NR Electric Co., Ltd.

PCS-9700
Automation System

The PCS-9700 is a state-of-the-art automation solution for The IEC-61850 standard provides an internationally recognized
substations, power generators and a variety of industries. The method targeted at increasing the interoperability between
PCS-9700 is equipped with diverce advanced technologies and IEDs from different venders. The IEC-61850 standard has
patents. It can be incorporated into a variety of substations, from built-in capabilities for high-speed control and data sharing
distribution level to the extra high voltage level. It integrates over the network, eliminating most dedicated control wiring.
the applications of protection, control, Ethernet, IT and Interoperation between multi-vendor IEDs using the IEC-61850
communication technologies based on international standards. standard is the future of communication technology. In the
Furthemore, PCS-9700 is fully compatible with the IEC-61850 long run, such inteconectivity should save capital in long-term
standard. The system adopts the layered distributed architecture upgrade investment for customers.
with a bay-oriented and object-oriented structure, which is more
reliable, extensible and easy to maintain. NR Electric protection relays, bay control units and substation
automation systems are completely compatible with IEC-61850.
The PCS-9700 helps customers realize the automation of local We also provide solutions that allow the migration from the
operations and collection, evaluation and forwarding of data. conventional substation automation system to the new standard.
It provides remote control and monitoring of the power system The PCS series protection and bay control units support the
operation status. It is suitable for the following applications: IEC-61850-9-2 standard and GOOSE message for the process
• Transmission and distribution substations, power generation bus. The sampled value, interlocking, real-time tripping/closing,
and a variety of industrial electrical systems interlocking and state information are transported via process
bus. Compared to traditional substations, the process bus based
• Utilities, power plants and industries
optical fiber is used to replace cable connections between IEDs.
• Newly constructed substations and retrofit substations This will significantly reduce the construction time and cost.
• Gas and air isolated switchgears
• Subway systems, light-rail systems, and electrified railway
systems
Process Bus Solution
The process bus is one of the cornerstones in the development
of the new digital substation. The process bus, with GOOSE
IEC-61850 Compatibility and IEC 61850-9- 2 standard, is adopted in NR Electric’s digital
NR Electric’s substation automation system is fully compatible substation solution. It realizes the transmission of sampled
with the IEC-61850 standard and has passed the IEC-61850 values, state information, tripping/closing commands and
conformance test, obtaining the level A certification issued by interlocking commands.
KEMA. NR Electric has set up its own IEC-61850 level B test
laboratory to confirm the standard compliance for all products.

146 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

NR Electric’s innovative digital substation solution aims at • Communication with control center
improving the modern substation operation modes by using Communication with control center is independent of local
a fiber optic network instead of conventional cable wiring, HMI. The control command is transmitted directly from the
thereby reducing the workload and extending the substations control center. It supports IEC standard protocols and other
operational period. NR Electric’s digital substation solutions standard protocols such as DNP3.0 and 1801.
include process level equipment such as electronic fiber CT/
VTs, merging units, circuit breaker controller and local control • Time synchronization
panels. It also includes PCS series protection and control The system receives GPS standard time signals for clock
devices like protective relays, disturbance recorders, automation synchronism. The absolute time is broadcasted through the
systems, remote control systems and protection information network. The second or minute pulse signal is inputted to the
systems. equipment by RS-485 ports or potential free contact. IRIG-B
signal (AC or DC) is also supported.
The merging unit is suitable for traditional CT/VTs and electronic
CT/VTs. It distributes the digitalized data of current/voltage to • Interfaces with third-party IEDs
various IEDs at the bay level via the process bus or point-to- Protocol converters complied with IEC-61850 standards are
point optical fibers. provided for the integration of third-party IEDs. These can
convert non-IEC-61850 protocols to IEC-61850 and realize
• Electronic CT/VTs digitalize the current/voltage signals and the full automation of all IEDs in the substation.
transmit them to various IEDs (protection units, control units,
metering and disturbance recorders) via optical fibers. • Protection and fault information management.
The system can acquire protection information, fault
• Merging Units gather digitalized data of current/voltage and information, power system stability control and other
distribute it to various IEDs via the process bus. automation equipment. Then it can display, analyze and
process information locally. The information subsystem
• Circuit Breaker Controllers collect state information from the provides a powerful fault analysis tool. When faults occur,
breaker, and transmits it to various IEDs via the process bus, the information subsystem can transmit protection operation
which receive the tripping/closing commands and implements information and fault reports to the dispatching center
them. quickly, helping dispatchers to get correct fault information,
make rapid and correct fault analysis as well as decisions on
• Local control panels realize the local installation of the fault clearance.
protection and control devices
• SAS software package (HMI)
• Gigabit switches guarantee the real-time transmission of The system provides a powerful and friendly human machine
information in the process bus. interface software package, which includes:
-- Setup and maintenance of data base
-- Reactive power and voltage automatic regulation
-- Configurable Alarm processing
Functions -- Sequence of events record and post-fault review
• Real-time data acquisition and processing -- Configuration and displaying of graph and chart
The system makes acquisition and processing of real-time
-- On-line calculation and reports preparing
data of the supervisory and control units, installed at the bay
-- Operation management
level.
-- Electricity processing
• Control operation, synchronism checking and interlocking -- Self-diagnosis and self-restoration
The system can make sequential operations on circuit
breakers, motor-driven isolators, transformer tap changer,
reactive power device group, etc. The PCS-9705 bay control
units carry out control operations, synchronous checking
and electrical interlocking functions. Interlocking software is
used mainly for implementation of edition, compilation and
download of interlocking logic.

Read more on the web


www.nrelect.com 147
NR Electric Co., Ltd.

