DGC 2001 Manual
DGC 2001 Manual
DGC 2001 Manual
FOR
DGC-1000
DIGITAL GENSET CONTROLLER
(Equivalent to DGC-2001)
Basler
Digital
Genset R
Controller
DGC-1000
Not In Supplying
Auto Alarm Load
Select Display
Raise Lower Previous
Enter Toggle
Scroll Scroll
D2839-10.vsd
12-04-98
Publication: 9358900990
Revision: F 07/06
INTRODUCTION
This instruction manual provides information about the operation and installation of the DGC-1000 Digital
Genset Controller. To accomplish this, the following information is provided.
WARNING!
To avoid personal injury or equipment damage, only qualified personnel should
perform the procedures in this manual.
NOTE
Be sure that the controller is hard-wired to earth ground with no smaller than 12
AWG copper wire attached to the ground terminal on the rear panel. When the
controller is configured in a system with other devices, it is recommended to use
a separate lead to the ground bus from each unit.
DGC-1000 Introduction i
First Printing: January 2002
Printed in USA
July 2006
CONFIDENTIAL INFORMATION
of Basler Electric, Highland Illinois, USA. It is loaned for confidential use, subject
to return on request, and with the mutual understanding that it will not be used in
any manner detrimental to the interest of Basler Electric.
It is not the intention of this manual to cover all details and variations in equipment, nor does this manual
provide data for every possible contingency regarding installation or operation. The availability and design
of all features and options are subject to modification without notice. Should further information be
required, contact Basler Electric.
BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND, IL 62249 USA
www.basler.com [email protected]
PHONE +1 618.654.2341 FAX +1 6.18.654.2351
ii Introduction DGC-1000
PRODUCT REVISION HISTORY
DGC-1000 Digital Genset Controllers with part number 93589XXXXX incorporate an SAE CAN/J1939
interface to support electronically controlled engine applications and replace earlier versions of the DGC-
1000 with part number 93275XXXXX.
The following information provides a historical summary of the changes made to the embedded software
(firmware), PC software (BESTCOMS), and hardware of the DGC-1000. The corresponding revisions
made to this instruction manual (9358900990) are also summarized. Revisions are listed in chronological
order.
iv Introduction DGC-1000
Manual Revision Change
E, 11/05 • Added 4-Wire Delta formulas to Section 3, Functional Description,
Microprocessor, Formulas.
• Added 4-Wire Delta information to Section 6, BESTCOMS Software,
Setting Definitions, Input/Output Settings, Programmable Input Contact
Setup Tab
• Added Programmable Input Contact Setup chart to the DGC-1000
Settings Record in Appendix A.
F, 07/06 • Added illustration and description of HMI menu 2.5 (communications
settings)
• Added HMI menu 2.5 to Figure 3-7 (menu 2 illustration)
• Corrected Figure 3-9 (wrong menu shown)
• Added note to Section 3 regarding the DGC-1000 operating mode at
power-up
• Added note to Table 3-5 and 3-6 regarding PreStart relay functionality
DGC-1000 Introduction v
This page intentionally left blank.
vi Introduction DGC-1000
CONTENTS
SECTION 1 • GENERAL INFORMATION................................................................................................. 1-1
List of Figures
Figure 1-1. DGC-1000 Style Number Identification Chart ......................................................................... 1-2
FEATURES
DGC-1000 Digital Genset Controllers have the following features.
• Resistant to moisture, salt fog, dust, and chemical contaminants
• Resistant to the entrance of insects and rodents
• Suitable for mounting in any top-mount enclosure
• Suitable for controlling isolated generating systems or paralleled generating systems
• Easy setup through serial communication and BESTCOMS software
• CANBus interface provides high-speed communication with the ECU on electronically-controlled
engines utilizing the SAE J1939 protocol or MTU MDEC protocol
FUNCTIONS
DGC-1000 Digital Genset Controllers perform the following functions.
Protection Metering
• Engine oil pressure • Generator voltage
• Fuel level sender • Generator current
• Coolant temperature • Generator frequency
• Overload • Engine coolant temperature
• Engine oil pressure
Control • Engine rpm
• Engine cranking • Engine run-time
• Engine cool-down • Watts
• VA
Monitoring • Power factor
• Battery condition • Watthours
• Engine maintenance • Battery voltage
• Battery charger failure • Fuel level
Detection Reporting
• Fuel leak • Engine diagnostics
• Low coolant level
OUTPUTS
Six sets of isolated, form A output contacts are provided: Start, Fuel Solenoid, Pre-start, Alarm, Pre-
alarm, and EPS Supplying Load. An addition eight sets of Form C output contacts are available as an
option. See Specifications, Output Contacts for contact ratings and terminal assignments.
DGC-1000
Model Number
Current Sensing
Continuous Rating
1 A Inputs: 0.02 to 1 A
5 A Inputs: 0.1 to 5 A
One Second Rating
1 A Inputs: 2.0 A
5 A Inputs: 10.0 A
Accuracy: ±0.5% of reading or ±1 A, whichever is greater (at 25°C (77°F))
Terminals:
1 A Inputs: P9, P11 (A-phase), P6, P8 (B-phase), P3, P5 (C-phase)
5 A Inputs: P10, P11 (A-phase), P7, P8 (B-phase), P4, P5 (C-phase)
Voltage Sensing
Continuous Rating: 12 to 576 V rms, 50/60 Hz
One Second Rating: 720 V rms
Accuracy: ±0.5% or reading or ±1 V, whichever is greater (at 25°C (77°F))
Burden: 1 VA
Terminals: P34 (A-phase), P35 (B-phase), P36 (C-phase), P37 (neutral)
Frequency
Range: 4 to 70 Hz
Accuracy: ±0.25% of reading or ±0.1 Hz, whichever is greater (at 25°C (77°F))
Contact Sensing
Configuration
Emergency Stop: NC, dry
Battery Charger Failure: NO, dry
Automatic Transfer Switch: NO, dry
Low Coolant Level: NO, dry
Auxiliary 1 – 4: NO, dry
Terminals
Emergency Stop: P17, P18
Battery Charger Failure: P16, P41
Automatic Transfer Switch: P15, P41
Low Coolant Level: P14, P41
Auxiliary 1: P5, P41
Auxiliary 2: P9, P41
Auxiliary 3: P13, P41
Auxiliary 4: P17, P41
Output Contacts
Configuration
Start: SPST, NO
Fuel Solenoid: SPST, NO
Pre-Start: SPST, NO
Alarm: SPST, NO
Pre-Alarm: SPST, NO
EPS Supplying Load: SPST, NO
Auxiliary 1 – 8: SPDT
Ratings
Start: 10 A at 24 Vdc, make, carry, and break
Fuel Solenoid: 10 A at 24 Vdc , make, carry, and break
Pre-Start: 2 A at 30 Vdc, make, carry, and break
Alarm: 2 A at 30 Vdc, make, carry, and break
Pre-Alarm: 2 A at 30 Vdc, make, carry, and break
EPS Supplying Load: 2 A at 30 Vdc, make, carry, and break
Auxiliary 1 – 8: 2 A at 30 Vdc, make, carry, and break
Terminals
Start: P25, P26
Fuel Solenoid: P19, P20
Pre-Start: P21, P22
Alarm: P23, P24
Pre-Alarm: P27, P28
EPS Supplying Load: P29, P30
Auxiliary 1: P4 (NO), P2 (NC), P3 (COM)
Auxiliary 2: P8 (NO), P6 (NC), P7 (COM)
Auxiliary 3: P12 (NO), P10 (NC), P11 (COM)
Auxiliary 4: P16 (NO), P14 (NC), P15 (COM)
Auxiliary 5: P20 (NO), P18 (NC), P19 (COM)
Auxiliary 6: P23 (NO), P21 (NC), P22 (COM)
Auxiliary 7: P26 (NO), P24 (NC), P25 (COM)
Auxiliary 8: P29 (NO), P27 (NC), P28 (COM)
1-4 General Information DGC-1000
Horn Output
Compatible Devices: Basler 29760, Mallory SC628NL
Terminals: P31 (−), P45 (+)
Calculated Data
Power Factor
Range: +1.0 to –1.0, both leading and lagging
Accuracy: ±0.01 PF at 25°C (77°F)
Kilovoltamperes
Range: 0 to 9,999 kVA
Accuracy: ±0.5% of reading or ±0.1 kVA, whichever is greater at 25°C (77°F)
Kilowatts
Range: 0 to 9,999 kW
Accuracy: ±0.5% of reading or ±0.1 kW, whichever is greater at 25°C (77°F)
Kilowatthours
Range: 0 to 999,999,999 kWh
Accuracy: ±0.5% of reading or ±1 kWh, whichever is greater at 25°C (77°F)
Engine Run Time
Range: 0 to 99,999 h
Accuracy: ±0.5% of reading or ±1 h, whichever is greater at 25°C (77°F)
Maintenance Interval
Range: 0 to 5,000 h
Accuracy: ±0.5% of reading or ±1 h, whichever is greater at 25°C (77°F)
Communication Interface
Full Duplex RS-232 Port
Connection: Female DB-9 connector (COM1)
Baud: 1200, 2400, or 9600
Data Bits: 8
Parity: None, Odd, or Even
Stop Bits: 1
Telephone Modem (FCC, part 68 approved modem)
Operating Temperature Range
Standard (style X1X): 0 to 50°C (32 to 122°F)
Extended (style X2X): −40 to 70°C (−40 to 158°F)
CANBus Interface
Differential Bus Voltage: 1.5 to 3 Vdc
Maximum Voltage: −32 to 32 Vdc with respect to negative battery terminal
Communication Rate: 250 kb/s maximum
Environment
Temperature Range
Operating: −40 to 70°C (−40 to 158°F)
Storage: −40 to 85°C (−40 to 185°F)
Type Tests
Shock: Withstands 15 G in each of three mutually perpendicular planes
Vibration: Withstands 2 G, in each of three mutually perpendicular planes, without
structural damage or degradation of performance. Device was swept
over the range of 10 to 500 Hz for a total of six 15-minute sweeps.
Salt Fog: Qualified to ASTM-117B-1989
UL Recognition
All DGC-1000 controllers are UL recognized per Standard 508, Standard for Industrial Control Equipment
(UL file E97035).
CSA Certification
All DGC-1000 controllers are CSA certified per Standard CAN/CSA-C22.2, Number 14-95, CSA file LR
23131.
Physical
Weight: 907 g (2.0 lb)
Dimensions: See Section 4, Installation for device dimensions and panel cutout
requirements.
List of Figures
Figure 2-1. Front Panel HMI Components................................................................................................. 2-1
Figure 2-2. Rear Panel HMI Components ................................................................................................. 2-2
Figure 2-3. CAN Interface Connector Location.......................................................................................... 2-4
List of Tables
Table 2-1. Front Panel HMI Descriptions................................................................................................... 2-1
Table 2-2. Rear Panel HMI Descriptions ................................................................................................... 2-3
FRONT PANEL
Figure 2-1 shows the HMI components of the front panel. Table 2-1 lists the locators of Figure 2-1 along
with a description of each HMI component.
REAR PANEL
All DGC-1000 terminals and connectors are accessed at the rear panel. Figure 2-2 shows the HMI
components (except the CAN interface connector) of the rear panel HMI. Table 2-2 lists the locators of
Figure 2-2 along with a description of each rear panel HMI component.
List of Tables
Table 3-1. Operating Parameters Obtained from CAN Interface Using J1939 Communication ............... 3-4
Table 3-2. Operating Parameters Obtained from CAN Interface Using MTU MDEC Communication...... 3-5
Table 3-3. Diagnostic Information Transmitted Over CAN Interface ......................................................... 3-5
Table 3-4. Front Panel Adjustable Settings ............................................................................................. 3-30
Table 3-5. Normal Output Relay Matrix ................................................................................................... 3-33
Table 3-6. Output Relay Matrix with ECU Support .................................................................................. 3-33
+5
POWER +12
SUPPLY -12 START
ISOLATED +5
FUEL
BATTERY VOLTAGE SOLENOID
SENSING AND
AC VOLTAGE CONDITIONING P0010-10
SENSING AND 10-29-04
PRE-START
CONDITIONING
ALARM
AC CURRENT
SENSING AND
CONDITIONING
PRE-ALARM
COOLANT TEMP.
SENSING AND EPS SUPPLYING
CONDITIONING LOAD
ANALOG
TO
FUEL LEVEL DIGITAL
SENSING AND CONVERTER
OPTIONAL OUTPUT
CONDITIONING
CONTACTS (8)
MICROCONTROLLER
OIL PRESSURE
SENSING AND OPTIONAL REMOTE
CONDITIONONG DISPLAY PANEL
ATS
LOW COOLANT
LEVEL
ISOLATION ISOLATION
BATTERY CHARGER
FAILURE
Transducer Inputs
The DGC-1000 transducer inputs are programmable. This gives the user the flexibility to choose the
transducer to be used in a particular application. For details on programming, see Section 6, BESTCOMS
Software, Programmable Senders.
Coolant Temperature
A current of less than 20 milliamperes is provided to the coolant temperature transducer (sending unit).
The developed voltage is measured and scaled for use by the internal circuitry. This input is not used
when the CAN interface is enabled.
Oil Pressure
A current of 30 milliamperes is provided to the oil pressure transducer. The developed voltage is
measured and scaled for use by the internal circuitry. This input is not used when the CAN interface is
enabled.
Fuel Level And Fuel Leak
A current of less than 20 milliamperes is provided to the fuel level transducer. The developed voltage is
measured and scaled for use by the internal circuitry. The internal fuel level transducer failure circuitry
and the fuel leak detector also use this input. An open circuit across these terminals will indicate a failed
fuel level transducer. A resistance of less than five ohms is used to indicate either a failed fuel level
transducer or a fuel leak detector contact closure.
NOTE
The sender return terminal must be connected to battery minus back at the
engine chassis to minimize the error in the analog sender and battery voltage
readings.
