KDGC Control Panel Manual PDF
KDGC Control Panel Manual PDF
KDGC Control Panel Manual PDF
for
DGC-2000
DIGITAL GENSET
CONTROLLER
Basler
Digital
Genset
Controller
DGC-2000
Not In Supplying
Auto Alarm Load
Select Display
Raise Lower Previous
Enter Toggle
Scroll Scroll
This manual provides information concerning the installation and operation of the DGC-2000 Digital
Genset Controller. To accomplish this, the following is provided.
• General Information
• Specifications
• Functional Description
• Installation Information
• Communication Software Description
• Testing Procedures
WARNING!
TO AVOID PERSONAL INJURY OR EQUIPMENT DAMAGE, ONLY QUALIFIED
PERSONNEL SHOULD PERFORM THE PROCEDURES PRESENTED IN THIS
MANUAL.
DGC-2000 INTRODUCTION i
First Printing: November 1997
Printed in USA
© 1997, 1998, 1999 Basler Electric Co., Highland, IL 62249
April 1999
CONFIDENTIAL INFORMATION
OF BASLER ELECTRIC COMPANY, HIGHLAND, IL. IT IS LOANED FOR
CONFIDENTIAL USE, SUBJECT TO RETURN ON REQUEST, AND WITH THE
MUTUAL UNDERSTANDING THAT IT WILL NOT BE USED IN ANY MANNER
DETRIMENTAL TO THE INTEREST OF BASLER ELECTRIC COMPANY.
It is not the intention of this manual to cover all details and variations in equipment, nor
does this manual provide data for every possible contingency regarding installation or
operation. The availability and design of all features and options are subject to
modification without notice. Should further information be required, contact Basler Electric
Company, Highland, Illinois.
BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND, IL 62249 USA
http://www.basler.com, [email protected]
PHONE 618-654-2341 FAX 618-654-2351
ii DGC-2000 INTRODUCTION
CONTENTS
SECTION 1 GENERAL INFORMATION ................................................................................................ 1-1
General................................................................................................................................ 2-1
Front Panel Display ............................................................................................................. 2-1
DGC-2000 Connections ...................................................................................................... 2-2
General................................................................................................................................ 3-1
Inputs................................................................................................................................... 3-2
Battery Operating Voltage ............................................................................................ 3-2
Contact Sensing Inputs................................................................................................. 3-2
Sending Unit Inputs....................................................................................................... 3-3
Speed Signal Inputs...................................................................................................... 3-3
Voltage Inputs ............................................................................................................... 3-3
Current Inputs ............................................................................................................... 3-3
Serial Communications Input ........................................................................................ 3-3
Microprocessor.................................................................................................................... 3-3
Formulas ....................................................................................................................... 3-3
Related circuits ............................................................................................................. 3-4
Outputs................................................................................................................................ 3-4
Software .............................................................................................................................. 3-5
Display Modes .............................................................................................................. 3-5
Normal Mode ................................................................................................................ 3-5
Menu Mode ................................................................................................................... 3-5
Exiting Menu Mode ..................................................................................................... 3-15
Modifying Setpoints..................................................................................................... 3-16
Alternate Display Mode............................................................................................... 3-17
Factory Key Code Setting ................................................................................................. 3-17
Allowable Key Code Pushbuttons ..................................................................................... 3-18
Parameters And Default Settings ...................................................................................... 3-18
Front Panel Adjustable Parameters ............................................................................ 3-18
All Parameters ............................................................................................................ 3-18
General................................................................................................................................ 4-1
Hardware............................................................................................................................. 4-1
Mounting.............................................................................................................................. 4-1
Connections ........................................................................................................................ 4-3
Communication Connectors And Settings........................................................................... 4-7
RS-232 Connector ........................................................................................................ 4-7
Communication Settings ............................................................................................... 4-7
Introduction.......................................................................................................................... 5-1
Equipment Required............................................................................................................ 5-1
Initial Test Procedure .......................................................................................................... 5-1
Metering Test Procedure..................................................................................................... 5-3
Metering Battery And Generator Voltages .................................................................... 5-3
Metering Bus Voltages.................................................................................................. 5-5
Metering Generator Current.......................................................................................... 5-5
Oil Pressure .................................................................................................................. 5-5
Coolant Temperature .................................................................................................... 5-5
Percent Fuel Level ........................................................................................................ 5-5
Engine Speed (RPM) .................................................................................................... 5-5
Generator Power Factor ............................................................................................... 5-6
Generator kW And kVA ................................................................................................ 5-6
Cranking Test Procedures................................................................................................... 5-6
Crank Cycle .................................................................................................................. 5-6
Running......................................................................................................................... 5-7
Protective Functions............................................................................................................ 5-7
Overcrank ..................................................................................................................... 5-7
Overspeed .................................................................................................................... 5-7
Low Oil Pressure .......................................................................................................... 5-7
High Coolant Temperature............................................................................................ 5-8
Air Damper.................................................................................................................... 5-8
Emergency Stop ........................................................................................................... 5-8
Low Coolant Level ........................................................................................................ 5-9
General................................................................................................................................ 6-1
Interface ........................................................................................................................ 6-1
Applications................................................................................................................... 6-1
Introduction To Modbus™ Protocol..................................................................................... 6-1
DGC-2000 MODBUS™ Protocol......................................................................................... 6-1
Message Structure........................................................................................................ 6-2
Device Address Field.................................................................................................... 6-2
Function Code Field...................................................................................................... 6-2
Data Block Field............................................................................................................ 6-2
Error Check Field.......................................................................................................... 6-2
Serial Transmission Details................................................................................................. 6-2
Message Framing And Timing Considerations ................................................................... 6-3
Error Handling And Exception Responses .......................................................................... 6-3
Communications Hardware Requirements.......................................................................... 6-3
Detailed Message Query And Response ............................................................................ 6-3
Read Holding Registers Query ..................................................................................... 6-3
Read Holding Registers Response............................................................................... 6-4
Return Query Data........................................................................................................ 6-4
Return Query ................................................................................................................ 6-5
Return Response.......................................................................................................... 6-5
Preset Multiple Register Query ..................................................................................... 6-6
Preset Multiple Register Response .............................................................................. 6-6
Changing The Logon Password .......................................................................................... 6-7
Data Formats....................................................................................................................... 6-7
Double Precision Data Format...................................................................................... 6-7
Triple Precision Data Format ........................................................................................ 6-7
Error Check................................................................................................................... 6-8
iv DGC-2000 INTRODUCTION
Settings Source Register (40081)................................................................................. 6-8
Saving Settings Register (40082) ................................................................................. 6-8
CONTENTS - Continued
SECTION 6 MODBUS™ COMMUNICATIONS - Continued
General................................................................................................................................ 7-1
Installation ........................................................................................................................... 7-1
Operating Requirements............................................................................................... 7-1
®
Installing the Program on Your PC with Windows 95 .................................................. 7-1
®
Installing the Program on Your PC with Windows 3.1 ................................................. 7-1
Configuring the System ................................................................................................ 7-1
Initializing Communications with the DGC 2000 Windows Software................................... 7-1
Changing the Programs Communication Parameters......................................................... 7-3
Changing Logon Passwords ............................................................................................... 7-4
Remote Start and Stop of Generator................................................................................... 7-4
Changing Settings ............................................................................................................... 7-5
Menus.................................................................................................................................. 7-5
File Menu ...................................................................................................................... 7-5
Communications Menu ................................................................................................. 7-5
Screens Menu............................................................................................................... 7-6
Configure Menu ............................................................................................................ 7-6
Help Menu..................................................................................................................... 7-6
Settings Definitions.............................................................................................................. 7-6
Sensing Transformers Settings .................................................................................... 7-7
Pre-Alarm Settings-Low Fuel-Low Cool-Batt. OverVolt. ............................................... 7-8
Pre-Alarm Settings-Maint. Inter.-Eng. kW Overload-Hi Cool ........................................ 7-9
Pre-Alarm Settings-Low Oil-Low Batt. Volt- Weak Batt Volt ....................................... 7-10
Pre-Alarm Settings-Audible-Battery Charger.............................................................. 7-11
Alarm Settings-Hi Cool Temp-Low Oil Press.............................................................. 7-12
Alarm Settings-Overspeed-Sender Failure................................................................. 7-13
Crank Settings ............................................................................................................ 7-14
System Settings .......................................................................................................... 7-15
Metering ...................................................................................................................... 7-16
Top Portion of the Screen........................................................................................... 7-17
Introduction..........................................................................................................................A-1
DGC-2000 Settings Record.................................................................................................A-2
DGC-2000 INTRODUCTION v
SECTION 1 • GENERAL INFORMATION
DESCRIPTION
DGC-2000 Digital Genset Controllers use microprocessor based technology to provide integrated engine-
generator set control, protection, and metering in a single package. Microprocessor based technology
allows for exact measurement, set point adjustment, and timing functions. The DGC-2000 allows for quick
and simple operation from the front panel or through serial link communications. Communications uses
the Modbus protocol or optional custom Basler Electric software. Because of the low sensing burden in
the DGC-2000, neither dedicated potential transformers nor current transformers are required. A wide
temperature range LCD display with backlighting allows the display to be viewed under any ambient light
condition. This combination of features in the DGC-2000 yields significant savings in installation and
setup costs.
