Room Planning
Room Planning
Room Planning
Room Planning
The layout required for the Brilliance is described in the following sections:
• System Components
• Technical Data
• Typical Room
• Dimensions of Units
• Floor Load in the Examination Room (Gantry)
• Cooling System Requirements
• Radiation Protection
• Occupational Dose Equivalent Value
• Environmental Conditions
System Components
UPS
Generator
(stationary)
Power
Distribution
230V or 120V
Heal exchanger
(optional)
Brilliance Workstation
Gantry
The Gantry covers are new. Except for the covers the Gantry is same to the Mx8000 IDT.
Patient Table
The Patient Table covers are new. Except for the covers the Patient Table is same to the Mx8000 IDT.
Cooling System
All Gantry components including the X-ray tube and oil-air heat exchanger are air-cooled. The air inside the Gantry
is cooled by water-air heat exchangers.
The are two cooling systems available for the Gantry:
• Water/water (*)
• Water/air (**)
NOTE * When water/water cooling systems are used, a connection for a ring cooling line or a stand-alone
cooling system should be provided on-site.
If no ring cooling line is present, we recommend using the water/air cooling system.
** When water/air cooling systems are used, one exterior wall with a corresponding outlet to the
outside must be provided.
Technical Data
Heat Dissipation
Table 3-2 shows the average heat dissipation in kJ/h at 4 kW of average tube output with a dehumidifier running.
Table 3-2: Heat Dissipation by Component
3 3
Component Air Flow m /h (ft /h) Heat Dissipation kW (BTU)
Gantry 50 (dehumidifier) (1765) 1.38** (4709)**
Patient Table - 0.15** (512)**
PDC 200 (7063) 1.2** (4095)**
Operating Console (with
- 0.16** (546)**
monitor)
Computer Rack - 0.65** (2218)**
0.5* (1706)*
-
Heat Exchanger (water-water) 9.5 (32415)
0.75 to the surrounding area (air) (26.5) 0.5* (1706)*
to the exhaust air
21 kW 50 Hz
Heat Exchanger (water-air) (71655 Btu) 50 Hz
26 kW 60 Hz
(88716 Btu) 60 Hz
* Refers to the heat from the WCS internal units, i.e. pump, compressor, etc.and not related to heat dissipation from Gantry water (secondary
cycle).
** Average heat dissipation values at 24°C (75°F) to the surrounding area in kJ/h at 4 kW average tube output and with a dehumidifier running.
NOTE Slight deviations in the parameters are possible. When the relative humidity is
< 30% at 24°C, heat dissipation in the Gantry decreases by an additional 0.6 kW (0.2047 Btu).
Center of Gravity
98 cm
230 cm (3' 3")
(7' 6")
205 cm
(6' 9")
82 cm
(2' 8")
115 cm
(3' 9")
36 cm
1 ft 2 in
109 cm
3 ft 7 in
60 cm
2 ft
107 cm 107 cm
3 ft 6 in 3 ft 6 in
Center of Gravity
Center of gravity (C.O.G.) including patient
with patient table fully extended and raised
Weight: 600 kg including patient
90 cm 76 cm
3 ft 2 ft 6 in
182 cm
6 ft
80 cm
2 ft 8 in
45 cm 38 cm
1 ft 6 in Center of Gravity 1 ft 3 in
78 cm
66 cm
33 cm 2 ft 7 in 33 cm
2 ft 2 in
1 ft 1 in 1 ft 1 in
76 cm
2 ft 6 in
32 cm
1 ft 0.5 in
Center of Gravity
Weight = 120 Kg This drawing is not to scale.
Center of gravity (C.O.G.)
Weight: 177 kg
Figure 3-5: Computer Rack COG and Weight
120 cm 78cm
3 ft 1 1 in 2 ft 7 in
6 0 cm 4 4 cm
1 ft 8 in 1 ft 5 in
7 6 cm
Center of Gravity 5 2 cm
2 ft 6 in
1 ft 8 in
Weight = 60 Kg 3 0 cm
1 ft
This drawing is not to scale.
C e n te r o f g ra vity (C .O .G .)
W e ig h t: 6 0 kg
182 cm
6 ft
93 cm
3 ft 0.5 in
45 cm 38 cm
1 ft 6 in Center of Gravity 1 ft 3 in
Weight = 500 Kg This drawing is not to scale.
90 cm 76 cm
3 ft 2 ft 6 in
182 cm
6 ft
75 cm
2 ft 6 in
45 cm 38 cm
1 ft 6 in Center of Gravity 1 ft 3 in
Typical Room
The room must be at least 2.475cm (8’1") high for the Gantry (see Figure 3-18). The heat exchanger may not be
more than four meters (13' 1") above or below the Gantry.