Features
• Optimized design scheme (compatible with Windows) or ORACLE (compatible with
The PCS-9700 system consideres various functions of UNIX) is selected as the database management software.
protection, local supervision, control, reactive power Based on softbus and network technology, the appropriate
and voltage regulation, interlocking, selective ground software package is intalled greatly enhancing the availability
fault protection (of an ineffectively grounded system), of the system.
management of equipements, operation and information
protection, fault recorder information, etc., • Direct data transmission to control center
Fu n c ti o n s o f e x te r n a l c o m m u n i c a ti o n a n d i n te r n a l
• Powerful and flexible communication facilities communication are independent to each other. Information
The station bus uses 100M Ethernet while the bay level can be acquired directly from the bay level and transmitted
uses dual 100M Ethernet for redundancy. A powerful to dispatching centers. Communication bottlenecks are a
communication platform is thus formed by merging these problem in traditional RTU schemes. These can be solved
facilities together with network communication equipment, so that reliability of information transmission can be greatly
such as 100Mbps Ethernet Switches and gateways. The enhanced in the PCS-9700 system.
process bus uses redundant Gigabit or 100M Ethernet based
on optical fibers. It will guarantee the real-time transmission • Object-oriented information structure
of important information, such as tripping/closing commands. The information structure is object-oriented. Each logic
device in the database is associated with a physical device.
The system uses IEC 60870-5-103 standard protocol for Influence of single item change is limited to a related part
communication with protection relays and other IEDs. The on the corresponding logic device. Thus, it is easy to be
RCS-9794A/B communication unit in the multiple CPU extended. Attribution of information is self-described. It
structure serves as protocol converter. It provides various supports on-line configuration and real-time check functions
standard ports so that the system can be connected with for the equipment.
equipment made by other manufactures. Therefore, the user
has the flexibility to select from various lines of products. • Secure and reliable bay control unit
The bay control unit is based on a 32 bits CPU and a DSP
• Open HMI software in substation level hardware platform. It adopts real-time multitasks operational
The software of the system is developed based on system with powerful processing ability and is well suited for
Windows and UNIX operational systems. Either, SQL server the requirements of data acquisition and processing at bay
level.

Figure 1-1. Automation system structures for substation applications

148 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

Figure 1-2. Automation system structures for substation applications

System Architecture
The system is comprised of three or four levels in dispatching, remote control and remote signal
hierarchical structure: Station Level, Network Level, Bay transmition.
Level and optional Process Level. • Real-time monitoring of electrical parameters and
other electrical devices if necessary
For Substations
• AGC and AVC functions
PCS-9700 HMI can be widely applied to substations.
• Power plant operation management and economic
For power plants power distribution between each generator set.
• Safety monitoring of electrical devices
• Complete telecontrol functions for power system For Solar Energy
dispatching, incorporating remote metering, remote PCS-9700 HMI also can be widely applied to PV
substations.

Figure 2-1. NCS structures for power plants applications

Read more on the web


www.nrelect.com 149
NR Electric Co., Ltd.

Figure 2-2. ECS structures for power plants applications

Figure 3. Automation system structures for solar energy applications

150 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

• Station Level and redundant Ethernet ports. These equipment can operate
The station level is a distributed system comprised of a single with long-term stability in severe environments; for example,
computer host or several hosts. It provides supervisory, control high temperatures, high humidity or high electro-magnetic
and management functions for operators in the substation. disturbance.
The man-machine interface is friendly and easy to handle. The
structure is flexible and capable of extention. Furthermore,
the operation mode is reliable. By applying the component • Process Level (Optional)
technology, “plug-and-play” can be realized for software The process level consists of process bus and intelligent
functions. It can communicate with dispatching centers or other devices including electronic CT/VTs, merging units, a circuit
concentrated control stations using different standard protocols breaker controller and a local control panel. Merging units can
such as IEC-60870-5-101 and IEC- 60870-5-104. be incorporated to traditional CT/VTs. Merging units receive
the current/voltage via cables, then converts them into digital
information and distributes them to various IEDs at the bay
• Network level level. A gigabit switch is supplied so that the process bus can
The network level supports single or dual networks, based realize the real-time information transmission. The process
on distributed or ring structures. Balance flow control is bus can be configured in a redundant structure utilizing either
used for duplicated network, so the reliability and the real- Ethernet or optical fiber.
time performance can be ensured. This network level can
communicate smoothly with equipment produced by other
manufacturers using IEC standard communication protocols • Typical structure description
or private communication protocols. Optical links are used -- The station level consists of a host, operator station and
as a transmission medium with sever EMC immunity. Time engineer station. Several computers or single computer
synchronization is conveniently and correctly realized by a GPS configuration may be adopted.
system.
-- Windows or UNIX can be used as the operational system.

-- The gateway can adopt RCS-9698G/H device, channel


• Bay level switching equipment and channel interface.
The bay level consists of bay control units, various protection -- RCS-9785 can be used as the GPS receiver.
devices, disturbance recorders and other IEDs. All of NR
-- PCS and RCS series protection equipment can be
Electric’s IEDs support IEC 61850-8-1 standards for station bus
connected with the station level directly via two 100M
Ethernet ports or via two RS-485 ports through a protocol
converter.

Technical Data
Ratings
AC power supply 380 V/220 V, 50 Hz, 60 Hz
DC power supply 250V/220 V/125V/110 V
Secondary current of TA 5 A/1 A
Secondary voltage of TV 100 V/31/2, 110V/31/2
Pulse input: potential free contact, 40 ms min.
Digital input: potential free contact, DC 250V/220 V/125V/110 V
Digital output: potential free contact, 8 A

Electromagnetic Compatibility
Electrostatic discharge IEC 61000-4-2, class 4
Radiated, radio-frequency electromagnetic field IEC 61000-4-3, class 3
Electrical fast transient/burst IEC 61000-4-4, class 4
Surge IEC 61000-4-5, class 3
Conducted disturbances, induced by radio-frequency fields IEC 61000-4-6, class 3
Power frequency magnetic field IEC 61000-4-8, class 4

Read more on the web


www.nrelect.com 151
NR Electric Co., Ltd.

Pulse magnetic field IEC 61000-4-9, class 5


Damped oscillatory magnetic field IEC 61000-4-10, class 5
Oscillatory waves IEC 61000-4-12, class 2
Maximum capacity
Telesignal 80000
Telemetering 40000

Telecontrol 20000
Total number of stations can be comprised in system of a controlling station 64

Accuracy
Resolution of A/D conversion 14 bits
GPS clock synchronism ≤ 1 ms

Total error of analog quantity measurement


Voltage and current ≤ 0.2%
Active and reactive power ≤ 0.5%
Power frequency ≤ ±0.005 Hz

Refreshing cycle
Telemetering, from acquisition input to communication interface output ≤ 3 sec
Telesignal, from change of state input to communication interface output ≤ 3 sec
Telecontrol, from command creation to communication interface output ≤ 1 sec
Updating period of analog quantities on chart ≤ 3 sec
Updating period of change of state on chart ≤ 2 sec
Switch over time of standby hosts ≤30s

Print Port
Characteristic Glass optical fiber
Optical fiber type Multi-mode
Connector type ST
Wave length 820nm
Minimum transmission power -25dBm
Margin Min. +3.0dB

Clock Synchronization Port


Type RS-485
Transmission distance <500m
Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level

Type Test
Environmental Tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005

Mechanical Tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I

152 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

Electrical Tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC

Electrical Tests
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
-- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
-- Spot frequency
-- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
-- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test
Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting

Read more on the web


www.nrelect.com 153
NR Electric Co., Ltd.