Voltage Inputs
Monitored generator voltages are sensed and scaled to levels suitable for use by the internal circuitry.
Differential amplifiers provide isolation for these inputs. Internal circuitry selects line-to-line, line-to-neutral
or single-phase values. Menu selections by the user determine these switch settings.
Current Inputs
Monitored generator currents are sensed and scaled to values suitable for use by the internal circuitry.
Internal current transformers provide isolation. Two taps on the primary of these transformers
accommodate either one or five ampere circuits.
Table 3-2 lists the operating parameters and annunciations obtained from the CAN interface using the
MTU MDEC communication protocol.
Table 3-2. Operating Parameters Obtained from CAN Interface Using MTU MDEC Communication
Metric English Decimal
Parameter Units Units Update Rate Place
Engine Coolant Temperature °C °F 100 ms when parameter None
changes, #20 s when
not changing
th
Engine Oil Pressure KPa psi 100 ms when parameter 10
changes, #20 s when
not changing
Engine Speed rpm rpm 100 ms when parameter None
changes, #20 s when
not changing
Alarms, Pre-Alarms N/A N/A As they occur N/A
WARNING!
When the CAN interface is enabled, the unit will ignore the following sender
inputs: oil pressure, coolant temperature and magnetic pickup.
The diagnostic function obtains the diagnostic condition of the transmitting electronic components. The
DGC-1000 will receive an unsolicited message of the currently active diagnostic trouble codes (DTC).
Previously active DTCs are available upon request. Active and previously active DTCs can be cleared on
request. See Table 3-3 for details on diagnostic messaging.
DTCs are reported in coded diagnostic information which include the Suspect Parameter Number (SPN),
Failure Mode Identifier (FMI) and Occurrence Count (OC). All parameters have an SPN and are used to
display or identify the items for which diagnostics are being reported. The FMI defines the type of failure
detected in the subsystem identified by an SPN. The problem may not be an electrical failure but may be
a subsystem condition needing to be reported to a technician or operator. The OC contains the number of
times a fault has gone from active to previously active.
MICROPROCESSOR
Software stored in the programmable flash memory controls how the DGC-1000 functions and makes all
decisions based on programming and system inputs. Formulas that are used to determine the various
calculated quantities and circuits related to microprocessor inputs are described in the follow paragraphs.
Formulas
For line-to-line (VL-L) voltage sensing:
V AB = V A 2 + V A × V B + V B 2
V BC = V B 2 + V B × VC + VC 2
VCA = V C 2 + V C × V A + V A 2
For the four-wire delta case (with the mid-point between phases B and C connected to the voltage neutral
terminal on the DGC-1000):
V AB = V A 2 + V B 2
V BC = V B + VC
VCA = VC 2 + V A 2
PF (power factor) equals the cosine of the measured angle between voltage and current zero-crossings.
For single-phase (VA to VB) voltage sensing configurations:
kVA: Total kVA = kVAA + kVAB
= (VAN × IA ÷ 1000) + (VBN × IB ÷ 1000)
kW: Total kW = kWA +kWB
= (kVAA × PF) + (kVAB × PF)
OUTPUTS
Each output relay is controlled by the microprocessor and the emergency stop contact input. All outputs
are electrically isolated from each other and from the internal circuitry. Two outputs (start and fuel
solenoid) are associated with engine cranking functions. The remaining four outputs (Figure 3-1) are
associated with the following conditions: pre-start, supplying load, pre-alarm and alarm.
TELEPHONE MODEMS
Two modems with dial-in, dial-out capability are available as optional equipment on the DGC-1000. The
standard modem is rated from 0°C to 50°C (32°F to 122°F). The extended operating temperature range
modem is rated from -40°C to 70°C (–40°F to 158°F). With the optional phone modem, the DGC-1000
can dial out to inform a pager that an alarm or pre-alarm condition has occurred. Up to four phone
numbers can be dialed in sequence until an answer is received. The supplied modem is registered with
the FCC under Part 68.
If Problems Arise
If any of your telephone equipment is not operating properly, you should immediately remove it from your
telephone line because it may cause harm to the telephone network. If the telephone company notes a
problem, they may temporarily disconnect service. When practical, they will notify you in advance of this
disconnection. If advance notice is not feasible, you will be notified as soon as possible. When you are
notified, you will be given the opportunity to correct the problem and be informed of your right to file a
complaint with the FCC. Contact your telephone company if you have any questions about your telephone
line.
Cellular Communications
Data transfer over an analog cellular system may be optimized when the MNP10-EC (Microcom Network
Protocol, Class 10, Enhanced Cellular) protocol is used. The modem connected to the PC must be
capable of supporting this protocol. It is also necessary to invoke this protocol with the appropriate
initialization string. This initialization string may be stored independently with each of the phone book
entries. (Refer to the Section 6, BESTCOMS Software.) When MNP10-EC protocol is enabled on the
landline modem, the DGC-1000 modem will automatically use MNP10-EC. This allows the user to enable
and disable the MNP10-EC protocol by simply changing the initialization string. An example of a typical
initialization strings is as follows:
AT &F\N5-SEC=1,18-K1M1L2
AT Informs the modem that commands are being sent to it.
&F Forces factory default settings.
\N5 Forces connection using MNP10-EC. (\N2 would allow the protocol to be negotiated as
LAPM or MNP.)
-SEC=1,18 Enables MNP10-EC protocol, and sets the transmit level at –18dBm
-K1 Enables V.42 LAPM to MNP10 conversion.
M1 Enables speaker during dial-up. (M2 would leave speaker on all of the time, and M0 turns
the speaker off.)
L2 Sets the speaker volume. (L0 is off, and L3 is the maximum value.)
The required initialization string will differ between different makes and models of modems. Please
consult the modem's manual for the proper initialization strings.
MNP10-EC adjusts the communication parameters during cellular connection and transmission to provide
quicker initial connection, to provide maximum throughput and to avoid disconnects. MNP10-EC
recognizes typical signal impairments caused by the cellular environment and quickly recovers from the
impairments. Typical impairments for which MNP10-EC compensates include frequent hand-offs,
dropouts, call inference, fading and echo. Performance is significantly improved when the modems on
each end of the connection support MNP10-EC.
Power-Up Sequence
When battery power is first applied, the DGC-1000 initiates a power up sequence. The version of
embedded software is displayed on the LCD and the memory is checked. Then all configuration data
stored in non-volatile EEPROM is brought into main memory. Immediately after this, the LCD display
begins in the Normal mode. When the Normal mode is displayed, all enabled functions are activated and
input monitoring begins.
NOTE
When DGC-1000 operating power is restored following a loss of battery power,
the DGC-1000 will resume operation in the mode that was active prior to the
power loss. For example, if the DGC-1000 is operating in Auto mode when
battery power is lost, the DGC-1000 will resume operation in Auto mode when
battery power is restored.
The run-time counter, kilowatt-hour meter and maintenance timers are updated in
volatile memory once per minute. Updated values are saved to nonvolatile
memory when the Auto/Off/Run mode of operation is changed. Additionally, while
the engine is running, the run time counter is saved every 15 minutes and the
kilowatt-hour meter is saved every eight hours. If the battery power source fails
during operation, these values are not updated and the changes made after the
last save operation are irretrievably lost.
Watchdog Timer
The purpose of the watchdog timer is to re-initialize the microprocessor and restart the software execution
process in the event that normal software execution is interrupted. During normal software execution, the
watchdog timer is periodically reset to prevent it from expiring and initiating a software reset.
When the watchdog timer expires, the unit re-initializes itself as it normally does on power-up. If the user
was logged into BESTCOMS when a watchdog timeout occurs, then BESTCOMS will lose communica-
tion with the DGC-1000. The user must close and reopen communications. If the watchdog times out five
times between power cycles, then the unit will lock-up in a safe mode. The LCD of a locked up unit will
read: "WATCHDOG FAILURE," "CYCLE POWER TO RESET." As long as the unit has not gone into the
safe mode, BESTCOMS will notify the user of a watchdog timeout next time he or she logs onto the unit.
After a watchdog timeout, the unit will return to the mode ("Run" but only if engine speed is still above
crank disconnect speed; "Off" or "Auto") it was last in before the reset occurred, unless it has gone into
the safe mode. The user must cycle the power to get out of safe mode. When in safe mode, the user
cannot log on with BESTCOMS and the engine is shut off.
Cranking
The DGC-1000 is programmable for either cycle crank or continuous crank. If cycle cranking is chosen,
the number of crank cycles allowed before the system shuts down can be selected. A crank cycle is
defined as 5 to 15 seconds of crank followed by an equal number of seconds of rest, selectable in 1-
second increments. The maximum number of cycles the DGC-1000 will allow is 7. If NFPA 100 Level 1 is
chosen, the number of crank cycles is 5.
If a delay to crank feature has been selected, the DGC-1000 will close the pre-start contact upon receipt
of a start command. The pre-start contact is programmable to either remain energized or to drop out after
the delay has expired.
Figure 3-2 illustrates one normal and four abnormal engine starts (crank curves).
Alarms
Reset of all alarms can only be done locally by setting the Auto/Off/Run switch to the OFF position. All
alarm conditions will light a red LED (labeled Alarm) along with displaying the condition on the LCD
screen and sounding the optional audible alarm. All alarms have a common Form A contact. When an
alarm condition occurs, the display indicates the cause of the alarm, the Form A Alarm contact closes and
the fuel solenoid contact opens which shuts down the engine.
Overcrank Alarm
When the crank timer times out, cranking terminates. At that time, the common alarm contacts close and
the LCD displays the message OVERCRANK and the current overcrank setting.
Overspeed Alarm
If the engine speed exceeds the overspeed value programmed by BESTCOMS and continues until the
programmed delay time expires, an overspeed alarm occurs. At that time, the common alarm contact
closes and the LCD displays the message OVERSPEED and the current overspeed setting.
High Coolant Temperature Alarm
If the engine coolant temperature exceeds the level programmed by the BESTCOMS software, an alarm
occurs. At that time, the common alarm contact closes and the LCD displays the message, HIGH
COOLANT TEMP and the current high coolant temperature setting.
Low Oil Pressure Alarm
If the oil pressure decreases below the low oil pressure alarm setting programmed by the BESTCOMS
software, an alarm occurs. At that time, the common alarm contact closes and the LCD displays the
message, LOW OIL PRESSURE and the current low oil pressure alarm setting.
Engine Sender Fault Alarm
If a failure of an engine sender (transducer) is enabled by the BESTCOMS software and a failure occurs,
an alarm occurs. At that time, the common alarm contact closes and the LCD displays the message
SENDER FAILURE and the failed sender. If a short circuit is detected across the fuel level transducer/fuel
leak detector input, the message SENDER FAIL/FUEL LEAK is displayed.
Low Fuel Level Alarm
If the fuel level decreases below the low fuel level alarm setting programmed by the BESTCOMS
software, an alarm occurs. At that time, the common alarm contact closes and the LCD displays the
message, LOW FUEL LEVEL and the current low fuel level alarm setting.
Low Coolant Level Alarm
This alarm stops the engine when a loss of coolant is detected via the low coolant level contact input. At
that time, the common alarm contact closes and the LCD displays the message LOW COOLANT LEVEL.
CAN Bus Alarm
A CAN Bus Failure annunciation may be enabled only when the CAN interface is enabled. The CAN
interface is configurable from BESTCOM. When configured to pre-alarm, annunciation occurs when CAN
communication is lost either by the unit becoming disconnected from the ECU or the ECU malfunctioning.
If CAN communication is lost and the annunciation is configured as an alarm, then a normal alarm
sequence will occur, including a CANBUS FAILURE ALARM message that appears on the display.
MTU MDEC ECU Alarms
A DGC-1000 connected to a genset equipped with an MTU MDEC engine controller is capable of
annunciating a set of alarms unique to the MDEC ECU. Alarms issued by the MDEC ECU can be viewed
on the MTU MDEC tab of the BESTCOMS Metering screen or through the front panel display. When an
MDEC alarm is in effect, the front panel Alarm LED lights and the alarm message text is displayed on the
front panel LCD. The first line displayed in an MDEC alarm message is MDEC ECU ALARM. The second
line of an MDEC alarm message displays text specific to the alarm condition. If multiple alarms exist at
the same time, then the first alarm encountered is the one displayed. The following paragraphs describe
Pre-Alarms
A pre-alarm condition is annunciated by the DGC-1000 in the following ways:
• The front panel Alarm LED flashes on and off.
• The horn output cycles on and off. (The horn output can be enabled or disabled for pre-alarms in
BESTCOMS.)
• A single set of Form A (SPST) output contacts closes.
• The front panel LCD displays the pre-alarms and associated values.
Low oil pressure, high coolant temperature, and battery voltage pre-alarms are shown on the main display
of the front panel LCD. All other pre-alarms are individually displayed in sequence using the Alternate
display mode. Values are flashed on and off to indicate their pre-alarm status. All pre-alarm parameters
are displayed in this manner before non-pre-alarm parameters.
Pre-alarms are reset by correcting the cause of the pre-alarm. Audible pre-alarms are reset by pressing
the Alarm Silence pushbutton on the front panel.
Magnetic Pickup (MPU) Failure Pre-Alarm
If the speed signal source is selected for MPU/GEN (Magnetic Pickup, Generator Frequency) via
BESTCOMS, a pre-alarm will be annunciated when the MPU fails.
High Coolant Temperature Pre-Alarm
If engine coolant temperature increases above the high coolant temperature pre-alarm setpoint
programmed by the BESTCOMS software for the programmed delay time, a pre-alarm occurs.
Low Coolant Temperature Pre-Alarm
If engine coolant temperature decreases below the low coolant temperature pre-alarm setpoint
programmed by the BESTCOMS software for the programmed delay time, a pre-alarm occurs.
Weak Battery Pre-Alarm
If the battery voltage drops below 60% of the nominal voltage for more than 2 seconds during engine
cranking, a pre-alarm occurs. The message, WEAK BATTERY is displayed in the alternate display mode
and is reset by scrolling through the alternate display.