NOTE For CCT option room height must be min/max 2650 / 3000 mm ( 104.3 / 118.1 in.).
See Section CCT Option Site Planning for full details.
3 3
The minimum room volume for the Water-air heat exchanger is 14.5m (512 ft ).
NOTE Minimum room volume is a safety factor that considers the possibility of coolant evaporation into the
room because of a possible defect in the water-air heat exchanger.
The lower edge of the lead glass window that opens into the clinic must be approximately 80 cm (1’ 1/2") from the
finished floor.
The emergency SHUTDOWN button must comply with local and national fire codes.
Layout
Plan the room so that operators will have the patient in full view. If necessary, install monitoring cameras.
Leave enough space between the wall and each individual unit for servicing the units and to comply with system
cooling and safety requirements.
A separate office and/or viewing room is recommended for the MxView workstation. We also recommend a
separate patient preparation area next to the scan room, for sites that will have heavy traffic.
Because of the high noise level of the fans, we recommend installing the water-air heat exchanger in a separate
control room. The heat exchanger may be to the left or the right of the PDC, or in a different room. Air hose
connections for the water or air heat exchanger must always be connected to an exterior wall.
Figure 3-9, Figure 3-10, and Figure 3-11 show typical layouts with their components.
Heat
Gantry Wall PDC
Exchanger
Max. 4 m (13' 1")
(air hoses)
14 m
(45' 11")
14 m (45' 11")
14 m (45' 11")
2 m (6' 6")
14 m (45' 11")
Figure 3-13: Maximum Distance between Cable Inlets for 16 Meter (52.5 ft.) Cables
Heat
Gantry Wall PDC
Exchanger
Max. 4 m (13' 1")
(air hoses)
22 m
(72' 2")
8 m (26' 3")
22 m (72' 2")
Figure 3-14: Maximum Distance between Cable Inlets for System 25 Meter (82 ft.)/ Console —8 Meter(26.25 ft.)
Cables
Heat
Gantry Wall PDC
Exchanger
Max. 4 m (13' 1")
(air hoses)
14 m
(45' 11")
14 m (45' 11")
14 m (45' 11")
CIRS Rack
14 m (45' 11")
Figure 3-15: Maximum Distance between Cable Inlets for 16 Meter (52.5 ft.) Cables
RapidView20 / CV Pro / CV Expert Option 5 Meter (16.4 ft.) Cable
Heat
Gantry Wall PDC
Exchanger
Max. 4 m (13' 1")
(air hoses)
22 m
(72' 2")
CIRS Rack
22 m (72' 2")
Figure 3-16: Maximum Distance between Cable Inlets for System 25 Meter (82 ft.)/ Console —8 Meter(26.25 ft.)
Cables
RapidView20 / CV Pro / CV Expert Option 8 Meter(26.25 ft.) Cable
Dimensions of Units
Slice Center
80 cm (2’ 8”)
35 cm 243.4 cm (8’)
(1’ 2”)
Front Wall
98.2 cm (3’ 3”)
80 cm (2’ 8")
205 cm (6’ 9”)
50cm
60 cm (2’) 124 cm (4’ 1”) 329.9 cm (10’ 10”) (1’ 8”)
Figure 3-17: Gantry with Patient Table - Front and Top View
75 cm 95 cm
90 cm (3') (2' 6") (3' 1")
181.5 cm
(6')
90 cm (3')
(0.4")
1 cm
70 cm
(2' 4")
95 cm (3' 1.4")
(1.6")
4 cm
Heat Exchangers
75 cm 95 cm
90 cm (3') (2' 6") (3' 1")
181.5 cm
(6')
90 cm (3')
(0.4")
1 cm
70 cm
(2' 4")
95 cm (3' 1.4")
(1.6")
4 cm
46.2 cm
(1' 6")
(1' 9 ")
53 cm
181.5 cm 19 cm
(6') (7.5 ")
(0.4")
1 cm
85 cm
(2' 9.5")
95 cm (3' 1.4")
(1.6")
4 cm
Computer Rack
The computer rack contains the host computer (Dell) and the Image Reconstruction System (IRS). For proper
cooling, ensure that the distances from the wall that are specified in Figure 3-22 are maintained.
66 cm 20 cm 78 cm
2’2” 8” 2’7”
76 cm
2’5”
Operator’s Table
The rear of the table must be at least 200 mm (7.87") from the wall.
1200mm (47")
760mm (30")
Figure 3-23: Operating Console - Table
CAUTION The Gantry with Patient Table and on-site mounting frames must be installed so as to
be free of vibrations.
CAUTION During installation of the scanning system (Gantry) on concrete or computer flooring,
the weight capacity of each floor plate should be at least 400 kg!
During transportation of the Gantry, the load on individual points may be greater. For
example, three points may support the whole load when the floor is not level.
