Itaan Pharma Offer For HVAC - R0 - 27.05.22 (1) - 15
Itaan Pharma Offer For HVAC - R0 - 27.05.22 (1) - 15
Itaan Pharma Offer For HVAC - R0 - 27.05.22 (1) - 15
1.1.2 Ducting work(22G) 1925 Sq.M 1,072 INR 20,63,600 240 INR 4,62,000
1.1.3 Ducting work(24G) 3575 Sq.M 877 INR 31,35,275 240 INR 8,58,000
1.1.4 Duct Leak test 3300 Sq.M 60 INR 1,98,000
Flexible Duct: Flexible round duct shall consistof inner and outer Aluminum jacket with fiberglass insulation and reinforcement suitable for connecting HEPA
1.2
Modules with spigot arrangement.
1.2.1 Flexible Duct Ø250 mm 310 RMT 310 INR 96,100 120 INR 37,200
1.2.2 Round rings/ Ties suitable for fixing flexible duct with clamps 225 Nos 700 INR 1,57,500 120 INR 27,000
1.2.3 Round collar ducts Ø250 mm 225 Nos 225 INR 50,625 120 INR 27,000
Thermal insulation for GI ducting: Insulation material - Chemically / Physically cross linked polyethylene (XLPE) class 'O' with factory laminated aluminium foil
installed with manufacturer recommended adhesive solution. All joints of insulation should be cover with minimum 3 inch width aluminum tape.
1.3
Make: Thermobreak / Armacell / supreme
1.3.1 Supply air duct - 19mm XLPE 2530 Sq.M 500 INR 12,65,000 144 INR 3,64,320
1.3.2 Return air duct - 13mm XLPE 3975 Sq.M 415 INR 16,49,625 144 INR 5,72,400
2 DUCTING ACESSORIES
Terminal HEPA fiter module: Supply, Installation of false ceiling mountable terminal HEPA filter housing with H-14 (EU-14) HEPA filter. Terminally mounted H-
14 HEPA filter with Gelseal type.Filter frame and housing shall be in extruded aluminium construction minimum 16 G thick, with diffuser plate,16 G SS 304
Perforated sheet and aluminium extruded volume control damper (shall be operated above false ceiling) . The filter holding clamp/knife edge shall be made
2.1 from anodised aluminum or suitable and fastened with nuts and retention tabs made from SS304.The filter module shall be provided with aerosol sample port,
aerosol injection port & differential pressure measuring port across the filter. Loading of the filter shall be from bottom
HEPA Make: Freudenberg / AAF
2.1.1 610 mm x 610 mm / 1000 CFM 85 Set 40,133 INR 34,11,305 960 INR 81,600
2.1.2 457 mm x 457 mm / 560 CFM 15 Set 29,476 INR 4,42,140 960 INR 14,400
2.1.3 305 mm x 305 mm / 250 CFM 7 Set 20,280 INR 1,41,960 960 INR 6,720
Supply and Return Air Diffuser: Extruded aluminium powder coated Diffuser with aluminium box type volume control damper. Dampers should be constructed
in anodized aluminium finished with powder coating. They should have aerofoil design for minimum pressure drop. The dampers should be air tight. The
damper are certified and approved to DIN 1946 Part 4, with opposed blades, distortion- free hollow profile aluminium fins, sealed with special rubber lips.
2.2
Bearing should be made of polyamide. The gear wheels for the drive should be located outside the air stream. The manually operated dampers should be
provided with locking arrangementthat remain perfectally locked at all conditions.
Make: Systemair/Equivalent
2.2.1 450 mm x 450 mm 295 Nos 2,000 INR 5,90,000 720 INR 2,12,400
2.2.1 300 mm x 300 mm 24 Nos 1,525 INR 36,600 720 INR 17,280
Smoke / Fire Damper: Fire dampers should be installed in Supply and return air duct and should have 90 minutes fire rating. closure Rating UL 555.The
construction of the damper should be in 16 G GI. Fire damper shall have FLP limit switch type and connected to DCS with interlock to blower. (wiring between
2.3
Limit switch and starter panel by client)
Make: SystemAir/Equivalent
2.3.1 Dampers 35 Sq.M 9,500 INR 3,32,500 1,800 INR 63,000
2.3.2 Supply /Installation/ Testing / Commissioning of fusible links 44 Nos 755 INR 33,220 60 INR 2,640
2.3.3 Limit Switches 44 Nos 1,450 INR 63,800 144 INR 6,336
2.4 BOX RETURN RISERS:Supply /Installation/ Testing / Commissioning 18G GI Powder Coated box Return Air Raisers with Damper and SS 304 Perforated Grills
2.4.3 Return raiser-R1(950mmX200mmX3000mm) 15 Nos 8,100 INR 1,21,500 2,281 INR 34,215
2.4.4 Return raiser-R1(950mmX200mmX2800mm) 8 Nos 8,100 INR 64,800 2,138 INR 17,104
2.4.5 Return raiser-R2(750mmX200mmX3000mm) 1 Nos 5,200 INR 5,200 1,884 INR 1,884
2.4.7 Return raiser-R3(650mmX150mmX3000mm) 1 Nos 5,200 INR 5,200 1,587 INR 1,587
2.4.8 Return raiser-R3(650mmX150mmX2800mm) 7 Nos 5,200 INR 36,400 1,487 INR 10,409
2.4.9 Return raiser-R4+(500mmX350mmX3000mm) 1 Nos 5,200 INR 5,200 1,686 INR 1,686
2.4.9 Return raiser-R4(500mmX150mmX3000mm) 8 Nos 5,200 INR 41,600 1,289 INR 10,312
2.4.10 Return raiser-R4(500mmX150mmX2800mm) 17 Nos 5,200 INR 88,400 1,209 INR 20,553
2.4.11 Return raiser-R5(500mmX150mmX2800mm) 4 Nos 5,200 INR 20,800 1,209 INR 4,836
2.4.12 Return raiser-R6(500mmX150mmX2800mm) 5 Nos 5,200 INR 26,000 1,209 INR 6,045
SS Grills For Panel Return Risres: Supply, Installation, Testing and Commissioning of SS 304 with matt finish perforated grills flush with wall pannel with
2.5 dome bolts fitting.