Low Battery Voltage Pre-Alarm
If the battery voltage decreases below the low battery voltage value programmed by the BESTCOMS
software, a pre-alarm occurs.
Battery Overvoltage Pre-Alarm
If the battery voltage exceeds the battery over voltage level programmed by the BESTCOMS software, a
pre-alarm occurs.
DISPLAY OPERATION
The DGC-1000 has three display modes: Normal, Alternate, and Menu. Pressing the Display Toggle
pushbutton when in the Normal display mode allows the user to scroll through the Normal, Alternate, and
menu display modes. DTC mode, when enabled, may be selected while in the Alternate mode. Figure 3-3
shows the top level of each display mode.
Normal Mode
This mode displays the engine and generator parameters as described by the labeling on the front panel.
Pressing the Phase Toggle pushbutton when the engine is running scrolls through the voltage and
current measurements that are available.
D2557-19
10-29-04 Normal Mode
Display
Toggle
Sel/Enter Sel/Enter
MDEC ECU
DTC Mode Alternate Mode
Faults Mode
Previous Previous
Display
Toggle
ECU Parameter
Mode
Display
Toggle
Display Display
Toggle Toggle
Menu Mode
Display
Toggle
Menu Mode
After pressing the Display Toggle pushbutton twice to begin the Menu
display mode (first time selects the Alternate mode), pressing Enter
Select/Enter begins the next level of menus. Pressing the Raise/Scroll Menu
Mode
or Lower/Scroll pushbutton (Figure 3-5) allows the user to scroll
through the menu display mode screens. Pressing the Display Toggle
pushbutton returns the display to the Normal mode.
D/T
Menu 1
Menu 1 is the alarm and pre-alarm menu. Pressing Select/Enter (Figure Menu Mode
Intro Screen
3-6) from this menu begins the 1.x menu level. Pressing Raise/Scroll
and Lower/Scroll from this menu scrolls through the 1.x menu level.
Menu 1.1
Menu 1.1 displays the overspeed alarm. Pressing Select/Enter begins Enter
the 1.1.1 level of menus and displays the function activation level.
Pressing Select/Enter displays the setting. This is not adjustable from Menu 1 Raise
Main Alarms
the front panel. Pressing Previous goes back to the 1.1.1 level. and Pre-Alarms
Pressing Raise/Scroll or Lower/Scroll begins the 1.1.2 function
activation delay level of menus. Pressing Select/Enter displays the Lower
activation delay time once the level has been exceeded. This is not
Raise
adjustable from the front panel.
Pressing Previous twice goes back to the 1.1 level. Pressing Menu 2
Raise/Scroll goes to the 1.2 menu level. Pressing Lower/Scroll goes System
Configuration
to the 1.13 menu level.
Menu 1.2 Lower
Menu 1.2 displays the high coolant temperature alarm. Pressing Raise
Select/Enter begins the 1.2.1 level of menus and displays the function
activation level. Pressing Select/Enter displays the setting. This is not
adjustable from the front panel. Menu 3
Sensing Devices
Pressing Previous goes back to the 1.2.1 level. Pressing Raise/Scroll
or Lower/Scroll begins the 1.2.2 function activation delay level of
Lower
menus. Pressing Select/Enter displays the activation delay time once
the engine crank disconnect speed is exceeded. This is not adjustable Raise
from the front panel.
Pressing Previous twice goes back to the 1.2 level. Pressing Menu 4 Lower
Engine Parameters
Raise/Scroll goes to the 1.3 menu level Pressing Lower/Scroll goes to and Cranking
the 1.1 menu level. D2609-01
04-23-97
Lower Raise
Raise Lower
Menu 1.3
High Coolant Menu 1.12
Temperature Battery Charger
Pre-Alarm Failure Pre-Alarm
Lower
Raise
Raise Lower
Menu 1.4
Menu 1.11
Low Coolant
Battery Over-
Temperature
Voltage Pre-Alarm
Pre-Alarm
Lower Raise
Raise Lower
Lower Raise
Raise Lower
Lower Raise
Raise Lower
D2840-03
04-15-01
Menu 1.3
Menu 1.3 displays high coolant temperature pre-alarm. Pressing Select/Enter begins the 1.3.1 level of
menus and displays the function activation level. Pressing Select/Enter displays the setting. This is not
adjustable from the front panel.
Pressing Previous returns to the 1.3.1 level. Pressing Raise/Scroll or Lower/Scroll begins the 1.3.2
function activation delay level of menus. Pressing Select/Enter displays the activation delay time once
the engine crank disconnect speed is exceeded. This is not front panel adjustable.
Pressing Previous twice goes back to the 1.3 level. Pressing Raise/Scroll goes to the 1.4 menu level
Pressing Lower/Scroll goes to the 1.2 menu level.
Menu 2
06-27-06
Enter
Enter
Menu 2.3
User Front Panel
Key Code
Lower
Raise
Menu 2.4
Global Pre-Alarm
Buzzer Enable
Lower
Raise
P0041-11
Figure 3-9. Menu 2.5
06-27-06
Prev
Communications
Menu 2.5.1 Settings
Enter Enter
Lower
Lower
Raise
Raise
Menu 3.1.2
Menu 3.2 Generator PT's
Sender Failure Secondary Rating
Alarms
Lower
Lower
Raise
Raise
Menu 3.1.3 Lower
Generator CT's
Lower Menu 3.3 Primary Rating
Input Calibration
Function
D2609-05
05-15-97
Figure 3-11. Menu 3.1
Menu 3.2
Menu 3.2 sender failure alarm menu. Pressing Select/Enter (Figure 3-12) begins menu 3.2.1
Menu 3.2.1
Menu 3.2.1 displays coolant temperature sensor failure alarm. Pressing Select/Enter displays the status
of this alarm. This is not adjustable from the front panel. Pressing Previous goes to menu 3.2.1.
Pressing Raise/Scroll goes to menu 3.2.2. Pressing Lower/Scroll goes to menu 3.2.5.
Menu 3.2.2
Menu 3.2.2 displays oil pressure sensor failure alarm. Pressing Select/Enter displays the status of this
alarm. This is not adjustable from the front panel. Pressing Previous goes to menu 3.2.2.
DGC-1000 Functional Description 3-25
Pressing Raise/Scroll goes to menu 3.2.3. Pressing Lower/Scroll goes to menu 3.2.1.
Menu 3.2.3
Menu 3.2.3 displays speed signal failure alarm. Pressing Select/Enter displays the status of this alarm.
This is not adjustable from the front panel. Pressing Previous goes to menu 3.2.3.
Pressing Raise/Scroll goes to menu 3.2.4. Pressing Lower/Scroll goes to menu 3.2.2.
Menu 3.2.4
Menu 3.2.4 displays voltage sensing failure alarm. Pressing Select/Enter displays the status of this
alarm. This is not adjustable from the front panel. Pressing Previous goes to menu 3.2.4.
Pressing Raise/Scroll goes to menu 3.2.5. Pressing Lower/Scroll goes to menu 3.2.3.
Menu 3.2.5
Menu 3.2.5 displays sensor failure alarm time delay. Pressing Select/Enter displays the delay time. After
pressing Raise/Scroll or Lower/Scroll the user will be instructed to enter the user key code. After
entering the user key code followed by pressing Select/Enter twice, the setting will be adjustable with the
Raise/Scroll and Lower/Scroll keys. After the desired setting has been selected, press Select/Enter to
save the new setting. Pressing Previous goes to menu 3.2. Pressing Raise/Scroll goes to menu 3.2.1.
Pressing Lower/Scroll goes to menu 3.2.4.
Pressing Raise/Scroll from menu 3.2 goes to menu 3.3. Pressing Lower/Scroll from menu 3.2 goes to
menu 3.1.
Enter
Menu 3.2.1
Lower Menu 3.2.5
Cool. Temp. Sensor
Sensor Failure
Failure Alarm Raise Alarm Delay
Enabled or Disabled
Lower Raise
Raise Lower
Lower Raise
Lower
Menu 3.2.3
Raise Speed Signal
Failure Alarm
Enabled or Disabled
D2609-07
05-15-97
Menu 3.3
Menu 3.3 displays the input calibration function. This function is for Basler Electric Company use only. For
more information contact Basler Electric Company.
Pressing Previous goes to menu 3. Pressing Raise/Scroll from menu 3 goes to menu 4. Pressing
Lower/Scroll goes to menu 2.
Enter
Lower
Raise Lower
Menu 4.7
Menu 4.2 Pre-Crank Contact
Cranking Mode After Cranking
Lower Raise
Raise Lower
Lower Raise
Raise Lower
D2609-08
04-23-97
NOTE
Using DISPLAY TOGGLE to exit Menu mode Exit
will save the user’s place within the menu Menu
system so that the next time Menu mode is Mode
entered, the display will return to the same
screen. Figure 3-14. Exiting Menu Mode
As an alternative, pressing Previous allows the user to back out of the menu mode one level at a time so
that the next time menu mode is entered, the display will start at the top of the menu structure.
Modifying Setpoints
To modify an existing setpoint, press the Select/Enter pushbutton (Figure 3-15). Press Raise/Scroll or
Lower/Scroll buttons to raise or lower the current parameter setpoint. Press the Select/Enter pushbutton
to save the modified setpoint value or press the Previous pushbutton to exit the parameter setting screen
without changing the value.
Once in the menu mode, the first time an attempt is made to change a setting that is front panel
adjustable, the user will be prompted to enter the key code. Upon successful entry of the key code, the
user may modify any of the adjustable settings without re-entering the key code during the current menu
mode session. The only exception to this is changing the key code itself. Changing the key code always
requires entry of the existing key code. Also, whether the key code is actually changed or not, any further
changes to other settings after that will require the key code to be entered once again. Leaving the Menu
mode after an editing session automatically terminates the editing privilege.
Press the Display Toggle pushbutton to exit the menu mode.
Key Code
The DGC-1000 is delivered with a key code consisting of the following pushbutton sequence.
1. Raise/Scroll
2. Lower/Scroll
3. Select/Enter
4. Previous
5. Display Toggle
6. Select/Enter
7. Select/Enter
The key code can be changed by accessing the CHANGE KEYCODE screen of Menu 2. Observe the
following guidelines when changing the key code.
• Allowable key code pushbuttons are Raise/Scroll, Lower/Scroll, Select/Enter, Previous, Display
Toggle, Phase Toggle, Alarm Silence, and Lamp Test.
• A key code entry must be followed by two presses of the Select/Enter pushbutton.
• A key code can consist of one to eight presses of the allowable key code pushbuttons.
• A key code cannot contain consecutive presses of the Previous pushbutton.
NOTE
With Enable ECU Support selected, a non-programmable Coolant Level Sender
Fail alarm can annunciate either when the engine is off or running. Coolant level
is only metered and displayed when Enable ECU Support is selected in
BESTCOMS.
the DGC-1000 establishes communications with an ECU, the engine run time, coolant level, coolant
temperature, oil pressure and engine speed will be updated with the ECUs values.
ECU Limitations
For some ECUs, an external source cannot stop the engine without removing power from the ECU.
Turning off power to the ECU is the only way to remove fuel from the engine, shutting it down. Different
ECU manufacturers have their own rpm-setpoints for reapplying fuel to an engine. If the ECU is powered
up and the engine is still spinning above 60 rpm, then the ECU will automatically turn the fuel on. Detroit
Diesel J1939 ECUs, for example, have a setpoint of 60 rpm.
Not being able to stop the engine without removing ECU power causes two problems. The first problem is
that the only way to stop the engine is to turn the ECU off and wait for the engine speed to fall below 60
rpm before powering the ECU back up. Otherwise, the engine will take off running. The second problem is
that while the ECU is off, you can no longer meter and update coolant level, coolant temperature, oil
pressure or engine speed values, effectively disabling features like low coolant temperature alarm/pre-
alarm and crank control.
The DGC-1000 Solution
The DGC-1000 resolves ECU limitations by using timers. There are four user-programmable timers in
ECU Timers under the Configure pull-down menu in BESTCOMS. In the ECU Related Time Values box
you will see the following timers and their corresponding default values.
• Pulse Cycle Time. The time in minutes the unit waits before pulsing.
• Response Timeout. The time in seconds to attempt communications with the ECU when the DGC-
1000 is in the Pulsing state or Connecting state.
• Settling Time. The time in tenths of seconds to gather data after connecting to the ECU during the
Pulsing state. This allows all the metered values to be sent and ramp up to their steady-state values.
Metered values are sent out by the ECU at different rates as designated by the J1939 protocol. ECU
values initially sent are low and the ECU takes time to average out its own data values.
• Engine Shut Down. The time in seconds to stay disconnected from the ECU when going from
Running to Shut-Down before starting the first pulse. This timer should allow enough time for the
engine to slow down so that when the DGC-1000 pulses, the ECU will not start the engine.
NOTE
When ECU Support is enabled, during the Pre-Start and Resting states, the fuel
solenoid is closed.
"ENGINE SPEED"
"NO COMMUNICATIONS"
WARNING!
The DGC-1000 should be removed from service for the purpose of upgrading
firmware as it will not be able to control or monitor the genset once the firmware
upgrade procedure has been started.
