NR Electric Automation Catalog
NR Electric Automation Catalog
NR Electric Automation Catalog
PCS-9700
Automation System
The PCS-9700 is a state-of-the-art automation solution for The IEC-61850 standard provides an internationally recognized
substations, power generators and a variety of industries. The method targeted at increasing the interoperability between
PCS-9700 is equipped with diverce advanced technologies and IEDs from different venders. The IEC-61850 standard has
patents. It can be incorporated into a variety of substations, from built-in capabilities for high-speed control and data sharing
distribution level to the extra high voltage level. It integrates over the network, eliminating most dedicated control wiring.
the applications of protection, control, Ethernet, IT and Interoperation between multi-vendor IEDs using the IEC-61850
communication technologies based on international standards. standard is the future of communication technology. In the
Furthemore, PCS-9700 is fully compatible with the IEC-61850 long run, such inteconectivity should save capital in long-term
standard. The system adopts the layered distributed architecture upgrade investment for customers.
with a bay-oriented and object-oriented structure, which is more
reliable, extensible and easy to maintain. NR Electric protection relays, bay control units and substation
automation systems are completely compatible with IEC-61850.
The PCS-9700 helps customers realize the automation of local We also provide solutions that allow the migration from the
operations and collection, evaluation and forwarding of data. conventional substation automation system to the new standard.
It provides remote control and monitoring of the power system The PCS series protection and bay control units support the
operation status. It is suitable for the following applications: IEC-61850-9-2 standard and GOOSE message for the process
• Transmission and distribution substations, power generation bus. The sampled value, interlocking, real-time tripping/closing,
and a variety of industrial electrical systems interlocking and state information are transported via process
bus. Compared to traditional substations, the process bus based
• Utilities, power plants and industries
optical fiber is used to replace cable connections between IEDs.
• Newly constructed substations and retrofit substations This will significantly reduce the construction time and cost.
• Gas and air isolated switchgears
• Subway systems, light-rail systems, and electrified railway
systems
Process Bus Solution
The process bus is one of the cornerstones in the development
of the new digital substation. The process bus, with GOOSE
IEC-61850 Compatibility and IEC 61850-9- 2 standard, is adopted in NR Electric’s digital
NR Electric’s substation automation system is fully compatible substation solution. It realizes the transmission of sampled
with the IEC-61850 standard and has passed the IEC-61850 values, state information, tripping/closing commands and
conformance test, obtaining the level A certification issued by interlocking commands.
KEMA. NR Electric has set up its own IEC-61850 level B test
laboratory to confirm the standard compliance for all products.
NR Electric’s innovative digital substation solution aims at • Communication with control center
improving the modern substation operation modes by using Communication with control center is independent of local
a fiber optic network instead of conventional cable wiring, HMI. The control command is transmitted directly from the
thereby reducing the workload and extending the substations control center. It supports IEC standard protocols and other
operational period. NR Electric’s digital substation solutions standard protocols such as DNP3.0 and 1801.
include process level equipment such as electronic fiber CT/
VTs, merging units, circuit breaker controller and local control • Time synchronization
panels. It also includes PCS series protection and control The system receives GPS standard time signals for clock
devices like protective relays, disturbance recorders, automation synchronism. The absolute time is broadcasted through the
systems, remote control systems and protection information network. The second or minute pulse signal is inputted to the
systems. equipment by RS-485 ports or potential free contact. IRIG-B
signal (AC or DC) is also supported.
The merging unit is suitable for traditional CT/VTs and electronic
CT/VTs. It distributes the digitalized data of current/voltage to • Interfaces with third-party IEDs
various IEDs at the bay level via the process bus or point-to- Protocol converters complied with IEC-61850 standards are
point optical fibers. provided for the integration of third-party IEDs. These can
convert non-IEC-61850 protocols to IEC-61850 and realize
• Electronic CT/VTs digitalize the current/voltage signals and the full automation of all IEDs in the substation.
transmit them to various IEDs (protection units, control units,
metering and disturbance recorders) via optical fibers. • Protection and fault information management.