PCS-9700
HMI Software
The PCS-9700 HMI (PCS-9700) is designed based on advanced
distributed network technology, object-oriented database
Functions
technology and cross-platform visualization technology. It is • Real-time data acquisition and processing
fully compatible with multiple International standards such as • Control operation, synchronism checking and interlocking
IEC60870-5-103 and IEC61850. The PCS-9700 is suitable for
• Setup and maintenance of data bases
conventional substations, digital substations, and NCS systems
in power plants. • Reactive power and voltage automatic regulation
• Configurable alarm processing
The system adopts distributed and expandable system • Sequence of events record and post-fault review
framework to accommodate different structures. Applications
• Configuration and displaying of graph and chart
and databases can be flexibly configured on each computer
node without modification. The whole system is comprises by
computers on which different operating systems are installed.
The systems functions can be easily expanded according to
user’s demands in order ensure system flexibility and scalability.

Figure 1. Basic functions for PCS-9700 HMI Software

154 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

Figure 2. Advanced functions for PCS-9700 HMI

The system adopts distributed and expandable system • On-line calculation and reports preparation
framework to accommodate different structures. Applications Based on the real-time data acquired, the system can make
and databases can be flexibly configured on each computer calculations on current, voltage, active and reactive power,
node without modification. The whole system is comprises by power factor, statistics of maximum and minimum value per
computers on which different operating systems are installed. day, month and year of assigned quantities and duration of
The systems functions can be easily expanded according to these values’ occurrence.
user’s demands in order ensure system flexibility and scalability.
• Operation management
• List of events The system can give suggestions on typical failure, fault,
The system can provide various information, such as accident or normal operation, and making of operational
protection information, list of protection events, real-time statistics.
and historical curves and real-time and historical reports.
Besides, users can perform the following functions via • Self-diagnosis and self-restoration
the main interface, such as the reset of protection signals Software and hardware can self-diagnose on-line. The range
and configuration of protection setting, post-fault review of self-diagnosis components include supervisory and control
and display of the results in picture form,,supervision of units, various kinds of stations, communication interface and
communication bit stream, etc. other equipment, networks, channels, clock synchronism
system and peripheral equipment.

Read more on the web


www.nrelect.com 155
NR Electric Co., Ltd.

Features
The PCS-9700 HMI fully satisfies the customers’ requirements • Adopting unified commercial and realtime database. The
through using up-to-date technology. It has the advantages of equipment oriented database management system supports
high reliability, extensibility, easy maintenance, friend ly user online equipment configuration and realtime verification
interface and high system performance.Its features are listed functions.
below:
• Realizing network information by mutually exchanging,
• Module and object oriented technologies are used to build processing and verifying technologies based on softbus
up the system. technology.

• The design adopts international standards such as C++, • Switching over of redundant equipment without disturbance
TCP/ IP, OLEDB, SQL,ActiveX, etc. through network and node redundant configuration.

• Supports various interfaces, such as: DDE and shared • Well-designed online self-diagnosing function to identify the
memory, supporting flexible network structure, connecting failures of equipmentand network on time.
easily with other systems
• Self-restoration function helps the system restore the normal
• Supporting cross platform function. operation mode when the program losses control.

• he system can operate in UNIX, LINUX and Windows • Having a well-designed online self-diagnosing function,
platforms and can be installed in computers with different finding the failure of equipment and network system on time,
OS. then providing alarm information

• Friendly HMI with online help function, which are easy to • Having self-restoration function, the system can restore itself
learn and use. to the normal operation mode when the program losses
control.

156 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

PCS-9705
Bay Control Unit (BCU)

PCS-9705 series bay control units (abbreviated as BCUs) are PCS-9705 series BCUs are designed for the control, monitoring
used for the control and monitoring of different types of bays of circuit breakers, disconnectors, and earthing switches in
inpower networks. PCS-9705 series BCUs are especiallysuitable any type of switchgear and different switchgear configurations.
for applications in control systemswith distributed control IEDs Additionally, PCS-9705 series BCUs enable the manual control
in all bays withhigh demands on reliability. The IED can beused of a tapchanger.
up to the highest voltage levels.

Functions
Main functions of PCS-9705 are listed in the following table:

Main functions of PCS-9705


No. Function ANSI

1 Synchronism-check 25

2 Tap changer control and supervision 84

3 Monitoring (Binary inputs, AC/DC analog inputs) /

4 Regulation(DC analog outputs) /

5 Control(Binary outputs) /

6 Interlocking /

158 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

Maximum configuration of PCS-9705 is listed in the following table:

Model PCS-9705A PCS-9705B PCS-9705C PCS-9705D PCS-9705E

AC inputs 5VT/4CT 13VT 8VT/7CT 24VT 12VT/12CT

Binary Inputs Up to 120 Up to 120 Up to 120 Up to 140 Up to 140

Binary Outputs Up to 32pairs Up to 32pairs Up to 32pairs Up to 25 pairs Up to 25 pairs

Configurable Outputs Up to 30 Up to 30 Up to 30 Up to 20 Up to 20

DC Inputs
Up to 16 Up to 16 Up to 16 Up to 16 Up to 16
(4-20mA,0-5V, 0-250V)

DC Outputs
Up to 4 Up to 4 Up to 4 0 0
(4-20mA)

Synchro-check 1 breaker 0 2 breaker 0 4breaker

Interlocking Logic Yes Yes Yes Yes Yes

Support to ECVT (optional) Yes Yes Yes NO NO

IEC61850 Process Bus (optional) Yes Yes Yes NO NO

Features
• PCS-9705 series BCUs adopt a fully-closed chassis with • Large scale LCD provides graph and text HMI, which make
a complete panel, and completely separated spaces for the operation convenient.
electronic and electrical systems provided.
• Duplex Ethernet ports with 100M optical fiber or RJ45?are
• PCS-9705 series BCUs adopt new UAPC hardware provided.
platform, 16 bits A/D converter, 320*240 graphic dot matrix
LCD, and real time multi-task operating system for industrial • Back plug-in module structure is adopted. Electrical and
purposes so as to realize high-capacity, high-precision, fast, electronic circuits are strictly separated, which enhances
real-time information processing. With high-precision A/D EMC immunity performance.
converters, synchronization sampling can be conducted for
all the AC signals to ensure the accuracy of analog quantity • Low power consumption and wide ambient temperature
measurements, which is up to the 15th harmonic component. range.

• Software and hardware clock synchronization are both • PCS-9705 series BCUs support IEC61850 and IEC60870-5-
adopted with 1ms timing accuracy to ensure the resolution of 103 protocols.
the Sequence Of Events (abbreviated as SOE).

Read more on the web


www.nrelect.com 159
NR Electric Co., Ltd.

