner Box    7. Apply Button   
8. Delete Button    9. View Button    10. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Index Synopsis:   1 to 65535


Default:   3
The index of this RMON Event record.

Type Synopsis:   { none, log, snmpTrap, logAndTrap }


Default:   logAndTrap
The type of notification that the probe will make about this event.
In the case of 'log', an entry is made in the RMON Log table for
each event. In the case of snmp_trap, an SNMP trap is sent to one
or more management stations.

Community Synopsis:   Any 31 characters


Default:   public
If the SNMP trap is to be sent, it will be sent to the SNMP
community specified by this string.

Last Time Sent Synopsis:   DDDD days, HH:MM:SS


The time from last reboot at the time this event entry last
generated an event. If this entry has not generated any events,
this value will be 0.

Description Synopsis:   Any 127 characters


Default:   EV2-Rise
A comment describing this event.

Owner Synopsis:   Any 127 characters


Default:   Monitor
The owner of this event record. It is suggested to start this string
withword 'monitor'.

4. Click Apply.

116 Adding an RMON Event


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Section 3.11.3.3
Deleting an RMON Event
To delete an RMON event, do the following:
1. Navigate to Ethernet Stats » Configure RMON Events . The RMON Events table appears.

Figure 66: RMON Events Table

2. Select the event from the table. The RMON Events form appears.

7 9

Figure 67: RMON Events Form


1. Index Box    2. Type List    3. Community Box    4. Last Time Sent Box    5. Description Box    6. Owner Box    7. Apply Button   
8. Delete Button    9. View Button    10. Reload Button

3. Click Delete.

Section 3.12

Upgrading/Downgrading Firmware
The following section describes how to upgrade and downgrade the firmware.

CONTENTS
• Section 3.12.1, “Upgrading Firmware”

Deleting an RMON Event 117


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

• Section 3.12.2, “Downgrading Firmware”

Section 3.12.1

Upgrading Firmware
Upgrading RUGGEDCOM ROS firmware, including the main, bootloader and FPGA firmware, may be necessary
to take advantage of new features or bug fixes. Binary firmware images are available from Siemens. Visit
www.siemens.com/ruggedcom to determine which versions/updates are available or contact Siemens Customer
Support.
Binary firmware images transferred to the device are stored in non-volatile Flash memory and require a device
reset in order to take effect.

IMPORTANT!
Non-Controlled (NC) versions of RUGGEDCOM ROS can not be upgraded to Controlled firmware
versions. However, Controlled firmware versions can be upgraded to an NC firmware version.

IMPORTANT!
If a microSD/microSDHC card is installed during the upgrade, the new firmware will be stored to both
the internal Flash and the microSD/microSDHC card.

NOTE
In the event the upgrade process is interrupted, possibly due to a power disruption, RUGGEDCOM ROS
is able to recover if a microSD/microSDHC card with a valid firmware image (main.bin) is installed
before the next reboot. RUGGEDCOM ROS will copy the firmware image to the internal memory and
boot up from it.

NOTE
The IP address set for the device will not be changed following a firmware upgrade.

To upgrade the RUGGEDCOM ROS firmware, do the following:


1. Upload a different version of the binary firmware image to the device or insert a microSD/microSDHC card
that contains the image. For more information about uploading files, refer to Section 3.5, “Uploading/
Downloading Files” .
2. Reset the device to complete the installation. For more information, refer to Section 3.13, “Resetting the
Device” .
3. Access the CLI shell and verify the new software version has been installed by typing version. The currently
installed versions of the main and boot firmware are displayed.

version
Current ROS-MPC83 Main Software v4.1.0.QA16 (May 06 2014 10:10)

Section 3.12.2

Downgrading Firmware
Downgrading the RUGGEDCOM ROS firmware is generally not recommended, as it may have unpredictable
effects. However, if a downgrade is required, do the following:

118 Upgrading Firmware


RUGGEDCOM ROS Chapter 3
User Guide Device Management

IMPORTANT!
Before downgrading the firmware, make sure the hardware and FPGA code types installed in the
device are supported by the older firmware version. Refer to the Release Notes for the older firmware
version to confirm.

IMPORTANT!
Non-Controlled (NC) versions of RUGGEDCOM ROS can not be downgraded to Controlled firmware
versions. However, Controlled firmware versions can be downgraded to an NC firmware version.

CAUTION!
Do not downgrade the RUGGEDCOM ROS boot version.

1. Disconnect the device from the network.


2. Log in to the device as an admin user. For more information, refer to Section 2.2, “Logging In” .
3. Make a local copy of the current configuration file. For more information, refer to Section 3.5, “Uploading/
Downloading Files” .

IMPORTANT!
Never downgrade the RUGGEDCOM ROS software version beyond RUGGEDCOM ROS v4.3
when encryption is enabled. Make sure the device has been restored to factory defaults before
downgrading.

4. Restore the device to its factory defaults. For more information, refer to Section 3.4, “Restoring Factory
Defaults” .
5. Upload and apply the older firmware version and its associated FPGA files using the same methods used to
install newer firmware versions. For more information , refer to Section 3.12.1, “Upgrading Firmware” .
6. Press Ctrl-S to access the CLI.
7. Clear all logs by typing:
clearlogs

8. Clear all alarms by typing:


clearalarms

IMPORTANT!
After downgrading the firmware and FPGA files, be aware that some settings from the previous
configuration may be lost or reverted back to the factory defaults (including user passwords if
downgrading from a security related version), as those particular tables or fields may not exist in
the older firmware version. Because of this, the unit must be configured after the downgrade.

9. Configure the device as required.

Section 3.13

Resetting the Device


To reset the device, do the following:
1. Navigate to Diagnostics » Reset Device . The Reset Device form appears.

Resetting the Device 119


Chapter 3 RUGGEDCOM ROS
Device Management User Guide

Figure 68: Reset Device Form


1. Confirm Button

2. Click Confirm.

Section 3.14

Decommissioning the Device


Before taking the device out of service, either permanently or for maintenance by a third-party, make sure the
device has been fully decommissioned. This includes removing any sensitive, proprietary information.
To decommission the device, do the following:
1. Disconnect all network cables from the device.
2. Connect to the device via the RS-232 serial console port. For more information, refer to Section 2.1.1,
“Connecting Directly” .
3. Restore all factory default settings for the device. For more information, refer to Section 3.4, “Restoring
Factory Defaults” .
4. Access the CLI. For more information, refer to Section 2.6, “Using the Command Line Interface” .
5. Upload a blank version of the banner.txt file to the device to replace the existing file. For more information
about uploading a file, refer to Section 3.5, “Uploading/Downloading Files” .
6. Confirm the upload was successful by typing:
type banner.txt

7. Clear the system and crash logs by typing:


clearlog

8. Generate a random SSL certificate by typing:


sslkeygen

This may take several minutes to complete. To verify the certificate has been generated, type:
type syslog.txt

When the phrase


Generated ssl.crt was saved
appears in the log, the SSL certificate has been generated.
9. Generate random SSH keys by typing:
sshkeygen

This may take several minutes to complete. To verify the keys have been generated, type:

120 Decommissioning the Device


RUGGEDCOM ROS Chapter 3
User Guide Device Management

type syslog.txt

When the phrase


Generated ssh.keys was saved
appears in the log, the SSH keys have been generated.
10. De-fragment and erase all free flash memory by typing:
flashfile defrag

This may take several minutes to complete.

Decommissioning the Device 121


RUGGEDCOM ROS Chapter 3
User Guide Device Management

Decommissioning the Device 122


RUGGEDCOM ROS Chapter 4
User Guide System Administration

System Administration
This chapter describes how to perform various administrative tasks related to device identification, user
permissions, alarm configuration, certificates and keys, and more.

CONTENTS
• Section 4.1, “Configuring the System Information”
• Section 4.2, “Customizing the Login Screen”
• Section 4.3, “Configuring Passwords”
• Section 4.4, “Clearing Private Data”
• Section 4.5, “Enabling/Disabling the Web Interface”
• Section 4.6, “Managing Alarms”
• Section 4.7, “Managing the Configuration File”
• Section 4.8, “Managing an Authentication Server”

Section 4.1

Configuring the System Information


To configure basic information that can be used to identify the device, its location, and/or its owner, do the
following:
1. Navigate to Administration » Configure System Identification . The System Identification form appears.

4 5

Figure 69: System Identification Form


1. System Name Box    2. Location Box    3. Contact Box    4. Apply Button    5. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

System Name Synopsis:   Any 24 characters

Configuring the System Information 123


Chapter 4 RUGGEDCOM ROS
System Administration User Guide

Parameter Description
The system name is displayed in all RUGGEDCOM ROS menu
screens. This can make it easier to identify the switches within
your network provided that all switches are given a unique name.

Location Synopsis:   Any 49 characters


The location can be used to indicate the physical location of the
switch. It is displayed in the login screen as another means to
ensure you are dealing with the desired switch.

Contact Synopsis:   Any 49 characters


The contact can be used to help identify the person responsible
for managing the switch. You can enter name, phone number,
email, etc. It is displayed in the login screen so that this person
may be contacted should help be required.

3. Click Apply.

Section 4.2

Customizing the Login Screen


To display a custom welcome message, device information or any other information on the login screen for the
Web and console interfaces, add text to the banner.txt file stored on the device.
If the banner.txt file is empty, only the Username and Password fields appear on the login screen.
To update the banner.txt file, download the file from the device, modify it and then load it back on to the
device. For information about uploading and downloading files, refer to Section 3.5, “Uploading/Downloading
Files” .

Section 4.3

Configuring Passwords
RUGGEDCOM ROS allows for up to three user profiles to be configured locally on the device. Each profile
corresponds to one of the following access levels:
• Guest
• Operator
• Admin
The access levels provide or restrict the user's ability to change settings and execute various commands.
User Type
Rights
Guest Operator Admin

View Settings ü ü ü

Clear Logs û ü ü

Reset Alarms û ü ü

Clear Statistics û ü ü

124 Customizing the Login Screen


RUGGEDCOM ROS Chapter 4
User Guide System Administration

User Type
Rights
Guest Operator Admin

Change Basic Settings û ü ü

Change Advanced Settings û û ü

Run Commands û û ü

Default passwords are configured for each user type initially. It is strongly recommended that these be changed
before the device is commissioned.

NOTE
Users can also be verified through a RADIUS or TACACS+ server. When enabled for authentication and
authorization, the RADIUS or TACACS+ server will be used in the absence of any local settings. For
more information about configuring a RADIUS or TACACS+ server, refer to Section 4.8, “Managing an
Authentication Server” .

CAUTION!
To prevent unauthorized access to the device, make sure to change the default passwords for each
profile before commissioning the device.

To configure passwords for one or more of the user profiles, do the following:
1. Navigate to Administration » Configure Passwords . The Configure Passwords form appears.

10

11

12 13

Figure 70: Configure Passwords Form


1. Auth Type Box    2. Guest Username Box    3. Guest Password Box    4. Confirm Guest Password Box    5. Operator Username Box   
6. Operator Password Box    7. Confirm Operator Password Box    8. Admin Username Box    9. Admin Password Box    10. Confirm
Admin Password Box    11. Password Minimum Length box    12. Apply Button    13. Reload Button

Configuring Passwords 125


Chapter 4 RUGGEDCOM ROS
System Administration User Guide

NOTE
RUGGEDCOM ROS requires that all user passwords meet strict guidelines to prevent the use of
weak passwords. When creating a new password, make sure it adheres to the following rules:
• Must not be less than 8 characters in length.
• Must not include the username or any 4 continous characters found in the username.
For example, if the username is Subnet25, the password may not be subnet25admin,
subnetadmin or net25admin. However, net-25admin or Sub25admin is permitted.
• Must have at least one alphabetic character and one number. Special characters are permitted.
• Must not have more than 3 continuously incrementing or decrementing numbers. For example,
Sub123 and Sub19826 are permitted, but Sub12345 is not.
An alarm will generate if a weak password is configured. The weak password alarm can be
disabled by the user. For more information about disabling alarms, refer to Section 4.6,
“Managing Alarms” .

2. Configure the following parameter(s) as required:

Parameter Description

Auth Type Synopsis:   { Local, RADIUS, TACACS+, RADIUSorLocal, TACACS


+orLocal }
Default:   Local
Password can be authenticated using localy configured values,
or remote RADIUS or TACACS+ server. Setting value to any of
combinations that involve RADIUS or TACACS+ require Security
Server Table to be configured.
Settings:
• Local - Authentication from the local Password Table.
• RADIUS - Authentication using a RADIUS server.
• TACACS+ - Authentication using a TACACS+ server.
• RADIUSOrLocal - Authentication using RADIUS. If the server
cannot be reached, authenticate from the local Password Table.
• TACACS+OrLocal - Authentication using TACACS+. If the server
cannot be reached, authenticate from the local Password Table

NOTE
For console access, local credentials will always be
checked first regardless of the device configuration.
If server authentication is required, requests to the
server will be sent only if local authentication fails.

Guest Username Synopsis:   Any 15 characters


Default:   guest
Related password is in field Guest Password; view only, cannot
change settings or run any commands.

Guest Password Synopsis:   19 character ASCII string


Related username is in field Guest Username; view only, cannot
change settings or run any commands.

Confirm Guest Password Synopsis:   19 character ASCII string


Related username is in field Guest Username; view only, cannot
change settings or run any commands.

Operator Username Synopsis:   Any 15 characters


Default:   operator

126 Configuring Passwords


RUGGEDCOM ROS Chapter 4
User Guide System Administration

Parameter Description
Related password is in field Oper Password; cannot change
settings; can reset alarms, statistics, logs, etc.

Operator Password Synopsis:   19 character ASCII string


Related username is in field Oper Username; cannot change
settings; can reset alarms, statistics, logs, etc

Confirm Operator Password Synopsis:   19 character ASCII string


Related username is in field Oper Username; cannot change
settings; can reset alarms, statistics, logs, etc.

Admin Username Synopsis:   Any 15 characters


Default:   admin
Related password is in field Admin Password; full read/write
access to all settings and commands.

Admin Password Synopsis:   19 character ASCII string


Related username is in field Admin Username; full read/write
access to all settings and commands.

Confirm Admin Password Synopsis:   19 character ASCII string


Related username is in field Admin Username; full read/write
access to all settings and commands.

Password Minimum Length Synopsis:   1 to 17


Default:   1
Configure the password string minimum length. The new
password shorter than the minimum length will be rejected.

3. Click Apply.

Section 4.4

Clearing Private Data


When enabled, during system boot up, a user with serial console access can clear all configuration data and keys
stored on the device, and restore all user names and passwords to factory default settings.
To clear private data, do the following:

NOTE
The commands used in the following procedure are time-sensitive. If the specified time limits are
exceeded before providing the appropriate response, the device will continue normal boot up.

1. Connect to the device via the RS-232 serial console port. For more information, refer to Section 2.1.1,
“Connecting Directly” .
2. Cycle power to the device. As the device is booting up, the following prompt will appear:

Press any key to start

3. Within four seconds, press CTRL + r. The access banner will appear, followed by the command prompt:

>

4. Type the following command, then press Enter within 30 seconds:

Clearing Private Data 127


Chapter 4 RUGGEDCOM ROS
System Administration User Guide

clear private data

5. When prompted "Do you want to clear private data (Yes/No)?", answer yes and press Enter within five
seconds. All configuration and keys in flash will be zeroized. An entry in the event log will be created.
Crashlog.txt files (if existing) and syslog.txt files will be preserved. The device will reboot automatically.

Section 4.5

Enabling/Disabling the Web Interface


In some cases, users may want to disable the web interface to increase cyber security.
To disable or enable the web interface, do the following:

NOTE
The web interface can be disabled via the web UI by configuring the Web Server Users Allowed
parameter in the IP Services form. For more information, refer to Section 3.10, “Configuring IP
Services” .

1. Log in to the device as an admin user and access the CLI shell. For more information about accessing the CLI
shell, refer to Section 2.6, “Using the Command Line Interface” .
2. Navigate to Administration » Configure IP Services » Web Server Users Allowed .
3. Select Disabled to disable the web interface, or select the desired number of web server users allowed to
enable the interface.

Section 4.6

Managing Alarms
Alarms indicate the occurrence of events of either importance or interest that are logged by the device.
There are two types of alarms:
• Active alarms signify states of operation that are not in accordance with normal operation. Examples include
links that should be up, but are not, or error rates that repeatedly exceed a certain threshold. These alarms are
continuously active and are only cleared when the problem that triggered the alarms is resolved.
• Passive alarms are a record of abnormal conditions that occurred in the past and do not affect th current
operation state of the device. Examples include authentication failures, Remote Network MONitoring (RMON)
MIB generated alarms, or error states that temporarily exceeded a certain threshold . These alarms can be
cleared from the list of alarms.

NOTE
For more information about RMON alarms, refer to Section 3.11.2, “Managing RMON Alarms” .

When either type of alarm occurs, a message appears in the top right corner of the user interface. If more than
one alarm has occurred, the message will indicate the number of alarms. Active alarms also trip the Critical Failure
Relay LED on the device. The message and the LED will remain active until the alarm is cleared.

128 Enabling/Disabling the Web Interface


RUGGEDCOM ROS Chapter 4
User Guide System Administration

NOTE
Alarms are volatile in nature. All alarms (active and passive) are cleared at startup.

CONTENTS
• Section 4.6.1, “Viewing a List of Pre-Configured Alarms”
• Section 4.6.2, “Viewing and Clearing Latched Alarms”
• Section 4.6.3, “Configuring an Alarm”
• Section 4.6.4, “Authentication Related Security Alarms”

Section 4.6.1

Viewing a List of Pre-Configured Alarms


To view a list of alarms pre-configured for the device, navigate to Diagnostic » Configure Alarms . The Alarms
table appears.

Figure 71: Alarms Table

Viewing a List of Pre-Configured Alarms 129


Chapter 4 RUGGEDCOM ROS
System Administration User Guide

NOTE
This list of alarms (configurable and non-configurable) is accessible through the Command Line
Interface (CLI) using the alarms. For more information, refer to Section 2.6.1, “Available CLI
Commands” .

For information about modifying a pre-configured alarm, refer to Section 4.6.3, “Configuring an Alarm” .

Section 4.6.2

Viewing and Clearing Latched Alarms


To view a list of alarms that are configured to latch, navigate to Diagnostics » View Latched Alarms . The
Latched Alarms table appears.

Figure 72: Latched Alarms Table

To clear the passive alarms from the list, do the following:


1. Navigate to Diagnostics » Clear Latched Alarms . The Clear Latched Alarms form appears.

Figure 73: Clear Latched Alarms Form


1. Confirm Button

2. Click Confirm.

Section 4.6.3

Configuring an Alarm
While all alarms are pre-configured on the device, some alarms can be modified to suit the application. This
includes enabling/disabling certain features and changing the refresh time.
To configuring an alarm, do the following:

130 Viewing and Clearing Latched Alarms


RUGGEDCOM ROS Chapter 4
User Guide System Administration

IMPORTANT!
Critical and Alert level alarms are not configurable and cannot be disabled.

1. Navigate to Diagnostic » Configure Alarms . The Alarms table appears.

Figure 74: Alarms Table

2. Select an alarm. The Alarms form appears.

Configuring an Alarm 131


Chapter 4 RUGGEDCOM ROS
System Administration User Guide

8 9

Figure 75: Alarms Form
1. Name Box    2. Level Box    3. Latch Box    4. Trap Box    5. Log Box    6. LED & Relay Box    7. Refresh Time Box    8. Apply Button   
9. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Name Synopsis:   Any 34 characters


Default:   sys_alarm
The alarm name, as obtained through the alarms CLI command.

Level Synopsis:   { EMRG, ALRT, CRIT, ERRO, WARN, NOTE, INFO, DEBG }
Severity level of the alarm:
• EMERG - The device has had a serious failure that caused a
system reboot.
• ALERT - The device has had a serious failure that did not cause a
system reboot.
• CRITICAL - The device has a serious unrecoverable problem.
• ERROR - The device has a recoverable problem that does not
seriously affect operation.
• WARNING - Possibly serious problem affecting overall system
operation.
• NOTIFY - Condition detected that is not expected or not
allowed.
• INFO - Event which is a part of normal operation, e.g. cold start,
user login etc.
• DEBUG - Intended for factory troubleshooting only.
This parameter is not configurable.

Latch Synopsis:   { On, Off }


Default:   Off
Enables latching occurrence of this alarm in the Alarms Table.

Trap Synopsis:   { On, Off }


Default:   Off
Enables sending an SNMP trap for this alarm.

Log Synopsis:   { On, Off }


Default:   Off

132 Configuring an Alarm


RUGGEDCOM ROS Chapter 4
User Guide System Administration

Parameter Description
Enables logging the occurrence of this alarm in syslog.txt.

LED & Relay Synopsis:   { On, Off }


Default:   Off
Enables LED and fail-safe relay control for this alarm. If latching is
not enabled, this field will remain disabled.

Refresh Time Synopsis:   0 s to 60 s


Default:   60 s
Refreshing time for this alarm.

4. Click Apply.

Section 4.6.4

Authentication Related Security Alarms


RUGGEDCOM ROS provides various logging options related to login authentication. A user can log into a
RUGGEDCOM ROS device in three different ways: Console, SSH or Telnet. RUGGEDCOM ROS can log messages
in the syslog, send a trap to notify an SNMP manager, and/or raise an alarm when a successful and unsuccessful
login event occurs. In addition, when a weak password is configured on a unit or when the primary authentication
server for TACACS+ or RADIUS is not reachable, RUGGEDCOM ROS will raise alarms, send SNMP traps and log
messages in the syslog.
The following is a list of log and alarm messages related to user authentication:
• Weak Password Configured
• Login and Logout Information
• Excessive Failed Login Attempts
• RADIUS Server Unreachable
• TACACS Server Unreachable
• TACACS Response Invalid
• SNMP Authentication Failure

NOTE
All alarms and log messages related to login authentication are configurable. For more information
about configuring alarms, refer to Section 4.6.3, “Configuring an Alarm” .

Weak Password Configured


RUGGEDCOM ROS generates this alarm and logs a message in the syslog when a weak password is configured in
the Passwords table.
Message Name Alarm SNMP Trap Syslog

Weak Password Configured Yes Yes Yes

Authentication Related Security Alarms 133


Chapter 4 RUGGEDCOM ROS
System Administration User Guide

Default Keys In Use


RUGGEDCOM ROS generates this alarm and logs a message in the syslog when default keys are in use. For more
information about default keys, refer to Section 1.9, “SSH and SSL Keys and Certificates” .

NOTE
For Non-Controlled (NC) versions of RUGGEDCOM ROS, this alarm is only generated when default SSL
keys are in use.

Message Name Alarm SNMP Trap Syslog

Default Keys In Use Yes Yes Yes

Login and Logout Information


RUGGEDCOM ROS generates this alarm and logs a message in the syslog when a successful and unsuccessful login
attempt occurs. A message is also logged in the syslog when a user with a certain privilege level is logged out
from the device.
Login attempts are logged regardless of how the user accesses the device (i.e. SSH, Web, Console, Telnet or RSH).
However, when a user logs out, a message is only logged when the user is accessing the device through SSH,
Telnet or Console.
Message Name Alarm SNMP Trap Syslog

Successful Login Yes Yes Yes

Failed Login Yes Yes Yes

User Logout No No Yes

Excessive Failed Login Attempts


RUGGEDCOM ROS generates this alarm and logs a message in the syslog after 10 failed login attempts by a user
occur within a span of five minutes. Furthermore, the service the user attempted to access will be blocked for one
hour to prevent further attempts.
Message Name Alarm SNMP Trap Syslog

Excessive Failed Login Attempts Yes Yes Yes

RADIUS Server Unreachable


RUGGEDCOM ROS generates this alarm and logs a message in the syslog when the primary RADIUS server is
unreachable.
Message Name Alarm SNMP Trap Syslog

Primary RADIUS Server Yes Yes Yes


Unreachable

TACACS+ Server Unreachable


RUGGEDCOM ROS generates this alarm and logs a message in the syslog when the primary TACACS+ server is
unreachable.

134 Authentication Related Security Alarms


RUGGEDCOM ROS Chapter 4
User Guide System Administration

Message Name Alarm SNMP Trap Syslog

Primary TACACS Server Yes Yes Yes


Unreachable

TACACS+ Response Invalid


RUGGEDCOM ROS generate this alarm and logs a message in the syslog when the response from the TACACS+
server is received with an invalid CRC.
Message Name Alarm SNMP Trap Syslog

TACACS Response Invalid Yes Yes Yes

SNMP Authentication Failure


RUGGEDCOM ROS generates this alarm, sends an authentication failure trap, and logs a message in the syslog
when an SNMP manager with incorrect credentials communicates with the SNMP agent in RUGGEDCOM ROS.
Message Name Alarm SNMP Trap Syslog

SNMP Authentication Failure Yes Yes Yes

Section 4.7

Managing the Configuration File


The device configuration file for RUGGEDCOM ROS is a single CSV (Comma-Separate Value) formatted ASCII text
file, named config.csv. It can be downloaded from the device to view, compare against other configuration
files, or store for backup purposes. It can also be overwritten by a complete or partial configuration file uploaded
to the device.
If a microSD/microSDHC card containing a complete or partial configuration file is loaded in the removable
memory card slot, these files will take precedence over the complete or partial configuration files stored in the
internal memory.
To prevent unauthorized access to the contents of the configuration file, the file can be encrypted and given a
password/passphrase key.

CONTENTS
• Section 4.7.1, “Configuring Data Encryption”
• Section 4.7.2, “Updating the Configuration File”

Section 4.7.1

Configuring Data Encryption


To encrypt the configuration file and protect it with a password/passphrase, do the following:

Managing the Configuration File 135


Chapter 4 RUGGEDCOM ROS
System Administration User Guide

NOTE
Data encryption is not available in Non-Controlled (NC) versions of RUGGEDCOM ROS. When switching
between Controlled and Non-Controlled (NC) versions of RUGGEDCOM ROS, make sure data encryption
is disabled. Otherwise, the NC version of RUGGEDCOM ROS will ignore the encrypted configuration file
and load the factory defaults.

NOTE
Only configuration data is encrypted. All comments and table names in the configuration file are saved
as clear text.

NOTE
When sharing a configuration file between devices, make sure both devices have the same passphrase
configured. Otherwise, the configuration file will be rejected.

NOTE
Encryption must be disabled before the device is returned to Siemens or the configuration file is shared
with Customer Support.

IMPORTANT!
Never downgrade the RUGGEDCOM ROS software version beyond RUGGEDCOM ROS v4.3 when
encryption is enabled. Make sure the device has been restored to factory defaults before downgrading.

1. Navigate to Administration » Configure Data Storage . The Data Storage form appears.

4 5

Figure 76: Data Storage Form


1. Encryption Options    2. Passphrase Box    3. Confirm Passphrase Box    4. Apply Button    5. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

Encryption Synopsis:   { On, Off }


Enable/disable encryption of data in configuration file.

Passphrase Synopsis:   31 character ascii string


This passphrase is used as a secret key to encrypt the
configuration data.
Encrypted data can be decrypted by any device configured with
the same passphrase.

Confirm Passphrase Synopsis:   31 character ascii string

136 Configuring Data Encryption


RUGGEDCOM ROS Chapter 4
User Guide System Administration

Parameter Description
This passphrase is used as a secret key to encrypt the
configuration data.
Encrypted data can be decrypted by any device configured with
the same passphrase.

3. Click Apply.

Section 4.7.2

Updating the Configuration File


Once downloaded from the device, the configuration file can be updated using a variety of different tools:

NOTE
For information about uploading/downloading files, refer to Section 3.5, “Uploading/Downloading
Files” .

• Any text editing program capable of reading and writing ASCII files
• Difference/patching tools (e.g. the UNIX diff and patch command line utilities)
• Source Code Control systems (e.g. CVS, SVN)

CAUTION!
Configuration hazard – risk of data loss. Do not edit an encrypted configuration file. Any line that has
been modified manually will be ignored.

RUGGEDCOM ROS also has the ability to accept partial configuration updates. For example, to update only the
parameters for Ethernet port 1 and leave all other parameters unchanged, transfer a file containing only the
following lines to the device:

# Port Parameters
ethPortCfg
Port,Name,Media,State,AutoN,Speed,Dupx,FlowCtrl,LFI,Alarm,
1,Port 1,100TX,Enabled,On,Auto,Auto,Off,Off,On,

Section 4.8

Managing an Authentication Server


The following section describes how to setup and configure an authentication server.

CONTENTS
• Section 4.8.1, “Managing RADIUS Authentication”

Updating the Configuration File 137


Chapter 4 RUGGEDCOM ROS
System Administration User Guide

• Section 4.8.2, “Managing TACACS+ Authentication”

Section 4.8.1

Managing RADIUS Authentication


RUGGEDCOM ROS can be configured to act as a RADIUS client and forward user credentials to a RADIUS (Remote
Authentication Dial In User Service) server for remote authentication and authorization.
RADIUS is a UDP-based protocol used for carrying authentication, authorization and configuration information
between a Network Access Server (NAS) that desires to authenticate its links and a shared authentication server. It
provides centralized authentication and authorization for network access.
RADIUS is also widely used in conjunction with the IEEE 802.1X standard for port security using the Extensible
Authentication Protocol (EAP).

NOTE
For more information about the RADIUS protocol, refer to RFC 2865.
For more information about the Extensible Authentication Protocol (EAP), refer to RFC 3748.

IMPORTANT!
RADIUS messages are sent as UDP messages. The switch and the RADIUS server must use the same
authentication and encryption key.

IMPORTANT!
RUGGEDCOM ROS supports both Protected Extensible Authentication Protocol (PEAP) and EAP-MD5.
PEAP is more secure and is recommended if available in the supplicant.

In a RADIUS access request, the following attributes and values are typically sent by the RADIUS client to the
RADIUS server:
Attribute Value

User-Name { Guest, Operator, Admin }

User-Password { password }

Service-Type 1

Vendor-Specific Vendor-ID: 15004


Type: 1
Length: 11
String: RuggedCom
A RADIUS server may also be used to authenticate access on ports with 802.1X security support. When this is
required, the following attributes are sent by the RADIUS client to the RADIUS server:
Attribute Value

User-Name { The username as derived from the client's EAP identity response }

NAS-IP-Address { The Network Access Server IP address }

Service-Type 2

Frame-MTU 1500

138 Managing RADIUS Authentication


RUGGEDCOM ROS Chapter 4
User Guide System Administration

Attribute Value
a
EAP-Message { A message(s) received from the authenticating peer }
a
EAP-Message is an extension attribute for RADIUS, as defined by RFC 2869.

CONTENTS
• Section 4.8.1.1, “Configuring the RADIUS Server”
• Section 4.8.1.2, “Configuring the RADIUS Client”

Section 4.8.1.1
Configuring the RADIUS Server
The Vendor-Specific attribute (or VSA) sent to the RADIUS server as part of the RADIUS request is used to
determine the access level from the RADIUS server. This attribute may be configured within the RADIUS server
with the following information:
Attribute Value

Vendor-Specific Vendor-ID: 15004


Format: String
Number: 2
Attribute: { Guest, Operator, Admin }

NOTE
If no access level is received in the response packet from the RADIUS server, access is denied.

Section 4.8.1.2
Configuring the RADIUS Client
The RADIUS client can be configured to use two RADIUS servers: a primary server and a backup server. If the
primary server is unavailable, the device will automatically attempt to connect with the backup server.

NOTE
The RADIUS client uses the Password Authentication Protocol (PAP) to verify access.

To configure access to either the primary or backup RADIUS servers, do the following:
1. Navigate to Administration » Configure Security Server » Configure RADIUS Server . The RADIUS Server
table appears.

Configuring the RADIUS Server 139


Chapter 4 RUGGEDCOM ROS
System Administration User Guide

Figure 77: RADIUS Server Table

2. Select either Primary or Backup from the table. The RADIUS Server form appears.

5
6
7

Figure 78: RADIUS Server Form


1. Server Box    2. IP Address Box    3. Auth UDP Port Box    4. Auth Key Box    5. Confirm Auth Key Box    6. Apply Button    7. Reload
Button

3. Configure the following parameter(s) as required:

Parameter Description

Server Synopsis:   Any 8 characters


Default:   Primary
This field tells whether this configuration is for a Primary or a
Backup Server.

IP Address Synopsis:   ###.###.###.### where ### ranges from 0 to 255


The Server IP Address.

Auth UDP Port Synopsis:   1 to 65535


Default:   1812
The IP Port on server.

Auth Key Synopsis:   31 character ASCII string


The authentication key to be shared with server.

Confirm Auth Key Synopsis:   31 character ASCII string


The authentication key to be shared with server.

4. Click Apply.

140 Configuring the RADIUS Client


RUGGEDCOM ROS Chapter 4
User Guide System Administration

Section 4.8.2

Managing TACACS+ Authentication


TACACS+ (Terminal Access Controller Access-Control System Plus) is a TCP-based access control protocol that
provides authentication, authorization and accounting services to routers, Network Access Servers (NAS) and
other networked computing devices via one or more centralized servers.
The following section describes how to configure TACACs+ authentication.