The system can acquire protection information, fault
• Merging Units gather digitalized data of current/voltage and information, power system stability control and other
distribute it to various IEDs via the process bus. automation equipment. Then it can display, analyze and
process information locally. The information subsystem
• Circuit Breaker Controllers collect state information from the provides a powerful fault analysis tool. When faults occur,
breaker, and transmits it to various IEDs via the process bus, the information subsystem can transmit protection operation
which receive the tripping/closing commands and implements information and fault reports to the dispatching center
them. quickly, helping dispatchers to get correct fault information,
make rapid and correct fault analysis as well as decisions on
• Local control panels realize the local installation of the fault clearance.
protection and control devices
• SAS software package (HMI)
• Gigabit switches guarantee the real-time transmission of The system provides a powerful and friendly human machine
information in the process bus. interface software package, which includes:
-- Setup and maintenance of data base
-- Reactive power and voltage automatic regulation
-- Configurable Alarm processing
Functions -- Sequence of events record and post-fault review
• Real-time data acquisition and processing -- Configuration and displaying of graph and chart
The system makes acquisition and processing of real-time
-- On-line calculation and reports preparing
data of the supervisory and control units, installed at the bay
-- Operation management
level.
-- Electricity processing
• Control operation, synchronism checking and interlocking -- Self-diagnosis and self-restoration
The system can make sequential operations on circuit
breakers, motor-driven isolators, transformer tap changer,
reactive power device group, etc. The PCS-9705 bay control
units carry out control operations, synchronous checking
and electrical interlocking functions. Interlocking software is
used mainly for implementation of edition, compilation and
download of interlocking logic.
Features
• Optimized design scheme (compatible with Windows) or ORACLE (compatible with
The PCS-9700 system consideres various functions of UNIX) is selected as the database management software.
protection, local supervision, control, reactive power Based on softbus and network technology, the appropriate
and voltage regulation, interlocking, selective ground software package is intalled greatly enhancing the availability
fault protection (of an ineffectively grounded system), of the system.
management of equipements, operation and information
protection, fault recorder information, etc., • Direct data transmission to control center
Fu n c ti o n s o f e x te r n a l c o m m u n i c a ti o n a n d i n te r n a l
• Powerful and flexible communication facilities communication are independent to each other. Information
The station bus uses 100M Ethernet while the bay level can be acquired directly from the bay level and transmitted
uses dual 100M Ethernet for redundancy. A powerful to dispatching centers. Communication bottlenecks are a
communication platform is thus formed by merging these problem in traditional RTU schemes. These can be solved
facilities together with network communication equipment, so that reliability of information transmission can be greatly
such as 100Mbps Ethernet Switches and gateways. The enhanced in the PCS-9700 system.
process bus uses redundant Gigabit or 100M Ethernet based
on optical fibers. It will guarantee the real-time transmission • Object-oriented information structure
of important information, such as tripping/closing commands. The information structure is object-oriented. Each logic
device in the database is associated with a physical device.
The system uses IEC 60870-5-103 standard protocol for Influence of single item change is limited to a related part
communication with protection relays and other IEDs. The on the corresponding logic device. Thus, it is easy to be
RCS-9794A/B communication unit in the multiple CPU extended. Attribution of information is self-described. It
structure serves as protocol converter. It provides various supports on-line configuration and real-time check functions
standard ports so that the system can be connected with for the equipment.
equipment made by other manufactures. Therefore, the user
has the flexibility to select from various lines of products. • Secure and reliable bay control unit
The bay control unit is based on a 32 bits CPU and a DSP
• Open HMI software in substation level hardware platform. It adopts real-time multitasks operational
The software of the system is developed based on system with powerful processing ability and is well suited for
Windows and UNIX operational systems. Either, SQL server the requirements of data acquisition and processing at bay
level.
System Architecture
The system is comprised of three or four levels in dispatching, remote control and remote signal
hierarchical structure: Station Level, Network Level, Bay transmition.
Level and optional Process Level. • Real-time monitoring of electrical parameters and
other electrical devices if necessary
For Substations
• AGC and AVC functions
PCS-9700 HMI can be widely applied to substations.
• Power plant operation management and economic
For power plants power distribution between each generator set.
• Safety monitoring of electrical devices
• Complete telecontrol functions for power system For Solar Energy
dispatching, incorporating remote metering, remote PCS-9700 HMI also can be widely applied to PV
substations.
• Station Level and redundant Ethernet ports. These equipment can operate
The station level is a distributed system comprised of a single with long-term stability in severe environments; for example,
computer host or several hosts. It provides supervisory, control high temperatures, high humidity or high electro-magnetic
and management functions for operators in the substation. disturbance.
