Turbo-Seal Insulated Gen2 Install 2016-10-10 - 0
Turbo-Seal Insulated Gen2 Install 2016-10-10 - 0
Turbo-Seal Insulated Gen2 Install 2016-10-10 - 0
Turbo-Seal ®
Insulated Gen 2
Installation Manual
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
MATERIAL, TOOLS, AND EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
ADDITIONAL REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
UNCRATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
ANCHORING METHODS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SIDE COLUMNS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
HEAD ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ANCHOR PLATES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
COUNTERWEIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
JUNCTION BOX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
ANTENNA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ENCODER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
DOOR SEALING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Close-Limit Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Open-Limit Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Rear. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
PHOTO EYES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Rear. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Testing Photo Eyes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
AIR BLOWER (DOOR OPENING Ht ≤ 16 ft) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
RAD 3 BLOWER (DOOR OPENING Ht > 16 ft) . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
1
INSTALLATION—MATERIAL, TOOLS, AND EQUIPMENT
INSTALLATION Electrician’s Responsibilities
MATERIAL, TOOLS, AND EQUIPMENT For complete details on the responsibilities of the
electrician, refer to the Rytec System 4 Drive &
1. Threaded rod (¹/₂-in. diameter) and other various
Control Installation, Owner’s Manual, & Door Specific
wall anchor hardware and material. Concrete
Electrical Schematic.
Anchor bolts (¹/₂-in. diameter). (See
“ANCHORING METHODS” on page 3) 1. Install fused disconnect and Rytec control panel.
(See Figure 2 for typical installation)
2. Assorted shim stock. (See Figure 10)
2. Install all necessary conduit tubing.
3. Double-sided tape (to temporarily hold shims).
NOTE: Separate conduit must be run for high and
4. Carpenter’s or spirit level (4-ft. minimum length). low voltage wiring.
5. Carpenter’s square. 3. Run electrical power lines to disconnect.
6. Fish tape. 4. Run power lines from disconnect to control panel.
7. Hammer drill. 5. Run power lines from control panel to junction
8. Masonry drill bit (for ¹/₂-in. diameter anchors). box(s) and door.
9. Three or four bar clamps (48-in. long). 6. Run power lines from control panel to door motor.
10. Four 12” C-clamps. 7. Run low-voltage cables from control panel to
door.
11. Pencil or Marker.
8. Wire low-voltage safety devices and activators (if
12. Hammer or mallet and blocks of wood. used).
13. Crowbar or pry bar. Run high and low voltage wires/cables in separate
14. Assorted hand tools (pliers, tape measure, etc.). metal conduit to the bottom of the System 4 control
panel.
15. Socket and wrench sets.
All wires/cables must be cut to length. DO NOT leave
16. Water level, line level, or transit. excess wire/cable loops on the door or in the control
17. Two ladders (taller than height of door opening). panel. Excess wires/cables can cause problems.
2
INSTALLATION—GENERAL ARRANGEMENT OF DOOR COMPONENTS
GENERAL ARRANGEMENT OF DOOR
COMPONENTS
Figure 2 shows the location of the major components
of the door and the general placement of the
associated subassemblies for a typical installation.
This illustration is provided to you for informational
purposes only. It should not be relied upon solely
during the installation of your door and its sub-
assemblies.
Center
Head Assembly Buck
(Includes Drive Motor
Gearbox Assembly)
Figure 3
Door Panel
System 4 Lifting Pockets ANCHORING METHODS
Control
Panel Correct anchoring of the side columns to the wall and
the floor is important for the smooth and safe
operation of the door. The wall material should be
strong enough to support the weight of the door and
all wall anchors.
Figure 4 through Figure 7 show anchoring methods
Blowers/Air
Curtain for various types of walls. Use the method that is best
suited for your particular installation site.
Bottom Bar All necessary anchoring hardware and material
Fused Assembly
Disconnect
required for the installation of this door are the
responsibility of the door owner. If you have any
questions, call your Rytec representative or the Rytec
Technical Support Department at 800-628-1909.
Left Side Column with Heated Blower
(Includes Serial Number Plate, NOTE: Use ¹/₂-in. diameter threaded through bolts or
Counterweight, and Patchwatch LED) ¹/₂-in. diameter threaded rods to anchor the
Right Side Column with Heated Blower door to all wall applications. Use ¹/₂-in.