CONTENTS
• Section 4.8.2.1, “Configuring TACACS+”
• Section 4.8.2.2, “Configuring User Privileges”

Section 4.8.2.1
Configuring TACACS+
RUGGEDCOM ROS can be configured to use two TACACS+ servers: a primary server and a backup server. If the
primary server is unavailable, the device will automatically attempt to connect with the backup server.
To configure access to either the primary or backup TACACS+ servers, do the following:
1. Navigate to Administration » Configure Security Server » Configure TacPlus Server » Configure TACACS
Plus Server . The TACACS Plus Server table appears.

Figure 79: TACACS Plus Server Table

2. Select either Primary or Backup from the table. The TACACS Plus Server form appears.

Managing TACACS+ Authentication 141


Chapter 4 RUGGEDCOM ROS
System Administration User Guide

6 7

Figure 80: TACACS Plus Server Form


1. Server Box    2. IP Address Box    3. Auth TCP Port Box    4. Auth Key Box    5. Confirm Key Box    6. Apply Button    7. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Server Synopsis:   Any 8 characters


Default:   Primary
This field tells whether this configuration is for a Primary or a
Backup Server.

IP Address Synopsis:   ###.###.###.### where ### ranges from 0 to 255


The Server IP Address.

Auth TCP Port Synopsis:   1 to 65535


Default:   49
The IP Port on server.

Auth Key Synopsis:   31 character ascii string


Default:   mySecret
The authentication key to be shared with server.

Confirm Auth Key Synopsis:   31 character ascii string


The authentication key to be shared with server.

4. Set the privilege levels for each user type (i.e. admin, operator and guest). For more information, refer to
Section 4.8.2.2, “Configuring User Privileges” .
5. Click Apply.

Section 4.8.2.2
Configuring User Privileges
Each TACACS+ authentication request includes a priv_lvl attribute that is used to grant access to the device. By
default, the attribute uses the following ranges:
• 15 represents the admin access level
• 2-14 represents the operator access level
• 1 represents the guest access level

142 Configuring User Privileges


RUGGEDCOM ROS Chapter 4
User Guide System Administration

To configure the privilege levels for each user type, do the following:
1. Navigate to Administration » Configure Security Server » Configure TacPlus Server » Configure TACPLUS
Serv Privilege Config . The TACPLUS Serv Privilege Config form appears.

4 5

Figure 81: TACPLUS Serv Privilege Config Form


1. Admin Priv Box    2. Oper Priv Box    3. Guest Priv Box    4. Apply Button    5. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

Admin Priv Synopsis:   (0 to 15)-(0 to 15)


Default:   15
Privilege level to be assigned to the user.

Oper Priv Synopsis:   (0 to 15)-(0 to 15)


Default:   2-14
Privilege level to be assigned to the user.

Guest Priv Synopsis:   (0 to 15)-(0 to 15)


Default:   1
Privilege level to be assigned to the user.

3. Click Apply.

Configuring User Privileges 143


RUGGEDCOM ROS Chapter 4
User Guide System Administration

Configuring User Privileges 144


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Setup and Configuration


This chapter describes how to setup and configure the device for use on a network using the various features
available in RUGGEDCOM ROS.

CONTENTS
• Section 5.1, “Managing Virtual LANs”
• Section 5.2, “Managing Spanning Tree Protocol”
• Section 5.3, “Managing Classes of Service”
• Section 5.4, “Managing MAC Addresses”
• Section 5.5, “Managing Time Services”
• Section 5.6, “Managing SNMP”
• Section 5.7, “Managing Network Discovery”
• Section 5.8, “Managing Multicast Filtering”
• Section 5.9, “Managing DHCP”
• Section 5.10, “Managing Port Security”
• Section 5.11, “Managing Link Aggregation”

Section 5.1

Managing Virtual LANs


A Virtual Local Area Network (VLAN) is a group of devices on one or more LAN segments that communicate as if
they were attached to the same physical LAN segment. VLANs are extremely flexible because they are based on
logical connections, rather than physical connections.
When VLANs are introduced, all traffic in the network must belong to one VLAN or another. Traffic on one VLAN
cannot pass to another, except through an inter-network router or Layer 3 switch.
VLANs are created in two ways:
• Explicitly
Static VLANs can be created in the switch. For more information about static VLANs, refer to Section 5.1.5,
“Managing Static VLANs” .
• Implicitly
When a VLAN ID (VID) is set for a port-based VLAN, static MAC address or IP interface, an appropriate VLAN is
automatically created if it does not yet exist.
For more information about VLANs, refer to Section 5.1.1, “VLAN Concepts” .

CONTENTS
• Section 5.1.1, “VLAN Concepts”
• Section 5.1.2, “Viewing a List of VLANs”

Managing Virtual LANs 145


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

• Section 5.1.3, “Configuring VLANs Globally”


• Section 5.1.4, “Configuring VLANs for Specific Ethernet Ports”
• Section 5.1.5, “Managing Static VLANs”

Section 5.1.1

VLAN Concepts
The following section describes some of the concepts important to the implementation of VLANs in RUGGEDCOM
ROS.

CONTENTS
• Section 5.1.1.1, “Tagged vs. Untagged Frames”
• Section 5.1.1.2, “Native VLAN”
• Section 5.1.1.3, “The Management VLAN”
• Section 5.1.1.4, “Edge and Trunk Port Types”
• Section 5.1.1.5, “Ingress and Egress Rules”
• Section 5.1.1.6, “Forbidden Ports List”
• Section 5.1.1.7, “VLAN-Aware and VLAN-Unaware Modes”
• Section 5.1.1.8, “GARP VLAN Registration Protocol (GVRP)”
• Section 5.1.1.9, “PVLAN Edge”
• Section 5.1.1.10, “QinQ”
• Section 5.1.1.11, “VLAN Advantages”

Section 5.1.1.1
Tagged vs. Untagged Frames
VLAN tags identify frames as part of a VLAN network. When a switch receives a frame with a VLAN (or 802.1Q)
tag, the VLAN identifier (VID) is extracted and the frame is forwarded to other ports on the same VLAN.
When a frame does not contain a VLAN tag, or contains an 802.1p (prioritization) tag that only has prioritization
information and a VID of 0, it is considered an untagged frame.

Section 5.1.1.2
Native VLAN
Each port is assigned a native VLAN number, the Port VLAN ID (PVID). When an untagged frame ingresses a port, it
is associated with the port's native VLAN.
By default, when a switch transmits a frame on the native VLAN, it sends the frame untagged. The switch can be
configured to transmit tagged frames on the native VLAN.

146 VLAN Concepts


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Section 5.1.1.3
The Management VLAN
Management traffic, like all traffic on the network, must belong to a specific VLAN. The management VLAN is
configurable and always defaults to VLAN 1. This VLAN is also the default native VLAN for all ports, thus allowing
all ports the possibility of managing the product. Changing the management VLAN can be used to restrict
management access to a specific set of users.

Section 5.1.1.4
Edge and Trunk Port Types
Each port can be configured as an edge or trunk port.
An edge port attaches to a single end device, such as a PC or Intelligent Electronic Device (IED). An edge port
carries traffic on the native VLAN.
Trunk ports are part of the network and carry traffic for all VLANs between switches. Trunk ports are automatically
members of all VLANs configured in the switch.
The switch can 'pass through' traffic, forwarding frames received on one trunk port out of another trunk port. The
trunk ports must be members of all VLANs that the 'pass through' traffic is part of, even if none of those VLANs are
used on edge ports.
Frames transmitted out of the port on all VLANs other than the port's native VLAN are always sent tagged.

NOTE
It may be desirable to manually restrict the traffic on the trunk to a specific group of VLANs. For
example, when the trunk connects to a device, such as a Layer 3 router, that supports a subset of the
available LANs. To prevent the trunk port from being a member of the VLAN, include it in the VLAN's
Forbidden Ports list.
For more information about the Forbidden Ports list, refer to Section 5.1.1.6, “Forbidden Ports List” .

Port Type VLANs Supported PVID Format Usage

Edge 1 (Native) Untagged VLAN Unaware Networks: All frames are sent and received without
Configured the need for VLAN tags.

Tagged VLAN Aware Networks: VLAN traffic domains are enforced on a


single VLAN.

Trunk All Configured Tagged or Untagged Switch-to-Switch Connections: VLANs must be manually created and
administered, or can be dynamically learned through GVRP.
Multiple-VLAN End Devices: Implement connections to end devices
that support multiple VLANs at the same time.

Section 5.1.1.5
Ingress and Egress Rules
Ingress and egress rules determine how traffic is received and transmitted by the switch.
Ingress rules are applied as follows to all frame when they are received by the switch:

The Management VLAN 147


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

a Priority Tagged
Frame Received Untagged Tagged (Valid VID)
(VID = 0)

VLAN ID associated with the frame PVID PVID VID in the Tag

Frame dropped due to its tagged/untagged format No No No

Frame dropped if the ingress port is not a member of the VLAN the Yes
frame is associated with and ingress filtering is enabled
a
Does not depend on the ingress port's VLAN configuration parameters.

Egress rules are applied as follows to all frames when they are transmitted by the switch.
On Other VLAN
Egress Port Type On Egress Port's Native VLAN
Port Is Not a Member
Port Is a Member Of the VLAN
Of the VLAN

Edge According to the egress port's Dropped


PVID Format parameter
Trunk Tagged Dropped

Section 5.1.1.6
Forbidden Ports List
Each VLAN can be configured to exclude ports from membership in the VLAN using the forbidden ports list. For
more information, refer to Section 5.1.5.2, “Adding a Static VLAN” .

Section 5.1.1.7
VLAN-Aware and VLAN-Unaware Modes
The native operation mode for an IEEE 802.1Q compliant switch is VLAN-aware. Even if a specific network
architecture does not use VLANs, RUGGEDCOM ROS's default VLAN settings allow the switch to still operate in a
VLAN-aware mode, while providing functionality required for almost any network application. However, the IEEE
802.1Q standard defines a set of rules that must be followed by all VLAN-aware switches:
• Valid VIDs are within the range of 1 to 4094. VIDs equal to 0 or 4095 are invalid.
• Each frame ingressing a VLAN-aware switch is associated with a valid VID.
• Each frame egressing a VLAN-aware switch is either untagged or tagged with a valid VID. Priority-tagged frames
with an invalid VID will never sent out by a VLAN-aware switch.

NOTE
Some applications have requirements conflicting with IEEE 802.Q1 native mode of operation. For
example, some applications explicitly require priority-tagged frames to be received by end devices.
To avoid conflicts and provide full compatibility with legacy (VLAN-unaware) devices, RUGGEDCOM
ROS can be configured to work in VLAN-unaware mode.
In that mode:
• Frames ingressing a VLAN-unaware device are not associated with any VLAN
• Frames egressing a VLAN-unaware device are sent out unmodified (i.e. in the same untagged,
802.1Q-tagged or priority-tagged format as they were received)

148 Forbidden Ports List


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Section 5.1.1.8
GARP VLAN Registration Protocol (GVRP)
GARP VLAN Registration Protocol (GVRP) is a standard protocol built on GARP (Generic Attribute Registration
Protocol) to automatically distribute VLAN configuration information in a network. Each switch in a network needs
only to be configured with VLANs it requires locally. VLANs configured elsewhere in the network are learned
through GVRP. A GVRP-aware end station (i.e. PC or Intelligent Electronic Device) configured for a particular VID
can be connected to a trunk on a GVRP-aware switch and automatically become part of the desired VLAN.
When a switch sends GVRP bridge protocol data units (BPDUs) out of all GVRP-enabled ports, GVRP BPDUs advertise
all the VLANs known to that switch (configured manually or learned dynamically through GVRP) to the rest of the
network.
When a GVRP-enabled switch receives a GVRP BPDU advertising a set of VLANs, the receiving port becomes a
member of those advertised VLANs and the switch begins advertising those VLANs through all the GVRP-enabled
ports (other than the port on which the VLANs were learned).
To improve network security using VLANs, GVRP-enabled ports may be configured to prohibit the learning of any
new dynamic VLANs but at the same time be allowed to advertise the VLANs configured on the switch.
The following is an example of how to use GVRP:

D2 D

D1

B3 B
B1
B2
B4

A1 A E1 E C1 C
1

A2 E2 C2

A E C 2

Figure 82: Using GVRP
1. Switch    2. End Node

• Switch B is the core switch, all others are edge switches


• Ports A1, B1 to B4, C1, D1, D2 and E1 are GVRP aware

GARP VLAN Registration Protocol (GVRP) 149


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

• Ports B1 to B4, D1 and D2 are set to advertise and learn


• Ports A1, C1 and E1 are set to advertise only
• Ports A2, C2 and E2 are edge ports
• End node D is GVRP aware
• End nodes A, E and C are GVRP unaware
• Ports A2 and C2 are configured with PVID 7
• Port E2 is configured with PVID 20
• End node D is interested in VLAN 20, hence VLAN 20 is advertised by it towards switch D
• D2 becomes a member of VLAN 20
• Ports A1 and C1 advertise VID 7
• Ports B1 and B2 become members of VLAN 7
• Ports B1, B2 and D1 advertise VID 20
• Ports B3, B4 and D1 become members of VLAN 20
For more information about how to configure GVRP, refer to Section 5.1.4, “Configuring VLANs for Specific
Ethernet Ports” .

Section 5.1.1.9
PVLAN Edge
Private VLAN (PVLAN) Edge isolates multiple VLAN Edge ports from each other on a single device. When VLAN
Edge ports are configured as protected, they are prohibited from sending frames to one another, but are still
permitted to send frames to other, non-protected ports within the same VLAN. This protection extends to all traffic
on the VLAN, including unicast, multicast and broadcast traffic.
For more information about how to configure a port as protected, refer to Section 5.1.4, “Configuring VLANs for
Specific Ethernet Ports” .

NOTE
This feature is strictly local to the switch. PVLAN Edge ports are not prevented from communicating
with ports outside of the switch, whether protected (remotely) or not.

Section 5.1.1.10
QinQ
QinQ, also referred to as Stacked VLANs, port bridging, double VLAN-tagging and Nested VLANs, is used to overlay
a private Layer 2 network over a public Layer 2 network.
A large network service provider, for example, might have several clients whose networks each use multiple
VLANs. It is likely the VLAN IDs used by these different client networks would conflict with one another, were
they mixed together in the provider's network. Using double QinQ, each client network could be further tagged
using a client-specific VID at the edges where the clients' networks are connected to the network service provider's
infrastructure.
Any tagged frames ingressing an edge port of the service provider's switch are tagged with VIDs of the customer’s
private network. When those frames egress the switch's QinQ-enabled port into the service provider network, the
switch always adds an extra tag (called an outer tag) on top of the frame's original VLAN tag (called an inner tag).

150 PVLAN Edge


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

The outer tag VID is the PVID of the frame's ingress edge port. This means that traffic from an individual customer
is tagged with their unique VID and is thus segregated from other customer's traffic. For untagged ingress frames,
the switch will only add the outer VLAN tag.
Within the service provider network, switching is based on the VID in the outer tag.
When double-tagged frames leave the service provider network, they egress a QinQ-enabled port of another
switch. The switch strips the outer tag while associating the frames with the VID extracted from it before stripping.
Thus, the frames are switched to appropriate edge ports ( i.e. customers).
The following figure shows an example of traffic flow using QinQ.
For tagged frames:
• Frames received from customer 1 with VID 100 would carry an inner tag of 100 and an outer tag of VID X (i.e.
VLAN 110) which is configured on the edge port connected to customer 1.
• Next, the frames from customer 1 are forwarded through the QinQ port carrying an inner and an outer tag.
• Finally, upon arrival of the frames in the peer switch, the outer VLAN tag is removed and the frames are
forwarded with the inner VLAN tag towards customer 1.
For untagged frames:
• Frames received from customer 2 would carry an outer tag of VID Y(i.e VLAN 220) which is configured on the
edge port connected to customer 2.
• Next, the frames from customer 2 are forwarded through the QinQ port carrying the outer tag.
• Finally, upon arrival of the frames in the peer switch, the outer VLAN tag is removed before the frames are
forwarded to customer 2.

2 1

5 5

4 4

1 2

Figure 83: Using QinQ
1. Customer 1 (PVID is X)    2. Customer 2 (PVID is Y)    3. Network Service Provider Infrastructure    4. Switch    5. QinQ

NOTE
Depending on the hardware installed, some switch models allow only one switch port be configured to
QinQ mode at a time.

NOTE
When QinQ is enabled, all non-QinQ ports will be untagged and cannot be changed, and all QinQ ports
will be tagged, and cannot be changed.

QinQ 151
Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Section 5.1.1.11
VLAN Advantages
The following are a few of the advantages offered by VLANs.

Traffic Domain Isolation


VLANs are most often used for their ability to restrict traffic flows between groups of devices.
Unnecessary broadcast traffic can be restricted to the VLAN that requires it. Broadcast storms in one VLAN need
not affect users in other VLANs.
Hosts on one VLAN can be prevented from accidentally or deliberately assuming the IP address of a host on
another VLAN.
The use of creative bridge filtering and multiple VLANs can carve seemingly unified IP subnets into multiple
regions policed by different security/access policies.
Multi-VLAN hosts can assign different traffic types to different VLANs.

1 3

2 4
5

Figure 84: Multiple Overlapping VLANs


1. VLAN    2. Switch

Administrative Convenience
VLANs enable equipment moves to be handled by software reconfiguration instead of by physical cable
management. When a host's physical location is changed, its connection point is often changed as well. With
VLANs, the host's VLAN membership and priority are simply copied to the new port.

Reduced Hardware
Without VLANs, traffic domain isolation requires the use of separate bridges for separate networks. VLANs
eliminate the need for separate bridges.
The number of network hosts may often be reduced. Often, a server is assigned to provide services for
independent networks. These hosts may be replaced by a single, multi-horned host supporting each network on
its own VLAN. This host can perform routing between VLANs.
Multi-VLAN hosts can assign different traffic types to different VLANs.

152 VLAN Advantages


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

199.85.245.1/25

1 4

199.85.245.128/26

199.85.245.192/26

Figure 85: Inter-VLAN Communications
1. Server, Router or Layer 3 Switch    2. Switch    3. VLAN 2    4. VLAN 3    5. VLAN 4

Section 5.1.2

Viewing a List of VLANs


To view a list of all VLANs, whether they were created statically or implicitly, navigate to Virtual LANs » View
VLAN Summary . The VLAN Summary table appears.

Figure 86: VLAN Summary Table

If a VLANs are not listed, add static VLANs as needed. For more information, refer to Section 5.1.5.2, “Adding a
Static VLAN” .

Section 5.1.3

Configuring VLANs Globally


To configure global settings for all VLANs, do the following:
1. Navigate to Virtual LANs » Configure Global VLAN Parameters . The Global VLAN Parameters form
appears.

Viewing a List of VLANs 153


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

4 5

Figure 87: Global VLAN Parameters Form


1. VLAN-aware Options    2. Ingress Filtering Options    3. QinQ Outer TPID options    4. Apply Button    5. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

VLAN-aware Synopsis:   { No, Yes }


Default:   Yes
Set either VLAN-aware or VLAN-unaware mode of operation.

Ingress Filtering Synopsis:   { Disabled, Enabled }


Default:   Disabled
Enables or disables VLAN ingress filtering on all ports. When
enabled, any tagged packet arriving at a port, which is not
a member of a VLAN with which that packet is associated, is
dropped. When disabled, packets are not dropped.

NOTE
Ingress filtering has no effect when ports are in
either VLAN-unaware mode or Q-in-Q mode.

QinQ Outer TPID Synopsis:   { 0x8100, 0x88A8 }


Default:   0x8100
Selects an Ethertype to be used as the Tag Protocol Identifier
(TPID) on VLAN QinQ ports when QinQ is enabled. Frames that
ingress a VLAN QinQ port will be identified as outer VLAN tagged
if the first Ethertype matches this value; an outer VLAN tag with
the TPID field assigned to this value will be inserted to frames that
egress a VLAN QinQ port.

NOTE
When QinQ is enabled, all non-QinQ ports will be
untagged and cannot be changed, and all QinQ
ports will be tagged, and cannot be changed.

3. Click Apply.

154 Configuring VLANs Globally


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Section 5.1.4

Configuring VLANs for Specific Ethernet Ports


When a VLAN ID is assigned to an Ethernet port, the VLAN appears in the VLAN Summary table where it can be
further configured.
To configure a VLAN for a specific Ethernet port, do the following:
1. Navigate to Virtual LANs » Configure Port VLAN Parameters . The Port VLAN Parameters table appears.

Figure 88: Port VLAN Parameters Table

2. Select a port. The Port VLAN Parameters form appears.

6 7

Figure 89: Port VLAN Parameters Form


1. Port(s) Box    2. Type List    3. PVID Box    4. PVID Format Options    5. GVRP List    6. Apply Button    7. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Port(s) Synopsis:   Any combination of numbers valid for this parameter


The port number as seen on the front plate silkscreen of the
switch (or a list of ports, if aggregated in a port trunk).

Type Synopsis:   { Edge, Trunk, PVLANEdge, QinQ }


Default:   Edge
This parameter specifies how the port determines its membership
in VLANs. There are few types of ports:

Configuring VLANs for Specific Ethernet Ports 155


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description
• Edge - the port is only a member of one VLAN (its native VLAN
specified by the PVID parameter).
• Trunk - the port is automatically a member of all configured
VLANs. Frames transmitted out of the port on all VLANs except
the port's native VLAN will be always tagged. It can also be
configured to use GVRP for automatic VLAN configuration.
• PVLANEdge - the port is only a member of one VLAN (its native
VLAN specified by the PVID parameter), and does not forward
traffic to other PVLANedge ports within the same VLAN.
• QinQ - the port is a trunk port using double-VLAN tagging, or
nested VLANs. An extra VLAN tag is always added to all frames
egressing this port. VID in the added extra tag is the PVID of the
frame's ingress port. VLAN tag is always stripped from frames
ingressing this port.

NOTE
Depending on the hardware installed, some
switch models allow only one switch port be
configured to QinQ mode at a time.

PVID Synopsis:   1 to 4094


Default:   1
The Port VLAN Identifier specifies the VLAN ID associated with
untagged (and 802.1p priority tagged) frames received on this
port.
Frames tagged with a non-zero VLAN ID will always be associated
with the VLAN ID retrieved from the frame tag.
Modify this parameter with care! By default, the switch is
programmed to use VLAN 1 for management and every port on
the switch is programmed to use VLAN 1. If you modify a switch
port to use a VLAN other than the management VLAN, devices on
that port will not be able to manage the switch.

PVID Format Synopsis:   { Untagged, Tagged }


Default:   Untagged
Specifies whether frames transmitted out of the port on its
native VLAN (specified by the PVID parameter) will be tagged or
untagged.

NOTE
When QinQ is enabled, all non-QinQ ports will be
untagged and cannot be changed, and all QinQ
ports will be tagged, and cannot be changed.

GVRP Synopsis:   { Adv&Learn, Adv Only, Disabled }


Default:   Disabled
Configures GVRP (Generic VLAN Registration Protocol) operation
on the port. There are several GVRP operation modes:
• DISABLED - the port is not capable of any GVRP processing.
• ADVERTISE ONLY - the port will declare all VLANs existing in the
switch (configured or learned) but will not learn any VLANs.
• ADVERTISE & LEARN - the port will declare all VLANs existing in
the switch (configured or learned) and can dynamically learn
VLANs.
Only Trunk ports are GVRP-capable.

4. Click Apply.

156 Configuring VLANs for Specific Ethernet Ports


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Section 5.1.5

Managing Static VLANs


The following section describes how to configure and manage static VLANs.

CONTENTS
• Section 5.1.5.1, “Viewing a List of Static VLANs”
• Section 5.1.5.2, “Adding a Static VLAN”
• Section 5.1.5.3, “Deleting a Static VLAN”

Section 5.1.5.1
Viewing a List of Static VLANs
To view a list of static VLANs, navigate to Virtual LANs » Configure Static VLANs . The Static VLANs table
appears.

Figure 90: Static VLANs Table

If a static VLAN is not listed, add the VLAN. For more information, refer to Section 5.1.5.2, “Adding a Static VLAN” .

Section 5.1.5.2
Adding a Static VLAN
To add a static VLAN, do the following:
1. Navigate to Virtual LANs » Configure Static VLANs . The Static VLANs table appears.

Managing Static VLANs 157


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Figure 91: Static VLANs Table


1. InsertRecord

2. Click InsertRecord. The Static VLANs form appears.

7 9

Figure 92: Static VLANs Form


1. VID Box    2. VLAN Name Box    3. Forbidden Ports Box    4. IGMP Options    5. DHCP Options    6. MSTI Box    7. Apply Button   
8. Delete Button    9. Reload Button

3. Configure the following parameter(s) as required:

NOTE
If IGMP Options is not enabled for the VLAN, both IGMP messages and multicast streams will be
forwarded directly to all members of the VLAN. If any one member of the VLAN joins a multicast
group, then all members of the VLAN will receive the multicast traffic.

Parameter Description

VID Synopsis:   1 to 4094


Synopsis:   1 to 4094

158 Adding a Static VLAN


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description
Default:   1
The VLAN Identifier is used to identify the VLAN in tagged
Ethernet frames according to IEEE 802.1Q.

VLAN Name Synopsis:   Any 19 characters


The VLAN name provides a description of the VLAN purpose (for
example, Engineering VLAN).

Forbidden Ports Synopsis:   Any combination of numbers valid for this parameter
These are ports that are not allowed to be members of the VLAN.
Examples:
• None - all ports of the switch are allowed to be members of the
VLAN
• 2,4-6,8 - all ports except ports 2, 4, 6, 7 and 8 are allowed to be
members of the VLAN

IGMP Synopsis:   { Off, On }


Default:   Off
This parameter enables or disables IGMP Snooping on the VLAN.

DHCP Synopsis:   { Off, On }


Default:   Off
This parameter enables or disables DHCP Snooping on the VLAN.

MSTI Synopsis:   0 to 16
Default:   0
This parameter is only valid for Multiple Spanning Tree Protocol
(MSTP) and has no effect if MSTP is not used. The parameter
specifies the Multiple Spanning Tree Instance (MSTI) to which the
VLAN should be mapped.

4. Click Apply.

Section 5.1.5.3
Deleting a Static VLAN
To delete a static VLAN, do the following:
1. Navigate to Virtual LANs » Configure Static VLANs . The Static VLANs table appears.

Deleting a Static VLAN 159


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Figure 93: Static VLANs Table

2. Select the static VLAN from the table. The Static VLANs form appears.

7 9

Figure 94: Static VLANs Form


1. VID Box    2. VLAN Name Box    3. Forbidden Ports Box    4. IGMP Options    5. DHCP Options    6. MSTI Box    7. Apply Button   
8. Delete Button    9. Reload Button

3. Click Delete.

160 Deleting a Static VLAN


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Section 5.2

Managing Spanning Tree Protocol


CONTENTS
• Section 5.2.1, “RSTP Operation”
• Section 5.2.2, “RSTP Applications”
• Section 5.2.3, “MSTP Operation”
• Section 5.2.4, “Configuring STP Globally”
• Section 5.2.5, “Configuring STP for Specific Ethernet Ports”
• Section 5.2.6, “Configuring eRSTP”
• Section 5.2.7, “Viewing Global Statistics for STP”
• Section 5.2.8, “Viewing STP Statistics for Ethernet Ports”
• Section 5.2.9, “Managing Multiple Spanning Tree Instances”
• Section 5.2.10, “Clearing Spanning Tree Protocol Statistics”

Section 5.2.1

RSTP Operation
The 802.1D Spanning Tree Protocol (STP) was developed to enable the construction of robust networks that
incorporate redundancy while pruning the active topology of the network to prevent loops. While STP is effective,
it requires that frame transfer halt after a link outage until all bridges in the network are guaranteed to be aware
of the new topology. Using the values recommended by 802.1D, this period lasts 30 seconds.
The Rapid Spanning Tree Protocol (RSTP, IEEE 802.1w) was a further evolution of the 802.1D Spanning Tree
Protocol. It replaced the settling period with an active handshake between bridges that guarantees the rapid
propagation of topology information throughout the network. RSTP also offers a number of other significant
innovations, including:
• Topology changes in RSTP can originate from and be acted upon by any designated bridges, leading to more
rapid propagation of address information, unlike topology changes in STP, which must be passed to the root
bridge before they can be propagated to the network.
• RSTP explicitly recognizes two blocking roles - Alternate and Backup Port - which are included in computations
of when to learn and forward. STP, however, recognizes only one state - Blocking - for ports that should not
forward.
• RSTP bridges generate their own configuration messages, even if they fail to receive any from the root bridge.
This leads to quicker failure detection. STP, by contrast, must relay configuration messages received on the root
port out its designated ports. If an STP bridge fails to receive a message from its neighbor, it cannot be sure
where along the path to the root a failure occurred.
• RSTP offers edge port recognition, allowing ports at the edge of the network to forward frames immediately
after activation, while at the same time protecting them against loops.
While providing much better performance than STP, IEEE 802.1w RSTP still required up to several seconds to
restore network connectivity when a topology change occurred.
A revised and highly optimized RSTP version was defined in the IEEE standard 802.1D-2004 edition. IEEE
802.1D-2004 RSTP reduces network recovery times to just milliseconds and optimizes RSTP operation for various
scenarios.

Managing Spanning Tree Protocol 161


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

RUGGEDCOM ROS supports IEEE 802.1D-2004 RSTP.

CONTENTS
• Section 5.2.1.1, “RSTP States and Roles”
• Section 5.2.1.2, “Edge Ports”
• Section 5.2.1.3, “Point-to-Point and Multipoint Links”
• Section 5.2.1.4, “Path and Port Costs”
• Section 5.2.1.5, “Bridge Diameter”
• Section 5.2.1.6, “eRSTP”
• Section 5.2.1.7, “Fast Root Failover”

Section 5.2.1.1
RSTP States and Roles
RSTP bridges have roles to play, either root or designated. One bridge - the Root Bridge - is the logical center of
the network. All other bridges in the network are Designated bridges. RSTP also assigns each port of the bridge a
state and a role. The RSTP state describes what is happening at the port in relation to address learning and frame
forwarding. The RSTP role basically describes whether the port is facing the center or the edges of the network
and whether it can currently be used.

State
There are three RSTP states: Discarding, Learning and Forwarding.
The discarding state is entered when the port is first put into service. The port does not learn addresses in this
state and does not participate in frame transfer. The port looks for RSTP traffic in order to determine its role in
the network. When it is determined that the port will play an active part in the network, the state will change to
learning.
The learning state is entered when the port is preparing to play an active part in the network. The port learns
addresses in this state but does not participate in frame transfer. In a network of RSTP bridges, the time spent in
this state is usually quite short. RSTP bridges operating in STP compatibility mode will spend six to 40 seconds in
this state.
After learning, the bridge will place the port in the forwarding state. The port both learns addresses and
participates in frame transfer while in this state.

IMPORTANT!
RUGGEDCOM ROS introduces two more states - Disabled and Link Down. Introduced purely for purposes
of management, these states may be considered subclasses of the RSTP Discarding state. The Disabled
state refers to links for which RSTP has been disabled. The Link Down state refers to links for which
RSTP is enabled but are currently down.

Role
There are four RSTP port roles: Root, Designated, Alternate and Backup. If the bridge is not the root bridge, it must
have a single Root Port. The Root Port is the "best” (i.e. quickest) way to send traffic to the root bridge.

162 RSTP States and Roles


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

A port is marked as Designated if it is the best port to serve the LAN segment it is connected to. All bridges on the
same LAN segment listen to each others’ messages and agree on which bridge is the Designated Bridge. The ports
of other bridges on the segment must become either Root, Alternate or Backup ports.

1
C 3
1 2
3 3

4 4

1 1
2 2

2 3 2
5 6 3

Figure 95: Bridge and Port Roles


1. Root Bridge    2. Designated Bridge    3. Designated Port    4. Root Port    5. Alternate Port    6. Backup Port

A port is alternate when it receives a better message from another bridge on the LAN segment it is connected to.
The message that an Alternate Port receives is better than the port itself would generate, but not good enough to
convince it to become the Root Port. The port becomes the alternate to the current Root Port and will become the
new Root Port should the current Root Port fail. The Alternate Port does not participate in the network.
A port is a Backup Port when it receives a better message from the LAN segment it is connected to, originating
from another port on the same bridge. The port is a backup for another port on the bridge and will become active
if that port fails. The Backup Port does not participate in the network.

Section 5.2.1.2
Edge Ports
A port may be designated as an Edge Port if it is directly connected to an end station. As such, it cannot create
bridging loops in the network and can thus directly transition to forwarding, skipping the listening and learning
stages.
Edge ports that receive configuration messages immediately lose their Edge Port status and become normal
spanning tree ports. A loop created on an improperly connected edge port is thus quickly repaired.
Because an Edge Port services only end stations, topology change messages are not generated when its link
toggles.