The man-machine interface is friendly and easy to handle. The
structure is flexible and capable of extention. Furthermore,
the operation mode is reliable. By applying the component • Process Level (Optional)
technology, “plug-and-play” can be realized for software The process level consists of process bus and intelligent
functions. It can communicate with dispatching centers or other devices including electronic CT/VTs, merging units, a circuit
concentrated control stations using different standard protocols breaker controller and a local control panel. Merging units can
such as IEC-60870-5-101 and IEC- 60870-5-104. be incorporated to traditional CT/VTs. Merging units receive
the current/voltage via cables, then converts them into digital
information and distributes them to various IEDs at the bay
• Network level level. A gigabit switch is supplied so that the process bus can
The network level supports single or dual networks, based realize the real-time information transmission. The process
on distributed or ring structures. Balance flow control is bus can be configured in a redundant structure utilizing either
used for duplicated network, so the reliability and the real- Ethernet or optical fiber.
time performance can be ensured. This network level can
communicate smoothly with equipment produced by other
manufacturers using IEC standard communication protocols • Typical structure description
or private communication protocols. Optical links are used -- The station level consists of a host, operator station and
as a transmission medium with sever EMC immunity. Time engineer station. Several computers or single computer
synchronization is conveniently and correctly realized by a GPS configuration may be adopted.
system.
-- Windows or UNIX can be used as the operational system.
Technical Data
Ratings
AC power supply 380 V/220 V, 50 Hz, 60 Hz
DC power supply 250V/220 V/125V/110 V
Secondary current of TA 5 A/1 A
Secondary voltage of TV 100 V/31/2, 110V/31/2
Pulse input: potential free contact, 40 ms min.
Digital input: potential free contact, DC 250V/220 V/125V/110 V
Digital output: potential free contact, 8 A
Electromagnetic Compatibility
Electrostatic discharge IEC 61000-4-2, class 4
Radiated, radio-frequency electromagnetic field IEC 61000-4-3, class 3
Electrical fast transient/burst IEC 61000-4-4, class 4
Surge IEC 61000-4-5, class 3
Conducted disturbances, induced by radio-frequency fields IEC 61000-4-6, class 3
Power frequency magnetic field IEC 61000-4-8, class 4
Telecontrol 20000
Total number of stations can be comprised in system of a controlling station 64
Accuracy
Resolution of A/D conversion 14 bits
GPS clock synchronism ≤ 1 ms
Refreshing cycle
Telemetering, from acquisition input to communication interface output ≤ 3 sec
Telesignal, from change of state input to communication interface output ≤ 3 sec
Telecontrol, from command creation to communication interface output ≤ 1 sec
Updating period of analog quantities on chart ≤ 3 sec
Updating period of change of state on chart ≤ 2 sec
Switch over time of standby hosts ≤30s
Print Port
Characteristic Glass optical fiber
Optical fiber type Multi-mode
Connector type ST
Wave length 820nm
Minimum transmission power -25dBm
Margin Min. +3.0dB
Type Test
Environmental Tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
Mechanical Tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
Electrical Tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
Electrical Tests
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
-- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
-- Spot frequency
-- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
-- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test
Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
PCS-9700
HMI Software
The PCS-9700 HMI (PCS-9700) is designed based on advanced
distributed network technology, object-oriented database
Functions
technology and cross-platform visualization technology. It is • Real-time data acquisition and processing
fully compatible with multiple International standards such as • Control operation, synchronism checking and interlocking
IEC60870-5-103 and IEC61850. The PCS-9700 is suitable for
• Setup and maintenance of data bases
conventional substations, digital substations, and NCS systems
in power plants. • Reactive power and voltage automatic regulation
• Configurable alarm processing
The system adopts distributed and expandable system • Sequence of events record and post-fault review
framework to accommodate different structures. Applications
• Configuration and displaying of graph and chart
and databases can be flexibly configured on each computer
node without modification. The whole system is comprises by
computers on which different operating systems are installed.
The systems functions can be easily expanded according to
user’s demands in order ensure system flexibility and scalability.
The system adopts distributed and expandable system • On-line calculation and reports preparation
framework to accommodate different structures. Applications Based on the real-time data acquired, the system can make
and databases can be flexibly configured on each computer calculations on current, voltage, active and reactive power,
node without modification. The whole system is comprises by power factor, statistics of maximum and minimum value per
computers on which different operating systems are installed. day, month and year of assigned quantities and duration of
The systems functions can be easily expanded according to these values’ occurrence.
user’s demands in order ensure system flexibility and scalability.
• Operation management
• List of events The system can give suggestions on typical failure, fault,
The system can provide various information, such as accident or normal operation, and making of operational
protection information, list of protection events, real-time statistics.
and historical curves and real-time and historical reports.
Besides, users can perform the following functions via • Self-diagnosis and self-restoration
the main interface, such as the reset of protection signals Software and hardware can self-diagnose on-line. The range
and configuration of protection setting, post-fault review of self-diagnosis components include supervisory and control
and display of the results in picture form,,supervision of units, various kinds of stations, communication interface and
communication bit stream, etc. other equipment, networks, channels, clock synchronism
system and peripheral equipment.
