FMDS0402 PDF
FMDS0402 PDF
FMDS0402 PDF
Table of Contents
Page
2006-2013 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced,
stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.
4-2 Water Mist Systems
Page 2 FM Global Property Loss Prevention Data Sheets
1.0 SCOPE
This data sheet provides information on installation criteria for water mist systems. Water mist systems are
special protection systems presently FM Approved for protection of enclosures with specific hazards
containing limited amounts of ignitable liquids, and process equipment, such as:
combustion turbine(s)
industrial oil cookers
continuous wood board presses
machinery in enclosures
computer room subfloors
indoor transformers
wet benches in cleanrooms
light hazard occupancies.
Additional information concerning water mist system installation criteria is contained in NFPA 750, Water
Mist Fire Protection Systems.
The effectiveness of water mist must be proven by fire testing on a hazard of the same configuration and
general hazard type. Presently, there is no design procedure that would allow extrapolation of test results to
different hazards or different enclosure configurations.
1.1 Changes
July 2013. Deleted preaction water mist systems to provide consistency with equipment that is FM Approved.
2.1.1.4 Provide Detail Sheets containing the following information: (a) nozzle description; (b) hydraulic
reference point; (c) total flow and flow at each nozzle in gpm (l/min); (d) all pipe sizes; (e) pipe lengths; (f)
equivalent pipe lengths for fittings and devices; (g) friction loss in psi/ft (bars/m) of pipe; (h) elevation head in
psi (bars); (i) required pressure in psi (bars) at each reference point; (j) velocity pressure and normal pressure
if included in calculations; (k) system flushing locations; (l) other calculations necessary for design of the
water mist system.
2.1.1.5 Graph Sheet. Provide a graphic representation of the complete hydraulic calculation, including the
water supply curve and the water mist system demand.
2.1.1.6 Pneumatic calculation documentation (for systems using gas). Provide pneumatic calculation
summary sheets that include the following: (a) identification of location; (b) description of hazard; (c) total
gas volume required.
2.1.1.7 Detail sheets for pneumatic calculations: (a) nozzle description; (b) pneumatic reference points;
(c) gas flow rate and pressure at each nozzle; (d) the gas pressure to water pressure ratio at each nozzle;
(e) pipe size; (f) pipe length; (g) total pressure loss between reference points; (h) required pressure in psi
(bars) at each reference point.
2.1.1.8 Include a set of as-built installation drawings, drawn to scale, providing the configuration of the
detection, actuation, and control system.
2.1.1.9 Include the Operation and Maintenance Manuals for each piece of equipment or device of the water
mist system. Ensure the manuals include a complete step-by-step description of the functioning of abort
and maintenance switches, delay timers, and all interlocked components.
a) Water mist may be used as a special protection system when it is able to extinguish all of the fire
scenarios for the hazard protected and where the installation has a limited agent supply. Double the agent
quantity needed to extinguish the worse-case fire scenario or 10 min, whichever is greater. If the ignition
source could remain (for example, hot surfaces on a combustion turbine), ensure the agent supply is
adequate for the rundown time of the turbine or 10 min, whichever is greater. Specific exceptions to these
guidelines may be made in the applicable occupancy data sheet.
b) Water mist may be used as primary protection if the system has been tested for the hazard protected
and duration of agent supply is that required for automatic sprinkler protection (see appropriate data
sheet).
2.1.4.3 Provide a reserve supply, at least equal to the minimum requirement for the in-service supply, under
any of the following conditions:
a) Provide a connected reserve when two or more hazards are protected by a single supply. A manually
actuated main/reserve switch is normally provided at the control panel for this purpose.
b) Provide a connected reserve when a special protection system is the sole protection for valuable and
important occupancies, unless all of the following criteria are met:
i) Protection can be fully restored within 24 hours,
ii) occupancies are constantly attended, and
iii) written impairment procedures have been established.
c) Provide a reserve when the extinguishing agent cannot be replaced within 24 hours following system
operation. Reserve supplies are necessary to permit prompt restoration of the system after a discharge,
to minimize interruption of the process and the interval of impaired protection.
2.1.4.4 Provide water equivalent in quality to a potable water source. Supply systems that use nozzles with
nozzle waterway dimensions less than 50 microns with demineralized water.
2.1.4.5 Provide gas supply from a dedicated source. Where facility dedicated air supply is available that meets
the requirements in quantity, quality, pressure, and reliability, it may be used as a source of atomizing media.
Monitor plant air or nitrogen used for this purpose at the fire control panel for high and low pressure. Set
the low air or nitrogen alarm at least 50% above the availability of two full system discharge requirements.