FEATURES
DGC-2000 Digital Genset Controllers have the following features.
• Packaged in metal cases for improved electromagnetic compatibility.
• Designed for use in harsh environments.
• Resistant to high moisture, salt fog, humidity, dust, dirt, and chemical contaminants.
• Resistant to the entrance of insects and rodents.
• Suitable for mounting in any top mount enclosure.
• Suitable for controlling isolated generating systems or paralleled generating systems.
• Serial link communications and the optional Basler Electric software package enhances the users
access to set-up parameters. The Basler Electric software package also provides real time
monitoring and control. When combined with a modem and a telephone line, monitoring and
control is possible from any remote location.
FUNCTIONS
DGC 2000 Digital Genset Controllers perform the following functions.
1. Engine cranking control 15. VA metering
2. Generator voltage metering 16. Airbox control
3. Bus voltage metering 17. Engine rpm metering
4. Generator frequency metering 18. Power factor metering
5. Bus frequency metering 19. Watthour metering
6. Generator current metering 20. Engine run time metering
7. Engine coolant temperature metering 21. Battery voltage metering
8. Engine coolant temperature protection 22. Battery condition monitoring
9. Engine oil pressure metering 23. Engine maintenance monitoring
10. Engine oil pressure protection 24. Overload protection
11. Fuel level sensing 25. Serial communication with Modbus
12. Fuel level protection protocol
13. Engine cool down 26. Low coolant level
14. Watt metering
OUTPUTS
There are thirteen isolated form A output contacts. Four are for engine cranking control and the remaining
nine are for the various protection features.
Frequency
Range 4 to 70 hertz
Accuracy ±0.25% of reading or ±0.2 Hz whichever is greater
Output Contacts
Contact Ratings For Engine Cranking Control The MASTER START, AUXILIARY START,
FUEL SOLENOID, and ENGINE RUN relays are
rated for 10 amperes at 24 Vdc, make, break,
and carry
Contact Ratings For Protection Features The PRE-START, ALARM, PRE-ALARM, LOW
OIL PRESSURE, LOW COOLANT TEMP-
ERATURE, HIGH COOLANT TEMPERATURE,
OVERCRANK, OVERSPEED, and AIR
DAMPER relays are rated for 2 amperes at 24
Vdc, make, break, and carry
Calculated Data
Hardware
Communication Port
Interface
Rear RS-232 9600 baud, 8N1 full duplex
Protocols
Rear RS-232 Modbus
Isolation 2000 Vac at 50/60 Hz for one minute between
ground and voltage sensing inputs. 500 Vac at
50/60 Hz for one minute between any of the
following groups
• Voltage Sensing - 70mA
• Battery, Contact Sensing, and Remote
Panel - 42 mA
• Current Transformer - 8mA
• Communications Port - RS-232 - 6 mA
• Contact Outputs - 23 mA
Impulse Qualified to IEC 255-5
Shock 15 g
Basler
Digital
Genset
A B
Controller
C D
DGC-2000
E
Generator Generator Generator Generator
Voltage Amps Phase Frequency
Not In Supplying F
Auto Alarm Load
Select Display
Raise Lower Previous
Enter Toggle
Scroll Scroll
H
Run Off Auto
S R Q P O N M L K J I
D2557-09
04-09-97
A Two line by twenty character LCD provides the primary visual interface for metering,
alarms, prealarms, and protective functions. In the normal mode, labels appear
above and below the display. In the alternate display mode, labels and the displayed
value appear on the display.
B Red LED turns ON when the device is not in the AUTO mode.
C Audible alarm annunciates when the unit is not in AUTO and when alarms and
prealarms occur.
D Red LED turns ON continuously for all alarm conditions and flashes for prealarm
conditions.
E Green LED turns ON when the generator is supplying more than two percent of rated
current.
F Pushbutton used to silence the audible alarm.
G Pushbutton used to exercise all segments of the LCD and to illuminate all LED’s.
H Pushbutton used to place the device in AUTO mode.
I Green LED turns ON when the device is in the AUTO mode.
J Pushbutton used to place the unit in the OFF mode.
K Red LED turns ON when the device is in the OFF mode.
L Pushbutton used to place the device in the RUN mode.
M Green LED turns ON when the device is in the RUN mode.
N Pushbutton used to scroll through the displays available in the normal display mode.
O Pushbutton used to scroll through the display modes.
P Pushbutton used to scroll through previous menu levels.
Q Pushbutton used to enter menu sublevels and select set points.
R Pushbutton used to scroll backward through the menus and to decrement set points.
S Pushbutton used to scroll forward through the menus and to increment set points.
DGC-2000 CONNECTIONS
Compression type terminal strips make wiring the DGC-2000 a simple task. These connections accept
one #10 or two #14 AWG wires. These operations are made even easier by user friendly labeling of the
terminal strips. Once wired, these terminals can be removed as an assembly and facilitate DGC-2000
replacement for out of circuit testing or maintenance. Figure 2-2 shows the DGC-2000 rear panel terminal
connections. Descriptions in Table 2-2 refer to callouts in Figure 2-2.
Table 2-2. DGC-2000 Connections
A Connection points for the speed sensing inputs.
B Connection points for voltage sensing inputs.
C Connection points for current sensing inputs.
D Connection points for relay output contacts.
E Connection point for chassis ground.
F RS-232 serial communication port.
G Connection points for remote displays in accordance with the National Fire Protection
Agency specifications.
H Connection points for operating power.
I Connection points for contact sensing inputs.
J Connection points for sending unit inputs.
E
05-08-98
H
D2557-15
1 A (-)
GROUND
CHASSIS
B (+)
RS 232
2
3 +
DISPLAY
REMOTE
POWER
4 -
LO COOLANT 33
TEMP 34
35
I
ALARM
36
AIR 37 5 -
BATTERY
DAMPER 38 6 +
D
39 7 EMERGENCY
PRE-ALARM
40 8 STOP
HI COOLANT 41 9 AIR
TEMP 42 10 DAMPER
J
43 11 AUTOMATIC
PRE-START
44 12 TRANS SWITCH
CONTACT INPUTS
OVERCRANK
46 14 FAILURE
47 15 - OIL
OVERSPEED
RELAY OUTPUTS
48 16 + PRESSURE
LO OIL 49 17 - FUEL
PRESSURE 50 18 + LEVEL
INPUTS
FUEL 51 19 - COOLANT
SENDING UNIT
SOLENOID 52 20 + TEMP
AUXILIARY 53 21
START 54 22 - MAGNETIC
55 23 + PICK-UP
RUN
56 24
SPEED
SIGNALS
COM 62
PHASE
1A 63 27 PHASE B
C CT
5A 64
BUS
I
CURRENT SENSING
PHASE
1A 69 30 PHASE C
A CT
5A 70
VOLTAGE SENSING
31 PHASE B
GENERATOR
C
32 PHASE A
B
2-3
SECTION 3 • FUNCTIONAL DESCRIPTION
GENERAL
DGC-2000 Digital Genset Controllers use microprocessor based technology to provide integrated engine-
generator set control, protection, and metering in a single package. Microprocessor based technology
allows for exact measurement, set point adjustment, and timing functions. Refer to the following
paragraphs for the DGC-2000 functional description.
Circuit functional description is divided into Inputs, Microprocessor, Outputs, and Software. Circuit
functions illustrated in Figure 3-1 are described in the following paragraphs.