List of Figures
Figure 4-1. Cutout Dimensions in Inches (Millimeters) .............................................................................. 4-1
Figure 4-2. DGC-1000 Dimensions ........................................................................................................... 4-2
Figure 4-3. DGC-1000 Communication Port Pin Assignments.................................................................. 4-3
Figure 4-4. Personal Computer to DGC-1000 Connections ...................................................................... 4-4
Figure 4-5. CAN Cable Assembly .............................................................................................................. 4-4
Figure 4-6. DGC-1000 System Ladder Diagram ....................................................................................... 4-5
Figure 4-7. Direct-Connected, Single-Phase, Three-Wire Sensing........................................................... 4-6
Figure 4-8. Direct-Connected, Three-Phase, Line-to-Line Sensing .......................................................... 4-7
Figure 4-9. Direct-Connected, Three-Phase, Line-to-Neutral Sensing ..................................................... 4-8
Figure 4-10. Direct-Connected, Single-Phase, Three-Wire Sensing, Volvo Penta EDC III .................... 4-10
Figure 4-11. Direct-Connected, Three-Phase, Line-to-Line Sensing, Volvo Penta EDC III .................... 4-11
Figure 4-12. Direct-Connected, Three-Phase, Line-to-Neutral Sensing, Volvo Penta EDC III ............... 4-12
Figure 4-13. Direct-Connected, Single-Phase, Three-Wire Sensing, MTU MDEC ECU......................... 4-13
Figure 4-14. Direct-Connected, Three-Phase, Line-to-Line Sensing, MTU MDEC ECU ........................ 4-14
Figure 4-15. Direct-Connected, Three-Phase, Line-to-Neutral Sensing, MTU MDEC ECU ................... 4-15
List of Tables
Table 4-1. DGC-1000 Communication Port Pin Assignments................................................................... 4-3
Table 4-2. CAN Cable Assembly Termination Assignments ..................................................................... 4-4
Table 4-3. MTU MDEC ECU Configuration Parameters ........................................................................... 4-9
DGC-1000 Installation i
This page intentionally left blank.
ii Installation DGC-1000
SECTION 4 • INSTALLATION
INTRODUCTION
DGC-1000 Digital Genset Controllers are delivered in sturdy cartons to prevent shipping damage. Upon
receipt of a unit, check the part number against the requisition and packing list for agreement. Inspect for
damage, and if there is evidence of such, immediately file a claim with the carrier and notify the Basler
Electric regional sales office, your sales representative, or a sales representative at Basler Electric,
Highland Illinois.
If the controller will not be installed immediately, store it in the original shipping package in a moisture-
and dust-free environment.
HARDWARE
DGC-1000 controllers are packaged for mounting in any top-mount enclosure. The front panel is resistant
to moisture, salt fog, humidity, dust, dirt, and chemical contaminants. It also inhibits insect and rodent
entrance.
A DGC-1000 controller is secured to a panel by the four permanently-attached 10-32 by ⅝ inch (½ inch
usable) studs and four nylon lined nuts (supplied). Hardware mounting torque is 30 in-lb (3.4 N•m).
MOUNTING
Case cutout dimensions are shown in Figure 4-1. Overall dimensions are shown in Figures 4-2.
NOTE
Ensure that the DGC-1000 control power wiring is correct. Reverse polarity will
not damage the controller, but it will prevent the DGC-1000 from operating.
Be sure that the DGC-1000 is hard-wired to earth ground with no smaller than 12
AWG copper wire attached to the ground terminal on the rear panel of the
controller.
Except as noted above, connections should be made with wire no smaller than 14 AWG.
Be sure to supply the controller with the correct level of operating power.
DGC-1000 Terminations
DGC-1000 terminals, excluding the serial communication port and CAN interface, consist of quarter-inch
blade, quick-connect terminals. These terminals accept female, quarter-inch connectors. All DGC-1000
terminals are located on the rear panel of the controller. The connectors used on the DGC-1000 make it
easy to remove the controller for out-of-circuit testing or maintenance.
DGC-1000 terminals are illustrated and described in Section 2, Human-Machine Interface.
Communication Port
The RS-232 port on the rear panel uses a DB9 female connector. Figure 4-3 illustrates the pin
assignments of the communication port and Table 4-1 identifies the RS-232 connector pin functions. A
standard communication cable terminated with a DB9 male connector is used for PC interface with the
DGC-1000 as shown in Figure 4-4.
CAN Connections
The CAN connector mates with the cable assembly (Basler P/N 9358900002) provided with the DGC-
1000. The cable assembly is illustrated in Figure 4-5 and the termination assignments are listed in Table
4-2.
1
2
3
4
5
6 DGC-1000
5A
7 POWER INPUT
8 P1 + - P2
9
10 P41
ATS
P15
11
LOW COOLANT LEVEL
P31 P14
12
HORN BATTERY CHARGER FAILURE
13 P45 P16
SENDER RETURN
14 P19
43 5-PIN
FOR J1939 COMMUNICATIONS WITH EECU
CONN
44
45 OPTIONS
PROGRAMMABLE ON AUX. BD. PROGRAMMABLE CONTACT
46 INPUTS WITH AUX. I/O OPTION
OUTPUT CONTACTS AUX 1
47 WITH AUX. I/O INPUT
AUX AUX 2
48 OPTION. 1 INPUT
AUX 3
49 INPUT
AUX 4
50 INPUT
AUX
51 2
RJ11 OPTIONAL FOR REMOTE COMMUNICATION
52 MODEM
53
AUX AUX
54 3 8
55
56
AUX AUX
57 4 7
58
59
AUX AUX
60 5 6 P0010-14.vsd
12-17-01
61
4-6
CIRCUIT
BREAKER
L1
A
TO L2
B GENERATOR
BUS 480V
N
N
PH A
PH B
PH C
NEUT.
AUTOMATIC BARE
P15 8
TRANSFER
SWITCH OIL PRESSURE P38
PHASE
PHASE
C CT
B CT
PHASE
A CT
7 LOW 2
P14 FUEL LEVEL P39
COOLANT SENDING FUEL
LEVEL UNITS LEAK
CONTACT 3
COOLANT TEMP P40 DETECTOR
SENSING
BATTERY 6
P16 CHARGER DGC-1000 4
SENDER RETURN P46
OUTPUT
RELAYS
FAIL
Installation
- P33
P41 GND
MPU
+ P32 MAGNETIC
PICK-UP
EPS
SUPPLYING
LOAD
PRE-ALARM
ALARM
5A
PRE-START
FUEL
SOLENOID
MASTER
START
+ P1 7
BATTERY
+
- P2
P29 P30 P27 P28 P23 P24 P21 P22 P19 P20 P25 P26
2 STEWART WARNER P/N 411-K OR EQUIVALENT. NOT USED IF J1939 IS USED. P0010-11
05/22/02
FUEL START
3 ISS PRO P/N R8925 OR EQUIVALENT 10 10
SOLENOID SOLENOID
8 J1939 SHIELD SHOULD BE GROUNDED AT ONLY ONE POINT. IF GROUNDED ELSEWHERE IN THE SYSTEM, CUT J1939 SHIELD CONNECTION TO UNIT.
9 IF UNIT IS NOT PROVIDING ONE END OF THE J1939 BACKBONE, THEN CUT JUMPER TO REMOVE ON-BOARD TERMINATION RESISTOR. ALSO,
IF NOT PART OF THE BACKBONE, THE STUB CONNECTING THE UNIT TO THE BACKBONE SHOULD NOT EXCEED 3 FEET IN LENGTH.
IT IS HIGHLY RECOMMENDED THAT EACH EXTERNAL DC RELAY BE FITTED WITH A FLY-BACK DIODE ACROSS IT’S ENERGIZING COIL TO MINIMIZE
10 THE VOLTAGE TRANSIENT PRODUCED WHEN THE COIL IS SUDDENLY DISCONNECTED FROM IT’S POWER SUPPLY.
DGC-1000
GENERATOR
CIRCUIT
BREAKER
A A
DGC-1000
TO B GENERATOR
B
BUS 480V
C
C
N N
PH A
PH B
PH C
AUTOMATIC NEUT. BARE
P15 8
TRANSFER
SWITCH
OIL PRESSURE P38
PHASE
C CT
PHASE
B CT
PHASE
A CT
7 LOW
P14 FUEL LEVEL P39 2
COOLANT SENDING FUEL
LEVEL UNITS LEAK
CONTACT 3
COOLANT TEMP P40 DETECTOR
SENSING
BATTERY 6
P16 CHARGER DGC-1000 4
SENDER RETURN P46
OUTPUT
RELAYS
FAIL
- P33
P41 GND
Installation
MPU
+ P32 MAGNETIC
PICK-UP
EPS
SUPPLYING
LOAD
PRE-ALARM
5A
ALARM
PRE-START
FUEL
SOLENOID
MASTER
START
+ P1 7
BATTERY
+
- P2
P29 P30 P27 P28 P23 P24 P21 P22 P19 P20 P25 P26
8 J1939 SHIELD SHOULD BE GROUNDED AT ONLY ONE POINT. IF GROUNDED ELSEWHERE IN THE SYSTEM, CUT J1939 SHIELD CONNECTION TO UNIT.
IF UNIT IS NOT PROVIDING ONE END OF THE J1939 BACKBONE, THEN CUT JUMPER TO REMOVE ON-BOARD TERMINATION RESISTOR. ALSO,
9
IF NOT PART OF THE BACKBONE, THE STUB CONNECTING THE UNIT TO THE BACKBONE SHOULD NOT EXCEED 3 FEET IN LENGTH.
IT IS HIGHLY RECOMMENDED THAT EACH EXTERNAL DC RELAY BE FITTED WITH A FLY-BACK DIODE ACROSS IT’S ENERGIZING COIL TO MINIMIZE P0010-12.VSD
10 12/17/01
THE VOLTAGE TRANSIENT PRODUCED WHEN THE COIL IS SUDDENLY DISCONNECTED FROM IT’S POWER SUPPLY.
4-7
GENERATOR
4-8
CIRCUIT
BREAKER
A A
TO B GENERATOR
B
BUS 480V
C
C
N N
PH A
PH B
PH C
NEUT.
AUTOMATIC BARE
P15 8
TRANSFER
SWITCH OIL PRESSURE P38
PHASE
C CT
PHASE
B CT
PHASE
A CT
7 LOW
P14 FUEL LEVEL P39 2
COOLANT SENDING FUEL
LEVEL UNITS LEAK
CONTACT 3
COOLANT TEMP P40 DETECTOR
SENSING
BATTERY 6
P16 CHARGER DGC-1000 4
SENDER RETURN P46
OUTPUT
RELAYS
FAIL
Installation
- P33
P41 GND
MPU
+ P32 MAGNETIC
PICK-UP
EPS
SUPPLYING
LOAD
PRE-ALARM
5A
ALARM
PRE-START
FUEL
SOLENOID
MASTER
START
+ P1 7
BATTERY
+
- P2
P29 P30 P27 P28 P23 P24 P21 P22 P19 P20 P25 P26
5 IF AN EMERGENCY STOP SWITCH IS NOT USED, JUMPER TERMINALS P17 AND P18.
8 J1939 SHIELD SHOULD BE GROUNDED AT ONLY ONE POINT. IF GROUNDED ELSEWHERE IN THE SYSTEM, CUT J1939 SHIELD CONNECTION TO UNIT.
IF UNIT IS NOT PROVIDING ONE END OF THE J1939 BACKBONE, THEN CUT JUMPER TO REMOVE ON-BOARD TERMINATION RESISTOR. ALSO,
9
IF NOT PART OF THE BACKBONE, THE STUB CONNECTING THE UNIT TO THE BACKBONE SHOULD NOT EXCEED 3 FEET IN LENGTH.
P0010-13.VSD
IT IS HIGHLY RECOMMENDED THAT EACH EXTERNAL DC RELAY BE FITTED WITH A FLY-BACK DIODE ACROSS IT’S ENERGIZING COIL TO MINIMIZE 12/17/01
10 THE VOLTAGE TRANSIENT PRODUCED WHEN THE COIL IS SUDDENLY DISCONNECTED FROM IT’S POWER SUPPLY.
DGC-1000
Volvo Penta EDC III Applications
Volvo engines equipped with Volvo Penta EDC III controllers, like the TAD124xGE series, can receive
engine control commands (such as start and stop) from the DGC-1000 through the SAE J1939
communication interface. To invoke this feature, the EDC must receive a J1939 message containing
engine control information within one second of waking (exiting sleep mode). If the EDC III does not
receive an engine control message within the prescribed time, it will enter the stand-alone mode and
ignore any J1939 control messages. If this occurs, the EDC III must be forced back into sleep mode by
pressing the auxiliary stop button on the engine or by momentarily disconnecting EDC power.
The interconnection diagrams of Figures 4-10, 4-11, and 4-12 illustrate the DGC-1000 and EDC
connections that allow the DGC-1000 to awaken the EDC and start the engine, or simply acquire engine
status information. Wakeup of the EDC is initiated by using the DGC-1000 fuel solenoid output contacts to
apply battery power to the EDC. To stop the engine, the DGC-1000 issues a sleep command through the
J1939 interface to the EDC and opens the fuel solenoid output contacts. This causes the EDC to stop the
engine and enter the sleep mode.
In order for the DGC-1000 to communicate with the EDC, two DGC-1000 settings must be changed from
their default values.
• The J1939 address of the DGC-1000 must be set at 17.
• The engine start/stop configuration setting must be set for “Volvo Penta EDC III”.
In order for the Volvo engine to operate at rated rpm, verify the following DGC-1000 settings.
• Speed Select setting should be set at “Primary”.
• Accelerator Position setting should be set at 50%.
The above settings are configured on the BESTCOMS System Settings screen. Section 6, BESTCOMS
Software has information about adjusting DGC-1000 settings through BESTCOMS.
The interconnection diagrams of Figure 4-13, 4-14, and 4-15 illustrate DGC-1000 and MDEC ECU
connections for three types of generator sensing configurations.
4-10
BREAKER
A
A
ENGINE
TO
VOLVO MOUNTED
B GENERATOR
B PENTA 8-POLE
BUS 480V DEUTSCH
EDC III CONNECTOR
N
N 1 2 3 4 5
1 2 3 4 5
LOW 2
P14 COOLANT FUEL LEVEL P39
SENDING
LEVEL CONTACT UNITS
COOLANT TEMP P40 3
SENSING FUEL
BATTERY LEAK
P16 CHARGER
DGC-1000 6 4 DETECTOR
SENDER RETURN P46
Installation
FAIL
Figure 4-10. Direct-Connected, Single-Phase, Three-Wire Sensing, Volvo Penta EDC III
8 J1939 SHIELD SHOULD BE GROUNDED AT ONLY ONE POINT. IF GROUNDED ELSEWHERE IN THE SYSTEM, CUT J1939 SHIELD CONNECTION TO UNIT.