Technical Data
Power Supply
Standard IEC 60255-11:2008
Rated voltage 110Vdc/125Vdc, 220Vdc/250Vdc
Operating range 88~300Vdc
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage

Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range 45~65Hz
Accuracy 0.2 class
Rated Current (In) 1A 5A
Linear to 0.05In ~ 2In
Thermal withstand capability continuously 2In
for 10s 12In
for 1s 30In
for half a cycle 75In
Burden <0.2VA/phase @Ln < 0.25VA/phase @Ln

Analog Voltage
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range 45~65Hz
Rated phase-to-phase voltage (Un) 100~130V
linear to 1~130V
Thermalwithstand capability continuously 130V
10s 200V
1s 250V
Burden < 0.20VA/phase @Ln

Transducer Inputs
Standard IEC 60255-1:2009
Input range 0-20mA 0-5V 0-48V 0-250V
Input resistance 235Ω 4.4kΩ 54.2kΩ 248kΩ
Accuracy class 0.5 class 0.5 class 0.5 class 0.5

DC Analog Output
Standard IEC 60255-1:2009
Output range 0-20mA /4-20mA 0-10V
Max load <500Ω <5mA
Dielectric tests 2000VAC 2000VAC
Accuracy class 0.5 class 0.5

160 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

Binary Inputs
Rated voltage 24Vdc 48Vdc 110Vdc 125Vdc 220Vdc 250Vdc
Rated current drain 1.2mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13~17Vdc 26~34Vdc 60.5~77Vdc 70~87.5Vdc 121~154Vdc
Dropoff voltage 50% of pickup voltage
Maximum permissible voltage 100Vdc 300Vdc
Withstand voltage 2000Vac, 2800Vdc (continuously)
Response time for logic input ≤1ms

Binary Outputs
Contact type Tripping/signaling contact
Output mode Potential free contact
5A@380Vac
Continuous carry 5A@250Vdc

Pickup time <8ms (typical 3~5ms)


Dropoff time <5ms
0.65A@48Vdc
0.30A@110Vdc
Breaking capacity (L/R=40ms)
0.15A@220Vdc

Burden 300mW
380Vac
Maximal system voltage 250Vdc

Test voltage across open contact 1000V RMS for 1min


6A@3s
[email protected]
Short duration current
[email protected]

Durability 10,000 operations minimum

Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×177.0mm×227.7mm (4U)
Mounting Way Flush mounted
Trepanning dimensions (W×H) 450.0mm×179.0mm, M6 screw
Chassis color Silver grey
Weight per device Approx. 8kg
Chassis material Aluminum alloy
Location of terminal Rear panel of the device
Device structure Plug-in modular type @ rear side, integrated frontplate
Protection class
Standard IEC 60225-1:2009
Front side IP40, up to IP51(With cover)
Other sides IP30
Rear side, connection terminals IP20

Ambient Temperature and Humidity Range


Standard IEC 60255-1:2009
Operating temperature -25~55 (Readability of display may be impaired below -20°C)
Transport and storage temperature range -40°C to +70°C
Permissible humidity 5%-95%, without condensation
Pollution degree 2
Altitude <3000m

Read more on the web


www.nrelect.com 161
NR Electric Co., Ltd.

Communication Port
- Ethernet Port
Connector type RJ-45 ST (Multi mode)
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX 100Base-FX
Transmission distance <100m <2km (1310nm)
Protocol IEC 60870-5-103:1997, DNP 3.0 or IEC 61850
Safety level Isolation to ELV level

- Optical Fiber Port


• For Station Level
Characteristic Glass optical fiber
Connector type ST
Fiber type Multi mode
Transmission distance <2km
Wave length 1310nm
Transmission power Min. -20.0dBm
Minimum receiving power Min. -30.0dBm
Margin Min. +3.0dB

• For Process Level


Characteristic Glass optical fiber
Connector type LC
Fiber type Multi mode
Transmission distance <2km
Wave length 1310nm
Transmission power Min. -20.0dBm
Minimum receiving power Min. -30.0dBm
Margin Min. +3.0dB

• For Synchronization Port


Characteristic Glass optical fiber
Connector type ST
Fiber type Multi mode
Wave length 820nm
Minimum receiving power Min. -25.0dBm
Margin Min. +3.0dB

- Clock Synchronization Port


Type RS-485
Transmission distance <500m
Maximal capacity 32
Timing standard PPS, PPM, IRIG-B
Safety level Isolation to ELV level

162 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

PCS-9799
Station Manager

The PCS-9799 is a station manager designed for the highest Features


standards of performance, safety and reliability in effort to
meet the requirements of a complex substation automation • High performance hardware architecture
system (SAS). It is an integral part of the SAS, and it is a -- CPU: >1Ghz, RAM: > 1GB
communication gateway that maps signals between protection
-- Capable for data management and communication of the
and control IEDs in industrial or utility substations and higher-
SAS of mega substation or power plant
level systems (such as Control Centers (CC) or Distributed
Control Systems (DCS)). -- Capacity of device access: > 512 sets
-- Multiple MON module: at most 4 with 6 net port on each
Generally the PCS-9799 is applied in a variety of voltage level module
substation. Its high performance provides multiple functions, -- COM module: each module has 5 serial ports, RS-485/
which are critical in a substation. It is used to acquire complete RS-232 configurable
information from substation. Then it builds the general data
-- MODEM module: 3/6 analog channels, parameters
platform and works as the terminal for data transmission. In
configurable
addition, it also provides many advanced functions, such as:
-- IO Module: 9 adaptable binary inputs and 6 outputs
substation supervision, general gateway, protection information
acquisition and transmission, on-line monitoring, electricity
• Advanced real-time database
metering, PMU, etc.
-- Object-oriented design attitude

The PCS-9799 supports various protocols: IIEC60870-5-101, -- Compatible for data model IEC61850 and IEC 103
IEC60870-5-104, CDT, DNP, etc. The data can be transmitted -- Multiple models included: Primary/ secondary equipment
across an analog channel, digital channel or net to the CC, DCS model, association model between primary and
or other control centers. The PCS-9799 can also receive signals secondary equipment, primary schematic diagram model
or commands from the remote centers.
-- Provides full view model and data information for
advanced applications
The information transmitted from the PCS-9799 applies the
-- Unified data gathering and sending for advanced
“Directly get and send” mode. This device can run independently
applications
with the HMI system although no interaction exists between
these two.

Read more on the web


www.nrelect.com 173
NR Electric Co., Ltd.