REGULATED
BATTERY
POWER
SUPPLY MASTER START
AUXILLARY START
PRE-START
AC
VOLTAGE AC VOLTAGE SENSING HIGH COOLANT TEMP
AND
CONDITIONING PRE-ALARM
LIQUID
FUEL CONVERTER CRYSTAL
SENSING FUEL LEVEL DISPLAY
SENSING
OIL
SENSING OIL PRESSURE
SENSING
ALT
STATOR ALTERNATOR
SENSING
SWITCH D2557-16
CONTACT SENSING 04-21-97
INPUTS
Emergency Stop
This input is continuously monitored. An open circuit indicates an Emergency Stop. Opening this circuit
removes power from all output relays.
Air Damper
This input is continuously monitored by the microprocessor and is used to indicate the position of the air
damper. An open circuit indicates an open air damper.
WARNING
If the air damper is functional, an auxiliary contact from the Emergency Stop switch must
be used to trip the air damper solenoid.
Charger Failure
This input is continuously monitored by the microprocessor and is used to indicate that ac power is
available to the battery charger. An open circuit indicates a failure of the battery charger.
Coolant temperature
A current of less than two milliamperes is provided to the coolant temperature sending unit. The
developed voltage is measured and scaled for use by the internal circuitry.
Oil Pressure
A current of less than 15 milliamperes is provided to the oil pressure sending unit. The developed voltage
is measured and scaled for use by the internal circuitry.
Fuel level
A current of less than 15 milliamperes is provided to the fuel level sending unit. The developed voltage is
measured and scaled for use by the internal circuitry.
Magnetic Pickup
The voltage from the magnetic pickup is scaled and conditioned for use by the internal circuitry as a speed
signal source.
Alternator Sensing
The voltage from the engine alternator stator is scaled and conditioned for use by the internal circuitry as a
speed signal source.
Voltage Inputs
Monitored generator and bus voltages are sensed and scaled to levels suitable for use by the internal
circuitry. Differential amplifiers provide isolation for these inputs. Internal solid state switches select
line-to-line, line-to-neutral or single-phase values. Menu selections by the user determine these switch
settings.
Current Inputs
Monitored generator currents are sensed and scaled to values suitable for use by the internal circuitry.
Internal current transformers provide isolation. Two taps on the primary of these transformers
accommodate either one or five ampere circuits.
MICROPROCESSOR
Software programmed in the erasable programmable read-only memory (EPROM) controls the overall
functionality of the device and makes all decisions based on programming and system inputs. Formulas
that are used to determine the various calculated quantities and circuits related to microprocessor inputs
are described in the follow paragraphs.
Formulas
Formulas used in calculating the various quantities are provided in the following paragraphs.
kVA: kVA A Phase = (Vab × Ia) divided by (1000 times square-root of three)
kVA B Phase = (Vbc × Ib) divided by (1000 times square-root of three)
kVA C Phase = (Vca × Ic) divided by (1000 times square-root of three)
Total kVA = kVA A Phase + kVA B Phase + kVA C Phase
Related Circuits
Signal Switching
Solid state switches, under microprocessor control, select the voltage or current sensing signal that is
applied to the RMS to dc converter. The resulting signal is sent to the twelve bit analog-to-digital
converter where it is digitized for use by the microprocessor.
RMS To DC Converter
Scaled and conditioned signals representing the voltage and current sensing inputs are used as the input
to the RMS to dc converter. This converter output is a dc level proportional to the RMS value of the input.
OUTPUTS
Each output relay is controlled by the microprocessor and the emergency stop contact input. When the
emergency stop contact input is open, all output contacts open. When the emergency stop contact input
is closed and a signal is given by the microprocessor, the output contacts close. All outputs are
electrically isolated from each other and from the internal circuitry. Four outputs (master start, auxiliary
start, run, and fuel solenoid) are associated with engine cranking functions. The remaining nine outputs
(Figure 3-1) are associated with the various alarms, prealarms, and prestart.
WARNING
If the air damper is functional, an auxiliary contact from the Emergency Stop switch must
be used to trip the air damper solenoid.
NOTE
The run time counter, kilowatt-hour meter and maintenance timers are updated in volatile
memory every minute. The updated value is saved to non-volatile memory only when
auto/off/run mode of operation is changed. This can be changed either from the front
panel or through the communications port. Should the battery power source fail during
operation these values will not be updated and the change in value incurred since the last
change of mode will not be saved. This information is irretrievably lost.
Display Modes
Pressing the Display Toggle pushbutton when in the Normal display mode allows the user to scroll
through the Normal, Alternate, and Menu display modes. Figure 3-2 shows the top level display modes.
Normal Mode
This displays the various engine and generator parameters as described by the front panel overlay.
Pressing the Phase Toggle pushbutton after the engine is running scrolls through the voltage and current
measurements that are available.
Display
Toggle
Normal Mode
Display
Toggle
Alternate Mode
Display
Toggle
Menu Mode
Display
D2557-18 Toggle
04-22-97
Menu 1. Menu 1 is the alarm and prealarm menu. Pressing Select/Enter (Figure 3-4) from this menu
begins the 1.x menu level. Pressing Raise/Scroll and Lower/Scroll from this menu scrolls through the
1.x menu level.
Menu 1.1. Menu 1.1 displays the overspeed alarm. Pressing Select/Enter begins the 1.1.1 level of
menus and displays the function activation level. Pressing Select/Enter displays the setting. This is not
adjustable from the front panel. Pressing previous goes back to the 1.1.1 level.
Pressing Raise/Scroll or Lower/Scroll begins the 1.1.2 function activation delay level of menus.
Pressing Select/Enter displays the activation delay time once the level has been exceeded. This is not
adjustable from the front panel.
Pressing Previous twice goes back to the 1.1 level. Pressing Raise/Scroll goes to the 1.2 menu level
Pressing Lower/Scroll goes to the 1.13 menu level.
Menu 1.2. Menu 1.2 displays high coolant temperature alarm. Pressing Select/Enter begins the 1.2.1
level of menus and displays the function activation level. Pressing Select/Enter displays the setting. This
is not adjustable from the front panel.
Pressing Previous goes back to the 1.2.1 level. Pressing Raise/Scroll or Lower/Scroll begins the 1.2.2
function activation delay level of menus. Pressing Select/Enter displays the activation delay time once
the engine crank disconnect speed is exceeded. This is not adjustable from the front panel.
Pressing Previous twice goes back to the 1.2 level. Pressing Raise/Scroll goes to the 1.3 menu level
Pressing Lower/Scroll goes to the 1.1 menu level.
D/T
Menu Mode
Intro Screen
Enter
Menu 1 Raise
Main Alarms
and Pre-Alarms
Lower
Raise
Menu 2
System
Configuration
Lower
Raise
Menu 3
Sensing Devices
Lower
Raise
Menu 4 Lower
Engine Parameters
and Cranking
D2609-01
04-23-97
Lower Raise
Raise Lower
Menu 1.3
High Coolant Menu 1.11
Temperature Battery Charger
Pre-Alarm Failure Pre-Alarm
Lower Raise
Raise Lower
Menu 1.4
Menu 1.10
Low Coolant
Battery Over-
Temperature
Voltage Pre-Alarm
Pre-Alarm
Lower Raise
Raise Lower
Lower Raise
Raise Lower
Lower Raise
Menu 1.7
Low Fuel
Raise Pre-Alarm Lower
D2609-02
05-07-98
Menu 1.3. Menu 1.3 displays high coolant temperature prealarm. Pressing Select/Enter begins the 1.3.1
level of menus and displays the function activation level. Pressing Select/Enter displays the setting. This
is not adjustable from the front panel.
Pressing Previous goes back to the 1.3.1 level. Pressing Raise/Scroll or Lower/Scroll begins the 1.3.2
function activation delay level of menus. Pressing Select/Enter displays the activation delay time once
the engine crank disconnect speed is exceeded. This is not adjustable from the front panel.
Enter
Enter
Menu 3.1.1
Generator PT's
Raise Menu 3.1 Primary Rating Raise
Transformer Ratios
Lower
Lower
Menu 3.1.3 Raise Menu 3.1.4
Generator CT's Bus PT's
Raise Primary Rating Lower Primary Rating
Menu 3.1.2. Menu 3.1.2 displays the generator potential transformer secondary voltage rating. Pressing
Select/Enter displays the value. This is not adjustable from the front panel. Pressing previous goes to
menu 3.1. Pressing Raise/Scroll goes to menu 3.1.3 Pressing Lower/Scroll goes to menu 3.1.1.
