FMDS0511 Lightning Protection System
FMDS0511 Lightning Protection System
FMDS0511 Lightning Protection System
Table of Contents
Page
©2007 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced,
stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.
5-11 Lightning and Surge Protection
Page 2 FM Global Property Loss Prevention Data Sheets
List of Figures
Fig. 1.
Annual mean number of days with thunderstorms. (U.S.A.) (U.S. Dept. of Commerce) ................ 13
Fig. 2.
Traveling waves caused by lightning stroke to power line. .............................................................. 14
Fig. 3.
Plot of data from Table 3, with 150 ft (45m) radius circle inscribed. ............................................... 16
Fig. 4.
Lightning protection from single mast or wire. ................................................................................. 17
Fig. 5.
300-ft rolling sphere principle. .......................................................................................................... 18
Fig. 6.
Station-type arresters. (Upper) Thyrite Magne-valve station-class arresters. For important
and valuable equipment in power stations and substations. Also made in line type. (General
Electric) (Lower) Autovalve type S.V. arresters. Heavy construction for power stations
and important substations. (Westinghouse) ..................................................................................... 22
Fig. 7. Intermediate arresters, line type. Pellet arresters, 300-volts minimum to 15-kv maximum.
(General Electric) .............................................................................................................................. 23
Fig. 8. Distribution arresters, valve type L.V. Rating 3 to 15 kv. (Westinghouse) ....................................... 23
Fig. 9. Tranquell (metal oxide) station surge arrestor. (General Electric Co.) ............................................ 24
Fig. 9a. Alugard 30-kv station arrester. (General Electric Co.) ................................................................... 25
Fig. 10. De-ion protector tube. For outdoor service. ................................................................................... 27
Fig. 11. dc capacitor-type arrester, 0 to 750 volts.
Molded insulation cover removed from one terminal. (General Electric) ....................................... 28
Fig. 12. Capacitor-type arrester, 751 to 2000 volts. (General Electric) ....................................................... 28
Fig. 13. Capacitor-type capacitor arrester, 2001 to 3900 volts. (General Electric) ..................................... 29
Fig. 14. Type MP valve arrester for dc circuits. (Westinghouse) ................................................................ 30
Fig. 15. Type RVS signal arrester for indoor a-c and dc circuits. (Westinghouse) ..................................... 30
Fig. 16a. Probable impulse withstand, volt-time, for a-c rotating machinery. .............................................. 44
Fig. 16b. Fundamental protection scheme. ................................................................................................. 45
Fig. 16c. Practical means of obtaining series inductance. .......................................................................... 46
Fig. 17. Additional arresters provided for line used to provide inductance and not shielded. .................... 46
Fig. 18. Length of line used as inductance with overhead shielded wire. .................................................. 47
Fig. 19. Basic scheme for providing lightning protection for machines directly connected to overhead
lines. ................................................................................................................................................ 48
Fig. 20. Protection for surge-grounded neutral machines and ungrounded neutral machines to 6900 volts. . 48
Fig. 21. Protection for machines rated at 11.5 kV and above, metallically connected to overhead lines,
not effectively grounded. ................................................................................................................. 49
Fig. 22. Base case for separate calculations. ............................................................................................. 51
Fig. 23. Multi-line, two-transformer station. .................................................................................................. 52
Voltage at Transformer
Fig. 24. Curve for determining a =
Voltage at Arrester. ........................................................................... 53
Fig. 25. Sample one-line diagram (partial) for examples 1 and 2. (for evaluation of adequacy of
transformer surge protection using methods of ANSI/IEEE standard C62.2-1981). ..................... 60
Fig. 26. Plan view and schematic of substation shown in Figure 27. ......................................................... 62
Fig. 27. Sectional view of substation shown in Figure 26. .......................................................................... 63
Fig. 28. Illustration of Step 1. ....................................................................................................................... 67
Fig. 29. Illustration of Step 2. ....................................................................................................................... 68
Fig. 30. Insulation coordination by the curve method. ................................................................................ 70
List of Tables
Table 1. Lightning Losses by State and Province, 1973 to 1982 .................................................................. 6
Table 2. Number of Thunderstorm Days Per Year, Canada ........................................................................ 12
Table 3. Protection Angles for 99.5% Protection ......................................................................................... 15
Table 4. Recommended Currents for Determining Discharge Voltages ...................................................... 18
Table 5. Voltage Ratings in kV ..................................................................................................................... 26
Table 6. Station and Intermediate Arrester Characteristics (ANSI C62.2-1981) ......................................... 32
Table 6a. Valve-Type Distribution Arrester Characteristics (ANSI C62.2-1981) .......................................... 33
Table 7. Protective Characteristics of Station Valve Arresters (ANSI C62.2-1981) .................................... 35
Table 7a. Protective Characteristics of Intermediate Valve Arresters (ANSI C62.2-1981) ........................ 36
Table 8. Relationships of Nominal System Voltage to Maximum System Voltage and Basic Lightning
Impulse Insulation Levels (BILs) for Systems 1100 kV and Below (ANSI C57.12-1980) ............ 37
Table 9. Interrelationships of Dielectric Insulation Levels for Liquid-Filled Transformers Used on Systems
with BILs 2425 kV and Below (ANSI C57.12-1980) ...................................................................... 38
Table 10. Insulation Levels for Dry-Type Transformers (ANSI C57.12.01-1979) ....................................... 39
Table 11. Rated Voltages and Insulation Levels for AC Switchgear Assemblies ........................................ 40
Table 12. Voltage Ratings for Metal-Enclosed Bus ..................................................................................... 41
Table 13. Electrical Characteristics of Transformer Bushings (applies only to bushings 34.5 kV and
below not listed in ANSI/IEEE Std 24-1977.) (ANSI C57.12-1980) ............................................ 42
Table 14. Commonly Applied Voltage Ratings of Arresters on Distribution Systems (ANSI C57.12-1980) . 43
Table 15. Protection Levels of Station-Type Arresters Designed for Machine Protection .......................... 49
Table 16. Maximum Allowable Separation ................................................................................................... 50
Table 17. Factors for Estimating Withstand Voltages of Mineral-Oil-Immersed Equipment ........................ 54
Table 18. Valve-Type Distribution Arrester Characteristics ......................................................................... 55
Table 19. Protective Characteristics of Distribution Valve Arresters ............................................................ 55
Table 20. Protective Characteristics of Secondary Valve Arresters ............................................................ 55
Table 21. Commonly Applied Voltage Ratings of Arresters on Distribution Systems .................................. 56
Table 22. Recommended Minimum Clearances .......................................................................................... 58
1.0 SCOPE
This data sheet describes modern procedures and practices for protecting industrial power distribution
systems and associated equipment from damage caused by overvoltages due to lightning, switching, or a sys-
tem abnormality.
The protection of chimneys, stacks, and related equipment against lightning is covered in Data Sheet 1-13,
Chimneys, and of ignitable liquid storage tanks in Data Sheet 7-88, Storage Tanks for Ignitable Liquids.
Grounding details are covered in Data Sheet 5-10, Protective Grounding for Electric Power Systems and
Equipment.
In the United States, lightning protection requirements for ordinary buildings, miscellaneous structures, and
special occupancies can be found in UL 96A, Installation Requirements for Lightning Protection Systems.
Other countries may have their own codes.
1.1 Changes
April 2012. Terminology related to ignitable liquids has been revised to provide increased clarity and consis-
tency with regard to FM Global’s loss prevention recommendations for ignitable liquid hazards.
2.1 Electrical
2.1.2.5 Substations. In addition to shielding the substation, ensure each entering exposed overhead line is
shielded and protected with a set of surge arresters. Additional arresters may be needed to protect the trans-
former depending upon the distance between the arresters and the transformer, the system voltage, and
the method of grounding. See Examples 1 and 2 in Figure 16c.
2.1.2.6 Rotating Machines. Protect important motors or generators with station-type arresters installed in par-
allel with surge capacitors at the machine terminals, and interconnect them with the machine frame and a
ground resistance of 1 ohm or less.
1. Provide each medium voltage (5 kV to 15 kV) motor above 500 hp with surge protection as described
above.
2. Ensure each motor over 200 hp connected to open overhead lines at the same voltage level as the motor
is similarly protected.
3. Protect all unit-connected generators with surge arresters and capacitors as recommended above, except
that on generators which have single-turn windings, the capacitor is not required.
2.1.2.7 Switchgear
2.1.2.7.1 In areas where lightning exposure is severe, have metal clad switchgear directly connected to over-
head circuits through roof entrance bushings or through noncontinuous metallic sheath cable protected with
station-type arresters.
2.1.2.7.2 Where the switchgear is connected through continuous metallic-sheath cables to overhead lines,
install arresters at the cable junction. They also may be needed at the switchgear depending upon the length
of cable, method of neutral grounding, and the class of arrester installed at the cable junction.
2.1.2.8 Protect buildings containing or processing ignitable liquids or flammable gases that are of signifi-
cant value or importance with lightning rods, especially if located in high-risk lightning areas. Refer to NFPA
780, Standard for the Installation of Lightning Protection Systems for details.
CANADA
Province Number
Quebec 20
Ontario 35
New Brunswick 4
Brit. Columbia 0
Manitoba 4
Alberta 1
More lightning losses occurred in North Carolina, 93, than in any other state. Pennsylvania was second with
89. Six other states had more than 50 lightning losses: Ohio, 85; Illinois, 80; Texas, 72; Florida, 65; Wisconsin,
62; and New Jersey, 53.
In Canada more lightning losses occurred in Ontario, 35, than in any of the other provinces. Only a total of
65 occurred in all of the provinces.
Many transformers were damaged by lightning. There were 204 oil-insulated units, most of which were rated
in excess of 600 volts; 62 were of the dry type and 89 were miscellaneous types, such as current and potential
transformers.
The principal type of equipment damaged by lightning in the remaining losses included motor starters,
synchronous motors, generators, circuit breakers, bus ducts, furnace transformers, distribution panels, switch-
gear, and wiring.