• Unified historical database • Powerful synchronization


-- Embedded historical database, completely solves the -- Independent synchronization system for each MON board
problem of large data storage -- Multiple synchronization source supported: Net message,
-- Database capacity: >8GB GPS, NTP net synchronization
-- Multiple data information: Historical event, operation -- Hardware synchronization: PPS, PPM, IRIG-B
report, wave file, etc.
• Unified substation data sending platform
• Real-time data transmission platform -- Realized the data model transformation between
-- Furthest ensure the real-time data transmission to the substation and RCC by using the SCD file
RCC, which provide the real-time data for the advanced -- Support most of mainstream protocols: IEC60870-5-
application in RCC 101/104, IEC60870-5-102, IEC60870-5-103, IEC61850
-- Internal SOE transmission delay: <100ms
• Redundant working mode
• Basic substation SCADA operation supported -- Automatically running-standby state switch
-- Basic SCADA functions integrated(require computer for -- Support channel-only switch mode which ensures the
HMI) seamless switch between different channels with different
-- Real-time and historical alarm query protocols
-- Measurement and operation supported
-- Powerful report recording function: device running report, • Powerful configuration tool
operation report, SOE report -- Fully use of the SCD file

-- Optimal report structure, high efficient query function -- Highly integrated functions
-- Total life cycle adoptable: project implementation, running
and maintenance, analyze and diagnose

Technical Data
Mechanical Specifications
Rated Voltage (Un) 110Vdc/125Vdc, 220Vdc/250Vdc;
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:1979
Per IEC 60255-11:1979
Voltage dips and voltage short interruptions 20ms for interruption without de-energizing, dips 60% of Un without reset
up to 100ms
Burden Single device: <45W

Mechanical Specifications
Chassis color Silver grey
Weight per device Approx. 15kg
Chassis material Aluminum alloy
Location of terminal Rear panel of the device
Device structure Plug-in modular type @ rear side, integrated frontplate
Protection class
Standard IEC 60225-1:2009
Front side IP40
Other sides IP30
Rear side, connection terminals IP20

174 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

Ambient Temperature and Humidity Range


Standard IEC60255-1:2009
Operating temperature -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible

Communication Port
Communication medium Parameters
Digital channel interfaces
Port number Up to 12/24 (single machine/dual machine)
Baud rate 300, 600, 1200, 2400, 9600, 19200 or 38400 bps
RS-232/422/485 (EIA) Transmission distance < 1000m@4800bps
Maximal capacity 32
Safety level Isolation to ELV level
Ethernet channel interfaces
Single machine: 4 ~ 16
Port number
Dual machine: 8 ~ 32
Connector type RJ45
EIA-485 Port Transmission Rate 10M/100Mbps auto-negotiation
Transmission standard 10Base-T/100Base-TX
Transmission distance < 100m
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number Up to 6/12(single machine/dual machine)
Baud rate 300bps, 600bps,1200bps asynchronous
MODEM
Center Frequency 1080 ~ 3000Hz
Offset Frequency ±150 ~±500Hz
EIA-422 Port
Port number 1
Transmission distance < 500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level

Communication Protocols
IEC 60870-5-101
IEC 60870-5-104
DNP 3.0 (serial and TCP/IP)
MODBUS
Upward Communication (To control centers) RP570
CDT
SC1801
New programs can be developed for new protocols to meet the
demands of the users.
Downward Communication (To local SCADA system manufactured by NR
IEC 60870-5-103
Electric)

Read more on the web


www.nrelect.com 175
NR Electric Co., Ltd.

Type Test
Environmental Tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005

Mechanical Tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I

Electrical Tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC

Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
IEC 60255-22-3:2007 class III

Frequency sweep
Radiated amplitude-modulated
10V/m(rms), f=80…1000MHz
Radio frequency interference tests
Spot frequency
Radiated amplitude-modulated
10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
10Vm(rms), f=900MHz

Per IEC 60255-22-4:2008


Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008

Surge immunity test Power supply, AC input, I/O port: class IV, 1.2/50us
Common mode: 4kV
Differential mode: 2kV

IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150
kHz~80MHz
IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
Auxiliary power supply performance IEC60255-11: 2008
- Voltage dips Up to 500ms for dips to 40% of rated voltage without reset
- Voltage short interruptions 100ms for interruption without rebooting

176 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

RCS-9794A/B
Protocol Converter

The RCS-9794A/B protocol converter is an integral part of PCS-


9700 substation automation system. It is used to establish
Functions
reliable and flexible communication links between IEDs and the • Universal protocol converter
workstation. The RCS-9794A/B is a highly reliable, fully non-blocking
intelligent protocol converter, which supports interworking
As a powerful and multifunctional communication and data between a wide range of protocols.
storage piece of equipment, the RCS-9794A/B builds a bridge
between workstation and IEDs using a variety of communication • Linking protection equipment and other IEDs to substation
protocols from diverse venders. With its modular configuration, it automation system
is flexible, allowing for the addition of new protocols. The device The RCS-9794 can send data from protective relays and
is fully compliant with IEC61850 communication protocol. RCS- other IEDs to SAS. It also can send the control commands
9794A can be used independently. In contrast, RCS-9794B from SAS to local bay units.
adopts duplicated scheme with two RCS-9794A units to realize
HOT-STANDBY or Dual- HOT running mode. • Linking protection equipment and other IEDs to remote
terminal units
The RCS-9794 can send data from protective relays and
other IEDs to RTUs. It can also send the remote commands
from the remote control center to local bay units.
Basic Communication Protocol
• Inspection and communication status monitoring.
• Upward: IEC 61850, IEC 60870-5-103 The RCS-9794 can inspect and monitor the communication
• Downward: IEC 60870-5-101, IEC 60870-5-103, IEC 61850- status of various types of equipment. If a connection or a
5-104, MODBUS, CDT, DNP 3.0 (serial port). disconnection occurs, the RCS-9794 will send a change-of-
• NR Electric can customize new protocols for specific state message to a station-level device, such as a local HMI
applications. or RTU.

• Clock synchronization and system time unification


The RCS-9794 can receive Pulses Per Second (PPS) and
timing signals from a GPS device. It also synchronizes its
clock with the GPS device and sends timing messages to all
linked equipment.

Read more on the web


www.nrelect.com 177
NR Electric Co., Ltd.

• Information synthesis and transmission • Embedded multiple processor architecture.All processors


According to engineering requirements, the RCS-9794 can are mutually independent and run parallel to each other.
consolidateseveral signals into one signal, and send this Moreover, the equipment can equalizeworkloads among
synthetic signal to the user appointed control center. theprocessors. This way, it exploits the full benefitsof the
distributed multiprocessor system’s parallel processing
• Self-diagnosis ability.
When in operating mode, the RCS-9794 continuously checks
for any hardware or software faults. • Configurable communication interfaces.