2.1.4.6 Install a check valve or other means to prevent entrance of water into the atomizing medium.
2.1.4.7 Install a backflow preventer between the system and the connection to a potable water supply.
2.1.5.1 General
2.1.5.1.1 Clean containers prior to installation, so debris and other impurities do not enter the piping system
and plug nozzles. Flush connections to municipal or private water supplies. Continue flushing for a sufficient
time to ensure thorough cleaning. Ensure the minimum rate of flow is either the hydraulically calculated water
demand or the maximum flow rate available to the system under fire conditions.
2.1.5.1.2 Design containers to meet the requirements of the U.S. Department of Transportation or Transport
Canada, if used as shipping containers. Design, fabricate, inspect, certify, and stamp containers in accordance
with Section VIII of the ASME Boiler and Pressure Vessel Code if not used as shipping containers.
Note: Use equivalent codes within the country of origin.
2.1.5.1.3 Provide a pressure relief device on each pressurized container.
2.1.5.1.4 Ensure containers supplying the same manifold outlet are the same size and interchangeable.
2.1.5.1.5 Securely install storage containers and accessories to prevent container movement during
discharge.
2.1.5.1.6 Provide liquid level indicators for all liquid storage containers.
2.1.5.1.7 Install containers to facilitate inspection, testing, maintenance, and recharging.
2.1.6.12 Label water and gas piping for twin fluid systems.
2.1.7 Hangers
2.1.7.1 Support pipe 1 in. (2.5 cm) and larger in diameter with hangers as specified in Data Sheet 2-0,
Installation Guidelines for Automatic Sprinklers. Ensure smaller piping is as specified in the manufacturers
Design and Installation Manual.
2.1.7.2 Do not use power-driven fasteners to attach hangers to the building structure where systems are
required to be protected against earthquake.
2.1.8 Nozzles
2.1.8.1 Install nozzles within the minimum and maximum spacing criteria identified in the system FM Approval.
This includes nozzle spacing, height limitations, distance from walls, distance below ceilings, spacing under
pitched or curved surfaces, and distance from obstructions.
2.1.8.2 Ensure maximum and minimum operating pressurers at each nozzle are within the FM Approved
range.
2.1.8.3 Locate nozzles in accordance with the FM Approvals listing and manufacturers design and installation
manual for continuous or discontinuous obstructions, when present.
2.1.8.4 Use FM Approved guards, where needed, to prevent mechanical damage to nozzles so the
effectiveness of the nozzle will not be reduced.
2.1.8.5 Use FM Approved escutcheon plates where specified by the manufacturer.
2.1.8.6 Use ordinary temperature ratings for automatic nozzles. If in unventilated areas such as attics, use
intermediate-temperature rated nozzles. If located within 10 ft (3 m) of hot surfaces, such as exhaust pipes or
steam pipes, use high-temperature rated nozzles.
2.1.8.7 Provide corrosion-resistant materials or coatings where there are corrosive atmospheres.
2.1.8.8 Provide FM Approved frangible disks, blow-off caps, or other suitable devices for discharge nozzles
where clogging by external foreign materials is likely.
2.1.8.9 Keep a supply of spare, thermally activated nozzles in stock. The number of nozzles depends on
the size of the system.
2.1.9 Valves
2.1.9.3.2 Install PRVs when the supply pressure is higher than the design operating pressure of the water
mist system. Ensure PRVs are capable of providing a stable, regulated output at the rated flow capacity and
design set point over the full range of input pressures that will be experienced during discharge.
2.1.9.3.3 Ensure pressure set point adjustments on PRVs are tamper resistant, and the adjustment indicated
by a permanent marking.
2.1.11 Pumps
2.1.11.1 Provide FM Approved pumps sized to 120% of the required system water flow rate, at minimum
system operating pressure.
2.1.11.2 Start pumps automatically on system activation.
2.1.11.3 Provide pressure relief valves from discharge to supply side of piping for pumps capable of
over-pressurizing the system. Ensure the pressure rating does not exceed the working pressure of the piping
system.
2.1.11.4 Do not arrange pumps to take suction under lift.
2.1.11.5 Install the power supply for pump drivers in accordance with NFPA 20, Standard for the Installation
of Stationary Pumps for Fire Protection; NFPA 70, National Electrical Code, and the manufacturers
instructions.
2.1.11.6 Arrange power supplies so that disconnecting power to the facility during a fire will not disconnect
power to the circuit feeding the pump.
Include 10% of the water mist nozzles in the activated zone. If contamination of filters or strainers is found
on inspection, inspect all nozzles in the activated zone.