Many of these losses could have been prevented if proper shielding, surge arresters, and effective grounding
had been provided.
4.0 REFERENCES
4.1 FM Global
Data Sheet 1-13, Chimneys.
Data Sheet 5-10, Protective Grounding for Electric Power Systems and Equipment.
Data Sheet 7-88, Storage Tanks for Ignitable Liquids.
4.2 Other
1. American National Standard for Surge Arresters for Alternating — Current Power Circuits. ANSI/IEEE
C62.1-1981. (New York: IEEE, 1981)
2. American National Standard Guide for the Application of Valve-Type Surge Arresters for Alternating Current
Systems. ANSI C62.2-1981. (New York: American National Standards Institute, 1981).
3. IEEE Guide for Surge Voltages in Low Voltage AC Power Circuits. IEEE Std. 587-1980. (New York: IEEE,
1980).
4. American National Standard Test Specifications for Gas Tube Surge Protective Devices. ANSI/IEEE
C62.31-1981 (formerly IEEE Std. 465-1977). (New York: IEEE, 1977).
5. Johnson, I.B., et al. Surge Protection in Power Systems. IEEE Tutorial Course 79 EH0144-6-PWR.
(Piscataway, N.J.: IEEE, 1978).
6. IEEE Working Group Progress Report. Impulse Voltage Strength of AC Rotating Machines. 81 WM 182-5,
1981 PES Winter Meeting.
7. Jackson, D.W. Discussion of Paper No. 81 WM 182-5 Impulse Voltage Strength of AC Rotating Machines.
1982 PES Winter Meeting.
8. Houghtaling, D.W. Discussion of Paper No. 81 WM 182-5 Impulse Voltage Strength of AC Rotating
Machines. 1981 PES Winter Meeting.
9. Rhudy, R.G. and Walsh, G.W. Closure of 81 WM 182-5. 1981 PES Winter Meeting.
10. Walsh, G.W. A Review of Lightning Protection and Grounding Practices. IEEE Transactions on Industry
Applications, March/April 1973.
11. Towne, H.M. Lightning Protection of Substations, March 29-30, 1951 Conference of Southeastern Electric
Exchange, October 1, 1954.
12. Station Surge Arrester Seminar. (Pittsfield, MA: General Electric Company, n.d.).
13. Boice, W.K. Suppression of Secondary Surges Caused by Lightning Overvoltages at Transformer
Primaries. (Piscataway: IEEE, 1980).
14. Surge Protection for Rotating Machines. Application Data 38-423 (Bloomington, IN: Westinghouse
Electric Corporation, 1970).
15. Walsh, G.W. A New Technology Station Class Arrester for Industrial and Commercial Power Systems.
(New York: IEEE, 1977).
16. Doble Client Committee on Arresters, Capacitors, and Insulators. Metal Oxide Surge Arresters. Minutes
of the 49th Annual Doble Client Conference, Section 9D-01. (Watertown, MA: Doble Engineering Company,
1982).
17. Doble Client Committee on Arresters, Capacitors, and Insulators. Arrester Field Test Guide. (Watertown,
MA: Doble Engineering Company, 1976).
18. Lee, R.H. Protection Zone for Buildings Against Lightning Strokes Using Trnasmission Line Protection
Practice. IEEE IAS 1977 Annual Transactions. (New York: IEEE, 1977).
19. Standard for the Installation of Lightning Protection Systems. NFPA 780 (National Fire Prevention
Association, 1983). Quincy, MA.
Note: The manufacturer’s literature for each surge arrester must be consulted for the characteristics of each
device. This literature is far too voluminous to list here.
Expulsion Element: a chamber in which an arc is confined and brought into contact with gas-evolving material.
Series Gap: an intentional gap(s) between spaced electrodes. It is in series with the valve or expulsion
element of the arrester, substantially isolating the element from line or ground, or both, under normal line
voltage conditions.
Valve Arrester: an arrester that includes a valve element.
Classification of Arresters: station valve arrester. Intermediate valve arrester. Distribution valve arrester.
Distribution Expulsion valve arrester.
Grading or Control Ring: a metal part usually circular or oval in shape, mounted to modify electrostatically
the voltage gradient or distribution.
Discharge Counter: a means for recording the number of arrester discharge operations.
Arrester Disconnector: a means for disconnecting an arrester in anticipation of, or after, a failure in order to
prevent a permanent fault on the circuit and to give indication of a failed arrester.
Lightning: an electric discharge that occurs in the atmosphere between clouds or between clouds and ground.
Lightning Surge: a transient electric disturbance in an electric circuit caused by lightning.
Wave: the variation with time of current, potential, or power at any point in an electric circuit.
Surge: a transient wave of current, potential, or power in an electric circuit.
Impulse: a surge of undirectional polarity.
Oscillatory Surge: a surge that includes both positive and negative polarity values.
Crest (Peak) Value (of a wave, surge, or impulse): the maximum value that it attains.
Wave Front (of a surge or impulse): that part which occurs prior to the crest value.
Wave Tail (of an impulse): that part between the crest value and the end of the impulse.
Wave shape (of an impulse test wave): the graph of the wave as a function of time.
Wave Shape Designation (of an impulse): the wave shape of an impulse (other than rectangular) of a current
or voltage is designated by a combination of two numbers. The first, an index of the wave front, is the virtual
duration of the wave front in microseconds. The second, an index of the wave tail, is the time in microseconds
from virtual zero to the instant at which one half of the crest value is reached on the wave tail. Examples are
1.2/50 and 8/20 waves.
The wave shape of a rectangular impulse of current or voltage is designated by two numbers. The first
designates the minimum value of current or voltage that is sustained for the time in microseconds designated
by the second number. An example is 75A - 1000 µsec wave.
Virtual Zero Point (of an impulse): the intersection with the zero axis of a straight line drawn through points
on the front of the current wave at 10% and 90% crest value, or through points on the front of the voltage
wave at 30% and 90% crest value.
Nominal Rate of Rise (of an impulse): of a wave front, the slope of the line that determines the virtual zero.
It is usually expressed in volts or amperes per microsecond.
Disruptive Discharge: the sudden and large increase in current through an insulating medium, due to the
complete failure of the medium under the electrostatic stress.
Flashover: a disruptive discharge around or over the surface of a solid or liquid insulator.
Sparkover: a disruptive discharge between electrodes of a measuring gap, voltage-control gap, or protective
device.
Impulse Sparkover Volt-Time Characteristic: the sparkover response of the device to impulses of a designated
wave shape and polarity, but of varying magnitudes. Note: For an arrester, this characteristic is shown by
a graph of values of crest voltage plotted against time to sparkover.
Power Frequency Withstand Voltage: a specified root-mean-square test voltage at power frequency that will
not cause a disruptive discharge.
Impulse Withstand Voltage: the crest value of an impulse that, under specified conditions, can be applied
without causing a disruptive discharge.
Voltage Rating: the designated maximum permissible operating voltage between its terminals at which an
arrester is designed to perform its duty cycle. It is the voltage rating specified on the nameplate.
Power-Frequency Sparkover Voltage: the root-mean-square value of the lowest power frequency sinusoidal
voltage that will cause sparkover when applied across the terminals of an arrester.
Impulse Sparkover Voltage: the highest value of voltage attained by an impulse of a designated wave shape
and polarity applied across the terminals of an arrester prior to the flow of discharge current.
Discharge Current: the surge current that flows through an arrester when sparkover occurs.
Discharge Voltage (IR): the voltage that appears across the terminals of an arrester during passage of
discharge current.
Discharge Voltage-Current Characteristic: the variation of the crest values of discharge voltage with respect
to discharge current. Note: This characteristic is normally shown as a graph based on three or more
current-surge measurements of the same wave shape but of different crest values.
Discharge Withstand Current Rating: the specified magnitude and wave shape of a discharge current that
can be applied to an arrester or specified number of times without causing damage to it.
Follow (Power) Current: the current from the connected power source that flows through an arrester during
and following the passage of discharge current.
Grounded System: an electric system in which at least one conductor or point (usually the neutral conductor
or neutral point of transformer or generator windings) is intentionally grounded, either solidly or through a
grounding device.
Coefficient of Grounding: the ratio ELG/ELL, expressed as a percentage, of the highest root-mean-square
line to ground power-frequency voltage ELG on a sound phase, at a selected location, during a fault to ground
affecting one or more phases to the line-to-line power frequency voltage ELL which would be obtained, at
the selected location, with the fault removed.
Notes:
1. Coefficients of grounding for three-phase systems are calculated from the phase-sequence impedance
components as viewed from the selected location. For machines use the subtransient reactance.
2. The coefficient of grounding is useful in the determination of an arrester rating for a selected location.
3. A value not exceeding 80% is obtained approximately when for all system conditions the ratio of
zero-sequence resistance to positive-sequence reactance is positive and less than three, and the ratio
of zero-sequence resistance to positive-sequence reactance is positive and less than 1.
Withstand Voltage: highest value of applied voltage at which an arrester will not flash over.
Ungrounded System: without an intentional connection to ground. Note: Although called ungrounded, this
system in reality is capacitively coupled to ground through the distributed phase-to-ground capacitance of the
windings and phase conductors of the systems.
Effectively Grounded: intentionally connected to earth through a ground connection or connections of
sufficiently low impedance where the coefficient of grounding does not exceed 80%, and having sufficient
current-carrying capacity to prevent the buildup of voltages that may result in undue hazard to connected
equipment or to persons.
Non-Effectively Grounded: the Coefficient of Grounding exceeds 80%.
Insulation Coordination: the process of correlating insulation strengths of electrical equipment with expected
overvoltages and with characteristics of surge protective devices.
Withstand Voltage: the voltage that electrical equipment is capable of withstanding without failure or disruptive
discharge when tested under specified conditions.
Transient Insulation Level (TIL): an insulation level expressed in terms of the crest value of the withstand
voltage for a specified transient wave shape; for example, lightning or switching impulse.