Edge Ports 163


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Section 5.2.1.3
Point-to-Point and Multipoint Links
RSTP uses a peer-peer protocol called Proposing-Agreeing to ensure transitioning in the event of a link failure. This
protocol is point-to-point and breaks down in multipoint situations, i.e. when more than two bridges operate on a
shared media link.
If RSTP detects this circumstance (based upon the port’s half duplex state after link up) it will switch off Proposing-
Agreeing. The port must transition through the learning and forwarding states, spending one forward delay in
each state.
There are circumstances in which RSTP will make an incorrect decision about the point-to-point state of the link
simply by examining the half-duplex status, namely:
• The port attaches only to a single partner, but through a half-duplex link.
• The port attaches to a shared media hub through a full-duplex link. The shared media link attaches to more than
one RSTP enabled bridge.
In such cases, the user may configure the bridge to override the half-duplex determination mechanism and force
the link to be treated in the proper fashion.

Section 5.2.1.4
Path and Port Costs
The STP path cost is the main metric by which root and designated ports are chosen. The path cost for a
designated bridge is the sum of the individual port costs of the links between the root bridge and that designated
bridge. The port with the lowest path cost is the best route to the root bridge and is chosen as the root port.

NOTE
In actuality the primary determinant for root port selection is the root bridge ID. Bridge ID is important
mainly at network startup when the bridge with the lowest ID is elected as the root bridge. After
startup (when all bridges agree on the root bridge’s ID) the path cost is used to select root ports. If the
path costs of candidates for the root port are the same, the ID of the peer bridge is used to select the
port. Finally, if candidate root ports have the same path cost and peer bridge ID, the port ID of the peer
bridge is used to select the root port. In all cases the lower ID, path cost or port ID is selected as the
best.

How Port Costs Are Generated


Port costs can be generated either as a result of link auto-negotiation or manual configuration. When the link
auto-negotiation method is used, the port cost is derived from the speed of the link. This method is useful when
a well-connected network has been established. It can be used when the designer is not too concerned with the
resultant topology as long as connectivity is assured.
Manual configuration is useful when the exact topology of the network must be predictable under all
circumstances. The path cost can be used to establish the topology of the network exactly as the designer intends.

STP vs. RSTP Costs


The IEEE 802.1D-1998 specification limits port costs to values of 1 to 65536. Designed at a time when 9600 bps
links were state of the art, this method breaks down in modern use, as the method cannot represent a link speed
higher than 10 gigabits per second.

164 Point-to-Point and Multipoint Links


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

To remedy this problem in future applications, the IEEE 802.1w specification limits port costs to values of 1 to
20000000, and a link speed up to 10 Tb per second can be represented with a value of 2.
RUGGEDCOM bridges support interoperability with legacy STP bridges by selecting the style to use. In practice,
it makes no difference which style is used as long as it is applied consistently across the network, or if costs are
manually assigned.

Section 5.2.1.5
Bridge Diameter
The bridge diameter is the maximum number of bridges between any two possible points of attachment of end
stations to the network.
The bridge diameter reflects the realization that topology information requires time to propagate hop by hop
through a network. If configuration messages take too long to propagate end to end through the network, the
result will be an unstable network.
There is a relationship between the bridge diameter and the maximum age parameter. To achieve extended ring
sizes, Siemens eRSTP™ uses an age increment of ¼ of a second. The value of the maximum bridge diameter is thus
four times the configured maximum age parameter.

NOTE
The RSTP algorithm is as follows:
• STP configuration messages contain age information.
• Messages transmitted by the root bridge have an age of 0. As each subsequent designated bridge
transmits the configuration message it must increase the age by at least 1 second.
• When the age exceeds the value of the maximum age parameter the next bridge to receive the
message immediately discards it.

IMPORTANT!
Raise the value of the maximum age parameter if implementing very large bridged networks or rings.

Section 5.2.1.6
eRSTP
Siemens's enhanced Rapid Spanning Tree Protocol (eRSTP) improves the performance of RSTP in two ways:
• Improves the fault recovery time performance (< 5 ms per hop)
• Improves performance for large ring network topologies (up to 80 switches)
eRSTP is also compatible with standard RSTP for interoperability with commercial switches.
For example, in a network comprised of 15 RUGGEDCOM hardened Ethernet switches in a ring topology, the
expected fault recovery time would be less than 75 ms (i.e. 5 ms x 15). However, with eRSTP, the worst case fault
recovery time is less than 26 ms.

Bridge Diameter 165


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Section 5.2.1.7
Fast Root Failover
Siemens’s Fast Root Failover feature is an enhancement to RSTP that may be enabled or disabled. Fast Root
Failover improves upon RSTP’s handling of root bridge failures in mesh-connected networks.

IMPORTANT!
In networks mixing RUGGEDCOM and non-RUGGEDCOM switches, or in those mixing Fast Root Failover
algorithms, RSTP Fast Root Failover will not function properly and root bridge failure will result in an
unpredictable failover time. To avoid potential issues, note the following:
• When using the Robust algorithm, all switches must be RUGGEDCOM switches
• When using the Relaxed algorithm, all switches must be RUGGEDCOM switches, with the exception
of the root switch
• All RUGGEDCOM switches in the network must use the same Fast Root Failover algorithm

Two Fast Root Failover algorithms are available:


• Robust – Guarantees a deterministic root failover time, but requires support from all switches in the network,
including the root switch
• Relaxed – Ensures a deterministic root failover time in most network configurations, but allows the use of a
standard bridge in the root role

NOTE
The minimum interval for root failures is one second. Multiple, near simultaneous root failures (within
less than one second of each other) are not supported by Fast Root Failover.

Fast Root Failover and RSTP Performance


• Running RSTP with Fast Root Failover disabled has no impact on RSTP performance in ring-connected networks.
• Fast Root Failover has no effect on RSTP performance in the case of failures that do not involve the root bridge
or one of its links.
• The extra processing introduced by Fast Root Failover significantly decreases the worst-case failover time due to
root bridge failure in mesh networks.

Recommendations On the Use of Fast Root Failover


• It is not recommended to enable Fast Root Failover in single ring network topologies.
• It is strongly recommended to always connect the root bridge to each of its neighbor bridges using more than
one link when enabled in ring-connected networks.

Section 5.2.2

RSTP Applications
The following section describes various applications of RSTP.

CONTENTS
• Section 5.2.2.1, “RSTP in Structured Wiring Configurations”

166 Fast Root Failover


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

• Section 5.2.2.2, “RSTP in Ring Backbone Configurations”


• Section 5.2.2.3, “RSTP Port Redundancy”

Section 5.2.2.1
RSTP in Structured Wiring Configurations
RSTP may be used to construct structured wiring systems where connectivity is maintained in the event of link
failures. For example, a single link failure of any link between A and N in Figure 96 would leave all the ports of
bridges 555 through 888 connected to the network.

1 A 1
111 222
2 B 2
4 3 4 3

C F

D E

1 2 1 2

444 444
6 3 6 3
5 4 5 4

G I H K J M L N

1 2 1 2 1 2 1 2

555 666 777 888

4 3 4 3 4 3 4 3

Figure 96: Example - Structured Wiring Configuration

To design a structured wiring configuration, do the following:


1. Select the design parameters for the network.
What are the requirements for robustness and network failover/recovery times? Are there any special
requirements for diverse routing to a central host computer? Are there any special port redundancy
requirements?

RSTP in Structured Wiring Configurations 167


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

2. Identify required legacy support.


Are STP bridges used in the network? These bridges do not support rapid transitioning to forwarding. If these
bridges are present, can they be re-deployed closer to the network edge?
3. Identify edge ports and ports with half-duplex/shared media restrictions.
Ports that connect to host computers, Intelligent Electronic Devices (IEDs) and controllers may be set to edge
ports in order to guarantee rapid transitioning to forwarding as well as to reduce the number of topology
change notifications in the network. Ports with half-duplex/shared media restrictions require special attention
in order to guarantee that they do not cause extended fail-over/recovery times.
4. Choose the root bridge and backup root bridge carefully.
The root bridge should be selected to be at the concentration point of network traffic. Locate the backup root
bridge adjacent to the root bridge. One strategy that may be used is to tune the bridge priority to establish
the root bridge and then tune each bridge’s priority to correspond to its distance from the root bridge.
5. Identify desired steady state topology.
Identify the desired steady state topology taking into account link speeds, offered traffic and QOS. Examine of
the effects of breaking selected links, taking into account network loading and the quality of alternate links.
6. Decide upon a port cost calculation strategy.
Select whether fixed or auto-negotiated costs should be used? It is recommended to use the auto-negotiated
cost style, unless it is necessary for the network design to change the auto-negotiated cost style. Select
whether the STP or RSTP cost style should be used. Make sure to configure the same cost style on all devices
on the network.
7. Enable RSTP Fast Root Failover option.
This is a proprietary feature of Siemens. In a mesh network with only RUGGEDCOM devices in the core of the
network, it is recommended to enable the RSTP Fast Root Failover option to minimize the network downtime
in the event of a Root bridge failure.
8. Calculate and configure priorities and costs.
9. Implement the network and test under load.

Section 5.2.2.2
RSTP in Ring Backbone Configurations
RSTP may be used in ring backbone configurations where rapid recovery from link failure is required. In normal
operation, RSTP will block traffic on one of the links, for example, as indicated by the double bars through link H in
Figure 97 . In the event of a failure on link D, bridge 444 will unblock link H. Bridge 333 will communicate with the
network through link F.

168 RSTP in Ring Backbone Configurations


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

A 1
111 222
B 1 2 C

3 3

L D

1
K 3
666 333
2 E
2 3

J F

1 1
I 3 2 H 3
555 444
2 G

Figure 97: Example - Ring Backbone Configuration

To design a ring backbone configuration with RSTP, do the following:


1. Select the design parameters for the network.
What are the requirements for robustness and network fail-over/recovery times? Typically, ring backbones are
chosen to provide cost effective but robust network designs.
2. Identify required legacy support and ports with half-duplex/shared media restrictions.
These bridges should not be used if network fail-over/recovery times are to be minimized.
3. Identify edge ports.
Ports that connect to host computers, Intelligent Electronic Devices (IEDs) and controllers may be set to edge
ports in order to guarantee rapid transitioning to forwarding as well as to reduce the number of topology
change notifications in the network.
4. Choose the root bridge.
The root bridge can be selected to equalize either the number of bridges, number of stations or amount of
traffic on either of its legs. It is important to realize that the ring will always be broken in one spot and that
traffic always flows through the root.

RSTP in Ring Backbone Configurations 169


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

5. Assign bridge priorities to the ring.


The strategy that should be used is to assign each bridge’s priority to correspond to its distance from the root
bridge. If the root bridge is assigned the lowest priority of 0, the bridges on either side should use a priority
of 4096 and the next bridges 8192 and so on. As there are 16 levels of bridge priority available, this method
provides for up to 31 bridges in the ring.
6. Decide upon a port cost calculation strategy.
It is recommended to use the auto-negotiated cost style, unless it is necessary for the network design to
change the auto-negotiated cost style. Select whether the STP or RSTP cost style should be used. Make sure to
configure the same cost style on all devices on the network.
7. Disable RSTP Fast Root Failover option.
This is a proprietary feature of Siemens. In RUGGEDCOM ROS, the RSTP Fast Root Failover option is enabled by
default. It is recommended to disable this feature when operating in a Ring network.
8. Implement the network and test under load.

Section 5.2.2.3
RSTP Port Redundancy
In cases where port redundancy is essential, RSTP allows more than one bridge port to service a LAN. In the
following example, if port 3 is designated to carry the network traffic of LAN A, port 4 will block traffic. Should an
interface failure occur on port 3, port 4 will assume control of the LAN.

1 2

4 3

Figure 98: Example - Port Redundancy

Section 5.2.3

MSTP Operation
The Multiple Spanning Tree (MST) algorithm and protocol provide greater control and flexibility than RSTP and
legacy STP. MSTP (Multiple Spanning Tree Protocol) is an extension of RSTP, whereby multiple spanning trees may
be maintained on the same bridged network. Data traffic is allocated to one or another of several spanning trees
by mapping one or more VLANs onto the network.
The sophistication and utility of the Multiple Spanning Tree implementation on a given bridged network is
proportional to the amount of planning and design invested in configuring MSTP.
If MSTP is activated on some or all of the bridges in a network with no additional configuration, the result will be a
fully and simply connected network, but at best, the result will be the same as a network using only RSTP. Taking
full advantage of the features offered by MSTP requires a potentially large number of configuration variables

170 RSTP Port Redundancy


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

to be derived from an analysis of data traffic on the bridged network, and from requirements for load sharing,
redundancy, and path optimization. Once these parameters have all been derived, it is also critical that they are
consistently applied and managed across all bridges in an MST region.
By design, MSTP processing time is proportional to the number of active STP instances. This means that MSTP will
likely be significantly slower than RSTP. Therefore, for mission critical applications, RSTP should be considered a
better network redundancy solution than MSTP.

CONTENTS
• Section 5.2.3.1, “MSTP Regions and Interoperability”
• Section 5.2.3.2, “MSTP Bridge and Port Roles”
• Section 5.2.3.3, “Benefits of MSTP”
• Section 5.2.3.4, “Implementing MSTP on a Bridged Network”

Section 5.2.3.1
MSTP Regions and Interoperability
In addition to supporting multiple spanning trees in a network of MSTP-capable bridges, MSTP is capable of inter-
operating with bridges that support only RSTP or legacy STP, without requiring any special configuration.
An MST region may be defined as the set of interconnected bridges whose MST Region Identification is identical.
The interface between MSTP bridges and non-MSTP bridges, or between MSTP bridges with different MST Region
Identification information, becomes part of an MST Region boundary.
Bridges outside an MST region will see the entire region as though it were a single (R)STP bridge; the internal
detail of the MST region is hidden from the rest of the bridged network. In support of this, MSTP maintains
separate hop counters for spanning tree information exchanged at the MST region boundary versus that
propagated inside the region. For information received at the MST region boundary, the (R)STP Message Age is
incremented only once. Inside the region, a separate Remaining Hop Count is maintained, one for each spanning
tree instance. The external Message Age parameter is referred to the (R)STP Maximum Age Time, whereas the
internal Remaining Hop Counts are compared to an MST region-wide Maximum Hops parameter.

MSTI
An MSTI (Multiple Spanning Tree Instance) is one of sixteen independent spanning tree instances that may be
defined in an MST region (not including the IST – see below). An MSTI is created by mapping a set of VLANs (in
RUGGEDCOM ROS, via the VLAN configuration) to a given MSTI ID. The same mapping must be configured on all
bridges that are intended to be part of the MSTI. Moreover, all VLAN to MSTI mappings must be identical for all
bridges in an MST region.
RUGGEDCOM ROS supports 16 MSTIs in addition to the IST.
Each MSTI has a topology that is independent of every other. Data traffic originating from the same source and
bound to the same destination but on different VLANs on different MSTIs may therefore travel a different path
across the network.

IST
An MST region always defines an IST (Internal Spanning Tree). The IST spans the entire MST region, and carries all
data traffic that is not specifically allocated (by VLAN) to a specific MSTI. The IST is always computed and is defined
to be MSTI zero.

MSTP Regions and Interoperability 171


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

The IST is also the extension inside the MST region of the CIST (see below), which spans the entire bridged
network, inside and outside of the MST region and all other RSTP and STP bridges, as well as any other MST
regions.

CST
The CST (Common Spanning Tree) spans the entire bridged network, including MST regions and any connected
STP or RSTP bridges. An MST region is seen by the CST as an individual bridge, with a single cost associated with its
traversal.

CIST
The CIST (Common and Internal Spanning Tree) is the union of the CST and the ISTs in all MST regions. The CIST
therefore spans the entire bridged network, reaching into each MST region via the latter’s IST to reach every
bridge on the network.

Section 5.2.3.2
MSTP Bridge and Port Roles
MSTP supports the following bridge and port roles:

Bridge Roles
Role Description

CIST Root The CIST Root is the elected root bridge of the CIST (Common and
Internal Spanning Tree), which spans all connected STP and RSTP
bridges and MSTP regions.

CIST Regional Root The root bridge of the IST within an MSTP region. The CIST Regional
Root is the bridge within an MSTP region with the lowest cost path
to the CIST Root. Note that the CIST Regional Root will be at the
boundary of an MSTP region. Note also that it is possible for the CIST
Regional Root to be the CIST Root.

MSTI Regional Root The root bridge for an MSTI within an MSTP region. A root bridge is
independently elected for each MSTI in an MSTP region.

Port Roles
Each port on an MSTP bridge may have more than one CIST role depending on the number and topology of
spanning tree instances defined on the port.
Role Description

CIST Port Roles • The Root Port provides the minimum cost path from the bridge
to the CIST Root via the CIST Regional Root. If the bridge itself
happens to be the CIST Regional Root, the Root Port is also the
Master Port for all MSTIs, and provides the minimum cost path to a
CIST Root located outside the region.
• A Designated Port provides the minimum cost path from an
attached LAN, via the bridge to the CIST Regional Root.

172 MSTP Bridge and Port Roles


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Role Description
• Alternate and Backup Ports function the same as they do in RSTP,
but relative to the CIST Regional Root.

MSTI Port Roles For each MSTI on a bridge:


• The Root Port provides the minimum cost path from the bridge to
the MSTI Regional Root, if the bridge itself is not the MSTI Regional
Root.
• A Designated Port provides the minimum cost path from an
attached LAN, via the bridge to the MSTI Regional Root.
• Alternate and Backup Ports function the same as they do in RSTP,
but relative to the MSTI Regional Root.
The Master Port, which is unique in an MSTP region, is the CIST Root
Port of the CIST Regional Root, and provides the minimum cost path
to the CIST Root for all MSTIs.

Boundary Ports A Boundary Port is a port on a bridge in an MSTP region that


connects to either: a bridge belonging to a different MSTP region, or
a bridge supporting only RSTP or legacy STP. A Boundary Port blocks
or forwards all VLANs from all MSTIs and the CIST alike.
A Boundary Port may be:
• The CIST Root Port of the CIST Regional Root (and therefore also
the MSTI Master Port).
• A CIST Designated Port, CIST Alternate/Backup Port, or Disabled. At
the MSTP region boundary, the MSTI Port Role is the same as the
CIST Port Role.
A Boundary Port connected to an STP bridge will send only STP
BPDUs. One connected to an RSTP bridge need not refrain from
sending MSTP BPDUs. This is made possible by the fact that the MSTP
carries the CIST Regional Root Identifier in the field that RSTP parses
as the Designated Bridge Identifier.

Section 5.2.3.3
Benefits of MSTP
Despite the fact that MSTP is configured by default to arrive automatically at a spanning tree solution for each
configured MSTI, advantages may be gained from influencing the topology of MSTIs in an MST region. The fact
that the Bridge Priority and each port cost are configurable per MST makes it possible to control the topology of
each MSTI within a region.

Load Balancing
MSTP can be used to balance data traffic load among sets of VLANs, enabling more complete utilization of a
multiply interconnected bridged network.
A bridged network controlled by a single spanning tree will block redundant links by design, in order to avoid
harmful loops. Using MSTP, however, any given link may have a different blocking state for MSTI, as maintained
by MSTP. Any given link, therefore, might be in blocking state for some VLANs, and in forwarding state for other
VLANs, depending on the mapping of VLANs to MSTIs.
It is possible to control the spanning tree solution for each MSTI, especially the set of active links for each tree,
by manipulating, per MSTI, the bridge priority and the port costs of links in the network. If traffic is allocated
judiciously to multiple VLANs, redundant interconnections in a bridged network which, using a single spanning
tree, would have gone unused, can now be made to carry traffic.

Benefits of MSTP 173


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Isolation of Spanning Tree Reconfiguration.


A link failure in an MSTP region that does not affect the roles of Boundary ports will not cause the CST to be
reconfigured, nor will the change affect other MSTP regions. This is due to the fact that MSTP information does
not propagate past a region boundary.

MSTP versus PVST


An advantage of MSTP over the Cisco Systems Inc. proprietary PVST protocol is the ability to map multiple VLANs
onto a single MSTI. Since each spanning tree requires processing and memory, the expense of keeping track of an
increasing number of VLANs increases much more rapidly for PVST than for MSTP.

Compatibility with STP and RSTP


No special configuration is required for the bridges of an MST region to connect fully and simply to non-MST
bridges on the same bridged network. Careful planning and configuration is, however, recommended in order to
arrive at an optimal network.

Section 5.2.3.4
Implementing MSTP on a Bridged Network
It is recommended the configuration of MSTP on a network proceed in the sequence outlined below.
Naturally, it is also recommended that network analysis and planning inform the steps of configuring the VLAN
and MSTP parameters in particular.
Begin with a set of MSTP-capable Ethernet bridges and MSTP disabled. For each bridge in the network:

NOTE
MSTP does not need to be enabled to map a VLAN to an MSTI. However, the mapping must be identical
for each bridge that belongs to the MSTP region.

1. Configure and enable STP globally and/or for specific Ethernet ports. For more information, refer to
Section 5.2.4, “Configuring STP Globally” or Section 5.2.5, “Configuring STP for Specific Ethernet Ports” .

NOTE
Static VLANs must be used in an MSTP configuration. GVRP is not supported.

2. Add static VLANs and map them to MSTIs. For more information, refer to Section 5.1.5.2, “Adding a Static
VLAN” .

NOTE
The Region Identifier and Revision Level must be the same for each bridge in the MST region.

3. Configure the revision level for the MST Region Identifier. For more information, refer to Section 5.2.9.3,
“Configuring the MST Region Identifier” .
4. Make sure the read-only digest for the MST Region Identifier is identical for each bridge in the MST region. If
the digest is different, the set of mappings from VLANs to MSTIs differs.
5. Configure the Bridge Priority for the global MSTI. For more information, refer to Section 5.2.9.4, “Configuring
a Global MSTI” .

174 Implementing MSTP on a Bridged Network


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

6. Configure the Port Cost and Priority per Port for each MSTI. For more information, refer to Section 5.2.9.5,
“Configuring an MSTI for an Ethernet Port” .
7. Set the STP Protocol Version to MSTP and enable STP. For more information, refer to Section 5.2.4,
“Configuring STP Globally”

Section 5.2.4

Configuring STP Globally


To configure global settings for the Spanning Tree Protocol (STP), do the following:
1. Navigate to Spanning Tree » Configure Bridge RSTP Parameters . The Bridge RSTP Parameters form
appears.

9 10

Figure 99: Bridge RSTP Parameters Form


1. State Options    2. Version Support List    3. Bridge Priority List    4. Hello Time Box    5. Max Age Time Box    6. Transmit Count
Box    7. Forward Delay Box    8. Max Hops Box    9. Apply Button    10. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

State Synopsis:   { Disabled, Enabled }


Default:   Enabled
Enable STP/RSTP/MSTP for the bridge globally. Note that STP/RSTP/
MSTP is enabled on a port when it is enabled globally and along
with enabling per port setting.

Version Support Synopsis:   { STP, RSTP, MSTP }


Default:   RSTP
Selects the version of Spanning Tree Protocol to support, either
only STP or Rapid STP or Multiple STP.

Bridge Priority Synopsis:   { 0, 4096, 8192, 12288, 16384, 20480, 24576,


28672, 32768, 36864, 40960, 45056, 49152, 53248, 57344,
61440 }
Default:   32768

Configuring STP Globally 175


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description
Bridge Priority provides a way to control the topology of the STP
connected network. The desired Root and Designated bridges
can be configured for a particular topology. The bridge with the
lowest priority will become root. In the event of a failure of the
root bridge, the bridge with the next lowest priority will then
become root. Designated bridges that (for redundancy purposes)
service a common LAN also use priority to determine which
bridge is active. In this way careful selection of Bridge Priorities
can establish the path of traffic flows in normal and abnormal
conditions.

Hello Time Synopsis:   1 to 10 s


Default:   2 s
Time between configuration messages issued by the root bridge.
Shorter hello times result in faster detection of topology changes
at the expense of moderate increases in STP traffic.

Max Age Time Synopsis:   6 to 40 s


Default:   20 s
The time for which a configuration message remains valid after
being issued by the root bridge. Configure this parameter with
care when many tiers of bridges exist, or slow speed links (such as
those used in WANs) are part of the network

Transmit Count Synopsis:   3 to 100 or { Unlimited }


Default:   Unlimited
Maximum number of BPDUs on each port that may be sent in one
second. Larger values allow the network to recover from failed
links/bridges more quickly.

Forward Delay Synopsis:   4 to 30 s


Default:   15 s
The amount of time a bridge spends learning MAC addresses on a
rising port before beginning to forward traffic. Lower values allow
the port to reach the forwarding state more quickly, but at the
expense of flooding unlearned addresses to all ports.

Max Hops Synopsis:   6 to 40


Default:   20
Only applicable to MSTP. The maximum possible bridge diameter
inside an MST region.
MSTP BPDUs propagating inside an MST region specify a time-
to-live that is decremented by every switch that propagates the
BPDU. If the maximum number of hops inside the region exceeds
the configured maximum, BPDUs may be discarded due to their
time-to-live setting.

3. Click Apply.

Section 5.2.5

Configuring STP for Specific Ethernet Ports


To configure the Spanning Tree Protocol (STP) for a specific Ethernet port, do the following:
1. Navigate to Spanning Tree » Configure Port RSTP Parameters . The Port RSTP Parameters table appears.

176 Configuring STP for Specific Ethernet Ports


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Figure 100: Port RSTP Parameters Table

2. Select an Ethernet port. The Port RSTP Parameters form appears.

10 8

11

Figure 101: Port RSTP Parameters Form


1. Port(s) Box    2. Enabled Options    3. Priority List    4. STP Cost Box    5. RSTP Cost Box    6. Edge Port List    7. Point to Point List   
8. Restricted Role Box    9. Restricted TCN Box    10. Apply Button    11. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Port(s) Synopsis:   Any combination of numbers valid for this parameter


The port number as seen on the front plate silkscreen of the
switch (or a list of ports, if aggregated in a port trunk).

Enabled Synopsis:   { Disabled, Enabled }


Default:   Enabled
Enabling STP activates the STP or RSTP protocol for this port per
the configuration in the STP Configuration menu. STP may be
disabled for the port ONLY if the port does not attach to an STP
enabled bridge in any way. Failure to meet this requirement WILL
result in an undetectable traffic loop in the network. A better
alternative to disabling the port is to leave STP enabled but to
configure the port as an edge port. A good candidate for disabling
STP would be a port that services only a single host computer.

Configuring STP for Specific Ethernet Ports 177


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description

Priority Synopsis:   { 0, 16, 32, 48, 64, 80, 96, 112, 128, 144, 160, 176,
194, 208, 224, 240 }
Default:   128
Selects the STP port priority. Ports of the same cost that attach to
a common LAN will select the port to be used based upon the port
priority.

STP Cost Synopsis:   0 to 65535 or { Auto }


Default:   Auto
Selects the cost to use in cost calculations, when the Cost
Style parameter is set to STP in the Bridge RSTP Parameters
configuration. Setting the cost manually provides the ability to
preferentially select specific ports to carry traffic over others.
Leave this field set to "auto" to use the standard STP port costs as
negotiated (4 for 1Gbps, 19 for 100 Mbps links and 100 for 10
Mbps links).
For MSTP, this parameter applies to both external and internal
path cost.

RSTP Cost Synopsis:   0 to 2147483647 or { Auto }


Default:   Auto
Selects the cost to use in cost calculations, when the Cost
Style parameter is set to RSTP in the Bridge RSTP Parameters
configuration. Setting the cost manually provides the ability to
preferentially select specific ports to carry traffic over others.
Leave this field set to "auto" to use the standard RSTP port costs
as negotiated (20,000 for 1Gbps, 200,000 for 100 Mbps links and
2,000,000 for 10 Mbps links).
For MSTP, this parameter applies to both external and internal
path cost.

Edge Port Synopsis:   { False, True, Auto }


Default:   Auto
Edge ports are ports that do not participate in the Spanning
Tree, but still send configuration messages. Edge ports transition
directly to frame forwarding without any listening and learning
delays. The MAC tables of Edge ports do not need to be flushed
when topology changes occur in the STP network. Unlike an STP
disabled port, accidentally connecting an edge port to another
port in the spanning tree will result in a detectable loop. The
"Edgeness" of the port will be switched off and the standard RSTP
rules will apply (until the next link outage).

Point to Point Synopsis:   { False, True, Auto }


Default:   Auto
RSTP uses a peer-to-peer protocol that provides rapid transitioning
on point-to-point links. This protocol is automatically turned off in
situations where multiple STP bridges communicate over a shared
(non point-to-point) LAN. The bridge will automatically take point-
to-point to be true when the link is found to be operating in full-
duplex mode. The point-to-point parameter allows this behavior
or overrides it, forcing point-to-point to be true or false. Force the
parameter true when the port operates a point-to-point link but
cannot run the link in full-duplex mode. Force the parameter false
when the port operates the link in full-duplex mode, but is still not
point-to-point (e.g. a full-duplex link to an unmanaged bridge that
concentrates two other STP bridges).

Restricted Role Synopsis:   { True or False }


Default:   False
A boolean value set by management. If TRUE, causes the Port
not to be selected as the Root Port for the CIST or any MSTI, even

178 Configuring STP for Specific Ethernet Ports


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description
if it has the best spanning tree priority vector. Such a Port will
be selected as an Alternate Port after the Root Port has been
selected. This parameter should be FALSE by default. If set, it can
cause a lack of spanning tree connectivity. It is set by a network
administrator to prevent bridges that are external to a core
region of the network from influencing the spanning tree active
topology. This may be necessary, for example, if those bridges are
not under the full control of the administrator.

Restricted TCN Synopsis:   { True or False }


Default:   False
A boolean value set by management. If TRUE, it causes the Port
not to propagate received topology change notifications and
topology changes to other Ports. If set, it can cause temporary
loss of connectivity after changes in a spanning tree’s active
topology as a result of persistent, incorrectly learned, station
location information. It is set by a network administrator to
prevent bridges that are external to a core region of the network
from causing address flushing in that region. This may be
necessary, for example, if those bridges are not under the full
control of the administrator or if the MAC_Operational status
parameter for the attached LANs transitions frequently.

4. Click Apply.

Section 5.2.6

Configuring eRSTP
To configure eRSTP, do the following:
1. Navigate to Spanning Tree » Configure eRSTP Parameters . The eRSTP Parameters form appears.

5
6
7

Figure 102: eRSTP Parameters Form


1. Max Network Diameter Options    2. BPDU Guart Timeout Box    3. Fast Root Failover List    4. IEEE802.1w Interoperability Options   
5. Cost Style Options    6. Apply Button    7. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

Max Network Diameter Synopsis:   { MaxAgeTime, 4*MaxAgeTime }


Default:   4*MaxAgeTime
The RSTP standard puts a limit on the maximum network size
that can be controlled by the RSTP protocol. The network size

Configuring eRSTP 179


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description
is described by the term 'maximum network diameter', which
is the number of switches that comprise the longest path that
RSTP BPDUs have to traverse. The standard supported maximum
network diameter is equal to the value of the 'MaxAgeTime' RSTP
configuration parameter.
eRSTP offers an enhancement to RSTP which allows it to cover
networks larger than ones defined by the standard.
This configuration parameter selects the maximum supported
network size.

BPDU Guard Timeout Synopsis:   1 to 86400 s or { Until reset, Don't shutdown }


Default:   Don't shutdown
The RSTP standard does not address network security. RSTP must
process every received BPDU and take an appropriate action.
This opens a way for an attacker to influence RSTP topology by
injecting RSTP BPDUs into the network.
BPDU Guard is a feature that protects the network from BPDUs
received by a port where RSTP capable devices are not expected
to be attached. If a BPDU is received by a port for which 'Edge'
parameter is set to 'TRUE' or RSTP is disabled, the port will be
shutdown for the time period specified by this parameter.
• DON'T SHUTDOWN - BPDU Guard is disabled
• UNTIL RESET - port will remain shutdown until the port reset
command is issued by the user

Fast Root Failover Synopsis:   { On, On with standard root, Off }


Default:   On
In mesh network topologies, the standard RSTP algorithm does
not guarantee deterministic network recovery time in the case of
a root switch failure. Such a recovery time is hard to calculate and
it can be different (and may be relatively long) for any given mesh
topology.
This configuration parameter enables Siemens's enhancement to
RSTP which detects a failure of the root switch and performs some
extra RSTP processing steps, significantly reducing the network
recovery time and making it deterministic.

NOTE
• This feature is only available in RSTP mode. In
MSTP mode, the configuration parameter is
ignored.
• In a single ring topology, this feature is not
needed and should be disabled to avoid longer
network recovery times due to extra RSTP
processing.

The Fast Root Failover algorithm must be supported by all


switches in the network, including the root, to guarantee optimal
performance. However, it is not uncommon to assign the root role
to a switch from a vendor different from the rest of the switches
in the network. In other words, it is possible that the root might
not suport the Fast Root Failover algorithm. In such a scenario,
a "relaxed" algorithm should be used, which tolerates the lack of
support in the root switch.
These are the supported configuration options:
• Off - Fast Root Failover algorithm is disabled and hence a root
switch failure may result in excessive connectivity recovery
time.