Features
The PCS-9700 HMI fully satisfies the customers’ requirements • Adopting unified commercial and realtime database. The
through using up-to-date technology. It has the advantages of equipment oriented database management system supports
high reliability, extensibility, easy maintenance, friend ly user online equipment configuration and realtime verification
interface and high system performance.Its features are listed functions.
below:
• Realizing network information by mutually exchanging,
• Module and object oriented technologies are used to build processing and verifying technologies based on softbus
up the system. technology.
• The design adopts international standards such as C++, • Switching over of redundant equipment without disturbance
TCP/ IP, OLEDB, SQL,ActiveX, etc. through network and node redundant configuration.
• Supports various interfaces, such as: DDE and shared • Well-designed online self-diagnosing function to identify the
memory, supporting flexible network structure, connecting failures of equipmentand network on time.
easily with other systems
• Self-restoration function helps the system restore the normal
• Supporting cross platform function. operation mode when the program losses control.
• he system can operate in UNIX, LINUX and Windows • Having a well-designed online self-diagnosing function,
platforms and can be installed in computers with different finding the failure of equipment and network system on time,
OS. then providing alarm information
• Friendly HMI with online help function, which are easy to • Having self-restoration function, the system can restore itself
learn and use. to the normal operation mode when the program losses
control.
PCS-9705
Bay Control Unit (BCU)
PCS-9705 series bay control units (abbreviated as BCUs) are PCS-9705 series BCUs are designed for the control, monitoring
used for the control and monitoring of different types of bays of circuit breakers, disconnectors, and earthing switches in
inpower networks. PCS-9705 series BCUs are especiallysuitable any type of switchgear and different switchgear configurations.
for applications in control systemswith distributed control IEDs Additionally, PCS-9705 series BCUs enable the manual control
in all bays withhigh demands on reliability. The IED can beused of a tapchanger.
up to the highest voltage levels.
Functions
Main functions of PCS-9705 are listed in the following table:
1 Synchronism-check 25
5 Control(Binary outputs) /
6 Interlocking /
Configurable Outputs Up to 30 Up to 30 Up to 30 Up to 20 Up to 20
DC Inputs
Up to 16 Up to 16 Up to 16 Up to 16 Up to 16
(4-20mA,0-5V, 0-250V)
DC Outputs
Up to 4 Up to 4 Up to 4 0 0
(4-20mA)
Features
• PCS-9705 series BCUs adopt a fully-closed chassis with • Large scale LCD provides graph and text HMI, which make
a complete panel, and completely separated spaces for the operation convenient.
electronic and electrical systems provided.
• Duplex Ethernet ports with 100M optical fiber or RJ45?are
• PCS-9705 series BCUs adopt new UAPC hardware provided.
platform, 16 bits A/D converter, 320*240 graphic dot matrix
LCD, and real time multi-task operating system for industrial • Back plug-in module structure is adopted. Electrical and
purposes so as to realize high-capacity, high-precision, fast, electronic circuits are strictly separated, which enhances
real-time information processing. With high-precision A/D EMC immunity performance.
converters, synchronization sampling can be conducted for
all the AC signals to ensure the accuracy of analog quantity • Low power consumption and wide ambient temperature
measurements, which is up to the 15th harmonic component. range.
• Software and hardware clock synchronization are both • PCS-9705 series BCUs support IEC61850 and IEC60870-5-
adopted with 1ms timing accuracy to ensure the resolution of 103 protocols.
the Sequence Of Events (abbreviated as SOE).
