A Comparison of The Fire Suppression Performance o PDF
A Comparison of The Fire Suppression Performance o PDF
A Comparison of The Fire Suppression Performance o PDF
net/publication/44068203
CITATIONS READS
4 559
3 authors, including:
Andrew Kim
National Research Council Canada
114 PUBLICATIONS 871 CITATIONS
SEE PROFILE
All content following this page was uploaded by Andrew Kim on 20 August 2014.
IRC-RR-146
January 2004
http://irc.nrc-cnrc.gc.ca/ircpubs
2
by
INTRODUCTION
Fixed pipe compressed-air foam (CAF) systems have been developed over the past
decade through a research collaboration between the National Research Council of Canada
(NRCC) and the Department of National Defence. Prototype CAF systems have demonstrated,
through full-scale testing [1-3], their superior fire suppression performance for controlling and
extinguishing fires for a number of hazards, including flammable liquids. To date, however, no
detailed comparison testing with other similar fire suppression systems for flammable liquids
Fixed pipe CAF systems represent a major innovation in fire suppression technology.
By injecting air into a foam-water stream in a mixing chamber, a significantly superior foam is
produced primarily as a result of uniform, small bubble sizes. That foam is transported through
a piping system to rotary nozzles which distribute foam over a prescribed area. There are
currently no specific fire suppression performance or installation standards for CAF systems;
thus, to assess the new technology for potential applications, comparisons must be made using
1
National Research Council of Canada
3
As a starting point for comparison, NFPA 16 – Standard for the Installation of Foam-
Water Sprinkler and Foam-Water Spray Systems [4] has been selected since it describes a
fixed pipe (overhead) fire suppression system using foam and water. Due to the differences in
the technologies, it was realized from the outset that many aspects of NFPA 16 cannot be
applied directly to CAF systems. It does, however, represent the best existing installation
standard for these first comparisons. The fire suppression performance of foam-water sprinkler
systems complying with NFPA 16 is evaluated in North America using UL-162 – Standard for
Foam Equipment and Liquid Concentrates [5]. One of the fire suppression tests from UL-162
has been chosen in this research as a first basis for evaluating comparable fire suppression
performance.
The research described in this report focuses on a parametric comparison of the fire
suppression performance of fixed pipe CAF systems and foam-water sprinkler systems
complying, to the extent that CAF systems can, with NFPA 16 and using fire testing as
described in UL-162. The CAF systems used in this evaluation were Integrated Compressed
Air Foam Systems manufactured by Fire Flex Systems Inc. under licence from the National
Research Council of Canada (NRCC). The research on which this report is based was a joint
EXPERIMENTAL SETUP
Class B fire tests using three different foam discharge methods: an overhead fixed piping
system using sprinklers or spray nozzles, subsurface injection devices and topside discharge
devices. For the current research project, only the overhead fixed piping system fire test was
2
Fire Flex Systems Inc.
4
used. While UL-162 prescribes a number of other tests for the nozzles, piping, etc., only the fire
Nozzles and Sprinklers – Two types of CAF nozzle were used in the overhead fixed
piping system fire tests. The first was a turbine action rotary (TAR) nozzle which has a 25 mm
(1 in.) diameter body with an outlet opening piece attached to the body (see Figure 1). The
outlet opening piece spins due to the momentum of the CAF flow through the nozzle. This
spinning action distributes CAF uniformly over a 5.2 m (17 ft) diameter circle (approximately
21 m2 (225 ft2)). The second was a gear drive rotary (GDR) CAF nozzle which has a 101 mm (4
in.) diameter body with an outlet opening piece attached to it, as shown in Figure 1. The body
contains a gear drive mechanism which rotates the outlet opening piece to distribute CAF
uniformly over a 9.4 m (31 ft) diameter circle (approximately 70 m2 (750 ft2)).
The sprinklers used in the fire suppression tests were standard orifice, pendent
sprinklers with a K-factor of 5.6. These sprinklers are used by one manufacturer for foam-water
sprinkler systems.
Piping Layout – For the foam-water sprinklers and the TAR CAF nozzles, the piping
system consisted of a 3.74 m x 3.74 m (12.25 ft x 12.25 ft) grid as shown schematically in
Figure 2. Foam-water sprinklers and TAR nozzles were installed at each corner of the grid.