180 Configuring eRSTP


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description
• On - Fast Root Failover is enabled and the most robust
algorithm is used, which requires the appropriate support in the
root switch.
• On with standard root - Fast Root Failover is enabled but a
"relaxed" algorithm is used, allowing the use of a standard
switch in the root role.

IEEE802.1w Interoperability Synopsis:   { On, Off }


Default:   On
The original RSTP protocol defined in the IEEE 802.1w standard
has minor differences from more recent, enhanced, standard(s).
Those differences cause interoperability issues which, although
they do not completely break RSTP operation, can lead to a longer
recovery time from failures in the network.
eRSTP offers some enhancements to the protocol which make the
switch fully interoperable with other vendors' switches, which
may be running IEEE 802.2w RSTP. The enhancements do not
affect interoperability with more recent RSTP editions.
This configuration parameter enables the aforementioned
interoperability mode.

Cost Style Synopsis:   { STP (16 bit), RSTP (32 bit) }


Default:   STP (16 bit)
The RSTP standard defines two styles of a path cost value. STP
uses 16-bit path costs based upon 1x10E9/link speed (4 for
1Gbps, 19 for 100 Mbps and 100 for 10 Mbps) whereas RSTP
uses 32-bit costs based upon 2x10E13/link speed (20,000 for
1Gbps, 200,000 for 100 Mbps and 2,000,000 for 10 Mbps).
However, switches from some vendors keep using the STP path
cost style even in RSTP mode, which can cause confusion and
interoperability problems.
This configuration parameter selects the style of link costs to
employ.
Note that RSTP link costs are used only when the bridge version
support is set to allow RSTP and the port does not migrate to STP.

3. Click Apply.

Section 5.2.7

Viewing Global Statistics for STP


To view global statistics for STP, navigate to Spanning Tree » View Bridge RSTP Statistics . The Bridge RSTP
Statistics form appears.

Viewing Global Statistics for STP 181


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

10

11

12

13

14

Figure 103: Bridge RSTP Statistics Form


1. Bridge Status Box    2. Bridge ID Box    3. Root ID Box    4. Root Port Box    5. Root Path Cost Box    6. Configure Hello Time Box   
7. Learned Hello Time Box    8. Configured Forward Delay Box    9. Learned Forward Delay Box    10. Configured Max Age Box    11. Learned
Max Age Box    12. Total Topology Changes Box    13. Time Since Last TC Box    14. Reload Button

This table displays the following information:

Parameter Description

Bridge Status Synopsis:   { , Designated Bridge, Not Designated For Any LAN, Root
Bridge }
Spanning Tree status of the bridge. The status may be root or
designated. This field may show text saying not designated for any
LAN if the bridge is not designated for any of its ports.

Bridge ID Synopsis:   $$ / ##-##-##-##-##-## where $$ is 0 to 65535, ## is 0


to FF
Bridge Identifier of this bridge.

Root ID Synopsis:   $$ / ##-##-##-##-##-## where $$ is 0 to 65535, ## is 0


to FF
Bridge Identifier of the root bridge.

Root Port Synopsis:   1/1 to maximum port number or { <empty string> }


If the bridge is designated, this is the port that provides connectivity
towards the root bridge of the network.

Root Path Cost Synopsis:   0 to 4294967295


Total cost of the path to the root bridge composed of the sum of
the costs of each link in the path. If custom costs have not been
configured. 1Gbps ports will contribute 4, 100 Mbps ports will
contribute 19 and 10 Mbps ports will contribute a cost of 100 to this
figure.
For the CIST instance of MSTP, this is an external root path cost,
which is the cost of the path from the IST root (i.e. regional root)
bridge to the CST root (i.e. network "global" root) bridge.

Configured Hello Time Synopsis:   0 to 65535


The configured Hello time from the Bridge RSTP Parameters menu.

Learned Hello Time Synopsis:   0 to 65535

182 Viewing Global Statistics for STP


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description
The actual Hello time provided by the root bridge as learned in
configuration messages. This time is used in designated bridges.

Configured Forward Delay Synopsis:   0 to 65535


The configured Forward Delay time from the Bridge RSTP Parameters
menu.

Learned Forward Delay Synopsis:   0 to 65535


The actual Forward Delay time provided by the root bridge as
learned in configuration messages. This time is used in designated
bridges.

Configured Max Age Synopsis:   0 to 65535


The configured Maximum Age time from the Bridge RSTP Parameters
menu.

Learned Max Age Synopsis:   0 to 65535


The actual Maximum Age time provided by the root bridge as
learned in configuration messages. This time is used in designated
bridges.

Total Topology Changes Synopsis:   0 to 65535


A count of topology changes in the network, as detected on this
bridge through link failures or as signaled from other bridges.
Excessively high or rapidly increasing counts signal network
problems.

Time since Last TC Synopsis:   DDDD days, HH:MM:SS


The time since the last time a topology change was detected by the
bridge.

Section 5.2.8

Viewing STP Statistics for Ethernet Ports


To view STP statistics for Ethernet ports, navigate to Spanning Tree » View Port RSTP Statistics . The Port RSTP
Statistics table appears.

Figure 104: Port RSTP Statistics Table

This table displays the following information:

Parameter Description

Port(s) Synopsis:   Any combination of numbers valid for this parameter

Viewing STP Statistics for Ethernet Ports 183


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description
The port number as seen on the front plate silkscreen of the switch
(or a list of ports, if aggregated in a port trunk).

Status Synopsis:   { Disabled, Listening, Learning, Forwarding, Blocking,


Link Down, Discarding }
Status of this port in Spanning Tree. This may be one of the
following:
• Disabled - STP is disabled on this port.
• Link Down - STP is enabled on this port but the link is down.
• Discarding - The link is not used in the STP topology but is
standing by.
• Learning - The port is learning MAC addresses in order to prevent
flooding when it begins forwarding traffic.
• Forwarding - The port is forwarding traffic.

Role Synopsis:   { , Root, Designated, Alternate, Backup, Master }


Role of this port in Spanning Tree. This may be one of the following:
• Designated - The port is designated for (i.e. carries traffic towards
the root for) the LAN it is connected to.
• Root - The single port on the bridge, which provides connectivity
towards the root bridge.
• Backup - The port is attached to a LAN that is serviced by another
port on the bridge. It is not used but is standing by.
• Alternate - The port is attached to a bridge that provides
connectivity to the root bridge. It is not used but is standing by.
• Master - Only exists in MSTP. The port is an MST region boundary
port and the single port on the bridge, which provides connectivity
for the Multiple Spanning Tree Instance towards the Common
Spanning Tree root bridge (i.e. this port is the root port for the
Common Spanning Tree Instance).

Cost Synopsis:   0 to 4294967295


Cost offered by this port. If the Bridge RSTP Parameters Cost Style
is set to STP, 1Gbps ports will contribute 4, 100 Mbps ports will
contribute 19 and 10 Mbps ports contribute a cost of 100. If the Cost
Style is set to RSTP, 1Gbps will contribute 20,000, 100 Mbps ports
will contribute a cost of 200,000 and 10 Mbps ports contribute a
cost of 2,000,000. Note that even if the Cost style is set to RSTP, a
port that migrates to STP will have its cost limited to a maximum of
65535.

RX RSTs Synopsis:   0 to 4294967295


The count of RSTP configuration messages received on this port.

TX RSTs Synopsis:   0 to 4294967295


The count of RSTP configuration messages transmitted on this port.

RX Configs Synopsis:   0 to 4294967295


The count of STP configuration messages received on this port.

TX Configs Synopsis:   0 to 4294967295


The count of STP configuration messages transmitted on this port.

RX Tcns Synopsis:   0 to 4294967295


The count of STP topology change notification messages received
on this port. Excessively high or rapidly increasing counts signal
network problems.

TX Tcns Synopsis:   0 to 4294967295

184 Viewing STP Statistics for Ethernet Ports


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description
The count of STP topology change notification messages transmitted
on this port.

Desig Bridge ID Synopsis:   $$ / ##-##-##-##-##-## where $$ is 0 to 65535, ## is 0


to FF
Provided on the root ports of designated bridges, the Bridge
Identifier of the bridge this port is connected to.

operEdge Synopsis:   True or False


The port is operating as an edge port or not.

Section 5.2.9

Managing Multiple Spanning Tree Instances


The following section describes how to configure and manage Multiple Spanning Tree Instances.

CONTENTS
• Section 5.2.9.1, “Viewing Statistics for Global MSTIs”
• Section 5.2.9.2, “Viewing Statistics for Port MSTIs”
• Section 5.2.9.3, “Configuring the MST Region Identifier”
• Section 5.2.9.4, “Configuring a Global MSTI”
• Section 5.2.9.5, “Configuring an MSTI for an Ethernet Port”

Section 5.2.9.1
Viewing Statistics for Global MSTIs
To view statistics for global MSTIs, navigate to Spanning Tree » View Bridge MSTI Statistics . The Bridge MSTI
Statistics form appears.

Managing Multiple Spanning Tree Instances 185


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

1 2

Figure 105: Bridge MSTI Statistics Form


1. Instance Box    2. Get Button    3. Bridge Status Box    4. Bridge ID Box    5. Root ID Box    6. Root Port Box    7. Root Path Cost Box   
8. Total Topology Changes Box    9. Reload Button

This table displays the following information:

Parameter Description

Bridge Status Synopsis:   { , Designated Bridge, Not Designated For Any LAN, Root
Bridge }
Spanning Tree status of the bridge. The status may be root or
designated. This field may show text saying not designated for any
LAN if the bridge is not designated for any of its ports.

Bridge ID Synopsis:   $$ / ##-##-##-##-##-## where $$ is 0 to 65535, ## is 0


to FF
Bridge Identifier of this bridge.

Root ID Synopsis:   $$ / ##-##-##-##-##-## where $$ is 0 to 65535, ## is 0


to FF
Bridge Identifier of the root bridge.

Root Port Synopsis:   1/1 to maximum port number or { <empty string> }


If the bridge is designated, this is the port that provides connectivity
towards the root bridge of the network.

Root Path Cost Synopsis:   0 to 4294967295


Total cost of the path to the root bridge composed of the sum of
the costs of each link in the path. If custom costs have not been
configured. 1Gbps ports will contribute 4, 100 Mbps ports will
contribute 19 and 10 Mbps ports will contribute a cost of 100 to this
figure.
For the CIST instance of MSTP, this is an external root path cost,
which is the cost of the path from the IST root (i.e. regional root)
bridge to the CST root (i.e. network "global" root) bridge.

Total Topology Changes Synopsis:   0 to 65535


A count of topology changes in the network, as detected on this
bridge through link failures or as signaled from other bridges.

186 Viewing Statistics for Global MSTIs


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description
Excessively high or rapidly increasing counts signal network
problems.

Section 5.2.9.2
Viewing Statistics for Port MSTIs
To view statistics for port MSTIs, navigate to Spanning Tree » View Port MSTI Statistics . The Port MSTI
Statistics form appears.

1 2

Figure 106: Port MSTI Statistics Form


1. Instance ID Box    2. Get Button

This table displays the following information:

Parameter Description

Port(s) Synopsis:   Any combination of numbers valid for this parameter


The port number as seen on the front plate silkscreen of the switch
(or a list of ports, if aggregated in a port trunk).

Status Synopsis:   { Disabled, Listening, Learning, Forwarding, Blocking,


Link Down, Discarding }
tatus of this port in Spanning Tree. This may be one of the following:
• Disabled - STP is disabled on this port.
• Link Down - STP is enabled on this port but the link is down.
• Discarding - The link is not used in the STP topology but is
standing by.
• Learning - The port is learning MAC addresses in order to prevent
flooding when it begins forwarding traffic.
• Forwarding - The port is forwarding traffic.

Role Synopsis:   { , Root, Designated, Alternate, Backup, Master }


Role of this port in Spanning Tree. This may be one of the following:
• Designated - The port is designated for (i.e. carries traffic towards
the root for) the LAN it is connected to.
• Root - The single port on the bridge, which provides connectivity
towards the root bridge.
• Backup - The port is attached to a LAN that is serviced by another
port on the bridge. It is not used but is standing by.

Viewing Statistics for Port MSTIs 187


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description
• Alternate - The port is attached to a bridge that provides
connectivity to the root bridge. It is not used but is standing by.
• Master - Only exists in MSTP. The port is an MST region boundary
port and the single port on the bridge, which provides connectivity
for the Multiple Spanning Tree Instance towards the Common
Spanning Tree root bridge (i.e. this port is the root port for the
Common Spanning Tree Instance).

Cost Synopsis:   0 to 4294967295


Cost offered by this port. If the Bridge RSTP Parameters Cost Style
is set to STP, 1Gbps ports will contribute 4, 100 Mbps ports will
contribute 19 and 10 Mbps ports contribute a cost of 100. If the Cost
Style is set to RSTP, 1Gbps will contribute 20,000, 100 Mbps ports
will contribute a cost of 200,000 and 10 Mbps ports contribute a
cost of 2,000,000. Note that even if the Cost style is set to RSTP, a
port that migrates to STP will have its cost limited to a maximum of
65535.

Desig Bridge ID Synopsis:   $$ / ##-##-##-##-##-## where $$ is 0 to 65535, ## is 0


to FF
Provided on the root ports of designated bridges, the Bridge
Identifier of the bridge this port is connected to.

Section 5.2.9.3
Configuring the MST Region Identifier
Configuring the region identifier and revision level puts the MSTP bridge in a defined group. Other bridges that
have the same identifier and revision level are interconnected within this region. For more information, refer to
Section 5.2.3.1, “MSTP Regions and Interoperability” .
To configure the Multiple Spanning Tree (MST) region identifier, do the following:
1. Navigate to Spanning Tree » Configure MST Region Identifier . The MST Region Identifier form appears.

4 5

Figure 107: MST Region Identifier Form


1. Name Box    2. Revision Level Box    3. Digest Box    4. Apply Button    5. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

Name Synopsis:   Any 32 characters


Default:   00-0A-DC-92-00-00

188 Configuring the MST Region Identifier


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description
The name of the MST region. All devices in the same MST region
must have the same region name configured.

Revision Level Synopsis:   0 to 65535


Default:   0
The revision level for MST configuration. Typically, all devices
in the same MST region are configured with the same revision
level. However, different revision levels can be used to create sub-
regions under the same region name.

Digest Synopsis:   Any 32 characters


Default:   0
This is a read-only parameter and should be only used for network
troubleshooting. In order to ensure consistent VLAN-to-instance
mapping, it is necessary for the protocol to be able to exactly
identify the boundaries of the MST regions. For that pupose, the
characteristics of the region are included in BPDUs. There is no
need to propagate the exact VLAN-to-instance mapping in the
BPDUs because switches only need to know whether they are
in the same region as a neighbor. Therefore, only this 16-octet
digest created from the VLAN-to-instance mapping is sent in
BPDUs.

3. Click Apply.

Section 5.2.9.4
Configuring a Global MSTI
To configure a global Multiple Spanning Tree Instance (MSTI) for the Spanning Tree Protocol (STP), do the
following:
1. Navigate to Spanning Tree » Configure Bridge MSTI Parameters . The Bridge MSTI Parameters form
appears.

1 2

4 5

Figure 108: Bridge MSTI Parameters Form


1. Instance ID Box    2. Get Button    3. Bridge Priority List    4. Apply Button    5. Reload Button

2. Under Instance ID, type an ID number for a Multiple Spanning Tree Instance (MSTI) and click GET. The
settings for the MSTI are displayed. Any changes made to the configuration will be applied specifically to this
instance ID.
3. Configure the following parameter(s) as required:

Configuring a Global MSTI 189


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description

Bridge Priority Synopsis:   { 0, 4096, 8192, 12288, 16384, 20480, 24576,


28672, 32768, 36864, 40960, 45056, 49152, 53248, 57344,
61440 }
Default:   32768
Bridge Priority provides a way to control the topology of the STP
connected network. The desired Root and Designated bridges
can be configured for a particular topology. The bridge with the
lowest priority will become root. In the event of a failure of the
root bridge, the bridge with the next lowest priority will then
become root. Designated bridges that (for redundancy purposes)
service a common LAN also use priority to determine which
bridge is active. In this way careful selection of Bridge Priorities
can establish the path of traffic flows in normal and abnormal
conditions.

4. Click Apply.

Section 5.2.9.5
Configuring an MSTI for an Ethernet Port
To configure a Multiple Spanning Tree Instance (MSTI) for an Ethernet port, do the following
1. Navigate to Spanning Tree » Configure Port MSTI Parameters . The Port MSTI Parameters table appears.

Figure 109: Port MSTI Parameters Table

2. Select an Ethernet port. The Port MSTI Parameters form appears.

190 Configuring an MSTI for an Ethernet Port


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

1 2

7 6

Figure 110: Port MSTI Parameters Form


1. Instance ID Box    2. Get Button    3. Port(s) Box    4. Priority List    5. STP Cost Box    6. RSTP Cost Box    7. Apply Button   
8. Reload Button

3. Under Instance ID, type an ID number for a Multiple Spanning Tree Instance (MSTI) and click GET. The
settings for the MSTI are displayed. Any changes made to the configuration will be applied specifically to this
instance ID.
4. Configure the following parameter(s) as required:

Parameter Description

Port(s) Synopsis:   Any combination of numbers valid for this parameter


The port number as seen on the front plate silkscreen of the
switch (or a list of ports, if aggregated in a port trunk).

Priority Synopsis:   { 0, 16, 32, 48, 64, 80, 96, 112, 128, 144, 160, 176,
192, 208, 224, 240 }
Default:   128
Selects the STP port priority. Ports of the same cost that attach to
a common LAN will select the port to be used based upon the port
priority.

STP Cost Synopsis:   0 to 65535 or { Auto }


Default:   Auto
Selects the cost to use in cost calculations, when the Cost
Style parameter is set to STP in the Bridge RSTP Parameters
configuration. Setting the cost manually provides the ability to
preferentially select specific ports to carry traffic over others.
Leave this field set to "auto" to use the standard STP port costs as
negotiated (4 for 1Gbps, 19 for 100 Mbps links and 100 for 10
Mbps links).
For MSTP, this parameter applies to both external and internal
path cost.

RSTP Cost Synopsis:   0 to 2147483647 or { Auto }


Default:   Auto
Selects the cost to use in cost calculations, when the Cost
Style parameter is set to RSTP in the Bridge RSTP Parameters
configuration. Setting the cost manually provides the ability to
preferentially select specific ports to carry traffic over others.
Leave this field set to "auto" to use the standard RSTP port costs
as negotiated (20,000 for 1Gbps, 200,000 for 100 Mbps links and
2,000,000 for 10 Mbps links).

Configuring an MSTI for an Ethernet Port 191


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description
For MSTP, this parameter applies to both external and internal
path cost.

5. Click Apply.

Section 5.2.10

Clearing Spanning Tree Protocol Statistics


To clear all spanning tree protocol statistics, do the following:
1. Navigate to Spanning Tree » Clear Spanning Tree Statistics . The Clear Spanning Tree Statistics form
appears.

Figure 111: Clear Spanning Tree Statistics Form


1. Confirm Button

2. Click Confirm.

Section 5.3

Managing Classes of Service


Classes of Service (CoS) provides the ability to expedite the transmission of certain frames and port traffic over
others. The CoS of a frame can be set to Normal, Medium, High, or Critical. By default, other than the control
frames, RUGGEDCOM ROS enforces Normal CoS for all incoming traffic received without a priority tag.

IMPORTANT!
Use the highest supported CoS with caution, as it is always used by the switch for handling network
management traffic, such as RSTP BPDUs.
If this CoS is used for regular network traffic, upon traffic bursts, it may result in the loss of some
network management frames, which in turn may result in the loss of connectivity over the network.

The process of controlling traffic based on CoS occurs over two phases:
1. Inspection Phase
In the inspection phase, the CoS priority of a received frame is determined from either:
• A specific CoS based upon the source and destination MAC address (as set in the Static MAC Address Table)
• The priority field in the IEEE 802.1Q tags
• The Differentiated Services Code Point (DSCP) component of the Type Of Service (TOS) field in the IP
header, if the frame is IP

192 Clearing Spanning Tree Protocol Statistics


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

• The default CoS for the port


Each frame’s CoS will be determined once the first examined parameter is found in the frame.

NOTE
For information on how to configure the Inspect TOS parameter, refer to Section 5.3.2,
“Configuring Classes of Service for Specific Ethernet Ports” .

The header of each received frame is first examined to determine if the frame is an IP packet and if Inspect
TOS is enabled in RUGGEDCOM ROS. The CoS is determined from the DSCP field.
If the frame is not an IP packet or if Inspect TOS is disabled, the frame is examined to determine if its
destination or source MAC address is found in the Static MAC address table. If it is, the CoS configured for the
static Mac address is used. If neither destination or source MAC address is in the Static MAC Address table, the
frame is then examined for 802.1Q tags and the priority field is mapped to a CoS. If a tag is not present, the
default CoS for the port is used.
After inspection, the frame is forwarded to the egress port for transmission.
2. Forwarding Phase
Once the CoS of the frame is determined, the frame is forwarded to the egress port, where it is collected into
one of the priority queues according to the assigned CoS.
CoS weighting selects the degree of preferential treatment that is attached to different priority queues. The
ratio of the number of higher CoS to lower CoS frames transmitted can be configured. If desired, lower CoS
frames can be transmitted only after all higher CoS frames have been serviced.

CONTENTS
• Section 5.3.1, “Configuring Classes of Service Globally”
• Section 5.3.2, “Configuring Classes of Service for Specific Ethernet Ports”
• Section 5.3.3, “Configuring Priority to CoS Mapping”
• Section 5.3.4, “Configuring DSCP to CoS Mapping”

Section 5.3.1

Configuring Classes of Service Globally


To configure global settings for Classes of Service (CoS), do the following:
1. Navigate to Classes of Service » Configure Global CoS Parameters . The Global CoS Parameters form
appears.

2 3

Figure 112: Global CoS Parameters Form


1. CoS Weighting Options    2. Apply Button    3. Reload Button

Configuring Classes of Service Globally 193


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

2. Configure the following parameter(s) as required:

Parameter Description

CoS Weighting Synopsis:   { 8:4:2:1, Strict }


Default:   8:4:2:1
During traffic bursts, frames queued in the switch pending
transmission on a port may have different CoS priorities. This
parameter specifies weighting algorithm for transmitting different
priority CoS frames.
Examples:
• 8:4:2:1 - 8 Critical, 4 High, 2 Medium and 1 Normal priority CoS
frame
• Strict - lower priority CoS frames will be only transmitted after
all higher priority CoS frames have been transmitted

3. Click Apply.
4. If necessary, configure CoS mapping based on either the IEEE 802.1p priority or Differentiated Services (DS)
field set in the IP header for each packet. For more information, refer to Section 5.3.3, “Configuring Priority to
CoS Mapping” or Section 5.3.4, “Configuring DSCP to CoS Mapping” .

Section 5.3.2

Configuring Classes of Service for Specific Ethernet Ports


To configure Classes of Service (CoS) for one or more Ethernet ports, do the following:
1. Navigate to Classes of Service » Configure Port CoS Parameters . The Port CoS Parameters table appears.

Figure 113: Port CoS Parameters Table

2. Select an Ethernet port. The Port CoS Parameters form appears.

194 Configuring Classes of Service for Specific Ethernet Ports


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

4 5

Figure 114: Port CoS Parameters Form


1. Port(s) Box    2. Default Pri Box    3. Inspect TOS Options    4. Apply Button    5. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Port(s) Synopsis:   Any combination of numbers valid for this parameter


The port number as seen on the front plate silkscreen of the
switch (or a list of ports, if aggregated in a port trunk).

Default Pri Synopsis:   0 to 7


Default:   0
This parameter allows to prioritize frames received on this port
that are not prioritized based on the frames contents (e.g. priority
field in the VLAN tag, DiffServ field in the IP header, prioritized
MAC address).

Inspect TOS Synopsis:   { No, Yes }


Default:   No
This parameters enables or disables parsing of the Type-Of-Service
(TOS) field in the IP header of the received frames to determine
what Class of Service they should be assigned. When TOS parsing
is enabled the switch will use the Differentiated Services bits in
the TOS field.

4. Click Apply.

Section 5.3.3

Configuring Priority to CoS Mapping


Frames received untagged can be automatically assigned a CoS based on their priority level.
To map a priority level to a CoS, do the following:
1. Navigate to Classes of Service » Configure Priority to CoS Mapping . The Priority to CoS Mapping table
appears.

Configuring Priority to CoS Mapping 195


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Figure 115: Priority to CoS Mapping Table

2. Select a priority level. The Priority to CoS Mapping form appears.

3 4

Figure 116: Priority to CoS Mapping Form


1. Priority Box    2. CoS List    3. Apply Button    4. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Priority Synopsis:   0 to 7
Default:   0
Value of the IEEE 802.1p priority.

CoS Synopsis:   { Normal, Medium, High, Crit }


Default:   Normal
CoS assigned to received tagged frames with the specified IEEE
802.1p priority value.

4. Click Apply.

Section 5.3.4

Configuring DSCP to CoS Mapping


Mapping CoS to the Differentiated Services (DS) field set in the IP header for each packet is done by defining
Differentiated Services Code Points (DSCPs) in the CoS configuration.
To map a DSCP to a Class of Service, do the following:

196 Configuring DSCP to CoS Mapping


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

1. Navigate to Classes of Service » Configure DSCP to CoS Mapping . The DSCP to CoS Mapping table
appears.

Figure 117: DSCP to CoS Mapping Table

2. Select a DSCP level. The DSCP to CoS Mapping form appears.

3 4

Figure 118: DSCP to CoS Mapping Form


1. DSCP Box    2. Priority Box    3. Apply Button    4. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

DSCP Synopsis:   0 to 63
Default:   0
Differentiated Services Code Point (DSCP) - a value of the 6 bit
DiffServ field in the Type-Of-Service (TOS) field of the IP header.

Priority Synopsis:   0 to 7
Default:   0
Priority assigned to received frames with the specified DSCP.

4. Click Apply.
5. Configure the CoS parameters on select switched Ethernet ports as needed. For more information, refer to
Section 5.3.2, “Configuring Classes of Service for Specific Ethernet Ports” .

Configuring DSCP to CoS Mapping 197


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Section 5.4

Managing MAC Addresses


The following section describes how to configure and manage MAC addresses.

CONTENTS
• Section 5.4.1, “Viewing a List of MAC Addresses”
• Section 5.4.2, “Configuring MAC Address Learning Options”
• Section 5.4.3, “Configuring MAC Address Flooding Options”
• Section 5.4.4, “Managing Static MAC Addresses”
• Section 5.4.5, “Purging All Dynamic MAC Addresses”

Section 5.4.1

Viewing a List of MAC Addresses


To view a list of all static and dynamically learned MAC addresses, navigate to MAC Address Tables » View MAC
Addresses . The MAC Addresses table appears.

Figure 119: MAC Address Table

If a MAC address is not listed, do the following:


• Configure the MAC address learning options to control the aging time of dynamically learned MAC addresses of
other devices on the network. For more information, refer to Section 5.4.2, “Configuring MAC Address Learning
Options” .
• Configure the address on the device as a static MAC address. For more information, refer to Section 5.4.4.2,
“Adding a Static MAC Address” .

198 Managing MAC Addresses


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Section 5.4.2

Configuring MAC Address Learning Options


The MAC address learning options control how and when MAC addresses are removed automatically from the
MAC address table. Individual addressees are removed when the aging timer is exceeded. Addresses can also be
removed when a link failure or topology change occurs.
To configure the MAC address learning options, do the following:
1. Navigate to MAC Address Tables » Configure MAC Address Learning Options . The MAC Address
Learning Options form appears.

3 4

Figure 120: MAC Address Learning Options Form


1. Aging Time Box    2. Age Upon Link Loss Options    3. Apply Button    4. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

Aging Time Synopsis:   15 to 800


Default:   300 s
This parameter configures the time that a learned MAC address is
held before being aged out.

Age Upon Link Loss Synopsis:   { No, Yes }


Default:   Yes
When set to Yes, all MAC addresses learned on a failed port will be
aged-out immediately upon link failure detection.
When link failure occurs the switch may have some MAC
addresses previously learned on the failed port. As long as those
addresses are not aged-out the switch will still be forwarding
traffic to that port, thus preventing that traffic from reaching its
destination via the new network topology.
Note that when a network redundancy protocol, e.g. RSTP/MSTP,
is enabled on the switch, that redundancy protocol may, upon
a link failure, flush MAC addresses learned on the failed port
regardless of the setting of this parameter.

3. Click Apply.

Section 5.4.3

Configuring MAC Address Flooding Options


To configure the MAC address flooding options, do the following:

Configuring MAC Address Learning Options 199


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

1. Navigate to MAC Address Tables » Configure MAC Address Flooding Options . The Flooding Options
table appears.

Figure 121: Flooding Options Table

2. Select a port. The Flooding Options form appears.

3 4

Figure 122: Flooding Options Form


1. Port(s) Box    2. Flood Unknown Unicast Options    3. Apply Button    4. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Port(s) Synopsis:   Comma-separated list of ports


The port number as seen on the front plate silkscreen of the
switch (or a list of ports, if aggregated in a port trunk).

Flood Unknown Unicast Synopsis:   { On, Off }


Default:   On
Normally, unicast traffic with an unknown destination address is
flooded out of all ports. When a port is configured to turn off this
kind of flooding, the unknown unicast traffic is not sent out from
the selected port.

4. Click Apply.

200 Configuring MAC Address Flooding Options


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Section 5.4.4

Managing Static MAC Addresses


Static MAC addresses must be configured when the device is only able to receive frames, not transmit them. They
may also need to be configured if port security (if supported) must be enforced.
Prioritized MAC addresses are configured when traffic to or from a specific device on a LAN segment is to be
assigned a higher CoS priority than other devices on that LAN segment.

NOTE
A MAC address cannot be learned on a VLAN that has not been configured in the Static VLAN table. If
a frame with an unknown VLAN tag arrives on a secured port, it is considered a security violation and
ROS will generate a port security alarm.

CONTENTS
• Section 5.4.4.1, “Viewing a List of Static MAC Addresses”
• Section 5.4.4.2, “Adding a Static MAC Address”
• Section 5.4.4.3, “Deleting a Static MAC Address”

Section 5.4.4.1
Viewing a List of Static MAC Addresses
To view a list of static MAC addresses configured on the device, navigate to MAC Address Tables » Configure
Static MAC Addresses . The Static MAC Addresses table appears.

Figure 123: Static MAC Address Table

If static MAC addresses have not been configured, add addresses as needed. For more information, refer to
Section 5.4.4.2, “Adding a Static MAC Address” .

Section 5.4.4.2
Adding a Static MAC Address
To add a static MAC address to the Static MAC Address Table, do the following:
1. Navigate to MAC Address Tables » Configure Static MAC Addresses . The Static MAC Addresses table
appears.

Managing Static MAC Addresses 201


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Figure 124: Static MAC Addresses Table


1. InsertRecord

2. Click InsertRecord. The Static MAC Addresses form appears.

5 7

Figure 125: Static MAC Addresses Form


1. MAC Address Box    2. VID Box    3. Port Box    4. Priority Box    5. Apply Button    6. Delete Button    7. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

MAC Address Synopsis:   ##-##-##-##-##-## where ## ranges 0 to FF


A MAC address learned by the switch.
Maximum of 6 wildcard characters may be used to specify a range
of MAC addresses allowed to be learned by the Port Security
module (when Port Security is set to 'Static MAC' mode). Wildcard
must start from the right hand end and continuous.
Examples:
• 00-0A-DC-**-**-** means the entire MAC address space of
RuggedCom.
• 00-0A-DC-12-3*-** means the range 00-0A-DC-12-30-00 to
00-0A-DC-12-3F-FF.

VID Synopsis:   1 to 4094 or { ANY }


Default:   1

202 Adding a Static MAC Address


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description
VLAN Identifier of the VLAN upon which the MAC address
operates.
Option ANY allows learning a MAC address through the Port
Security module on any VLAN's that are configured on the switch.

Port Synopsis:   1/1 to maximum port number or { Learn }


Default:   Learn
Enter the port number upon which the device with this address is
located. The security mode of the port being selected should not
be '802.1X'.
If the port should be auto-learned, set this parameter to 'Learn'.
The option 'Learn' is applicable for Port Security in 'Static MAC'
mode.

Priority Synopsis:   0 to 7 or { N/A }


Default:   N/A
Prioritizes traffic for the specified MAC address. To not prioritize
traffic based on the address, select N/A.

4. Click Apply.

Section 5.4.4.3
Deleting a Static MAC Address
To delete a static MAC address from the Static MAC Address Table, do the following:
1. Navigate to MAC Address Tables » Configure Static MAC Addresses . The Static MAC Addresses table
appears.

