ABB Feeder Protection and Control

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Relion ® 605 series

Feeder protection and control /


Overcurrent protection / Motor protection
and control
REF601 / REJ601 / REM601
Optimized solution for protection and
Control of Utility and Industrial installation
REF601/REJ601 and REM601 are members of ABB’s Ease of use
Relion® protection and control product family and its 605 The pre-configured functionality of relay facilitates easy and fast
series. These relays provide an optimised composition of commissioning of switchgear.
protection, monitoring and control functionality in one unit,
with the best performance and usability in its class. Three dedicated and five configurable LEDs indicate the status
of relay and protection functions while the LCD displays meas-
The relay REF601/REJ601 offers various application urements, settings, events and recorded data. The relay can
configurations for Feeder protection and control while be set-up and configured entirely from the local HMI or with
REM601 offers application configurations for Motor PCM600.
protection and control.
A single wide range auxiliary supply eliminates the need for
Protection and control ordering variance. The relays also boast a press-fit mounting
REF601/REJ601 offer three-stage overcurrent and two-stage design for effortless installations on panels. Configurable inputs
ground fault protection functions. The low-set stages for over- and outputs are included which can be easily altered by the
current and ground fault protection are equipped with selectable LHMI.
characteristics – Definite Time (DT) and Inverse Definite Mini-
mum Time (IDMT). The relay features standard IDMT charac- These relays incorporate detachable terminals with CT short-
teristics according IEC 61255-3 - Normal Inverse, Very Inverse, ing which aids in improving MTTR (Mean Time to Repair) thus
Extremely Inverse, Long-time Inverse. They also feature charac- further reducing downtime and improving productivity.
teristics according to ANSI C37.112 - Moderate Inverse, Normal
Inverse, Very Inverse, Extremely Inverse. The relay has a special Supervision
characteristic RI Inverse (RI) for better coordination with the rest To ensure continuous availability of protection, self-supervi-
of the network. Additionally the relays also support two setting sion of the relay hardware and software is incorporated. The
groups. REF601/REJ601 and REM601 also include an integrated
trip-circuit monitoring function which monitors the external trip
Thermal overload protection for feeder, cable and transformer, signal path. A built-in test mode which enables users to test the
negative phase sequence protection phase discontinuity pro- relay HMI, protection functions, and binary outputs.
tection and circuit breaker failure protection are also offered. An
auto-reclose function for overhead line feeders is optional. The 605 series relays can store 100 events with time stamps at
a resolution of 1 ms. They can also store analog fault records
The REM601 offers protections for motors such as thermal for the last five trip events. This data is stored in non-volatile
overload protection, short circuit protection, startup supervision, memory.
loss-of-phase protection, negative phase sequence protection,
ground fault protection, undercurrent protection and circuit The optional communication card extends local monitoring and
breaker failure protection. An emergency restart feature allows control facility of the HMI to remote automation systems over
motor start up even when start inhibit is activated. MODBUS RTU / IEC 60870-5-103 protocol.

The residual current for CT configured relays is derived from the Sensor support
phase currents. When applicable the zero sequence CT can be These relays support both conventional CTs and Rogowski cur-
used for measuring residual current especially when sensitive rent sensors. The sensor option helps to obtain equipment size
ground fault protection is required. reduction, performance improvement and better standardization
in compact MV switchgear.
The REF601 integrates basic control functionality. Apart from
display of data and parameter settings, the user friendly local
human-machine interface (LHMI) supports control of one circuit
breaker with dedicated control push buttons. The LHMI display
has built in support for multiple languages.

All three relays are equipped with a three level, role-based user
authentication system with individual passwords for the opera-
tor, engineer and administrator levels.

2 REF601 / REJ601 / REM601 | Descriptive bulletin


Feeder protection and control / Feeder
protection, REF601/REJ601

REF601/REJ601 is a dedicated feeder protection and REF601/REJ601 provides main protection for overhead lines
control relay intended for the protection and control and cable feeders of distribution and sub-distribution networks.
of utility and industrial power system, in primary and Further, inrush current stabilization function allows the relay to
secondary distribution networks. be used as main protection of distribution transformers.

The compact size of REF601 makes it suitable for even The relay with application configuration B offers, non-directional
mounting on ABB circuit breaker VD4 and HD4. over current and ground fault protection.