2.1.12.2.4 Clean or replace filters and strainers after each system operation due to fire.
2.1.13 Calculations
2.1.13.1 Use the Hazen-Williams calculation method for hydraulic calculations for low-pressure systems with
no additives. The Hazen-Williams method also can be used for intermediate- and high-pressure systems
having a minimum pipe size of 34 in. (20 mm) if the maximum flow velocity does not exceed 25 ft/s (7.6 m/s).
For copper and stainless steel piping or tubing, Hazen-Williams C values of 150 may be used.
2.1.13.2 Use the Darcy-Weisbach calculation method for hydraulic calculations for intermediate- and high-
pressure, single fluid, single-phase systems that cannot be calculated using the Hazen-Williams method (see
Chapter 6, NFPA 750, Standard on Water Mist Fire Protection).
2.1.13.3 Hydraulic calculations for twin fluid systems can be conducted as follows:
1. Determine water pressure required at the most remote nozzle using nozzle specifications supplied by
the manufacturer. Determine flow rates and pressure at each nozzle location.
2. Determine water pressure and flow rates at each nozzle from information provided by the nozzle
manufacturer.
3. Calculate the pneumatic piping system independently to verify the pipe sizes are adequate to provide
the required pressure and flow at each nozzle, and that the system is sized to provide the flow rate and
pressure needed.
2.2.1 Introduction
Use water mist systems FM Approved for LHO to protect non-storage and non-manufacturing occupancies
designated as Hazard Category 1 (HC-1) in Data Sheet 3-26, Fire Protection Water Demand for Nonstorage
Sprinklered Properties.
2.2.2.1 Limitations
2.2.2.1.1 Where systems are FM Approved for Light Hazard Occupancies (HC-1), the following limitations
apply from their FM Approvals listing:
Maximum enclosure area
Maximum ceiling height
Maximum nozzle spacing
Minimum water pressure
Maximum water pressure
Clearance from obstructions
Minimum fire-resistance rating of room walls: 30 minutes
The maximum room size limitation does not apply to corridors that can be protected by one row of nozzles.
2.2.2.1.2 Limit the maximum ceiling height to that specified by the FM Approvals Listing and listed
manufacturers design and installation manual.
2.2.2.1.3 Use water mist systems FM Approved for a Light Hazard Occupancy with an unrestricted maximum
enlosure area to protect large compartments.
2.2.2.1.4 Limit application of FM Approved systems to wet pipe systems. Do not use dry systems.
2.3.1 Introduction
Local application water mist systems are typically used for ignitable liquid hazards. Water mist is considered
a special protection system. An automatic sprinkler system is normally required for building protection.
2.3.4 Limitations
2.3.4.1 Limit the system to protection of the fluid tested. If the system has been tested using a specific ignitable
liquid, limit the system to protection of ignitable liquid fire hazards with equivalent or higher flash points.
2.3.4.2 Install using nozzle type, nozzle height, spacing, and angle of discharge as specified in the
manufacturers design and installation manual identified in the FM Approvals listing.
3.1 General
3.1.1 Design
No general design method is recognized for water mist protection systems. Performance objectives need
to be proven by fire test in the configuration and for the hazard and types of fire scenarios expected.
FM Approval testing for water mist systems involves the completion of a series of fire tests identified in a
fire test protocol, as well as reliability testing of the components that make up the water mist system. The test
protocol describes the fire tests needed to prove the water mist system is effective. The fire test specifies
the type of fuel in configuration(s) that would be most realistic for the hazard protected. Reliability testing
consists of testing all components of the system to verify they will function properly.
3.1.2 Obstructions
Obstructions will affect the performance of water mist protection and vary according to the type of spray
technology and the type of application. Water mist nozzles have a wide range of projection distances, spray
velocity and spray patterns.
Spray from nozzles that impinge too close on obstructions will not fully atomize, and a portion of the water
mass will be removed from suspension. Such losses diminish the extinguishing effectiveness of total flooding
or local application systems. For combustibles where prewtting is an important factor in preventing fire
growth, obstructions to spray development prevent wetting of unburned materials and diminish the
performance of the water mist system.
Additional nozzles can be required to ensure complete water mist fire protection when obstructions and
maximum coverage distances to obstructions are not evaluated as part of the FM Approval.
Also, do not extrapolate from a 10,000 ft3 (283 m3) compartment to a 5,000 ft3 (142 m3) compartment using
12 the number of nozzles and 12 the agent. Use the same number of nozzles and same amount of agent
as for the tested system unless the system has been tested for smaller compartments.