(Includes Serial Number Plate, diameter concrete anchor bolts to anchor
Counterweight, and Patchwatch LED)
the door to a concrete floor.
Figure 2
NOTE: Figure 2 shows the front side of the door. If expansion anchors are used, a quarterly
Left and right are determined when viewing inspection should be implemented for safe
the front side of the door. and secure door operation.
Your Rytec door has been crated to allow for minimal Concrete
handling of assemblies during the installation Wall Side
process. Column
NOTE: Remove parts and sub-assemblies Expansion
from the shipping crate in the order Anchor
directed throughout this manual.
1. Remove the top of the crate.
2. Remove the front of the crate. (See Figure 3) A0500005
Figure 4
Through Bolt or
A0500037 Threaded Rod
or Figure 5
Threaded
Centerline
Rod
Insulated Wall of Opening
Insulated
Wall
Overall Width of
Door Opening
Half Width of
Door Opening
A0500001
Through Bolt or or
Figure 8
Threaded Rod Threaded
Aluminum-Clad Lumber (Front Rod
LOCATING SIDE COLUMNS
and Back Sides — Full Length)
A0500039 1. Locate the layout drawing of the door. It should
or Figure 6
be attached to the small parts carton packed
Threaded inside the shipping crate. This drawing identifies
Rod the production width of your door. Verify the
Insulated dimension provided by measuring the width
Wall (length) of the head assembly.
Side
Column 2. Using the centerline as a reference point, lay out
and mark half of the door’s production width
along the floor. (See Figure 9)
Through Bolt or
Threaded Rod
Aluminum-Clad Lumber This door is equipped with a breakaway
(Back Side — Full Length) bottom bar assembly. To ensure that it works
A0500038
or properly, the width of the door opening must
Figure 7
Threaded not be smaller (narrower) than the
Rod production width of the door. If the width of
the opening is narrower than the width of the
door, do not proceed with the installation.
Contact your Rytec representative or the
Rytec Technical Support Department at 800-
628-1909.
4
INSTALLATION—SIDE COLUMNS
5. Use a plumb bob or carpenter’s level to check the
Half of Door Centerline of wall for plumb in the areas where the side
Production Width Opening columns are to be mounted. Also, inspect the wall
for any obstructions.
If the wall is not plumb, shims must be used as
required @ each side column fastener. If you find
an obstruction, remove it or shim the column to
avoid the obstruction. (See Figure 10 and Figure
11)
This Dimension Must
Be Equal on Both
Extend and Mark Sides of Door Opening
Edges of Door Along Floor
A0500002
or Figure 9 Shim
Threaded (if required)
With a carpenter’s square placed against the wall,
3.Rod
mark both sides of the door along the floor.
Extend the line along each edge.
4. Check the floor for level across the door opening.
The floor must be level within 0.12 in. from side –
to - side. If one side of the opening is higher than
the other, a shim under the low side column will
be required.
Figure 10 and Figure 11 show two methods that Water Level
Shim
can be used to ensure level side columns. (if required)
A0500004
NOTE: Contact the Rytec Technical Department if or
Threaded Figure 11
the floor is more than 1 in. out of level.
Rod
SIDE COLUMNS
Line Level The following procedure details the installation of the
side columns.
Shim
(if required)
This Dimension Must 1. Remove the blocking from the head assembly
Be Equal on Both buck in the middle of the shipping crate to gain
Sides of Door Opening access to the side columns. (See Figure 3)
Shim 2. Remove the side columns from the shipping
A0500003 (if required) crate. Remove the covers from the side columns
or Figure 10 by removing the screws that hold the covers in
Threaded place. Save all hardware and covers for
Rod
reassembly for each one. Do not mix the parts up.
3. Stand one side column on the floor. Place it
against the wall on the appropriate side of the
door opening (i.e. left on left side, right on the
right side), just outside the line indicating the
production width of the door. Use clamps as
needed. (See Figure 12)
5
INSTALLATION—SIDE COLUMNS
IMPORTANT: It is critical that the side columns
are mounted square and plumb
with the wall and level across the
door opening. Utilizing a 4-foot
level and carpenter’s square to
check this will help ensure the
columns are correctly set. Place
shims as necessary. Carpenter’s
Level
Additionally, using bar clamps to
temporarily secure the side
columns to the wall will allow you Anchor Points
make slight adjustments during the
installation process.