This arrangement is identical to that required in UL-162. The grid, nozzles and sprinklers were
located 4.42 m (14.5 ft) above the floor. The piping arrangement for the GDR nozzle is shown
in Figure 3. For the GDR CAF nozzles, the grid was installed at the same height above the
floor, however, due to the size of the nozzle, the nozzle discharge orifice was located 4.2 m (14
ft) above the floor. This GDR nozzle arrangement is a modification of the UL-162 setup since
only one GDR nozzle was used to suppress the test fire rather than four sprinklers. The
5
location and CAF coverage area for the GDR nozzle were determined as a result of preliminary
testing.
Following a first series of tests with the piping grid located at 4.42 m (14.5 ft) above the
floor, a second series was conducted with the piping grid located 7.62 m (25 ft) above the floor.
Fire Test Pan – The fire test pan was square, straight-sided, with an area of 4.65 m2 (50
ft2), and was made of 6.4 mm (1/4 in.) thick steel plate as required by UL-162. The height of the
pan was 300 mm (12 in.) with a continuous horizontal lip of 38 mm (1.5 in.) wide projecting
outwards on the top edge of all sides. The test fire was a heptane pool fire using commercial
grade heptane fuel. The fire test pan was placed on the floor, centered below the piping grid for
the foam-water sprinkler and TAR nozzle tests as shown in Figure 2. These details complied
with UL-162. For the GDR nozzle tests, the test pan was placed on the floor, with its centre
2.22 m (7.3 ft) away from the point on the floor directly below the CAF nozzle.
The test pan contained a water layer of not less than 25.4 mm (1 in.) deep, with 100 or
205 L (26.4 or 54.1 US gal) of heptane poured over the water. With the rapid fire suppression
by the CAF, it was found that there was excessive unburned fuel left over when 205 L (54.1 US
gal) were used for a fire suppression test, thus creating an environmental problem. The fuel
quantity was reduced to 100 L (26.4 US gal), however, the 203 mm (8 in.) distance from the top
of the pan to the liquid surface, as required in UL-162, was maintained by adding additional
water.
Foam Concentrates – Tests were conducted using "listed" Class B and Class A foam
used at 3% in the foam-water sprinkler tests and at approximately 2% in the CAF tests. The
Class A foam concentrate, used only in the CAF tests, was at a concentration of approximately
1%.
TEST PROCEDURE
The heptane in the test pan was ignited and the resulting fire was allowed to burn freely
for a period of approximately 15 s. At the end of the 15 s pre-burn, the CAF nozzle or foam-
water sprinkler spray discharge was activated manually and allowed to continue operating for 5
min. During this period, as per UL-162, the time for complete extinguishment of the heptane
pool fire was noted. Video records for all tests were made. In some tests, the pre-burn period
was a few seconds longer as the manual operation of the CAF system was slightly delayed.
Following completion of the 5 min CAF or foam-water sprinkler discharge, the foam
blanket formed on top of the fuel was left undisturbed for 15 min. During this 15 min period, a
lighted torch was passed approximately 25.4 mm (1 in.) above the entire foam blanket, including
the corners of the pan, in an attempt to re-ignite the fuel. This torch test was conducted twice
during the 15-min period: immediately following the CAF or foam-water discharge, and 14 min
following discharge completion – which was 1 min prior to the burn-back test. Each torch test
lasted for a period of not less than 1 minute. This procedure is as required in UL-162.
The UL-162 test procedure for foam-water sprinklers requires that, following the 5 min
allowed to occur. The water discharge is followed by a period of 10 min during which the foam
is left undisturbed. Since a CAF system is not designed to flow water alone, it was decided to
follow the 5 min foam discharge with a 15 min waiting period during which the foam was left
7
undisturbed. This latter procedure of a 5 min foam discharge followed by a 15 min undisturbed
period is an accepted alternative procedure in UL-162 when a polar solvent fuel is used. This
same procedure (5 min discharge + 15 min undisturbed) was used for the foam-water sprinklers
At 15 min from the end of the CAF or foam-water discharge, a burn-back test was
conducted as per UL-162. In this test, a 0.3 m (1 ft) diameter "stovepipe" was placed
approximately 0.76 m (30 in.) from each of two adjacent sides of the test pan. The stovepipe
was placed in the corner where the flame extinguished last, and was placed in such a manner
that the foam blanket was not disturbed. The portion of the foam blanket that was enclosed by
the stovepipe was removed. The fuel inside the stovepipe was ignited and allowed to burn for 1
min. The stovepipe was then slowly removed from the pan while the fuel continued to burn.