• Hardware time synchronization (pulse per second (PPS))

• Various communication interfaces can be flexible selected

Features according to engineering requirements. Serial ports, copper


Ethernet ports, fiber serial ports and fiber Ethernet ports can
• Various communication protocols can be selected flexibly for be selected.
individualcommunication ports,
• Data marshalling and distribution
• Suitable for installation in cubicles.
• Continuous self-monitoring
• Supporting a dual machine system configuration with the
merit of absolute electrical independence. • Continuous supervision of connected devices

• D u a l E t h e r n e t c o m m u n i c a t i o n i s u s e d f o r u p w a r d • Powerful and friendly configuration tools and debugging tools


communication with local HMI or RTUs at the station level to
• Standard device functions (e.g. general alarm, general fault
ensure the reliability of all upward communication.
signal, communication monitoring, etc.)

Technical Data
Power Supply
Rated Voltage (Un) 110V, 125Vdc, 220V, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11
Per IEC 61000-4-11:2004, IEC 60255-11:2008
Voltage dips and voltage short interruptions 20ms for interruption without de-energizing, dips 60% of Un without reset
up to 100ms
Burden <40W

Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×177.0×291(unit: mm)
Trepanning dimensions 450.0×179.0, M6 screw
Mounting Way Flush mounted
Front side: IP51
Protection class Rear side, connection terminals: IP20
Other Sides: IP30

Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible

178 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

Communication Interfaces
Communication medium Parameters
Serial Interfaces
Baud rate 300bits/s ~ 38400bits/s
Copper Transmission distance < 1000m@4800bps
Safety level Isolation to ELV level
Baud rate 300bits/s ~ 38400bits/s
RS-232/422/485 Optical Fiber Type Multi-mode
Connector type ST
Fiber
Wavelength 850nm
Transmission distance ≤ 2000m
Safety level Isolation to ELV level
Baud rate 9600bits/s
Copper
Safety level Isolation to ELV level
Connector type 9600bits/s
Optical Fiber Type Multi-mode
LonWorks
Connector type ST
Fiber
Wavelength 850nm
Transmission distance ≤ 2000m
Safety level Isolation to ELV level
Ethernet Interfaces
Connector type RJ-45
Transmission Rate 100Mbits/s
Copper Ethernet Ports) Transmission standard 100BASE-TX
Transmission distance < 100m
Safety level Isolation to ELV level
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Fiber Ethernet Ports Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 2000m
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
Transmission distance < 500m
RS-485 (EIA)
Timing standard PPS
Safety level Isolation to ELV level

Type Test
Environmental Tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005

Mechanical Tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I

Read more on the web


www.nrelect.com 179
NR Electric Co., Ltd.

Electrical Tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC

Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
- Radiated amplitude-modulatedSpot frequency 10V/m(rms), f=80…1000MHz
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008

Surge immunity test Power supply, AC input, I/O port: class IV, 1.2/50us
Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150
kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150
kHz~80MHz
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m

IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting

180 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

PCS-9882
Ethernet Switch

The PCS-9882 series switches can be used in substation switches support up to twenty-four 10/100Mbps electrical
automation system (SAS), networked control system (NCS) and Ethernetports and four 1000Mbps Ethernet ports.The fiber ports
distributed control systems (DCS). They can also be used in adopt SFP sockets, which support hot plugging.
power plants, industrial control systems, etc.
The following table shows the sub types of PCS-9882.The
PCS-9882 series switches provide 1000Mbps Ethernet ports number and type of the fiber ports are different in each sub type
with higher data transmission rates to meetthe increasing in order to meet various requirements.
requirements of the device communication.PCS-9882 series

Type Communication Ports Maximum Power Supply


1000Mbpsfiber ports 100Mbpsfiber ports 10/100Mbps electrical ports
PCS-9882AD 0~4 0~2 22~24 2
PCS-9882BD 0~2 0~16 0 2
PCS-9882ED 0 0~12 12 2
PCS-9882PD 0~4 0~4 24 2
PCS-9882QD 0~4 0~18 0 2

Functions
Ethernet Switch
• Provide 10/100Mbps self-adaptiveelectrical Ethernet • The 1000Mbps fiber ports of this device adopt SFP socket.
ports. The electrical Ethernet ports comply with 10BASE- The SFP transceiver complies with IEEE802.3 1000BASE-
T/100BASE-TX standardsThey are self-adaptive for SX 1000Mbps fiber Ethernet (1.25GBd) standardscan be
crossover and straight-through network cable. MDI/MDIX plugged into the 1000Mbps SFP socket of this device.
automatic identification is supported.
• Both the 100Mbps SFP socket and the 100Mbps SFP device
• The 100Mbps fiber ports of this device adopt SFP socket. socket support hot plugging.
The SFP transceiver complies with IEEE802.3 100BASE-
• The switching mode adopts non-blocking store and forward.
FX fiber Ethernet standards andcan be plugged into the
100Mbps SFP socket of this device. • Support IEEE802.3x Flow Control.

Read more on the web


www.nrelect.com 181
NR Electric Co., Ltd.

Flow Control Multicast Management


• Network storm protection: • Supports VLAN multicast based on IEEE802.1Q
The upper rate limit to forward broadcasting/multicasting/
• Supports static multicast management based on MAC address
addressing-failure messages is configurable.
• Supports GMRP dynamic multicast management
• Port rate Limiting:
• Note!GMRP is the abbreviation of “GARP Multicast
The message forwarding rate and burst rate of each port is
Registration Protocol”.
configurable.
• Supports IGMP snooping dynamic multicast management.
• Port mirror function:
The user can designate a specific port to monitor the
inflow/outflow data from the other ports.
Port Security
• Provides 3 port security states:
• Link aggregation:
-- None;
Supports link aggregation based on port, MAC address,
-- Static MAC address;
etc.
-- 802.1X.

• QoS control: • Supports network security protocols based on SSL/SSH.


Supports message priority control based on IEEE
• Supportsquantitative limitation on MAC address learning.
802.1pstandards; it also supports strict priority strategy and
weighted priority strategy. • Supports Telnet functionsenable and disable.

• Free of DoS(Denial-of-Service) attacks.


VLAN
• Support VLAN based on port • Supports security log and operation log.

• Support VLAN based on MAC address

• SupportVLAN based on protocol


File Management
• Support VLAN based on IEEE 802.1Q • Supports offline modification functions of the switch
configuration file.
• Support overlapped VLAN configuration
• Supports switch configuration file upload and download.
• Support VLAN tag insertion, modification or deletion
• SupportsPC download functions of switch log and event file.
• Support GARP VLAN registration protocol.

Note!
GARP is the abbreviation of “Generic Attribute Registration Management Method
Protocol”. • Supports WEB Server, Telnet and CLI.