Technical Data
Power Supply
Standard IEC 60255-11:2008
Rated voltage 110Vdc/125Vdc, 220Vdc/250Vdc
Operating range 88~300Vdc
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range 45~65Hz
Accuracy 0.2 class
Rated Current (In) 1A 5A
Linear to 0.05In ~ 2In
Thermal withstand capability continuously 2In
for 10s 12In
for 1s 30In
for half a cycle 75In
Burden <0.2VA/phase @Ln < 0.25VA/phase @Ln
Analog Voltage
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range 45~65Hz
Rated phase-to-phase voltage (Un) 100~130V
linear to 1~130V
Thermalwithstand capability continuously 130V
10s 200V
1s 250V
Burden < 0.20VA/phase @Ln
Transducer Inputs
Standard IEC 60255-1:2009
Input range 0-20mA 0-5V 0-48V 0-250V
Input resistance 235Ω 4.4kΩ 54.2kΩ 248kΩ
Accuracy class 0.5 class 0.5 class 0.5 class 0.5
DC Analog Output
Standard IEC 60255-1:2009
Output range 0-20mA /4-20mA 0-10V
Max load <500Ω <5mA
Dielectric tests 2000VAC 2000VAC
Accuracy class 0.5 class 0.5
Binary Inputs
Rated voltage 24Vdc 48Vdc 110Vdc 125Vdc 220Vdc 250Vdc
Rated current drain 1.2mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13~17Vdc 26~34Vdc 60.5~77Vdc 70~87.5Vdc 121~154Vdc
Dropoff voltage 50% of pickup voltage
Maximum permissible voltage 100Vdc 300Vdc
Withstand voltage 2000Vac, 2800Vdc (continuously)
Response time for logic input ≤1ms
Binary Outputs
Contact type Tripping/signaling contact
Output mode Potential free contact
5A@380Vac
Continuous carry 5A@250Vdc
Burden 300mW
380Vac
Maximal system voltage 250Vdc
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×177.0mm×227.7mm (4U)
Mounting Way Flush mounted
Trepanning dimensions (W×H) 450.0mm×179.0mm, M6 screw
Chassis color Silver grey
Weight per device Approx. 8kg
Chassis material Aluminum alloy
Location of terminal Rear panel of the device
Device structure Plug-in modular type @ rear side, integrated frontplate
Protection class
Standard IEC 60225-1:2009
Front side IP40, up to IP51(With cover)
Other sides IP30
Rear side, connection terminals IP20
Communication Port
- Ethernet Port
Connector type RJ-45 ST (Multi mode)
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX 100Base-FX
Transmission distance <100m <2km (1310nm)
Protocol IEC 60870-5-103:1997, DNP 3.0 or IEC 61850
Safety level Isolation to ELV level
PCS-9799
Station Manager
The PCS-9799 supports various protocols: IIEC60870-5-101, -- Compatible for data model IEC61850 and IEC 103
IEC60870-5-104, CDT, DNP, etc. The data can be transmitted -- Multiple models included: Primary/ secondary equipment
across an analog channel, digital channel or net to the CC, DCS model, association model between primary and
or other control centers. The PCS-9799 can also receive signals secondary equipment, primary schematic diagram model
or commands from the remote centers.
-- Provides full view model and data information for
advanced applications
The information transmitted from the PCS-9799 applies the
-- Unified data gathering and sending for advanced
“Directly get and send” mode. This device can run independently
applications
with the HMI system although no interaction exists between
these two.
-- Optimal report structure, high efficient query function -- Highly integrated functions
-- Total life cycle adoptable: project implementation, running
and maintenance, analyze and diagnose
Technical Data
Mechanical Specifications
Rated Voltage (Un) 110Vdc/125Vdc, 220Vdc/250Vdc;
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:1979
Per IEC 60255-11:1979
Voltage dips and voltage short interruptions 20ms for interruption without de-energizing, dips 60% of Un without reset
up to 100ms
Burden Single device: <45W
Mechanical Specifications
Chassis color Silver grey
Weight per device Approx. 15kg
Chassis material Aluminum alloy
Location of terminal Rear panel of the device
Device structure Plug-in modular type @ rear side, integrated frontplate
Protection class
Standard IEC 60225-1:2009
Front side IP40
Other sides IP30
Rear side, connection terminals IP20
Communication Port
Communication medium Parameters
Digital channel interfaces
Port number Up to 12/24 (single machine/dual machine)
Baud rate 300, 600, 1200, 2400, 9600, 19200 or 38400 bps
RS-232/422/485 (EIA) Transmission distance < 1000m@4800bps
Maximal capacity 32
Safety level Isolation to ELV level
Ethernet channel interfaces
Single machine: 4 ~ 16
Port number
Dual machine: 8 ~ 32
Connector type RJ45
EIA-485 Port Transmission Rate 10M/100Mbps auto-negotiation
Transmission standard 10Base-T/100Base-TX
Transmission distance < 100m
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number Up to 6/12(single machine/dual machine)
Baud rate 300bps, 600bps,1200bps asynchronous
MODEM
Center Frequency 1080 ~ 3000Hz
Offset Frequency ±150 ~±500Hz
EIA-422 Port
Port number 1
Transmission distance < 500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
Communication Protocols
IEC 60870-5-101
IEC 60870-5-104
DNP 3.0 (serial and TCP/IP)
MODBUS
Upward Communication (To control centers) RP570
CDT
SC1801
New programs can be developed for new protocols to meet the
demands of the users.