Menu 3.1.3. Menu 3.1.3 displays the generator current transformer primary current rating. Pressing
Select/Enter displays the value. This is not adjustable from the front panel. Pressing previous goes to
menu 3.1. Pressing Raise/Scroll goes to menu 3.1.4. Pressing Lower/Scroll goes to menu 3.1.2.
Menu 3.1.4. Menu 3.1.4 displays the bus potential transformer primary voltage rating. Pressing
Select/Enter displays the value. This is not adjustable from the front panel. Pressing previous goes to
menu 3.1. Pressing Raise/Scroll goes to menu 3.1.5. Pressing Lower/Scroll goes to menu 3.1.3.
Menu 3.1.5. Menu 3.1.5 displays the bus potential transformer secondary voltage rating. Pressing
Select/Enter displays the value. This is not adjustable from the front panel. Pressing previous goes to
menu 3.1. Pressing Raise/Scroll goes to menu 3.1.1. Pressing Lower/Scroll goes to menu 3.1.4.
Pressing Raise/Scroll from menu 3.1 goes to menu 3.2.
NOTE
Using DISPLAY TOGGLE to exit Menu mode will save the user’s place within the menu
system so that the next time Menu mode is entered, the display will return to the same
screen.
As an alternative, pressing Previous allows the user to back out of the menu mode one level at a time so
that the next time menu mode is entered, the display will start at the top of the menu structure.
Previous
Any Menu Mode Level
Display
Toggle
Exit
Menu
Mode
D2609-09
04-23-97
Menu y.y
Setpoint = value
Enter
Edit
Setpoint
Enter
Accept
Setpoint
Menu y.y
New setpoint saved
D2609-10
04-23-97
All Parameters
Specific parameters (settings) are not adjustable at either the front panel or through computer
communications. These settings are identified in the following list as (not adjustable). All other
parameters may be set through computer communications. Only those settings identified in the previous
paragraph are adjustable at the front panel. The following list provides the parameters and the default
setting.
Metric Conversion (ON, OFF) default is OFF
Generator Connection (3-phaseL-L or 3-phaseL-N, 1-phaseA-B) default is 3-phaseL-N
Gen. PT Primary (1 - 15000 V) default is 480 V
Gen. PT Secondary (1 - 480 V) default is 480 V
Gen. CT Primary (1 - 5000 A) default is 500 A
Bus. PT Primary (1 - 15000 V) default is 480 V
Bus. PT Secondary (1 - 480 V) default is 480 V
Cooldown time (0 - 60 minutes) default is 0 minutes
Generator Speed Signal Sources = MPU/Alt/Gen
Overspeed Alarm:
Threshold (105 - 140%) default is 110%
Activation Delay (10 - 500 milliseconds) default is 50 milliseconds
High Coolant Temperature Alarm:
Threshold (100 - 280ºF) default is 275ºF
Arming Delay (not adjustable) is 60 seconds
High Coolant Temperature Prealarm is OFF:
Threshold (100 - 280ºF) default is 250ºF
Arming Delay default is 60 seconds
Low Oil Pressure Alarm:
Threshold (3 - 100 PSI) default is 15 PSI
Arming Delay (5 - 15 seconds) default is 10 seconds
HARDWARE
DGC-2000 Controllers are packaged in aluminum cases for improved electromagnetic compatibility and
are suitable for mounting in any top mount enclosure. The metal case is resistant to moisture, salt fog,
humidity, dust, dirt, and chemical contaminants. It also inhibits insect and rodent entrance. DGC-2000
Controllers are mounted using the permanently attached 10-32 by 5/8 inch (1/2 inch usable) studs.
MOUNTING
Case cutout dimensions are shown in Figure 4-1. Overall dimensions are shown in Figures 4-2 and 4-3.
10.75 (273.0)
0.218 (5.537)
10.25 (260.4) DIA. HOLE (4 PL)
0.25 (6.4)
0.25 (6.4)
D2609-11
04-24-97
11.25
(285.8)
Basler
Digital
Genset R
Controller
- 2000
DGC
Not In Supplying
Auto Alarm Load
D2609-12
06-12-97
(618) 654-2341
R
INPUTS:
Power Input:
12/24 Vdc Nominal @ 12 Watts
Voltage Sensing Input:
100 - 480 Vac Nominal, 50/60 Hz @ < 1 VA/Phase
Current Sensing Input:
1 or 5 Amp 50/60 Hz @ < 1 VA/Phase
Alternator Stator Sensing Input:
12/24 Vdc Nominal System
100 - 900 Hz Nominal
Magnetic Pick Up Input:
2 Vac During Cranking
625 Hz - 10 kHz Nominal 6.6 3
Fuel Level Sending Unit Input:
Resistance 0 - 250 Ohms Nominal
(168.28)
Oil Pressure Sending Unit Input:
Resistance 0 - 250 Ohms Nominal
Coolant Temperature Sending Unit Input:
Resistance 0 - 1000 Ohms Nominal
D2609-13
04-16-99
CONNECTIONS
Incorrect wiring may result in damage to the controller.
WARNING!
If the air damper is functional, an auxiliary contact from the Emergency Stop switch must
be used to trip the air damper solenoid.
CAUTION
Be sure the controller battery input polarity is wired correctly. Reverse polarity battery
power will damage the controller.
NOTE
Be sure the controller is hard-wired to earth ground with no smaller than 12 AWG copper
wire attached to the ground terminal on the rear of the controller case
Except as noted above, connections should be made with minimum wire size of 14 AWG. Be sure to use
the correct input power for the power supply. Figure 4-4 is a typical ac connection diagram for direct
connected single-phase sensing system. Figure 4-5 is a typical ac connection diagram for direct
connected three-phase line to line sensing system. Figure 4-6 is a typical ac connection diagram for direct
connected three-phase line to neutral sensing system.
DGC-2000 INSTALLATION 4-3
4-4
GENERATOR
CIRCUIT
BREAKER
A
A
TO
BUS
B GENERATOR
B 480V
STATOR
ENGINE
ALTERNATOR
N.C. 66
27 28 65 67 31 32
7
EMERGENCY 1A
5 6 STOP COM 5A ALTERNATOR 25
8
PHASE B
PHASE A
PHASE B
9 PHASE A OIL
+ 16
AIR
PRESSURE
DAMPER - 15
10 2
PHASE
BCT
CONTACT
BUS
11 AUTOMATIC SENSING FUEL + 18
TRANSFER SENDING LEVEL
12 SWITCH UNITS - 17 3
13 BATTERY + 20
COOLANT
CHARGER
TEMP 4
14 FAIL DGC-2000 - 19
OUTPUT
RELAYS
LOW COOLANT
26 LEVEL
- 22
5
MPU
GND + 23
MAGNETIC
7 10A PICK-UP
LOW
COOLANT
TEMP
ALARM
AIR
DAMPER
PRE-ALARM
HIGH
COOLANT
TEMP
PRE-START
OVERCRANK
OVERSPEED
LOW OIL
PRESSURE
FUEL
SOLENOID
AUXILIARY
START
RUN
MASTER
START
+ 6
BATTERY 24 VDC
- 5
+
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58
DGC-2000 INSTALLATION
GENERATOR
CIRCUIT
BREAKER
A
A
TO B GENERATOR
BUS B 480V
C
C
N
DGC-2000 INSTALLATION
STATOR
1 1 1
63 66 69
N.C. 27 28 62 64 65 67 68 70 30 31 32 ENGINE
7 1A 1A 1A ALTERNATOR
EMERGENCY COM 5A
COM 5A
COM 5A
5 6
STOP
8 ALTERNATOR 25
PHASE B
PHASE A
PHASE C
PHASE B
PHASE A
9 + 16
AIR OIL
DAMPER PRESSURE
PHASE
CCT
PHASE
BCT
PHASE
ACT
10 - 15 2
BUS
CONTACT
11 AUTOMATIC SENSING + 18
TRANSFER SENDING FUEL
12 SWITCH UNITS LEVEL
- 17 3
13 BATTERY + 20
CHARGER COOLANT
14 FAIL TEMP 4
DGC-2000 - 19
OUTPUT
RELAYS
LOW COOLANT
26 LEVEL
5 - 22
GND MPU
+ 23
MAGNETIC
7 10A PICK-UP
LOW
COOLANT
TEMP
ALARM
AIR
DAMPER
PRE-ALARM
HIGH
COOLANT
TEMP
PRE-START
OVERCRANK
OVERSPEED
LOW OIL
PRESSURE
FUEL
SOLENOID
AUXILIARY
START
RUN
MASTER
START
+ 6
BATTERY 24 VDC
- 5
+
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58
4-5
4-6
GENERATOR
CIRCUIT
BREAKER
A
A
TO B GENERATOR
BUS B 480V
C
C
N
STATOR
1 1 1
N.C. 63 66 69 ENGINE
7 27 28 62 64 65 67 68 70 29 30 31 32
EMERGENCY ALTERNATOR
5 6 1A 1A 1A
STOP COM COM COM
8 5A 5A 5A
ALTERNATOR 25
PHASE B
PHASE A
NEUTRAL
PHASE C
PHASE B
9 PHASE A OIL + 16
AIR
DAMPER PRESSURE
10
- 15 2
PHASE
CCT
PHASE
BCT
PHASE
ACT
CONTACT
BUS
11 AUTOMATIC SENSING SENDING FUEL + 18
TRANSFER
UNITS LEVEL
12 SWITCH
- 17 3
13 BATTERY
CHARGER C O O L A N T + 20
FAIL TEMP
14 4
DGC-2000 - 19
OUTPUT
RELAYS
LOW COOLANT
26 LEVEL
5 - 22
GND MPU
+ 23
MAGNETIC
7 10A PICK-UP
ALARM
AIR
DAMPER
PRE-ALARM
HIGH
COOLANT
TEMP
PRE-START
OVERCRANK
OVERSPEED
LOW OIL
PRESSURE
FUEL
SOLENOID
AUXILIARY
START
RUN
MASTER
START
LOW
COOLANT
TEMP
+ 6
BATTERY 24 VDC
- 5
+
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58
DGC-2000 INSTALLATION
COMMUNICATION CONNECTORS AND SETTINGS
RS-232 Connector
The RS-232 connector is a DB-9 female connector. Connector pin numbers, functions, names, and signal
directions are shown in Table 4-1. Figure 4-7 provides the RS-232 cable connection diagram.
Communication Settings
Communication settings are the formal set of conventions controlling the format and relative timing of
message exchange between two communications terminals. Default settings baud rate = 9600, parity =
None, and stop bits = 1.
EQUIPMENT REQUIRED
• DC Power Supply, 24 Volts
• 10 Amp Fuse
• Voltage Source, 60 hertz, 0 to 120V
• Current Source, 60 hertz, 0 to 5A
• Signal Generator, Sine Wave, 0 to 5k hertz, 0 to 5V
• Digital Voltmeter, 4 1/2 Digits (Fluke 8050A or Equivalent)
• Continuity Tester
• Four Single-Pole Switches
• 2 each, 250 ohm variable resistors
• 1 each 2500 ohm variable resistor
NOTE
Displayed voltage is equal to the generator potential transformer primary voltage setting
times the applied voltage divided by the generator potential transformer secondary
voltage setting.
Step 1. Verify that the battery input (terminals 5 and 6) voltage is 24.0 Vdc.
Step 2. Verify that the DGC-2000 displayed value is 24.0 ±0.5 Vdc.
Step 3. Apply 120.0 Vac, 60.0 hertz to phase A (line to neutral) generator voltage input (terminals 32 and
29).
Step 4. Verify that the DGC-2000 generator frequency displayed value is 60.0 ±0.2 hertz.
Step 5. Verify that the DGC-2000 phase A to neutral voltage displayed value is 120.0 ±2.0 Vac.
Step 6. Remove the voltage.
Step 7. Apply 120.0 Vac, 60.0 hertz to phases A and B generator voltage input (terminals 32 and 31).
Step 8. Verify that the DGC-2000 generator A to B voltage displayed value is 120.0 ±2.0 Vac.
Step 9. Remove the voltage.
Step 10. Apply 120.0 Vac, 60.0 hertz (line to neutral) to phase B generator voltage input (terminals 31 and
29).
Step 11. Verify that the DGC-2000 line to neutral voltage displayed value is 120.0 ±2.0 Vac.
Step 12. Remove the voltage.
Step 13. Apply 120.0 Vac, 60.0 hertz to phases B and C generator voltage input (terminals 31 and 30).
Step 14. Verify that the DGC-2000 generator B to C voltage displayed value is 120.0 ±2.0 Vac.
Step 15. Remove the voltage.
Step 16. Apply 120.0 Vac, 60.0 hertz (line to neutral) to phase C generator voltage input (terminals 30 and
29).
Step 17. Verify that the DGC-2000 line to neutral voltage displayed value is 120.0 ±2.0 Vac.
Step 18. Remove the voltage.
Step 19. Apply 120.0 Vac, 60.0 hertz to phases C and A generator voltage input (terminals 30 and 32).
Step 20. Verify that the DGC-2000 generator C to A voltage displayed value is 120.0 ±2.0 Vac.
Step 21. Remove the voltage.
PHASE B
PHASE A
NEUTRAL
PHASE C
PHASE B
PHASE A
9 PHASE C CT PHASE B CT PHASE A CT
OPEN AIR + 16
DAMPER OIL PRESSURE 250 OHMS (SET TO 60 OHMS)
10
BUS VOLTAGE GEN VOLTAGE - 15
11 AUTOMATIC CONTACT
OPEN TRANSFER SENSING + 18
SWITCH FUEL LEVEL 250 OHMS (SET TO 100 OHMS)
12
SENDING - 17
13 BATTERY UNITS
OPEN CHARGER + 20
2500 OHMS
FAIL COOLANT TEMP (SET TO 100 OHMS)
14
DGC-2000 - 19
LOW COOLANT OUTPUT RELAYS
26 SIGNAL GENERATOR
LEVEL
OPEN
0-5 kHZ, 0-5 VAC
5 - 22
GND MPU
+ 23
24 VDC
+
10A
ALARM
AIR
DAMPER
PRE-ALARM
HIGH
COOLANT
TEMP
PRE-START
OVERCRANK
OVERSPEED
LOW OIL
PRESSURE
FUEL
SOLENOID
AUXILIARY
START
RUN
MASTER
START
DGC-2000 TESTING
Metering Bus Voltages
NOTE
Displayed voltage is equal to the bus potential transformer primary voltage setting times
the applied voltage divided by the bus potential transformer secondary voltage setting.
Step 1. Apply 120.0 Vac, 60.0 hertz to phases A and B bus voltage input (terminals 28 and 27).
Step 2. Verify that the DGC-2000 bus A and B frequency displayed value is 60.0 ±0.2 hertz.
Step 3. Verify that the DGC-2000 bus A and B voltage displayed value is 120.0 ±2.0 Vac.
Step 4. Remove the voltage.
NOTE
Displayed current is equal to the generator current transformer primary current setting
times the applied current divided by one or five (the nominal current value).
Step 1. Apply 1.000 Aac to the DGC-2000 generator five ampere phase A CT input (terminals 70 and
68).
Step 2. Verify that the DGC-2000 phase A current displayed value is 100.0 ±2.0 amperes.
Step 3. Remove the current.
Step 4. Apply 1.000 Aac to the DGC-2000 generator five ampere phase B CT input (terminals 67 and
65).
Step 5. Verify that the DGC-2000 phase B current displayed value is 100.0 ±2.0 amperes.
Step 6. Remove the current.
Step 7. Apply 1.000 Aac to the DGC-2000 generator five ampere phase C CT input (terminals 64 and
62).
Step 8. Verify that the DGC-2000 phase C current displayed value is 100.0 ±2.0 amperes.
Step 9. Remove the current.
Oil Pressure
Step 1. Apply 60 ohms across the Oil Pressure sender input (terminals 16 and 5).
Step 2. Verify that the DGC-2000 displayed value is 80 ±2.0 PSI.
Coolant Temperature
Step 1. Apply 100 ohms across the Coolant Temperature sender input (terminals 20 and 5).
Step 2. Verify that the DGC-2000 displayed value is 205 ±4.0° C.
NOTE
RPM as derived from the MPU is equal to [MPU output frequency (hertz) times 60]
divided by the number of flywheel teeth.
RPM as derived from the alternator is equal to [alternator output frequency (hertz) times
rated RPM] divided by the rated alternator frequency (hertz).
RPM as derived from the generator is equal to [generator output voltage frequency
(phase A to neutral in hertz)] divided by the rated generator frequency (hertz).
NOTE
The DGC-2000 uses phase A voltage and phase B current for Power Factor calculations.
Therefore, if this test is performed with the current lagging the voltage by 120 degrees.,
the displayed Power Factor will be approximately 1.00.
Step 1. Apply 120 Vac to phase A to neutral generator voltage inputs (terminals 32 and 29).
Step 2. Apply 1.0 Aac to phase B current transformer inputs (terminals 67 and 65) in phase with the
phase A to neutral voltage.
Step 3. Verify that the DGC-2000 displayed value is -0.50 ±0.02.
Step 4. Remove voltage and current.
NOTE
The displayed kW is equal to the kVA times the Power Factor.
Step 1. Apply in parallel 120 Vac to phase A to neutral (terminals 32 and 29), phase B to neutral
(terminals 31 and 29), and phase C to neutral (terminals 30 and 29).
Step 2. Apply in series and in phase with the voltage 1 Aac to Phase A current transformer input
(terminals 69 and 68), Phase B current transformer input (terminals 66 and 65), and Phase C
current transformer input (terminals 63 and 62).
Step 3. Verify that the DGC-2000 displayed value for individual phase kW is -30 ±2 kW.
Step 4. Verify that the DGC-2000 displayed value for total kW is -90 ±2 kW.
Step 5. Verify that the DGC-2000 displayed value for individual phase kVA is 60 ±2 kVA.
Step 6. Verify that the DGC-2000 displayed value for total kVA is within 180 ±5 kVA.
Step 7. Remove voltage and current.
Crank Cycle
NOTE
The DGC will go into Overcrank if the Off switch is not pressed before two crank cycles
expire. Pressing Off will reset this condition if it occurs.
Step 1. Verify that all output contacts are open.
Step 2. Press the Run switch on the front panel.
Step 3. Verify that the DGC-2000 displays CRANKING STATUS.
Step 4. Verify that only the Master Start, Auxiliary Start, Fuel Solenoid, and Pre-Start output contacts are
closed during CRANKING CYCLE.
Step 5. Verify that only the Pre-Start contact remains closed during RESTING.
Step 6. Press the Off switch on the front panel.
Step 7. Press the Auto switch on the front panel.
Step 8. Apply a contact closure across the Automatic Transfer Switch inputs (terminals 11 and 12).
Step 9. Verify that the DGC-2000 displays CRANKING STATUS.
Step 10. Verify that only the Master Start, Auxiliary Start, Fuel Solenoid, and Pre-Start output contacts are
closed during CRANKING CYCLE.
5-6 DGC-2000 TESTING
Step 11. Verify that only the Pre-Start contact remains closed during RESTING.
Step 12. Press the Off switch on the front panel.
Step 13. Open the contact across the Automatic Transfer Switch inputs.
Running
Step 1. Press the Run switch on the front panel.
Step 2. Within 5 seconds of beginning cranking, apply in parallel 120 Vac to phase A to neutral (terminals
32 and 29), phase B to neutral (terminals 31 and 29), and phase C to neutral (terminals 30 and
29).
Step 3. Verify that only the Run and Fuel Solenoid output contacts are closed.
Step 4. Verify that the DGC-2000 normal mode display now meters the active generator values listed on
the front panel instead of displaying READY.
Step 5. Press the Off switch on the front panel.
Step 6. Remove the voltage.
Step 7. Press the Auto switch on the front panel.
Step 8. Apply a contact closure across the Automatic Transfer Switch inputs (terminals 11 and 12).
Step 9. Within 5 seconds of beginning cranking, apply in parallel 120 Vac to phase A to neutral (terminals
32 and 29), phase B to neutral (terminals 31 and 29), and phase C to neutral (terminals 30 and
29).
Step 10. Verify that only the Run and Fuel Solenoid output contacts are closed.
Step 11. Verify that the DGC-2000 normal mode display now meters the active generator values listed on
the front panel instead of displaying READY.
Step 12. Press the Off switch on the front panel.
Step 13. Remove the voltage.
Step 14. Open the contact across the Automatic Transfer Switch inputs.
PROTECTIVE FUNCTIONS
Overcrank
Step 1. Press the Run switch on the front panel.
Step 2. Verify that after two cycles the DGC-2000 display indicates GEN OVER-CRANK ALARM and
that only the Alarm, Air Damper, and Overcrank output contacts are closed.
Step 3. Press the Off switch on the front panel and verify that the DGC-2000 resets to the Ready mode
and that all output contacts open.
Overspeed
Step 1. Apply in parallel 120 Vac to phase A to neutral (terminals 32 and 29), phase B to neutral
(terminals 31 and 29), and phase C to neutral (terminals 30 and 29).
Step 2. Apply a 5 Vac, 4000 hertz sine wave to the DGC-2000 MPU inputs (terminals 23 and 22).
Step 3. Press the Run switch on the front panel.
Step 4. Slowly increase the frequency to the DGC-2000 MPU input until an overspeed shutdown occurs.
Step 5. Verify shutdown occurs within 4158 ±83 hertz (1980 ±38 RPM).
Step 6. Verify that the DGC-2000 display indicates GEN OVERSPEED ALARM and that only the Alarm,
Air Damper, and Overspeed output contacts are closed.
Step 7. Remove the voltages.
Step 8. Press the Off switch on the front panel and verify that the DGC-2000 resets to the Ready mode
and that all output contacts open.
Air Damper
Step 1. Apply in parallel 120 Vac to phase A to neutral (terminals 32 and 29), phase B to neutral
(terminals 31 and 29), and phase C to neutral (terminals 30 and 29).
Step 2. Press the Run switch on the front panel.
Step 3. Apply a contact closure across the Air Damper Inputs (terminals 9 and 10).
Step 4. Verify that the DGC-2000 indicates AIR DAMPER SHUTDOWN (CLOSED) and that only the
Alarm and Air Damper output contacts are closed.
Step 5. Open the contact across the Air Damper inputs.
Step 6. Press the Off switch on the front panel and verify that the DGC-2000 resets to the Ready mode
and that all output contacts open.
Step 7. Remove the voltage.
Emergency Stop
Step 1. Apply in parallel 120 Vac to phase A to neutral (terminals 32 and 29), phase B to neutral
(terminals 31 and 29), and phase C to neutral (terminals 30 and 29).
Interface
The rear panel interface uses a standard RS-232 (DB-9) connector. The communications protocol is
compatible with readily available modem/terminal software. The RS-232 communication port supports full
duplex operation.
For all communication ports :
• The communications baud rate is fixed at 9600.
• The number of data bits is fixed at 8.
• The parity is fixed at NONE (N).
• The number of stop bits is fixed at 1.
Applications
Rear panel communication port may be used to interface terminals, computers, serial printers, modems,
and intermediate communication/control interfaces such as RS-232 serial multiplexors. DGC-2000
communications protocol supports only the RTU mode.
Once a valid query is received, the DGC-2000 waits a minimum amount of time before responding. This
time delay is set in the remote delay time register (40052). This register contains a value from 1 - 20
representing 10 - 200 milliseconds. The default value is 1 (10 milliseconds). The user may set the remote
delay time register to 0 to minimize response latency.
Table 6-1 provides the response message transmission time (in seconds) and 3.5 character times (in
milliseconds) for various message lengths and baud rate.
Device Address
Function Code 03 (hex)
Byte Count
Data Hi (For each requested register, there is one Data Hi and one Data Lo.)
Data Lo
Data Hi
Data Lo
CRC error check
One-Half Of Slave Response Frame Sent Back to Master (Continuation Of First One-Half)
Data Output Data Output Data Output Checksum Checksum
Registers Lo 40113 Registers Hi 40114 Registers Lo 40114 Hi Lo
55h 21h 45h nn nn
Device Address
Function Code 08 (hex)
Subfunction Hi 00 (hex)
Subfunction Lo 00 (hex)
Data Hi
Data Lo
CRC error check
Return Response
The response message echoes the starting address and the number of registers. There is no response
message when the query is broadcast.
Device Address
Function Code 10 (hex)
Starting Address Hi
Starting Address Lo
No. of Registers Hi
No. of Registers Lo
CRC Error Check
DATA FORMATS
Some DGC-2000 data must be reformatted for transmission over the Modbus network. Parameters
whose values can exceed 9999 but not exceed 99,999,999 are represented in double precision format.
Parameters whose values can exceed 99,999,999 must be formatted in triple precision. Single byte data
resides in the register least-significant byte with the most-significant byte set to zero. Negative values
(single and double precision only) are represented by a sign bit (register MSB) and magnitude.
Error Check
This field contains a two-byte CRC value for transmission error detection. The master first calculates the
CRC and appends it to the query message. The DGC-2000 recalculates the CRC value for the received
query and performs a comparison to the query CRC value to determine if a transmission error has
occurred. If so, no response message is generated. If no transmission error has occurred, the slave
calculates a new CRC value for the response message and appends it to the message for transmission.
The CRC calculation is performed using all bytes of the device address, function code and data block
fields. A 16-bit CRC-register is initialized to all 1's. Then each eight-bit byte of the message is used in the
following algorithm:
First, exclusive-OR the message byte with the low-order byte of the CRC-register. The result, stored in
the CRC-register, will then be right-shifted eight times. The CRC-register MSB is zero-filled with each
shift. After each shift, the CRC-register LSB is examined. If the LSB IS a 1, the CRC-register is then
exclusive-ORed with the fixed polynomial value A001 (hex) prior to the next shift. Once all bytes of the
message have undergone the above algorithm, the CRC-register will contain the message CRC value to
be placed in the error check field.
Conventions
The Data Format column uses the following abbreviations.
DP Double precision
TP Triple Precision
Data formatted in double precision uses a two register group designated (a) and (b) and is defined as
follows:
NOTE
Query address n will access the holding register n+1.
COMMUNICATION PARAMETERS
40051 Comm Baud Rate 0 R W 0 =9600 Baud
40052 Remote Delay Time 0-20 R W 0=Min. MilliSec 10
1 =10
2 = 20
etc.