• Supports simple network management protocol SNMPV1/


V2C/V3.
Ring Network
• Support STP (802.1D) and RSTP (802.1w), fast switch to • SupportsRMON Management
backup linksin case of communication link failure.
• Provides an alarm signal output contact to indicate any
• Supports“NR Electric-Ring” private ring network protocol with abnormity of the device.
a fast ring network recovery speed.
• Provides a block signal output contact to indicate device
• Supports the dedicated ring network protocol, able to blocking.
minimize network storms when cooperating with a common
• Supports IP conflict detection.
Ethernet switch (i.e.: the Ethernet switch unable to deal with
network storm).

• Supports MRP ring protocol.

182 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

Features
All PCS-9882 series switches adopt a high-performance • Optimized RSTP protocol is adopted. The restoration time of
switch chip and excellent industrial design to keep line speed the device is less than 1.2 ms per hop. A leading international
forwarding under full-duplex and full-rate operation of all the landmark.
ports. The design and manufacturing of the device has fully
considersvarious adverse conditions and interference factors • The processing capacity guarantees report handling at an
in industrial applications to ensure reliable data transmission average speed between 64-1518bytes without losing any
under tough environments. packages.

• This device is suitable for application according to IEC61850 • VLAN, traffic prioritization, RSTP, port security, GMRP/GVRP,
and indigital substation. IGMP applications are supported to meets the process level
requirements in intelligent substations.
• Patent protected advanced heat emission technology
incorporated to the device in order to ensure excellent heat • Provides port security methods (based on static MAC
emission performance. This device can perform in a range address or based on 802.1X) to guarantee securityin linking
of temperatures, from-40°C~ +85°C. Furthermore, it does so of IEDs in substations.
stably and reliably.
• Network security protocol based on SSL/SSH is supported,
• The device adopts the following advanced technologies: so as to ensure safe access control.
totally enclosed chassis, partitioned grounding connection,
anti-interference power supply, printed circuit board • Static multicast management is supported. In this way,
(abbreviated PCB) division by voltage level, cable transparent and reliable flow control oflinkied IEDs to the
shielding. Therefore, no package loss occur under strong device is ensured.
electromagnetic interferences (abbreviated EMI).
• This device is designed as an industrial management
• Compact field parallel processing technology is incorporated Ethernet switch with abundant functions (e.g.: port flow
into this device to ensure excellent performance. control, network storm limitation, port mirroring, SNMP,
RMON, WEB, port trunking, SNTP clock synchronization).
• Save and transfer processes occur in less that 2μs due to
the 100 Mbps ports. • In case of short power supply interruptions, the device can
still work up to 500ms.
• Process time of save and transfer at 1000Mbps ports is less
than 1μs. • Several 1000Mbps cascading fiber ports are provided to
improve the cascading performance.
• Supports IEC61850 protocol modeling, the user can monitor
the device with the IEC61850 protocol. • Dual power supply technology based on load balance is
supported. Both AC and DC power supplies can be applied
to this device.

Read more on the web


www.nrelect.com 183
NR Electric Co., Ltd.

Technical Data
AC Power Supply
Standard IEC 61000-4-11:2004
Rated voltage 110Vac/220Vac
Operating range 88~264Vac
PCS-9882AD: <14W
Burden (No load) PCS-9882BD: <13W
PCS-9882ED: <14W

PCS-9882AD: <20W
Burden (Full load) PCS-9882BD: <34W
PCS-9882ED: <28W

DC Power Supply
Standard GB/T 17626.29-2006(idt IEC 61000-4-29:2000).

3 options available:
110Vdc/125Vdc/220Vdc/250Vdc;
Rated voltage
48Vdc;
24Vdc.

88~300Vdc (Rated voltage is 110Vdc/125Vdc/220Vdc/250Vdc) ;


Operating range 36~72Vdc (Rated voltage is 48Vdc).
16~36Vdc (Rated voltage is 24Vdc)

Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage


PCS-9882AD: <10W
Burden (No load) PCS-9882BD: <9W
PCS-9882ED: <10W

PCS-9882AD: <16W
Burden (Full load) PCS-9882BD: <30W
PCS-9882ED: <24W

Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×44.4mm×266.0mm(1U)
Mounting Way Flush mounted
Trepanning dimensions (W×H) 450.0mm×44.45mm, M6 screw
Chassis color Silver grey
Weight per device Approx. 3.5kg
Chassismaterial Aluminumalloy
Location of terminal Rear panel of the device
Device structure Plug-in modular type @ rear side, integrated frontplate
Protection class
Standard IEC 60225-1:2009
Front side IP40, up to IP51(With cover)
Other sides IP50
Rear side, connection terminals IP30

Ambient Temperature and Humidity


IEC 60255-1:2009;
Standard
IEEE1613:2007
Operating temperature -40°C to +85°C
Transport and storage temperature range -40°C to +85°C
Permissible humidity 5%-95%, without condensation
Pollution degree 2
Altitude <3000m

184 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

Communication Interfaces
Communication Standards IEEE 802.3, IEEE 802.3u, IEEE 802.3ab, IEEE802.3z, IEEE802.3x
100Mbits/s Ethernet Port
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Safety level Isolation to ELV level
100Mbits/s Optical Fiber Port
Characteristic Glass optical fiber
Connector type LC
Transmission standard 100Base-FX
50/125μm multimode fiber
Fiber type 62.5/125μm multimode fiber
9/125μm single mode fiber
Multi mode: <2km
Transmission distance
Single mode: <40km
1000Mbits/s Optical Fiber Port
Characteristic Glass optical fiber
Connector type LC
Transmission standard 1000Base-SX
50/125μm multimode fiber
Fiber type 62.5/125μm multimode fiber
9/125μm single mode fiber
Multi mode: <500m
Single mode: <10km
Transmission distance
If procured by users themselves, the transmission distance is subject to the SFP transceiver
module.

Type Test
Environmental Tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005

Mechanical Tests
IEC60870-2-2:1996 Class Cm,
Vibration
IEEE1613:2007
Shock IEC60870-2-2:1996 Class Cm

Electrical Tests
IEEE1613:2007, Ur <50V then 500 Vrms
Dielectric tests
51<Ur <250V then 2000 Vrms

IEC60255-5:2000, test voltage: 5kV


Impulse voltage tests
IEEE1613:2007, 5kV
Overvoltage category III
Insulation resistance measurements IEC60255-5:2000, Isolation resistance >100MΩ@500VDC

Read more on the web


www.nrelect.com 185
NR Electric Co., Ltd.