Figure 126: Static MAC Addresses Table

2. Select the MAC address from the table. The Static MAC Addresses form appears.

Deleting a Static MAC Address 203


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

5 7

Figure 127: Static MAC Addresses Form


1. MAC Address Box    2. VID Box    3. Port Box    4. Priority Box    5. Apply Button    6. Delete Button    7. Reload Button

3. Click Delete.

Section 5.4.5

Purging All Dynamic MAC Addresses


To purge the dynamic MAC address list of all entries, do the following:
1. Navigate to MAC Address Tables » Purge MAC Address Table . The Purge MAC Address Table form
appears.

Figure 128: Purge MAC Address Table Form


1. Confirm Button

2. Click Confirm.

Section 5.5

Managing Time Services


The System Time Manager offers the following time-keeping and time synchronization features:
• Local hardware time keeping and time zone management
• SNTP (Simple Network Time Protocol) client and server

204 Purging All Dynamic MAC Addresses


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

• IEEE 1588 master and slave (ordinary) clock, boundary clock, and transparent clock modes of operation
• Configurable PPS (Pulse Per Second) output
• IRIG-B IN and OUT services
• GPS-referred system time

NOTE
GPS and IRIG-B time services require a Precision Time Protocol (PTP) card.

The device can be configured to provide time-keeping services via IEEE 1588, IRIG-B or SNTP. The time service can
be synchronized via GPS, IEEE 1588, IRIG-B and (S)NTP.

CONTENTS
• Section 5.5.1, “Configuring the Time and Date”
• Section 5.5.2, “Configuring IRIG-B”
• Section 5.5.3, “Managing the Precision Time Protocol (PTP)”
• Section 5.5.4, “Configuring the Time Source”
• Section 5.5.5, “Managing NTP”
• Section 5.5.6, “Viewing the Status of Time Synchronization Subsystems”

Section 5.5.1

Configuring the Time and Date


To set the time, date and other time-keeping related parameters, do the following:
1. Navigate to Administration » System Time Manager » Configure Time and Date . The Time and Date
form appears.

8 9

Figure 129: Time and Date Form


1. Time    2. Date    3. Time Zone    4. DST Offset    5. DST Rule    6. Current UTC Offset Box    7. Leap Second Pending Options   
8. Apply Button    9. Reload Button

Configuring the Time and Date 205


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

2. Configure the following parameter(s) as required:

Parameter Description

Time Synopsis:   HH:MM:SS


This parameter allows for both the viewing and setting of the
local time.

Date Synopsis:   MMM DD, YYYY


This parameter allows for both the viewing and setting of the
local date.

Time Zone Synopsis:   { UTC-12:00 (Eniwetok, Kwajalein), UTC-11:00


(Midway Island, Samoa), UTC-10:00 (Hawaii), UTC-9:00
(Alaska), UTC-8:00 (Los Angeles, Vancouver), UTC-7:00 (Calgary,
Denver), UTC-6:00 (Chicago, Mexico City), UTC-5:00 (New York,
Toronto), UTC-4:30 (Caracas), UTC-4:00 (Santiago), UTC-3:30
(Newfoundland), UTC-3:00 (Brasilia, Buenos Aires), UTC-2:00
(Mid Atlantic), UTC-1:00 (Azores), UTC-0:00 (Lisbon, London),
UTC+1:00 (Berlin, Paris, Rome), UTC+2:00 (Athens, Cairo,
Helsinki), ... }
Default:   UTC-5:00 (New York, Toronto)
This setting allows for the conversion of UTC (Universal
Coordinated Time) to local time.

DST Offset Synopsis:   HH:MM:SS


Default:   00:00:00
This parameter specifies the amount of time to be shifted
forward/backward when DST begins and ends. For example for
most part of USA and Canada, DST time shift is 1 hour (01:00:00)
forward when DST begins and 1 hour backward when DST ends.

DST Rule Synopsis:   mm.n.d/HH:MM:SS mm.n.d/HH:MM:SS


This parameter specifies a rule for time and date when the
transition between Standard and Daylight Saving Time occurs.
• mm - Month of the year (01 - January, 12 - December)
• n - nth d-day in the month (1 - 1st d-day, 5 - 5th/last d-day)
• d - day of the week (0 - Sunday, 6 - Saturday)
• HH - hour of the day (0 - 24)
• MM - minute of the hour (0 - 59)
• SS - second of the minute (0 - 59)
Example: The following rule applies in most part of USA and
Canada:

03.2.0/02:00:00 11.1.0/02:00:00

DST begins on March's 2nd Sunday at 2:00am.


DST ends on November's 1st Sunday at 2:00am.

Current UTC Offset Synopsis:   0 to 1000 s


Default:   36 s
Coordinated Universal Time (UTC) is a time standard based on
International Atomic Time (TAI) with leap seconds added at
irregular intervals to compensate for the Earth's slowing rotation.
Current UTC offset parameter allows user to adjust the difference
between UTC and TAI. The International Earth Rotation and
Reference System Service (IERS) observes the Earth's rotation
and nearly six months in advance (January and July) a Bulletin-C
message is sent out, which reports whether or not to add a leap
second in the end of June and December.

206 Configuring the Time and Date


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description
Please note that change in current UTC offset parameter will
result in temporally disruption in the timing network.

Leap Second Pending Synopsis:   { No, Yes }


Default:   No
This parameter allows user to manage the leap second event.
A leap second is a second added to Coordinated Universal Time
(UTC) in order to keep it synchronized with astronomical time.
The International Earth Rotation and Reference System Service
(IERS) observes the Earth's rotation and nearly six months in
advance (January and July) a Bulletin-C message is sent out,
which reports whether or not to add a leap second in the end of
June and December. This parameter must set at least 5 minutes in
advance before the occurrence of leap second event.

Section 5.5.2

Configuring IRIG-B
To configure IRIG-B, do the following:
1. Navigate to Administration » System Time Manager » Configure IRIGB . The IRIGB form appears.

9 10

Figure 130: IRIGB Form
1.  TTL Output List    2. PPx Pulse Interval List    3. PPx Pulse Width List    4. PPx Start Time List    5. AM Output Options    6. Time Code
List    7. IRIGB Ext List    8. IRIGB Input Options    9. Apply Button    10. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

TTL Output Synopsis:   { Off, PWM, PPS, PPx }


Default:   PWM
Selects Operational mode of TTL output port. PWM mode
complies with IRIG Standard 200-04. PPx provides generic pulse
per x second interface to synchronize external devices.

Configuring IRIG-B 207


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description

PPx Pulse Interval Synopsis:   1 to 86400 s


Default:   1 s
Selects Pulse Interval for TTL output port. This parameter is used
in conjunction with PPx in order to provides generic pulse per x
second interface to synchronize external devices.

PPx Pulse Width Synopsis:   1 to 200 ms


Default:   1 ms
Selects Pulse Width for TTL output port. This parameter is used in
conjunction with PPx to control the width of the pulse.

PPx Start Time Synopsis:   YYYY/MM/DD HH:MM:SS


Default:   1970/01/01 00:00:00
This parameter is used in conjunction with PPx to set the starting
time of first PPx event. Note that this parameter must be set at
least 15 seconds before the start of desired PPx otherwise first PPx
event might be lost.

AM Output Synopsis:   { Off, AM }


Default:   AM
Selects AM (Amplitude Modulation) mode of IRIGB port. AM mode
complies with IRIG Standard 200-04.

Time Code Synopsis:   { Bxx0, Bxx1, Bxx2, Bxx3, Bxx4, Bxx5, Bxx6, Bxx7 }
Default:   Bxx4
This device uses the following convention to decode the IRIGB
time code: letter [B] represents IRIG-B format, [xx] represents [00]
for PWM/TTL mode of operation and [12] for AM operation. For
example, Bxx7 represents B007 for PWM/TTL operation and B127
for AM operation. Please note that only Bxx0, Bxx1, Bxx4 and
Bxx5 time codes support IRIGB extensions.

IRIGB Ext Synopsis:   { Off, IEEE1344, C37.118-2005, C37.118-2011 }


Default:   Off
IRIGB extensions use extra bits of the Control Functions (CF)
portion of the IRIGB time code. Within this portion of the time
code, bits are designated for additional features, including:
Calendar Year, Leap seconds, leap seconds pending, Daylight
Saving Time (DST), DST pending, local time offset and time
quality. Please note that only Bxx0, Bxx1, Bxx4 and Bxx5 time
codes support IRIGB extensions.

IRIGB Input Synopsis:   { Off, PWM, AM }


Default:   PWM
Selects operational mode of IRIGB input port. IRIGB module is
capable of interpreting IRIGB extensions such as C37.118-2011,
C37.118-2005 and IEEE1344.

3. Click Apply.
4. If IRIGB Ext was modified, reset the device. For more information, refer to Section 3.13, “Resetting the
Device” .

208 Configuring IRIG-B


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Section 5.5.3

Managing the Precision Time Protocol (PTP)


The Precision Time Protocol (PTP) is a standard method of synchronizing network clocks over Ethernet.
RUGGEDCOM ROS supports PTP v2, which is defined by the IEEE 1588 working group in the IEEE 1588-2008
standard.
PTP is a distributed protocol that allows multiple clocks in a network to synchronize with one another. These clocks
are organized into a master-slave synchronization hierarchy with a grandmaster clock at the top of the hierarchy,
which determines the reference time for the entire system. Synchronization is achieved via the exchange of PTP
timing messages. Slave clocks use the timing information in PTP messages to adjust their time to that of the
master in their part of the hierarchy.
The PTP protocol executes within a logical scope called a domain. The time established via the protocol within one
domain is independent of the time in other domains.
A PTP v2 system may consist of a combination of both PTP-aware and PTP-unaware devices. There are five basic
PTP device types defined in the IEEE 1588-2008 standard:
• Ordinary Clocks
• Boundary Clocks
• End-to-End Transparent Clocks
• Peer-to-Peer Transparent Clocks
• Management Nodes
RUGGEDCOM ROS supports Ordinary Clock, Peer-to-Peer Transparent Clock, Boundary Clock and End-to-End
Transparent Clock modes:
• The Ordinary Clock can be either the grandmaster clock in a system or a slave clock in the master-slave
hierarchy. The selection of grandmaster and slave clocks is based on the Best Master Clock (BMC) algorithm
defined in the IEEE 1588-2008 standard.
• A Peer-to-Peer Transparent Clock forwards all messages just as a normal bridge, router, or repeater does. The
difference is that a Peer-to-Peer Transparent Clock also computes the residence time (message departure time -
message arrival time) and link delay (packet propagation delay between peer ports) and adds this information in
PTP event messages (which carry timestamps). Ethernet ports on a Peer-to-Peer Transparent Clock use the peer
delay mechanism to compute the packet propagation delay between peer ports.
• A Boundary Clock can be considered an IEEE 1588 gateway. A Boundary Clock translates the PTP messages
between PTP regions implementing different transport and messaging protocols, or different PTP profiles. For
example, a device in Boundary Clock mode can act as a timing sync (PTP Slave) from the Telecom network and
as a timing distribution source (PTP master) in a power substation environment.
• The End-to-End Transparent Clock supports the use of the end-to-end delay measurement mechanism between
slave clocks and the master clock. It forwards all messages just as a normal bridge, router or repeater does. The
difference is that an End-to-End Transparent Clock computes the residence time (message departure time -
message arrival time) and adds this information to PTP event messages (messages that carry a time-stamp).

CONTENTS
• Section 5.5.3.1, “Configuring PTP Globally”
• Section 5.5.3.2, “Configuring an Ordinary or Transparent Clock”
• Section 5.5.3.3, “Configuring a Boundary Clock Slave”
• Section 5.5.3.4, “Configuring the PTP Delay Request Interval”
• Section 5.5.3.5, “Configuring a VLAN for PTP Traffic”

Managing the Precision Time Protocol (PTP) 209


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

• Section 5.5.3.6, “Viewing PTP Clock Statistics”


• Section 5.5.3.7, “Viewing Boundary Clock Slave Statistics”
• Section 5.5.3.8, “Viewing Peer Delay Statistics”

Section 5.5.3.1
Configuring PTP Globally
To configure the global settings for PTP, do the following:
1. Navigate to Administration » System Time Manager » Precision Time Protocol » Configure Global
Parameters . The Global Parameters form appears.

IMPORTANT!
Before performing SNMP get or SNMP set operations for MIBs IEEE C37.238-2011 and
RUGGEDCOM-PTP1588-MIB.mib, make sure the PTP Enable parameter is set to Yes. For more
information about supported MIBs, refer to Section 1.6, “SNMP Management Interface Base (MIB)
Support” .

210 Configuring PTP Globally


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

10

11

12

13 14

Figure 131: Global Parameters Form


1. PTP Enable Options    2. Clock Type Options    3. PTP Profile List    4. Ethernet Ports Box    5. VLAN ID Box    6. Class Of Service Box   
7. Transport Protocol Options    8. Grandmaster ID Box    9. Startup Wait Box    10. Desired Clock Accuracy List    11. Network Class
Options    12. 1 Step Master Clock Options    13. Apply Button    14. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

PTP Enable Synopsis:   { No, Yes }


Default:   No
Enables PTP (Precision Time Protocol) protocol.

Clock Type Synopsis:   { Ordinary Clock, Boundary Clock, OC and P2P TClock,
P2P TClock, E2E TClock }
Default:   P2P TClock
Selects the PTP (Precision Time Protocol) clock type. Note that the
Ordinary Clock will become a Master Clock (MC) or Slave Clock
(SC) subject to network negotiation. If, however, IRIGB or GPS
is selected as the Time Source, the device will either negotiate
Mastership and act as a Grandmaster Clock (GMC) or remain in a
passive PTP state.

Configuring PTP Globally 211


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description
Note that only P2P (Peer-to-Peer) Transparent Clock (TClock),
E2E (End-to-End) Transparent Clock and P2P Grandmaster Clock
modes are supported on ports 2/4, 4/4, 6/4 and 7/2.

PTP Profile Synopsis:   { Power Profile, Default P2P Profile, Utility Profile
Level, Default E2E Profile, Custom Profile }
Synopsis:   { Power Profile, Default P2P Profile, Utility Profile
Level, Default E2E Profile, Custom Profile }
Default:   Power Profile
Selects the PTP (Precision Time Protocol) clock profile. PTP profile
represents a set of allowed PTP features applicable to specific
industry.

Ethernet Ports Synopsis:   Comma-separated list of ports


Default:   All
Selects Ethernet port(s) which take part in PTP (Precision Time
Protocol) message exchanges.
Note that only P2P (Peer-to-Peer) Transparent Clock (TClock),
E2E (End-to-End) Transparent Clock and P2P Grandmaster Clock
modes are supported on ports 2/4, 4/4, 6/4 and 7/2.

VLAN ID Synopsis:   1 to 4094 or { Disable }


Default:   1
The VLAN ID associated with untagged (and 802.1p priority
tagged) frames received on this port. Frames tagged with a non-
zero VLAN ID will always be associated with the VLAN ID retrieved
from the frame tag. Frames tagged with a zero VLAN ID will
always be associated with the VLAN ID 1 unless this parameter is
configured.

Class Of Service Synopsis:   1 to 7 or { Disable }


Default:   4
Selects the PTP (Precision Time Protocol) message priority based
on the IEEE 802.1p specification. IEEE 802.1p defines eight
different classes of service, usually expressed using the 3-bit
priority field in an IEEE 802.1Q header added to the Ethernet
frame. If the VLAN option is enabled and the Class Of Service
option is set to 'Disable' then it represents priority '0' in terms of
the IEEE 802.1p specification.

Transport Protocol Synopsis:   { Layer 2 Multicast, Layer 3 Multicast }


Default:   Layer 2 Multicast
Selects network transport protocol for PTP (Precision Time
Protocol) messages.

Grandmaster ID Synopsis:   3 to 255


Default:   255
This parameter is specific to the Power Profile (IEEE C37.238
version). All PTP master capable devices must configure a
network-wide, unique instance of this parameter in the range of 3
to 254 for proper operation.

Startup Wait Synopsis:   0 to 3600 s


Default:   10 s
Normally the start-up time of a non-GPS master clock is less than
that of a GPS-enabled master (i.e. by the time it takes to acquire
GPS lock). This parameter provides the ability to bootstrap the PTP
network in an orderly fashion.

Desired Clock Accuracy Synopsis:   { 50 ns, 100 ns, 250 ns, 1 us, 2.5 us, 10 us, 25 us, 100
us, 250 us, 1 ms, 2.5 ms, 10 ms, 25 ms, 100 ms, 250 ms }
Default:   1 us

212 Configuring PTP Globally


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description
This parameter allows the user to configure the desired clock
accuracy. This represents the instantaneous value of the time
offset between master and slave clocks. The system will generate
an alarm if the time offset from the master exceeds the desired
accuracy.

Network Class Synopsis:   { IEEE1588 network, Non-IEEE1588 network }


Default:   IEEE1588 network
Clock servo stability is highly dependent on network personality.
This parameter allows the user to configure a network personality
to reflect a particular network environment. This might mean, for
example, whether all devices in the timing plane are IEEE1588
aware (IEEE1588 network) or whether the timing plane includes
non-IEEE1588 devices as well (non-IEEE1588 network). Note that
a IEEE1588 network is independent of traffic load. Only the E2E
mechanism is applicable to non-IEEE1588 networks.

1 Step Master Clock Synopsis:   { No, Yes }


Default:   Yes
This parameter is specific to the Ordinary Clock type. It allows the
user to configure 1-step or 2-step master clock functionality.

3. Click Apply.

Section 5.5.3.2
Configuring an Ordinary or Transparent Clock
To configure settings for a PTP ordinary or transparent clock, do the following:
1. Navigate to Administration » System Time Manager » Precision Time Protocol » Configure Clock
Parameters . The Clock Parameters form appears.

8
9
10

Figure 132: Clock Parameters Form


1. Domain Number Box    2. Sync Interval List    3. Announce Interval List    4. Announce Receipt Timeout Box    5. Priority 1 Box   
6. Priority 2 Box    7. Path Delay Mechanism Options    8. Slave Only Options    9. Apply Button    10. Reload Button

Configuring an Ordinary or Transparent Clock 213


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

2. Configure the following parameter(s) as required:

Parameter Description

Domain Number Synopsis:   0 to 127


Default:   0
Selects the PTP (Precision Time Protocol) domain number. A PTP
domain is a logical grouping of PTP clocks that synchronize to
each other using the PTP protocol.

Sync Interval Synopsis:   { 125 ms, 250 ms, 500 ms, 1 s, 2 s }


Default:   1 s
Selects the PTP (Precision Time Protocol) Sync interval (mean time
interval between successive Sync messages) in seconds. Sync
messages are sent periodically by the Master Clock which provide
time of day information to PTP Slave Clocks.

Announce Interval Synopsis:   { 1 s, 2 s, 4 s, 8 s, 16 s, 32 s }


Default:   1 s
Selects the PTP (Precision Time Protocol) Announce interval
(mean time interval between successive Announce messages)
in seconds. Announce messages are sent periodically by the
Master Clock to provide its status and characteristic information.
Announce messages are used to establish the synchronization
hierarchy, i.e., using the BMC (Best Master Clock) algorithm.

Announce Receipt Timeout Synopsis:   2 to 10


Default:   3
Selects the PTP (Precision Time Protocol) Announce receipt
timeout. This parameter specifies the number of intervals
that may pass without receipt of an Announce message. This
parameter is part of BMC (Best Master Clock) algorithm.
Please note that a change in this parameter may be disruptive.

Priority1 Synopsis:   0 to 255


Default:   128
Selects the PTP (Precision Time Protocol) clock priority1 during
the execution of the BMC (Best Master Clock) algorithm. A lower
value corresponds to a higher precedence. The BMC algorithm
selects clocks from a set with a lower value of priority1 over clocks
from a set with a greater value

Priority2 Synopsis:   0 to 255


Default:   128
Selects the PTP (Precision Time Protocol) clock priority2 during
the execution of the BMC (Best Master Clock) algorithm. A lower
value corresponds to a higher precedence. In the event that
the operation of the BMC algorithm fails to order the clocks
based on the values of priority1, clockClass, clockAccuracy and
scaledOffsetLogVariance, the priority2 attribute allows the
creation of up to 256 priorities to be evaluated before the tie-
breaker. The tie-breaker is based on the clock identity.

Path Delay Mechanism Synopsis:   { Disabled, Peer-to-Peer, End-to-End }


Default:   Peer-to-Peer
Selects the PTP (Precision Time Protocol) delay mechanism. There
are two mechanisms used in PTP to measure the propagation
delay between PTP ports: The P2P (Peer-to-Peer) delay mechanism
measures the port to port propagation time such as link delay
and frame residence time. The P2P mechanism is independent of
whether the PTP port is acting as Master or Slave.

214 Configuring an Ordinary or Transparent Clock


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description
The E2E (End-to-End) delay mechanism measures the message
propagation time between Master and Slave clocks across the
whole intervening network.
Note that the P2P mechanism does not inter-operate with path
delay measurements based on the E2E (also called request-
response) delay mechanism.

Slave Only Synopsis:   { No, Yes }


Default:   No
This option may be used to force an Ordinary Clock be a Slave
only clock. A slave only clock never enters the master state.
Slave only and Transparent Clock functionality may be used in
combination. Please note that a Boundary Clock must not be
configured as a slave only clock.

3. Click Apply.

Section 5.5.3.3
Configuring a Boundary Clock Slave
To configure settings for a PTP boundary clock slave, do the following:
1. Navigate to Administration » System Time Manager » Precision Time Protocol » Configure BClock Slave .
The BClock Slave form appears.

10

11 12

Figure 133: BClock Slave Form


1. PTP Profile List    2. Ethernet Port Box    3. Domain Number Box    4. Sync Interval List    5. Announce Interval List    6. Transparent
Protocol List    7. Path Delay Mechanism List    8. Auto Registration Options    9. Master IP Address Box    10. Backup Master IP Address
Box    11. Apply Button    12. Reload Button

2. Configure the following parameter(s) as required:

Configuring a Boundary Clock Slave 215


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description

PTP Profile Synopsis:   { Power Profile, Default P2P Profile, Utility Profile Level
1, Default E2E Profile, Telecom Profile, Custom Profile }
Default:   Telecom Profile
Selects the PTP (Precision Time Protocol) clock profile. Each
profile is a set of allowed PTP features applicable to the device.
Supported profiles are: Power Profile (IEEE C37.238 version),
Default P2P (Peer-to-Peer) Profile as defined in IEEE1588-2008
standard with layer 2 transport, Default E2E (End-to-End) Profile
as defined in IEEE1588-2008 standard with layer 2 transport, and
User Defined Custom Profile.

Ethernet Port Synopsis:   Comma-separated list of ports


Default:   None
Selects the Ethernet port which will act as the Slave port when the
device is configured as a Boundary Clock.
Note that Boundary Clock slave mode is not supported on ports
2/4, 4/4, 6/4 and 7/2.

Domain Number Synopsis:   0 to 127


Default:   0
Selects the PTP (Precision Time Protocol) domain number for the
Slave Clock. A PTP domain is a logical grouping of PTP clocks that
synchronize to each other using the PTP protocol.

Sync Interval Synopsis:   { 125 ms, 250 ms, 500 ms, 1 s, 2 s }


Default:   1 s
This parameter is specific to unicast transport and represents a
requested Sync interval (mean time interval between successive
Sync messages) in seconds. It is transmitted in the request for
unicast transmissions.

Announce Interval Synopsis:   { 1 s, 2 s, 4 s, 8 s, 16 s, 32 s }


Default:   2 s
Selects the PTP (Precision Time Protocol) Announce interval
(mean time interval between successive Announce messages)
in seconds. Announce messages are sent periodically by the
Master Clock to provide its status and characteristic information.
Announce messages are used to establish the synchronization
hierarchy, i.e., using the BMC (Best Master Clock) algorithm.

Transport Protocol Synopsis:   { Layer 2 Multicast, Layer 3 Multicast , Layer 3


Unicast }
Default:   Layer 3 Unicast
Selects layer 2 (Ethernet) multicast transport, layer 3 (UDP/IP)
multicast transport or layer 3 (UDP/IP) unicast transport for PTP
(Precision Time Protocol) messages.

Path Delay Mechanism Synopsis:   { Disabled, Peer-to-Peer, End-to-End }


Default:   End-to-End
Selects the PTP (Precision Time Protocol) delay mechanism. There
are two mechanisms used in PTP to measure the propagation
delay between PTP ports: The P2P (Peer-to-Peer) delay mechanism
measures the port-to-port propagation time such as link delay and
frame residence time.
The E2E (End-to-End) delay mechanism measures the message
propagation time between Master and Slave clocks across the
whole intervening network.
Note that the P2P mechanism does not inter-operate with path
delay measurements based on the E2E (also called request-
response) delay mechanism.

216 Configuring a Boundary Clock Slave


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description

Auto Registration Synopsis:   { No, Yes }


Default:   Yes
This parameter is specific to unicast transport. This parameter
allows user to auto register the slave clock to unicast master as
specified by the 'Master IP Address' attribute.

Master IP Address Synopsis:   ###.###.###.### where ### ranges from 0 to 255


This parameter is specific to unicast transport and represents the
IP address of the unicast PTP (Precision Time Protocol) master
clock.

Backup Master IP Address Synopsis:   ###.###.###.### where ### ranges from 0 to 255
This parameter is specific to unicast transport and represents the
IP address of the unicast backup PTP (Precision Time Protocol)
master clock.

3. Click Apply.

Section 5.5.3.4
Configuring the PTP Delay Request Interval
To configure the PTP delay request interval, do the following:
1. Navigate to Administration » System Time Manager » Precision Time Protocol » Configure Path Delay .
The Path Delay form appears.

3 4

Figure 134: Path Delay Form


1. P2P Request Interval List    2. E2E Request Interval List    3. Apply Button    4. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

P2P Request Interval Synopsis:   { 1 s, 2 s, 4 s, 8 s, 16 s, 32 s }


Default:   1 s
Selects PTP delay request interval (mean time interval between
successive delay request messages) in seconds. The peer delay
mechanism measures the port-to-port propagation time, such as
the link delay, between two communicating ports supporting the
peer delay mechanism.

E2E Request Interval Synopsis:   { 1 s, 2 s, 4 s, 8 s, 16 s, 32 s }


Default:   1 s

Configuring the PTP Delay Request Interval 217


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description
Selects PTP delay request interval (mean time interval between
successive delay request messages) in seconds. The E2E (also
called request-response) delay mechanism measures the message
propagation time between master and slave clocks.

3. Click Apply.

Section 5.5.3.5
Configuring a VLAN for PTP Traffic
To configure a VLAN specifically for PTP traffic, do the following:
1. Assign a VLAN ID to all PTP traffic. For more information, refer to Section 5.5.3.1, “Configuring PTP Globally” .
2. Add a static VLAN with the same ID. For more information about configuring a static VLAN, refer to
Section 5.1.5.2, “Adding a Static VLAN” .
3. For each Ethernet port that will transport PTP traffic, configure the PVID to match the VLAN ID configured in
Step 1 . For more information, refer to Section 5.1.4, “Configuring VLANs for Specific Ethernet Ports” .
4. Configure the PVID format for each affected Ethernet port to control whether PTP traffic is transported as
tagged or untagged frames. Or, if necessary, configure the port to be a VLAN trunk. For more information,
refer to Section 5.1.4, “Configuring VLANs for Specific Ethernet Ports” .

Section 5.5.3.6
Viewing PTP Clock Statistics
To view statistics for the Precision Time Protocol (PTP) clock, navigate to Administration » System Time
Manager » Precision Time Protocol » View PTP Statistics » View PTP Clock Stats . The PTP Clock Stats form
appears.

Figure 135: PTP Clock Stats Form (Example)

This form displays the following information:

NOTE
Parameters are available dependent on the status of the device.

218 Configuring a VLAN for PTP Traffic


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description

Status Synopsis:   Any 31 Characters


Shows the status of PTP (Precision Time Protocol) node, if device is
configured as an ordinary clock then this field will show the status
of the PTP state such as MASTER, SLAVE, LISTENING. If the device
is configured as a Transparent Clock then this field simply reflects
configuration setting.

Current Offset Synopsis:   -2147483647 ns to 2147483647 ns


Shows the current time offset between the master and slave clocks,
calculated according to the IEEE1588-2008 specification. Note that
this parameter reflects the approximate value and may ignore link
asymmetry.

Servo Status Synopsis:   Any 15 Characters


Shows the status of the clock servo. The clock servo mechanism
disciplines the system clock. If the clock accuracy is within the
desired limits, the status is set to lock. Note that an alarm might
occur convergence of the clock servo.

GM ID Synopsis:   Any 31 Characters


Shows the identity of PTP (Precision Time Protocol) grandmaster ID.
Please note that master clock may be the same as grandmaster clock.

Master ID Synopsis:   Any 31 Characters


Shows the identity of PTP (Precision Time Protocol) master clock.
Please note that master clock may be the same as grandmaster clock.

Section 5.5.3.7
Viewing Boundary Clock Slave Statistics
To view statistics for the Precision Time Protocol (PTP) boundary clock slave, navigate to Administration »
System Time Manager » Precision Time Protocol » View PTP Statistics » Viewing BClock Slave Stats . The
BClock Slave Stats form appears.

Figure 136: BClock Slave Stats Form

This form displays the following information:

Parameter Description

Status Synopsis:   Any 31 Characters


Shows the status of PTP (Precision Time Protocol) boundary clock
slave such as SLAVE, LISTENING.

Viewing Boundary Clock Slave Statistics 219


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description

GM ID Synopsis:   Any 31 Characters


Shows the identity of PTP (Precision Time Protocol) grandmaster ID.
Please note that master clock may be the same as grandmaster clock.

Master ID Synopsis:   Any 31 Characters


Shows the identity of PTP (Precision Time Protocol) master clock.
Please note that master clock may be the same as grandmaster clock.

Section 5.5.3.8
Viewing Peer Delay Statistics
To view statistics for the Precision Time Protocol (PTP) peer delay, do the following:
1. Navigate to Administration » System Time Manager » Precision Time Protocol » View PTP Statistics »
View Peer Delay Stats . The PTP Delay Stats table appears.

Figure 137: Peer Delay Stats Table

2. Select an Ethernet port. The PTP Delay Stats form appears.

4 5

Figure 138: Peer Delay Stats Form


1. Port Box    2. State Box    3. Peer Delay Box    4. Reload Button

This table displays the following information:

Parameter Description

Port Synopsis:   1/1 to maximum port number


The port number as seen on the front plate silkscreen of the
switch.

State Synopsis:   { On, Off }

220 Viewing Peer Delay Statistics


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description
Shows the status of PTP port with respect to P2P (Peer To Peer)
delay mechanism.

PeerDelay Synopsis:   0 to 2147483647 ns


Shows peer delay in nanoseconds. The peer delay mechanism
measures the port-to-port propagation time, such as the link
delay, between two communicating ports supporting the peer
delay mechanism.

Section 5.5.4

Configuring the Time Source


To configure a reference time source to be used by the device for the local clock and for all served time
synchronization outputs, do the following:
1. Navigate to Administration » System Time Manager » Configure Time Source . The Time Source form
appears.

6 7

Figure 139: Time Source Form


1. Primary Time Source List    2. GPS/IRIGB Local Interval Box    3. GPS Cable Compensation Box    4. IRIGB Cable Compensation Box   
5. GPS Antenna Power Options    6. Apply Button    7. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

Primary Time Source Synopsis:   { LOCAL CLK, IRIGB, IEEE1588, NTP Server, GPS }
Default:   LOCAL CLK
To select time source that will discipline the local clock. Note that
changing the time source may produce a step change in the time
seen via any of the clock outputs.

GPS/IRIGB Lock Interval Synopsis:   1 min to 120 min or { Forever }


Default:   Forever
The time interval in which the GPS/IRIG-B receiver should acquire
a lock to the time source.
Normally the GPS (or IRIG-B) receiver needs a short interval on
the order of minutes to lock the signal. If the time interval expires

Configuring the Time Source 221


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description
without acquiring the lock, then system starts distributing the
time using the local clock.

GPS Cable Compensation Synopsis:   1 to 50000 ns or { none }


Default:   none
Cable compensation may be desired to compensate for a long
cable run in order to minimize the timing inaccuracy.

IRIGB Cable Compensation Synopsis:   1 to 50000 ns or { none }


Default:   none
Cable compensation may be desired to compensate for a long
cable run in order to minimize the timing inaccuracy.

GPS Antenna Power Synopsis:   { On, Off }


Default:   On
GPS receiver requires an active antenna. An active antenna
includes preamplifier that filters and amplifies the GPS signals
before delivery to the receiver. This option allows user to activate
or deactivate the power of GPS antenna. If GPS antenna is share
among multiple devices than all but one device should power the
GPS antenna.