Right Side
Column
6
INSTALLATION—HEAD ASSEMBLY
NOTE: Personal injury or equipment damage
may result from the head assembly
Side Columns Must
not being secured when being lifted.
Be Plumb On Both
Side and Front
Horizontal Measurements
The head assembly is extremely heavy;
Must Be Equidistant.
use proper lifting and support equipment
when removing it from the crate. Personal
injury may result from using improper
handling procedures.
Secure the head assembly to the forklift
prior to lifting it to the top of the side
columns.
NOTE: To prevent damage to the door
Diagonal components, use cloth or packing
Measurements Must material between the forks and the
Be Equidistant head assembly. Pay close attention to
the foam door panel.
2. Secure the head assembly with C-clamps and a
Horizontal Measurements strap around the front spreader, door panel
Must Be Equidistant. drum, and the idler drum to the forks of the forklift
or mechanical lift before lifting it into position. C-
clamps should be used on both sides of the front
spreader to secure the head in place. (See
A87000XX Figure 16 - 18)
Figure 14
HEAD ASSEMBLY
1. Remove the head assembly from the crate. Using
a fork lift, guide the forks into the slots in the front
of the head assembly making sure that the forks
are below the panel and idler drum. The lifting
slots are provided to aid in lifting the head and
preventing damage to the foam panel, drum, and
head assembly. (See Figure 15 and Figure 16)
Figure 16
Straps
Forks
Figure 15
7
INSTALLATION—HEAD ASSEMBLY
Block 3/8-16UNC UNI-
Material STRUT NUTS
Clamps
Forks
Figure 18 Cutout shown
for clarity only
3. Insert the grommet with the Pathwatch LED and
Photo eye wires running through it into the slot in
the side column as shown.
4. With the head assembly safely secured to the
forklift, raise it up above the door to mount to the 3/8-16UNC x 1-1/4 LG Plug, Top
SERRATED FLANGE SCREWS Insulation
side columns. Guide the head in toward the wall
while keeping the side column edges clear of the Figure 20 (Broken out view for clarity)
head assembly mating edges and wires exiting 7. With the head assembly snugly bolted in place to
the top of the side columns. Line up the mating the side columns, check the overall plumb and
holes on the head assembly with the fastener squareness of the overall assembly (side
holes in the side columns. (See Figure 18 - Figure columns and head). Compare the diagonal
20) measurements and the upper and lower
horizontal measurements across the columns.
Grommet The columns are square and parallel when the
diagonal measurements are equal and the
horizontal measurements are equal. Check the
head for level and plumb.
8. Mount and secure the Top Rear Spreader Brush
Holes for Pathwatch LED and Photo Seal in between the side columns as shown. Use
securing eye wires in Grommet alternating fastener holes. (See Figure 21)
wires, etc.
Spreader
Weather Seal
Brush
Seal Assy.
Figure 19
6. Next align and fasten the head assembly to the 9. Once the assembly is set plumb and square,
opposite side column just like in the previous finish fully anchoring the loose side column to the
steps. DO NOT completely tighten the fasteners. wall.
Adjustments will need to be made yet. (See 10. Tighten the fasteners and secure the head
Figure 20) assembly to the side columns.
9
INSTALLATION—COUNTERWEIGHTS
3. Place a counterweight in the bottom of each side
column as shown, positioning it so it will not fall.
(See Figure 23)
COUNTERWEIGHT
MOUNTING PLATE
COUNTERWEIGHT
GUIDE PLATE
COUNTERWEIGHT
Figure 25
Figure 23
6. Securely tighten the mounting plate and guide
NOTE: For clarity, the side column extrusion is shown plate to the counterweights with (2) ³/₈-16 UNC x
with a cut to show counterweight placement. 1-1/2 Long hex head cap screws and (2) ³/₈ in. flat
4. Place the counterweight guide plate into the side washers. (See Figure 25)
column by rotating the plate sideways and orienting 7. Remove the plastic tie from each counterweight
it as shown with the wide end toward the front. strap. (See Figure 26)
(See Figure 24)
NOTE: Door must be in the fully open position.
COUNTERWEIGHT
STRAP SPOOL
HORIZONTALLY
ROTATE INTO
POSITION
WIDE END
IN FRONT
IDLER DRUM
ZIP TIE
COUNTERWEIGHT
STRAP
Figure 26
GUIDE PLATE
8. Route the counterweight strap over the idler
Figure 24 pulley and feed down into the side column
5. Set mounting plate on top of the guide plate. assembly as shown. (See Figure 26)
(See Figure 24) NOTE: The counterweight strap is installed at the
factory. The factory standard is three pre-
wraps around the counterweight spool.