Downward Communication (To local SCADA system manufactured by NR
IEC 60870-5-103
Electric)
Type Test
Environmental Tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
Mechanical Tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
Electrical Tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m(rms), f=80…1000MHz
Radio frequency interference tests
Spot frequency
Radiated amplitude-modulated
10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
10Vm(rms), f=900MHz
Surge immunity test Power supply, AC input, I/O port: class IV, 1.2/50us
Common mode: 4kV
Differential mode: 2kV
IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150
kHz~80MHz
IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
Auxiliary power supply performance IEC60255-11: 2008
- Voltage dips Up to 500ms for dips to 40% of rated voltage without reset
- Voltage short interruptions 100ms for interruption without rebooting
RCS-9794A/B
Protocol Converter
Technical Data
Power Supply
Rated Voltage (Un) 110V, 125Vdc, 220V, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11
Per IEC 61000-4-11:2004, IEC 60255-11:2008
Voltage dips and voltage short interruptions 20ms for interruption without de-energizing, dips 60% of Un without reset
up to 100ms
Burden <40W
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×177.0×291(unit: mm)
Trepanning dimensions 450.0×179.0, M6 screw
Mounting Way Flush mounted
Front side: IP51
Protection class Rear side, connection terminals: IP20
Other Sides: IP30
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Serial Interfaces
Baud rate 300bits/s ~ 38400bits/s
Copper Transmission distance < 1000m@4800bps
Safety level Isolation to ELV level
Baud rate 300bits/s ~ 38400bits/s
RS-232/422/485 Optical Fiber Type Multi-mode
Connector type ST
Fiber
Wavelength 850nm
Transmission distance ≤ 2000m
Safety level Isolation to ELV level
Baud rate 9600bits/s
Copper
Safety level Isolation to ELV level
Connector type 9600bits/s
Optical Fiber Type Multi-mode
LonWorks
Connector type ST
Fiber
Wavelength 850nm
Transmission distance ≤ 2000m
Safety level Isolation to ELV level
Ethernet Interfaces
Connector type RJ-45
Transmission Rate 100Mbits/s
Copper Ethernet Ports) Transmission standard 100BASE-TX
Transmission distance < 100m
Safety level Isolation to ELV level
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Fiber Ethernet Ports Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 2000m
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
Transmission distance < 500m
RS-485 (EIA)
Timing standard PPS
Safety level Isolation to ELV level
Type Test
Environmental Tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
Mechanical Tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
Electrical Tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
- Radiated amplitude-modulatedSpot frequency 10V/m(rms), f=80…1000MHz
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Surge immunity test Power supply, AC input, I/O port: class IV, 1.2/50us
Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150
kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150
kHz~80MHz
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
PCS-9882
Ethernet Switch
The PCS-9882 series switches can be used in substation switches support up to twenty-four 10/100Mbps electrical
automation system (SAS), networked control system (NCS) and Ethernetports and four 1000Mbps Ethernet ports.The fiber ports
distributed control systems (DCS). They can also be used in adopt SFP sockets, which support hot plugging.
power plants, industrial control systems, etc.
The following table shows the sub types of PCS-9882.The
PCS-9882 series switches provide 1000Mbps Ethernet ports number and type of the fiber ports are different in each sub type
with higher data transmission rates to meetthe increasing in order to meet various requirements.
requirements of the device communication.PCS-9882 series
Functions
Ethernet Switch
• Provide 10/100Mbps self-adaptiveelectrical Ethernet • The 1000Mbps fiber ports of this device adopt SFP socket.
ports. The electrical Ethernet ports comply with 10BASE- The SFP transceiver complies with IEEE802.3 1000BASE-
T/100BASE-TX standardsThey are self-adaptive for SX 1000Mbps fiber Ethernet (1.25GBd) standardscan be
crossover and straight-through network cable. MDI/MDIX plugged into the 1000Mbps SFP socket of this device.
automatic identification is supported.
• Both the 100Mbps SFP socket and the 100Mbps SFP device
• The 100Mbps fiber ports of this device adopt SFP socket. socket support hot plugging.
The SFP transceiver complies with IEEE802.3 100BASE-
• The switching mode adopts non-blocking store and forward.
FX fiber Ethernet standards andcan be plugged into the
100Mbps SFP socket of this device. • Support IEEE802.3x Flow Control.
Note!
GARP is the abbreviation of “Generic Attribute Registration Management Method
Protocol”. • Supports WEB Server, Telnet and CLI.
