System description
PLCC is widely used in all power utilities as a primary communication service
for telephony, telemetry and tele-protection.
The high tension transmission line of the utility serves as a metallic medium
for propagation of HF carrier. The PLCC system is completely under the control
and ownership of the utility which is the biggest advantage.
This system of communication is very economic, dependable and secure
compared to other alternatives like HF wireless , VSAT or lease line.
If the communication requirement is more than 10 voice channels between
two stations, adoption of wide band systems like microwave radio or OPGW
communication is justified , other wise PLCC is the best solution for inter
communication between grid substations in a power utility.
PLCC communication is feasible for any distance of the line section up to 800
kM.
3
The alloted frequency band used for PLCC is 90 – 500kHz in India. Type of modulation
recommended is SSB-SC as per IEC-495 specification.
PLCC channel carrying voice and super imposed data has a gross band width of 4kHz.
The RF power requirement of a PLCC transmitter is 20W to overcome a line attenuation
of 40dB . PLCC terminals of 40W and 80W RF output are available.
The RF out put of PLCC terminal is injected in to high voltage transmission line using a
suitable high voltage HF coupling capacitor CC or CVT of capacitance 4 to10nF
Also wave traps having main coil inductance of 0.2mH to 2mH are inserted at both ends
of the line to block the RF power entering into the substation bus..
4
EHT Line
Wave Trap
Coupling
Capacitor
Components of PLCC
PLCC Terminal
Coaxial
Translates voice cable
and data into Radio
LMU
Freq. Carrier.
5
POWER FREQUENCY & CARRIER FREQUENCY
Power Line
WT (50Hz)
CC
RF carrier
(90-500kHz)
PAX
RTU
PLCC TERMINAL
Transmission line
(ABB-ETL41)
6
Function of PLCC terminal
IF
AF IF PA R.F Signal
IF RF
(90 to 500 kHz)
User Signal H H
(0 to 4 kHz) AF RF
IF
AF
A gain RF
IF
User Side Line Side
IF
Frequency conversion : audio signals into radio spectrum and vice versa
7
Wave Trap function
90- 500kHz ( HF) : Blocked
WAVE
Trap
PLCC terminal
8
Wave trap function
50 Hz (Power Freq): through pass
HV Line
Power energy
PLC Signal
Substation
9
Wave Traps Mounting Options
10
Wave Trap is a Band Stop filter (50-
500kHz)
Inductance
of
main Coil
Series
Lightning
resistance
Arrester
Tuning
Capacitor
Corona ring
Lifting lug
Terminal
Main coil
Tuning device
Pedestal
Protective device
Tie rod
12
Capacitive Voltage Transformer
( CVT )
13
220kV
CVT and HF connection
8800 pf
8800 pf CVT
HF
LMU DISCONNECT
HF to GND
COAXIAL CABLE
20mH
Drain coil
PLCC
TERMINAL
14
LMU : Type-MCD-80, ABB make
15
Co-axial Cable
16
LMU function
LMU = impedance matching + high
voltage Protection
To prevent dangerous potential on the
PLCC connection
s/s
To match impedance of PLCC set with
power Line impedance. LMU PLCC
Coaxial
Matching + Protection
LMU
17
LMU functional blocks
Substation HV -line
Wave
trap
PLCC
Coupling Panel
capacitor
Tx
or Coax cable Rx
ABB
MCD 80
18
ABB- MCD 80
internal wiring
Coax
To PLCC
CVT
Z 2 75ž
3 T
A G K C1 L H 125ž
L
B
E.S
A C M C2 N 2
Drain
Z1 Coil Z2
Q1 D Match
F1 O C3 P
E L2 Trans
L1 F Q C4 R T1
1
LE C
19
Built in HV protection devices of
LMU
20
HF Coupling modes
LT
LT
Cc LT
Cc Cc
PLC LMU
Cc Cc
Phase-to-Ground
LMDU LMU
Inter circuit
PLC
Phase-to-Phase
21