NOTE The values indicated for floor load are valid only if the Gantry is level.
The static values can deviate about ±10% from the given values in the table.
Always valid for the floor load: FG ≤20000 N
Water Valve
Flow Meter
Water Temperature
Gauge
Figure 3-25: Water Flow in a Primary Circuit for a Water-Water Heat Exchanger
NOTE At water inlet to the primary system, you must install the following (purchased locally):
• Water valve
• Flow meter
• Water temperature gauge
The chilled water supply of the hospital must meet the following conditions for the primary circuit of a water-water
Heat Exchanger:
• Water Temperature - 2 - 16 °C (35.60 - 60.80°F)
• Switch OFF - An automatic switch-off control system for the water circulation when the CT system is not in use is
integrated in the WCS.
• Water Quality - We recommend water of drinkable quality. With water of lesser quality, a filter must be installed
with a mesh of 0.2 mm in the primary inlet.
• Temperature Gradient - 0.5 K/min (−0.9 °F/min)
• Operating Pressure - Maximum pressure of 10 bar
• Circulating Volume - The minimum circulating volume depends on the temperature of the chilled water as
illustrated in Figure 3-26. If the flow rate from the on-site water supply is insufficient, a pump having the
appropriate power should be installed.
If the circulating volume from the on-site water supply is insufficient, install a pump to bring it to the required level.
• Power output to the on-site chilled water - 15.0 kW
NOTE When upgrading from Mx8000 to Brilliance, all CT system components must be replaced. Existing
mains connections, water connection, and premises can be used.
Cooling Power
7500 l/h (33 g/m) With Anti-freeze
7000 l/h (30.8 g/m) (to -20°C, -4°F)
6500 l/h (28.6 g/m)
6000 l/h (26.4 g/m) 9.5 kW
Circulating Volume
5500 l/h (24.3 g/m) Without
Anti-freeze
5000 l/h (22 g/m)
4500 l/h (19.9 g/m)
4000 l/h (17.6 g/m)
3500 l/h (15.4 g/m)
3000 l/h (13.2 g/m)
2500 l/h (11 g/m)
2000 l/h (8.8 g/m)
1500 l/h (6.6 g/m)
1000 l/h (4.4 g/m)
500 l/h (2.2 g/m)
12°C (53.6°F)
14°C (57.2°F)
16°C (60.8°F)
2°C (35.6°F)
4°C (39.2°F)
6°C (42.8°F)
8°C (46.4°F)
10°C (50°F)
Figure 3-26: Minimum Circulating Water Volume Required at Different Temperatures
• Anti-freeze - In locations where the water temperature may fall below the freezing point, add anti-freeze to the
water (primary water circuit only) to provide protection to -20°C (-4°F).
The mixture should be 25% anti-freeze. To compensate for the resulting reduction in cooling capacity, increase
the water flow rate (refer to Figure 3-26).
NOTE Do not add anti-freeze to the secondary water circuit. Add to the primary water circuit only.
• Temperature Deviation - Use the following formula to check the temperature deviation of the water:
15 x (860)
∆t[K] =
(Flowrate)[1/h]
CAUTION Water with anti-freeze from the chiller must be at least +2°C (35.6°F). Water with this
temperature may then flow through the water-water heat exchanger.
• Pressure Drop - The minimum pressure drop required depends on the water circulation. Figure 3-27 illustrates
the relationship between the circulating volume of water and the minimum pressure drop required in the primary
system of the water-water heat exchanger.
1200
1100 With 25% Anti-freeze
(to -20°C, -4°F)
1000
500
400
300
200
100
0
2000 l/h (8.8 g/m)
Circulating Volume
Figure 3-27: Minimum Pressure Drop Required per Circulating Volume
• Switch OFF - Switch OFF the circulation of water when the CT system is not in use. Use either a magnetic valve
that is installed on-site or switch OFF the feed pump using a contactor.
The potential-free switching contact in the power distribution system is X263 pin 3,4. Loading capacity maximum
is 277 VAC/2A, or 24 VDC/2A, handling category AC 14/15 and DC12/13.
• Water Quality - We recommend drinking quality water. When water is below drinking quality, install a filter with a
mesh of 0.2 mm (0.01 inches) in the primary inlet.
• Service - The installation of ball valves is recommended for troubleshooting. A temperature indicator for the
primary and secondary circuit and a flow rate indicator is integrated in the WCS.
Water Valve
Flow Meter
Water Temperature
Gauge
CAUTION If the air intake temperature falls below or exceeds the limits stated, add room air. The
air mixture must be integrated on-site. Provisions for this must be made by the
customer.
install back-draft flaps in the air ducts to prevent ice formation at sub-freezing
temperatures.
CAUTION Do not operate the pump in the secondary cooling circuit without water in the
system. It will damage the pump.