9. With the strap hanging straight, route the straps
through the clamp bars as shown. Note that it
goes in on the front side-center of the
counterweight. Remove any slack in the strap(s) and
attach it to the counterweight using (2) ³/₈-16 UNC
x 1-1/2” Long hex head cap screws and clamp
bars. (See Figure 27)
10
INSTALLATION — COUNTERWEIGHTS
15. Completely loosen the clamp bars from the
HEX HEAD COUNTERWEIGHT counterweight straps so the door may travel freely.
SCREWS STRAP
Once again move the door but this time to its fully
CLAMP BARS open position. This should be when the door panel
bottom bar is at least level or just above the top door
COUNTERWEIGHT jam. Remove any slack in the strap(s) and retighten
MOUNTING PLATE
the clamp bars to secure each strap again.
16. Carefully remove the support block from under
FRONT
SIDE each counterweight to allow the weights to hang
REAR/ free. If necessary, readjust the straps.
MOUNTING
SIDE
17. Reinstall the counterweights bottom mounting plate
COUNTERWEIGHT and guide plate. Orient them as shown and
GUIDE PLATE
identically to the top ones with the wide end of the
guide toward the front of the side column. Close
COUNTERWEIGHT the door. (See Figure 28)
COUNTERWEIGHT STRAP ASSEMBLY (RH SHOWN)
IMPORTANT: The 8 to 10 in. mounting height for
Figure 27 each counterweight, as indicated
10. Tighten the clamp bars to secure each strap. in Figure 27, is adequate for most
Turbo-Seal Insulated Doors.
11. Repeat steps 4-10 for the opposing side However, for extra-wide or -short
counterweight. doors, the counterweights may
12. Remove the zip ties securing the door panel to have to be adjusted closer to the
the idler drum. Release the motor brake and bottom of the side column.
using the hand crank, lower the door panel and To check the position of each
raise the counterweights about 18” while guiding counterweight, first release the
the panel into the side columns. motor brake by pulling on the brake
release cable. Then manually move
13. Securely block each counterweight above the
the door to its fully closed position.
bottom of the side column by the same amount:
The minimum clearance between
8 to 10 inches. (See Figure 28)
the top of each counterweight and
the bottom face of the top
COUNTERWEIGHT insulation plug of its associated
GUIDE PLATE side column must be at least 2 in.
(See Figure 20)
If adjustment is necessary, move
the door to the fully open position.
After placing a support block under
the counterweight, readjust the
COUNTERWEIGHT strap, as required, until the 2-in.
MOUNTING PLATE clearance is achieved.
8”-10”
18. Route the side column heater power cord in the
side column. Refer to the “Side Column Heated
Blower”.
19. Install the counterweight crash plates.
Figure 28 20. Attach the mating side column covers using the
NOTE: For photo purpose, the counterweight bottom saved hardware as they were originally attached.
mounting plate and guide plate are shown and JUNCTION BOX
should NOT be installed at this time.
14. Release the motor brake and lower the The junction box is shipped loose in the shipping
counterweight onto the blocking and move the crate and needs to be mounted separate of the doors
door to the full open position. head assembly.
1. Locate, identify, & remove junction box from the
crate.
11
INSTALLATION— ANTENNA, ENCODER, DOOR SEALING
2. Orient the Junction Box assembly as shown. 4. Install the antenna bracket assembly to the front
Mount the J-Box assembly with appropriate spreader with (2) 10-24NC x ¾” long hex flanged
fasteners/anchors for the wall construction. Allow slotted machine screws. Fastener hardware is
ample room for access to the J-Box, Bearings, located in the small parts carton. (See Figure 30)
Motor & the head assembly. (See Figure 29)
5. Route the antenna wire along the front spreader
Mounting J-Box to the motor encoder and connect it as
Holes Assembly documented in that section. (See Figure 30)
NOTE: To secure antenna cable, use plastic ties
as required.
ENCODER
1. Install the Feig encoder hub shaft end to the end
Head of the encoder coupling shaft and tighten set
Assembly- screw plate. The Feig encoder hub can be found
Drive Side in the small parts carton.
NOTE: The Eurodrive washer, split lock washer, and
encoder coupling shaft are factory installed on
Motor Assy not
shown for clarity
the gearbox. Use a mild thread locker on set
screw.