Features
All PCS-9882 series switches adopt a high-performance • Optimized RSTP protocol is adopted. The restoration time of
switch chip and excellent industrial design to keep line speed the device is less than 1.2 ms per hop. A leading international
forwarding under full-duplex and full-rate operation of all the landmark.
ports. The design and manufacturing of the device has fully
considersvarious adverse conditions and interference factors • The processing capacity guarantees report handling at an
in industrial applications to ensure reliable data transmission average speed between 64-1518bytes without losing any
under tough environments. packages.
• This device is suitable for application according to IEC61850 • VLAN, traffic prioritization, RSTP, port security, GMRP/GVRP,
and indigital substation. IGMP applications are supported to meets the process level
requirements in intelligent substations.
• Patent protected advanced heat emission technology
incorporated to the device in order to ensure excellent heat • Provides port security methods (based on static MAC
emission performance. This device can perform in a range address or based on 802.1X) to guarantee securityin linking
of temperatures, from-40°C~ +85°C. Furthermore, it does so of IEDs in substations.
stably and reliably.
• Network security protocol based on SSL/SSH is supported,
• The device adopts the following advanced technologies: so as to ensure safe access control.
totally enclosed chassis, partitioned grounding connection,
anti-interference power supply, printed circuit board • Static multicast management is supported. In this way,
(abbreviated PCB) division by voltage level, cable transparent and reliable flow control oflinkied IEDs to the
shielding. Therefore, no package loss occur under strong device is ensured.
electromagnetic interferences (abbreviated EMI).
• This device is designed as an industrial management
• Compact field parallel processing technology is incorporated Ethernet switch with abundant functions (e.g.: port flow
into this device to ensure excellent performance. control, network storm limitation, port mirroring, SNMP,
RMON, WEB, port trunking, SNTP clock synchronization).
• Save and transfer processes occur in less that 2μs due to
the 100 Mbps ports. • In case of short power supply interruptions, the device can
still work up to 500ms.
• Process time of save and transfer at 1000Mbps ports is less
than 1μs. • Several 1000Mbps cascading fiber ports are provided to
improve the cascading performance.
• Supports IEC61850 protocol modeling, the user can monitor
the device with the IEC61850 protocol. • Dual power supply technology based on load balance is
supported. Both AC and DC power supplies can be applied
to this device.
Technical Data
AC Power Supply
Standard IEC 61000-4-11:2004
Rated voltage 110Vac/220Vac
Operating range 88~264Vac
PCS-9882AD: <14W
Burden (No load) PCS-9882BD: <13W
PCS-9882ED: <14W
PCS-9882AD: <20W
Burden (Full load) PCS-9882BD: <34W
PCS-9882ED: <28W
DC Power Supply
Standard GB/T 17626.29-2006(idt IEC 61000-4-29:2000).
3 options available:
110Vdc/125Vdc/220Vdc/250Vdc;
Rated voltage
48Vdc;
24Vdc.
PCS-9882AD: <16W
Burden (Full load) PCS-9882BD: <30W
PCS-9882ED: <24W
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×44.4mm×266.0mm(1U)
Mounting Way Flush mounted
Trepanning dimensions (W×H) 450.0mm×44.45mm, M6 screw
Chassis color Silver grey
Weight per device Approx. 3.5kg
Chassismaterial Aluminumalloy
Location of terminal Rear panel of the device
Device structure Plug-in modular type @ rear side, integrated frontplate
Protection class
Standard IEC 60225-1:2009
Front side IP40, up to IP51(With cover)
Other sides IP50
Rear side, connection terminals IP30
Communication Interfaces
Communication Standards IEEE 802.3, IEEE 802.3u, IEEE 802.3ab, IEEE802.3z, IEEE802.3x
100Mbits/s Ethernet Port
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Safety level Isolation to ELV level
100Mbits/s Optical Fiber Port
Characteristic Glass optical fiber
Connector type LC
Transmission standard 100Base-FX
50/125μm multimode fiber
Fiber type 62.5/125μm multimode fiber
9/125μm single mode fiber
Multi mode: <2km
Transmission distance
Single mode: <40km
1000Mbits/s Optical Fiber Port
Characteristic Glass optical fiber
Connector type LC
Transmission standard 1000Base-SX
50/125μm multimode fiber
Fiber type 62.5/125μm multimode fiber
9/125μm single mode fiber
Multi mode: <500m
Single mode: <10km
Transmission distance
If procured by users themselves, the transmission distance is subject to the SFP transceiver
module.