IF UNIT IS NOT PROVIDING ONE END OF THE J1939 BACKBONE, THEN CUT JUMPER TO REMOVE ON-BOARD TERMINATION RESISTOR. ALSO,
9 IF NOT PART OF THE BACKBONE, THE STUB CONNECTING THE UNIT TO THE BACKBONE SHOULD NOT EXCEED 3 FEET IN LENGTH.
DGC-1000
GENERATOR
CIRCUIT
BREAKER
A
A
DGC-1000
ENGINE
VOLVO MOUNTED
TO B GENERATOR
B PENTA 8-POLE
BUS 480V DEUTSCH
EDC III CONNECTOR
C
C 1 2 3 4 5
N 1 2 3 4 5
N
LOW 2
P14 COOLANT FUEL LEVEL P39
SENDING
LEVEL CONTACT UNITS
COOLANT TEMP P40 3
SENSING FUEL
BATTERY LEAK
P16 CHARGER
DGC-1000 6 4 DETECTOR
SENDER RETURN P46
FAIL
OUTPUT RELAYS
Installation
- P33
CHASSIS
P41
GND MPU
EPS
+ P32 MAGNETIC
SUPPLYING FUEL MASTER
PICK-UP
LOAD PRE-ALARM ALARM PRE-START SOLENOID START 5A
+ P1 7
BATTERY
- P2
P29 P30 P27 P28 P23 P24 P21 P22 P19 P20 P25 P26
+
Figure 4-11. Direct-Connected, Three-Phase, Line-to-Line Sensing, Volvo Penta EDC III
8 J1939 SHIELD SHOULD BE GROUNDED AT ONLY ONE POINT. IF GROUNDED ELSEWHERE IN THE SYSTEM, CUT J1939 SHIELD CONNECTION TO UNIT.
IF UNIT IS NOT PROVIDING ONE END OF THE J1939 BACKBONE, THEN CUT JUMPER TO REMOVE ON-BOARD TERMINATION RESISTOR. ALSO,
9 IF NOT PART OF THE BACKBONE, THE STUB CONNECTING THE UNIT TO THE BACKBONE SHOULD NOT EXCEED 3 FEET IN LENGTH.
4-11
GENERATOR
CIRCUIT
4-12
BREAKER
A
A
ENGINE
VOLVO MOUNTED
TO B GENERATOR
B PENTA 8-POLE
BUS 480V DEUTSCH
EDC III CONNECTOR
C
C 1 2 3 4 5
N 1 2 3 4 5
N
LOW 2
P14 COOLANT FUEL LEVEL P39
SENDING
LEVEL CONTACT UNITS
COOLANT TEMP P40 3
SENSING FUEL
BATTERY LEAK
P16 CHARGER
DGC-1000 6 4 DETECTOR
Installation
SENDER RETURN P46
FAIL
Figure 4-12. Direct-Connected, Three-Phase, Line-to-Neutral Sensing, Volvo Penta EDC III
8 J1939 SHIELD SHOULD BE GROUNDED AT ONLY ONE POINT. IF GROUNDED ELSEWHERE IN THE SYSTEM, CUT J1939 SHIELD CONNECTION TO UNIT.
IF UNIT IS NOT PROVIDING ONE END OF THE J1939 BACKBONE, THEN CUT JUMPER TO REMOVE ON-BOARD TERMINATION RESISTOR. ALSO,
9 IF NOT PART OF THE BACKBONE, THE STUB CONNECTING THE UNIT TO THE BACKBONE SHOULD NOT EXCEED 3 FEET IN LENGTH.
DGC-1000
USER-SUPPLIED
GENERATOR MATING
CIRCUIT CONNECTOR
BREAKER
MDEC
A ECU
A
DGC-1000
G F E h g ECU CONNECTOR "X1"
TO B GENERATOR G F E h g Mating
B
BUS 480V Connector
X1 Wiring
49 50 51 25 26 Wire Harness
Numbers
N
N
USER-SUPPLIED
TERMINAL STRIP
J1939 CABLE
PROVIDED WITH UNIT
1 1
N.C. P9 P6 P3 9
P31 P45 P11 P8 P5 P34 P35 P36 P37 TERMINATION 1 1
P18 P10 P7 P4
EMERGENCY RESISTOR 2 2
5
- + 1A 1A 1A VOLT. VOLT. VOLT. VOLT. RED
STOP COM COM COM CAN HI 3 3
P17 5A 5A 5A PH A PH B PH C NEUT. BLK
CAN LO 4 4
HORN 5 5
AUTOMATIC BARE
P15 VOLT.
TRANSFER 8
PHASE PHASE PHASE
SWITCH OIL PRESSURE
C CT B CT A CT P38
LOW
P14 FUEL LEVEL P39
COOLANT SENDING 2
LEVEL CONTACT UNITS
COOLANT TEMP P40 4 3
SENSING FUEL
BATTERY LEAK
P16 CHARGER
DGC-1000 6 DETECTOR
SENDER RETURN P46
FAIL
Installation
GND MPU
EPS
+ P32 MAGNETIC
SUPPLYING FUEL MASTER
PICK-UP
LOAD PRE-ALARM ALARM PRE-START SOLENOID START 5A
+ P1 7
BATTERY
- P2
P29 P30 P27 P28 P23 P24 P21 P22 P19 P20 P25 P26
+
IF UNIT IS NOT PROVIDING ONE END OF THE J1939 BACKBONE, THEN CUT JUMPER TO REMOVE ON-BOARD TERMINATION RESISTOR. ALSO,
9
IF NOT PART OF THE BACKBONE, THE STUB CONNECTING THE UNIT TO THE BACKBONE SHOULD NOT EXCEED 3 FEET IN LENGTH.
IT IS HIGHLY RECOMMENDED THAT EACH EXTERNAL DC RELAY BE FITTED WITH A FLY-BACK DIODE ACROSS IT’S ENERGIZING COIL TO MINIMIZE
10
THE VOLTAGE TRANSIENT PRODUCED WHEN THE COIL IS SUDDENLY DISCONNECTED FROM IT’S POWER SUPPLY.
4-13
GENERATOR
4-14
CIRCUIT
BREAKER MDEC
A ECU
A
J1939 CABLE
PROVIDED WITH UNIT
1 1 1
N.C. P9 P6 P3 9
P31 P45 P11 P8 P5 P34 P35 P36 P37 TERMINATION 1 1
P18 P10 P7 P4
EMERGENCY RESISTOR 2 2
5 - + 1A 1A 1A VOLT. VOLT. VOLT. VOLT. RED
STOP COM COM COM CAN HI 3 3
P17 5A 5A 5A PH A PH B PH C NEUT. BLK
CAN LO 4 4
HORN 5 5
AUTOMATIC BARE
P15
TRANSFER 8
PHASE PHASE PHASE
SWITCH OIL PRESSURE
C CT B CT A CT P38
LOW
P14 FUEL LEVEL P39
COOLANT SENDING 2
LEVEL 3
CONTACT UNITS
COOLANT TEMP P40
SENSING FUEL
BATTERY LEAK
DGC-1000 6 DETECTOR
P16 CHARGER 4
SENDER RETURN P46
FAIL
Installation
OUTPUT RELAYS - P33
CHASSIS
P41
GND MPU
EPS
+ P32 MAGNETIC
SUPPLYING FUEL MASTER
PICK-UP
LOAD PRE-ALARM ALARM PRE-START SOLENOID START 5A
+ P1 7
BATTERY
- P2
P29 P30 P27 P28 P23 P24 P21 P22 P19 P20 P25 P26
+
IF UNIT IS NOT PROVIDING ONE END OF THE J1939 BACKBONE, THEN CUT JUMPER TO REMOVE ON-BOARD TERMINATION RESISTOR. ALSO,
9
IF NOT PART OF THE BACKBONE, THE STUB CONNECTING THE UNIT TO THE BACKBONE SHOULD NOT EXCEED 3 FEET IN LENGTH.
IT IS HIGHLY RECOMMENDED THAT EACH EXTERNAL DC RELAY BE FITTED WITH A FLY-BACK DIODE ACROSS IT’S ENERGIZING COIL TO MINIMIZE
10
THE VOLTAGE TRANSIENT PRODUCED WHEN THE COIL IS SUDDENLY DISCONNECTED FROM IT’S POWER SUPPLY.
DGC-1000
GENERATOR
CIRCUIT
BREAKER
MDEC
A ECU
A
DGC-1000
G F E h g ECU CONNECTOR "X1"
TO B GENERATOR G F E h g
B Mating
BUS 480V Connector
X1 Wiring
49 50 51 25 26 Wire Harness
Numbers
C
C
N USER-SUPPLIED
N TERMINAL STRIP
J1939 CABLE
PROVIDED WITH UNIT
1 1 1
N.C. P9 P6 P3 9
P31 P45 P11 P8 P5 P34 P35 P36 P37 TERMINATION 1 1
P18 P10 P7 P4
EMERGENCY RESISTOR 2 2
- + 1A 1A 1A VOLT. VOLT. VOLT. VOLT. RED
5 STOP COM COM COM CAN HI 3 3
P17 5A 5A 5A PH A PH B PH C NEUT. BLK
CAN LO 4 4
HORN 5 5
AUTOMATIC BARE
P15
TRANSFER 8
PHASE PHASE PHASE
SWITCH
C CT B CT A CT OIL PRESSURE P38
LOW
P14 FUEL LEVEL P39
COOLANT SENDING 2
LEVEL 3
CONTACT UNITS
COOLANT TEMP P40
SENSING FUEL
BATTERY LEAK
DGC-1000 6
P16 CHARGER
4 DETECTOR
SENDER RETURN P46
FAIL
Installation
GND MPU
EPS
+ P32 MAGNETIC
SUPPLYING FUEL MASTER
PICK-UP
LOAD PRE-ALARM ALARM PRE-START SOLENOID START 5A
+ P1 7
BATTERY
- P2
P29 P30 P27 P28 P23 P24 P21 P22 P19 P20 P25 P26
+
8 J1939 SHIELD SHOULD BE GROUNDED AT ONLY ONE POINT. IF GROUNDED ELSEWHERE IN THE SYSTEM, CUT J1939 SHIELD CONNECTION TO UNIT.
4-15
This page intentionally left blank.
List of Figures
Figure 5-1. Test Set Diagram..................................................................................................................... 5-4
List of Tables
Table 5-1. Default Parameter Settings ...................................................................................................... 5-1
DGC-1000 Testing i
This page intentionally left blank.
ii Testing DGC-1000
SECTION 5 • TESTING
INTRODUCTION
The procedures of this section test DGC-1000 operation using the preset, factory-default settings.
EQUIPMENT REQUIRED
• Power supply, 12 or 24 Vdc
• Fuse, 2 A
• Voltage source, 60 Hz, 0 to 120 Vac
• Current source, 60 Hz, 0 to 5 Aac
• Signal generator, sine-wave, 0 to 5 kHz, 0 to 5V
• Digital voltmeter, 4½ digits (Fluke 8050A or equivalent)
• Continuity tester
• SPST switch (4)
• Variable resistor, 250 ohms (2)
• Variable resistor, 2,500 ohms
NOTE
Displayed voltage is equal to the generator potential transformer primary voltage setting
times the applied voltage divided by the generator potential transformer secondary
voltage setting.
Step 1. Verify that the battery input (terminals P1 and P2) voltage is 24.0 Vdc.
Step 2. Verify that the DGC-1000 displayed value is 24.0 ±0.5 Vdc.
Step 3. Apply 120.0 Vac, 60.0 hertz to phase A (line-to-neutral) generator voltage input (terminals P34
and P37).
Step 4. Verify that the DGC-1000 generator frequency displayed value is 60.0 ±0.2 hertz.
Step 5. Verify that the DGC-1000 phase A to neutral voltage displayed value is 120.0 ±2.0 Vac.
Step 6. Remove the voltage.
Step 7. Apply 120.0 Vac, 60.0 hertz to phases A and B generator voltage input (terminals P34 and P35).
Step 8. Verify that the DGC-1000 generator A to B voltage displayed value is 120.0 ±2.0 Vac.
Step 9. Remove the voltage.
Step 10. Apply 120.0 Vac, 60.0 hertz (line-to-neutral) to phase B generator voltage input (terminals P35
and P37).
Step 11. Verify that the DGC-1000 line-to-neutral voltage displayed value is 120.0 ±2.0 Vac.
Step 12. Remove the voltage.
Step 13. Apply 120.0 Vac, 60.0 hertz to phases B and C generator voltage input (terminals P35 and P36).
Step 14. Verify that the DGC-1000 generator B to C voltage displayed value is 120.0 ±2.0 Vac.
Step 15. Remove the voltage.
Step 16. Apply 120.0 Vac, 60.0 hertz (line-to-neutral) to phase C generator voltage input (terminals P36
and P37).
Step 17. Verify that the DGC-1000 line-to-neutral voltage displayed value is 120.0 ±2.0 Vac.
Step 18. Remove the voltage.
Step 19. Apply 120.0 Vac, 60.0 hertz to phases C and A generator voltage input (terminals P36 and P34).
Step 20. Verify that the DGC-1000 generator C to A voltage displayed value is 120.0 ±2.0 Vac.
Step 21. Remove the voltage.
PH A
PH B
PH C
NEUT.