REF601/REJ601 is available in three alternative application The application configuration C additionally offers thermal
configurations. overload protection for feeders, cables and transformers, phase
discontinuity protection and circuit breaker failure protection.

The application configuration D provides highest functionality


with incorporation of negative phase sequence protection and
multi shot auto-reclose functionality making relay suitable for
overhead line feeders.

Functional overview of the application configuration of REF601 / REJ601

REF601/REJ601 Protection
REF601/
FEEDER PROTECTION AND CONTROL/OVERCURRENT PROTECTION
REJ601
a)
51P 50P-1 50P-2 49
LOCAL HMI ADDITIONAL FUNCTIONS
3 (3I>) (3I>>) (3I>>>) (3lth)

- Sequence of events
a)
46
a)
46PD
a)
50BF 68
- Analog fault data
(I2>) (I2/I1>) (3I>BF) (3I2F>) - IED self-supervision
- User management
- Two seng groups
*

a)
SUPERVISION COMMUNICATION
51N 50N 50NBF
(I0>) (I0>>) (3I0>BF)
Protocols:
- MODBUS RTU
TCM
(TCS) - IEC 60870-5-103

Interfaces:
- Serial: RS-485, 2 wire
52 94/86
Master Trip Lockout Relay

CONTROL MEASUREMENT

- Ability to control a single circuit - Phase current


breaker with local HMI - Neutral/Ground current
- Circuit breaker control is standard - Negave phase sequence current
on REF601 - Thermal level
- Operaon counter
*OPTIONAL ZERO SEQUENCE CT CONNECTION - Motor running me
b)
79

~ Analog Interface:
(OI)
REF601/REJ601 Protection
1) Convenonal CT version: 4 CTs
~~ ~~ 2) Sensor version: 3 sensor inputs, 1
CT input
a)
51N 50N 50NBF
(I0>) (I0>>) (3I0>BF)
REMARKS a) Available with applicaon
52 configuraon “C” and “D”

~ ~
*Oponal zero sequence CT is b) Available with applicaon

~
available by configuraon configuraon “D”

Descriptive bulletin | REF601 / REJ601 / REM601 3


Motor protection and control / Motor
protection, REM601

REM601 is a dedicated motor protection and control relay REM601 provides motor protection during starting and running
intended for the protection and control of asynchronous condition. Application configuration B offers thermal overload
motors in manufacturing and process industry. The relay protection, short-circuit protection, startup supervision, negative
can be used for three phase motors in all conventional phase sequence protection and loss-of-phase protection. The
contactor or circuit breaker controlled motor drives. relay also incorporates sensitive fault protection, undercurrent
protection and circuit ground breaker failure protection.
REM601 is available in two alternative application
configurations. The emergency restart feature helps to keep functionally critical
motors running by allowing motor start up even though start
inhibit is activated.

The application configuration C adds breaker control


functionality.

Functional overview of the application configuration of REM601

REM601 Protection
REM601 MOTOR PROTECTION AND CONTROL

49M 51P 50P-1 46R


3 (3θ>M)
(3θ>M) (3I>) (3I>>)
(3I>>) (I2>>)
(I2>>)
LOCAL HMI ADDITIONAL FUNCTIONS

46 46PD 14/48/66
14/48/66
- Sequence of events
(I2>) (I2/I1>) (Is22t>, n<)
(Is - Analog fault data
- IED self-supervision
- User management
50LR 37 50BF - Two seng groups
(I>>>)
(I>>>) (3I<) (3I>BF)
- Emergency restart
- Provision of speed switch input
*

SUPERVISION COMMUNICATION

Protocols:
51N 50N 50NBF
- MODBUS RTU
TCM
(I0>) (I0>>) (3I0>BF) (TCS) - IEC 60870-5-103

Interfaces:
- Serial: RS-485, 2 wire
94/86
52 Master Trip Lockout Relay

CONTROL MEASUREMENT

M - Ability to control a single circuit - Phase current


breaker with local HMI - Neutral/Ground current
- Circuit breaker control is available - Negave phase sequence current
with configuraon “C” - Thermal level
- Operaon counter
*OPTIONAL ZERO SEQUENCE CT CONNECTION - Motor running me