Basic Lightning Impulse Insulation Level (BIL): a specific insulation level expressed in terms of the crest
value of a standard lightning impulse.
Basic Switching Impulse Insulation Level (BSL): a specific insulation level expressed in terms of the crest
value of a standard switching impulse.
Lightning Impulse Protection Level (LPL) (of a protective device): the maximum lightning impulse voltage
expected at the terminals of a surge protective device under specified conditions of operation.
Switching Impulse Protection Level (SPL) (of a protective device): the maximum switching impulse expected
at the terminals of a surge protective device under specified conditions of operation.
Switching Surge Protective Level (SSP): the greater of switching surge sparkover or switching discharge
voltage.
Chopped Wave (CWW): an impulse voltage wave that is suddenly reduced substantially to zero value by
the sparkover of an air gap.
Front of Wave Sparkover (FOW): the maximum spark-over on a linearly rising impulse front. The rate of rise
of the front increases with arrester rating.
Let-through Sparkover (LT): a measure of the highest lightning surge an arrester is likely to withstand without
sparkover in 3 µsec or less.
Temporary Overvoltage (TOV): an oscillatory overvoltage associated with switching of relatively long duration
which is undamped or slightly damped.
Arrester Recovery Voltage: the crest voltage that occurs across the terminals of an arrester following a unit
operation.
Research Voltage Rating of an Arrester: the maximum arrester recovery voltage permitted for a specified
time following one or more unit operations with discharge currents of specified magnitude and duration.
C.1 General
Electrical breakdowns caused by overvoltages due to lightning are responsible for considerable property dam-
age and business interruption. No section of the United States is immune, although in the Pacific Coast area
lightning storms are infrequent. The Southeastern and South Central States experience the largest number
of lightning storms each year.
In Canada lightning storms are fairly frequent in the provinces of Ontario and Quebec and less frequent in
the other provinces. In Newfoundland they occur relatively infrequently.
Procedures outlined herein for protecting against overvoltages comply with the standard of the Institute of
Electronic and Electrical Engineers and the American National Standards Institute, the requirements of the
National Electric Code, and the recommendations of the manufacturers of electrical equipment.
Determining the surge protection requirements for a particular installation is a specialized job. The assis-
tance of manufacturers’ representatives in selecting suitable arresters and other safeguards is recom-
mended if experienced personnel are not available.
Overvoltages on power systems are produced in a number of different ways; those of particular concern
are listed below and are discussed later in more detail.
1. Lightning.
2. Contact with higher voltage systems.
3. Resonance effect in inductive and capacitive circuits.
©2007 Factory Mutual Insurance Company. All rights reserved.
Lightning and Surge Protection 5-11
FM Global Property Loss Prevention Data Sheets Page 11
4. Ferro-resonance.
5. Switching surges.
6. Forced current zero interruption.
7. Autotransformer connection.
8. Loss of neutral ground on a normally grounded system.
9. Sudden loss of load and/or generator overspeed.
C.3.1 Current
Current measurements of more than 4000 strokes to high voltage transmission lines ranged from 2400 amps
to 218,000 amps. Fifty percent of the strokes equaled or exceeded the median value of 14,000 amps. Super
strokes in the order of 300,000 to 400,000 amps have been recorded in the United States and Europe, but
these occur infrequently and their magnitude is an estimate because of the limitation of instrumentation.
C.3.2 Voltage
The voltage of a lightning stroke is difficult to measure, but it has been estimated that the potential difference
between a charged cloud and the earth ranges from 5 to 50 MV. With voltages of this magnitude, it is obvious
why it is impossible to insulate a power system sufficiently to withstand a direct lightning stroke.
C.3.3 Waveshape
The waveshape of a lightning surge is usually referred to by the wave front and the wave tail. The front is
the time required to reach crest magnitude; the tail is the time to decay to half the crest value.
Characteristically, a lightning discharge will crest in several microseconds and decay to half the crest value
in 20 to more than 100 microseconds.
The maximum or crest value of this impulse voltage is often higher than the impulse strength of the insulation
of transformers, generators, motors or other electrical equipment on the system. Insulation failures are to
be expected unless proper surge protection is provided.
In the application of surge protection, the effective rate of rise is of greater importance than the elapsed time
from the beginning of the surge to the crest value.
C.3.4 Polarity
Based on thousands of measurements, 90% of the strokes to earth have negative polarity, resulting from a
negative charge center in the lower part of a cloud and a positive charge in the earth below.
C.3.5 Charge
The quantity of charge in a stroke may range from 2 to 200 coulombs (ampere-seconds), while the average
is about 20 coulombs. A lightning stroke may have a peak current of 200,000 amps or more but being so
short-lived, the surge current can easily be handled by a small conductor. The largest recorded conductor to
be vaporized by a stroke is a No. 10 AWG.
C.3.6 Frequency
The frequency that lightning strokes occur to transmission lines in open country indicates the degree of
exposure that occurs to a power system. Figure 1 is an isokeraunic map which shows the number of
thunderstorm days per year that occur in the United States.
Table 2 shows the number of thunderstorm days per year that occur in each of the Canadian provinces for
the period 1941 to 1970; more recent data is not yet available. The table shows the minimum and maximum
number of thunderstorm days reported for each province depending on the location of the weather stations.
The number of lightning strokes to a transmission line or to open ground is assumed to vary directly with
the isokeraunic level (IKL).
An analysis of several thousand strokes to transmission lines protected with a single 100-ft (30-m) high ground
wire indicated that it would be struck 100 times per 100 miles per year in an area having an IKL of 30.
Fig. 1. Annual mean number of days with thunderstorms. (U.S.A.) (U.S. Dept. of Commerce)
IZ 8,000 × 500
E= , or E = = 2,000,000 Volts.
2 2
In other words, a traveling wave current of 8,000 amps will generate 2000 kV on the power line.
The traveling waves caused by the lightning stroke will continue along the line until they encounter a change
in impedance, such as when they come to a transformer, a circuit breaker, an open circuit, another connected
line, or a short circuit. At this point, the voltage and current waves are reflected back upon the line, while
at the same time they travel beyond this point. Upon encountering a transformer, the reflected waves combine,
resulting in double the traveling wave voltage at the transformer. The current wave at an open circuit
termination is also reflected, but being of opposite polarity the result is zero current at the end of the line.
When a line ends in a short circuit, the incoming and reflected voltage waves have the same magnitude and
opposite polarity, resulting in zero voltage at the terminal. However, the current waves have the same
magnitude and the same polarity which doubles the traveling wave current, a well-known phenomenon. This
doubling of the traveling wave current is an important factor to consider in the application of a surge arrester
on the end of a line. The resistance of an arrester is very low compared to the surge impedance of the line,
and the current that it will be required to discharge is nearly double the traveling wave current.
The table shows that at 150 ft (45 m) above ground, a zero angle of protection is provided by the higher
conductor. Above 150 ft (45 m), the negative angles indicate that the overhead ground wire should extend
beyond the position of the conductor being protected.
The data in Table 3 was then plotted on a linear scale. When the plotted points were connected, as shown
in Figure 3, they formed almost exactly the arc of a circle of 150 ft (45 m) radius tangent to the earth’s surface
at a point 150 ft (45 m) away from the 150 ft (45 m) high (zero protection angle) point. It should be noted
that the 150-ft (45-m) radius criterion matches well with the 45 meter predominant step leader length
mentioned previously.
Fig. 3. Plot of data from Table 3, with 150 ft (45m) radius circle inscribed.
By applying this same concept to the protection that would be afforded by a single elevated rod or wire, an
object above ground level will be protected against direct lightning strokes if it does not protrude above the
surface of an inverse circular sided cone of 150-ft (45-m) radius. (See Fig. 4.)
To better visualize this concept, imagine a sphere of 150-ft (45-m) radius [300-ft (91-m) diameter] rolling
over the surface of the earth, up and over all projections above the earth surface. All objects which the sphere
touches are susceptible to direct stroke, while those which the sphere does not touch because of being lifted
over them by higher (protecting) objects are not susceptible to direct stroke. It is obvious that objects more
than 150 ft (45 m) away from almost any high structure will receive little or no protection from that structure.
The Rolling Sphere Principle is further illustrated in Figure 5. Structure B, which lies below the 150-ft (45-m)
radius curve, would be protected, but any object that projects through this radius, such as Structure A, would
be exposed to direct stroke.
The new protection curve to the left of the mast is a combination of two 150-ft (45-m) radius curves intersecting
on Structure A or the locus of a 150-ft (45-m) radius sphere rolling up and over Structure A, then from the
roof of A until it touches the mast at Point C. The height of the mast above Point C provides no additional
protection and is called ″useless height.″
Other factors in addition to tower height that influence the lightning performance of a transmission line are
the number of ground wires, the number of insulators, and the resistance of the tower footings. Lines that are
shielded with two ground wires usually perform better than those with only one ground wire, due to the lower
surge impedance and better coupling with the phase conductors.
A ground or coupling wire sometimes installed below the phase conductors and shield wires of a transmission
line will also help to prevent flashovers. Due to the increased coupling, the potential difference between phase
conductors and grounded wires is lowered because the percentage of the ground wire potential impressed
on the phase conductor is raised following the termination of a stroke on the shield wires or structure.
Transmission lines are generally considered to be ‘‘lightning-proof’’ if they are designed so that outages due
to lightning are limited to one or less per 100 miles (160 km) per year. This is commonly accepted as an
economical and practical design standard.
Flashovers on transmission lines due to switching surges are prevented by providing an adequate number
of insulators. The number necessary is determined by the magnitude of the switching surges expected, the
surge impedance of the conductors, overhead ground wires, and resistance of the tower footings.
C.4.2 Substations
Lightning surges can enter a substation either by a direct stroke to the equipment or through transmission
lines that are connected to it. The degree of shielding is vitally important in determining the protection needed.