AUTOMATIC
P15
TRANSFER
SWITCH OIL PRESSURE P38
PHASE
PHASE
PHASE
CCT
BCT
ACT
FUEL LEVEL P39 FUEL
SENDING
UNITS LEAK
CONTACT COOLANT TEMP P40 DETECTOR
SENSING
BATTERY
P16 CHARGER DGC1000 SNDR RTN P46
OUTPUT
RELAYS
FAIL
Testing
- P33
P41 GND
MPU
+ P32 MAGNETIC
5A PICK-UP
EPS
SUPPLYING
LOAD
PRE-ALARM
ALARM
PRE-START
FUEL
SOLENOID
MASTER
START
+ P1
D2839-11.vsd
04-24-01
DGC-1000
Metering Generator Current
NOTE
Displayed current is equal to the generator current transformer primary current setting
times the applied current divided by one or five (the nominal current value).
Step 1. Apply 1.000 Aac to the DGC-1000 generator five ampere phase A CT input (terminals P4 and
P5).
Step 2. Verify that the DGC-1000 phase A current displayed value is 100.0 ±2.0 amperes.
Step 3. Remove the current.
Step 4. Apply 1.000 Aac to the DGC-1000 generator five ampere phase B CT input (terminals P7 and
P8).
Step 5. Verify that the DGC-1000 phase B current displayed value is 100.0 ±2.0 amperes.
Step 6. Remove the current.
Step 7. Apply 1.000 Aac to the DGC-1000 generator five ampere phase C CT input (terminals P10 and
P11).
Step 8. Verify that the DGC-1000 phase C current displayed value is 100.0 ±2.0 amperes.
Step 9. Remove the current.
Oil Pressure
Step 1. Apply 60 ohms across the Oil Pressure transducer input (terminals P38 and P2).
Step 2. Verify that the DGC-1000 displayed value is 80 ±2.0 psi.
Coolant Temperature
Step 1. Apply 100 ohms across the Coolant Temperature transducer input (terminals P40 and P2).
Step 2. Verify that the DGC-1000 displayed value is 205 ±4.0°F.
NOTE
RPM as derived from the MPU is equal to [MPU output frequency (hertz) times 60]
divided by the number of flywheel teeth.
RPM as derived from the generator is equal to [generator output voltage frequency]
divided by the rated generator frequency (hertz) times the rated rpm.
Step 1. Apply a 5 Vac, 3,780 hertz sine wave to the DGC-1000 magnetic pickup unit inputs (terminals
P32 and P33).
Step 2. Verify that the DGC-1000 displayed value is 1,800 ±36 rpm.
Step 3. Remove the voltage.
NOTE
The DGC-1000 uses phase A voltage and phase B current for Power Factor calculations.
Therefore, if this test is performed with the current lagging the voltage by 120 degrees,
the displayed Power Factor will be approximately 1.00.
Step 1. Apply 120 Vac to phase A to neutral generator voltage inputs (terminals P34 and P37).
Step 2. Apply 1.0 Aac to phase B current transformer inputs (terminals P7 and P8) in phase with the
phase A to neutral voltage.
Step 3. Verify that the DGC-1000 displayed value is -0.50 ±0.02.
Step 4. Remove voltage and current.
NOTE
The displayed kW is equal to the kVA times the power factor.
Step 1. Apply in parallel 120 Vac to phase A to neutral (terminals P34 and P37), phase B to neutral
(terminals P35 and P37), and phase C to neutral (terminals P36 and P37).
Step 2. Apply in series and in phase with the voltage 1 Aac to Phase A current transformer input
(terminals P3 and P5), Phase B current transformer input (terminals P6 and P8), and Phase C
current transformer input (terminals P9 and P11).
Step 3. Verify that the DGC-1000 displayed value for individual phase kW is –30 ±2 kW.
Step 4. Verify that the DGC-1000 displayed value for total kW is –90 ±2 kW.
Step 5. Verify that the DGC-1000 displayed value for individual phase kVA is 60 ±2 kVA.
Step 6. Verify that the DGC-1000 displayed value for total kVA is within 180 ±5 kVA.
Step 7. Remove voltage and current.
Crank Cycle
NOTE
The DGC will go into cvercrank if the Off switch is not pressed before two crank cycles
expire. Pressing Off will reset this condition if it occurs.
Step 1. Verify that all output contacts are open.
Step 2. Press the Run switch on the front panel.
Step 3. Verify that the DGC-1000 displays CRANKING STATUS.
Step 4. Verify that only the Master Start, Auxiliary Start, Fuel Solenoid and Pre-Start output contacts are
closed during CRANKING CYCLE.
Step 5. Verify that only the Pre-Start contact remains closed during RESTING.
Step 6. Press the Off switch on the front panel.
Step 7. Press the Auto switch on the front panel.
Step 8. Apply a contact closure across the Automatic Transfer Switch input (terminals P15 and P2).
Step 9. Verify that the DGC-1000 displays CRANKING STATUS.
Step 10. Verify that only the Master Start, Auxiliary Start, Fuel Solenoid and Pre-Start output contacts are
closed during CRANKING CYCLE.
Step 11. Verify that only the Pre-Start contact remains closed during RESTING.
Step 12. Press the Off switch on the front panel.
Step 13. Open the contact across the Automatic Transfer Switch inputs.
Overcrank
Step 1. Press the Run switch on the front panel.
Step 2. Verify that after two crank cycles the DGC-1000 display indicates GEN OVER-CRANK ALARM
and that only the Alarm output contacts are closed.
Step 3. Press the Off switch on the front panel and verify that the DGC-1000 resets to the Ready mode
and that all output contacts open.
Overspeed
Step 1. Apply in parallel 120 Vac to phase A to neutral (terminals P34 and P37), phase B to neutral
(terminals P35 and P37), and phase C to neutral (terminals P36 and P37).
Step 2. Apply a 5 Vac, 4,000 hertz sine wave to the DGC-1000 MPU inputs (terminals P32 and P33).
Step 3. Press the Run switch on the front panel.
Step 4. Slowly increase the frequency to the DGC-1000 MPU input until an overspeed shutdown occurs.
Step 5. Verify shutdown occurs within 4,158 ±83 hertz (1,980 ±38 rpm).
Step 6. Verify that the DGC-1000 display indicates GEN OVERSPEED ALARM and that only the Alarm
output contacts are closed.
Step 7. Remove the voltages.
Step 8. Press the Off switch on the front panel and verify that the DGC-1000 resets to the Ready mode
and that all output contacts open.
Step 7. Verify that the DGC-1000 displayed value is within 0 to 17 psi when shutdown occurs.
Step 8. Verify that the DGC-1000 display indicates LOW OIL PRESSURE ALARM and that only the
Alarm output contacts are closed.
Step 9. Remove the voltage and return the resistance to 60 ohms.
Step 10. Press the Off switch on the front panel and verify that the DGC-1000 resets to the Ready mode
and that all output contacts open.
Emergency Stop
Step 1. Apply in parallel 120 Vac to phase A to neutral (terminals P34 and P37), phase B to neutral
(terminals P35 and P37), and phase C to neutral (terminals P36 and P37).
Step 2. Press the Run switch on the front panel.
Step 3. Open the contact across the Emergency Stop inputs (terminals P17 and P18).
Step 4. Verify that the DGC-1000 indicates EMERGENCY SHUTDOWN SWITCH PRESSED and that
all output contacts are open.
Step 5. Reapply the contact closure across the Emergency Stop inputs.
Step 6. Press the Off switch on the front panel and verify that the DGC-1000 resets to the Ready mode
and that all output contacts open.
Step 7. Remove the voltage.
List of Figures
Figure 6-1. BESTCOMS Title and Version ................................................................................................ 6-1
Figure 6-2. Sensing Transformers Screen................................................................................................. 6-1
Figure 6-3. RS-232 Comm Port Screen..................................................................................................... 6-2
Figure 6-4. Password Screen .................................................................................................................... 6-2
Figure 6-5. RS-232 Phone Book (Phone Book 2)...................................................................................... 6-2
Figure 6-6. Modem Comm Port Screen..................................................................................................... 6-3
Figure 6-7. Modem Phone Book ................................................................................................................ 6-3
Figure 6-8. Sensing Transformers Screen................................................................................................. 6-5
Figure 6-9. Pre-Alarms Screen, Low Fuel-Low Cool-Batt. OverVolt. Tab ................................................. 6-5
Figure 6-10. Pre-Alarms Screen, Maint. Interv.-Eng. kW Overload-Hi Cool Tab ...................................... 6-6
Figure 6-11. Pre-Alarms Screen, Low Oil-Low Batt Volt-Weak Batt Volt Tab ........................................... 6-7
Figure 6-12. Pre-Alarms Screen, Audible-Battery Charger-Fuel Level Sender Tab ................................. 6-8
INSTALLATION
BESTCOMS-DGC-1000 software operates with IBM-compatible personal computers (PCs) using
Microsoft® Windows® 95, 98, Me, 2000, XP, and NT®. The minimum recommended operating
requirements are listed below.
• IBM-compatible PC, 486DX2 or faster and a minimum of 4 MB of RAM
• CD-ROM drive
• An available serial port
Installing BESTCOMS-DGC-1000
1. Insert the BESTCOMS CD-ROM into the PC CD-ROM drive.
2. When the DGC-1000 Setup and Documentation CD menu appears, click the Install button for the
BESTCOMS application. The setup utility automatically installs BESTCOMS-DGC-1000 on your PC.
STARTING BESTCOMS
BESTCOMS is started by clicking the Windows® Start button, pointing to Programs, the Basler Electric
folder, and then clicking the BESTCOMS-DGC-1000 icon. At startup, a screen with the program title and
version number (Figure 6-1) is displayed briefly. After this dialog is displayed, the Sensing Transformers
screen (Figure 6-2) is displayed.
Version X.XX.XX
Copyright Basler Electric
ESTABLISHING COMMUNICATION
Communication between BESTCOMS and the DGC-1000 must be established before reading or
changing settings. BESTCOMS screen settings are updated only after communication is opened or the
communication settings have been changed.
DGC-1000 communication with BESTCOMS can be established through the RS-232 serial interface or
optional modem.
DGC. This limited access password allows all DGC-1000 settings to be read, but prevents any settings
changes.
DGC1000. This full access password allows all DGC-1000 settings to be read and changed.
OEMLVL. This special access password allows all DGC-1000 settings to be read and changed. It also
allows the DGC-1000 embedded firmware to be upgraded.
Passwords are case sensitive; all default passwords use upper-case letters. More information about
passwords is provided in the Password Protection sub-section.
The unit ID number displayed in the Password screen indicates the identification number of the DGC-
1000. Information about changing the unit ID for polled communication is provided in Changing the
Communication Parameters.
When the appropriate password is entered in the Password screen and OK is clicked, communication
with the DGC-1000 is established.
RS-232 Phone Book
The RS-232 phone book (Phone Book 2, Figure 6-5) is
accessed by clicking the Phone Book button on the
RS-232 Comm Port screen (accessed by clicking
Communications on the menu bar, then Open,
RS232 Connection). This screen allows phone book
entries to be selected, added, edited, and deleted.
Selecting an Entry. A phone book entry is selected
from the list of entries in the Name window of the
phone book screen. When an entry in the list is
highlighted, the entry's communication port number is
indicated in the Comm Port field. Clicking OK selects
the entry and returns to the Comm Port screen. The
communication port number will be displayed in the
Comm Port field of the Comm Port screen.
Adding an Entry. A phone book entry is added to the
list of entries in the Name window of the phone book
screen by clicking Add Entry. When the Add Entry
button is clicked, an Add New Entry screen appears.
This screen has a field for assigning a descriptive Figure 6-5. RS-232 Phone Book
name to the entry and a Comm Port field for assigning (Phone Book 2)
a communication port number to the entry. Clicking the
OK button saves the entry and returns to the Phone
Book 2 screen.
Unit ID
Clicking Unit ID on the menu bar and then clicking Select Another Unit ID displays the Select Another
Unit dialog box. The ID number of another DGC-1000 on the same network can be entered in the Unit ID
field. Clicking the Save button causes BESTCOMS to disconnect from the current DGC-1000 and log
onto the DGC-1000 identified by the number in the Unit ID field. Because this feature allows selection of a
new unit ID without breaking communication, it is useful for applications where a modem is used to
remotely connect to a network of units.
DGC-1000 BESTCOMS Software 6-3
CHANGING SETTINGS
DGC-1000 settings are arranged into seven groups.
• Sensing Transformers • System
• Pre-Alarms • Auxiliary I/O
• Alarms • Modem
• Crank
Each setting group has a corresponding button (shown in Figure 6-8) that can be selected to access that
group of settings. The seven setting groups can also be accessed by clicking Screens on the menu bar
and then selecting the desired setting group from the list. Once a setting group is accessed, the individual
settings of the group can be viewed and changed.
A setting is changed by clicking within the setting field and typing the new setting. If the new setting is
outside the prescribed setting range, a dialog box showing the acceptable range appears when another
setting field is accessed or when attempting to send the new setting to the DGC-1000. The following
paragraphs describe how settings are sent to the DGC-1000.
Sending Settings
Setting changes are sent to the DGC-1000 by clicking the Send Settings button. This causes all
BESTCOMS settings to become the DGC-1000 settings. Settings can also be sent to the DGC-1000 by
clicking Communications on the menu bar and clicking Send to DGC.
Receiving Settings
DGC-1000 settings are retrieved by clicking the Get Settings button. This causes the current settings of
the DGC-1000 to be loaded into BESTCOMS. Settings can also be received from the DGC-1000 by
clicking Communications on the menu bar and clicking Get from DGC. Settings are also automatically
retrieved when logging onto the DGC-1000.
SETTING DEFINITIONS
Each of the seven setting groups has a corresponding BESTCOMS screen. The settings of each screen
are categorized by one or more tabs. In the following paragraphs, settings are arranged and defined
according to the organization of the BESTCOMS screens and tabs.
Sensing Transformers
The button displaying a transformer icon is clicked to access the Sensing Transformers screen. The
Sensing Transformers screen can also be accessed by clicking Screens on the menu bar and clicking
Sensing Transformers. Sensing Transformer settings are shown in Figure 6-8 and described in the
following paragraphs.