Figure 29
2. Install encoder mounting plate with encoder
ANTENNA using four M8 x 1.25 x 18 mm socket head cap
screws.
IMPORTANT: The antenna is a fragile and highly
sensitive instrument. Extreme care 3. Connect the encoder cable to the encoder.
should be used in handling this
piece of equipment. 4. Install plastic zip tie into socket head screw and
secure the encoder cable. (See Figure 31)
1. Remove antenna from small parts carton.
NOTE: The zip tie that is used to secure the
2. Carefully remove packing material from antenna. encoder cable is of special design. The
Inspect for damage. ribbed end inserts into the valley of the
NOTE: Do not install antenna if it is found to be socket head cap screw.
damaged. Call your local Rytec All hardware is located in the small parts
representative or the Technical Support carton.
Department at 800-628-1909 for a
replacement. Socket
Head
Screw
3. Locate and identify the insert nuts for mounting
the antenna bracket assembly. They are on the To/From Wireless
Encoder Antenna
lower inside of the front spreader on the drive Mounting
Plate
side. (See Figure 30)
Zip Split Lock
Tie Washer
Encoder
ANTENNA Feig
BRACKET Encoder
ASSEMBLY Hub Shaft
Encoder
Coupling
Shaft Eurodrive
INSERT NUT Washer
FASTENERS
HEX SLOTTED
FLANGED
SCREWS
A9800016
Figure 30
Figure 31
12
INSTALLATION—CONTROL PANEL & ELECTRICAL CONNECTIONS, DOOR OPEN &
CLOSE LIMITS
DOOR SEALING side column, as well as conduit running
from the control box to the floor, is provided
Foam insulation is built into the side column. The
by the door owner/installer or the
insulation is a technical and important item in the
electrician. All wiring and conduit must
proper operation of the Turbo-Seal Insulated Door.
meet all local and state codes. Wires
From the moment the door is uncrated until the door
provided with the door are labeled with
is installed, strict care should be taken not to damage
terminal or contact numbers.
the insulation on the back side of the side column.
(See Figure 32)
In addition to the insulation, a thermal break foam
core is constructed into the components of the door
assembly. This gives the door an extra barrier to
combat against temperature differential. (See Figure
32 & Figure 33)
For a tight and air-proof seal, a bead of caulk should
be applied at the inside perimeter of the door
assembly. Use a construction grade of caulk to seal Figure 33
the door. Route Encoder, Pathwatch, Blower relay wire from
IMPORTANT: Use caulk as directed per the System 4, & Photoeye cables to the low power J-box;
manufacturer’s instructions. Motor cable to the high power J-box;
Improper wall preparation may Blower & side column heater power to J-box (110
result in poor adhesion. The door VAC), and Side column relay from System 4 to J-
may not be altered in any form to box.
apply caulk. DOOR OPEN & CLOSE LIMIT POSITIONS
See the Rytec System 4 Drive & Control Installation &
Foam Owner’s Manual for the proper procedure for setting
Insulation Wall the open and close door limits. The close- and open-
limit door positions are detailed below.
Close-Limit Position
The close-limit position should be adjusted so that
the door travel allows the edge seal on the bottom
bar to gently seal against the floor. (See Figure 34)
13
INSTALLATION— REVERSING EDGE SWITCH INSPECTION AND ADJUSTMENT
Reversing Edge Switch Air Bleed Check
Open-Limit Position
The reversing edge switch is located inside the bot-
When the door is knocked out of position, the System
tom bar assembly, on the same end as the drive
4 Drive & Control takes over and will raise the tabs
motor.
high enough to be reinserted into the side columns.
The open-limit position should be adjusted so that
the door travel allows a minimum of half the foam
breakaway tab into the yellow channel guides of
each side column. (See Figure 35) The disconnect must be in the OFF
position and properly locked and tagged
before performing the following
procedure.
Foam End Tab
1. To inspect and adjust the switch, remove the
access cover from the wireless enclosure
assembly on the face of the bottom bar
assembly. (See Figure 35)
2. Make sure the clear PVC hose is in tight contact
RY-WI Access
Cover with the air input post so that air leakage cannot
occur and that vibration will not cause the hose
to fall off. Also make sure the PVC hose is not
Bottom Bar
kinked. (See Figure 36)
Assembly
3. The air bleed has been set at the factory and
Yellow Channel should not require adjustment. If adjustment is
A8700080 Guide necessary, turn the air bleed adjustment screws
located on the front and back of the switch fully
Figure 35 clockwise — but do not overtighten. Then turn
REVERSING EDGE SWITCH INSPECTION each screw back (counterclockwise) one full turn.