20 =200
40053 Comm Parity 0-2 R W 0 =None
1 =Odd
2 =Even
40054 Device Address 1-247 R W
40055 Modern Time Delay 0-9999 R W Microseconds
40056 Embedded Code Version No. 100-9999 R - Version No. x 100
PARAMETER SETTINGS
40078 Remote (PC) Emergency 0-1 - W 0 =Off
Stop 1 = Stop
40079 Remote Start / Stop 0-1 - W 0 =Stop
1 =Start
40080 <Reserved>
40081 Settings Source 0-2 R W 0 =Factory
1 =OEM
2 =User
40082 Save Settings Data=Don’t Care -W
40083 <Reserved>
SYSTEM PARAMETERS
40091 Generator Connection 0-2 R W 0=3ph L-L
1=3ph L-N
2=1ph A-B
40092 NFPA Level 0-2 R W 0 =Off
1 =Level 1
2 =Level 2
40093 Unit System 0-1 R W 0=English
1=Metric
40094 Battery Volts 0-1 R W 0=12 VDC
1=24 VDC
40095 Generator Frequency 0-1 R W 0=50 HZ
1=60 HZ
40096 Rated Engine RPM 750-3600 R W RPM
40097 Rated Engine RPM Minimum 750 R - RPM
40098 Rated Engine RPM 3600 R - RPM
Maximum
40099 Rated Engine RPM Stepsize 50 R - RPM
40100 Number Flywheel Teeth 50-500 R W
40101 Number Flywheel Teeth 50 R -
Minimum
40102 Number Flywheel Teeth 500 R -
Maximum
40103 Number Flywheel Teeth 1 R -
Stepsize
40104 Genset KW Rating 25-9999 R W KWatt
40105 Genset KW Rating Minimum 25 R - KWatt
40106 Genset KW Rating Maximum 9999 R - KWatt
40107 Genset KW Rating Stepsize 1 R - KWatt
40108 No Load Cool Down Time 0-60 R W Minutes
40109 No Load Cool Down Time 0 R - Minutes
Minimum
40110 No Load Cool Down Time 60 R - Minutes
Maximum
40111 No Load Cool Down Time 5 R - Minutes
Stepsize
40112 Alternator Frequency Rated 100-900 R W Hertz
40113 Alternator Frequency Rated 100 R - Hertz
Minimum
40114 Alternator Frequency Rated 900 R - Hertz
Maximum
6-10 DGC-2000 MODBUS™ COMMUNICATIONS
Holding Variable’s Read/Write Data
Register Parameter Allowed Range Supported Format Units
GENERATOR PT PRIMARY
40121 Voltage(a) 1-15000 R W DP VoltsAC x 10000
40122 Voltage(b) R W DP VoltsAC
40123 Voltage Minimum(a) 1 R - DP VoltsAC x 10000
40124 Voltage Minimum(b) R - DP VoltsAC
40125 Voltage Maximum(a) 15000 R - DP VoltsAC x 10000
40126 Voltage Maximum(b) R - DP VoltsAC
40127 Voltage Stepsize(a) 1 R - DP VoltsAC x 10000
40128 Voltage Stepsize(b) R - DP VoltsAC
GENERATOR PT SECONDARY
40129 Voltage 1-480 R W VoltsAC
40130 Voltage Minimum 1 R - VoltsAC
40131 Voltage Maximum 480 R - VoltsAC
40132 Voltage Stepsize 1 R - VoltsAC
GENERATOR CT PRIMARY
40133 Current 1-5000 R W AmpsAC
40134 Current Minimum 1 R - AmpsAC
40135 Current Maximum 5000 R - AmpsAC
40136 Current Stepsize 1 R - AmpsAC
BUS PT PRIMARY
40141 Voltage(a) 1-15000 R W DP VoltsAC x 10000
40142 Voltage(b) R W DP VoltsAC
40143 Voltage Minimum(a) 1 R - DP VoltsAC x 10000
40144 Voltage Minimum(b) R - DP VoltsAC
40145 Voltage Maximum(a) 15000 R - DP VoltsAC x 10000
40146 Voltage Maximum(b) R - DP VoltsAC
40147 Voltage Stepsize(a) 1 R - DP VoltsAC x 10000
40148 Voltage Stepsize(b) R - DP VoltsAC
BUS PT SECONDARY
40149 Voltage 1-480 R W VoltsAC
40150 Voltage Minimum 1 R - VoltsAC
40151 Voltage Maximum 480 R - VoltsAC
40152 Voltage Stepsize 1 R - VoltsAC
OVERSPEED ALARM
40301 Enable 0-1 R W 0 =Off
1 =On
40302 Shutdown Enable 0-1 R W 0 =Off
1 =On
40303 Threshold 105-140 R W % of Rated
40304 Minimum 105 R - % of Rated
40305 Maximum 140 R - % of Rated
40306 Stepsize 1 R - % of Rated
40307 Alarm Activation Time Delay 0-500 R W MilliSec
40308 Activation Time Delay 0 R - MilliSec
Minimum
40309 Activation Time Delay 500 R - MilliSec
Maximum
40310 Activation Time Delay 10 R - MilliSec
Stepsize
CRANKING PARAMETERS
40351 Cranking Style 0-1 R W 0=Contin.
1=Cycle
40352 Number of Crank Cycles 1-7 R W
40353 Number of Crank Cycles 1 R -
Minimum
40354 Number of Crank Cycles 7 R -
Maximum
40355 Number of Crank Cycles 1 R -
Stepsize
40356 Cycle Crank Time 5-15 R W Seconds
40357 Cycle Crank Time Minimum 5 R - Seconds
40358 Cycle Crank Time Maximum 15 R - Seconds
40359 Cycle Crank Time Stepsize 1 R - Seconds
40360 Continuous Crank Time 1-60 R W Seconds
40361 Continuous Crank Time 1 R - Seconds
Minimum
40362 Continuous Crank Time 60 R - Seconds
Maximum
40363 Continuous Crank Time 1 R - Seconds
Stepsize
40364 Crank Disconnect Limit 10-100 R W % of Rated
40365 Crank Disconnect Limit 10 R - % of Rated
Minimum
40366 Crank Disconnect Limit 100 R - % of Rated
Maximum
40367 Crank Disconnect Limit 1 R - % of Rated
Stepsize
40368 Pre-crank Delay 0-30 R W Seconds
40369 Pre-crank Delay Minimum 0 R - Seconds
40370 Pre-crank Delay Maximum 30 R - Seconds
40371 Pre-crank Delay Stepsize 1 R - Seconds
40372 Pre-crank Contact after 0-1 R W 0=Open
Disconnect 1=Closed
SYSTEM MONITOR
40374 Remaining Cooldown Time 0-60 R - Minutes
40375 <Reserved>
40376 Active Speed Signal Sources 1-4 R - 1 =MPU
2 =ALT
3 =GEN
4 =NONE
40377 Sender Failure Alarm Codes R - b0=Cool Temp
b1=Oil Press
b2 Reserved
b3=Spd Signal
b4=Gen Volt
b5-b7 Not
Used
DGC-2000 MODBUS™ COMMUNICATIONS 6-15
Holding Variable’s Read/Write Data
Register Parameter Allowed Range Supported Format Units
GENERATOR MONITOR
40394 Phase a-b RMS Voltage(a) R - DP RMS Volt x10000
40395 Phase a-b RMS Voltage(b) R - DP RMS Volt
40396 Phase b-c RMS Voltage(a) R - DP RMS Volt x10000
Gen. Phase
Rotation
b4=0 for A-B-C
b4=1 for A-C-B
Maintenance
Timer
b5=0 is active
b5=1 to reset
GENERATOR PT PRIMARY
40452 Voltage(a) 1-15000 R W DP VoltsAC x 10000
40453 Voltage(b) R W DP VoltsAC
GENERATOR PT SECONDARY
40454 Voltage 1-480 R W VoltsAC
GENERATOR CT PRIMARY
40455 Current 1-5000 R W AmpsAC
40456 <Reserved>
BUS PT PRIMARY
40457 Voltage(a) 1-15000 R W DP VoltsAC x 10000
40458 Voltage(b) R W DP VoltsAC
BUS PT SECONDARY
40459 Voltage 1-480 R W VoltsAC
LOW FUEL PRE-ALARM
40460 Enable 0-1 R W 0 =Off
1 =On
40461 Threshold 10-100 R W % Full Tank
OVERSPEED ALARM
40488 Enable 0-1 R W 0 =Off
1 =On
40489 Shutdown Enable 0-1 R W 0 =Off
1 =On
40490 Threshold 105-140 R W % of Rated
40491 Alarm Activation Time Delay 0-500 R W MilliSec
CRANKING PARAMETERS
40500 Cranking Style 0-1 R W 0=Contin.
1=Cycle
40501 Number of Crank Cycles 1-7 R W
40502 Cycle Crank Time 5-15 R W Seconds
40503 Continuous Crank Time 1-60 R W Seconds
40504 Crank Disconnect Limit 10-100 R W % of Rated
40505 Pre-crank Delay 0-30 R W Seconds
40506 Pre-crank Contact after 0-1 R W 0=Open
Disconnect 1=Closed
SYSTEM MONITOR
40507 Accumulated Engine R W DP Minutes x 10000
Runtime Warranty(a)
40508 Accumulated Engine R W DP Minutes
Runtime Warranty(b)
CALIBRATION
40509 Voltage Calibration A(a) R W DP x 10000
40510 Voltage Calibration A(b) R W DP x1
40511 Voltage Calibration B(a) R W DP x 10000
40512 Voltage Calibration B(b) R W DP x1
40513 Voltage Calibration C(a) R W DP x 10000
40514 Voltage Calibration C(b) R W DP x1
40515 Voltage Calibration N(a) R W DP x 10000
40516 Voltage Calibration N(b) R W DP x1
40517 Current Calibration A(a) R W DP x 10000
40518 Current Calibration A(b) R W DP x1
CALIBRATION - Continuation
40583 Phase angle (a) R W DP
40584 Phase angle (b) R W DP
GENERAL
®
DGC-2000 Windows Software is an application that enhances communication between the personal
®
computer (PC) user and the DGC-2000. DGC-2000 Windows Software serves two main purposes. First,
it provides a user friendly environment for changing DGC-2000 settings. Second, it provides on-screen,
real time metering that is updated approximately every one and one-half seconds. The interface software
also allows users to save the current setting configurations and data information to a disk. Users can
save multiple setups for later use which saves setup time when configuring multiple units. Without DGC-
®
2000 Windows Software, users must be familiar with the limited function operations at the DGC-2000
front panel.
INSTALLATION
DGC 2000 Windows software contains a setup utility that installs the program on your PC. When it installs
the program, an uninstall icon is created that you may use to uninstall (remove) the program from your
PC. The minimum operating requirements are listed in the following paragraph.
Operating Requirements
To use DGC 2000 Windows software, you will need the following:
• IBM compatible PC, 486DX2 or faster, and a minimum of four megabytes of RAM
• Microsoft Windows 95 or Windows 3.1
• 3.5 inch floppy drive
• RS-232 Serial port
®
Installing The Program On Your PC With Windows 95
1. Insert disk 1 in the 3.5 inch floppy drive
2. From the Task Bar select Start then Run
3. Enter a:\Setup.exe and press enter or click on Browse and select the A: drive and double click
Setup.exe.
®
Installing The Program On Your PC With Windows 3.1
1. Insert disk 1 in the 3.5 inch floppy drive
2. From Program Manager select File menu and then Run
3. Enter a:\Setup.exe and press enter or select the A: drive and double click Setup.exe.
Configuring The System
Communication with a DGC 2000 unit can be done by a direct cable connection or through a modem. The
installation section of the manual has the RS-232 serial link connection pinouts. For direct connection use
a standard RS-232 cable. For modem communications connection use a modem to the DGC RS-232 port
and a null-modem cable. Connect another modem to the host computer with a standard RS-232 cable.
CHANGING SETTINGS
Settings are arranged in five groups.
• Sensing Transformers
• Pre-Alarms
• Alarm
• Crank
• System
To change settings, you must first select the screen associated with the setting. When you are logged on
with the limited access password you can see all of the current settings in the unit but cannot change all of
them. The settings that can not be changed will be disabled so that you can not select them. Double
clicking on any white rectangular box will allow you to change (if allowed) that setting. Once all of the
settings have been entered, pull down the Communications menu and select Send to DGC, this will
send the settings to the DGC and verify them.
MENUS
File Menu
1) Open - Opens a saved settings file from a disk.
2) Save - Saves the current settings to a file on a disk. The file will be saved with the extension .dgc.
3) Print - Used to print a hard copy of the settings file.
4) Exit - Used to exit the program.
Communications Menu
1) Open - Used to initiate communications with the DGC2000.
2) Close - Used to terminate communications with the DGC2000.
Screens Menu
1) Sensing Transformers - Used to program the sensing transformer ratings.
2) Pre-Alarms - Used to program pre-alarm settings.
3) Alarm - Used to program alarm settings.
4) Crank - Used to program engine cranking settings.
5) System - Used to program system parameters.
6) Meter - Used to display measured quantities. Metering must be enabled to view the measured
quantities.
Configure Menu
1) RS232 - Used to program communication settings.
2) Sensor Curve - Future addition.
Help Menu
1) About - Displays current software version number.
SETTINGS DEFINITIONS
Definitions for all of the available settings are provided in the following paragraphs.
Figure 7-10. Pre-Alarm Settings - Low Fuel - Low Cool - Batt. OverVolt. Screen
Figure 7-11. Pre-Alarm Settings - Maint. Inter. - Eng. kW Overload - Hi Cool Screen
Figure 7-12. Pre-Alarm Settings - Low Oil - Low Batt Volt - Weak Batt Volt Screen
Audible Alarm
1) Enable - Used to enable or disable the external contact to indicate the battery charger has failed.
Figure 7-14. Alarm Settings - Hi Cool Temp - Low Oil Press Screen
Overspeed Alarm
INTRODUCTION
This appendix provides a complete listing of all DGC-2000 settings. This listing is in the form of a settings
record that you may use to record information relative to your system. These settings sheets may be
removed and photo copied.
Genset ID Date
DGC-2000 Serial Number Software Version Number
WEAK BATTERY
PRE-ALARM
THRESHOLD
ACTIVATION DELAY
LOW BATTERY
PRE-ALARM
THRESHOLD
ACTIVATION DELAY
BATTERY OVERVOLTAGE
PRE-ALARM
THRESHOLD
BATTERY CHARGER
FAILURE PRE-ALARM
GLOBAL SENDER
FAILURE ALARM
ARMING DELAY
GLOBAL PRE-ALARM
BUZZER
MAINTENANCE INTERVAL
PRE-ALARM
THRESHOLD
ENGINE KILOWATT
OVERLOAD PRE-ALARM
THRESHOLD
CRANKING STYLE
CRANK CYCLES
PRE-CRANK DELAY