3. Do not make a judgement that the system will extinguish a fire based on a discharge test. A discharge
test is important to verify a system will operate properly. However, a successful discharge test does not
guarantee the system will extinguish a fire. For example, nozzles were installed at 20 ft (6.1 m) elevation
above a simulated diesel generator in the 60 ft (18.3 m) high section of the FM Global Research Campus.
The area was not enclosed. When the system was activated, the diesel generator was completely enclosed
by the water mist. When a 6 MW fire was started on the diesel generator and the system was activated it
had no apparent effect on the fire. A ceiling was constructed over the nozzles. Again there was no apparent
affect on fire intensity. When the sides were enclosed some test fires could be extinguished.
4. Do not assume that one successful fire test is proof that a water mist system will adequately protect the
hazard. Typically, several tests have to be conducted to characterize the hazard. The combustion turbine
testing includes shielded spray and pool fires and spray fires in the open.
5. Conduct tests in as realistic a manner as possible. Effects that adversely affect water mist systems are
simulated during the test. For example, if ventilation will not be shut off in a fire, the tests are conducted with
ventilation in operation.
3.3.2 Cleanrooms
Fire testing is conducted on a wet bench in a simulated cleanroom. One test series simulates a fire within
the sub-surface area of the wet bench. Another test series simulates a fire on the surface of the wet bench.
Fire testing conducted below the surface is conducted in an enclosure 2.5 7.5 2 ft (0.8 2.3 0.6 m)
high. Fire tests involve burning pools of polypropylene beads and ignitable liquid in pans ranging in diameter
from 4 to 12 in. (10.1 to 30.5 cm). The pan is shielded from direct impingement from the water mist nozzles
to simulate obstructions in the plenum.
Tests also are conducted on the surface of the wet bench. The surface is 2.5 ft (0.8 m) 7.5 ft (2.3 m) long.
Tests are conducted with ventilation rates of up to 140 ft3/min/linear ft (13 m3/min/linear m) of bench.
The tests require fire extinguishment within 1 minute.
pocket is 3.3 ft (1 m) 12 ft (3.6 m) long. The pockets are open at both ends. The frame walls are partial
height walls. It is anticipated that a pool oil fire and/or a spray oil fire could occur in this area. The fire would
expose the frame walls (steel) of the press and the platens used to heat the stainless steel belt. Pool and/or
spray fires could occur in this area involving either hydraulic fluid or thermal oil. The objective is to determine
whether the water mist system will extinguish or control temperature from pool and spray fires. Temperature
control is considered to be providing adequate cooling to prevent damage to the press frame.
1. Heat tunnel tests. The heat tunnel runs the length of the press. It contains the stainless steel belt used
to form the board. The fire exposure is oil that has dripped off the belt and collected on one side of the bottom
of the tunnel (tunnel floor is sloped). There also is a concern that rapid cooling will damage the belt. Testing
is done using a 16.4 ft (5 m) long mock-up of the tunnel with a stainless steel belt in the tunnel.
a) One test is conducted in which the belt and the enclosure are heated to normal operating temperature
and the water mist system is activated to simulate accidental activation. Belt samples are taken for
metallurgical analysis.
b) A second test is conducted with fuel oil in the trough. Fuel oil is ignited and allowed to burn until the
channel is fully involved. The water mist system is actuated. The time to extinguish the fire is determined.
Belt samples are taken for metallurgical analysis. Tests such as tensile strength, measurements of the
width and length of the belt section tested, and bendability testing are done before and after fire testing
to identify changes in belt properties.
4.0 REFERENCES
4.1 FM Global
Data Sheet 2-8, Earthquake Protection for Water-Based Fire Protection Systems
Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers
Data Sheet 3-26, Fire Protection Water Demand for Nonstorage Sprinklered Properties
Data Sheet 4-0, Special Protection Systems
Data Sheet 5-48, Automatic Fire Detection
4.3 Others
ASME, Boiler and Pressure Vessel Code, Section VIII, Rules for Construction of Pressure Vessels.
ANSI B31.1 Power Piping Code.
ANSI, National Electrical Safety Code.
U.S. Dept of Transportation, Title 49, Code of Federal Regulations, Parts 171 to 190, Sections 178.36 and
178.37
Intermediate Pressure System: A water mist system where the distribution system piping is exposed to
pressures greater than 175 psi (12.1 bar) but less than 500 psi (34.5 bar).
Local application systems: A water mist system arranged to discharge on the protected hazard and within
the containment or confinement area around the hazard.
Low Pressure System: A water mist system where the distribution system piping is exposed to pressures
of 175 psi (12.1 bar) or less.
LPCD: Loss Prevention Certification Board, UK.