After the stovepipe was removed, the time for the flame to spread across the remaining foam
blanket over an area larger than 0.9 m2 (10 ft2) was measured. This procedure is as required in
UL-162.
The pass/fail criteria used in these tests were those from UL-162 for overhead fixed
• The foam blanket must spread over and completely cover the test fuel surface.
• The fire must be completely extinguished during or at the end of the 5 min foam
discharge.
• The test fuel blanketed with foam must not reignite, candle, flame, or flashover when
a lighted torch is moved over all areas of the surface. (Minor flaming that self-
extinguishes is permitted.)
1) Restrict, for 5 min, the spread of fire to an area not larger than 0.9 m2 (10 ft2), or
In some tests, the expansion ratio and drainage time of the CAF was measured. Also,
several tests were conducted to determine the distribution pattern and density of the foam from
the foam-water sprinklers, and the TAR and GDR CAF nozzles. The 16-pan distribution test
protocol from UL-199 – Standard for Automatic Sprinklers for Fire Protection Services [6] was
used to measure the distribution pattern of both the foam-water sprinklers and the CAF nozzles.
This is different from the distribution pattern and density tests in UL-162. This UL-199 test
method uses sixteen 30 cm x 30 cm x 30 cm (12 in. x 12 in. x 12 in.) pans installed side by side
in a square in the centre of the discharge pattern of the sprinkler or nozzle. This pan
arrangement was also used to confirm the application density of the CAF nozzles' discharge.
This testing also differed from UL-199 in that the sprinklers and nozzles were 4.42 m (14.5 ft)
The results from the tests are grouped together to enable a comparison of the
performance of the CAF system and the foam-water sprinkler system. The results with the
piping grid at the 14.5 ft (4.42 m) and at the 25 ft (7.62 m) heights are presented separately.
• Comparison of foam-water sprinklers and TAR CAF nozzles at 4.42 m (14.5 ft) and
• Comparison of foam-water sprinklers and GDR CAF nozzle at 4.42 m (14.5 ft) and
fire.
Tables 1 and 2 provide a summary of results of the tests conducted with foam-water
sprinklers and TAR CAF nozzles at 4.42 m (14.5 ft) and 7.62 m (25 ft) heights. Figure 4
provides a photographic sequence of Test No. 2, one of the tests using TAR CAF nozzles.
10
Test No. 1 2 3 4 5
Foam-Water
Nozzle type TAR Nozzle TAR Nozzle TAR Nozzle TAR Nozzle
Sprinklers
No. of nozzles 4 4 4 4 4
Extinguishment time
2 : 32 0 : 50 0 : 49 0 : 59 1 : 16
(min:s)
At the 4.42 m (14.5 ft) height, Test Nos. 1, 2 and 3 provide a direct comparison of fire
suppression performance using Class B foam between the foam-water sprinklers and the CAF
system using TAR nozzles. As can be seen, the extinguishment time of the CAF system was
less than half that of the foam-water sprinklers and the burn-back time of the CAF system was
approximately double. In Tests 4 and 5, using Class A foam, the fire extinguishment time of the
11
CAF system was again less than one-half that of foam-water sprinklers. The burn-back
performance of the CAF system with Class A foam was, in Test No. 4, slightly better than the
foam-water system but approximately two-thirds the foam-water system time in Test 5. The
burn-back performance in both Tests 4 and 5 exceeded the minimum time of 5 min specified in
UL-162.
It is suspected that the Extinguishment Time in Test 5 was 17 s greater than Test 4
since the pre-burn time was 2 s longer (13%) due to manual operation delays in CAF reaching
the nozzles. This additional pre-burn time combined with a warmer ambient temperature (at
least 3° C warmer) resulted in hotter pan walls that allowed small candle flames to burn longer
at the sides of the pan. As well, the burn-back time was reduced due primarily to these two
factors which elevate the temperature of the fuel below the foam blanket.
12
Test No. 6 7 8
Foam-Water
Nozzle type TAR Nozzle TAR Nozzle
Sprinklers
No. of nozzles 4 4 4
Extinguishment time
2 : 16 0 : 50 1 : 09
(min:s)
At the 7.62 m (25 ft) height, the fire extinguishment and burn-back performance of the
CAF system (using both Class B and A foams) was approximately the same as that for the
4.42 m (14.5 ft) height with extinguishment at approximately one-half the time of the foam-water
systems. The CAF system with Class B foam burned back at approximately twice the time for
the foam-water sprinklers and Class A foam burned back at approximately two-thirds the time.
