The residual current for CT configured relays is derived from the Sensor support
phase currents. When applicable the zero sequence CT can be These relays support both conventional CTs and Rogowski cur-
used for measuring residual current especially when sensitive rent sensors. The sensor option helps to obtain equipment size
ground fault protection is required. reduction, performance improvement and better standardization
in compact MV switchgear.
The REF601 integrates basic control functionality. Apart from
display of data and parameter settings, the user friendly local
human-machine interface (LHMI) supports control of one circuit
breaker with dedicated control push buttons. The LHMI display
has built in support for multiple languages.
All three relays are equipped with a three level, role-based user
authentication system with individual passwords for the opera-
tor, engineer and administrator levels.
REF601/REJ601 is a dedicated feeder protection and REF601/REJ601 provides main protection for overhead lines
control relay intended for the protection and control and cable feeders of distribution and sub-distribution networks.
of utility and industrial power system, in primary and Further, inrush current stabilization function allows the relay to
secondary distribution networks. be used as main protection of distribution transformers.
The compact size of REF601 makes it suitable for even The relay with application configuration B offers, non-directional
mounting on ABB circuit breaker VD4 and HD4. over current and ground fault protection.
REF601/REJ601 is available in three alternative application The application configuration C additionally offers thermal
configurations. overload protection for feeders, cables and transformers, phase
discontinuity protection and circuit breaker failure protection.
REF601/REJ601 Protection
REF601/
FEEDER PROTECTION AND CONTROL/OVERCURRENT PROTECTION
REJ601
a)
51P 50P-1 50P-2 49
LOCAL HMI ADDITIONAL FUNCTIONS
3 (3I>) (3I>>) (3I>>>) (3lth)
- Sequence of events
a)
46
a)
46PD
a)
50BF 68
- Analog fault data
(I2>) (I2/I1>) (3I>BF) (3I2F>) - IED self-supervision
- User management
- Two seng groups
*
a)
SUPERVISION COMMUNICATION
51N 50N 50NBF
(I0>) (I0>>) (3I0>BF)
Protocols:
- MODBUS RTU
TCM
(TCS) - IEC 60870-5-103
Interfaces:
- Serial: RS-485, 2 wire
52 94/86
Master Trip Lockout Relay
CONTROL MEASUREMENT
~ Analog Interface:
(OI)
REF601/REJ601 Protection
1) Convenonal CT version: 4 CTs
~~ ~~ 2) Sensor version: 3 sensor inputs, 1
CT input
a)
51N 50N 50NBF
(I0>) (I0>>) (3I0>BF)
REMARKS a) Available with applicaon
52 configuraon “C” and “D”
~ ~
*Oponal zero sequence CT is b) Available with applicaon
~
available by configuraon configuraon “D”
REM601 is a dedicated motor protection and control relay REM601 provides motor protection during starting and running
intended for the protection and control of asynchronous condition. Application configuration B offers thermal overload
motors in manufacturing and process industry. The relay protection, short-circuit protection, startup supervision, negative
can be used for three phase motors in all conventional phase sequence protection and loss-of-phase protection. The
contactor or circuit breaker controlled motor drives. relay also incorporates sensitive fault protection, undercurrent
protection and circuit ground breaker failure protection.
REM601 is available in two alternative application
configurations. The emergency restart feature helps to keep functionally critical
motors running by allowing motor start up even though start
inhibit is activated.
REM601 Protection
REM601 MOTOR PROTECTION AND CONTROL
46 46PD 14/48/66
14/48/66
- Sequence of events
(I2>) (I2/I1>) (Is22t>, n<)
(Is - Analog fault data
- IED self-supervision
- User management
50LR 37 50BF - Two seng groups
(I>>>)
(I>>>) (3I<) (3I>BF)
- Emergency restart
- Provision of speed switch input
*
SUPERVISION COMMUNICATION
Protocols:
51N 50N 50NBF
- MODBUS RTU
TCM
(I0>) (I0>>) (3I0>BF) (TCS) - IEC 60870-5-103
Interfaces:
- Serial: RS-485, 2 wire
94/86
52 Master Trip Lockout Relay
CONTROL MEASUREMENT