~ REM601 Protection Analog Interface:


1) Convenonal CT version: 4 CTs
~~ ~~ 2) Sensor version: 3 sensor inputs, 1
CT input
51N 50N 50NBF
(I0>) (I0>>) (3I0>BF)
REMARKS
52
~ ~
*Oponal zero sequence CT is available by configuraon

4 REF601 / REJ601 / REM601 | Descriptive bulletin


Standard configurations

REF601/REJ601 application configuration


Description Application configuration
Non-directional overcurrent and non-directional ground fault protection B
Non-directional overcurrent and non-directional ground fault protection, thermal overload protection for feeders, cable C
and transformers, phase-discontinuty protection
Non-directional overcurrent and non-directional ground fault protection, thermal overload protection for feeders, cable D
and transformers, phase-discontinuty protectiontion, negative phase-sequence
protection, auto recloser

REM601 application configuration


Description Application configuration
Motor protection without breaker control functionality B
Motor protection with breaker control functionality C

Supported functions, codes, and symbols


Included = •, Optional = - Function Name REJ601/ REJ601/ REF601 REM601 REM601
REF601 REF601
Function ANSI IEC B C D B C
Protection
Non-directional overcurrent protection, low-set stage 51P 3I> • • • • •
Non-directional overcurrent protection, high-set stage 50P-1 3I>> • • • • •
Non-directional overcurrent protection, instantanious stage 50P-2 3I>>> • • • - -
Ground fault protection, low-set stage 51N Io> • • • • •
Ground fault protection, high-set stage 50N Io>> • • • • •
Three-phase transformer inrush detector 68 3I2f> • • • - -
Three-phase thermal overload protection for feeders, 49 3Ith> - • • - -
cables, and distribution transformers
Three-phase thermal overload protection for motors 49M 3Ith> - - - • •
Phase discountinuty protection 46PD I2/I1> - • • - -
Phase discountinuty/single phasing protection for motor 46PD I2/I1> - - - • •
Negative sequence overcurrent protection 46 I2> - - • • •
Phase reversal protection 46R I2R> - - - • •
Under current protection 37 3I< - - - • •
Motor startup supervision, stalling protection with provision 51LRS/ Is t n<
2
- - - • •
of speed switch input, repetative start protection, restart 14/48/66
inhibit
Blocking/doubling during motor start up 68M - - - • •
Locked rotor protection 50-2 3I>>> - - - • •
Commulative startup time counter and restart inhibit 66 - - - • •
function
Circuit breaker failure protection 50BF/ 3I>BF/ - • • • •
50NBF Io>BF
Master trip 94/86 Master Trip • • • • •
Two setting groups • • • • •
Control (function not included on REJ601)
Breaker control functionality 52CB I <-> O CB • • • - •
Auto-reclosing, 4 shots 79 O -> I - - • - -
Emergency restart for motor ESTART ESTART - - - • •

Descriptive bulletin | REF601 / REJ601 / REM601 5


Standard configurations

Supported functions, codes, and symbols (continued)


Included = •, Optional = - Function Name REJ601/ REJ601/ REF601 REM601 REM601
REF601 REF601
Function ANSI IEC B C D B C
Condition monitoring
Trip circuit supervision TCM TCS • • • • •
Measurement
Three-phase current measurement 3I 3I • • • • •
Residual current measurement IN Io • • • • •
Negative phase sequence current I2 I2 - - • • •
Thermal level θ ϑ - • • • •
Operation counter - - - • • • •
Start-up time of latest motor startup - - - - - • •
Start-up current of latest motor startup - - - - - • •
Cumulative startup time counter - - - - - • •
Time to next possible motor startup - - - - - • •
Inputs/outputs
Analog inputs 4 / 3+1 1) 4 / 3+11) 4 / 3+11) 4 / 3+11) 4 / 3+11)
Binary inputs 4 4 4 4 4
Binary outputs 6 6 6 6 6
1)
Conventional CT version - support for conventional current transformer input, sensor version - support for three current sensors and one conventional Io input (1A).

6 REF601 / REJ601 / REM601 | Descriptive bulletin


Notes

Descriptive bulletin | REF601 / REJ601 / REM601 7