Generator PT – Primary (Volts). This setting selects the rating of the primary side of the transformer used
to sense generator voltage. The primary voltage setting is adjustable from 1 to 15,000 Vac.
Generator PT – Secondary (Volts). This setting selects the rating of the secondary side of the transformer
used to sense generator voltage. The secondary voltage setting is adjustable from 1 to 480 Vac.
Generator CT – Primary (Amps). This setting selects the rating of the primary side of the transformer used
to sense generator current. The primary current setting is adjustable from 1 to 5,000 Aac.
Pre-Alarms
Click the Pre Alarm button to access the Pre-Alarm Settings screen or click Screens on the menu bar
and click Pre-Alarm Settings. The Pre-Alarms screen consists of five tabs.
• Low Fuel-Low Cool-Batt. OverVolt. • Audible – Battery Charger – Fuel Level Sender
• Maint. Interv.-Eng. kW Overload-Hi Cool • CAN Bus – Diagnostic Trouble Codes.
• Low Oil-Low Batt. Volt-Weak Batt Volt
Low Fuel Pre-Alarm – Enable. This setting enables and disables annunciation of a low fuel pre-alarm.
Low Fuel Pre-Alarm – Threshold (% Full Tank). This setting selects the fuel level that will trigger a low fuel
pre-alarm. A threshold setting of 10 to 100 percent may be entered.
Maintenance Interval Pre-Alarm – Enable. This setting enables and disables annunciation of a
maintenance interval pre-alarm.
Maintenance Interval Pre-Alarm – Threshold (Hours). This setting selects the length of the maintenance
interval. An interval of 0 to 5,000 hours may be selected. When a new threshold setting is entered, the
Maintenance Interval Timer Reset checkbox of the System Settings screen is selected to apply the new
value.
Engine kW Over Load Pre-Alarm – Enable. This setting enables and disables annunciation of an engine
kW overload pre-alarm.
Engine kW Over Load Pre-Alarm – Threshold (% of Rated). This setting, expressed as a percentage of
the engine rating, selects the generator power level that will trigger an engine kW overload pre-alarm. A
threshold setting of 95 to 140 percent may be entered.
Hi Coolant Temperature Pre-Alarm – Enable. This setting enables and disables annunciation of a high
coolant temperature pre-alarm. A 60 second activation delay prevents a high coolant temperature pre-
alarm from occurring at engine startup.
Hi Coolant Temperature Pre-Alarm – Threshold (Deg). This setting selects the coolant temperature that
will trigger a high coolant temperature pre-alarm. A threshold setting of 100 to 280 degrees Fahrenheit or
6-6 BESTCOMS Software DGC-1000
38 to 138 degrees Celsius may be entered. The unit of measure (Fahrenheit or Celsius) is determined by
the Unit System setting of the System screen.
Low Oil-Low Batt Volt-Weak Batt Volt Tab
The Low Oil-Low Batt Volt-Weak Batt Volt Tab settings are shown in Figure 6-11 and described in the
following paragraphs.
Figure 6-11. Pre-Alarms Screen, Low Oil-Low Batt Volt-Weak Batt Volt Tab
Low Oil Pressure Pre-Alarm – Enable. This setting enables and disables annunciation of a low oil
pressure pre-alarm. A 10 second activation time delay prevents low oil pressure annunciation during
engine startup.
Low Oil Pressure Pre-Alarm – Threshold. This setting selects the oil pressure level that will trigger a low
oil pressure pre-alarm. A threshold setting of 3 to 150 psi or 20 to 1035 kPa may be entered. The unit of
measure (psi or kPa) is determined by the Unit System setting of the System screen. A 10 second
activation time delay prevents low oil pressure annunciation during engine startup.
Low Battery Voltage Pre-Alarm – Enable. This setting enables and disables annunciation of a low battery
voltage pre-alarm.
Low Battery Voltage Pre-Alarm – Threshold (Volts). This setting selects the voltage level that will trigger a
low battery voltage pre-alarm. The threshold is adjustable from 6 to 12 Vdc for 12 Vdc systems and 12 to
24 Vdc for 24 Vdc systems.
Low Battery Voltage Activation Time Delay (Sec). This setting selects the time delay from when low
battery voltage is detected until a pre-alarm is annunciated. A time delay of 1 to 10 seconds may be
entered.
Weak Battery Voltage Pre-Alarm – Enable. This setting enables and disables annunciation of a weak
battery voltage pre-alarm.
Weak Battery Voltage Pre-Alarm – Threshold (Volts). This setting selects the voltage level that will trigger
a weak battery voltage pre-alarm. The threshold is adjustable from 4 to 8 Vdc for 12 Vdc systems and 8 to
16 Vdc for 24 Vdc systems.
Weak Battery Voltage Pre-Alarm – Activation Time Delay (Sec). This setting selects the time delay from
when weak battery voltage is detected until a pre-alarm is annunciated. A time delay of 1 to 10 seconds
may be entered.
Audible Alarm. This setting enables and disables the DGC-1000 horn output.
Battery Charger Failure Pre-Alarm. This setting enables and disables annunciation of a battery charger
failure pre-alarm.
Fuel Level Sender Failure Pre-Alarm. This setting enables and disables annunciation of a fuel level
sender failure pre-alarm.
CAN Bus – Diagnostic Trouble Codes Tab
The CAN Bus – Diagnostic Trouble Codes Tab settings are shown in Figure 6-13 and described in the
following paragraphs.
Loss of ECU Communication – Pre Alarm Selection. This setting enables and disables annunciation of a
loss of ECU communication pre-alarm. This pre-alarm can occur only when the DGC-1000 is in Off mode
and pulsing the ECU has failed to establish communication with the ECU. For details about ECU support,
refer to Section 3, Functional Description.
Diagnostic Trouble Code Pre-Alarm – Enable. This setting enables and disables annunciation of
diagnostic trouble codes (DTC) pre-alarms as they are received from the ECU.
Alarms
Click the Alarm button to access the Alarms screen or click Screens on the menu bar and click Alarm
Settings. The Alarms screen consists of two tabs: Hi Cool-Low Fuel-Low Oil and Overspeed-Sender Fail.
Hi Cool-Low Fuel-Low Oil Tab
The Hi Cool-Low Fuel-Low Oil Tab settings are shown in Figure 6-14 and described in the following
paragraphs.
Hi Cool Temperature Alarm – Alarm Enable. This setting enables and disables annunciation of a high
coolant temperature alarm and engine shutdown. A 60 second activation delay prevents a Hi Coolant
Temperature Alarm from occurring at engine startup.
Overspeed Alarm – Alarm Enable. This setting enables and disables alarm annunciation and engine
shutdown for an overspeed condition.
Overspeed Threshold (% of Rated). This setting selects the percentage of overspeed that triggers an
overspeed alarm and engine shutdown. The threshold is adjustable from 105 to 140 percent of nominal
speed.
6-10 BESTCOMS Software DGC-1000
Overspeed Alarm – Alarm Activation (MilliSecond). This setting adjusts the time delay from when an
overspeed alarm condition is detected until it is annunciated and the engine is shut down. A time delay of
0 to 500 milliseconds may be entered.
Sender Failure Alarm – Cool Temp. Send Fail Alarm. This setting enables and disables alarm
annunciation and engine shutdown for a coolant temperature sender failure.
Sender Failure Alarm – Coolant Temp Alarm Delay. This setting adjusts the time delay from when a
coolant temperature sender failure is detected until it is annunciated and the engine is shut down. A time
delay of 5, 10, 15, 20, 25, or 30 minutes may be selected.
Sender Failure Alarm – Oil Press. Sender Fail Alarm. This setting enables and disables alarm
annunciation and engine shutdown for an oil pressure sender failure. An oil pressure sender failure alarm
is annunciated and engine shutdown is initiated when the Global Sender Failure Alarm Time Delay setting
expires.
Sender Failure Alarm – Loss of Gen. Voltage Alarm. This setting enables and disables alarm
annunciation and engine shutdown for a loss of generator voltage. A loss of generator voltage alarm is
annunciated when the generator voltage decreases below 1.5 Vac and the Global Sender Failure Alarm
Time Delay expires. This setting does not disable a Sender Failure alarm for the speed signal source
when generator frequency is selected as the speed signal source.
Sender Failure Alarm – Global Sender Failure Alarm Time Delay (Sec). This setting selects the time delay
between when an oil pressure sender failure, loss of generator voltage failure, or MPU sender failure is
detected and alarm annunciation and engine shutdown.
Engine Cranking
Click the Crank button to access the Engine Cranking screen or click Screens on the menu bar and click
Crank Settings. Engine cranking settings are shown in Figure 6-16 and are described in the following
paragraphs.
Cranking Style. This setting selects the engine cranking method as continuous or cycle.
Crank Disconnect Limit (% of Rated). This setting selects the percentage of rated engine speed at which
cranking is terminated. A disconnect limit of 10 to 100 percent may be entered.
Crank Disconnect Limit (% of Rated). This setting selects the percentage of rated engine speed at which
cranking is terminated. A disconnect limit of 10 to 100 percent may be entered.
System
Click the SYST button to access the System Settings screen or click Screens on the menu bar and click
System Settings. System settings are shown in Figure 6-17 and are described in the following
paragraphs.
Genset’s kW Rating. The generator power rating is entered in this field. A genset kW rating of 10 to 9,999
may be entered.
Cool Down Time. This setting selects the time between when the generator load is removed and the
engine is stopped by a remote shutdown. A cool-down time of 0 to 60 minutes may be entered.
Rated Engine RPM. This setting selects the rated rotating speed of the engine. A value of 750 to 3,600
rpm may be entered.
Maintenance Interval Timer Reset. Selecting this checkbox terminates the maintenance interval pre-alarm
and resets the maintenance interval timer back to the programmed value. The Send Settings button
must be clicked for the reset to take effect.
Embedded Firmware Version. This read-only field displays the DGC-1000 firmware version.
Total kW Hours Reset. Selecting this checkbox resets the accumulated kilowatt-hours to zero. The Send
Settings button must be clicked for the reset to take effect.
6-12 BESTCOMS Software DGC-1000
Battery Volts. This setting selects either 12 Vdc or 24 Vdc as the starting battery nominal voltage.
NFPA Level. This setting selects whether or not NFPA (National Fire Prevention Association)
requirements are in effect. If NFPA compliance is not required, a setting of 0 can be selected to disable
the feature. Selecting NFPA level 1 or 2 affects DGC-1000 operation in the following ways.
• The number of crank cycles is fixed at 3.
• Crank cycle time is fixed at 15 seconds.
• Continuous crank time is fixed at 45 seconds.
• The low coolant temperature pre-alarm setting is fixed at 70°F.
# Flywheel Teeth. This setting selects the number of teeth on the engine flywheel. A value of 50 to 500
may be entered.
Speed Signal Source. This setting selects from three sources for obtaining the engine speed. The speed
signal source can be obtained from the magnetic pickup (MPU), generator frequency, or derived from
both the MPU and generator frequency. When both the MPU and generator frequency are selected as the
speed signal source, the MPU has priority. If both MPU and generator frequency are selected and the
MPU fails, generator frequency is used as the speed signal source and a non-programmable MPU sender
failure pre-alarm is annunciated.
Generator Connection. This setting selects the configuration of the generator voltage sensing circuitry.
Three-phase line-to-line, three-phase line-to-neutral, or single-phase A-phase to B-phase sensing may be
selected.
Generator Frequency. This setting selects either 50 hertz or 60 hertz as the nominal generator frequency.
Unit System. This setting selects either the English or metric unit system for displaying the oil pressure
and coolant temperature parameters in BESTCOMS and the DGC-1000 HMI.
NOTE
CANBus Interface settings are disabled (and grayed out) unless OEM-level
password access is obtained. See Password Protection for information regarding
password access levels.
Generator Rotation. This setting selects either ABC or ACB phase rotation.
CANBus Interface – Enable ECU Support. This setting enables and disables the DGC-1000 CAN
interface. When enabled, the CAN interface allows the DGC-1000 to communicate with an engine control
unit (ECU). The mode of J1939 communication depends on the Engine Configuration setting selected.
CANBus Interface – Engine Configuration. This setting selects one of three CAN interface configurations:
Standard J1939, Volvo Penta EDC III, or MTU MDEC.
CANBus Interface – Unit J1939 Address. This setting, enabled only for an Engine Configuration setting of
Standard J1939 or Volvo Penta EDC III, selects the address to be used by the DGC-1000 for SAE J1939
communication. A value of 0 to 253 may be entered.
CANBus Interface – Speed Select. This setting, enabled only for an Engine Configuration setting of Volvo
Penta EDC III, configures the Volvo Penta EDC III to operate the engine at the primary or secondary base
speed. If the engine is configured by Volvo for 60 hertz applications, the primary base speed is 1,800 rpm
and the secondary base speed is 1,500 rpm. If the engine is configured by Volvo for 50 hertz applications,
the primary base speed is 1,500 rpm and the secondary base speed is 1,800 rpm.
CANBus Interface – Accelerator Position. This setting, enabled only for an Engine Configuration setting of
Volvo Penta EDC III, is expressed as a percentage and tells the Volvo Penta EDC III where to set the
engine speed (trim) relative to the base speed. The range of the setting is the base speed ±120 rpm. A
setting of 0% will cause the engine to run at 120 rpm below the base speed, a setting of 50% will cause
the engine to run at the base speed, and a setting of 100% will cause the engine to run at 120 rpm above
the base speed. The Accelerator Position setting is linear with a gain of 2.4 rpm/%. This setting is not
saved in nonvolatile memory and defaults back to 50% after DGC-1000 operating power is cycled.
CANBus Interface – Module Type. This setting, enabled only for an Engine Configuration setting of MTU
MDEC, selects one of four MDEC ECU types: Module 201, Module 302, Module 303, or Module 304.
