A deluge valve is a quick release, hydraulically operated diaphragm valve used in deluge systems for fast application of water in a spray system. It has three chambers and operates by venting the top chamber on detection of fire, allowing water flow.

The main types of trim discussed are basic trim, wet pilot trim (hydraulic release), dry pilot trim (pneumatic release), and test and alarm trim. Each type has different components for detection and actuation.

DELUGE VALVE

MODEL-H

TECHNICAL DATA :
MODEL NOMINAL SIZE MAXIMUM SERVICE PRESSURE THREADED OPENING MOUNTING H 200, 150, 100 and 80 NB 12 Bar ( 175 psi )

BSPT Vertical or Horizontal mounting 25 Kg./sq.cm. ( 355 psi )

FACTORY HYDROSTATIC TEST PRESSURE FLANGE CONNECTION RECOMMENDED FLOW RATE

ANSI B 16.5 #150 200NB- 300 to 1150 m3/hr 150NB - 170 to 650 m3/hr 100NB - 50 to 225 m3/hr 80NB - 30 to 110 m3/hr 200NB 150NB 100NB 80NB 44.00metres 35.00metres 15.00metres 10.50metres

LISTED 9P76

FRICTIONAL LOSS IN TERMS OF EQUIVALENT LENGTH OF PIPE (C-120) WET PILOT SPRINKLER HEIGHT LIMITATION NET WEIGHT WITHOUT TRIM

DESCRIPTION
Deluge Valve is known as a system control valve in a deluge system, used for fast application of water in a spray system. To protect areas such as power transformer installation, storage tank, conveyor protection and other industrial application etc. With the addition of foaming agent they do protect Aircraft hangar and inflammable liquid fire.

As per graph in the catalogue. 200NB 150NB 100NB 80NB 172 101 69 46 Kg. Kg. Kg. Kg.

VALVE OPERATION
HD Deluge valve is a quick release, hydraulically operated diaphragm valve. It has three chambers, isolated from each other by the diaphragm operated clapper and seat seal. While in SET position, water pressure is transmitted through an external bypass check valve and restriction orifice from the system supply side to the top chamber, so that supply pressure in the top chamber act across the diaphragm operated clapper which holds the seat against the inlet supply pressure because of the differential pressure design. On detection of fire the top chamber is vented to atmosphere through the outlet port via opened actuation devices. The top chamber pressure cannot be replenished through the restricted inlet port, and the upward force of the supply pressure lifts the clapper allowing the water flow to the system piping network and alarm devices.

FINISH APPROVAL

Fire red epoxy painted Except 200NB all other sizes are UL listed. 1. Size of valve. 2. Flange specification. 3. Valve trim vertical or horizontal. 4. Trim type - Dry pilot, Wet pilot, Electric, Test and alarm.

ORDERING INFORMATION

TRIM DESCRIPTION
a) BASIC TRIM
The basic trim is required on all HD Deluge valve regardless of release system. It contain those components which are required in all types of installation, such as the Main drain valve, Priming connection, Drip check valve, Emergency release valve and pressure gauges. JANUARY, 2006 PAGE 1 OF 14 HD103

b) DRY PILOT TRIM (PNEUMATIC RELEASE)

Dry pilot operation uses a pilot line of closed Sprinkler/ QB detector containing air under pressure, located in the area to be protected. It requires regulated dry air supply with main supply point through restricted orifice. The air pressure to be maintained as specified in the catalogue of Dry Pilot Actuator, Model-H. The pilot line is connected to air inlet side of actuator. The top chamber of the deluge valve is connected to water inlet side of actuator. When there is an air pressure drop, or due to release of any of the release device on detection of fire, the diaphragm of actuator is lifted and allows the water to drain. This releases the water pressure in the top chamber of the deluge valve, allowing the deluge valve to open and water to flow into the system piping & alarm devices. Recommended air supply pressure for dry pilot trim system is 3 to 4 kg/sq.cm.

priming valve fully. Open the upstream side of the stop valve provided below the Deluge valve. No water should flow into the system. Note : The valve can be reset without undergoing above procedure, by just closing / replacing the release device as valve is auto reset type. The reset time may be long or cause vibration while closing depending on back pressure at the outlet of the valve.

CAUTION
(a) Do not close the priming valve, down stream and upstream stop valves, while the system is in service. (b) The releasing device must be maintained in the open position, when actuated, to prevent the deluge valve from closure. (c) While using a Deluge valve in the wet pilot system the height and the length of the wet pilot detection line is to be limited as shown in the wet pilot sprionkler height limitation graph. (d) Do not connect the Sprinkler Alarm outlet drainline to close a common drain as it may create back pressure and Sprinkler Alarm may not function. (e) Deluge valve must have support to absorb sudden opening or closing vibration shock to the piping. (f) The responsibility of maintenance of the protection system and devices in proper operating condition lies with the owner of the system.

c) WET PILOT TRIM ( HYDRAULIC RELEASE )


Wet pilot operation uses a pilot line of closed sprinklers containing pressurized water, supplied through the upstream side of the Deluge valve, through a restricted orifice. All the release lines are connected to a common release line. Due to release fo any one of the release device, the water presure in the top chamber of the Deluge valve drops, and the Deluge valve opens.

d) ELECTRIC RELEASE TRIM

To actuate a Deluge valve electrically, a solenoid valve is provided to drain the water from the top chamber of the Deluge valve. A pressure switch is provided to activate an electric alarm, to shut down the desired equipement or to give "Tripped" indication to the Deluge valve. In addition to this a pressure switch can also monitor "Low air pressure" and "Fire condition" when used in dry pilot air line.

SYSTEM TESTING PROCEDURE


(i) Keep the upstream side of the stop valve partially open. To avoid water flow to system side close the system side stop valve. This valve is to be kept in open position after the testing is completed.

e) TEST AND ALARM TRIM WITH SPRINKLER ALARM

This trim is supplied with the sprinkler alarm bell, which bells on actuation of the Deluge valve. A test valve is provided to test the normal operation of the sprinkler alarm bell.

RESETTING PROCEDURE FOR THE DELUGE VALVE


(i) ii) Close the upstream side stop valve provided below the deluge valve. Open both the drain valves and close when the flow of water has ceased.

(ii) Let any of the release devices to trip. This will result in a sudden drop of water pressure in the deluge valve top chamber resulting the deluge valve to open. Close the upstream side stop valve immediately. (iii) Reset the valve as per the procedure given under heading "RESETTING PROCEDURE FOR THE DELUGE VALVE".

INSPECTION AND MAINTENANCE


Installed system piping network must be flushed properly before placing the Deluge valve in service. A qualified and trained person must commission the system. After few initial successful test an authorized person must be trained to perform inspection and testing of the system. It is recommended to have regular inspection and test run of the system as per NFPA

(iii) Close the release device/replace the Sprinkler if release was through Sprinkler/Q.B.Detector. iv) Inspect and release if required, or close the section of the detection system subjected to "Fire condition". (v) In case of dry pilot detection system, open the air supply valve to build-up air pressure. Open the

JANUARY, 2006

PAGE

2 OF 14

HD103

guideline or in accordance to the organisation having local jurisdiction.

(ii) FALSE TRIPS


(a) Check for clogging in priming line, restriction orifice check valve, priming valve & strainer. (b) Leakage in the release system. (c) The deluge air panel orifice clogged or low supply pressure.

(i) WARNING
Inspection and testing is to be carried out only by authorised and trained personnel. DO NOT TURN OFF the water supply or close any valve to make repair(s) or test the valve, without placing a roving fire patrol in the area covered by the system. Also inform the local security personnel and central alarm station, so that there is no false alarm signal. It is recommended to carry out physical inspection of the system at least twice in a week. The inspection should verify that all the control valves are in proper position as per the system requirement and no damage has taken place to any component.

(iii) LEAKAGE THROUGH THE DELUGE VALVE


(a) Damaged deluge valve seat or obstruction on the seat face by foreign object. (b) Leakage in release system. (c) Partly clogged priming line restriction orifice check valve. (d) Low air pressure on release system line or leakage in release system.

(ii) NORMAL CONDITION


(a) All main valves are open and are sealed with tamper proof seal. (b) Drain valves must be kept closed. (c) No leak or drip is detected from the drip valve. (d) All the gauges except the system side water pressure gauge, should show the required pressure. (e) There should be no leakage in the system.

(iii) NORMAL CONDITION TEST


(a) The system should be checked for normal condition at least once in a week. (b) Test the sprinkler alarm bell or electric alarm by turning the alarm test valve to the test position. The alarm should sound. This test should be carried out at least once in a week. (c) Depress the drip valve knob. Significant water accumulation indicates a possible seat leakage. (d) Conduct the water flow test as per the procedure of system testing at least once a month.

(iv) PERIODIC CHECK

Conduct the water flow test by actuating few of the release devices provided in the system.Clean all strainer(s) and priming line restriction.This test is to be carried out at least once in three months.

ABNORMAL CONDITION
(i) ALARM FAILS TO SOUND
(a) Check for any obstruction in the alarm test line, make certain that the sprinkler alarm is free to operate. (b) If an electric alarm is provided, check the electrical circuitry to the alarm.

JANUARY, 2006

PAGE

3 OF 14

HD103

DELUGE VALVE MODEL - H SIZE 200/150 / 100 / 80 NB


18 20 19

15
14

16 17
B 3

13
12

DIMENSION
VALVE NOMINAL SIZE 200 NB 150 NB 100 NB 80 NB

in millimeter ( Approximate )

21

'A' 552 462 412 372

'B' 360 321 290 272

10
9

8 7 5 4 2 1

6 3

A 3

PART LIST
ITEM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 200 NB 3641 9147 9135 3646 8537 9112 3645 3648 9986 3650 3643 3647 3644 8806 3651 9047 3655 9982 3649 2514 9019 PART NO. 150 100 NB NB 2421 9147 9135 2426 9783 9112 2425 2428 9986 2432 2423 2427 2424 9151 2433 9047 2431 9787 2429 2514 9019 2501 9147 9135 2506 9784 9112 2505 2508 9986 2511 2503 2507 2504 9151 2512 9047 2510 9788 2509 2514 9019 80 NB 2781 9147 9135 2785 9791 2789 2787 9986 2791 2784 2786 2788 9151 2792 9058 2793 9982 2783 2514 9018 DESCRIPTION HOUSING LOCK NUT HEX NUT SEAT "O" RING HEX HEAD BOLT RUBBER CLAMP RUBBER SEAT "O" RING SPINDLE CLAPPER DIAPHRAGM CLAMP RING HEX HEAD BOLT SPRING HEX HEAD BOLT "O" RING COVER PLUG HEX NUT 200 NB 1 1 1 1 1 6 1 1 1 1 1 1 1 8 1 12 1 1 1 12 150 NB 1 1 1 1 1 4 1 1 1 1 1 1 1 8 1 12 1 1 1 1 12 QTY. 100 NB 1 1 1 1 1 4 1 1 1 1 1 1 1 8 1 12 1 1 1 1 12 80 NB 1 1 1 1 1 1 1 1 1 1 1 1 8 1 12 1 1 1 1 12 MATERIAL SPECIFICATION CAST STEEL /ASTM A216 WCB STAINLESS STEEL 304 STAINLESS STEEL 304 BRONZE IS:318 LTB-II/ASTM B62 NEOPRENE RUBBER STAINLESS STEEL 304 BRONZE IS:318 LTB-II/STM B 62 NEOPRENE RUBBER NEOPRENE RUBBER S.S. 304/ASTM A276 TYPE-304 BRONZE IS:318 LTB-II/ASTM B62 NEOPRENE RUBBER BRONZE IS:318 LTB-II/ASTM B62 STAINLESS STEEL 304 STAINLESS STEEL 316 IS:1363/STEEL ISO 4018 (GALVANISED) BRASS IS:319-I/ASTM B16 NEOPRNE RUBBER CAST STEEL / ASTM A216 GR WCB STEEL PLATED IS:1363/STEEL IS 4018 (GALVANISED) HD103

SPINDLE ADAPTOR 1

JANUARY, 2006

PAGE

4 OF 14

PNEUMATIC & ELECTRIC RELEASE TRIM FOR HORIZONTAL MOUNTING DELUGE VALVE MODEL - H, 200/150/100/80 NB

15 38 33 34 36 35 13 14

**
#
43 2 7 7

12

#
2

#
39 40

31 32 31 30

42 41

11 7 2 2 7 6

29

#
4

#
FROM COMPRESSOR

9 10 1 8 15 TO OPEN DRAIN 24

*
37

5 26

*
4 2 28

27 13

25 2 18 1 18 22 2 3 19 15 13 21 TO PRIMING CONNECTION (BELOW UP-STREAM STOP VALVE) 20 16 14 TO OPEN DRAIN 23

TO OPEN DRAIN 17 TO OPEN DRAIN

** *

ELECTRIC TRIM OPTIONAL TO SUIT AT SITE BY USER. TEST & ALARM TRIM OPTIONAL

NOTE: WHEN TEST & ALARM TRIM IS SUPPLY THEN SL.NO.27 & 28 PLUG NOT REQUIRED. WHEN ELECTRIC TRIM IS SUPPLY THEN SL.NO.29 PLUG NOT REQUIRED.

JANUARY, 2006

PAGE

5 OF 14

HD103

PNEUMATIC & ELECTRIC RELEASE TRIM FOR HORIZONTAL MOUNTING DELUGE VALVE MODEL - H, 200/150/100/80 NB
NO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 19 20 20 21 22 23 24 25 25 26 27 28 29 30 31 32 33 34 35 35 35 35 36 37 37 38 39 40 41 42 43 CODE 8627 9365 9423 8616 9381 1906 8619 9480 9397 1921 1561 9413 9477 9374 9526 9363 1911 9367 8950 8952 9394 9392 9552 8621 9486 9391 9413 9552 8629 8630 8629 8629 8617 9366 9421 8620 9553 3653 2438 2518 2796 9423 9441 9406 9382 9365 9365 8619 DESCRIPTION UNION HEX NIPPLE BALL VALVE ELBOW Y TYPE STRAINER RESTRICTION CHECK VALVE TEE PIPE NIPPLE PIPE NIPPLE EMERGENCY RELEASE STATION DRY PILOT ACTUATOR REDUCING HEX NIPPLE GAUGE VALVE ELBOW PRESSURE GAUGE HEX NIPPLE DRIP VALVE HEX NIPPLE PIPE NIPPLE PIPE NIPPLE ANGLE VALVE ANGLE VALVE REDUCING NIPPLE TEE REDUCING HEX NIPPLE ANGLE VALVE REDUCING HEX NIPPLE REDUCING NIPPLE PLUG PLUG PLUG PLUG ELBOW HEX NIPPLE SWING CHECK VALVE TEE REDUCING HEX NIPPLE COPPER TUBE ASSY COPPER TUBE ASSY COPPER TUBE ASSY COPPER TUBE ASSY BALL VALVE. PIPE NIPPLE PIPE NIPPLE Y TYPE STRAINER HEX NIPPLE SOLENOID VALVE HEX NIPPLE TEE PRESSURE SWITCH SIZE HD MAKE MODEL-A X 80 MM X 100 MM HD MAKE MODEL-MR HD MAKE MODEL-DPA X HD MAKE MODEL-A 1 2 X 80 MM 1-1/4 X 80 MM 2 1-1/4 X1/2X65 MM 1 1 X 1 X XX65 MM X X 80 MM X 100 MM TWO WAY 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 200NB 2 8 1 2 1 2 4 1 1 1 1 1 3 2 3 1 1 2 1 1 1 1 1 1 1 1 1 1 150NB 2 8 1 2 1 2 4 1 1 1 1 1 3 2 3 1 1 2 1 1 1 1 1 1 1 1 1 1 100NB 2 8 1 2 1 2 4 1 1 1 1 1 3 2 3 1 1 2 1 1 1 1 1 1 1 1 1 1 80NB 2 8 1 2 1 2 4 1 1 1 1 1 3 2 3 1 1 2 1 1 1 1 1 1 1 1 1 1

TEST AND ALARM TRIM ( OPTIONAL)

ELECTRIC TRIM FOR SOLENOID VALVE ( OPTIONAL)

ELECTRIC TRIM FOR PRESSURE SWITCH ( OPTIONAL)

JANUARY, 2006

PAGE

6 OF 14

HD103

HYDRAULIC & ELECTRIC RELEASE TRIM FOR HORIZONTAL MOUNTING DELUGE VALVE MODEL - H, 200/150/100/80 NB

36 31 32 34 33 4 29 30 29 28 35 9 7 6 5 24 8 13 TO OPEN DRAIN 22 7 2 4 9 10 27

**
#
37

#
38

# #

*
4 2 25

26 11 23

2 16 1 16 20 2 3 17 13 11 19 TO PRIMING CONNECTION (BELOW UP-STREAM STOP VALVE) 18 14 12 TO OPEN DRAIN 21

TO OPEN DRAIN 15 TO OPEN DRAIN

TO SUIT AT SITE BY ** TEST & ALARM TRIMUSER. OPTIONAL *

# ELECTRIC TRIM OPTIONAL

NOTE: WHEN TEST & ALARM TRIM IS SUPPLY THEN SL.NO.25 & 26 PLUG NOT REQUIRED. WHEN ELECTRIC TRIM IS SUPPLY THEN SL.NO.27 PLUG NOT REQUIRED.

JANUARY, 2006

PAGE

7 OF 14

HD103

HYDRAULIC & ELECTRIC RELEASE TRIM FOR HORIZONTAL MOUNTING DELUGE VALVE MODEL - H, 200/150/100/80 NB
NO. CODE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 17 18 18 19 20 21 22 23 23 24 25 26 27 28 29 30 31 32 33 33 33 33 34 35 35 36 37 38 8627 9365 9423 8616 9381 1906 8619 9480 9397 1921 9477 9374 9526 9363 1911 9367 8850 8952 9394 9392 9552 8621 9486 9391 9413 9552 8629 8629 8630 8629 8617 9366 9421 8620 9553 3653 2438 2518 2796 9423 9441 9406 9382 9365 DESCRIPTION UNION HEX NIPPLE BALL VALVE ELBOW Y TYPE STRAINER RESTRICTION CHECK VALVE TEE PIPE NIPPLE PIPE NIPPLE EMERGENCY RELEASE STATION GAUGE VALVE ELBOW PRESSURE GAUGE HEX NIPPLE DRIP VALVE HEX NIPPLE PIPE NIPPLE PIPE NIPPLE ANGLE VALVE ANGLE VALVE REDUCING NIPPLE TEE REDUCING NIPPLE ANGLE VALVE REDUCING HEX NIPPLE REDUCING NIPPLE PLUG PLUG PLUG PLUG ELBOW HEX NIPPLE SWING CHECK VALVE TEE REDUCING HEX NIPPLE COPPER TUBE ASSY COPPER TUBE ASSY COPPER TUBE ASSY COPPER TUBE ASSY BALL VALVE. PIPE NIPPLE PIPE NIPPLE Y TYPE STRAINER HEXNIPPLE SOLENOID VALVE SIZE HD MAKE MODEL A X 80 MM x 100 MM HD MAKE MODEL MR HD MAKE MODEL-A 1 2 X 80 MM 1 X 80 MM 2 1 XX65 MM 1 1 X 1 X XX65 MM X X 80 MM X 100 MM X TWO WAY 200NB 1 4 1 4 1 1 2 1 2 1 2 1 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 150NB 1 4 1 4 1 1 2 1 2 1 2 1 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 100NB 1 4 1 4 1 1 2 1 2 1 2 1 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 80NB 1 4 1 4 1 1 2 1 2 1 2 1 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1

TEST AND ALARM TRIM ( OPTIONAL)

ELECTRIC TRIM FOR SOLENOID VALVE ( OPTIONAL)

JANUARY, 2006

PAGE

8 OF 14

HD103

PNEUMATIC & ELECTRIC RELEASE TRIM FOR VERTICAL MOUNTING DELUGE VALVE MODEL - H, 200/150/100/80 NB

**
35 34 15 14 16 17 15 14 4 6 2 7 8 1 2 5 TO PRIMING CONNECTION (BELOW UP-STREAM STOP VALVE) 1 2 9 17 13 33 32 31 18 29 36

38

37 36 24

25

TO OPEN DRAIN 23 22

*
2

30

*
27 39 19

22 21 20

TO OPEN DRAIN

TO OPEN DRAIN 44 26 26 26 10 2 12 2 1 3 2 14 13 9 9 2 9 2 42 # 15 TO DETECTION LINE #

8 43 #

11

28

# 40 #

TO OPEN DRAIN

41 #

* TEST & ALARM TRIM * * TO SUIT AT SITE BY USER. # ELECTRIC TRIM OPTIONAL.

NOTE : WHEN TEST & ALARM TRIM IS SUPPL THEN SL.NO.27 PLUG NOT REQUIRED. Y WHEN ELECTRIC TRIM IS SUPPL THEN SL.NO.28 PLUG NOT REQUIRED. Y

JANUARY, 2006

PAGE

9 OF 14

HD103

PNEUMATIC & ELECTRIC RELEASE TRIM FOR VERTICAL MOUNTING DELUGE VALVE MODEL - H, 200/150/100/80 NB
NO CODE 1 8627 2 3 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 24 25 25 26 27 28 29 30 30 30 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 9365 9561 9569 9568 9423 8616 9381 1906 8619 9480 1921 1561 9413 9477 9526 9363 9374 9552 1911 9486 8621 9367 9391 8950 8952 9394 9392 8629 8630 8629 8616 3654 2411 2519 2797 8619 9365 9423 9553 8620 9366 9421 9382 9365 9365 9365 8619 DESCRIPTION UNION HEX NIPPLE PIPE NIPPLE PIPE NIPPLE PIPE NIPPLE BALL VALVE ELBOW Y TYPE STRAINER RESTRICTION CHECK VALVE TEE PIPE NIPPLE EMERGENCY RELEASE STATION DRY PILOT ACTUATOR REDUCING HEX NIPPLE GAUGE VALVE PRESSURE GAUGE HEX NIPPLE ELBOW REDUCING NIPPLE DRIP VALVE REDUCING HEX NIPPLE TEE HEX NIPPLE ANGLE VALVE PIPE NIPPLE PIPE NIPPLE ANGLE VALVE ANGLE VALVE PLUG PLUG PLUG ELBOW COPPER TUBE ASSY. COPPER TUBE ASSY. COPPER TUBE ASSY. COPPER TUBE ASSY. TEE HEX NIPPLE BALL VALVE REDUCING HEX NIPPLE TEE HEX NIPPLE SWING CHECK VALVE Y TYPE STRAINER HEX NIPPLE HEX NIPPLE SOLENOID VALVE HEX NIPPLE TEE PRESSURE SWITCH SIZE X 60 MM X 90 MM X 90 MM HD MAKE MODEL A X 80 MM HD MAKE MODEL MR HD MAKE MODEL DPA X X X 65MM HD MAKE MODEL-A 1 X 1 1 1 2 X 80 MM 1 X 80 MM 2 1 X ( OPOTIONAL) TWO WAY 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 200NB 3 9 1 1 1 1 1 2 5 1 1 1 2 3 3 1 2 1 1 1 1 2 1 1 1 3 1 1 1 1 1 1 1 1 1 2 1 1 1 150NB 3 9 1 1 1 1 1 2 5 1 1 1 2 3 3 1 2 1 1 1 1 2 1 1 1 3 1 1 1 1 1 1 1 1 1 2 1 1 1 100NB 3 9 1 1 1 1 1 2 5 1 1 1 2 3 3 1 2 1 1 1 1 2 1 1 1 3 1 1 1 1 1 1 1 1 1 2 1 1 1 80NB 3 9 1 1 1 1 1 2 5 1 1 1 2 3 3 1 2 1 1 1 1 2 1 1 1 3 1 1 1 1 1 1 1 1 1 2 1 1 1

TEST AND ALARM TRIM ( OPTIONAL)

ELECTRIC TRIM FOR SOLENOID VALVE

ELCTRIC TRIM FOR PRESSURE SWITCH ( OPTIONAL)

JANUARY, 2006

PAGE 10 OF 14

HD103

HYDRAULIC & ELECTRIC RELEASE TRIM FOR VERTICAL MOUNTING DELUGE VALVE MODEL - H, 200/150/100/80 NB

**
36 35 14 13 15 16 14 13 25 6 2 7 8 1 2 5 TO PRIMING CONNECTION (BELOW UP-STREAM STOP VALVE) 16 34 33 32 17 30 37

39

38 37 23

24

TO OPEN DRAIN

*
2

31

*
27 29 21 21 18 20 19 TO OPEN DRAIN 22

26 12 26 26 10

TO OPEN DRAIN

9 4 9 3 # 11 9 28 # # 40 # 41

* TEST & ALARM TRIM * * TO SUIT AT SITE BY USER. # ELECTRIC TRIM OPTIONAL.

TO OPEN DRAIN

NOTE : WHEN TEST & ALARM TRIM IS SUPPLY THEN SL.NO.27 PLUG NOT REQUIRED. WHEN ELECTRIC TRIM IS SUPPL THEN SL.NO.28 PLUG NOT REQUIRED. Y

JANUARY, 2006

PAGE 11 OF 14

HD103

HYDRAULIC & ELECTRIC RELEASE TRIM FOR VERTICAL MOUNTING DELUGE VALVE MODEL - H, 200/150/100/80 NB
NO 1 2 3 3 4 4 5 6 7 6 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23 24 24 25 26 27 28 29 30 31 31 31 31 32 33 34 35 36 37 38 39 40 41 CODE 8627 9365 9561 9569 9397 9399 9423 8616 9381 1906 8619 9480 1921 9413 9477 9526 9363 9374 9552 1911 9486 8621 9367 9391 8950 8952 9394 9392 9568 8629 8630 8629 9365 8616 3654 2411 2519 2797 8619 9365 9423 9553 8620 9366 9421 9382 9365 DESCRIPTION UNION HEX NIPPLE PIPE NIPPLE PIPE NIPPLE PIPE NIPPLE PIPE NIPPLE BALL VALVE ELBOW Y TYPE STRAINER RESTRICTION CHECK VALVE TEE PIPE NIPPLE EMERGENCY RELEASE STATION REDUCING HEX NIPPLE GAUGE VALVE PRESSURE GAUGE HEX NIPPLE ELBOW REDUCING NIPPLE DRIP VALVE REDUCING HEX NIPPLE TEE HEX NIPPLE ANGLE VALVE PIPE NIPPLE PIPE NIPPLE ANGLE VALVE ANGLE VALVE PIPE NIPPLE PLUG PLUG PLUG HEX NIPPLE ELBOW COPPER TUBE ASSY. COPPER TUBE ASSY. COPPER TUBE ASSY. COPPER TUBE ASSY. TEE HEX NIPPLE BALL VALVE REDUCING HEX NIPPLE TEE HEX NIPPLE SWING CHECK VALVE Y TYPE STRAINER HEX NIPPLE SOLENOID VALVE SIZE X 60MM X 90MM X 100 MM X 130 MM HD MAKE MODEL A X 80 MM HD MAKE MODEL MR X X X 65 MM HD MAKE MODEL-A 1 X 1 1 1 2 X 80 MM 1- X 80 MM 2 1- X 90 MM X TWO WAY 200NB 1 3 1 1 1 1 1 1 3 1 1 1 2 2 1 2 1 1 1 1 2 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 150NB 1 3 1 1 1 1 1 1 3 1 1 1 2 2 1 2 1 1 1 1 2 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 100NB 1 3 1 1 1 1 1 1 3 1 1 1 2 2 1 2 1 1 1 1 2 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 80NB 1 3 1 1 1 1 1 1 3 1 1 1 2 2 1 2 1 1 1 1 2 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1

TEST AND ALARM TRIM ( OPTIONAL)

ELECTRIC TRIM FOR SOLENOD VALVE ( OPTIONAL)

JANUARY, 2006

PAGE 12 OF 14

HD103

ELECTRIC & PNEUMATIC RELEASE TRIM - SCHEMATIC DELUGE VALVE - 200/150 / 100 / 80 NB HORIZONTAL MOUNTING
TO DETECTION LINE PS RCV
G

VERTICAL MOUNTING
TO DETECTION LINE FROM COMPRESSOR PG RCV DR.V OD
DPA

PG

OUT LET

*
~

PG

RCV

TO DRAIN PG

DPA M

*
SV OD

OD PG

OD G

PV

OUTLET

PV

PG
DR.V OD CD CD

ELECTRIC & HYDRAULIC RELEASE TRIM - SCHEMATIC DELUGE VALVE - 200/150 / 100 / 80 NB HORIZONTAL MOUNTING VERTICAL MOUNTING

PG

SV OD

OD G

PV

FROM SUPPL Y

INLET

DV
OUTLET

OD
DV INLET OD M

PG
DR.V OD CD CD

FROM SUPPL Y

VALVE STRAINER OPTIONAL GAUGE VALVE ANGLE VALVE

STOP VALVE BY USER SV - SOLONOID VALVE PS - PRESSURE SWITCH M - SIX WAY MANIFOLD

JANUARY, 2006

PAGE 13 OF 14

RCV

*
OD PG

OUT LET

TO DETECTION LINE

FROM SUPPL Y

INLET

FROM SUPPL Y

INLET

DV

OD

RCV M OD

TO DRAIN

*
SV

OD

DV

PG

DR.V OD TO DETECTION LINE

RCV

*
SV

OD

PV

DR.V - DRIP VALVE CD - COMMON DRAIN F - FUNNEL DV - DELUGE VALVE PG - PRESSUER GAUGE

NON RETURN VALVE OD - OPEN DRAIN ER - EMERGENCY RELESE BOX RCV - RESTRECTION CHECK VALVE

HD103

WET PILOT SPRINKLER HEIGHT LIMITATION OF 150 NB

WET PILOT SPRINKLER HEIGHT LIMITATION OF 100 NB

WET PILOT SPRINKLER HEIGHT LIMITATION OF 80 NB

LIMITED WARRANTY
Products manufactured by HD FIRE PROTECT PVT.LTD.. are warranted against defects in material and workmanship for a period of Two (2) years from the date of shipment. HD's obligation under this warranty is limited to replace or repair the products or its parts, which are shown to HD's examination to be in a defective condition attributable to HD. No warranty is given for products or components which have been subject, to misuse, improper installation, corrosion, wear and tear, improper storage, modification or repaired. If the defect attributable to HD cannot be rectified by repair or replacement, then HD may elect to refund the purchase price of the equipment in complete discharge of its obligation under this Limited Warranty. IN NO EVENT SHALL HD FIRE PROTECT PVT. LTD. BE LIABLE IN CONTRACT, STRICT LIABILITY OR ANY OTHER LEGAL THEORY, FOR INCIDENTAL, IN-DIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES, INCLUDING DAMAGES. FOR INJURY TO PERSON OR DEATH OR DAMAGE TO PROPERTY AND OR PENALTIES RESULTING FROM ANY PRODUCTS OR COMPONENT MANUFACTURED OR ASSEMBLED BY HD. THIS IS LIMITED WARRANTY ONLY. HD DISCLAIMS WITH RESPECT TO THE PRODUCTS ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND ALL IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE. THERE IS NO WARRANTY OF ANY NATURE MADE BY HD BEYOND AS STATED ABOVE. NOTICE : The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and also with the provision of government codes or ordinances wherever applicable. The information provided by us are to the best of our knowledge and belief, and are general guidelines only. Site handling and installation control is beyond our reach. Hence we give no guarantee for result and take no liability for damages, loss or penalties whatsoever, resulting from our suggestion, information, recommendation or damages due to our product. Product development is a continuous programme of HD FIRE PROTECT PVT. LTD. and hence the right to modify any specification without prior notice is reserved with the company.

C-3/6, THE NANDANVAN IND. ESTATE, L.B.S. MARG, THANE 400 604., INDIA. PHONES : +(91) 22 2583 5434 2582 6958 2582 6793 FAX : +(91) 22 2581 2524 5596 9049
EMAIL : [email protected] WEBSITE : www.hdfire.com

JANUARY, 2006

PAGE 14 OF 14