A1350 Flyer Ea3

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Electronic polyphase meter

alpha A1350

Electronic three-phase meter for residential and


light commercial customers
With the deregulation of the energy market, in combination with a changing
cost situation, new flexible tariff structures and a modern energy management
are required. Remote metering and the standardization process become more
and more important. With the adaptation of the alpha meter A1350, the condi-
tions to match these new requirements were created.

The alpha meter is available either for direct or CT/VT connection. The meter is
in accordance with the relevant EN, IEC and MID standards.

Features
• High accuracy and stability • installation support features
• Efficient certification mode  • optical interface acc. EN 62056-21
reduction of the test and certifica- • electrical interfaces (CL0, RS232,
tion time RS485) acc. EN62056-21
• 4-Quadrant measurement • use of OBIS identifier system
• 4 energy and 2 demand tariffs, (EN62056-61)
independently controllable • log file for registration of all events
• measurement of active, reactive with time and date stamps
and apparent demand • load profile for billing data (up to 8
• integrated tariff clock channels)
• time back-up with internal battery • measuring of instantaneous values
• readout of meter data according (U, I, f, …)
to VDEW specification by use of • profile of instrumentation values
the EN 62056-21 protocol • 3 electronic S0 outputs
• readout of meter data without • 1 control input
main power
• user friendly reading, setting and
• Anti-Tampering features, like programming tool alphaSET
- terminal and main cover re-
moval detection
- absolute value measurement
- hardware lock against repro-
gramming
Technical Data Modifications or deviations are reserved R 1.4

Nominal voltage 4-wire meter, 3 systems 3x58/100V, 3x63/110V, 3x220/380V,


3x230/400V
3-wire meter, 2 systems 3x100 .. 110V, 3x220..3x230V
Nominal frequency 50 / 60Hz, +/-5%
Nominal / maximum current Continuous current DC: 5(60)A, 5(80)A, 5(100)A
CT: 5//1, 1(2)A, 1.5(6)A, 5(6)A,
5(10)A, 5(15)A
Short duration DC: 7000A for 2 cycles, CT: 300A for 0,5s
Starting current DC: < 16mA
CT: < 1mA
Accuracy Class 2 or 1, A or B acc. EN62053-21, EN50470-3,
MID-app. MI-003
Control input Control voltage Max. 265V AC
Threshold „O FF“ at <40V, „ON“ at >60V
Electronic outputs Only S0 standard acc. IEC 62053-31
Interfaces Optical interface Protocol acc. EN62056-21, max 9600 Baud
Electrical interface: CL0 or RS232 or
RS485
Internal tariff source 4 tariffs, 4 seasons acc. EN 62054-21
weekday dependent tariff scheme
o
Time backup for RTC Battery > 5 years continuous operation at 25 C
shelf life of 10+ years
Accuracy < 5ppm
Time backup for readout without Supercap > 1 day
main power
o o
Temperature conditions Operating temperature -40 ...+70 C
o o
Storage temperature -40 ...+80 C
Humidity acc. EN62052-11
o
Temperature coefficient 0,01% per C (PF=1), <0,04% (PF=0,5)
EMC compatibility Surge withstand (1,2/50µs) 6kV, Rsource = 2 Ohm
12kV, Rsource = 40 Ohm *)
Dielectric test 4kV, 1min, 50Hz
EMC environmental conditions MID E2
Power consumption DC: < 1,5W, <2,2VA per phase
CT: Voltage circuit < 1,5W, <2,2VA per phase
Current circuit < 0,01W, <0,01VA per phase
Connections CT connected meter Terminals: 6mm x 5mm
Direct connected meter Terminals: 10,3mm x 8,3mm
2
Auxiliary connections Terminals: 2,5mm
Housing Dimensions DIN 43857 part 2, DIN 43859
Protection class Housing: IP52, terminal block: IP31
Material Polycarbonate, non-inflammable, self-
extinguishing synthetic material, recyclable
Mechanical environmental conditions MID M1
Weight approx. 1,3 kg
*) only between main terminals

ELSTER GmbH
Otto-Hahn-Str. 25
68623 Lampertheim
Germany

Phone +49 (0) 62 06 / 933-0


Fax +49 (0) 62 06 / 933-292
Mail to [email protected]
www.elstermesstechnik.com