AND ADJUSTMENT
Reversing
Edge Switch
(On Same
Side as Door
Motor)
Do not stand under the door panel
when testing the reversing edge. If the
reversing edge switch is not working
properly, the panel could strike
personnel and cause injury.
To check the reversing edge switch, run the door PVC Hose — Must Air Bleed
through the down cycle. As the door is lowered, tap Be Tight on Lower Adjustment
the bottom of the reversing edge. The door should Input Hose Screw
immediately reverse direction and open. The door is
A7500227
set up from the factory for 3 impacts of the reversing
edge after which it will remain open. If the reversing Figure 36
edge is tripped 3 times consecutively the door will
remain open and code F:361 will appear on the
display. Push and hold the STOP/ RESET button 3 to
5 seconds and the control will reset. Push the down
arrow to close the door.
If the door does not reverse direction, check the air
bleed and sensitivity of the reversing edge switch.
14
INSTALLATION—RESETTING BOTTOM BAR
Reversing Edge Switch Sensitivity Adjustment RESETTING BOTTOM BAR
Bottom Bar
The disconnect must be in the OFF Assembly
position and properly locked and tagged
before performing the following
procedure.
1. The reversing edge switch is a normally open
contact. The PVC hose is on the lower air input
post. To adjust the switch, first remove the Foam Tabs out
resistor from the contact terminals and attach an of Side Column
ohmmeter across the two terminals. (See Figure
37) A8700003
Figure 38
15
INSTALLATION—PATHWATCH LED™ WARNING LIGHTS
Foam NOTE: The door function is fully automatic; it will
Breakaway Tab reset, rise to the open position, and
reinsert the bottom bar according to factory
installed parameters. Cycling the door and
checking for proper door operation is not
required unless prescribed, but an
occasional test of the self-repair system
would ensure its proper operation. Should
slight adjustments of the door be needed,
please contact your Rytec Technical Sup-
port at 800-628-1909.
RY-WI Cover
Access Cover Amber and Red
Pathwatch
LED™ Warning
A8700080 Lights
Figure 41
A8700017
Figure 42
16
INSTALLATION— PATHWATCH LED™ WARNING LIGHTS
Front NOTE: Use the rear spreader of the head
assembly to route the cables/wires to the
1. Find and identify the Pathwatch LED warning
junction box.
light cables/wires in the side columns, both front
and rear. They should be coiled & labeled at the 3. Secure cables/wires with plastic ties to the rear
top and pre-routed through the side column’s spreader of the head assembly. (See Figure 44)
wire chases.
4. Connect cable to junction box per schematic.
2. After the side columns and head assembly have
been assembled and mounted to the wall, PATHWATCH LED & PHOTO EYE
CABLE ROUTING (RH SHOWN)
confirm the front Pathwatch LED Warning light
cables/wires are routed as shown in Figure 19, Pathwatch
Figure 43, and Figure 44: LED Cables
a. Through the wire chase on the inside front of
the side column and down to the bottom. (See
Figure 43)
b. Flat across the side column bottom back to the
rear of the side column. Make sure the cables
are flat on the bottom and don’t interfere w/ the
counterweight or crush plate. (See Figure 43)
Photo Eye
c. Up the side column rear wire chase through Cables
the grommet and inside wire chase slot. (See
Figure 19)
d. Up through the gap between the head
assembly rear spreader and the wall. (See
Figure 44)
3. Secure cables/wires with plastic ties to the rear
spreader of the head assembly.
4. Connect cables/wires to junction box per
schematic.
Rear
1. Find and identify the rear Pathwatch LED
warning light cables/wires in the side columns. Figure 43
They should be coiled & labeled at the top and
pre-routed through the side column’s wire
chases.
2. After the side columns and head assembly have
been assembled and mounted to the wall, Pathwatch LED &
confirm the rear Pathwatch LED Warning light Photo Eye Cables
cables/wires are routed as shown in Figure 19,
Figure 43, and Figure 44:
a. Up the side column rear wire chase through
the grommet and inside wire chase slot. (See
Figure 19 and Figure 43)
b. Through the gap between the head assembly
rear spreader and the wall and to the junction
box. (See Figure 44)
Figure 44
18
INSTALLATION— AIR BLOWER
Testing Photo Eyes 2. Install the blower mounting brackets to the head
assembly with (4) 3/8-16 x 1.25 long Hex Flanged
With the power on, the green light on the transmitter
Socket Screws and 3/8 Flat Washers. Both
indicates the photo eye module is powered up. When
brackets must be aligned and use the same
the yellow light on the receiver module is also lit, the
mounting holes on each side of the head
transmitter and receiver modules are properly
assembly mounting plates. (See Figure 47)
aligned.
3. Mount the Air Blower Assembly to the Door Head
Placing your hand in front of the receiver breaks the
Assembly. Place the UNI-Strut Beam on the
light path causing the yellow light to go out.
Blower Assembly Mounting brackets and secure
Removing your hand causes the yellow light to go
with (2) 3/8-16 x 1.25 long Hex Flanged Socket
back on.
Screws and 3/8 Flat Washers into the 3/8-16 UNI-
AIR BLOWER (DOOR OPENING Ht ≤ 16 ft) Strut nuts. (See Figure 48)
The Air Blower is an optional item providing frost 4. Space the blower(s) so that when mounted to the
prevention and buildup. Door openings that are 16 ft head assembly it/they are evenly spaced along
high or less utilize this style/model blower. the door width. Loosen fasteners and adjust as
required. Tighten all fasteners securing the
NOTE: Hardware is located in the small parts carton.
Blower Assembly and brackets in place. (See
1. Locate and gather all the items in Figure 46. Figure 49)
Install each air blower to the UNI-Strut Beam
using (2) 3/8-16 x 1.25 in. long hex flange
serrated machine screws, Ø3/8 in. flat washers,
and 3/8-16 UNI-Strut nuts. Tighten fasteners.
Orient the blower(s) with the air intake facing
away from the door as shown (See Figure 47)
Figure 47
Blower
Bracket
Blower Mounting
Assy. & Uni-Strut holes
Nuts Blower
Hanger power
Bracket Support clips cords
Figure 50
Blower
Bracket
Mounting
bolts &
washers
Figure 48
19
INSTALLATION— RAD 3 BLOWER
6. Route the Blower electrical power cord(s)/ wiring 3. Adjust the side column mounting brackets so they
to the junction box through the Head Assembly clear the side columns. Guide the blower
door side mounting plate as shown. Use the side assembly into mounting position on the door.
clips for support as shown. (See Figure 50)
4. On the right side align the mounting holes on the
7. Connect cable/wires to junction box per electrical rear of the blower bracket with those on the rear
schematic. of the side columns. Install fasteners, (2) 3/8-16 x
1.25 in. long hex flange serrated machine screws
8. Test the airflow pattern of the blower(s) and make
and Uni-Strut Nuts in the rear holes. Fully tighten
adjustments as necessary to achieve the best
fasteners. (See Figure 52)
airflow coverage.
5. Repeat the procedure for the left side blower
RAD 3 BLOWER (DOOR OPENING Ht > 16 ft) bracket rear mounting holes. (See Figure 52)
The Air Blower is an optional item providing frost
6. Repeat the procedure for the front mounting holes
prevention and buildup. Door openings that are over
on both sides of the door. (See Figure 52)
16 ft high utilize this style/model blower.
NOTE: Hardware is located in the small parts carton.
1. Locate and gather all the items in Figure 51 and
Figure 52. Fasten the air blower side brackets to
the blower using (2) 3/8-16 x 1.25 in. long hex Mounting bolts
flange serrated machine screws, Ø⅜ in. flat
washers, and 3/8-16 Hex Nylock nuts. Do not Support
tighten fasteners as they need to be adjusted. bracket
Orient brackets/blower as shown for RH, LH
bracket is opposite hand. (See Figure 51 and
Figure 52)
Blower
Lock Nuts Blower
Washers
Support
bracket
Mounting bolts Uni-Strut Nuts
Figure 51
Figure 52
2. Safely balance and secure the blower to a lifting
device such as a fork lift in the same manner as 7. Space the blower so that when mounted to the
the head assembly (See Figure 18). Lift the head assembly it is centered along the door
blower/bracket assembly up to the door assembly width. Loosen fasteners and adjust as required.