Make: Systemair / Equivalent
2.5.1 Crossection area 10 Sq.M 14,616 INR 1,46,160 1,800 INR 18,000
HVAC BOQ
Dampers: Dampers should be constructed in anodized aluminium finished with powder coating. They should have aerofoil design for minimum pressure drop.
The dampers should be air tight. The damper are certified and approved to DIN 1946 Part 4, with opposed blades, distortion- free hollow profile aluminium fins,
sealed with special rubber lips. Bearing should be made of polyamide. The gear wheels for the drive should be located outside the air stream. Risers Damper
2.6
blade thickness shall be 1.6 mm .Damper operating Handle side rubber gasket /Rubber Bush fixing for air locking. The manually operated dampers should be
provided with locking arrangementthat remain perfectally locked at all conditions.
Make: Systemair / Equivalent
2.6.1 crossection area 40 Sq.M 12789 INR 5,11,560 1,800 INR 72,000
SUPPLY AIR GRILL:Extruded aluminium powder coated double deflection type grilles with aluminium box type volume control damper Make: Systemair
2.7
/ Equivalent
2.7.1 Dampers crossection area 8 Sq.M 10962 INR 87,696 1,800 INR 14,400
Return AIR GRILL:Extruded aluminium powder coated single deflection type grilles with aluminium box type volume control damper Make: Systemair
2.8
/ Equivalent
2.8.1 Dampers crossection area 8 Sq.M 5,875 INR 47,000 1,800 INR 14,400
Back Draft Dampers: Back Draft Damper with frame and blade are in extruded aluminium construction.It should prevent the reverse airflow.The damper to be
2.9 opened by air pressuredifferential and closed by gravity
Make: Systemair / Equivalent
2.9.1 crossection area 10 Sq.M 7000 INR 70,000 1,800 INR 18,000
FRESH AIR LOUVERS: Box type Fresh air intake louver made of 18 G GI powder coated sheet with G3 filter. Louvers shall be complete with all necessary
2.10 mounting arrangements.
Make: Systemair / Equivalent
2.10.1 crossection area 10 Sq.M 9250 INR 92,500 2,160 INR 21,600
3 MISCELLANEOUS
3.1 INLINE FAN:
Cabinet type Inline Fan complete with G4 filters and all necessary duct mounting arrangement.
Make: Systemair
EX.Tag No. Airflow CFM SP mm of WG
3.1.1 EX-001 1705 50 1 Nos 46869 INR 46,869 3,000 INR 3,000
3.1.2 EX-002 562 50 1 Nos 37283 INR 37,283 3,000 INR 3,000
3.1.3 EX-003 562 50 1 Nos 37283 INR 37,283 3,000 INR 3,000
INR 1,49,60,701 INR 32,26,327
A Basic Value
INR 1,81,87,028
B Packing Charges 0% INR 0
C Freight Charges INR 0
Total (A+B+C) INR 1,81,87,028
Taxes , as appicable INR 0
Grand Total (Including Taxes) INR 1,81,87,028
Note:
1. Any extra material at site and not installed need to be taken back by the bidder. The cost of all transportation etc. is in the
2. Unloading of material at site and internal shifting at the time of installation is in the bidder's scope
3. Billing will be done as per site measurements
4. Vendor should provide Execustion Drawings with execution BOQ before supply/execution
5. All MOC certificates should be provided along with Material
6. Vendor has to provide Asbuilt Drawings
Reference Documents:
1.QPS-FD-21-1233-STD_H002 Ducting & Acessories DATA SHEET