3. Click Apply.

Section 5.5.5

Managing NTP
RUGGEDCOM ROS may be configured to refer periodically to a specified NTP server to correct any accumulated
drift in the on-board clock. RUGGEDCOM ROS will also serve time via the Simple Network Time Protocol (SNTP) to
hosts that request it.
Two NTP servers (primary and backup) may be configured for the device. The primary server is contacted first for
each attempt to update the system time. If the primary server fails to respond, the backup server is contacted. If
either the primary or backup server fails to respond, an alarm is raised.

CONTENTS
• Section 5.5.5.1, “Enabling/Disabling NTP Service”
• Section 5.5.5.2, “Configuring NTP Servers”

Section 5.5.5.1
Enabling/Disabling NTP Service
To enable or disable NTP Service, do the following:
1.
NOTE
If the device is running as an NTP server, NTP service must be enabled.

Navigate to Administration » System Time Manager » Configure NTP » Configure NTP Service . The SNTP
Parameters form appears.

222 Managing NTP


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

2 3

Figure 140: SNTP Parameters Form


1. SNTP Options    2. Apply Button    3. Reload Button

2. Select Enabled to enable SNTP, or select Disabled to disable SNTP.


3. Click Apply.

Section 5.5.5.2
Configuring NTP Servers
To configure either the primary or backup NTP server, do the following:
1. Navigate to Administration » System Time Manager » Configure NTP » Configure NTP Servers . The NTP
Servers table appears.

Figure 141: NTP Servers Table

2. Select either Primary or Backup. The NTP Servers form appears.

Configuring NTP Servers 223


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

4 5

Figure 142: NTP Servers Form


1. Server Box    2. IP Address Box    3. Update Period Box    4. Apply Button    5. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Server Synopsis:   Any 8 characters


Default:   Primary
This field tells whether this configuration is for a Primary or a
Backup Server.

IP Address Synopsis:   ###.###.###.### where ### ranges from 0 to 255


The Server IP Address.

Update Period Synopsis:   1 to 1440 min


Default:   60 min
Determines how frequently the (S)NTP server is polled for a time
update.If the server cannot be reached in three attempts that are
made at one minute intervals an alarm is generated.

4. Click Apply.

Section 5.5.6

Viewing the Status of Time Synchronization Subsystems


To view the current status of each time synchronization subsystem, navigate to Administration » System Time
Manager » View Time Sync Status . The Time Sync Status form appears. This form varies based on the time
source configured.

224 Viewing the Status of Time Synchronization Subsystems


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Figure 143: Time Sync Status Form (Local Time Source)

Figure 144: Time Sync Status Form (IRIG-B Time Source)

Figure 145: Time Sync Status Form (GPS Time Source)

Viewing the Status of Time Synchronization Subsystems 225


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Figure 146: Time Sync Status Form (IEEE 1588 Time Source)

Figure 147: Time Sync Status Form (NTP Server Time Source)

This table displays the following information:

Parameter Description

Time Source Synopsis:   { LOCAL CLK, IRIGB, IEEE1588, NTP Server, GPS }
A time source that is driving the local clock.

GPS Status Synopsis:   { NULL, NotPresent, Disabled, Locked, Searching,


Acquiring, Holdover, ParityError, SignalDecodingError,
ReceiverShortCircuit, DeviceConfigFailure }
The system synchronization status with respect to selected primary
time source.

IRIGB Status Synopsis:   { NULL, NotPresent, Disabled, Locked, Searching,


Acquiring, Holdover, ParityError, SignalDecodingError,
ReceiverShortCircuit, DeviceConfigFailure }
The system synchronization status with respect to selected primary
time source.

Satellites in View Synopsis:   0 to 24


The Number of Satellites shows how many satellites are currently
being tracked by the GPS module.

GPS Latitude Synopsis:   Any 31 characters


The Latitude and Longitude fields show the current position of the
GPS antenna. A position's distance north or south of the equator,
measured by degrees from zero to 90. One minute of latitude equals
one nautical mile. Latitude is often measured in degrees, with
minutes and seconds for finer measurements. A degree is divided
into 60 minutes. One minute can be further divided into 60 seconds.

GPS Longitude Synopsis:   Any 31 characters

226 Viewing the Status of Time Synchronization Subsystems


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description
The Latitude and Longitude fields show the current position of
the GPS antenna. The distance east or west of the prime meridian
(measured in degrees). The prime meridian runs from the north
to south pole through Greenwich, England. It is an angular
measurement, expressed in degrees, minutes and seconds.

SNTP Offset Synopsis:   -2147483647 to 2147483646 us or { Acquiring,


Holdover }
Shows the current time offset between (S)NTP server and client
clocks and is calculated as - .

Frequency Adjustment Synopsis:   -2147483647 to 2147483646 ppb


Shows the current amount of discipline applied to the local
frequency reference (TCXO); i.e. the amount of correction on this
system required to synchronize to the current reference.

Section 5.6

Managing SNMP
RUGGEDCOM ROS supports versions 1, 2 and 3 of the Simple Network Management Protocol (SNMP), otherwise
referred to as SNMPv1, SNMPv2c and SNMPv3 respectively. SNMPv3 provides secure access to the devices through
a combination of authentication and packet encryption over the network. Security features for this protocol
include:
Feature Description

Message Integrity Makes sure that a packet has not been tampered with in-transit.

Authentication Determines if the message is from a valid source.

Encryption Encrypts the contents of a packet to prevent it from being seen by an unauthorized source.

SNMPv3 provides security models and security levels. A security model is an authentication strategy setup for
a user and the group in which the user resides. A security level is a permitted level of security within a security
model. A combination of a security model and level will determine which security mechanism is employed when
handling an SNMP packet.
Before configuring SNMPv3, note the following:
• Each user belongs to a group
• A group defines the access policy for a set of users
• An access policy defines what SNMP objects can be accessed for (i.e. reading, writing and creating notifications)
• A group determines the list of notifications its users can receive
• A group also defines the security model and security level for its users
For SNMPv1 and SNMPv2c, a community string can be configured. The string is mapped to the group and access
level with a security name, which is configured as User Name.

CONTENTS
• Section 5.6.1, “Managing SNMP Users”
• Section 5.6.2, “Managing Security-to-Group Mapping”

Managing SNMP 227


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

• Section 5.6.3, “Managing SNMP Groups”

Section 5.6.1

Managing SNMP Users


The following section describes how to configure and manage SNMP users.

CONTENTS
• Section 5.6.1.1, “Viewing a List of SNMP Users”
• Section 5.6.1.2, “Adding an SNMP User”
• Section 5.6.1.3, “Deleting an SNMP User”

Section 5.6.1.1
Viewing a List of SNMP Users
To view a list of SNMP users configured on the device, navigate to Administration » Configure SNMP »
Configure SNMP Users . The SNMP Users table appears.

Figure 148: SNMP Users Table

If users have not been configured, add users as needed. For more information, refer to Section 5.6.1.2, “Adding
an SNMP User” .

Section 5.6.1.2
Adding an SNMP User
Multiple users (up to a maximum of 32) can be configured for the local SNMPv3 engine, as well as SNMPv1 and
SNMPv2c communities.

NOTE
When employing the SNMPv1 or SNMPv2c security level, the User Name parameter maps the
community name with the security group and access level.

To add a new SNMP user, do the following:

228 Managing SNMP Users


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

1. Navigate to Administration » Configure SNMP » Configure SNMP Users . The SNMP Users table appears.

Figure 149: SNMP Users Table


1. InsertRecord

2. Click InsertRecord. The SNMP Users form appears.

9
10
12

11

Figure 150: SNMP Users Form


1. Name Box    2. IP Address Box    3. v1/v2c Community Box    4. Auth Protocol Box    5. Priv Protocol Box    6. Auth Key Box   
7. Confirm Auth Key Box    8. Priv Key Box    9. Confirm Priv Key Box    10. Apply Button    11. Delete Button    12. Reload Button

NOTE
RUGGEDCOM ROS requires that all user passwords meet strict guidelines to prevent the use of
weak passwords. When creating a new password, make sure it adheres to the following rules:
• Must not be less than 6 characters in length.

Adding an SNMP User 229


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

• Must not include the username or any 4 continuous alphanumeric characters found in
the username. For example, if the username is Subnet25, the password may not be
subnet25admin or subnetadmin. However, net25admin or Sub25admin is permitted.
• Must have at least one alphabetic character and one number. Special characters are permitted.
• Must not have more than 3 continuously incrementing or decrementing numbers. For example,
Sub123 and Sub19826 are permitted, but Sub12345 is not.
An alarm will generate if a weak password is configured. The weak password alarm can be
disabled by the user. For more information about disabling alarms, refer to Section 4.6,
“Managing Alarms” .

3. Configure the following parameter(s) as required:

Parameter Description

Name Synopsis:   Any 32 characters


Default:   initial
The name of the user. This user name also represents the security
name that maps this user to the security group.

IP Address Synopsis:   ###.###.###.### where ### ranges from 0 to 255


The IP address of the user's SNMP management station. If IP
address is configured, SNMP requests from that user will be
verified by IP address as well. SNMP Authentication trap will be
generated to trap receivers if request was received from this user,
but from any other IP address.If IP address is empty, traps can not
be generated to this user, but SNMP requests will be served for
this user from any IP address.

v1/v2c Community Synopsis:   Any 32 characters


The community string which is mapped by this user/security name
to the security group if security model is SNMPv1 or SNMPv2c. If
this string is left empty, it will be assumed to be equal to the same
as user name.

Auth Protocol Synopsis:   { noAuth, HMACMD5, HMACSHA }


Default:   noAuth
An indication of whether messages sent on behalf of this user to/
from SNMP engine, can be authenticated, and if so, the type of
authentication protocol which is used.

Priv Protocol Synopsis:   { noPriv, CBC-DES }


Default:   noPriv
An Indication of whether messages sent on behalf of this user to/
from SNMP engine can be protected from disclosure, and if so,
the type of privacy protocol which is used.

Auth Key Synopsis:   31 character ASCII string


The secret authentication key (password) that must be shared
with SNMP client. If the key is not an emtpy string, it must be at
least 6 characters long.

Confirm Auth Key Synopsis:   31 character ASCII string


The secret authentication key (password) that must be shared
with SNMP client. If the key is not an emtpy string, it must be at
least 6 characters long.

Priv Key Synopsis:   31 character ASCII string

230 Adding an SNMP User


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description
The secret encription key (password) that must be shared with
SNMP client. If the key is not an emtpy string, it must be at least 6
characters long.

Confirm Priv Key Synopsis:   31 character ASCII string


The secret encription key (password) that must be shared with
SNMP client. If the key is not an emtpy string, it must be at least 6
characters long.

4. Click Apply.

Section 5.6.1.3
Deleting an SNMP User
To delete an SNMP user, do the following:
1. Navigate to Administration » Configure SNMP » Configure SNMP Users . The SNMP Users table appears.

Figure 151: SNMP Users Table

2. Select the user from the table. The SNMP Users form appears.

Deleting an SNMP User 231


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

9
10
12

11

Figure 152: SNMP Users Form


1. Name Box    2. IP Address Box    3. v1/v2c Community Box    4. Auth Protocol Box    5. Priv Protocol Box    6. Auth Key Box   
7. Confirm Auth Key Box    8. Priv Key Box    9. Confirm Priv Key Box    10. Apply Button    11. Delete Button    12. Reload Button

3. Click Delete.

Section 5.6.2

Managing Security-to-Group Mapping


The following section describes how to configure and manage security-to-group maps.

CONTENTS
• Section 5.6.2.1, “Viewing a List of Security-to-Group Maps”
• Section 5.6.2.2, “Adding a Security-to-Group Map”
• Section 5.6.2.3, “Deleting a Security-to-Group Map”

Section 5.6.2.1
Viewing a List of Security-to-Group Maps
To view a list of security-to-group maps configured on the device, navigate to Administration » Configure
SNMP » Configure SNMP Security to Group Maps . The SNMP Security to Group Maps table appears.

232 Managing Security-to-Group Mapping


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Figure 153: SNMP Security to Group Maps Table

If security-to-group maps have not been configured, add maps as needed. For more information, refer to
Section 5.6.2.2, “Adding a Security-to-Group Map” .

Section 5.6.2.2
Adding a Security-to-Group Map
Multiple combinations of security models and groups can be mapped (up to a maximum of 32) for SNMP.
To add a security-to-group map, do the following:
1. Navigate to Administration » Configure SNMP » Configure SNMP Security to Group Maps . The SNMP
Security to Group Maps table appears.

Figure 154: SNMP Security to Group Maps Table


1. InsertRecord

2. Click InsertRecord. The SNMP Security to Group Maps form appears.

Adding a Security-to-Group Map 233


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

4 6

Figure 155: SNMP Security to Group Maps Form


1. Security Model Box    2. Name Box    3. Group Box    4. Apply Button    5. Delete Button    6. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

SecurityModel Synopsis:   { snmpV1, snmpV2c, snmpV3 }


Default:   snmpV3
The Security Model that provides the name referenced in this
table.

Name Synopsis:   Any 32 characters


The user name which is mapped by this entry to the specified
group name.

Group Synopsis:   Any 32 characters


The group name to which the security model and name belong.
This name is used as an index to the SNMPv3 VACM Access Table.

4. Click Apply.

Section 5.6.2.3
Deleting a Security-to-Group Map
To delete a security-to-group map, do the following:
1. Navigate to Administration » Configure SNMP » Configure SNMP Security to Group Maps . The SNMP
Security to Group Maps table appears.

234 Deleting a Security-to-Group Map


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Figure 156: SNMP Security to Group Maps Table

2. Select the map from the table. The SNMP Security to Group Maps form appears.

4 6

Figure 157: SNMP Security to Group Maps Form


1. Security Model Box    2. Name Box    3. Group Box    4. Apply Button    5. Delete Button    6. Reload Button

3. Click Delete.

Section 5.6.3

Managing SNMP Groups


Multiple SNMP groups (up to a maximum of 32) can be configured to have access to SNMP.

CONTENTS
• Section 5.6.3.1, “Viewing a List of SNMP Groups”
• Section 5.6.3.2, “Adding an SNMP Group”

Managing SNMP Groups 235


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

• Section 5.6.3.3, “Deleting an SNMP Group”

Section 5.6.3.1
Viewing a List of SNMP Groups
To view a list of SNMP groups configured on the device, navigate to Administration » Configure SNMP »
Configure SNMP Access . The SNMP Access table appears.

Figure 158: SNMP Access Table

If SNMP groups have not been configured, add groups as needed. For more information, refer to Section 5.6.3.2,
“Adding an SNMP Group” .

Section 5.6.3.2
Adding an SNMP Group
To add an SNMP group, do the following:
1. Navigate to Administration » Configure SNMP » Configure SNMP Access . The SNMP Access table appears.

Figure 159: SNMP Access Table


1. InsertRecord

2. Click InsertRecord. The SNMP Access form appears.

236 Viewing a List of SNMP Groups


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

6
7
9

Figure 160: SNMP Access Form


1. Group Box    2. Security Model Box    3. Security Level Box    4. ReadViewName Box    5. WriteViewName Box    6. NotifyViewName
Box    7. Apply Button    8. Delete Button    9. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Group Synopsis:   Any 32 characters


The group name to which the security model and name belong.
This name is used as an index to the SNMPv3 VACM Access Table.

SecurityModel Synopsis:   { snmpV1, snmpV2c, snmpV3 }


Default:   snmpV3
In order to gain the access rights allowed by this entry, configured
security model must be in use.

SecurityLevel Synopsis:   { noAuthNoPriv, authNoPriv, authPriv }


Default:   noAuthNoPriv
The minimum level of security reqwuired in order to gain
the access rights allowed by this entry. A security level of
noAuthNoPriv is less than authNoPriv, which is less than authPriv.

ReadViewName Synopsis:   { noView, V1Mib, allOfMib }


Default:   noView
This parameter identifies the MIB tree(s) to which this entry
authorizes read access. If the value is noView, then no read access
is granted.

WriteViewName Synopsis:   { noView, V1Mib, allOfMib }


Default:   noView
This parameter identifies the MIB tree(s) to which this entry
authorizes write access. If the value is noView, then no write
access is granted.

NotifyViewName Synopsis:   { noView, V1Mib, allOfMib }


Default:   noView
This parameter identifies the MIB tree(s) to which this entry
authorizes access for notifications. If the value is noView, then no
access for notifications is granted.

Adding an SNMP Group 237


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

4. Click Apply.

Section 5.6.3.3
Deleting an SNMP Group
To delete an SNMP group, do the following:
1. Navigate to Administration » Configure SNMP » Configure SNMP Access . The SNMP Access table appears.

Figure 161: SNMP Access Table

2. Select the group from the table. The SNMP Access form appears.

6
7
9

Figure 162: SNMP Access Form


1. Group Box    2. Security Model Box    3. Security Level Box    4. ReadViewName Box    5. WriteViewName Box    6. NotifyViewName
Box    7. Apply Button    8. Delete Button    9. Reload Button

3. Click Delete.

Section 5.7

Managing Network Discovery


RUGGEDCOM ROS supports the Link Layer Discovery Protocol (LLDP) and RUGGEDCOM Discovery Protocol (RCDP),
both Layer 2 protocols for automated network discovery.

238 Deleting an SNMP Group


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

LLDP is an IEEE standard protocol, IEEE 802.11AB, that allows a networked device to advertise its own basic
networking capabilities and configuration.
LLDP allows a networked device to discover its neighbors across connected network links using a standard
mechanism. Devices that support LLDP are able to advertise information about themselves, including their
capabilities, configuration, interconnections, and identifying information.
LLDP agent operation is typically implemented as two modules: the LLDP transmit module and LLDP receive
module. The LLDP transmit module, when enabled, sends the local device’s information at regular intervals, in
IEEE 802.1AB standard format. Whenever the transmit module is disabled, it transmits an LLDPDU (LLDP data unit)
with a time-to-live (TTL) type-length-value (TLV) containing 0 in the information field. This enables remote devices
to remove the information associated with the local device in their databases. The LLDP receive module, when
enabled, receives remote devices’ information and updates its LLDP database of remote systems. When new or
updated information is received, the receive module initiates a timer for the valid duration indicated by the TTL
TLV in the received LLDPDU. A remote system’s information is removed from the database when an LLDPDU is
received from it with TTL TLV containing 0 in its information field.

NOTE
LLDP is implemented to keep a record of only one device per Ethernet port. Therefore, if there are
multiple devices sending LLDP information to a switch port on which LLDP is enabled, information
about the neighbor on that port will change constantly.

CONTENTS
• Section 5.7.1, “Network Discovery Concepts”
• Section 5.7.2, “Configuring LLDP Globally”
• Section 5.7.3, “Configuring LLDP for an Ethernet Port”
• Section 5.7.4, “Enabling/Disabling RCDP”
• Section 5.7.5, “Viewing Global Statistics and Advertised System Information”
• Section 5.7.6, “Viewing Statistics for LLDP Neighbors”
• Section 5.7.7, “Viewing Statistics for LLDP Ports”

Section 5.7.1

Network Discovery Concepts


The following section describes some of the concepts important to the implementation of network discovery in
RUGGEDCOM ROS.

CONTENTS
• Section 5.7.1.1, “Link Layer Discovery Protocol (LLDP)”
• Section 5.7.1.2, “ RUGGEDCOM Discovery Protocol (RCDP)”

Section 5.7.1.1
Link Layer Discovery Protocol (LLDP)
LLDP is an IEEE standard protocol, IEEE 802.11AB, that allows a networked device to advertise its own basic
networking capabilities and configuration.

Network Discovery Concepts 239


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

LLDP allows a networked device to discover its neighbors across connected network links using a standard
mechanism. Devices that support LLDP are able to advertise information about themselves, including their
capabilities, configuration, interconnections, and identifying information.
LLDP agent operation is typically implemented as two modules: the LLDP transmit module and LLDP receive
module. The LLDP transmit module, when enabled, sends the local device’s information at regular intervals, in
IEEE 802.1AB standard format. Whenever the transmit module is disabled, it transmits an LLDPDU (LLDP data unit)
with a time-to-live (TTL) type-length-value (TLV) containing 0 in the information field. This enables remote devices
to remove the information associated with the local device in their databases. The LLDP receive module, when
enabled, receives remote devices’ information and updates its LLDP database of remote systems. When new or
updated information is received, the receive module initiates a timer for the valid duration indicated by the TTL
TLV in the received LLDPDU. A remote system’s information is removed from the database when an LLDPDU is
received from it with TTL TLV containing 0 in its information field.

NOTE
LLDP is implemented to keep a record of only one device per Ethernet port. Therefore, if there are
multiple devices sending LLDP information to a switch port on which LLDP is enabled, information
about the neighbor on that port will change constantly.

Section 5.7.1.2
RUGGEDCOM Discovery Protocol (RCDP)
RUGGEDCOM Discovery Protocol (RCDP) supports the deployment of RUGGEDCOM ROS-based devices that have
not been configured since leaving the factory. RUGGEDCOM ROS devices that have not been configured all have
the default IP (Layer 3) address. Connecting more than one of them on a Layer 2 network means that one cannot
use standard IP-based configuration tools to configure them. The behavior of IP-based mechanisms such as the
web interface, SSH, telnet, or SNMP will all be undefined.
Since RCDP operates at Layer 2, it can be used to reliably and unambiguously address multiple devices even
though they may share the same IP configuration.
Siemens's RUGGEDCOM Explorer is a lightweight, standalone Windows application that supports RCDP. It is
capable of discovering, identifying and performing basic configuration of RUGGEDCOM ROS-based devices via
RCDP. The features supported by RCDP include:
• Discovery of RUGGEDCOM ROS-based devices over a Layer 2 network.
• Retrieval of basic network configuration, RUGGEDCOM ROS version, order code, and serial number.
• Control of device LEDs for easy physical identification.
• Configuration of basic identification, networking, and authentication parameters.
For security reasons, RUGGEDCOM Explorer will attempt to disable RCDP on all devices when Explorer is shut
down. If RUGGEDCOM Explorer is unable to disable RCDP on a device, RUGGEDCOM ROS will automatically disable
RCDP after approximately one hour of inactivity.

NOTE
RCDP is not compatible with VLAN-based network configurations. For correct operation of RUGGEDCOM
Explorer, no VLANs (tagged or untagged) must be configured. All VLAN configuration items must be at
their default settings.

NOTE
RUGGEDCOM ROS responds to RCDP requests only. It does not under any circumstances initiate any
RCDP-based communication.

240 RUGGEDCOM Discovery Protocol (RCDP)


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Section 5.7.2

Configuring LLDP Globally


To configure the global settings for LLDP, do the following:
1. Navigate to Network Discovery » Link Layer Discovery Protocol » Configure Global LLDP Parameters .
The Global LLDP Parameters form appears.

6 7

Figure 163: Global LLDP Parameters Form


1. State Options    2. Tx Interval Box    3. Tx Hold Box    4. Reinit Delay Box    5. Tx Delay Box    6. Apply Button    7. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

State Synopsis:   { Disabled, Enabled }


Default:   Enabled
Enables LLDP protocol. Note that LLDP is enabled on a port when
LLDP is enabled globally and along with enabling per port setting
in Port LLDP Parameters menu.

Tx Interval Synopsis:   5 to 32768 s


Default:   30 s
The interval at which LLDP frames are transmitted on behalf of
this LLDP agent.

Tx Hold Synopsis:   2 to 10
Default:   4
The multiplier of the Tx Interval parameter that determines the
actual time-to-live (TTL) value used in a LLDPDU. The actual TTL
value can be expressed by the following formula:

TTL = MIN(65535, (Tx Interval * Tx Hold))

Reinit Delay Synopsis:   1 to 10 s


Default:   2 s
The delay in seconds from when the value of Admin Status
parameter of a particular port becomes 'Disbled' until re-
initialization will be lattempted.

Tx Delay Synopsis:   1 to 8192 s


Default:   2 s

Configuring LLDP Globally 241


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description
The delay in seconds between successive LLDP frame
transmissions initiated by value or status changed. The
recommended value is set by the following formula:

1 <= txDelay <= (0.25 * Tx Interval)

3. Click Apply.

Section 5.7.3

Configuring LLDP for an Ethernet Port


To configure LLDP for a specific Ethernet Port, do the following:
1. Navigate to Network Discovery » Link Layer Discovery Protocol » Configure Port LLDP Parameters . The
Port LLDP Parameters table appears.

Figure 164: Port LLDP Parameters Table

2. Select a port. The Port LLDP Parameters form appears.

4 5

Figure 165: Port LLDP Parameters Form


1. Port Box    2. Admin Status List    3. Notifications Options    4. Apply Button    5. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Port Synopsis:   1/1 to maximum port number

242 Configuring LLDP for an Ethernet Port


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description
Default:   1/1
The port number as seen on the front plate silkscreen of the
switch.

Admin Status Synopsis:   { rxTx, txOnly, rxOnly, Disabled }


Default:   rxTx
rxTx: the local LLDP agent can both transmit and receive LLDP
frames through the port.
txOnly: the local LLDP agent can only transmit LLDP frames.
rxOnly: the local LLDP agent can only receive LLDP frames.
disabled: the local LLDP agent can neither transmit or receive
LLDP frames.

Notifications Synopsis:   { Disabled, Enabled }


Default:   Disabled
Disabling notifications will prevent sending notifications and
generating alarms for particular port from the LLDP agent.

4. Click Apply.

Section 5.7.4

Enabling/Disabling RCDP
RUGGEDCOM ROS supports the RUGGEDCOM Discovery Protocol (RCDP). RCDP supports the deployment of
RUGGEDCOM ROS-based devices that have not been configured since leaving the factory. RUGGEDCOM ROS
devices that have not been configured all have the default IP (Layer 3) address. Connecting more than one of
them on a Layer 2 network means that one cannot use standard IP-based configuration tools to configure them.
The behavior of IP-based mechanisms such as the web interface, SSH, telnet, or SNMP will all be undefined.
Since RCDP operates at Layer 2, it can be used to reliably and unambiguously address multiple devices even
though they may share the same IP configuration.
Siemens's RUGGEDCOM Explorer is a lightweight, standalone Windows application that supports RCDP. It is
capable of discovering, identifying and performing basic configuration of RUGGEDCOM ROS-based devices via
RCDP. The features supported by RCDP include:
• Discovery of RUGGEDCOM ROS-based devices over a Layer 2 network.
• Retrieval of basic network configuration, RUGGEDCOM ROS version, order code, and serial number.
• Control of device LEDs for easy physical identification.
• Configuration of basic identification, networking, and authentication parameters.
For security reasons, RUGGEDCOM Explorer will attempt to disable RCDP on all devices when Explorer is shut
down. If RUGGEDCOM Explorer is unable to disable RCDP on a device, RUGGEDCOM ROS will automatically disable
RCDP after approximately one hour of inactivity.

NOTE
RCDP is not compatible with VLAN-based network configurations. For correct operation of RUGGEDCOM
Explorer, no VLANs (tagged or untagged) must be configured. All VLAN configuration items must be at
their default settings.

Enabling/Disabling RCDP 243


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

NOTE
RUGGEDCOM ROS responds to RCDP requests only. It does not under any circumstances initiate any
RCDP-based communication.

To enable or disable RCDP, do the following:


1. Navigate to Network Discovery » RuggedCom Discovery Protocol » Configure RCDP Parameters . The
RCDP Parameters form appears.

2 3

Figure 166: RCDP Parameters Form


1. RCDP Discovery Options    2. Apply Button    3. Reload Button

2. Select Enabled to enable RCDP, or select Disabled to disable RCDP.


3. Click Apply.

Section 5.7.5

Viewing Global Statistics and Advertised System Information


To view global statistics for LLDP and the system information that is advertised to neighbors, navigate to Network
Discovery » Link Layer Discovery Protocol » View LLDP Global Remote Statistics . The LLDP Global Remote
Statistics form appears.

Figure 167: LLDP Global Remote Statistics Form


1. Inserts Box    2. Deletes Box    3. Drops Box    4. Ageouts Box    5. Reload Button

This form displays the following information:

Viewing Global Statistics and Advertised System


244 Information
RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description

Inserts Synopsis:   0 to 4294967295


A number of times the entry in LLDP Neighbor Information Table was
inserted.

Deletes Synopsis:   0 to 4294967295


A number of times the entry in LLDP Neighbor Information Table was
deleted.

Drops Synopsis:   0 to 4294967295


A number of times an entry was deleted from LLDP Neighbor
Information Table because the information timeliness interval has
expired.

Ageouts Synopsis:   0 to 4294967295


A counter of all TLVs discarded.

Section 5.7.6

Viewing Statistics for LLDP Neighbors


To view statistics for LLDP neighbors, navigate to Network Discovery » Link Layer Discovery Protocol » View
LLDP Neighbor Information . The LLDP Neighbor Information table appears.

5
6

Figure 168: LLDP Neighbor Information Table


1. Port Box    2. ChassisId Box    3. PortId Box    4. SysName Box    5. SysDesc Box    6. Reload Button

This form displays the following information:

Parameter Description

Port Synopsis:   1/1 to maximum port number


The local port associated with this entry.

ChassisId Synopsis:   Any 45 characters


Chassis Id information received from remote LLDP agent.

PortId Synopsis:   Any 45 characters


Port Id information received from remote LLDP agent.

SysName Synopsis:   Any 45 characters

Viewing Statistics for LLDP Neighbors 245


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description
System Name information received from remote LLDP agent.

SysDesc Synopsis:   Any 45 characters


System Descriptor information received from remote LLDP agent.

Section 5.7.7

Viewing Statistics for LLDP Ports


To view statistics for LLDP ports, navigate to Network Discovery » Link Layer Discovery Protocol » View LLDP
Statistics . The LLDP Statistics table appears.

Figure 169: LLDP Statistics Table

This table displays the following information:

Parameter Description

Port Synopsis:   1/1 to maximum port number


The port number as seen on the front plate silkscreen of the switch.

FrmDrop Synopsis:   0 to 4294967295


A counter of all LLDP frames discarded.

ErrFrm Synopsis:   0 to 4294967295


A counter of all LLDPDUs received with detectable errors.

FrmIn Synopsis:   0 to 4294967295


A counter of all LLDPDUs received.

FrmOut Synopsis:   0 to 4294967295


A counter of all LLDPDUs transmitted.

Ageouts Synopsis:   0 to 4294967295


A counter of the times that a neighbor's information has been
deleted from the LLDP remote system MIB because the txinfoTTL
timer has expired.

TLVsDrop Synopsis:   0 to 4294967295


A counter of all TLVs discarded.

TLVsUnknown Synopsis:   0 to 4294967295


A counter of all TLVs received on the port that are not recognized by
the LLDP local agent.

246 Viewing Statistics for LLDP Ports


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Section 5.8

Managing Multicast Filtering


Multicast traffic can be filtered using IGMP (Internet Group Management Protocol) snooping or GMRP (GARP
Multicast Registration Protocol).

CONTENTS
• Section 5.8.1, “Managing IGMP”
• Section 5.8.2, “Managing GMRP”

Section 5.8.1

Managing IGMP
IGMP is used by IP hosts to report their host group memberships with multicast routers. As hosts join and leave
specific multicast groups, streams of traffic are directed to or withheld from that host.
The IGMP protocol operates between multicast routers and IP hosts. When an unmanaged switch is placed
between multicast routers and their hosts, the multicast streams will be distributed to all ports.This may introduce
significant traffic onto ports that do not require it and receive no benefit from it.
IGMP Snooping, when enabled, will act on IGMP messages sent from the router and the host, restricting traffic
streams to the appropriate LAN segments.

IMPORTANT!
RUGGEDCOM ROS restricts IGMP hosts from subscribing to the following special multicast addresses:
• 224.0.0.0 to 224.0.0.255
• 224.0.1.129
These addresses are reserved for routing protocols and IEEE 1588. If an IGMP membership report
contains one of these addresses, the report is forwarded by the switch without learning about the host.

CONTENTS
• Section 5.8.1.1, “IGMP Concepts”
• Section 5.8.1.2, “Viewing a List of Multicast Group Memberships”
• Section 5.8.1.3, “Viewing Forwarding Information for Multicast Groups”
• Section 5.8.1.4, “Configuring IGMP”

Section 5.8.1.1
IGMP Concepts
The following describes some of the concepts important to the implementation of multicast filtering using IGMP:

IGMP In Operation
The following network diagram provides a simple example of the use of IGMP.

Managing Multicast Filtering 247


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

P1

2 M1 M2 2

3 3

C3 C4 C1 C2

4 4 5 4 4

Figure 170: Example – IGMP In Operation


1. Producer    2. Membership Queries    3. Membership Reports    4. Consumer    5. Multicast Router

One producer IP host (P1) is generating two IP multicast streams, M1 and M2. There are four potential consumers
of these streams, C1 through C4. The multicast router discovers which host wishes to subscribe to which stream
by sending general membership queries to each segment.
In this example, the general membership query sent to the C1-C2 segment is answered by a membership report
(or join) indicating the desire to subscribe to stream M2. The router will forward the M2 stream to the C1-C2
segment. In a similar fashion, the router discovers that it must forward stream M1 to segment C3-C4.
A consumer may join any number of multicast groups, issuing a membership report for each group. When a host
issues a membership report, other hosts on the same network segment that also require membership to the same
group suppress their own requests, since they would be redundant. In this way, the IGMP protocol guarantees the
segment will issue only one membership report for each group.
The router periodically queries each of its segments in order to determine whether at least one consumer still
subscribes to a given stream. If it receives no responses within a given time period (usually two query intervals),
the router will prune the multicast stream from the given segment.
A more common method of pruning occurs when consumers wishing to unsubscribe issue an IGMP leave group
message. The router will immediately issue a group-specific membership query to determine whether there are
any remaining subscribers of that group on the segment. After the last consumer of a group has unsubscribed, the
router will prune the multicast stream from the given segment.