Electromagnetic Compatibility
IEC 61000-4-18
Damped oscillatory wave immunity test Common mode: class III ±2.5kV
Differential mode: class III ±1.0kV
IEC61000-4-2
Electrostatic discharge test For contact discharge: class IV, ±8kV
For air discharge: class IV, ±15kV
IEC61000-4-3

Radio frequency interference tests Radiated amplitude-modulated


f=80~1000MHz, class III, AM 80%, 1kHz,10V/m (un-modulated)
f=800~960MHz and 1400~2000MHz, class III, AM 80%, 1kHz,10V/m (un-modulated)

IEC61000-4-4
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 5kHz or 100kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHzor 100kHz, 5/50ns
IEC61000-4-5

Surge immunity test Power supply, AC input, I/O port: class IV,1.2/50μs
Common mode: ±4kV
Differential mode: ±2kV
IEC61000-4-6

Conducted RF Electromagnetic Disturbance Power supply, AC, I/O, Comm. Terminal:Class III,
0.15~80MHz AM 80%
1kHz 10V (un-modulated)
IEC61000-4-8
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
IEC61000-4-9
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC61000-4-10
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m

Auxiliary AC power supply performance Per IEC 61000-4-11:2004,


- Voltage dips dips to 40% of rated voltage without reset up to 12 cycles,
dips to 70% of rated voltage without reset up to 30 cycles,
dips to 80% of rated voltage without reset up to 300 cycles.

- Voltage short interruptions 500ms for interruption without rebooting(only for 220Vac),
60ms for interruption without rebooting(only for 110Vac).

Auxiliary DC power supply performance Per IEC 61000-4-29:2000,


- Voltage dips Up to 100ms for dips to 40% of rated voltage without reset

- Voltage short interruptions 100ms for interruption without rebooting.

186 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

RCS-9785C/D
GPS Synchronization Clock

The RCS-9785C/D is a GPS Synchronized Unit with abuiltin • Various output interfaces forthe time signals
GPS receiver module. It receives timing messages through a The RCS-9785C/D can provide electrical (including RS-
built-in GPS receiver module. Alternatively, it receives IRIG-B 232/RS- 485, TTL, and AC modulation) or optical output
standardized timing code through one of the two input channels, timing signals. The timing signals supports IRIG-B, PPS,
decodes and converts the timing code, and then outputs such PPM, PPH, etc.
timing signals to the whole station. Output timing signals can
be IRIG-B signals, pulse per second (PPS) signals, pulse • Application for large system
per minute (PPM), pulse per hour (PPH) signals and timing The device is equipped with enough ports for output. The
messages. It also can provide Ethernet clock synchronization RCS- 9785C/D can be used to multiply time synchronizing
services (CSS) for bay units. The Ethernet CSS can work in the pulses to meet demand if required.
dual Ethernet mode (RJ45 over 100BASE-TX).Multi-business
acquisition simultaneous, access BCU, protection, PMU, meter, • High reliability
online monitoring device and among other advanced functions. The use of high-integration circuits and modular design
technology in the RCS-9785C/D enhances the reliability of
the device.

Features
• Highly accurate time signal output
-- The device is precise with a lag time of ±1μs for IRIG-B/
PPS/PPM/PPH time signals (excluding the propagation
delay time on the cable). The pulse front edges of these
time signals are less than 50ns.

-- The inaccuracies of IRIG-B/PPS/PPM/PPH output signals


for RS- 485 and TTL are ≤100ns.

-- The inaccuracies of IRIG-B/PPS/PPM/PPH output signals


foroptic-coupled dry (potential-free) contacts are ≤3μs.

Read more on the web


www.nrelect.com 187
NR Electric Co., Ltd.

Technical Data
Power Supply
Rated Voltage (Un) 110V/125Vdc, 220V/250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:1979
Burden <40W

Binary Outputs
Item Signal contact
Output mode Potential free contact
Max system voltage 380Vac, 250Vdc
Test voltage across open contact 1000V RMS for 1min
Continuous carry 8.0A
0.4A resistance
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms)
Short duration current 50A for 200ms
Pickup time 5ms/10ms
Drop-off time <8ms
Bounce time 1ms

Mechanical Specifications
Enclosure dimension (W×H×D) 482.6×177.0×291.0(unit: mm)
Trepanning dimension (W×H) 450.0×179.0, (unit: mm), M6 screw
Mounting Flush mounted
Front side: IP51
Protection class(per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30

Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible

Communication Interfaces
Communication medium Parameters
Ports to Transmit Clock Synchronization Signals
Port number 7 per module
Connector type RJ45
Transmission Rate 100Mbps
Ethernet Transmission standard 10Base-T/100Base-TX
Transmission distance < 100m
Protocol SNTP
Safety level Isolation to ELV level
Port number 7 per module
RS-232 Transmission distance <30m
Safety level Isolation to ELV level
Port number 7 per module
Maximal capacity 32
RS-485 (EIA)
Transmission distance <500m
Safety level Isolation to ELV level
Port number 8 per module
Operating voltage ≤ 300Vdc
Optic-Coupled Dry Contact Operating current ≤ 60mA
Transmission distance < 200m
Safety level Isolation to ELV level

192 Read more on the web


www.nrelect.com
NR Electric Co., Ltd.

Port number 8 per module


Connector type ST
Fiber type 62.6/125 μm for multi-mode
Wave length 820nm
The optical fiber has light in it when the channel
is idle.
Transmission mode Or:
The optical fiber has no light in it when the
channel is idle
Transmission distance < 2000m
Safety level Isolation to ELV level
Port number 8 per module
Output voltage 0 - 5V
TTL Port Output impedance 50Ω
Transmission distance <100m
Safety level Isolation to ELV level
Ports to Receive Clock Synchronization Signals
RS-485 (EIA) Port number 2
Synchronization Standard IRIG-B
Safety level Isolation to ELV level
Port number 2
TTL Port Synchronization Standard IRIG-B
Safety level Isolation to ELV level
Port number 2
Connector type ST
Fiber type 62.6/125 μm for multi-mode
Wave length 820nm
The optical fiber has light in it when the channel
Optical Fiber Port is idle.
Transmission mode Or:
The optical fiber has no light in it when the
channel is idle.
Synchronization Standard IRIG-B
Safety level Isolation to ELV level

Type Test
Environmental Tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005

Mechanical Tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I

Electrical Tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC

Read more on the web


www.nrelect.com 193
NR Electric Co., Ltd.

Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test
Common mode: 4kV
Differential mode: 2kV
Conducted RF Electromagnetic Disturbance Per IEC 60255-22-6:2001
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150
kHz~80MHz
Power Frequency Magnetic Field Immunity Per IEC 61000-4-8:2001
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150
kHz~80MHz
Pulse Magnetic Field Immunity Per IEC 61000-4-9:2001
class V, 6.4/16μs, 1000A/m for 3s
Damped oscillatory magnetic field immunity IEC 61000-4-10:2001
class V, 100kHz & 1MHz–100A/m

IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting

194 Read more on the web


www.nrelect.com