The CAF system exceeded the minimum fire extinguishment and burn-back benchmarks
13
required by UL-162 using both the Class B and Class A foams. It should be noted that the
ambient temperatures for the 7.62 m (25 ft) test series were all above 30°C. Higher
temperatures have been observed to have a negative effect in this type of test, especially on
burn-back.
Tables 3 and 4 provide a summary of results of the tests conducted with foam-water
sprinklers and the GDR CAF nozzle using both Class B and Class A foams. Figure 5 provides a
photographic sequence of Test No. 10, one of the tests using a GDR CAF nozzle.
The closest comparison of the GDR nozzle with the foam-water sprinklers at the 4.42 m
(14.5 ft) height is shown in Table 3 with Tests 9 and 10 compared to Test 1 (Class B foam). As
with the TAR nozzles, the fire extinguishment time for the CAF system was approximately one-
half the foam-water sprinklers and the burn-back time approximately double. With the GDR
nozzle and Class A foam, the fire extinguishment performance of the CAF system was
marginally better than the foam-water with Class B foam, however, the burn-back time was
approximately 60% that of the foam-water system. Both extinguishment and burn-back times
Table 3 – Results of Foam-Water Sprinklers and Gear Drive Rotary CAF Nozzle
Test No. 1 9 10 11 12 13
Foam-
Water GDR GDR GDR GDR GDR
Nozzle type
Sprinkler Nozzle Nozzle Nozzle Nozzle Nozzle
s
No. of nozzles 4 1 1 1 1 1
Extinguishment time
2 : 32 1 : 23 1 : 10 1 : 53 1 : 44 2 : 05
(min:s)
Table 4 – Results of Foam-Water Sprinklers and Gear Drive Rotary CAF Nozzle
Test No. 6 14 15
Foam-Water
Nozzle type GDR Nozzle GDR Nozzle
Sprinklers
No. of nozzles 4 1 1
Extinguishment time
2 : 16 1 : 02 1 : 23
(min:s)
At the 7.62 m (25 ft) height with the GDR nozzle using Class B foam, the fire
extinguishment time was approximately 50% of the foam-water sprinklers and the burn-back
time was approximately 1.3 times. For this arrangement with Class A foam, the fire suppression
time was approximately 60% that of the foam-water sprinklers, however, the burn-back time was
only 50% of the foam-water sprinklers and below the 5 min benchmark of UL-162.
16
The reason for the marginal burn-back performance of the Class A foam with the GDR
nozzle at the 7.62 m (25 ft) height appears to be partly due to the 203 mm distance to the pan
lip above the liquid level in the test pan. With the 4 TAR nozzles, the entire pan surface was
covered with foam quickly and all edges and corners were coated. With the 1 GDR nozzle
spraying foam from only one direction, a slight shadow effect occurred adjacent to the pan wall
on the GDR nozzle side. This shadow effect meant that extinguishment was delayed (due to
more foam being carried up in the longer unsuppressed fire plume) thus not as much foam
reached the liquid surface. The lesser thickness of the foam blanket appeared to be the reason
for the burn-back problems with Class A foam. The superior film-forming capabilities of the
Class B foam tended to compensate for this shadow effect with the GDR nozzle. As well, the
higher ambient temperature for the 7.62 m (25 ft) tests also had a negative impact on
While UL-162 requires a 4 foam-water sprinkler array with overlapping spray patterns in
assessing the impact of fire suppression and burn-back performance, this research was
extended beyond the UL-162 requirement to assess the impact of a single sprinkler/nozzle on
fire suppression and burn-back performance. To assess this impact, some of the tests at the
4.42 m (14.5 ft) height were conducted with only one sprinkler/nozzle operating. A sketch of the
set-up for the single sprinkler and nozzle tests is shown in Figure 6. The sprinkler/nozzle
location was determined to ensure coverage of the entire test pan. The results of these tests
Test No. 16 17 18
Foam-Water Foam-Water
Nozzle type TAR Nozzle
Sprinklers Sprinklers
No. of nozzles 1 1 1
Discharge density
- - -
GPM/ft2 (L/min/m2)
Extinguishment time
Not Ext. 2 : 32 2 : 49
(min:s)
In Test No. 16, the fire suppression performance of a single foam-water sprinkler in a
4-sprinkler array, with the minimum water flow rate (0.10 GPM/ft2) specified in UL-162 was not
sufficient to extinguish the test fire. The solution flow rate was increased to 0.16 GPM/ft2 in
Test No. 17. This resulted in fire suppression and burn-back performance meeting the UL-162
benchmarks and provided a basis for comparison with the single TAR CAF nozzle. The water
18
flow rate for the TAR CAF nozzle was, however, the same as the single nozzle rate in the four-
nozzle test and the solution flow rate only one-quarter that of the foam-water sprinkler. The
Comparing Test Nos. 17 and 18 using Class B foam for a single nozzle as shown in
Figure 6, shows that the CAF system fire extinguishment time was 17 s greater than the foam-
water sprinkler system but the burn-back time was approximately double. Both the CAF and
foam-water sprinkler systems met the UL-162 benchmarks for extinguishment and burn-back
performance.