Switch IGMP Operation


The IGMP Snooping feature provides a means for switches to snoop (i.e. watch) the operation of routers, respond
with joins/leaves on the behalf of consumer ports, and prune multicast streams accordingly. There are two modes
of IGMP the switch can be configured to assume: active and passive.
• Active Mode
IGMP supports a routerless mode of operation.
When such a switch is used without a multicast router, it is able to function as if it is a multicast router sending
IGMP general queries.

248 IGMP Concepts


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

• Passive Mode
When such a switch is used in a network with a multicast router, it can be configured to run Passive IGMP. This
mode prevents the switch from sending the queries that can confuse the router causing it to stop issuing IGMP
queries.

NOTE
A switch running in passive mode requires the presence of a multicast router or it will be unable to
forward multicast streams at all if no multicast routers are present.

NOTE
At least one IGMP Snooping switch must be in active mode to make IGMP functional.

IGMP Snooping Rules


IGMP Snooping adheres to the following rules:
• When a multicast source starts multicasting, the traffic stream will be immediately blocked on segments from
which joins have not been received.
• Unless configured otherwise, the switch will forward all multicast traffic to the ports where multicast routers are
attached.
• Packets with a destination IP multicast address in the 224.0.0.X range that are not IGMP are always forwarded
to all ports. This behavior is based on the fact that many systems do not send membership reports for IP
multicast addresses in this range while still listening to such packets.
• The switch implements IGMPv2 proxy-reporting (i.e. membership reports received from downstream are
summarized and used by the switch to issue its own reports).
• The switch will only send IGMP membership reports out of those ports where multicast routers are attached, as
sending membership reports to hosts could result in unintentionally preventing a host from joining a specific
group.
• Multicast routers use IGMP to elect a master router known as the querier. The querier is the router with the
lowest IP address. All other routers become non-queriers, participating only in forwarding multicast traffic.
Switches running in active mode participate in the querier election the same as multicast routers.
• When the querier election process is complete, the switch simply relays IGMP queries received from the querier.
• When sending IGMP packets, the switch uses its own IP address, if it has one, for the VLAN on which packets are
sent, or an address of 0.0.0.0, if it does not have an assigned IP address.

NOTE
IGMP Snooping switches perform multicast pruning using a multicast frames’ destination MAC
multicast address, which depends on the group IP multicast address. IP address W.X.Y.Z corresponds to
MAC address 01-00-5E-XX-YY-ZZ where XX is the lower 7 bits of X, and YY and ZZ are simply Y and Z
coded in hexadecimal.
One can note that IP multicast addresses, such as 224.1.1.1 and 225.1.1.1, will both map onto the
same MAC address 01-00-5E-01-01-01. This is a problem for which the IETF Network Working Group
currently has offered no solution. Users are advised to be aware of and avoid this problem.

IGMP and RSTP


An RSTP change of topology can render the routes selected to carry multicast traffic as incorrect. This results in lost
multicast traffic.

IGMP Concepts 249


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

If RSTP detects a change in the network topology, IGMP will take some actions to avoid the loss of multicast
connectivity and reduce network convergence time:
• The switch will immediately issue IGMP queries (if in IGMP Active mode) to obtain potential new group
membership information.
• The switch can be configured to flood multicast streams temporarily out of all ports that are not configured as
RSTP Edge Ports.

Combined Router and Switch IGMP Operation


The following example illustrates the challenges faced with multiple routers, VLAN support and switching.
Producer P1 resides on VLAN 2 while P2 resides on VLAN 3. Consumer C1 resides on both VLANs whereas C2 and
C3 reside on VLANs 3 and 2, respectively. Router 2 resides on VLAN 2, presumably to forward multicast traffic to a
remote network or act as a source of multicast traffic itself.

P1 2 3

P2 4

C1 C2 C3

Figure 171: Example – Combined Router and Switch IGMP In Operation


1. Producer    2. Multicast Router 1    3. Multicast Router 2    4. Switch    5. Host

In this example:
• P1, Router 1, Router 2 and C3 are on VLAN 2
• P2 and C2 are on VLAN 3
• C1 is on both VLAN 2 and 3
Assuming that router 1 is the querier for VLAN 2 and router 2 is simply a non-querier, the switch will periodically
receive queries from router 1 and maintain the information concerning which port links to the multicast router.
However, the switch port that links to router 2 must be manually configured as a router port. Otherwise, the
switch will send neither multicast streams nor joins/leaves to router 2.
Note that VLAN 3 does not have an external multicast router. The switch should be configured to operate in its
routerless mode and issue general membership queries as if it is the router.
• Processing Joins
If host C1 wants to subscribe to the multicast streams for both P1 and P2, it will generate two membership
reports. The membership report from C1 on VLAN 2 will cause the switch to immediately initiate its own
membership report to multicast router 1 (and to issue its own membership report as a response to queries).

250 IGMP Concepts


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

The membership report from host C1 for VLAN 3 will cause the switch to immediately begin forwarding
multicast traffic from producer P2 to host C2.
• Processing Leaves
When host C1 decides to leave a multicast group, it will issue a leave request to the switch. The switch will poll
the port to determine if host C1 is the last member of the group on that port. If host C1 is the last (or only)
member, the group will immediately be pruned from the port.
Should host C1 leave the multicast group without issuing a leave group message and then fail to respond to a
general membership query, the switch will stop forwarding traffic after two queries.
When the last port in a multicast group leaves the group (or is aged-out), the switch will issue an IGMP leave
report to the router.

Section 5.8.1.2
Viewing a List of Multicast Group Memberships
Using IGMP snooping, RUGGEDCOM ROS records group membership information on a per-port basis based on
membership reports it observes between the router and host.
To view a list of multicast group memberships, navigate to Multicast Filtering » View IGMP Group Membership
. The IGMP Group Membership table appears.

Figure 172: IGMP Group Membership Table

This table provides the following information:

Parameter Description

Port Synopsis:   1/1 to maximum port number


The port number as seen on the front plate silkscreen of the switch.

VID Synopsis:   0 to 65535


VLAN Identifier of the VLAN upon which the multicast group
operates.

Group Synopsis:   ###.###.###.### where ### ranges from 0 to 255


Multicast Group Address.

Ver Synopsis:   { v3, v2, v1 }


Specifies the IGMP version of the learnt multicast group.

Reporter Synopsis:   ###.###.###.### where ### ranges from 0 to 255


Specifies the source IP address that is reporting subscription to the
multicast group.

Age Synopsis:   0 to 7210 s


Specifies the current age of the IP multicast group learned on the
port in seconds.

Viewing a List of Multicast Group Memberships 251


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

If the table is empty, do the following:


• Make sure traffic is being sent to the device.
• Make sure IGMP is properly configured on the device. For more information, refer to Section 5.8.1.4,
“Configuring IGMP” .

Section 5.8.1.3
Viewing Forwarding Information for Multicast Groups
Multicast forwarding information for every source, group and VLAN combination learned by RUGGEDCOM ROS is
recorded in the IGMP Multicast Forwarding table.
To view the IGMP Multicast Forwarding table, navigate to Multicast Filtering » View IGMP Multicast
Forwarding . The IGMP Multicast Forwarding table appears.

Figure 173: IGMP Multicast Forwarding Table

This table provides the following information:

Parameter Description

VID Synopsis:   0 to 65535


VLAN Identifier of the VLAN upon which the multicast group
operates.

Group Synopsis:   ###.###.###.### where ### ranges from 0 to 255


Multicast Group Address.

Source Synopsis:   ###.###.###.### where ### ranges from 0 to 255 or


{*}
Source Address. * means all possible source addresses.

Joined Ports Synopsis:   Comma-separated list of ports


All ports that currently receive multicast traffic for the specified
multicast group.

Router Ports Synopsis:   Comma-separated list of ports


All ports that have been manually configured or dynamically
discovered (by observing router specific traffic) as ports that link to
multicast routers.

If the table is empty, do the following:


• Make sure traffic is being sent to the device.
• Make sure IGMP is properly configured on the device. For more information, refer to Section 5.8.1.4,
“Configuring IGMP” .

252 Viewing Forwarding Information for Multicast Groups


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Section 5.8.1.4
Configuring IGMP
To configure the IGMP, do the following:
1. Make sure one or more static VLANs exist with IGMP enabled. For more information, refer to Section 5.1.5,
“Managing Static VLANs” .
2. Navigate to Multicast Filtering » Configure IGMP Parameters . The IGMP Parameters form appears.

7 8

Figure 174: IGMP Parameters Form


1. Mode Options    2. IGMP Version    3. Query Interval Box    4. Router Ports Box    5. Router Forwarding Options    6. RSTP Flooding
Options    7. Apply Button    8. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Mode Synopsis:   { Passive, Active }


Default:   Passive
Specifies the IGMP mode. Options include:
• PASSIVE – the switch passively snoops IGMP traffic and never
sends IGMP queries
• ACTIVE – the switch generates IGMP queries, if no queries
from a better candidate for being the querier are detected for a
while.

IGMP Version Synopsis:   { v2, v3 }


Default:   v2
Specifies the configured IGMP version on the switch. Options
include:
• v2 – Sets the IGMP version to version 2. When selected for a
snooping switch, all IGMP reports and queries greater than v2
are forwarded, but not added to the IGMP Multicast Forwarding
table.
• v3 – Sets the IGMP version to version 3. General queries are
generated in IGMPv3 format, all versions of IGMP messages
are processed by the switch, and traffic is pruned based on
multicast group address only.

Query Interval Synopsis:   10 to 3600


Default:   60 s
The time interval between IGMP queries generated by the switch.

Configuring IGMP 253


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description

NOTE
This parameter also affects the Group Membership
Interval (i.e. the group subscriber aging time),
therefore, it takes effect even in PASSIVE mode.

Router Ports Synopsis:   Comma-separated list of ports


Default:   None
This parameter specifies ports that connect to multicast routers. If
you do not configure known router ports, the switch may be able
to detect them, however it is advisable to pre-configure them.

Router Forwarding Synopsis:   { Off, On }


Default:   On
This parameter specifies whether multicast streams will be always
forwarded to multicast routers.

RSTP Flooding Synopsis:   { Off, On }


Default:   Off
This parameter specifies whether multicast streams will be
flooded out of all RSTP non-edge ports upon topology change
detection. Such flooding is desirable, if guaranteed multicast
stream delivery after topology change is most important.

4. Click Apply.

Section 5.8.2

Managing GMRP
The GMRP is an application of the Generic Attribute Registration Protocol (GARP) that provides a Layer 2
mechanism for managing multicast group memberships in a bridged Layer 2 network. It allows Ethernet switches
and end stations to register and unregister membership in multicast groups with other switches on a LAN, and for
that information to be disseminated to all switches in the LAN that support Extended Filtering Services.
GMRP is an industry-standard protocol first defined in IEEE 802.1D-1998 and extended in IEEE 802.1Q-2005. GARP
was defined in IEEE 802.1D-1998 and updated in 802.1D-2004.

CONTENTS
• Section 5.8.2.1, “GMRP Concepts”
• Section 5.8.2.2, “Viewing a Summary of Multicast Groups”
• Section 5.8.2.3, “Configuring GMRP Globally”
• Section 5.8.2.4, “Configuring GMRP for Specific Ethernet Ports”
• Section 5.8.2.5, “Viewing a List of Static Multicast Groups”
• Section 5.8.2.6, “Adding a Static Multicast Group”

254 Managing GMRP


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

• Section 5.8.2.7, “Deleting a Static Multicast Group”

Section 5.8.2.1
GMRP Concepts
The following describes some of the concepts important to the implementation of multicast filtering using GMRP:

Joining a Multicast Group


In order to join a multicast group, an end station transmits a GMRP join message. The switch that receives the join
message adds the port through which the message was received to the multicast group specified in the message.
It then propagates the join message to all other hosts in the VLAN, one of which is expected to be the multicast
source.
When a switch transmits GMRP updates (from GMRP-enabled ports), all of the multicast groups known to the
switch, whether configured manually or learned dynamically through GMRP, are advertised to the rest of network.
As long as one host on the Layer 2 network has registered for a given multicast group, traffic from the
corresponding multicast source will be carried on the network. Traffic multicast by the source is only forwarded by
each switch in the network to those ports from which it has received join messages for the multicast group.

Leaving a Multicast Group


Periodically, the switch sends GMRP queries in the form of a leave all message. If a host (either a switch or an
end station) wishes to remain in a multicast group, it reasserts its group membership by responding with an
appropriate join request. Otherwise, it can either respond with a leave message or simply not respond at all. If the
switch receives a leave message or receives no response from the host for a timeout period, the switch removes
the host from the multicast group.

Notes About GMRP


Since GMRP is an application of GARP, transactions take place using the GARP protocol. GMRP defines the
following two Attribute Types:
• The Group Attribute Type, used to identify the values of group MAC addresses
• The Service Requirement Attribute Type, used to identify service requirements for the group
Service Requirement Attributes are used to change the receiving port's multicast filtering behavior to one of the
following:
• Forward All Multicast group traffic in the VLAN, or
• Forward All Unknown Traffic (Multicast Groups) for which there are no members registered in the device in a
VLAN
If GMRP is disabled on the RSG2488, GMRP packets received will be forwarded like any other traffic. Otherwise,
GMRP packets will be processed by the RSG2488, and not forwarded.

Establishing Membership with GMRP


The following example illustrates how a network of hosts and switches can dynamically join two multicast groups
using GMRP.

GMRP Concepts 255


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

In this scenario, there are two multicast sources, S1 and S2, multicasting to Multicast Groups 1 and 2, respectively.
A network of five switches, including one core switch (B), connects the sources to two hosts, H1 and H2, which
receive the multicast streams from S1 and S2, respectively.

1 S1

D1
D
D2
B3
B1
B B2
B4
A1 E1 C1
A E C 2
A2 E2 C2

H1 H2 3
1 S2

Figure 175: Example – Establishing Membership with GMRP


1. Multicast Source    2. Switch    3. Multicast Host

The hosts and switches establish membership with the Multicast Group 1 and 2 as follows:
1. Host H1 is GMRP unaware, but needs to see traffic for Multicast Group 1. Therefore, Port E2 on Switch E is
statically configured to forward traffic for Multicast Group 1.
2. Switch E advertises membership in Multicast Group 1 to the network through Port E1, making Port B4 on
Switch B a member of Multicast Group 1.
3. Switch B propagates the join message, causing Ports A1, C1 and D1 to become members of Multicast Group 1.
4. Host H2 is GMRP-aware and sends a join request for Multicast Group 2 to Port C2, which thereby becomes a
member of Multicast Group 2.
5. Switch C propagates the join message, causing Ports A1, B2, D1 and E1 to become members of Multicast
Group 2.
Once GMRP-based registration has propagated through the network, multicast traffic from S1 and S2 can reach its
destination as follows:
• Source S1 transmits multicast traffic to Port D2 which is forwarded via Port D1, which has previously become a
member of Multicast Group 1.
• Switch B forwards the Group 1 multicast via Port B4 towards Switch E.
• Switch E forwards the Group 1 multicast via Port E2, which has been statically configured for membership in
Multicast Group 1.
• Host H1, connected to Port E2, thus receives the Group 1 multicast.
• Source S2 transmits multicast traffic to Port A2, which is then forwarded via port A1, which has previously
become a member of Multicast Group 2.
• Switch B forwards the Group 2 multicast via Port B2 towards Switch C.

256 GMRP Concepts


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

• Switch C forwards the Group 2 multicast via Port C2, which has previously become a member of Group 2.
• Ultimately, Host H2, connected to Port C2, receives the Group 2 multicast.

Section 5.8.2.2
Viewing a Summary of Multicast Groups
To view a summary of all multicast groups, navigate to Multicast Filtering » View Multicast Group Summary .
The Multicast Group Summary table appears.

Figure 176: Multicast Group Summary Table

This table provides the following information:

Parameter Description

VID Synopsis:   0 to 65535


VLAN Identifier of the VLAN upon which the multicast group
operates.

MAC Address Synopsis:   ##-##-##-##-##-## where ## ranges 0 to FF


Multicast group MAC address.

Static Ports Synopsis:   Any combination of numbers valid for this parameter
Ports that joined this group statically through static configuration
in Static MAC Table and to which the multicast group traffic is
forwarded.

GMRP Dynamic Ports Synopsis:   Any combination of numbers valid for this parameter
Ports that joined this group dynamically through GMRP Application
and to which the multicast group traffic is forwarded.

Section 5.8.2.3
Configuring GMRP Globally
To configure global settings for GMRP, do the following:
1. Navigate to Multicast Filtering » Configure Global GMRP Parameters . The Global GMRP Parameters form
appears.

Viewing a Summary of Multicast Groups 257


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

4 5

Figure 177: Global GMRP Parameters Form


1. GMRP Enable Options    2. RSTP Flooding Options    3. Leave Timer Box    4. Apply Button    5. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

GMRP Enable Synopsis:   { No, Yes }


Default:   No
Globally enable or disable GMRP.
When GMRP is globally disabled, GMRP configurations on
individual ports are ignored. When GMRP is globally enabled, each
port can be individually configured.

RSTP Flooding Synopsis:   { On, Off }


Default:   Off
This parameter specifies whether multicast streams will be
flooded out of all RSTP non-edge ports upon topology change
detection. Such flooding is desirable, if guaranteed multicast
stream delivery after topology change is most important.

Leave Timer Synopsis:   600 to 300000 ms


Default:   4000 ms
Time (milliseconds) to wait after issuing Leave or LeaveAll before
removing registered multicast groups. If Join messages for
specific addresses are received before this timer expires, the
addresses will be kept registered.

3. Click Apply.

Section 5.8.2.4
Configuring GMRP for Specific Ethernet Ports
To configure GMRP for a specific Ethernet port, do the following:
1. Make sure the global settings for GMRP have been configured. For more information, refer to Section 5.8.2.3,
“Configuring GMRP Globally” .
2. Navigate to Multicast Filtering » Configure Port GMRP Parameters . The Port GMRP Parameters table
appears.

258 Configuring GMRP for Specific Ethernet Ports


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Figure 178: Port GMRP Parameters Table

3. Select an Ethernet port. The Port GMRP Parameters form appears.

3 4

Figure 179: Port GMRP Parameters Form


1. Port(s) Box    2. GMRP List    3. Apply Button    4. Reload Button

4. Configure the following parameter(s) as required:

Parameter Description

Port(s) Synopsis:   Any combination of numbers valid for this parameter


The port number as seen on the front plate silkscreen of the
switch (or a list of ports, if aggregated in a port trunk).

GMRP Synopsis:   { Disabled, Adv Only, Adv&Learn }


Default:   Default: Disabled
Configures GMRP (GARP Multicast Registration Protocol) operation
on the port. There are several GMRP operation modes:
• DISABLED - the port is not capable of any GMRP processing.
• ADVERTISE ONLY - the port will declare all MCAST addresses
existing in the switch (configured or learned) but will not learn
any MCAST addresses.
• ADVERTISE & LEARN - the port will declare all MCAST Addresses
existing in the switch (configured or learned) and can
dynamically learn MCAST addresses.

5. Click Apply.

Configuring GMRP for Specific Ethernet Ports 259


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Section 5.8.2.5
Viewing a List of Static Multicast Groups
To view a list of static multicast groups, navigate to Multicast Filtering » Configure Static Multicast Groups .
The Static Multicast Groups table appears.

Figure 180: Static Multicast Groups Table

If a static multicast group is not listed, add the group. For more information, refer to Section 5.8.2.6, “Adding a
Static Multicast Group” .

Section 5.8.2.6
Adding a Static Multicast Group
To add a static multicast group from another device, do the following:
1. Navigate to Multicast Filtering » Configure Static Multicast Groups . The Static Multicast Groups table
appears.

Figure 181: Static Multicast Groups Table


1. InsertRecord

2. Click InsertRecord. The Static Multicast Groups form appears.

260 Viewing a List of Static Multicast Groups


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

5 7

Figure 182: Static Multicast Groups Form


1. MAC Address Box    2. VID Box    3. Priority Box    4. Ports Box    5. Apply Button    6. Delete Button    7. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

MAC Address Synopsis:   ##-##-##-##-##-## where ## ranges 0 to FF


Default:   00-00-00-00-00-00
Multicast group MAC address.

VID Synopsis:   1 to 4094


Default:   1
VLAN Identifier of the VLAN upon which the multicast group
operates.

Priority Synopsis:   0 to 7 or { N/A }


Default:   N/A
Prioritizes traffic for the specified MAC address. To not prioritize
traffic based on the address, select N/A.

Ports Synopsis:   Any combination of numbers valid for this parameter


Default:   None
Ports to which the multicast group traffic is forwarded.

4. Click Apply.

Section 5.8.2.7
Deleting a Static Multicast Group
To delete a static multicast group, do the following:
1. Navigate to Multicast Filtering » Configure Static Multicast Groups . The Static Multicast Groups table
appears.

Deleting a Static Multicast Group 261


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Figure 183: Static Multicast Groups Table

2. Select the group from the table. The Static Multicast Groups form appears.

5 7

Figure 184: Static Multicast Groups Form


1. MAC Address Box    2. VID Box    3. Priority Box    4. Ports Box    5. Apply Button    6. Delete Button    7. Reload Button

3. Click Delete.

Section 5.9

Managing DHCP
Dynamic Host Configuration Protocol (DHCP) is a communications protocol that allows network administrators
to centrally manage and automate the network configuration of devices attached to an Internet Protocol (IP)
network.

CONTENTS
• Section 5.9.1, “DHCP Concepts”
• Section 5.9.2, “Configuring the DHCP Relay Agent”
• Section 5.9.3, “Configuring DHCP Snooping”
• Section 5.9.4, “Configuring DHCP Port Parameters”
• Section 5.9.5, “Configuring the Static DHCP Binding Table”

262 Managing DHCP


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

• Section 5.9.6, “Viewing the DHCP Binding Table”


• Section 5.9.7, “Saving the Static DHCP Binding Table”
• Section 5.9.8, “Viewing ARP Inspection Statistics”
• Section 5.9.9, “Clearing ARP Inspection Statistics”

Section 5.9.1

DHCP Concepts
The following section describes concepts important to the configuration and application of DHCP.

CONTENTS
• Section 5.9.1.1, “DHCP Snooping”
• Section 5.9.1.2, “Trusted and Untrusted Ports”
• Section 5.9.1.3, “DHCP Binding Table”
• Section 5.9.1.4, “DHCP Relay Agent (Option 82)”
• Section 5.9.1.5, “Dynamic ARP Inspection”
• Section 5.9.1.6, “Preventable Network Attacks”

Section 5.9.1.1
DHCP Snooping
DHCP snooping is a network security feature that protects the network from untrusted DHCP servers and untrusted
clients by keeping track of ports where DHCP clients and servers reside. This information is tracked by building
a DHCP binding table that contains all MAC-IP associations the switch has learned by snooping client and server
DHCP communications. The binding table contains MAC-IP information which can be further utilized by DHCP
snooping applications. RUGGEDCOM ROS will log messages in the syslog and/or raise an alarm when DHCP
violations are detected.
RUGGEDCOM ROS will log messages in the syslog and/or raise an alarm when DHCP violations are detected.

NOTE
DHCP Snooping is enabled on the device on a per-VLAN basis. For more information about enabling
DHCP snooping on individual VLANs, refer to Section 5.1.5, “Managing Static VLANs” .

Section 5.9.1.2
Trusted and Untrusted Ports
DHCP Snooping classifies ports as trusted and untrusted. This port classification determines how a DHCP message
is handled by the switch. DHCP messages received on trusted ports are forwarded without any further checking,
while messages received from untrusted ports are verified to determine if the message is legitimate. The user is
expected to configure the ports as trusted or untrusted.
From a deployment perspective, it is also expected the user configures network ports as trusted. Network ports
typically connect to another switch or a router. This is necessary because a DHCP server may not be directly
connected to a switch port.

DHCP Concepts 263


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

For more information about configuring ports as trusted or untrusted, refer to Section 5.9.4, “Configuring DHCP
Port Parameters” .

Section 5.9.1.3
DHCP Binding Table
DHCP snooping dynamically builds and maintains a binding table using information extracted from intercepted
DHCP messages. The table contains an entry for each untrusted host with a leased IP address from the DHCP
server. The table does not contain entries for hosts connected through trusted interfaces. The DHCP snooping
feature updates the table when the switch receives specific DHCP messages.
When the device is reset, all the MAC-IP binding information learned by the switch will be lost, unless the learned
bindings are saved in the switch configuration file.
If a switch port link goes down, all the dynamically-learned binding table entries on that particular port are
removed from the table.
Manually-entered records can also be configured using a static binding table. For more information about
configuring the static DHCP binding table, refer to Section 5.9.5, “Configuring the Static DHCP Binding Table” .

Section 5.9.1.4
DHCP Relay Agent (Option 82)
A DHCP Relay Agent is a device that forwards DHCP packets between clients and servers when they are not on the
same physical LAN segment or IP subnet. The feature is enabled if the DHCP server IP address and a set of access
ports are configured.
DHCP Option 82 provides a mechanism for assigning an IP Address based on the location of the client device in the
network. Information about the client’s location can be sent along with the DHCP request to the server. Based on
this information, the DHCP server makes a decision about an IP Address to be assigned.
The DHCP Relay Agent takes the broadcast DHCP requests from clients received on the configured access port and
inserts the relay agent information option (Option 82) into the packet. Option 82 contains the VLAN ID (2 bytes)
and the port number of the access port (2 bytes: the circuit ID sub-option) and the switch’s MAC address (the
remote ID sub-option). This information uniquely defines the access port’s position in the network. For example,
the Circuit ID for VLAN 1 on port 1 is 00:01:00:01.
The DHCP Server supporting DHCP Option 82 sends a unicast reply and echoes Option 82. The DHCP Relay Agent
removes the Option 82 field and broadcasts the packet to the port from which the original request was received.
These parameters provide the ability to configure the switch to act as a relay agent for DHCP Option 82.
The DHCP Relay Agent communicates to the server on a management interface. The agent’s IP address is the
address configured for the management interface.
For more information about configuring the DHCP Relay Agent, refer to Section 5.9.2, “Configuring the DHCP
Relay Agent” .

Section 5.9.1.5
Dynamic ARP Inspection
Dynamic ARP Inspection (DAI) is a DHCP snooping application that validates Address Resolution Protocol (ARP)
packets in a network. DAI filters ARP packets with invalid IP-to-MAC address bindings. This protects the network

264 DHCP Binding Table


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

from some man-in-the-middle attacks. Dynamic ARP inspection makes sure only valid ARP requests and responses
are relayed.

NOTE
Dynamic ARP Inspection can only be enabled if DHCP snooping is enabled on the device.

ARP request and reply packets ingressing on untrusted ports are intercepted by the device and subject to
validation. ARP packets are not intercepted on ports that are configured as trusted. The user is expected to
configure the network ports as trusted, so that ARP traffic between devices is not subject to inspection.
The sender MAC and sender IP address fields in an ARP request/reply packets are validated against the MAC-IP
binding entry present in the DHCP snooping binding table. If a binding entry is not present in the table, or if the
information in the entry does not match, the ARP request/reply packet is dropped.
For more information about ARP inspection statistics, refer to Section 5.9.8, “Viewing ARP Inspection Statistics” .

Section 5.9.1.6
Preventable Network Attacks
The following network attacks can be prevented by enabling DHCP snooping and Dynamic ARP Inspection on the
switch. For more information, refer to Section 5.9.3, “Configuring DHCP Snooping” .
• Host Misconfiguration by a Rogue DHCP Server
A rogue DHCP server can assign an incorrect IP address, default gateway and/or DNS server parameters to the
client. A misconfigured client is susceptible to a potential network attack. Switches that support DHCP snooping
can identify DHCP messages from a rogue DHCP server and block these messages in the switch itself.

1 3

Figure 185: Misconfiguration by a Rogue DHCP Server


1. DHCP Client    2. Switch    3. DHCP Server    4. Rogue DHCP Server

• DHCP Client Attack


A roque DHCP client, or attacker host, can cancel the lease for an IP address assigned to another client by
sending a DHCPRELEASE message to the DHCP server. It can also decline the IP address for another client by
sending a DHCPDECLINE message.
DHCP snooping builds a DHCP binding table to validate the legitimacy of DHCPRELEASE and DHCPDECLINE
messages. If validation of these messages fail, they are dropped by the device.

Preventable Network Attacks 265


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

1 4

3
2

Figure 186: DHCP Client Attack


1. DHCP Client    2. Attacker Host    3. Switch    4. DHCP Server

• DHCP Starvation Attack


DHCP starvation occurs when a DHCP server is flooded with DHCP requests from a single rogue DHCP client that
has spoofed the client hardware addresses of other clients. This exhausts the DHCP server's IP address pool,
after which the server is unable to respond and provide new leases to legitimate DHCP clients. DHCP snooping
provides users an option to verify the client hardware address in the DHCP-REQUEST message, thus preventing a
starvation attack.

1 4

3
2

Figure 187: DHCP Starvation/Consumption Attack


1. DHCP Client    2. Attacker    3. Switch    4. DHCP Server

• ARP Spoofing Attack/Cache Poisoning


ARP spoofing attacks and cache poisoning can occur because ARP allows a gratuitous reply from a host even if
an ARP request was not received. After the attack, all traffic from the device under attack flows to the attacker's
computer. An ARP spoofing attack can target hosts, switches, and routers connected to a Layer 2 network by
poisoning the ARP caches of systems connected to the subnet and by intercepting traffic intended for other
hosts on the subnet.
An ARP spoofing attack can be prevented by enabling Dynamic ARP Inspection on the switch. For more
information about enabling Dynamic ARP Inspection, refer to Section 5.9.3, “Configuring DHCP Snooping” .

266 Preventable Network Attacks


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

1 1

3
2

Figure 188: ARP Cache Poisoning


1. Host    2. Attacker    3. Switch

Section 5.9.2

Configuring the DHCP Relay Agent


To configure the device as a DHCP Relay Agent, do the following:
1. Navigate to Network Access Control » DHCP Snooping » Configure DHCP Parameters . The DHCP
Parameters form appears.

4 5

Figure 189: DHCP Parameters Form


1. DHCP Server Address Box    2. ARP Inspection Options    3. Verify Hardware Address Options    4. Apply Button    5. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

DHCP Server Address Synopsis:   ###.###.###.### where ### ranges from 0 to 255
IP address of the DHCP server to which DHCP requests will be
forwarded. DHCP server IP must be configured for Relay Agent to
work.

3. Click Apply.
4. Navigate to Network Access Control » DHCP Snooping » Configure DHCP Port Parameters . The DHCP
Port Parameters table appears.

Configuring the DHCP Relay Agent 267


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Figure 190: DHCP Port Parameters Table

5. Select an Ethernet port. The DHCP Port Parameters form appears.

4 5

Figure 191: Port DCHP Parameters Form


1. Port Box    2. Trusted Options    3. Option-82 Options    4. Apply Button    5. Reload Button

6. Configure the following parameter(s) as required:

Parameter Description

Option-82 Synopsis:   { Disabled, Enabled }


Default:   Disabled
Insert DHCP Option 82.

7. Click Apply.

Section 5.9.3

Configuring DHCP Snooping


To configure DHCP snooping, do the following:

NOTE
DHCP Snooping is enabled on the device on a per-VLAN basis. For more information about enabling
DHCP snooping on individual VLANs, refer to Section 5.1.5, “Managing Static VLANs” .

1. Navigate to Network Access Control » DHCP Snooping » Configure DHCP Parameters . The DHCP
Parameters form appears.

268 Configuring DHCP Snooping


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

4 5

Figure 192: DHCP Parameters Form


1. DHCP Server Address Box    2. ARP Inspection Options    3. Verify Hardware Address Options    4. Apply Button    5. Reload Button

2. Configure the following parameter(s) as required:

Parameter Description

ARP Inspection Synopsis:   { Disabled, Enabled }


Default:   Disabled
Enable or Disable Dynamic ARP Inspection.

Verify Hardware Address Synopsis:   { No, Yes }


Default:   Yes
Verify if the Client hardware address present in the DHCP message
received on untrusted port matches with the Source MAC address.

3. Click Apply.

Section 5.9.4

Configuring DHCP Port Parameters


To configure individual ports to be considered trusted or untrusted by the device, do the following:
1. Navigate to Network Access Control » DHCP Snooping » Configure DHCP Port Parameters . The DHCP
Port Parameters table appears.

Figure 193: DHCP Port Parameters Table

2. Select an Ethernet port. The DHCP Port Parameters form appears.

Configuring DHCP Port Parameters 269


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

4 5

Figure 194: Port DCHP Parameters Form


1. Port Box    2. Trusted Options    3. Option-82 Options    4. Apply Button    5. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Port Synopsis:   1/1 to 8/2


The port number as seen on the front plate silkscreen of the
switch.

Trusted Synopsis:   { No, Yes }


Default:   No
DHCP trust setting for the port.

Option-82 Synopsis:   { Disabled, Enabled }


Default:   Disabled
Insert DHCP Option 82.

4. Click Apply.

Section 5.9.5

Configuring the Static DHCP Binding Table


To configure the static DHCP binding table, do the following:
1. Navigate to Network Access Control » DHCP Snooping » Configure Static DHCP Binding Table . The
Configure Static DHCP Binding Table appears.

270 Configuring the Static DHCP Binding Table


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Figure 195: Static DHCP Binding Table


1. InsertRecord

2. Click InsertRecord. The Static DHCP Binding Table form appears.

5 7

Figure 196: Static DHCP Binding Table Form


1. MAC Address Box    2. IP Address Box    3. VID Box    4. Port Box

3. Configure the following parameter(s) as required:

Parameter Description

MAC Address Synopsis:   ##-##-##-##-##-## where ## ranges 0 to FF


Default:   00-00-00-00-00-00
MAC Address of the DHCP Host.

IP Address Synopsis:   ##-##-##-##-##-## where ## ranges 0 to 255


IP Address assigned to the DHCP Host.

VID Synopsis:   0 to 65535


Default:   1
VLAN where in the IP-MAC binding entry was registered.

Port Synopsis:   1/1 to 8/2


Default:   1/1 to 8/2
Port on which IP-MAC binding entry was regsitered.

4. Click Apply.

Configuring the Static DHCP Binding Table 271


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Section 5.9.6

Viewing the DHCP Binding Table


To view the static DHCP binding table, do the following:
1. Navigate to Network Access Control » DHCP Snooping » View DHCP Binding Table . The View DHCP
Binding Table appears.

Figure 197: View DHCP Binding Table

2. Select an Ethernet port. The DHCP Binding Table form appears.

7 8

Figure 198: DHCP Binding Table


1. MAC Address Box    2. IP Address Box    3. VID Box    4. Port Box    5. Type Box    6. Lease (secs) Box

3. The following parameter(s) are displayed:

Parameter Description

MAC Address Synopsis:   ##-##-##-##-##-## where ## ranges 0 to FF


MAC Address of the DHCP Host.

IP Address Synopsis:   ##-##-##-##-##-## where ## ranges 0 to 255


IP Address assigned to the DHCP Host.

VID Synopsis:   0 to 65535


VLAN where in the IP-MAC binding entry was registered.

Port Synopsis:   1/1 to 8/2


Port on which IP-MAC binding entry was regsitered.

272 Viewing the DHCP Binding Table


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Parameter Description

Type Synopsis:   { Static, Dynamic }


Dynamic DHCP IP-MAC Binding Entries.

Lease (secs) Synopsis:   0 to 4294967295 or { - }


Lease time assigned to a Dynamic binding entry in seconds.If the
entry is Static then the lease time is infinite denoted as - .

4. Click Reload.

Section 5.9.7

Saving the Static DHCP Binding Table


To save the static DHCP binding table, do the following:
1. Navigate to Network Access Control » DHCP Snooping » Save DHCP Binding Table . The Save DHCP
Binding Table table appears.

Figure 199: Save DHCP Binding Table Form


1. Confirm Button

2. Click Confirm.

Section 5.9.8

Viewing ARP Inspection Statistics


To view ARP Inspection Statistics, do the following:
1. Navigate to Network Access Control » DHCP Snooping » View ARP Inspection Statistics . The ARP
Inspection Statistics table appears.

Saving the Static DHCP Binding Table 273


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Figure 200: ARP Inspection Statistics Form

2. Select an Ethernet port. The ARP Inspection Statistics form appears.

Figure 201: Port DCHP Parameters Form


1. Port Box    2. In Packets Box    3. Dropped Packets Box    4. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Port Synopsis:   1/1 to 8/2


The port number as seen on the front plate silkscreen of the
switch.

In Packets Synopsis:   0 to 4294967295


Total number of incoming ARP packets that were processed by
Dynamic ARP Inspection on this port.

Dropped Packets Synopsis:   0 to 4294967295


Total number of incoming ARP packets that were dropped by
Dynamic ARP Inspection on this port.

4. Click Apply.

Section 5.9.9

Clearing ARP Inspection Statistics


To clear ARP Inspection Statistics, do the following:

274 Clearing ARP Inspection Statistics


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

1. Navigate to Network Access Control » DHCP Snooping » Clear ARP Inspection Statistics . The Clear ARP
Inspection Statistics form appears.

Figure 202: Clear ARP Inspection Statistics Form


1. Confirm Button

2. Click Confirm.

Section 5.10

Managing Port Security


Port security, or port access control, provides the ability to filter or accept traffic from specific MAC addresses.
Port security works by inspecting the source MAC addresses of received frames and validating them against the list
of MAC addresses authorized by the port. Unauthorized frames are filtered and, optionally, the part that received
the frame can be shut down permanently or for a specified period of time. An alarm will be raised indicating the
detected unauthorized MAC address.
Frames to unknown destination addresses are flooded through secure ports.

CONTENTS
• Section 5.10.1, “Port Security Concepts”
• Section 5.10.2, “Viewing a List of Authorized MAC Addresses”
• Section 5.10.3, “Configuring Port Security”
• Section 5.10.4, “Configuring IEEE 802.1X”

Section 5.10.1

Port Security Concepts


The following section describes some of the concepts important to the implementation of port security in
RUGGEDCOM ROS.

CONTENTS
• Section 5.10.1.1, “Static MAC Address-Based Authentication”
• Section 5.10.1.2, “IEEE 802.1x Authentication”
• Section 5.10.1.3, “IEEE 802.1X Authentication with MAC Address-Based Authentication”

Managing Port Security 275


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

• Section 5.10.1.4, “Assigning VLANS with Tunnel Attributes”

Section 5.10.1.1
Static MAC Address-Based Authentication
With this method, the switch validates the source MAC addresses of received frames against the contents in the
Static MAC Address Table.
RUGGEDCOM ROS also supports a highly flexible Port Security configuration which provides a convenient means
for network administrators to use the feature in various network scenarios.
A Static MAC address can be configured without a port number being explicitly specified. In this case, the
configured MAC address will be automatically authorized on the port where it is detected. This allows devices to
be connected to any secure port on the switch without requiring any reconfiguration.
The switch can also be programmed to learn (and, thus, authorize) a pre-configured number of the first source
MAC addresses encountered on a secure port. This enables the capture of the appropriate secure addresses when
first configuring MAC address-based authorization on a port. Those MAC addresses are automatically inserted into
the Static MAC Address Table and remain there until explicitly removed by the user.

Section 5.10.1.2
IEEE 802.1x Authentication
The IEEE 802.1x standard defines a mechanism for port-based network access control and provides a means of
authenticating and authorizing devices attached to LAN ports.
Although IEEE 802.1x is mostly used in wireless networks, this method is also implemented in wired switches.
The IEEE 802.1x standard defines three major components of the authentication method: Supplicant,
Authenticator and Authentication server. RUGGEDCOM ROS supports the Authenticator component.

1 2 3 4

Figure 203: IEEE 802.1x General Topology


1. Supplicant    2. Authenticator Switch    3. LAN    4. Authentication Server

IMPORTANT!
RUGGEDCOM ROS supports both Protected Extensible Authentication Protocol (PEAP) and EAP-MD5.
PEAP is more secure and is recommended if available in the supplicant.

IEEE 802.1x makes use of the Extensible Authentication Protocol (EAP), which is a generic PPP authentication
protocol that supports various authentication methods. IEEE 802.1x defines a protocol for communication
between the Supplicant and the Authenticator, referred to as EAP over LAN (EAPOL).
RUGGEDCOM ROS communicates with the Authentication Server using EAP over RADIUS.

276 Static MAC Address-Based Authentication


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

NOTE
The switch supports authentication of one host per port.

NOTE
If the host’s MAC address is configured in the Static MAC Address Table, it will be authorized, even if the
host authentication is rejected by the authentication server.

Section 5.10.1.3
IEEE 802.1X Authentication with MAC Address-Based Authentication
This method, also referred to as MAB (MAC-Authentication Bypass), is commonly used for devices, such as VoIP
phones and Ethernet printers, that do not support the 802.1x protocol. This method allows such devices to be
authenticated using the same database infrastructure as that used in 802.1x.
IEEE 802.1x with MAC-Authentication Bypass works as follows:
1. The device connects to a switch port.
2. The switch learns the device MAC address upon receiving the first frame from the device (the device usually
sends out a DHCP request message when first connected).
3. The switch sends an EAP Request message to the device, attempting to start 802.1X authentication.
4. The switch times out while waiting for the EAP reply, because the device does not support 802.1x.
5. The switch sends an authentication message to the authentication server, using the device MAC address as
the username and password.
6. The switch authenticates or rejects the device according to the reply from the authentication server.

Section 5.10.1.4
Assigning VLANS with Tunnel Attributes
RUGGEDCOM ROS supports assigning a VLAN to the authorized port using tunnel attributes, as defined in RFC
3580 [http://tools.ietf.org/html/rfc3580], when the Port Security mode is set to 802.1x or 802.1x/MAC-Auth.
In some cases, it may be desirable to allow a port to be placed into a particular VLAN, based on the authentication
result. For example:
• To allow a particular device, based on its MAC address, to remain on the same VLAN as it moves within a
network, configure the switches for 802.1X/MAC-Auth mode
• To allow a particular user, based on the user’s login credentials, to remain on the same VLAN when the user logs
in from different locations, configure the switches for 802.1X mode
If the RADIUS server wants to use this feature, it indicates the desired VLAN by including tunnel attributes in the
Access-Accept message. The RADIUS server uses the following tunnel attributes for VLAN assignment:
• Tunnel-Type=VLAN (13)
• Tunnel-Medium-Type=802
• Tunnel-Private-Group-ID=VLANID
Note that VLANID is 12-bits and takes a value between 1 and 4094, inclusive. The Tunnel-Private-Group-ID is a
string as defined in RFC 2868 [http://tools.ietf.org/html/rfc2868], so the VLANID integer value is encoded as a
string.

IEEE 802.1X Authentication with MAC Address-Based


Authentication 277
Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

If the tunnel attributes are not returned by the authentication server, the VLAN assigned to the switch port
remains unchanged.

Section 5.10.2

Viewing a List of Authorized MAC Addresses


To view a list of static MAC addresses learned from secure ports, navigate to Network Access Control » Port
Security » View Authorized MAC Addresses . The Authorized MAC Addresses table appears.

NOTE
Only MAC addresses authorized on a static MAC port(s) are shown. MAC addresses authorized with
IEEE 802.1X are not shown.

Figure 204: Authorized MAC Addresses Table

This table displays the following information:

Parameter Description

Port Synopsis:   1/1 to maximum port number


Port on which MAC address has been learned.

MAC Address Synopsis:   ##-##-##-##-##-## where ## ranges 0 to FF


Authorized MAC address learned by the switch.

VID Synopsis:   0 to 65535


VLAN Identifier of the VLAN upon which the MAC address operates.

Sticky Synopsis:   { No, Yes }


This describes whether the authorized MAC address/Device can move
to another port or not:
• YES - authorized MAC address/Device cannot move to a different
switch port
• NO - authorized MAC address/Device may move to another switch
port

If a MAC address is not listed, do the following:


• Configure port security. For more information, refer to Section 5.10.3, “Configuring Port Security” .
• Configure IEEE 802.1X. For more information, refer to Section 5.10.4, “Configuring IEEE 802.1X” .

278 Viewing a List of Authorized MAC Addresses


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Section 5.10.3

Configuring Port Security


To configure port security, do the following:
1. Navigate to Network Access Control » Port Security » Configure Ports Security . The Ports Security table
appears.

Figure 205: Ports Security Table

2. Select an Ethernet port. The Ports Security form appears.

7 8

Figure 206: Ports Security Form


1. Port Box    2. Security List    3. Autolearn Box    4. Sticky Options    5. Shutdown Time Box    6. Status Box    7. Apply Button   
8. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Port Synopsis:   1/1 to maximum port number


Default:   1
The port number as seen on the front plate silkscreen of the
switch.

Security Synopsis:   { Off, Static MAC, 802.1X, 802.1x/MAC-Auth }


Default:   Off
Enables or disables the port's security feature. Two types of port
access control are available:

Configuring Port Security 279


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description
• Static MAC address-based. With this method, authorized MAC
address(es) should be configured in the Static MAC Address
table. If some MAC addresses are not known in advance (or it is
not known to which port they will be connected), there is still
an option to configure the switch to auto-learn certain number
of MAC addresses. Once learned, they do not age out until the
unit is reset or the link goes down.
• IEEE 802.1X standard authentication.
• IEEE 802.1X with MAC-Authentication, also known as MAC-
Authentication Bypass. With this option, the device can
authenticate clients based on the client’s MAC address if IEEE
802.1X authentication times out.

Autolearn Synopsis:   1 to 16 or { None }


Default:   None
Only applicable when the 'Security' field has been set to 'Static
MAC'. It specifies maximum number of MAC addresses that can
be dynamically learned on the port. If there are static addresses
configured on the port, the actual number of addresses allowed
to be learned is this number minus the number of the static MAC
addresses.

Sticky Synopsis:   { No, Yes }


Default:   Yes
Only applicable when the 'Security' field has been set to 'Static
MAC'. Change the behaviour of the port to either sticky or non-
sticky.
If Sticky is 'Yes', MACs/Devices authorized on the port 'stick' to the
port and the switch will not allow them to move to a different
port.
If Sticky is 'No', MACs/Devices authorized on the port may move to
another port.

Shutdown Time Synopsis:   1 to 86400 s or { Until reset, Don't shutdown }


Default:   Don't shutdown
Specifies for how long to shut down the port, if a security
violation occurs.

Status Synopsis:   Any 31 characters


Describes the security status of the port.

NOTE
There are a few scenarios in which static MAC addresses can move:
• When the link is up/down on a non-sticky secured port
• When traffic switches from or to a non-sticky secured port

NOTE
Traffic is lost until the source MAC Address of the incoming traffic is authorized against the static
MAC address table.

4. Click Apply.

280 Configuring Port Security


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Section 5.10.4

Configuring IEEE 802.1X


To configure IEEE 802.1X port-based authentication, do the following:
1. Navigate to Network Access Control » Port Security » Configure 802.1X . The 802.1X Parameters table
appears.

Figure 207: 802.1X Parameters Table

2. Select an Ethernet port. The 802.1X Parameters form appears.

10 11

Figure 208: 802.1X Parameters Form


1. Port Box    2. tX Period Box    3. quietPeriod Box    4. reAuthEnabled Options    5. reAuthPeriod Box    6. reAuthMax Box   
7. suppTimeout Box    8. serverTimeout Box    9. maxReq Box    10. Apply Button    11. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Port Synopsis:   1/1 to maximum port number


Default:   1
The port number as seen on the front plate silkscreen of the
switch.

txPeriod Synopsis:   1 to 65535

Configuring IEEE 802.1X 281


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Parameter Description
Default:   30 s
The time to wait for the Supplicant's EAP Response/Identity packet
before retransmitting an EAP Request/Identity packet.

quietPeriod Synopsis:   0 to 65535


Default:   60 s
The period of time not to attempt to acquire a Supplicant after the
authorization session failed.

reAuthEnabled Synopsis:   { No, Yes }


Default:   No
Enables or disables periodic re-authentication.

reAuthPeriod Synopsis:   60 to 86400


Default:   3600 s
The time between periodic re-authentication of the Supplicant.

reAuthMax Synopsis:   1 to 10
Default:   2
The number of re-authentication attempts that are permitted
before the port becomes unauthorized.

suppTimeout Synopsis:   1 to 300


Default:   30 s
The time to wait for the Supplicant's response to the
authentication server's EAP packet.

serverTimeout Synopsis:   1 to 300


Default:   30 s
The time to wait for the authentication server's response to the
Supplicant's EAP packet.

maxReq Synopsis:   1 to 10
Default:   2
The maximum number of times to retransmit the authentication
server's EAP Request packet to the Supplicant before the
authentication session times out.

4. Click Apply.

Section 5.11

Managing Link Aggregation


Link aggregation, also referred to as port trunking or port bundling, provides the ability to aggregate or gather
several Ethernet ports into one logical link (port trunk) with higher bandwidth. This allows for highly randomized
load balancing between the aggregated links based on both the source and destination MAC addresses of the
forwarded frames.
Link Aggregation can be used for two purposes:
• To obtain increased, linearly incremental link bandwidth.
• To improve network reliability by creating link redundancy. If one of the aggregated links fails, the switch will
balance the traffic between the remaining links.

282 Managing Link Aggregation


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

1 2

Figure 209: Examples of Link Aggregation


1. Switch    2. Server

RUGGEDCOM ROS allows up to 15 port trunks to be configured on a single device, with each consisting of up to 8
ports.

NOTE
The maximum number of port trunks for each device depends on the number of ports available. At
least two ports are required to configure a port trunk.

NOTE
The aggregated port with the lowest port number is called the Port Trunk Primary Port. Other ports in
the trunk are called Secondary Ports.

CONTENTS
• Section 5.11.1, “Link Aggregation Concepts”
• Section 5.11.2, “Managing Port Trunks”

Section 5.11.1

Link Aggregation Concepts


The following section describes some of the concepts important to the implementation of link aggregation in
RUGGEDCOM ROS.

CONTENTS
• Section 5.11.1.1, “Rules and Limitations”

Link Aggregation Concepts 283


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

• Section 5.11.1.2, “Link Aggregation and Layer 2 Features”


• Section 5.11.1.3, “Link Aggregation and Physical Layer Features”

Section 5.11.1.1
Rules and Limitations
The implementation of link aggregation must adhere to the following rules and limitations:
• Each port can belong to only one port trunk at a time.
• A port mirroring target port can not be member of a port trunk. However, a port mirroring source port can be
member of a port trunk.
• If only one QinQ port is supported by the switch, the port working in QinQ mode cannot be a secondary
member of a port trunk.
• DHCP Relay Agent Client port cannot be a member of a port trunk.
• Load balancing between the links of a bundle is randomized and may not be ideal. For instance, if three 100
Mbs links are aggregated, the resulting bandwidth of the port trunk may not be precisely 300 Mbs.
• A Static MAC Address should not be configured to reside on an aggregated port – it may cause some frames
destined for that address to be dropped.
• A secure port cannot be a member of a port trunk.
• The IEEE 802.3ad Link Aggregation standard requires all physical links in the port trunk to run at the same speed
and in full-duplex mode. If this requirement is violated, the performance of the port trunk will drop.
The switch will raise an appropriate alarm, if such a speed/duplex mismatch is detected.
• STP dynamically calculates the path cost of the port trunk based on its aggregated bandwidth. However, if the
aggregated ports are running at different speeds, the path cost may not be calculated correctly.
• Enabling STP is the best way for handling link redundancy in switch-to-switch connections composed of more
than one physical link. If STP is enabled and increased bandwidth is not required, Link Aggregation should not
be used because it may lead to a longer fail-over time.

Section 5.11.1.2
Link Aggregation and Layer 2 Features
Layer 2 features (e.g. STP, VLAN, CoS, Multicast Filtering) treat a port trunk as a single link.
• If the Spanning Tree Protocol (STP) puts an aggregated port in blocking/forwarding, it does it for the whole port
trunk.
• If one of the aggregated ports joins/leaves a multicast group (e.g. via GMRP), all other ports in the trunk will
join/leave too.
• Any port configuration parameter (e.g. VLAN, CoS) change will be automatically applied to all ports in the trunk.
• Configuration/status parameters of the secondary ports will not be shown and their port numbers will be simply
listed next to the primary port number in the appropriate configuration/status UI sessions.
• When a secondary port is added to a port trunk, it inherits all the configuration settings of the primary port.
When this secondary port is removed from the port trunk, the settings it had previous to the aggregation are
restored.

284 Rules and Limitations


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

Section 5.11.1.3
Link Aggregation and Physical Layer Features
Physical layer features (e.g. physical link configuration, link status, rate limiting, Ethernet statistics) will still treat
each aggregated port separately.
• Physical configuration/status parameters will NOT be automatically applied to other ports in the trunk and will
be displayed for each port as usual.
• Make sure that only ports with the same speed and duplex settings are aggregated. If auto-negotiation is used,
make sure it is resolved to the same speed for all ports in the port trunk.
• To get a value of an Ethernet statistics counter for the port trunk, add the values of the counters for all ports in
the port trunk.

Section 5.11.2

Managing Port Trunks


The following section describes how to configure and manage port trunks.

CONTENTS
• Section 5.11.2.1, “Viewing a List of Port Trunks”
• Section 5.11.2.2, “Adding a Port Trunk”
• Section 5.11.2.3, “Deleting a Port Trunk”

Section 5.11.2.1
Viewing a List of Port Trunks
To view a list of port trunks configured on the device, navigate to Link Aggregation » Configure Port Trunks .
The Port Trunks table appears.

Figure 210: Port Trunks Table

If port trunks have not been configured, add trunks as needed. For more information, refer to Section 5.11.2.2,
“Adding a Port Trunk” .

Link Aggregation and Physical Layer Features 285


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Section 5.11.2.2
Adding a Port Trunk
To add a port trunk, do the following:

IMPORTANT!
The port trunk must be properly configured on both sides of the aggregated link. In switch-to-switch
connections, if the configuration of both sides does not match (i.e. some ports are mistakenly not
included in the port trunk), it will result in a loop. Therefore, the following procedure is strongly
recommended to configure a port trunk:
a. Disconnect or disable all the ports involved in the configuration, i.e. either being added to or
removed from the port trunk.
b. Configure the port trunk on both switches.
c. Double-check the port trunk configuration on both switches.
d. Reconnect or re-enable the ports.
If the port trunk is being configured while the ports are not disconnected or disabled, the port will be
automatically disabled for a few seconds.

1. Navigate to Link Aggregation » Configure Port Trunks . The Port Trunks table appears.

Figure 211: Port Trunks Table


1. InsertRecord

2. Click InsertRecord. The Port Trunks form appears.

286 Adding a Port Trunk


RUGGEDCOM ROS Chapter 5
User Guide Setup and Configuration

4 6

Figure 212: Port Trunks
1. Trunk ID Box    2. Trunk Name Box    3. Ports Box    4. Apply Button    5. Delete Button    6. Reload Button

3. Configure the following parameter(s) as required:

Parameter Description

Trunk ID Synopsis:   1 to 2
Default:   1
Trunk number. It doesn't affect port trunk operation in any way
and is only used for identification.

Trunk Name Synopsis:   Any 19 characters


Provides a description of the aggregated link purpose.

Ports Synopsis:   Any combination of numbers valid for this parameter


Default:   None
List of ports aggregated in the trunk.

4. Click Apply.

Section 5.11.2.3
Deleting a Port Trunk
To delete a port trunk, do the following:
1. Navigate to Link Aggregation » Configure Port Trunks . The Port Trunks table appears.

Deleting a Port Trunk 287


Chapter 5 RUGGEDCOM ROS
Setup and Configuration User Guide

Figure 213: Port Trunks Table

2. Select the port trunk from the table. The Port Trunks form appears.

4 6

Figure 214: Port Trunks Form


1. Trunk ID Box    2. Trunk Name Box    3. Ports Box    4. Apply Button    5. Delete Button    6. Reload Button

3. Click Delete.

288 Deleting a Port Trunk


RUGGEDCOM ROS Chapter 6
User Guide Troubleshooting

Troubleshooting
This chapter describes troubleshooting steps for common issues that may be encountered when using
RUGGEDCOM ROS or designing a network.

IMPORTANT!
For further assistance, contact a Customer Service representative.

CONTENTS
• Section 6.1, “General”
• Section 6.2, “Ethernet Ports”
• Section 6.3, “Spanning Tree”
• Section 6.4, “VLANs”

Section 6.1

General
The following describes common problems.
Problem Solution

The switch is not responding to ping Is the switch being pinged through a router? If so, the switch gateway address must be
attempts, even though the IP address and configured as well. The following figure illustrates the problem.
gateway have been configured. The switch
is receiving the ping because the LEDs are
flashing and the device statistics are logging
the pings. What is going on? 1 2 3

192.168.0.1 10.10.0.2

10.10.0.1
192.168.0.2

Figure 215: Using a Router As a Gateway


1. Work Station    2. Router    3. Switch

The router is configured with the appropriate IP subnets and will forward the ping from the
workstation to the switch. When the switch responds, however, it will not know which of its
interfaces to use in order to reach the workstation and will drop the response. Programming
a gateway of 10.0.0.1 will cause the switch to forward unresolvable frames to the router.
This problem will also occur if the gateway address is not configured and the switch tries to
raise an SNMP trap to a host that is not on the local subnet.

General 289
Chapter 6 RUGGEDCOM ROS
Troubleshooting User Guide

Section 6.2

Ethernet Ports
The following describes common problems related to Ethernet ports.
Problem Solution

A link seems fine when traffic levels are low, A possible cause of intermittent operation is that of a ‘duplex mismatch’. If one end of the
but fails as traffic rates increase OR a link can link is fixed to full-duplex and the peer auto-negotiates, the auto-negotiating end falls back
be pinged but has problems with FTP/SQL/ to half-duplex operation.
HTTP/etc. At lower traffic volumes, the link may display few if any errors. As the traffic volume
rises, the fixed negotiation side will begin to experience dropped packets while the auto-
negotiating side will experience collisions. Ultimately, as traffic loads approach 100%, the
link will become entirely unusable.
The ping command with flood options is a useful tool for testing commissioned links. The
command ping 192.168.0.1 500 2 can be used to issue 500 pings each separated by
two milliseconds to the next switch. If the link used is of high quality, then no pings should
be lost and the average round trip time should be small.

Links are inaccessible, even when using the Make sure LFI is not enabled on the peer as well. If both sides of the link have LFI enabled,
Link Fault Indication (LFI) protection feature. then both sides will withhold link signal generation from each other.

Section 6.3

Spanning Tree
The following describes common problems related to the Spanning Tree Protocol (STP).
Problem Solution

The network locks up when a new port is Is it possible that one of the switches in the network or one of the ports on a switch in the
connected and the port status LEDs are network has STP disabled and accidentally connects to another switch? If this has occurred,
flashing rapidly. then a traffic loop has been formed.
If the problem appears to be transient in nature, it is possible that ports that are part of the
Occasionally, the ports seem to experience
spanning tree have been configured as edge ports. After the link layers have come up on
significant flooding for a brief period of time.
edge ports, STP will directly transition them (perhaps improperly) to the forwarding state.
A switch displays a strange behavior where If an RSTP configuration message is then received, the port will be returned to blocking. A
the root port hops back and forth between traffic loop may be formed for the length of time the port was in forwarding.
two switch ports and never settles down. If one of the switches appears to flip the root from one port to another, the problem may be
one of traffic prioritization. For more information refer to "The network becomes unstable
when a specific application is started."
Another possible cause of intermittent operation is that of an auto-negotiation mismatch.
If one end of the link is fixed to full-duplex mode and the peer auto-negotiates, the auto-
negotiating end will fall back to half-duplex operation. At lower traffic, the volumes the
link may display few if any errors. As the traffic volume rises, the fixed negotiation side
will begin to experience dropped packets while the auto-negotiating side will experience
collisions. Ultimately, as traffic loads approach 100%, the link will become entirely unusable.
At this point, RSTP will not be able to transmit configuration messages over the link and
the spanning tree topology will break down. If an alternate trunk exists, RSTP will activate it
in the place of the congested port. Since activation of the alternate port often relieves the
congested port of its traffic, the congested port will once again become reliable. RSTP will
promptly enter it back into service, beginning the cycle once again. The root port will flip
back and forth between two ports on the switch.

A computer or device is connected to a Is it possible that the RSTP edge setting for this port is set to false? If Edge is set to false, the
switch. After the switch is reset, it takes a bridge will make the port go through two forward delay times before the port can send or
long time for it to come up. receive frames. If Edge is set to true, the bridge will transition the port directly to forwarding
upon link up.

290 Ethernet Ports


RUGGEDCOM ROS Chapter 6
User Guide Troubleshooting

Problem Solution
Another possible explanation is that some links in the network run in half-duplex mode.
RSTP uses a peer-to-peer protocol called Proposal-Agreement to ensure transitioning in the
event of a link failure. This protocol requires full-duplex operation. When RSTP detects a
non-full duplex port, it cannot rely on Proposal-Agreement protocol and must make the port
transition the slow (i.e. STP) way. If possible, configure the port for full-duplex operation.
Otherwise, configure the port’s point-to-point setting to true.
Either one will allow the Proposal-Agreement protocol to be used.

When the switch is tested by deliberately Is it possible that some ports participating in the topology have been configured to STP mode
breaking a link, it takes a long time before or that the port’s point-to-point parameter is set to false? STP and multipoint ports converge
devices beyond the switch can be polled. slowly after failures occur.
Is it possible that the port has migrated to STP? If the port is connected to the LAN segment
by shared media and STP bridges are connected to that media, then convergence after link
failure will be slow.
Delays on the order of tens or hundreds of milliseconds can result in circumstances where
the link broken is the sole link to the root bridge and the secondary root bridge is poorly
chosen. The worst of all possible designs occurs when the secondary root bridge is located
at the farthest edge of the network from the root. In this case, a configuration message will
have to propagate out to the edge and then back in order to reestablish the topology.

The network is composed of a ring of A properly operating unmanaged bridge is transparent to STP configuration messages. The
bridges, of which two (connected to managed bridges will exchange configuration messages through the unmanaged bridge
each other) are managed and the rest are part of the ring as if it is non-existent. When a link in the unmanaged part of the ring fails
unmanaged. Why does the RSTP protocol however, the managed bridges will only be able to detect the failure through timing out of
work quickly when a link is broken between hello messages. Full connectivity will require three hello times plus two forwarding times to
the managed bridges, but not in the be restored.
unmanaged bridge part of the ring?

The network becomes unstable when a RSTP sends its configuration messages using the highest possible priority level. If CoS is
specific application is started. The network configured to allow traffic flows at the highest priority level and these traffic flows burst
returns to normal when the application is continuously to 100% of the line bandwidth, STP may be disrupted. It is therefore advised
stopped. not to use the highest CoS.

When a new port is brought up, the root Is it possible that the port cost is incorrectly programmed or that auto-negotiation derives an
moves on to that port instead of the port it undesired value? Inspect the port and path costs with each port active as root.
should move to or stay on.

An Intelligent Electronic Device (IED) or Certain low CPU bandwidth controllers have been found to behave less than perfectly when
controller does not work with the device. they receive unexpected traffic. Try disabling STP for the port.
If the controller fails around the time of a link outage, there is the remote possibility that
frame disordering or duplication may be the cause of the problem. Try setting the root port
of the failing controller’s bridge to STP.

Polls to other devices are occassionally lost. Review the network statistics to determine whether the root bridge is receiving Topology
Change Notifications (TCNs) around the time of observed frame loss. It may be possible there
are problems with intermittent links in the network.

The root is receiving a number of TCNs. Examine the RSTP port statistics to determine the port from which the TCNs are arriving.
Where are they coming from? Sign-on to the switch at the other end of the link attached to that port. Repeat this step until
the switch generating the TCNs is found (i.e. the switch that is itself not receiving a large
number of TCNs). Determine the problem at that switch.

Section 6.4

VLANs
The following describes common problems related to the VLANs.

VLANs 291
Chapter 6 RUGGEDCOM ROS
Troubleshooting User Guide

Problem Solution

VLANs are not needed on the network. Can Yes. Simply leave all ports set to type edge and leave the native VLAN set to 1. This is the
they be turned off? default configuration for the switch.

Two VLANs were created and a number of If the devices need to communicate at the physical address layer, they must be members of
ports were made members of them. Now the same VLAN. If they can communicate in a Layer 3 fashion (i.e. using a protocol such as IP
some of the devices in one VLAN need to or IPX), use a router. The router will treat each VLAN as a separate interface, which will have
send messages to devices in the other VLAN. its own associated IP address space.

On a network of 30 switches, management At the switch where the management station is located, configure a port to use the new
traffic needs to be restricted to a separate management VLAN as its native VLAN. Configure a host computer to act as a temporary
domain. What is the best method for doing management station.
this while staying in contact with these At each switch, configure the management VLAN to the new value. Contact with each
switches? individual switch will be lost immediately as they are being configured, but it should be
possible re-establish communication from the temporary management station. After all
switches have been taken to the new management VLAN, configure the ports of all attached
management devices to use the new VLAN.

NOTE
Establishing a management domain is often accompanied with the
establishment of an IP subnet specifically for the managed devices.

You might also like