Overhead ground wires or masts are generally employed to shield against direct strokes, and surge arresters
are installed to limit the magnitude of any surge voltages entering over the transmission lines. The arresters,
when properly applied, will also protect against those surges that are generated within the system during
switching operations.
For a small station, one or two overhead ground wires strung above the station from adjacent line towers
are usually sufficient to protect all parts of the station. For larger substations, additional overhead ground wires
may be used, or if this is not feasible, masts or rods may be erected at the corners or over vertical columns
to protect all equipment within the substation.
The degree of shielding provided for a substation and its connected lines determines to a large extent the
magnitude of the surge current that flows through a surge arrester when sparkover occurs. This is termed the
discharge current, and will vary from 1000 to 20,000 amperes with effective shielding, depending upon the
system voltage. Table 4 shows the discharge currents for various system voltages.
An installation is considered effectively shielded against direct strokes if the station and all connecting lines
are shielded. To be effective, the shielding should extend for at least one-half mile from the station.
Temporary overvoltages (TOV) are produced by sudden loss of load or generator overspeed and voltage
regulation. When a line is open circuited during heavy load conditions, it is acting like a capacitor bank and
the voltage regulators are higher than necessary. The overvoltage will be sustained until the regulator is
lowered. Likewise, the generator will tend to accelerate and increase both the voltage and frequency until
the governor reduces the speed of the unit. In machines that have slow governor action, such as on
water-wheel generators and nuclear units, this latter effect is very important.
In the majority of cases, the switching surges that occur on a system are sufficiently small that they do not
cause an insulation breakdown or trip a protective device.
Power systems are commonly protected from switching surges either by controlling the magnitude of the
surge when it is generated or by limiting the effects of the surge. The magnitude of the surge may be limited
by incorporating surge suppression resistors in the switching device, whether it be a circuit breaker or a
disconnecting switch. The magnitude may also be limited by controlling the point on the voltage wave at which
the contacts close. The generated surge will be greatly reduced if the contacts close at a time that the voltage
across them is at a minimum.
In the case of a trapped charge on the line, a surge can be controlled by draining the charge from the line
before it is allowed to reclose. A power transformer that is connected to the line will accomplish this when the
line is opened. However, if shunt reactors are connected on the line they limit, the effective Ferranti rise on
the line which can lead to reduced transient and temporary overvoltage.
Other means of suppression and control of switching surges are effective neutral grounding, excitation and
speed control, potential transformers, intermediate switching stations, transformer tertiaries, circuit
configuration and parameters, transfer trip, and surge arrestors.
C.6.2.2 Ferro-Resonance
A ground fault in a potential transformer or an ungrounded system, the core of which becomes saturated,
can be responsible for damaging overvoltages. The effective reactance of the inductive circuit becomes much
lower than the unsaturated reactance and the voltage will tend to oscillate between voltage limits. This causes
the effective inductive reactance to match the capacitive reactance value. This performance is known as
ferro-resonance.
Current limiting fuses and vacuum breakers, for example, have the property of being able to reduce the current
to zero value ahead of the inherent normal current zero. During the operation of these devices, the
overvoltage developed can be dangerous at some insulation levels.
Fig. 6. Station-type arresters. (Upper) Thyrite Magne-valve station-class arresters. For important and valuable equipment
in power stations and substations. Also made in line type. (General Electric) (Lower) Autovalve type S.V. arresters. Heavy
construction for power stations and important substations. (Westinghouse)
Valve arresters are divided into four main classes: station (2.4 kV - 765 kV) (Figs. 6, 9, and 9a); intermediate
(3 kV - 120 kV) (Fig. 7); distribution (1 kV - 30 kV) (Fig. 8); and secondary (0.175 kV - 0.65 kV). Each of
these have different sparkover and discharge voltage characteristics for the same nominal voltage rating of
the arrester. The root-mean-square voltage ratings in kilovolts are as shown in Table 5.
Fig. 7. Intermediate arresters, line type. Pellet arresters, 300-volts minimum to 15-kv maximum. (General Electric)
Fig. 9. Tranquell (metal oxide) station surge arrestor. (General Electric Co.)
The metal oxide arrester shown in Figure 9 is a relatively new development in a station surge arrester in
which the series gap has been eliminated. The valve elements are highly nonlinear resistors formulated from
a zinc oxide compound. This arrester differs from the conventional arrester in that it responds to over-voltages
promptly. Since there is no gap, no abrupt transient can occur such as when sparkover in the conventional
arrester occurs, and there is negligible power follow current after a surge operation.
The number of parts in the metal oxide arrester is considerably reduced, resulting in improved reliability,
improved performance under contaminated conditions, and smooth transition into and out of conduction as
the overvoltage increases and then disappears.
The function of the valve arrester is similar to the relief valve on a steam boiler, i.e., when the pressure
becomes too high, the relief valve opens and discharges the excess pressure; then it closes when conditions
are safe again. During normal conditions on the system, a valve arrester is merely an insulator between
the power line and ground. There is usually no flow of current through the arrester. In some types however,
there is a fraction of a milliampere of current through the resistance spacers to maintain a uniform voltage
distribution over the arrester gaps.
The metal oxide arrester is said to be particularly suitable for the protection of gas (SF6) insulated substations
in which surge propagation and over-voltage phenomena are quite different from those of air-insulated
substations. They are available for use on nominal system voltages from 2.5 kV to 765 kV.
The nominal voltage rating of the arrester is the maximum voltage at which it is guaranteed to interrupt follow
current after it has sparked over.
Station arresters are heavy-duty units designed to withstand a maximum crest current of 65,000 amperes.
Distribution arresters, intermediate valve arresters, expulsion arresters, and protector tubes will also withstand
65,000 amperes; secondary arresters will withstand 10,000 amperes.
Table 6 shows other durability characteristics for station and intermediate class arresters. Distribution class
arresters (Table 6a) do not have standardized pressure relief ratings. The pressure relief ratings indicate
the maximum fault current that the arrester will withstand without violent disintegration.
Protector tubes operate on a different principle than the valve type for interruption of the ″follow current.″
The gap is so arranged that when sparkover occurs, the arc passes through a tube that causes gas to be
generated from the lining of the tube, which upon discharge out of the open end, stretches and extinguishes
the arc as the alternating current wave passes through zero.
Because of the gaseous discharge, the protector tube is not suitable for indoor applications or for mounting
in close proximity to other apparatus. Repeated operations also cause erosion of the tube with a gradual
reduction in protection which may result in failure.
C.7.4 dc Arresters
There are several different kinds of arresters available for the protection of dc circuits and equipment
depending upon the voltage and the application. dc capacitor-type arresters are employed for the protection
of dc generators or motors and rotary convertors on electric railway, trolley bus, and mine haulage systems.
These are available in three voltage classes: 0 to 750, 751 to 2000, and 2001 to 3900 as shown in Figures
11, 12, and 13. They are installed either indoors or outdoors and connected from line-to-ground in close shunt
relation to the insulation of the apparatus being protected. Their purpose is to reduce the turn-to-turn stresses
and the major insulation stress from line-to-ground. The inherent characeristics of the capacitor protects the
insulation by sloping off the steep front of the lightning wave and reducing the amplitude of the wave.
For the protection of dc rotating machinery up to 750 V, a valve-type arrester as shown in Figure 14 is also
available. This is a multipath arrester consisting of a silicon carbide block enclosed in a cast iron case for
outdoor use. It is made in two voltage classifications: 100 to 400, and 401 to 750 V. Low voltage low energy
systems such as railway signal and fire alarm circuits may be protected with special signal arresters as shown
Fig. 13. Capacitor-type capacitor arrester, 2001 to 3900 volts. (General Electric)
in Figure 15. These consist of a valve element and a multispear gap enclosed in a transparent vinylite housing.
They are intended for indoor use for the protection of dc circuits up to 75 volts, but may also be used on
ac circuits up to 175 volts.
Fig. 15. Type RVS signal arrester for indoor a-c and dc circuits. (Westinghouse)
Protective characteristics for distribution arresters are shown in Tables 18 and 19 in Section C.9, Protection
of Distribution System.
It is the usual practice when applying lightning arresters to provide a protective margin of 20%. That is, the
arrester sparkover and discharge voltage, plus the voltage drop due to the arrester lead and the ground
resistance, should be 20% less than the BIL of the apparatus being protected as expressed by the following
formulas:
Protective Margin =
Apparatus CWW
100 > 20%
Impulse Sparkover Voltage
Protective Margin =
Apparatus BIL
100 > 20%
Arrester Discharge Voltage + IdRG
IdRG = Voltage drop across ground resistance due to discharge current (Delete if arrester ground wire is
connected to equipment frame.)
CWW = 115% BIL for all filled transformers.
CWW = 100% BIL for dry transformers.
When applying surge arresters, there are three basic items that must be carefully determined: the rating,
the class, and the location.
Page 32
5-11
Protective Levels* Durability Characteristics†
Per-Unit Crest Arrester Rating (1) (2) (3) (4)
Range of
Discharge Voltage. Duty Cycle Initiating Transmission Line High Current
Application Nominal Front-of-Wave 1.2 × 50-µs Switching Surge Pressure Relief
Ratings (kV rms) 10-kA, 8 × 20-µs Surge Discharge Withstand
System Voltage Sparkover Sparkover Sparkover (rms symmetrical amperes)
Wave (crest amperes) (miles) (crest amperes)
(kV)
Station Class Class I Class II
3-9 2.2-12.47 2.24-4.24 1.89-3.30 Test 1.57-1.77 10 000 150 65 000 65 000 25 000
12-15 13.2-18 2.12-2.83 1.89-2.42 not 1.57-1.70 10 000 150 65 000 65 000 25 000
21-48 18-46 2.09-2.56 1.80-2.29 required 1.56-1.70 10 000 150 65 000 40 000 25 000
60-120 69-138 1.99-2.24 1.60-1.94 1.60-1.80 1.56-1.69 10 000 150 65 000 40 000 25 000
©2007 Factory Mutual Insurance Company. All rights reserved.
144-240 161-287 1.83-2.22 1.57-1.70 1.57-1.61 1.56-1.79 10 000 175 65 000 40 000‡ 25 000
258-312 345 2.10-2.17 1.56-1.70 1.57-1.61 1.56-1.58 10 000 200 65 000 25 000 25 000
372 or higher 500 or higher 1.94-2.10 1.65-1.70 1.44-1.58 1.54-1.60 10 000 200 65 000 Not established
Intermediate Class
3-6 2.4-7.2 2.47-2.83 2.24-2.83 Test not 1.77-2.36 5 000 100 65 000 16 100
9-48 7.2-46 2.14-2.55 1.78-2.28 required 1.77-2.07 5 000 100 65 000 16 100
† This refers to the ability of the arrester to protect itself against the stresses resulting from:
(1) Cumulative power-follow current and surge discharge operations (which also determine the ability to reseal against a voltage equal to the arrester rating).
(2) Long-duration lightning.
(3) Severe lightning discharges.
NOTE: Protective level (kV) = per-unit level × rating × √2. For example, range of FOW sparkover for a 12-kV arrester is (2.83 to 3.77) × 12√2 = 48 to 64 kV.
Page 33
5-11
5-11 Lightning and Surge Protection
Page 34 FM Global Property Loss Prevention Data Sheets
The minimum arrester voltage rating selected should be at least 1.25 times the maximum line-to-ground
operating voltage.
1
Actually, under normal conditions, the arrester is only exposed to 58%, ( ) of the system voltage.
√3
For ungrounded or noneffectively grounded systems, the arrester voltage rating should be 100% of the system
voltage rating. While the arrester is exposed to only 58% of the voltage under normal conditions, during a
phase-to-ground fault it will be exposed to full phase-to-phase system voltage.
The voltage ratings for the arresters usually selected for grounded and ungrounded distribution systems are
shown in Table 14.
C.8.4 Shielding
Whether an installation is effectively or noneffectively shielded against direct strokes is of major importance
in providing adequate surge protection.
Page 35
5-11
648 2000 1790-1865 1525-1570 1380-1445 977-1070 1138-1190 1261-1290 1407-1440 1619-1670 1974-1996
684 2000 1880-1960 1610-1680 1455-1525 1031-1130 1153-1260 1331-1360 1489-1520 1709-1765 2063-2107
Table 7a. Protective Characteristics of Intermediate Valve Arresters (ANSI C62.2-1981)
Page 36
5-11
Impulse Sparkover Voltage Switching Surge
Front-of-Wave 1.2 × 50-µs Sparkover Discharge Voltage for 8 × 20-µs Discharge Current Wave
Voltage
Voltage Rating Rate of Rise of kV Crest kV Crest kV Crest kV Crest for kV Crest for kV Crest for kV Crest for kV Crest for
of Arrester Test Voltage (Range of (Range of (Range of 1500 A 3000 A 5000 A 10 000 A 20 000 A
(kV/µs) Maxima) Maxima) Maxima) (Range of (Range of (Range of (Range of (Range of
Maxima) Maxima) Maxima) Maxima) Maxima)
3 25 11-12 11-12 - 5.2-7.5 6-8 6.6-9 7.5-10 8.7-12
6 50 21-21 19-19 - 10.4-13.5 11.9-14 13.2-15.5 15-17.5 17.4-20
9 75 31-32.5 27.5-29 - 15.6-21 17.9-22 19.8-24 22.5-26 26.1-28.5
©2007 Factory Mutual Insurance Company. All rights reserved.
Table 8. Relationships of Nominal System Voltage to Maximum System Voltage and Basic Lightning
Impulse Insulation Levels (BILs) for Systems 1100 kV and Below (ANSI C57.12-1980)
Nominal Maximum System
System Voltage (from ANSI
Voltage C84.1-1977 and ANSI Basic Lightning Impulse Insulation Levels (BILs)
Application (kV rms) C92.2-1978) (kV rms) in Common Use (kV crest)
Distribution 1.2 30
2.5 45
5.0 60
8.7 75
15.0 95
25.0 150 125
34.5 200 150 125
*46.0 48.3 250 200
69.0 72.5 350 250
Power 1.2 45 30
2.5 60 45
5.0 75 60
8.7 95 75
15.0 110 95
25.0 150
34.5 200
*46.0 48.3 250 200
69.0 72.5 350 250
115.0 121.0 550 450 350
138.0 145.0 650 550 450
*161.0 169.0 750 650 550
230.0 242.0 1050 900 825 750 650
345.0 362.0 1175 1050 900 825
500.0 550.0 1675 1550 1425 1300
765.0 800.0 2050 1925 1800
1100.0 1200.0 2425 2300 2175 2050
* Non-preferred voltage (ANSI C84.1-1977)
Notes:
(1) BIL values in bold type-face are listed as standard in ANSI C57.12.10-1977, C57.12.20-1974, C57.12.21-
1980, C57.12.22-1980, C57.12.23-1978, C57.12.24-1978, C57.12.25-1975, and C57.12.26-1975, and
C57.12.30-1977.
(2) When specified, and when suitable surge protection and effective grounding are provided, lower insulation
levels may be used in transformers. For high-voltage systems it is common to use insulation dependent
on the degree of surge protection obtainable. For example, in 230 kV systems, BILs with corresponding
low-frequency tests of 1050, 900, 825, 750, and 650 kV have been used. Application of reduced BILs
is most common on grounded Y-connected systems. In applying ∆-connected transformers with reduced
BILs the system should be reviewed for effective grounding adequacy.
(3) When reduced BILs are involved, internal and external phase-to-phase low-frequency insulation levels
should not be reduced below the values listed in Table 6a.
(4) Single-phase distribution and power transformers and regulating transformers for voltage ratings between
terminals of 8.7 kV and below are designed for both Y and ∆ connection and are insulated for the test
voltages corresponding to the Y connection, so that a single line of transformers serves for the Y and ∆
applications. The test voltages for such transformers when operated ∆-connected are, therefore, higher
than needed for their voltage rating.
(5) For series windings in transformers such as regulating transformers, the test values to ground shall be
determined by the BIL of the series windings rather than by the rated voltage between terminals.
‡ When specified, switching surge tests are normally specified only on one winding of 450 kV BIL and higher.
These voltage values shall be used to establish the limiting induced switching surge voltage in low-voltage windings when a high-voltage
winding is tested.
Notes:
(1) The BIL values of Table 4 are based on ANSI C62.2-1969, using low-sparkover surge arresters and a
5 kA discharge current. If there is any possibility that the transformer terminals will be subjected to
transient overvoltages exceeding their BILs, they should be protected with appropriate surge arresters.
(2) Insulation levels for voltages between listed values of Table 4 may be determined as follows:
(a) Coordinate with available surge arresters per ANSI C62.2-1969, or
(b) Use insulation level for the next higher voltage rating.
(3) When specified, other BILs may be furnished.
In addition to providing effective shielding, substation equipment should be protected against voltage surges
by the proper application of surge arresters. In some cases, these arresters may not afford adequate
protection due to the circuit distance between the arresters and the transformer, the method of grounding,
and the system voltage. In such cases, a separate set of arresters are necessary to protect the transformer.
Although each case should be considered separately, for station equipment rated 23 kV and above having
full BIL insulation, separation distances of 75 to 200 ft can usually be tolerated. For equipment rated 15 kV and
below, the best practice is to avoid any separation distance.
In effectively shielded stations, discharge currents rarely exceed 5000 amperes.
Table 11. Rated Voltages and Insulation Levels for AC Switchgear Assemblies
Rated Voltage (rms) Insulation Levels (kV)
Rated Nominal Rated Maximum Power Frequency DC Withstand* Impulse Withstand
Voltage Voltage Withstand (rms)
Metal-Enclosed Low-Voltage Power Circuit Breaker Switchgear
Volts Volts
240 250 2.2 3.1 —
480 500 2.2 3.1 —
600 630 2.2 3.1 —
Metal-Clad Switchgear
kV kV
4.16 4.76 19 27 60
7.2 8.25 36 50 95
13.8 15.0 36 50 95
34.5 38.0 80 † 150
Metal-Enclosed Interrupter Switchgear
kV kV
4.16 4.76 19 27 60
7.2 8.25 26 37 75
13.8 15.0 36 50 95
14.4 15.5 50 70 110
23.0 25.8 60 † 125
34.5 38.0 80 † 150
Station-Type Cubicle Switchgear
kV kV
14.4 15.5 50 † 110
34.5 38.0 80 † 150
69.0 72.5 160 † 350
From IEEE Std 27-1974.
* The column headed ‘‘DC Withstand’’ is given as a reference only for those using direct-current tests and represents values believed to
be appropriate and approximately equivalent to the corresponding power frequency withstand test values specified for each voltage class
of switchgear. The presence of this column in no way implies any requirement for a direct-current withstand test on alternating-current
equipment. When making direct-current tests, the voltage should be raised to the test value in discrete steps and held for a period of 1 min.
† Because of the variable voltage distribution encountered when making direct-current withstand tests, the manufacturer should be contacted
for recommendations before applying direct-current withstand tests to the switchgear. Potential transformers above 34.5 kV should be
disconnected when testing with direct current. Refer to 6.8 of ANSI C57.13-1968, and in particular to 6.8.2 which reads ‘‘Periodic kenotron
tests should not be applied to transformers of higher than 34.5 kV voltage ratings.’’
Where metal-clad switchgear is supplied directly by means of an overhead metallic sheathed cable, arresters
should be installed at the junction point between the transmission lines and the cable. Whether a set of
arresters is also needed at the switchgear depends upon 1) the length and type of cable, 2) junction arrester
protective level voltages, and 3) method of system neutral grounding.
If the cables are nonmetallic-sheathed types, arresters are required at the switchgear because they have
higher surge impedance than the metallic-sheathed cables which can also be interconnected with the arrester
ground and switchgear ground bus. In this case, station class arresters will afford adequate protection,
although distribution arresters may also be used but will afford less protection. The installation of a neutral
or a ground wire in the same duct with each 3-phase nonmetallic-sheathed cable provides practically the same
surge impedance as continuous metallic-sheathed cable, and surge protection can be applied accordingly.
As a precautionary measure, the momentary capability of the sheath of 3-phase cables should be investigated
before grounding both ends, and special consideration may be necessary for single-phase cable with shields
that cannot be grounded at both ends.
Protection of dry-type transformers against switching surges is of little concern. They are used mostly for
applications involving low voltages and involve high ratios of insulation strength to operating voltage.
Consequently, the magnitude of most switching surges is not high enough to cause damage to dry-type
transformers.
Table 14. Commonly Applied Voltage Ratings of Arresters on Distribution Systems (ANSI C57.12-1980)
System Voltage (kilovolts rms) Usually Applied Arrester Ratings (kilovolts rms)
Four-Wire Three-Wire
Maximum Voltage Delta and Spacer-Cable
Nominal Voltage Multigrounded Unigrounded
Range B* Ungrounded Wye Circuits†
Neutral Wye Neutral Wye
2400 2540 3
4160Y/2400 4400Y/2540 3 6 3
4160 4400 6
4800 5080 6
6900 7260 9 or 9/10
8320Y/4800 8800Y/5080 6 9 or 9/10 6
12 000Y/6930 12 700Y/7330 9 or 9/10 9/10 or 10 9/10 or 10
12 470Y/7200 13 200Y/7620 9 or 9/10 12 9/10 or 10
13 200Y/7620 13 970Y/8070 9/10 or 10 12 9/10 or 10
13 800Y/7970 14 520Y/8380 9/10, 10, or 12 12 12
13 800 14 520 15
20 780Y/12 000 22 000Y/12 700 15 18 18
22 860Y/13 200 24 200Y/13 970 18 21 21
23 000 24 340 25
24 940Y/14 400 26 400Y/15 240 18 21 21
34 500Y/19 920 36 510Y/2180 25 or 27 30 30
34 500 36 510 36 ‡ or 37 ‡
* See ANSI C84.1-1977 and ANSI C84.1a-1980.
† The use of spacer cables at most system voltages has had limited application, reducing the experience factor in establishing arrester
ratings usually applied. Where experience is a factor, arrester ratings lower than 1.5 × nominal system line-to-ground voltage have been
used. This is taken into account for the voltage ratings listed.
‡ Nonstandard distribution arrester voltage ratings.
protection to use a value of 1.25 times the crest of the one minute ac proof test of twice rated voltage plus
100 [1.25 √2 2ELL + 1000)] for the impulse strength of rotating machine insulation. At that time it was agreed
by the machine manufacturers that the impulse strength of the ground wall insulation was well above this value
before being placed in service.
Recently however, a Working Group of the Institute of Electrical and Electronic Engineers has arrived at
the current consensus on the volt-time impulse withstand strength of machine insulation as shown in
Figure 16a and reasonable agreement is likely. Under consideration is the time T2 to reach maximum applied
surge; whether it should be 10 µsec., 5 µsec, or some shorter time, to accurately reflect the insulation
capability on multi-turn machines. It also appears that a single recommendation will apply to both motors
and generators.
Fig. 16a. Probable impulse withstand, volt-time, for a-c rotating machinery.
The envelope of withstand strength shown in Figure 16a is essentially in accord with long-established
manufacturers’ recommendations. It is a composite based on both the impulse strength of ground wall
insulation and impulse strength of turn insulation.
For adequate protection of rotating machines, the following is essential:
1. Effective shielding.
2. Arresters at the machine terminals.
3. Surge capacitors at the machine terminals.
4. Low resistance ground connections, interconnected with the machine frame and the arrester and capacitor.
The complete basic protective circuit for rotating machines is shown in Figure 16b. The arrester AL limits
the incoming voltage and the inductance L and capacitance C lengthen the time to crest and limit the rate
of rise of the voltage at the machine terminal. The second arrester AM limits the magnitude of the voltage from
the machine terminal to its frame.
As illustrated in Figure 16c, there are four different practical methods in use for obtaining the series inductance
and control of the voltage impressed on the LC circuit. Example 1 of this figure shows the use of a choke
coil or reactor as a bumped inductance. Example 2 uses a length of line from 500 feet (152 m) for 650V
machines and 1500 feet (457 m) for all higher voltage machines out to the line arrester AL. Example 3 in
Figure 16c shows a length of cable with a grounded metallic sheath connected between the machine and
the overhead line. The cable must be long to be effective and afford protection with the line arrester AL at the
cable junction. If the cable is not long enough, additional inductance in the form of a choke coil or more line
with another arrester will be required as shown by the dashed lines in Example 3. Example 4 shows a
transformer installed between the machine protection and the line which provides high inductance and a high
degree of protection. With this arrangement all the grounds are readily connected together.
Regarding Example 2, which shows an unshielded time, a stroke hitting the line between the line arrester
and the machine would impair the protection because the full required inductance would not be in series with
the capacitor and the line arrester cannot limit the voltage on the system as effectively as it would for a stroke
hitting ahead of the arrester.
Another disadvantage of this arrangement is that the resistance of the ground connection of the line arrester
should not exceed 2 or 3 ohms. Otherwise the voltage drop due to high currents flowing through the ground
connection when added to the discharge voltage of the arrester could permit voltages which may damage
the turn-to-turn insulation.
If the average number of lightning strokes to a transmission line of 100 times per 100 miles per year is used
in an isokeraunic level (IKL) of 30, the average probability of a stroke on 1500 feet (457.5 m) of line is about
one in 3-1⁄2 years. With the protection illustrated in Example 2, many of the strokes will not be severe enough
to damage the machine.
With the above arrangement the maximum permissible pole and arrester ground resistance RG may be higher
as shown in the following tabulation.
If the above values of ground resistance cannot be obtained, a buried counterpoise connecting all the grounds
together should be installed.
If the shield wire is not used, another method of improving the protection (illustrated in Example 2) is installing
additional line arresters as shown in Figure 17.
Fig. 17. Additional arresters provided for line used to provide inductance and not shielded.
The maximum permissible line arrester ground resistance with arresters spaced 500 ft (152 m) apart is shown
in the following tabulation:
If these values of ground resistance cannot be obtained, a buried counterpoise connecting all grounds
together should be installed.
Where the lightning exposure is severe and grounding conditions are unfavorable and continued operation
of the machine is important, the reliability of protection for Example 2 can be greatly improved by installing a
shield wire grounded at every pole in addition to the line arrester and the machine grounds as shown in
Figure 18.
Fig. 18. Length of line used as inductance with overhead shielded wire.
The length of conductor between the line arrester AL and the machine in Figure 18 should not be less than
500 feet (152.4 m) but it need not be more, and the overhead shield wire should be installed in accordance
with the recommended practice. In general the shielding angle should not exceed 30 degrees. The insulation
between the shield wire and down leads and the line conductors should be able to withstand 250,000 volts
of 1-1⁄2 × 40 microsecond wave shape without flashover.
The basic lightning protective scheme for directly connected machines is shown in Figure 19. This scheme
shows capacitors and arresters at the machine terminal, and in some cases at the neutral of the machine,
and one or more arresters on the line. The phase conductors are also shielded by an overhead ground wire.
The arresters AM and AN limit the magnitude of the surge voltage to a value less than the machine’s
conductor-to-ground insulation strength. The rate of rise of the surge voltage at the machine terminals is also
decreased by the arrester AL, which discharges the majority of the surge current and limits the voltage applied
to the inductance of the transmission line at the capacitor C. Since the value of C and the rating and
characteristics of AL are fixed, it is only necessary to determine the minumum separation D in order to obtain
sufficient inductance.
The protection required for surge-grounded neutral machines and for ungrounded neutral machines up to
and including 6900 volts that are directly connected to exposed overhead lines is shown in Figure 20. Terminal
protection is required on each phase.
For machines rated at 11.5 kV and above metallically connected to exposed overhead lines and not effectively
grounded, the recommended protection is shown in Figure 21. Terminal protection is required on each phase.
Table 15 shows protection levels of station-type arresters of one manufacturer for the protection of rotating
ac machines. These are recommended for large important machines. For smaller machines the distribution
type may be used if the higher cost of the station type is not warranted.
Fig. 19. Basic scheme for providing lightning protection for machines directly connected to overhead lines.
Fig. 20. Protection for surge-grounded neutral machines and ungrounded neutral machines to 6900 volts.
If the machine is not surge grounded at the neutral, then arresters and surge capacitors should be installed
at the neutral or double surge capacitors at the line terminals. (See Fig. 21, Sketch b)
The information in Table 15 is primarily for motors and generators with multiturn windings. In the past, large
generators with single-turn coils in the stator windings and unit connected to delta-wye step-up transformers
properly protected with arresters and effectively shielded from direct lightning strokes were considered as
adequately protected. Experience has shown that the generator can be damaged by positive and negative
surges arriving simultaneously on two phases, ineffective shielding, failure of the high side protective
equipment, and accidental interconnection between the high-side and low-side transformer windings due to
internal failure. Accordingly, the present practice is to recommend the installation of surge arresters at the
terminals of the machine. Capacitors are not required where the generator has single turn coils.
Fig. 21. Protection for machines rated at 11.5 kV and above, metallically connected to overhead lines,
not effectively grounded.
Table 15. Protection Levels of Station-Type Arresters Designed for Machine Protection
Lightning Arrester Rotating Ac Machine
Rating kv Maximum Maximum Discharge Machine Circuit Neutral Not Effectively Grounded
Rms Impulse Voltage kv Crest‡ Grounding Effectively Grounded
Sparkover Impulse Impulse
kv Crest† Standard Withstand Standard Withstand
1500 5000 Voltage 60 Hertz Strength Voltage 60 Hertz Strength
Amperes Amperes Class Sparkover kv Crest Class Sparkover kv Crest
650 Volts* 3 3 3.5 650 3.3 4 650 3.3 4
3 9.5 8 9.5 2400 8.2 10 2400 8.2 10
3 9.5 8 9.5 4160 13.2 16 — — —
4.5 14.5 12 14 4800 15.0 19 4160 13.2 16
6 19 16 19 6900 20.9 21 4800 15.0 19
7.5 24 20 23 — — — 6900 20.9 21
9 28 24 28 11500 33.9 42 — — —
12 37 32 37 13800 40.5 50 11500 33.9 42
15 46 40 47 — — — 13800 40.5 50
16.5 51 44 51 14400 42.1 53
18 55 48 56 Machine voltages in these ratings 16500 48.0 60
are not standardized. Large
19.5 60 52 61 18000 52.3 65
generators usually have
21 64 56 65 impedance grounded neutral. 20000 57.9 72
24 76 67 78 24000 69.2 86
* Standard 3-phase secondary-type valve arrester.
† Sparkover on test wave rising to sparkover voltage in 10 microseconds.
‡ Crest voltage across arrester during discharge of a 1500-ampere or a 5000-ampere 8 × 20 micro-second current.
The ‘‘three point method’’ of insulation coordination as described in the following text is in accordance with
ANSI-C62.2-1981 and the tutorial course on Surge Protection in Power Systems, Course Text 79EH0144-
6-PWR developed by the IEEE - Surge Protection Committee of the IEE Power Engineering Society. This
method makes use of the ratios of insulation withstand to arrester protective levels for 1) front-of-wave, 2) full
wave, and 3) switching surge ranges. In addition, the effect of the length of the leads (‘‘separation effect’’
[SE]), if significant, separating the arrester from the protected equipment is evaluated.
Significant separation occurs where the crest of the voltage of the protected insulation exceeds the arrester
protective level sufficiently to reduce protective margins or ratios to unacceptable levels and must be taken
into consideration.
In this method the basic assumption is made that the insulation will be protected over the entire range of
lightning and switching impulses that can occur in service, provided the margin is adequate at the three points.
There are five standard protective ratios (PR) and protective margins (PM) which are identified as follows:
1. Where separation is not significant.
a) PR(1)=CWW/FOW PM(1)=[PR(1)-1]100
b) PR(2)=BIL/LPL PM(2)=[PR(2)-1]100
c) PR(3)=BSL/SSP PM(3)=[PR(3)-1]100
2. Where there is significant separation.* (See Note below)
d) PR(1S)=CWW/E1 PM(1S)=[PR(1S)-1]100
e) PR(2S)=BIL/E1 PM(2S)=[PR(2S)-1]100
f) PR(3)=BSL/SSP PM(3S)=[PR(3)-1]100
*Separation effects are significant when they result in a PR that is less than 1.15. Table 16 gives the
maximum separation that may be used without violating the 1.15 minimum limit for PR(1S) as shown in
the following tabulation:
PR Limits For Coordination.
PR(1)≥1.2 PR(1S)≥1.15
PR(2)≥1.2 PR(2S)≥1.15
PR(3)≥1.15 PR(3)≥1.15
Note: Table separations are calculated using an incoming surge with a rate of rise of 8.33 crest kV/µs/kV
(rms) of arrester rating.
The multi-line two-transformer stations shown in Figure 23 may be reduced to an equivalent base case by
application of the following rules;
Rule 1. Remove the transformer that is not being considered.
Rule 2.
a) Identify junction c, the common point between transformer lead (S), arrester lead (L), and the line
assumed to have an incoming surge.
b) Identify S as the bus connection between junction C and the transformer.
c) Identify L as the connection between junction C and the surge arrester.
Rule 3. Identify junction t, the common point between the surged line, bus connection to transformer 1, and
bus connection to transformer 2. Note that t and C may be the same point. Also that t does not exist in a
single-transformer station.
A Class A connection has junction t either coincindent with C or on the line side of C.
3Rf
The rate of rise Rf =
n + 2,
Where Rf is the rate of rise of the incoming surge in kV/microsecond. (Use the standard FOW sparkover
test rate of rise.) Rf is the equivalent rate of rise of incoming surge in kV/microsecond at protected equipment
depending upon the number of lines.
To determine the electrical surge separation distance, the distance D from the arrester ground to the protected
equipment is defined as follows:
D = S + L (Fig. 22)
Where S = the combined length of bus and jumper connections between junction C and the protected
equipment terminals.
L = The combined length of bus and jumper connections between junction C and the arrester ground.
The physical distance D and the rate of rise of the surge Rf and the velocity V and the protective level of
the arrester Ef is used to determine the electrical surge distance from the protected equipment as follows:
D = D(Rf/Ef/V)
where D = S + L in feet.
Rf = Rate-of-rise of incoming front, kV/µsec.
Ef = Arrester front of wave sparkover in kV.
V = Traveling wave velocity (1000 ft/µsec for conductors in air, 600 ft/µsec in cable).
Voltage at Transformer
Fig. 24. Curve for determining a =
Voltage at Arrester.
α= D
0.0125 + 476D
If the separation distance D does not exceed the values in Table 16, then separation effects need not be
considered when PR(1) and PR(2) are met.
The rates of rise in switching surges are quite low compared to lightning surges, and separation effects are
correspondingly low. Therefore separation effects can be ignored when checking BSL, SPL coordination.
In applying the 3-point method of insulation coordination as described above, for specific values of front of
wave sparkover (FOW), chopped wave withstand (CWW) and arrester protective levels needed to calculate
the several protective ratios, it is best to procure this information from the arrester manufacturer’s literature
as shown in Table 9. This information is from one specific manufacturer and may vary for other manufacturers.
For proper insulation coordination, the protective ratios (a), (b), (c) or (d), and (e), as applicable must be
satisfied. For example:
CWW
1. Lightning front of wave coordination Point PR(1) calculated from must be equal to or exceed 1.2.
FOW
BIL
2. Lightning full wave coordination Point PR(2) calculated from must be equal to or greater than 1.2
LPL
and
BSL
3. The switching surge coordination Point PR(3) calculated from must be equal to or greater than 1.15.
SSP
In achieving coordination it is possible that the first arrester selected has protective levels that will not
coordinate with the desired insulation withstand levels. When this occurs other alternatives must be
considered such as: 1) an arrester with a lower lightning or switching surge protective level involving a different
class, design or voltage rating; 2) changing the arrester location to reduce the separation distance S, or
arrester lead length L or both; 3) increasing the insulation level of the equipment to be protected; 4) improving
the shielding; 5) installing additional arresters at a different point in the station.
In lieu of the availability of specific information, the following approximate factors can be used to estimate
the withstand voltages of mineral-oil-immersed equipment. For insulation coordination the front-of-wave factor
should be checked with the equipment manufacturer.
NOTE: Protective level (kV) = per-unit level × rating × √2. For example, range of FOW sparkover for a 12-kV
arrester is (2.83 to 3.77) × 12 √2 = 48 to 64 kV.
On 15-kV systems insulation coordination for equipment connected to overhead lines has been more or less
neglected because the protective margin (PM) between the standard equipment basic lightning impulse
insulation level (BIL) and the protective characteristics of modern distribution arresters is usually substantially
more than 20%. However, on distribution systems rated at 25 kV and higher, insulation coordination is quite
important especially where reduced BIL values are used for line protection and for protection of underground
distribution systems.
The following arrester applications require special consideration with respect to duty requirements to which
the arrester is subjected or in regard to protection requirements: 1) protection of shunt capacitor banks,
2) protection of switches, reclosers, etc., 3) protection of voltage regulators, 4) protection of underground
circuits; and 5) exposure to contaminated atmospheres.
1. For four-wire multi-grounded-wye open wire circuits the nominal phase-to-ground voltage of the system
is multiplied by 1.25.
2. For spacer-cable circuits the nominal phase-to-ground voltage of the system is multiplied by 1.50. For
open-wire systems having operating voltages not listed in Table 21, the 1.25 factor should be used to
determine the arrester rating and the 1.5 factor for spacer-cable circuits.
When arresters cannot be installed at individual equipment locations in the underground system, they are
located at the junction of the overhead line conductors and the underground cable. Recently, consideration
has been given to installing arresters on underground transformers on systems rated at 15 kV and above
in order to provide larger protective margins for the transformers. The voltages that propagate into the
underground cable after sparkover of the arrester at the riser pole is the sum of the arrester sparkover voltage
plus the inductive voltage drop in the arrester connecting leads. These voltages as they propagate in the
cable may double their value due to reflections at open switches, terminating transformers, and similar points
where there is a change in impedance.
For the determination of protective margins, the following rules should be used to calculate the voltages at
terminating points.
1. Assume no attenuation. This is a conservative assumption for cables that exceed 300 feet (91.5 m) in
length.
2. Assume incident voltages will double at open points and terminating transformers.
3. Use manufacturers’ published values for front-of-wave sparkover and discharge voltage at 10 kA.
4. Calculate inductive voltage drop in arrester connecting leads based on 1.6 kV per foot.
5. Compare double front-of-wave sparkover voltage with chopped wave withstand for liquid-filled
transformers and with BIL for dry-type transformers. Compare the doubled sum of discharge voltage, at
assumed current, and connecting lead voltage with transformer BIL.
Then, using the recommended protective margin of 20%:
Oil: CWW ≥ 1.2 × 2 × FOW
Dry: BIL ≥ 1.2 × 2 × FOW
Both: BIL ≥ 1.2 × 2 × (IR + Vlead wire)
Fig. 25. Sample one-line diagram (partial) for examples 1 and 2. (for evaluation of adequacy of transformer surge
protection using methods of ANSI/IEEE standard C62.2-1981).
Assumptions:
1. Transformer BIL is 250 kV (fully insulated), chopped wave withstand insulation level (CWW) is 290 kV.
(See Table 9.)
2. Station class surge arresters are provided with 3 circuit feet of transformer primary bushings. Separation
effect (α factor) is negligible.
3. Surge arresters are of the series-gapped, valve-type of modern manufacture.
4. The surge arrester ground terminal leads are connected directly to the transformer ground connection,
minimizing effects of ground (earth) resistance on surge behavior of the arrester-transformer system.
Note: The values used for surge arrester characteristics in these calculations are chosen from a single
manufacturer’s tables. Characteristic values for surge arresters of other manufacturers or series may vary
slightly from those used here.
Calculations:
CWW 290
PR(1) = + = 2.42
FOW 120
Limit from
ANSI C62.2-1981 Values used:
1.2 (min) CWW = 290 kV
FOW = 120 kV
(39 kV Station Class surge
arresters used)
BIL 250
PR(2) = + = 2.40
LPL 104
Limit from
ANSI C62.2-1981
1.2 (min)
LPL = The greater of 1.2 × 50 µs sparkover voltage - 104 kV BIL = 250 kV or lightning discharge voltage
at selected current - 102 kV LPL = 104 kV, (assuming 20 kA discharge current)
Note: Switching surge protective margins PR(3) are not considered here, because experience has shown
that switching surges are not troublesome at this voltage level.
Conclusions:
Since both PR(1) and PR(2) are larger than the limits specified in the referenced standard, surge protection
is adequate.
Example No. 2 (Ref. ANSI Standard C62.2-1981, Section 3.9)
Determine adequacy of surge protection for 1500-kVA dry-type transformer (2) in Figure 25.
Assumptions:
1. Transformer BIL is 60 kV (standard BIL; see ANSI/IEEE Standard C57.12.01-1979 or Table 10).
2. Distribution class surge arresters of the low sparkover type are installed in the transformer enclosure,
as close as is practical to the transformer primary connections.
3. The surge arresters are of the series-gapped, valve type of modern manufacture.
4. The surge arrester ground terminal leads are connected directly to the transformer ground connection,
minimizing effects of ground (earth) resistance on surge behavior of the arrester-transformer system.
5. The 13.8-kV distribution system is not effectively grounded (low-resistance grounded scheme), requiring
the use of fully-rated (15-kV) arresters.
Note: The values used for surge arrester characteristics in the following calculations are chosen from a
single manufacturer’s tables. Characteristic values for surge arresters of other manufacturers or series may
vary slightly from those used here.
Calculations:
Values used
Minimum BIL = 1.2 (FOW) FOW = 56 kV (from
55.2 = 1.2 (46) manufacturer’s literature)
Conclusions:
The specified minimum BIL is 55 kV; the transformer’s as-supplied BIL is 60 kV. Therefore, insulation
coordination is satisfactory.
Note: This example uses the most favorable conditions to prove satisfactory insulation coordination. If the
dry-type transformer was built with a lower BIL value, was connected to an exposed overhead line, or if
different surge arresters were used, insulation coordination may not be achieved.
Example No. 3
I. Evaluation of Surge Protection (See Figs. 26 and 27.)
Fig. 26. Plan view and schematic of substation shown in Figure 27.
Notes:
1. The characteristic values chosen for transformer transient insulation levels in this example are those which
a transformer built to ANSI/IEEE Standard C57.12.00-1980, IEEE Standard General Requirements For
Liquid-Immersed Distribution, Power, And Regulating Transformers, would possess. Proper evaluation of
a specific case requires that these values be obtained from the transformer manufacturer.
2. The characteristic values chosen for surge arrester performance in this example are taken from the
manufacturer’s literature for a specific model of 60 kV, station class, gapped, valve-element-type surge
arrester. Proper evaluation of a specific case requires that these values be obtained from the surge arrester
manufacturer.
3. The methods presented in this example will provide good results when properly applied. For critical and/or
complex cases, the use of a computer model may provide more accurate results and different conclusions.
4. These methods are not applicable to use of the gapless, metal-oxide surge arresters. For application of
those devices, consult the arrester manufacturer.
A. Information Required
1. System characteristics:
Nominal voltage. The voltage at which the surge protection is to be applied. For this example, 69 kV is used.
Degree of Grounding. Also called the grounding coefficient. This value is dependent on the zero and positive
sequence characteristics (X0, X1, and R0) of the electrical system at the point where the arrester is
connected. For this example, the system is considered effectively grounded. That is, the following conditions
are met:
Xo R0
( X1
≤ 3 and
X1
≤1
)
Available Short Circuit Current. At the point of surge arrester application. This value should be determined
by calculation (may be obtained from the supplying electric utility), and should not exceed the pressure relief
characteristics for the arrester chosen. For this example, it is assumed that the proper arrester class is used.
Temporary Overvoltage History. At the arrester location. This aspect should be discussed with the supplying
electric utility, and may influence arrester voltage rating. For this example, it is assumed that the proper
arrester voltage rating has been chosen.
Physical Arrangement of Equipment. From construction drawings. For this example, see Figure 27.
2. Characteristics of equipment to be protected:
BIL, Front of Wave, Withstand, CWW, BSL.
Obtained from nameplate, manufacturer’s specifications, or construction standards. For this example, the
transformer is assumed to conform to the ANSI/IEEE construction standard, and the following values are
chosen:
BIL — 350 kV
Front of Wave Withstand.
580 kV
CWW — 400 kV
BSL — 280 kV
CWW 400 kV
= = 2.4
FOW 170 kV
Step B.
Compare equipment BIL to surge arrester lightning protective level (LPL). LPL or let-through-level is defined
as being the higher of the 1.2 × 50 µsec sparkover value or the arrester discharge voltage (IR). To determine
the arrester discharge current for an effectively shielded location (that is, where the incoming lines are
protected by an overhead shield wire for at least 2500 ft from the station, and the station itself is properly
shielded from a direct lightning stroke), the following values may be used.:
BIL 350 kV
= = 2.5
LPL 141 kV
BSL 280 kV
= = 2.1
SSP 136 kV
Step 1
Remove transformers that are not under consideration.
In this simple, symmetrical station, either transformer may be studied. It is assumed that the results will hold
true for either transformer. In this example, Transformer 1 is being evaluated; Transformer 2 is removed.
The equivalent circuit now looks like Figure 28. (Disconnect switches and circuit breakers are not shown.)
Step 2
Refer to Figure 29. Identify junction ‘‘c’’, the common point between the line having the incoming surge, the
arrester connection, and the transformer connection. Identify the distance, ‘‘S’’, between junction ‘‘c’’ and
the transformer bushings. Identify the distance, ‘‘L’’, between junction ‘‘c’’ and the arrester’s connection to
the ground mat, exclusive of arrester length.
In this example, it is assumed that the 69-kV line from the utility substation ‘‘A’’ is the surged line.
Step 3
Identify junction ‘‘t’’, which is the common point between the surged line, the bus connection to Transformer
1, and the bus connection to Transformer 2. Junctions ‘‘t’’ and ‘‘c’’ may be the same point, or may be different
points. If junction ‘‘t’’ is not on the surged line side or coincident with junction ‘‘c’’, the value of α calculated
below must be increased by 5%.
In this example, junctions ‘‘c’’ and ‘‘t’’ are coincident.
Step 4
Remove any lines connected between the arrester terminal and junction ‘‘c’’. In this example, there are no
lines connected between these points.
Step 5
Multiply Rf (defined below) by 3/(n + 2) where n is equal to the number of lines remaining after Step 4 is
completed.
In this example, two lines (one from substation A and one from substation B) remain connected, so Rf will
be multiplied by 3/(2 + 2), or 0.75.
V. Separation Effect Calculations
A. Reduce station to the base case equivalent per IV above.
B. The following parameters will be used:
S = The distance in circuit feet between junction ‘‘c’’ and the protected equipment terminals. See
Figure 29.
L = The distance in circuit feet between junction ‘‘c’’ and the surge arrester’s connection to the ground
mat, less the length of the arrester body.
D = S+L
Rf = The rate of rise of the incoming surge in kV/µsec. For most calculations, the following may be used:
Example
_ D (Rf/Ef) D = 78 (375/170)
1. D = 1000
v
D = 0.17
_ α= 0.17
2. α = D 0.0125 + (0.476)(0.17)
0.0125 + 0.476(D) α = 1.82
3. Ei1 = (α)Ef1 Ei1 = (1.82)(170)
Ei1 = 309 kV
4. Ei2 = (α)Ef2 Ei2 = (1.82)(141)
Ei2 = 257 kV
experience has been obtained with the assumptions implicit in the preceding rules: a) The full BIL strength
will apply for front times between 8 and 50 µs. b) Minimum switching surge withstand occurs between 50 and
2000 µs.
Arrester Curve. Approximate sparkover curve as follows:
A. Plot three points for the following published sparkover voltages for the specific arresters to be installed:
1) front-of-wave, 2) 1.2 × 50 sparkover (at 8 µs), and 3) switching surge protective level as a straight line from
about 30 to 2000 µs. Connect the points with a curve of approximately the shape shown. If a manufacturer’s
voltage-time sparkover curve is available, it may be used instead of the approximation.
B. Draw a ladder of lines each extending from 5 µs to 10 µs at levels corresponding to 5 kA, 10 kA, and
20 kA discharge voltage. Add a similar line passing through the 1.2 × 50 µs sparkover.
Two additional points, corresponding to FOW and LPL when separation effects are considered, are shown
in Figure 30 for illustrative purposes. If separation between the arresters and the protected equipment is
significant, the method described elsewhere in this data sheet will provide a satisfactory means of evaluating
separation effects.
How to Use the Curve
The criteria of both 1. and 2. must be met for satisfactory coordination:
1. Locate the point between 0.5 and 50 µs where the separation between withstand and arrester curve(s)
is minimum. (Treat 1.2 × 50 sparkover and selected discharge kA lines as separate curves.) Calculate
PR = Withstand voltage/Arrester voltage
PR must be equal to or greater than 1.20 at this point.
2. Make a similar check between 50 and 2000 µs. PR must be equal to or greater than 1.15.