Carlo Gavazzi Phase Monitoring Relay DPA51CM44

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Monitoring Relays

3-Phase Sequence and Phase Loss


Type DPA51
• 3-phase monitoring relay for phase
sequence and phase loss
• Detects when all phases are present and have the
correct sequence
• Measures its own power supply
• Power supply range: 208 to 480 VAC (±15%)
• Output: 5 A SPDT relay normally energized
• For mounting on DIN-rail in accordance with
DIN/EN 50 022
• 17.5 mm DIN-rail housing (DIN 43880)
• LED indication for relay and power supply ON

Product Description Ordering Key DPA 51 C M44


3-Phase relay for detection of Housing 17.5 mm wide, Housing
incorrect phase sequence, SPDT relay output, suitable Function
total and partial phase loss. for back and front panel Type
Supply range from 208 to 480 mounting. The device Item number
VAC. For mounting on DIN- detects regenerated voltage Output
rail. up to 85% of the nominal Power supply
voltage (phase-phase).

Type Selection
Mounting Output Supply: 208 to 480 VAC

DIN-rail SPDT DPA 51 C M44

Input Specifications Output Specifications


Input Output SPDT relay, N.E.
L1, L2, L3 Terminals L1, L2, L3 Rated insulation voltage 250 VAC
Measures its own supply
Contact ratings (AgSnO2) µ
Measuring range Resistive loads AC 1 5 A @ 250 VAC
208 to 480 VAC 177 to 550 VAC DC 12 5 A @ 24 VDC
ON-level > 85% of the phase- phase Small inductive loads AC 15 2.5 A @ 250 VAC
voltage DC 13 2.5 A @ 24 VDC
Mechanical life ≥ 30 x 106 operations
Electrical life ≥ 105 operations
(at 5 A, 250 V, cos ϕ = 1)
Operating frequency ≤ 7200 operations/h
Dielectric strength
Supply Specifications Dielectric voltage ≥ 2 kVAC (rms)
Power supply Overvoltage cat. III Rated impulse withstand volt. 4 kV (1.2/50 µs)
Rated operational voltage (IEC 60664, IEC 60038)
through terminals: L1, L2, L3
208 to 480 VAC ± 15%,
45 to 65 Hz
Rated operational power 13 VA @ 400 VAC, 50 Hz
Supplied by L2 and L3

Specifications are subject to change without notice (30.03.10) 1


DPA51

General Specifications
Reaction time Housing
Alarm ON delay < 100 ms Dimensions 17.5 x 81 x 67.2 mm
Alarm OFF delay < 300 ms Material PA66 or Noryl
Accuracy (15 min warm-up time) Weight Approx. 75 g
Temperature drift ± 1000 ppm/°C Screw terminals
Repeatability ± 0.5% Tightening torque Max. 0.5 Nm
Indication for acc. to IEC 60947
Power supply ON LED, green Product standard EN 60947-5-1
Relay ON LED, yellow
Approvals UL, CSA
Environment CCC (GB14048.5)
Degree of protection IP 20
Pollution degree 3 CE Marking L.V. Directive 2006/95/EC
Operating temperature EMC Directive 2004/108/EC
@ Max. voltage, 50 Hz -20 to +60°C, R.H. < 95% EMC
@ Max. voltage, 60 Hz -20 to +50°C, R.H. < 95% Immunity According to EN 61000-6-2
Storage temperature -30 to +80°C, R.H. < 95% Emissions According to EN 61000-6-3

Mode of Operation
DPA51 monitors its own 3- below 85% of the other Example 1 Example 2
phase power supply voltage. phase-phase voltages or The relay monitors that the The relay releases in case of
The relay operates when all when the phase sequence is power supply has the correct interruption of one or more
the phases are present and the wrong. phase sequence and that all phases, provided that the
phase sequence is correct. phases are present. regenerated voltage does
The relay releases when one not exceed 85% of the
phase-phase voltage drops phase-phase voltage.

Operation Diagram

Wiring Diagrams
Example 1 Example 2

2 Specifications are subject to change without notice (30.03.10)


DPA51

Dimensions

17.5
67.2

18.7
81

45
2

Specifications are subject to change without notice (30.03.10) 3