Type Test
Environmental Tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
Mechanical Tests
IEC60870-2-2:1996 Class Cm,
Vibration
IEEE1613:2007
Shock IEC60870-2-2:1996 Class Cm
Electrical Tests
IEEE1613:2007, Ur <50V then 500 Vrms
Dielectric tests
51<Ur <250V then 2000 Vrms
Electromagnetic Compatibility
IEC 61000-4-18
Damped oscillatory wave immunity test Common mode: class III ±2.5kV
Differential mode: class III ±1.0kV
IEC61000-4-2
Electrostatic discharge test For contact discharge: class IV, ±8kV
For air discharge: class IV, ±15kV
IEC61000-4-3
IEC61000-4-4
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 5kHz or 100kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHzor 100kHz, 5/50ns
IEC61000-4-5
Surge immunity test Power supply, AC input, I/O port: class IV,1.2/50μs
Common mode: ±4kV
Differential mode: ±2kV
IEC61000-4-6
Conducted RF Electromagnetic Disturbance Power supply, AC, I/O, Comm. Terminal:Class III,
0.15~80MHz AM 80%
1kHz 10V (un-modulated)
IEC61000-4-8
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
IEC61000-4-9
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC61000-4-10
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
- Voltage short interruptions 500ms for interruption without rebooting(only for 220Vac),
60ms for interruption without rebooting(only for 110Vac).
RCS-9785C/D
GPS Synchronization Clock
The RCS-9785C/D is a GPS Synchronized Unit with abuiltin • Various output interfaces forthe time signals
GPS receiver module. It receives timing messages through a The RCS-9785C/D can provide electrical (including RS-
built-in GPS receiver module. Alternatively, it receives IRIG-B 232/RS- 485, TTL, and AC modulation) or optical output
standardized timing code through one of the two input channels, timing signals. The timing signals supports IRIG-B, PPS,
decodes and converts the timing code, and then outputs such PPM, PPH, etc.
timing signals to the whole station. Output timing signals can
be IRIG-B signals, pulse per second (PPS) signals, pulse • Application for large system
per minute (PPM), pulse per hour (PPH) signals and timing The device is equipped with enough ports for output. The
messages. It also can provide Ethernet clock synchronization RCS- 9785C/D can be used to multiply time synchronizing
services (CSS) for bay units. The Ethernet CSS can work in the pulses to meet demand if required.
dual Ethernet mode (RJ45 over 100BASE-TX).Multi-business
acquisition simultaneous, access BCU, protection, PMU, meter, • High reliability
online monitoring device and among other advanced functions. The use of high-integration circuits and modular design
technology in the RCS-9785C/D enhances the reliability of
the device.
Features
• Highly accurate time signal output
-- The device is precise with a lag time of ±1μs for IRIG-B/
PPS/PPM/PPH time signals (excluding the propagation
delay time on the cable). The pulse front edges of these
time signals are less than 50ns.
Technical Data
Power Supply
Rated Voltage (Un) 110V/125Vdc, 220V/250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:1979
Burden <40W
Binary Outputs
Item Signal contact
Output mode Potential free contact
Max system voltage 380Vac, 250Vdc
Test voltage across open contact 1000V RMS for 1min
Continuous carry 8.0A
0.4A resistance
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms)
Short duration current 50A for 200ms
Pickup time 5ms/10ms
Drop-off time <8ms
Bounce time 1ms
Mechanical Specifications
Enclosure dimension (W×H×D) 482.6×177.0×291.0(unit: mm)
Trepanning dimension (W×H) 450.0×179.0, (unit: mm), M6 screw
Mounting Flush mounted
Front side: IP51
Protection class(per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Ports to Transmit Clock Synchronization Signals
Port number 7 per module
Connector type RJ45
Transmission Rate 100Mbps
Ethernet Transmission standard 10Base-T/100Base-TX
Transmission distance < 100m
Protocol SNTP
Safety level Isolation to ELV level
Port number 7 per module
RS-232 Transmission distance <30m
Safety level Isolation to ELV level
Port number 7 per module
Maximal capacity 32
RS-485 (EIA)
Transmission distance <500m
Safety level Isolation to ELV level
Port number 8 per module
Operating voltage ≤ 300Vdc
Optic-Coupled Dry Contact Operating current ≤ 60mA
Transmission distance < 200m
Safety level Isolation to ELV level
Type Test
Environmental Tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
Mechanical Tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
Electrical Tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test
Common mode: 4kV
Differential mode: 2kV
Conducted RF Electromagnetic Disturbance Per IEC 60255-22-6:2001
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150
kHz~80MHz
Power Frequency Magnetic Field Immunity Per IEC 61000-4-8:2001
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150
kHz~80MHz
Pulse Magnetic Field Immunity Per IEC 61000-4-9:2001
class V, 6.4/16μs, 1000A/m for 3s
Damped oscillatory magnetic field immunity IEC 61000-4-10:2001
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting