Fire Pump Testing - Periodic Operational Test

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5
At a glance
Powered by AI
The key takeaways are that periodic testing of fire pumps helps ensure they will operate properly in the event of a fire. Testing verifies pumps will start automatically and operate without failure. It also helps identify any issues that require correction.

The purpose of periodic fire pump testing is to verify that the pumps will start automatically and operate without failure when needed. Testing helps ensure the pump will operate without mechanical difficulty and protect the facility if a fire should occur.

The steps involved in conducting a periodic fire pump test are to notify the alarm company, start the pump, check the pump packing glands, check for issues, record system data, run the pump for the required time, check for overheating, shut down the pump manually, restart the jockey pump, and notify the alarm company. Any issues identified during testing should be analyzed and corrected.

RISK CONTROL

REDUCE RISK. PREVENT LOSS. SAVE LIVES.

Fire pump testing periodic operational test

Introduction
The following covers the basic concept of periodic start testing of electric motor and diesel engine driven fire pumps.
Testing helps verify that the pumps will start automatically and operate without failure when needed. Periodic means
weekly for diesel engine driven fire pumps or monthly for electric motor driven pumps.

This information provided is not intended to cover all aspects of the periodic maintenance needed by a fire pump system,
its drivers, fuel supplies, power supplies or back-up power supply mechanisms. It is not intended to cover the testing of
fire pumps driven by gasoline engines, steam engines or other types of drivers, although many of the procedures are
similar. Nor does the test cover the annual flow test that should be completed on all fire pumps to help verify that the
pumps are operating at the manufacturers specifications. The procedures in this document are not intended to comply
with any governmental regulations.

Procedures
The periodic operational test of all fire pumps should be conducted by running the pump in a no-flow or churn situation
with all valves open as per normal. Qualified operating personnel should monitor the pump while the pump is running.
Each pump should run for the proper time interval and be observed for problems. This document contains checklists for
an electric motor and a diesel engine driven pump. The proper checklist should be used to record vital data about the
pump and to help identify abnormalities in the operation of the pump. Any abnormalities should be corrected immediately
or noted for future correction. If any major malfunctions, such as smoke, excessive vibration, or excessive noise are
witnessed, discontinue the test immediately and repair equipment as soon as possible.

A. Test procedure: The periodic pump operational test is part of the overall preventive maintenance procedures for a
fire pump. The run test helps ensure that the pump will operate without mechanical difficulty and protect the facility if a
fire should occur.

1. Notify the alarm company that the fire pump is going to be tested.

2. Start the pump with a drop in system pressure. To do this, open the drain cock located near the pump controller with
the jockey pump turned off. Record the pump starting pressure.

3. Check the pump packing glands to verify that a slight discharge of water is visible. If no water is dripping, adjust the
packing gland nuts appropriately.

4. Check for excessive vibration, unusual noise, or other signs of malfunction. Make corrections as needed. Discontinue
the test if destructive failure appears imminent. Make repairs as soon as possible. If all appears normal continue with
the test.

5. Record the system suction and discharge pressures. Record other system data as listed on the appropriate checklist.

6. Verify that the pump operates for the appropriate time period; a minimum of 10 minutes for electric motor driven
pumps and 30 minutes for diesel engine driven pumps.

7. Periodically verify that the pump and driver are not overheating during the test.

8. Shut down the pump manually.

9. Turn the jockey pump back on. Restore the fire pump controller to the automatic start position.

10. Notify the alarm company that the test is complete and that the alarm system should be put back to normal service.

B. Interpretation of test results: Once test data is recorded, compare it to previous tests to determine if the pump is
operating satisfactorily. Significant differences in operation should be analyzed as to the cause. Corrective actions
should be completed as soon as possible and the pump retested.

PAGE 1
RISK CONTROL

Fire pump testing periodic operational test

Maintenance
Fire pump components should receive preventive maintenance. As with any mechanical device the fire pump needs
inspection, lubrication, fluid checks and changes, cleaning and testing. The following systems are typically part of a fire
pump and require scheduled preventive maintenance: pump systems; mechanical transmission components; electrical
systems; diesel engine systems; exhaust systems; lubrication systems; cooling systems; and battery systems.

The best resource for a preventive maintenance program for a fire pump is from the fire pump manufacturer. Fire pumps
should be maintained in accordance with manufacturers specifications; the procedures in this paper are suggested
guidelines. NFPA 25 also suggests schedules for weekly, monthly, quarterly and annual inspection, testing and
maintenance of these systems.

Fire pumps also should receive annual full-flow testing to measure the pumps flow and pressure performance against the
manufacturers rating of the pump. Any significant reduction in pump performance should be investigated and/or repaired
immediately.

Conclusion
Fire pumps are required at many facilities to provide the needed pressure for the sprinkler and fire hose standpipe
systems. Without a fire pump these systems would not operate adequately. Proper testing and maintenance of fire pump
systems is critical to maintaining fire protection for such facilities. The testing procedures and checklists in this guide can
help increase the reliability of a fire pump. The checklists included at the end of this document can be used as they are or
they can be adapted for a particular facility and fire pump installation.

References
National Fire Protection Association. Inspection, Testing and Maintenance of Water-based Fire Protection Systems.
NFPA 25 Quincy, MA

Engineering and Safety Service (ISO). Fire Protection Report FP-43-04, Fire Pumps American Insurance Services
Group, Inc. New York, NY.

Note: The checklists begin on the following page.

PAGE 2
RISK CONTROL

Fire pump testing periodic operational test

FIRE PUMP
WEEKLY TESTING AND INSPECTION CHECKLIST
(Diesel Engine Driven)

By: __________________________________________________ Date: __________________________________

Before testing the fire pump, contact the alarm receiving station at telephone #: ____________________________

WEEKLY TESTING AND INSPECTION


ITEM STATUS
Yes No N/A
o o
Pump room heat maintained at 40 F? (70 F for diesel engines without heaters?)
Piping valves (suction, discharge and bypass) open? (Test header valve is closed?)
Water-jacket heater or other engine heater operating?
Room ventilation louvers free to operate?
Suction reservoir full?
Wet pit suction screens unobstructed and in place?
Both banks of the batteries' voltage readings normal?
Both banks of the batteries' charging current readings normal?
Both banks of the batteries' pilot lights on or battery failure pilot lights off?
Electrolyte level in batteries normal?
Battery terminals free from corrosion?
Engine crankcase oil level normal?
Engine cooling water level normal?
Engine hours Start of test __________ hours
Pump started automatically by dropping pressure? Start pressure __________ psi
Pump running suction pressure normal? __________ psi
Pump running discharge pressure normal? __________ psi
Pump running oil pressure normal? __________ psi
o
Engine coolant temperature normal? __________ F
Pump packing glands have slight water drip? (The water drip cools the packing)
Pump casing temperature within proper range (not hot to the touch)?
Heat exchanger temperature within proper range and has visible water flow to drain?
Water piping in good condition (no leaks from joints, cracks, etc.)?
Relief valve operational?
Pump run at churn (no flow) for at least 30 minutes?
Engine hours End of test __________ hours
Fuel tank at least two-thirds full?
Pump controller selector in "AUTOMATIC" position?
All alarm pilot lights off?

A "no" response above indicates the need for investigation and corrective action to restore the system to normal
operation. These weekly inspection and test items are considered minimum requirements. The manufacturers' inspection
and test requirements for the pump and engine may be more comprehensive and should be followed at all times.

Additional Comments: ____________________________________________________________________________


___________________________________________________________________________________________________________

___________________________________________________________________________________________________________

After testing the fire pump, contact the alarm receiving station to verify alarms were received and restore alarm
system to normal status.

PAGE 3
RISK CONTROL

Fire pump testing periodic operational test

FIRE PUMP
MONTHLY TESTING AND INSPECTION CHECKLIST
(Electric - Motor Driven)

By: __________________________________________________ Date: __________________________________

Before testing the fire pump, contact the alarm receiving station at telephone #: ____________________________

MONTHLY TESTING AND INSPECTION


ITEM STATUS
Yes No N/A
o
Pump room heat maintained at 40 F?
Piping valves (suction, discharge and bypass) open? (Test header valve is closed?)
Suction reservoir full?
Wet pit suction screens unobstructed and in place?
Pump started automatically by dropping pressure Start pressure __________ psi
Pump running suction pressure normal? __________ psi
Pump running discharge pressure normal? __________ psi
Pump packing glands have slight water drip? (The water drip cools the packing)
Circulating relief valve has adequate flow while pump is running? (Cools pump)
Pump casing temperature within proper range (not hot to the touch)?
Water piping in good condition (no leaks from joints, cracks, etc.)?
Oil level in sight glass normal? (vertical pumps only)
Relief valve operational? (if provided)
Pump run at churn (no flow) for 10 minutes?
Pump controller pilot light (power on) illuminated?
Pump controller pilot light (transfer switch) illuminated?
Reverse phase pilot light off or normal phase pilot light on?
Exercise isolating switch and circuit breaker?

A "no" response above indicates the need for investigation and corrective action to restore the system to normal
operation. These weekly inspection and test items are considered minimum requirements. The manufacturers' inspection
and test requirements for the pump and motor may be more comprehensive and should be followed at all times.

Additional Comments: ____________________________________________________________________________


___________________________________________________________________________________________________________

___________________________________________________________________________________________________________

___________________________________________________________________________________________________________

___________________________________________________________________________________________________________

After testing the fire pump, contact the alarm receiving station to verify alarms were received and restore alarm
system to normal status.

IMPORTANT! To save a copy of this form once filled in, you must choose File/Save As from the top menu bar, give it a
unique name and save a copy to your computer. You may also print out a completed copy by clicking on the Print Form
button.

PAGE 4
RISK CONTROL

Fire pump testing periodic operational test

For more information, log in to the Risk Control Customer Portal at travelers.com/riskcontrol. (Need help? Read
our Registration Quick Guide.) You also can contact your Risk Control consultant or email Ask-Risk-
[email protected].

travelers.com

The Travelers Indemnity Company and its property casualty affiliates. One Tower Square, Hartford, CT 06183

The information provided in this document is intended for use as a guideline and is not intended as, nor does it constitute, legal or professional advice. Travelers does not
warrant that adherence to, or compliance with, any recommendations, best practices, checklists, or guidelines will result in a particular outcome. In no event will Travelers or
any of its subsidiaries or affiliates be liable in tort or in contract to anyone who has access to or uses this information. Travelers does not warrant that the information in this
document constitutes a complete and finite list of each and every item or procedure related to the topics or issues referenced herein. Furthermore, federal, state or local
laws, regulations, standards or codes may change from time to time and the reader should always refer to the most current requirements. This material does not amend, or
otherwise affect, the provisions or coverages of any insurance policy or bond issued by Travelers, nor is it a representation that coverage does or does not exist for any
particular claim or loss under any such policy or bond. Coverage depends on the facts and circumstances involved in the claim or loss, all applicable policy or bond
provisions, and any applicable law.

2008-2012 The Travelers Indemnity Company. All rights reserved. Travelers and the Travelers Umbrella logo are registered trademarks of The Travelers Indemnity
Company in the U.S. and other countries. 209
PAGE 5

You might also like