CANBus Interface – Speed Demand Source. This setting, enabled only for an Engine Configuration
setting of MTU MDEC, selects one of six speed demand sources for the MDEC ECU: Analog CAN, Up
Down ECU, Up Down CAN, Analog ECU, Frequency, or No CAN Demand.
DGC-1000 BESTCOMS Software 6-13
CANBus Interface – Engine RPM. This setting, enabled only for an Engine Configuration setting of MTU
MDEC, selects the rated rpm for the engine.
Input/Output Settings
Click the AUX I/O button to access the Input/Output Settings screen or click Screens on the menu bar
and click Input/Output Settings. The Input/Output Settings screen consists of two tabs: Programmable
Input Contact Setup and Aux Output Setup.
NOTE
In order for the four-wire delta voltage sensing mode to function when an
appropriately programmed auxiliary input closes, the Generator Connection
setting on the System Settings screen must be set for 3 Phase L-N.
annunciate an alarm or pre-alarm when the selected function triggers the programmable input.
Programmable Input – Auxiliary Input Label. This setting field is enabled only when Auxiliary Input is
selected as the programmable input function. A user-assigned label (eight characters, maximum) can be
entered for the corresponding programmable input.
Figure 6-18. Input/Output Settings Screen, Programmable Input Contact Setup Tab
The last four items of the list are the four programmable load buttons that appear on the metering screen.
These four buttons may be configured to operate any combination of the eight auxiliary output contacts.
Load buttons 1 and 2 have fixed labels of Load 1 and Load 2. Load buttons 3 and 4 have programmable
labels. Each label can consist of six alphanumeric characters, maximum. Refer to the Metering
paragraphs for more information about using the Load buttons.
Modem Settings
If equipped with a modem (style X1X or X2X), the DGC-1000 can dial an alphanumeric pager when any
of the selected inputs are activated or selected events occur. Click the MODEM button to access the
NOTE
Upon completion of DGC-1000 setup, communication with BESTCOMS must be
closed to enable modem dial-in and dial-out.
When a fault occurs for which dial-out has been programmed, the modem will
dial out and send a message. During the dial-out time, neither dial-in nor local
RS-232 access is available. Access is available after the message has been sent
or during the modem off-line delay. If no access is allowed, removing the fault
and cycling the power to the DGC-1000 resets the DGC-1000 and allows access.
The ECU DTC Info and ECU Data tabs are visible and enabled only when ECU support is enabled on the
BESTCOMS System Settings screen and the Engine Configuration is Standard J1939 or Volvo Penta
EDC III.
The MTU MDEC tab is visible and enabled only when ECU support is enabled on the BESTCOMS
System Settings screen and the Engine Configuration is MTU MDEC.
When viewing the Metering screen, metering can be enabled and disabled by clicking the Meter button.
When viewing other screens, metering can be enabled and disabled through the Metering menu on the
menu bar
System Tab
System tab metering values are shown in Figure 6-22 and described in the following paragraphs.
Coolant Temp. Two metering fields display engine coolant temperature in degrees Fahrenheit and
degrees Celsius.
Oil Pressure. Two metering fields display engine oil pressure in pounds per square inch and kilopascals.
Battery Voltage. This metering value indicates the battery voltage level.
Fuel Level. This metering value indicates the percentage of remaining fuel.
Speed. This metering value indicates the rotational speed of the engine in revolutions per minute.
Load. This metering value, expressed as a percentage of the genset power rating, indicates the genset
load. The genset power rating is entered through the Genset’s kW Rating setting on the System Settings
screen.
Voltage Tab
Metering values displayed on the Voltage tab (Figure 6-23) depend upon the Generator Connection
setting of the System Settings screen.
Current Tab
Metering values displayed on the Current tab (Figure 6-24) depend upon the Generator Connection
setting of the System Settings screen.
Power Tab
The Power tab (Figure 6-25) displays generator apparent power (kVA) and generator real power (kW).
Metered power values depend upon the Generator Connection setting of the System Settings screen.
When the Generator Connection setting is 3 Phase L-L or 3 Phase L-N, metered power values are
displayed for phases A, B, C, and all phases combined.
When the Generator Connection setting is 1 Phase A-B, metered power values are displayed for phases
A, B, and both phases combined.
General Tab
General tab metering values are displayed in Figure 6-26 and described in the following paragraphs.
Power Factor. This value is the calculated result of the real generator power divided by the apparent
generator power (W ÷ VA).
Gen Frequency. This metering value indicates the frequency, in hertz, of the monitored generator voltage.
Total KW Hours. This metering value displays the accumulated generator kilowatt-hours. Total kilowatt-
hours can be reset through the Total KW Hours Reset checkbox on the System Settings screen. Total
kilowatt-hours can also be adjusted by a user with OEM-level password access. See Run Time and KW
Hours for more information.
Summary Tab
The Summary tab (Figure 6-27) displays all of the metering values contained on the System, Voltage,
Current, Power, and General tabs. Voltage, current, and power metering values displayed on the
Summary tab depend upon the Generator Connection setting of the System Settings screen.
Alarms Tab
Alarms tab indicators (Figure 6-28) are divided into four categories: Pre-Alarms, Alarms, Sender Failure
Alarms, and EPS.
Pre-Alarms, Alarms, and Sender Failure Alarms. When a pre-alarm or an alarm becomes active, the
indicator next to the pre-alarm or alarm label changes from gray to green. In order for a pre-alarm to be
annunciated, it must be enabled through the settings of the Pre-Alarms screen. In order for an alarm or
sender failure alarm to be annunciated, it must be enabled through the settings of the Alarms screen.
EPS – Supplying Load. When the generator is supplying current to the load, this indicator changes from
gray to green.
Clicking the View Engine Configuration button on the ECU Data tab displays the Engine Configuration
screen shown in Figure 6-30. This screen displays a list of specifications that are specific to the engine
being controlled by the ECU.
DGC-1000 BESTCOMS Software 6-23
Figure 6-30. Engine Configuration Screen
PROGRAMMABLE SENDERS
Click Configure on the menu bar and click Programmable Senders to access the Programmable
Senders screen. (If the Metering screen is being viewed, metering will need to be disabled to access the
Configure menu.)
The Programmable Senders screen has three tabs: Coolant Temperature, Oil Pressure, and Percent Fuel
Level. Because the setting fields and buttons of each tab are so similar, only the Coolant Temperature tab
settings (Figure 6-34) are described here.
Get Cool. Data From DGC. If communication with a DGC-1000 is enabled, clicking this button retrieves
the sender data points from the DGC-1000 and refreshes the graph.
Send Cool. Data To DGC. Clicking this button sends the displayed data points to the DGC-1000.
Load Cool. Settings File. Clicking this button displays an Open dialog box where a sender file containing
sender data points can be retrieved. Some standard data point files for the three senders are included
with BESTCOMS. Coolant temperature sender files have a CS1 extension, oil pressure sender files have
an OS1 extension, and fuel level sender files have an FS1 extension.
Create Cool. Settings File. Clicking this button displays a Save As dialog box where the transducer data
points created in BESTCOMS can be saved in a sender file. While it is possible to create individual
sender files for each transducer, it is not necessary. The data for all three senders is automatically saved
with the DGC-1000 configuration file. The Settings Files sub-section contains information about creating
DGC-1000 configuration files.
Resistance. The 11 resistance points in this column are not adjustable. The DGC-1000 has been factory
calibrated at these points to maximize accuracy.
Degrees F/Degrees C. Temperature values entered in this column must always maintain a descending
order. If English units are used, adjacent coolant temperature points must be separated by at least 2°F. If
metric units are used, adjacent oil pressure points must be separated by at least 7 kPa. The coolant
temperature range is 32 to 400°F or 0 to 240°C. The oil pressure setting range is 0 to 250 psi or 0 to
1,725 kPa. The fuel level setting range is 0 to 100%.
Sender Slope. If a sender requires a positive slope, Positive can be selected to invert the values in the
Resistance column.
6-26 BESTCOMS Software DGC-1000
Figure 6-34. Programmable Senders Screen, Coolant Temperature Tab
Print This Graph. Clicking this button displays a print preview screen that allows selection of a printer,
page orientation, and graph image magnification. Clicking Print sends the graph image to the target
printer. Clicking Close returns to the Programmable Senders screen.
Reset Factory Settings. Clicking this button restores the factory default data points in the Degrees
NOTE
When metric values are used and changes are made to the oil pressure sender
data points, undesirable internal rounding of some data points can occur. For
example, select 700 kPa for one data point, create a sender file, and the value is
rounded to 697. Rounding that occurs will never be greater than 4 kPa.
F/Degrees C column and graph. This does not update the data points in the DGC-1000. the DGC-1000 is
updated by clicking the Send Cool. Data to DGC button.
EVENT LOG
The event log provides a historical record of events detected by the DGC-1000. Click Event Log on the
menu bar to access the event log screen (Figure 6-367).
PASSWORD PROTECTION
Password protection guards against unauthorized changing of DGC-1000 settings. DGC-1000 passwords
are case sensitive. Three levels of password protection are available. Each level is described in the
following paragraphs.
• Limited Access. This password level allows all DGC-1000 settings to be read, but prevents any
changes to settings. The default, limited-access password is DGC.
• Full Access. This password level allows all DGC-1000 settings
to be read and allows all settings except Accumulated Engine
Runtime and Total KW Hours to be changed. The default, full-
access password is DGC1000.
• OEM Access. This password allows all DGC-1000 settings to be
read and allows all settings to be changed. It also allows the
DGC-1000 embedded firmware to be upgraded. The default,
OEM-access password is OEMLVL.
Changing Passwords
Passwords can be changed only after communication between the
PC and DGC-1000 is established. Changes to passwords are made
through the Change Password dialog box. To access the Change
Password dialog box, click Communications on the menu bar and
click Change Password.
The content of the Change Password dialog box depends on the
password level used when accessing the dialog box. For example,
someone logged in with a full-access password will be able to
change only the limited-access and full-access passwords—not the
OEM-access password. Figure 6-389 illustrates the Change Pass-
word dialog box with all three access levels shown.
Figure 6-39. Change
A password is changed by selecting the access level, entering the
Password Dialog Box
new password, and then re-entering the new password to confirm
the entry.
Once a password is changed, it should be stored in a secure location. If a user-defined password is lost
or forgotten, contact Basler Electric for instructions on regaining password access.
TERMINATING COMMUNICATION
DGC-1000 communication is terminated by clicking Communications on the menu bar and clicking
Close. If unsaved settings changes were made, you are prompted to save the changes in a new or
existing settings file. When you execute the close communication command, with or without saving
settings, communication with the DGC-1000 is terminated. If you choose to exit BESTCOMS (by clicking
File on the menu bar and then Exit) without first closing communication, you are still given the opportunity
to save any settings changes.
EMBEDDED FIRMWARE
Embedded firmware is the operating program that controls the actions of the DGC-1000. The DGC-1000
stores firmware in nonvolatile flash memory that can be reprogrammed through the RS-232
communication port. It is not necessary to replace EPROM chips when updating the firmware with a
newer version.
Updating Firmware
Future enhancements to DGC-1000 functionality may make a firmware update desirable. Because default
settings are loaded when DGC-1000 firmware is updated, your settings should be saved in a file prior to
upgrading firmware. DGC-1000 firmware can be updated by performing the following steps.
1. Connect a communication cable between the RS-232 connector of the DGC-1000 and the
appropriate communication port of your PC. Start BESTCOMS-DGC-1000, open communication, and
gain password access with the OEM-access password.
2. Place the DGC-1000 in Off mode. This can be accomplished by double-clicking the Off indicator on
any of the BESTCOMS screens or by pressing the Off button on the DGC-1000 front panel.
3. Click Configure on the menu bar and click Upgrade Embedded Firmware. The Embedded
Firmware Upgrade screen of Figure 6-40 will appear.
INTRODUCTION
This appendix lists all DGC-1000 parameter settings and their default values. This listing is in the form of
a settings record that may be used to record information relative to your system. These settings sheets
may be removed and photocopied.
Genset ID Date
DGC-1000 Serial Number Software Version Number
Pre-Alarm Settings
Setting Parameter Default Setting User Setting
Low Fuel Pre-Alarm Status Disabled
Low Fuel Pre-Alarm Threshold 25% of Full Tank
Low Coolant Temp Pre-Alarm Status Disabled
Low Coolant Temp Pre-Alarm Threshold 50°F
Battery Overvoltage Pre-Alarm Status Disabled
Battery Overvoltage Pre-Alarm Threshold 30.0 V
Maintenance Interval Pre-Alarm Status Disabled
Maintenance Interval Pre-Alarm Threshold 500 h
Cranking Settings
System Settings
10 320°F
30 300°F
60 242°F
100 205°F
150 180°F
200 160°F
300 138°F
400 122°F
600 104°F
25 113°F
50 83°F
75 68°F
100 52°F
125 37°F
150 26°F
175 17°F
200 10°F
225 6°F
250 0°F
33 99%
58 87%
84 75%
110 62%
136 50%
162 38%
188 26%
214 13%
240 1%
250 0%
Condition to Annunciate #1 #2 #3 #4 #5 #6 #7 #8
High Coolant Temperature Alarm
Low Oil Pressure Alarm
Coolant Temp. Sender Failure Alarm
Oil Pressure Sender Failure Alarm
Loss of Generator Voltage Alarm
Speed Sender Failure Alarm
Low Fuel Alarm
Low Coolant Level Alarm
Over-Crank Alarm
Emergency Stop Alarm
Overspeed Alarm
Low Fuel Pre-Alarm
Low Coolant Temp. Pre-Alarm
kW Overload Pre-Alarm
High Coolant Temp. Pre-Alarm
Low Oil Pressure Pre-Alarm
Low Battery Voltage Pre-Alarm
Weak Battery Voltage Pre-Alarm
Battery Charger Failure Pre-Alarm
Scheduled Maintenance Pre-Alarm
Unit Not in Auto
Fuel Leak/Sender Failure Pre-Alarm
Modem/Dial-Out Settings