Machinery Space: These areas include internal combustion engines, generators, transformers, oil pumps,
oil reservoirs, fuel filters, gear boxes, drive shafts, lubrication skids, and other similar equipment using liquid
hydrocarbon fuel and/or hydraulic, heat transfer, and lubrication fluids, and enclosures with incidental luse
of ignitable liquids of not more than two 55 gal (208 L) drums arranged for dispensing with safety bungs.
Primary protection: Water mist may be considered primary protection if the system has been tested for the
hazard protected, and the duration of the agent supply is equivalent to that required for the same hazard
protected by an automatic sprinkler system.
Single Fluid System: A water mist system utilizing a single piping system to supply each nozzle. Nozzles
may be supplied with water or a mixture of gas and water.
Special protection systems: Water mist is considered a special protection system when it is able to extinguish
all of the fire scenarios for the hazard protected, and where it has a limited agent supply.
The agent supply is usually specified as the greater of (a) twice the time to extinguish the worse-case fire
scenario in an accepted fire test scenario, (b) the total time to shutdown process equipment including the time
it takes surfaces to decrease to a safe temperature, or (c) 10 minutes. Safe surface temperature may be
specified in the data sheet pertaining to protection of the occupancy. Discharge times other than 10 min may
also be allowed in the data sheet pertaining to protection of the occupancy. Special protection systems such
as CO2, dry chemical, or clean agent may also be suitable for protection of the hazard. Occupancies suitable
for protection by special protection systems are described in FM Global data sheets.
SSL: Scientific Services Laboratory, Melbourne, Australia.
Total Flooding System: A system designed to protect all the hazards in an enclosure.
Twin Fluid System: A water mist system in which water and atomizing media are supplied to the water mist
nozzle using separate piping systems.
VdS: Verband der Sachversicher, Cologne, Germany.
Water Mist: A water spray for which the Dv 0.99, for the flow weighted cumulative volumetric distribution of
water droplets, is less than 1,000 microns at the minimum design operating pressure of the water mist nozzle.
Water Mist Nozzle: A special purpose device containing one or more orifices designed to produce and deliver
an atomized water spray meeting the definition of water mist or meeting the specific requirements of an
FM Approved water mist fire test protocol. Nozzles can be designed to operate independently of other nozzles,
as a group of nozzles, or a combination of the two.
Zoned Application System: A system designed to protect hazards in a predetermined portion of an enclosure.
September 2006. Minor editorial changes were made for this revision.January 2006. Clarified
recommendations for when a reserve supply of agent is needed, and added three new definitions to Appendix
A. Also, the water demand for light hazard occupancies is now based on area rather than number of
sprinklers.
January 2005. Minor editorial changes were made for this revision.
September 2004. Section 2.2.1 was modified to allow the use of light hazard water mist systems FM Approved
for open area protection.
January 2004. Minor editorial changes were made for this revision.
September 2003. Minor editorial changes were made for this revision.
January 2003. Minor editorial changes were made for this revision.
September 2002. Minor editorial changes were made for this revision.
September 2001. The following changes were made for this revision:
1. Loss experience was added.
2. Fire test descriptions were included for FM Approved water mist systems.
3. General criteria for water mist system installation was provided.
C.2.1.1 General
Galvanized steel was examined as a material of construction for piping used in water mist systems. Some
of the earlier systems were FM Approved with galvanized piping. In hot dip galvanizing, a zinc coating is
applied to iron or steel by immersing the material in a bath consisting primarily of molten zinc. A layer of
zinc is formed on the pipe. As long as the coating is continuous and unbroken it will corrode like solid zinc.
The fresh zinc surface initially corrodes rapidly until it is covered with a protective film of corrosion products.
The corrosion then continues at a reduced rate. When there is a break in the coating, the corrosion rate of
galvanized steel pipe is similar to carbon steel pipe.
thick to 2 in. (50 mm) diameter. The occurrence of 3 or more leaks in a galvanized pipe section of 12 in.
(0.3 m) is not uncommon. In one case there were as many as 10 leaks in a 1.5 ft (0.46 m) long pipe section.
The causes of tubercle formation in dry pipe systems are (a) entrapped water, moisture, and air after testing,
and (b) microbiologically influenced corrosion (MIC).
In most environments, galvanized steel has good corrosion resistance. However, zinc begins to corrode
rapidly at elevated temperatures, especially in wet or moist environments. The rate of tubercle formation of
galvanized pipe is enhanced greatly at temperatures between 120F and 200F (49C and 93C), peaking
at 160F (71C).
C.2.1.4 Conclusion
Galvanized steel piping is no longer recommended for water mist systems.