An important issue that must be addressed in examining the results of fire suppression
system tests is the repeatability of the fire suppression performance with as few changes as
possible (preferably none) in the test parameters. In this research, four sets of nearly duplicate
tests on CAF systems were run thus allowing a determination of the repeatability of results.
These results are shown in Tables 6 and 7 for TAR and GDR nozzles, respectively.
In Repeatability Set 1 using TAR nozzles and Class B foam, it can be seen that the fire
suppression time was within 1 s and the burn-back time within 6 min. With TAR nozzles and
Class A foam (Repeatability Set 2), the fire extinguishment time was within 17 s and the burn-
back time within 4 min. In all cases, the extinguishment and burn-back times were within the
UL-162 limits.
Using GDR nozzles and Class B foam, it can be seen in Repeatability Set 3 that the fire
extinguishment time was within 13 s and the burn-back time within 1 min. With GDR nozzles
19
and Class A foam, the fire extinguishment time was within 12 s and the burn-back time within 2
s. In all cases, extinguishment and burn-back times were within the UL-162 limits.
Test No. 2 3 4 5
No. of nozzles 4 4 4 4
Extinguishment time
0 : 50 0 : 49 0 : 59 1 : 16
(min:s)
Repeatability Set
Repeatability Set 3
4
Test No. 9 10 11 13
No. of nozzles 1 1 1 1
294.2
Air flow rate 280 280 294
(1113.
GPM (L/min) (1060) (1060) (1113)
9)
Class
Foam type Class B Class B Class A
A
Extinguishment time
1 : 23 1 : 10 1 : 53 2 : 05
(min:s)
It can be argued that the performance of foam-water sprinkler and CAF systems with
nozzles located at a greater height may be diminished, as a result of the water and foam
21
droplets having greater difficulty in reaching the fuel surface due to the greater distance
between the sprinkler/nozzle and the fire source and thus the greater effect of the buoyancy of
the large fire plume. The UL-162 test procedure requires that fixed pipe foam suppression
systems be located approximately 4.42 m (14.5 ft) above the test chamber floor. There are
obviously many practical applications for foam systems that require a greater height of nozzles,
such as aircraft hangars. To assess the impact of increasing the height of the foam-water
sprinklers and CAF nozzles, the test series evaluated the fire suppression performance with
piping grids located both 4.42 m (14.5 ft) and 7.62 m (25 ft) above the floor of the test chamber.
Tables 8 and 9 show the comparative fire extinguishment and burn-back performance at
different heights for foam-water sprinklers and for TAR CAF nozzles and GDR CAF nozzles,
In examining Height Set 1 with foam-water sprinklers using Class B foam, it can be seen
that the fire extinguishment time was 16 s less at the 7.62 m (25 ft) height and the burn-back
time 21 s greater. These represent improvements in performance. With the TAR nozzle and
Class B foam in Height Set 2, it can be seen that the fire suppression times were identical and
the burn-back time was 5 s greater – again identical or better performance at the greater height.