CAUTION Turn off the power supply to the WCS before filling water. Do not fill the secondary
cooling circuit with water when the power is on.
Environment Requirements
Installation
Figure 3-29 illustrates the ranges in temperature per relative humidity required for operation of the heat exchangers,
i.e., between +5°C and +40°C (+41°F and +104°F) at relative humidity levels between 15 and 85%.
In addition, the barometric pressure must be maintained in the range 70 to 106 kPa, and the environment must be
guaranteed frost-free, i.e., temperatures ≥ 5°C (41°F).
Air Temperature in °C
60
50
40
30
25
20
10 Absolute
Humidity
3
0 in g/m
-10
-20 1
-30
-40
0 10 20 30 40 50 60 70 80 90 100
Relative Humidity (%)
Figure 3-29: Climatic Conditions for Operating Heat Exchanger
Radiation Protection
General
Prior to beginning operation with a CT system, radiation protection zones must be set up and delineated, so that
access and occupational zones are restricted when the X-ray tube is in operation.
DIN 6812 contains the radiation protection guidelines for Germany pertaining to protection from injury resulting from
radiation exposure.
NOTE Adhere to the IEC 60601 and CFR 21 or the corresponding country-specific regulations.
Maximum
Spatial Dose Distance to Stray Radiation Center
Zone (mSv)
Per Per 2.0 m 2.5 m 3.0 m 3.5 m 4.0 m 5.0 m 6.0 m
Week Year (6.56') (8.20') (9.84') (11.48') (13.12') (16.40') (19.69')
1 1.00 50.0 0.6 mm 0.4 mm 0.2 mm 0.2 mm 0.2 mm 0.1 mm 0.0 mm
0.02" 0.02" 0.01" 0.01" 0.01" 0.00" 0.0"
2 0.30 15.0 0.9 mm 0.8 mm 0.7 mm 0.7 mm 0.5 mm 0.3 mm 0.2 mm
0.04" 0.03" 0.03" 0.03" 0.02" 0.01" 0.01"
3 0.10 5.0 1.3 mm 1.1 mm 1.0 mm 1.0 mm 0.8 mm 0.7 mm 0.6 mm
0.05" 0.04" 0.04" 0.04" 0.03" 0.03" 0.02"
4 0.03 1.5 1.7 mm 1.5 mm 1.4 mm 1.4 mm 1.2 mm 1.0 mm 0.9 mm
0.07" 0.06" 0.06" 0.06" 0.05" 0.04" 0.04"
Environmental Conditions
Environmental Requirements
Table 3-5: Temperature/Relative Humidity in the Room (Climatograms)
Temperature
Air temperature Relative humidity Air pressure
Components gradient
[°C] [%] [hPA]
max. [K/h]
Examination room with Gantry and
15 to 28 15 to 75
Patient Table (see Figure 3-31)
Control room with operator’s console,
Computer Rack with Host and IRS 15 to 28 15 to 75 10 700 to 1060
computers (see Figure 3-31)
Cooling system water/water or water/air 5 to 40 15 to 85
PDC cabinet (see Figure 3-31) 15 to 35 15 to 75
Scanning Room
The optimal environment for the operating personnel and the system is 22°C (71.6°F) with a relative humidity
between 40–60%. The temperature gradient may not exceed 10°C/h (50°F/h). Figure 3-31 shows the permitted
range of temperatures for the permitted range of relative humidities in the scanning room.
If this climate cannot be guaranteed throughout the different seasons, install an air conditioning unit with a
thermostat, as well as a humidifier and a de-humidifier.
NOTE If the required climatic ranges cannot be ensured with the changing seasons, appropriate measures
with respect to ensuring room climate must be taken (see Dimensions, Weight and Noise)
NOTE Remember to consider the heat dissipation from the components in the room (see Table 2-2).
Equip exterior air vents (fresh air) with a filtration
system. Use filter class EU3 to EU4 to filter dust particles
>10µm (DIN 24185, part 2).
Control Room
The operating temperature in the control room should be in the range 15°C to 28°C (59 to 82.4°F). The temperature
gradient may not exceed 5°C/h (41°F/h). The relative humidity in the control room must be in the range 20% to
75%.
35°C/95°F
30°C/86°F
25°C/77°F
20°C/68°F
15°C/59°F
10°C/50°F
5°C/41°F
0°C/32°F
0 10 20 30 40 50 60 70 80 90 100
% Relative Humidity
Figure 3-32: Climatic Prerequisites for Operating the PDC
Fire Extinguisher 2
Observe the country-specific fire codes as well as insurance requirements.
CAUTION Use only CO2 fire extinguishers in case of fire to prevent damage to the system.
Light Box 2
We recommend installing a light box in the system control room.