for mounting to the side columns just below the Once positioned correctly, apply medium-blue
head. (See Figure 52) Loctite® #242 or equal to fastener threads and
tighten, securing the Blower Assembly and
brackets in place. (See Figure 49)
20
INSTALLATION—SIDE COLUMN HEATED BLOWER
8. Route the Blower electrical power cord/wiring LH Side Column
along the Blower over to the head assembly side Blower Assembly
mounting plate. Run cord to the door side where
the power supply junction box and control panel
are located. Secure the cord(s) with zip ties,
Power
cord
clips, or equal. (See Figure 50)
9. Route the Blower electrical power cord/wiring to
the junction box through the Head Assembly
door side mounting plate as shown. Use the side
clips for support as shown. (See Figure 50)
10. Connect cable/wires to junction box per electrical
schematic.
11. Test the airflow pattern of the blower and make
adjustments as necessary to achieve the best
airflow coverage.
SIDE COLUMN HEATED BLOWER Grommet
There are two Side Column Heated Blowers shipped Figure 54
with each door. They are to be installed in the bottom 1. Locate and gather all the items in Figure 53 and
of each side column, are RH/LH specific, and are not Figure 54 along w/ #12-24 x ½ Long Hex Flanged
interchangeable. Warm air is generated and machine screws.
blown/circulated through the internal side column
cavity by the blower and is controlled with a 2. Remove side column covers.
thermostat. (See Figure 53 - Figure 55)
NOTE: Heated blowers are shipped loose and
holes are pre-cut in side columns.
Power
cord Thermostat
Control
Figure 55
21
INSTALLATION— SIDE COLUMN HEATED BLOWER
b. Run the cord out the top between the wall and Fasteners
the Head Assembly rear spreader. (See Figure
56)
Power
cord
Wire
chase
Power
cord
RH Side Column
Assembly End RH Side Column Blower Assembly Installation
Figure 56 Figure 57
22
INSTALLATION—CLEAR SIDE COLUMN TOP COVERS
CLEAR SIDE COLUMN TOP COVERS FINAL CHECKS
The side columns have a transparent cover that gets NOTE: Check all of the following door
mounted at the very top just below the Head or components and systems once the door
Blower Assembly. panel has been cycled at least 20 times.
1. Locate the Clear-transparent Top Side Column Side Columns: Check that side columns are plumb
Cover. It should be in the Small Parts Container. and square and that all anchor bolts are secure and
tight.
2. Remove the covering film from the Top Side
Column Covers. Head Assembly: Check that all mounting hardware
is in place and tight.
3. Mount the covers on each Side Column as
shown. (See Figure 59 & Figure 60) Bottom Bar: Smoothly travels up and down within
the side columns.
Screw, #12-14 x 1.00” Limit Positions: Adjusted properly. Up and down
Ref. Part: travel of the door should be as described in “DOOR
#R5550222-0 OPEN- AND CLOSE-LIMIT POSITIONS” on pages
13 and 14.
Motor: Check that the door travels in the proper
direction when the button is pressed.
Reversing Edge: Works properly. As the door is
closing, if the reversing edge makes contact with an
object, the door should immediately return to the fully
open position as described in “REVERSING EDGE
SWITCH INSPECTION AND ADJUSTMENT” on
page 14.
Upper Side Timers: Automatic timers must be set to ensure that
Column Cover
Ref. Part: the door closes properly, as described in the Rytec
(PH<192) System 4 Drive & Control Installation & Owner’s
#R1170524-0 Manual.
RH Side Column Assembly Top Cover Installation Activators: Operate as specified by manufacturer.
Figure 59 Caulk: Ensure that the side columns and head
assembly are caulked where they meet the wall of
Upper Side
Column Cover the building.
Ref. Part:
(PH≥192) Counterweight Straps: Check the routing of all
#R1170627-0 counterweight straps as indicated in Figure 27 and
Figure 28. Ensure that the straps are in full contact
with all rollers.
Counterweights: Counterweights should be
adjusted as shown in Figure 28 & Figure 29. Adjust if
necessary.
Photo Eyes: Make sure the photo eyes are working
Screw, #12-14 x 1.00” as described in “DAILY INSPECTION” in the Turbo-
Ref. Part:
#R5550222-0 Seal Insulated Owner’s Manual.
Defrost System: Make sure the blowers are
adjusted and operating properly.
RH Side Column Assembly Top Cover Installation
Figure 60
23
NOTES
24
NOTES
25