With the TAR nozzles and Class A foam (Height Set 3), the fire suppression time was 10 s
longer and the burn-back time approximately 3.5 min less. While this represents a poorer
performance at the greater height, the results at the greater height were still within the UL-162
benchmark times. As well, the 7.62 m (25 ft) tests were conducted at a higher ambient
Test No. 1 6 2 7 4 8
Foam- Foam-
TAR TAR TAR TAR
Nozzle type Water Water
Nozzle Nozzle Nozzle Nozzle
Sprinklers Sprinklers
No. of nozzles 4 4 4 4 4 4
Extinguishment time
2 : 32 2 : 16 0 : 50 0 : 50 0 : 59 1 : 09
(min:s)
In examining Height Set 4 (in Table 9) with GDR nozzles and Class B foam, the fire
extinguishment time was reduced by 21 s and the burn-back time reduced by approximately
burn-back performance – still within the UL-162 limits. For GDR Nozzles and Class A foam
(Height Set 5) at the greater height, the fire extinguishment time was 30 s less, however, the
burn-back time was approximately 1 min less. The burn-back time in Test No. 15 fell below the
23
UL-162 benchmark time for the reasons (explained previously) of impact of lip height and
ambient temperature.
Test No. 1 6 9 14 11 15
Foam- Foam-
GDR GDR GDR GDR
Nozzle type Water Water
Nozzle Nozzle Nozzle Nozzle
Sprinklers Sprinklers
No. of nozzles 4 4 1 1 1 1
Extinguishment time
2 : 32 2 : 16 1 : 23 1 : 02 1 : 53 1 : 23
(min:s)
CONCLUSIONS
24
This research has compared the fire suppression and burn-back performance of foam-
water sprinkler systems and compressed-air foam nozzle systems using Class A and Class B
foams and the UL-162 fire test protocol. From the tests, it can be concluded that:
• Using TAR nozzles and either Class B or Class A foam, the fire extinguishment
times for the CAF system were superior to foam-water sprinklers in all tests and, in
most cases, the burn-back times were superior. This was consistent at both the 4.42
m (14.5 ft) and 7.62 m (25 ft) height above the test room floor.
• Using GDR nozzles and Class B foam, the fire extinguishment and burn-back times
were superior to foam-water sprinklers. With Class A foam, the fire extinguishment
time was superior, however, the burn-back time was less, in one case falling below
• In evaluating the performance of a single nozzle and Class B foam, the CAF fire
extinguishment time was marginally higher, however, the burn-back time was almost
double the foam-water sprinkler. It should be noted that the solution flow rate for the
foam-water sprinkler was increased above the one-quarter flow rate of the four
sprinkler array and was over 4 times the flow rate of the CAF nozzle.
• CAF system performance for both TAR and GDR nozzles was repeatable within a
• Foam-water and CAF system performance was only marginally affected by changing
the height of the nozzles with some better and some lesser performances with
changing height.
25
REFERENCES
1. Kim, A.K. and Dlugogorski, B.Z., “Multipurpose Overhead Compressed-Air Foam System
and Its Fire Suppression Performance,” Journal of Fire Protection Engineering, Vol. 8, No. 3,
1997.
2. Crampton, G.P., Kim, A.K. and Richardson, J.K., “A New Fire Suppression Technology,”
4. NFPA 16 – Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray
5. UL-162 – UL Standard for Safety for Foam Equipment and Liquid Concentrates, Seventh
ACKNOWLEDGEMENT
Authors would like to acknowledge the assistance of Mr. Michael Ryan of IRC and Mr.
Raymond Quenneville of Fire Flex Systems Inc. for their assistance in the CAF testing.
Authors would also like to express deep appreciation to Mr. J. Kenneth Richardson of Ken
Richardson Fire Technologies Inc. for his contribution in the preparation of this report.
26
12'-3"
6'-112" 6'-121"
6'-112"
50 SQ.FT. SYSTEM
6'-121"
4 NOZZLES SET-UP
PLAN VIEW
14'-6"
ICAF
SYSTEM
0'-10"
4 NOZZLES SET-UP
ELEVATION
9'-2"
EQ
FIRE TEST PAN ICAF
50 SQ.FT. SYSTEM
EQ
14'-6"
ICAF
SYSTEM
0'-10"
Figure 4 Fire extinguishment by CAF system with 4 nozzles, using Class B foam concentrate
30
Figure 4 Fire extinguishment by CAF system with 4 nozzles, using Class B foam concentrate (Cont.)
31
Figure 5 Fire extinguishment by CAF system with one large rotary nozzle, using Class B foam concentrate
32
Figure 5 Fire extinguishment by CAF system with one large rotary nozzle, using Class B foam concentrate (Cont.)
33
5'-021"
EQ
FIRE TEST PAN ICAF
50 SQ.FT. SYSTEM
EQ
1 NOZZLE SET-UP
PLAN VIEW
14'-6"
ICAF
SYSTEM
0'-10"
1 NOZZLE SET-UP
ELEVATION