S1 - 2300manual Booster
S1 - 2300manual Booster
S1 - 2300manual Booster
USE
Reciprocating Compressor
Model: N 753 --- G
Table of Contents
Chapter --- Page
1
1
1
1
2
2
2
2
3
3
5
2
2
2
2
2
2
2
2
-----------------
7
7
8
8
9
9
9
10
3
3
3
3
---------
11
11
11
11
-----------------------
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 --- 11
3.1
3.2
3.3
3.4
1
1
1
1
1
1
1
1
1
1
1
Booster Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Noise Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compressor Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Drive Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inlet Pressure Switch Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Relief Valve Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Greasing the Electrical Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Oil Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensional Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
4
4
4
4
4
-------------
12
12
13
13
13
14
5
5
5
5
5
5
-------------
15
16
17
18
18
18
Table of Contents
Chapter --- Page
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 --- 19
6.1
6.2
6.2.1
6.3
6.4
6.4.1
6.4.2
6.5
6.6
6.7
6.8
6.8.1
6.8.2
6.8.3
6.8.4
6.8.5
---------------------------------
19
19
20
21
21
22
22
23
23
25
28
28
28
28
28
28
7
7
7
7
7
7
7
---------------
29
29
30
31
31
31
33
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 34
8.1
8.2
8.3
8.4
8.4.1
8.4.2
8.4.3
8.4.4
8.4.5
8.4.6
8.4.7
8.4.8
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
8
8
8
8
8
8
8
8
8
8
8
8
-------------------------
34
34
35
36
36
36
36
36
37
37
37
37
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 38
9.1
9.2
9.3
9.4
Observe the following rules during all maintenance and servicing work: . . . . . . .
Regular Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Regular Maintenance of the Prefilter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Oil Level Check and Top ---Off (Compressor Block) . . . . . . . . . . . . . . . . . . . . . . . . .
9
9
9
9
---------
38
39
40
40
ii
Table of Contents
Chapter --- Page
9.5
9.6
9.7
9.8
9.9
9.10
9.11
9.11.1
9.11.2
9.12
9.13
9.14
9.15
9.16
9.17
9.18
9.19
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
-----------------------------------
41
42
43
44
45
47
47
47
48
49
50
51
51
52
53
54
55
11 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 --- 58
11.1
11.2
11.2.1
11.2.2
Electrical Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Temperature Sensor Technical Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
11
11
11
---------
58
79
79
79
iii
Technical Specification
1
Technical Specification
1.1
Booster Unit
Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N 753 --- G
Overall weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1565 lbs
Maximum permitted pressure ratio . . . . . . . . . . . . . . . . . . . . 4.5:1
(see permitted duty cycle, chapter 5.3)
Diagrams:
Dimensional diagram . . . . . . . . . . . . . . . . . . . . . . . . 1.2300.20500
Electrical diagram . . . . . . . . . SKK---U0927.00 & SKK---U0947.00
P & I flow diagram . . . . . . . . . . . . . . . FKKN753 ---GST---00090.02
(Pipework and Instrument flow diagram)
1.2
Noise Level
Noise level to CAGI---Pneurop . . . . . . . . . . . . . . . . . . . . . . . . . . 80 dB(A)
at 1 m distance (free sound field measurement)
1.3
Compressor Block
Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N 753
Displacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35.3 cfm
Capacity CFM (FAD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327.4 cfm
at 500 psig working pressure
Inlet pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 ---145 psig
Maximum working pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . 500 psig
Maximum duty cycle:
3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 %
Pressure ratio
Pressure ratio 3 (load 60 min., idle 15 min.) . . . . . . . . . . . . 80 %
Number of cylinders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1250 rpm
Oil capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2 qts.
Oil top ---off quantity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.2 qts.
1.4
Drive Motor
Rated power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 hp
Rated speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3600 rpm
Enclosure rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TEFC
Max. starts per hour . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 times
Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wye---Delta
1 --- 1
Technical Specification
1.5
Electrical Connection
Main voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 460 V 3 ---phase
Full load current FLA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 A
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Hz
Recommended main disconnect fuses
(Dual element or time---delay) . . . . . . . . . . . . . . . . . . . . . . . . . 80 A
Recommended power supply cable (Cu multi---stranded )
cross---section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 AWG
Maximum dual element time --- delay fuses are selected according to
2002 N.E.C. Article 240 --- 6, 430 --- 52 and Tables 430 --- 52, 430 --- 148 &
150.
Attention!
1.6
12
MDR 43/11
11
10
9
8
7
6
5
4
3
10 11 12
1.7
bar
1.8
Installation Requirements
Attention!
1 --- 2
Technical Specification
1.9
14.1 oz
1.10
Oil Recommendations
Lubrication of an air compressor is essential to reliable operation. Carbon and varnish can
form in compressor oils. These deposits block the flow of lubricant and cause excessive
wear and failure of moving parts. Contamination of the oil can allow the formation of acids,
causing extensive internal corrosion. Water may be condensed decreasing the oils lubricity.
KAESER COMPRESSORS has several lubricants available that are specially formulated to
match these demands. They feature excellent lubricity, outstanding demulsibility (ability to
separate from water), and long life.
RECOMMENDED KAESER LUBRICANTS
SIGMA
DESCRIPTION
LUBRICANT
MAXIMUM RECOMMENDED
CHANGE INTERVAL*
First Oil Change
Subsequent Oil
Change
M---150
50 Hours
1,000 Hours
S---150
100 Hours
2,000 Hours
1 --- 3
Technical Specification
M --- SERIES SEMI --- SYNTHETIC LUBRICANTS
M---Series SIGMA compressor fluids are the highest quality petroleum lubricants.
M---150 is specially blended to provide reliable performance in KAESER reciprocating
compressors.
S--- SERIES SYNTHETIC LUBRICANTS
S---Series SIGMA compressor oils are formulated from the most advanced synthetic
lubricants. These synthetic lubricants begin as high quality petroleum feed stock.
They are then refined, processed and purified into fluids with very consistent molecular
structure. These oils are carefully blended to produce extremely lubricants with superior properties. SIGMA synthetic lubricants feature all the advantages of both PAO and
diester fluids.
S---150 lubricant is recommended for compressors operating in ambient temperatures
between 40 F and 105 F.
Specialty KAESER LUBRICANTS
FG---150 synthetic hydrocarbon based food grade lubricant is designed for use in reciprocating compressors in the application where incidental food contact may occur
with the discharge air. This lubricant meets the requirements of the FDA Regulation 21
CRF 178.3570 and is USDA H ---1 approved. FG---150 is approved for canning, food
packing, meat and poultry processing and other applications where incidental food
contact may occur.
SPECIALTY KAESER LUBRICANTS
(Refer to product information to determine suitability.)
SIGMA
DESCRIPTION
LUBRICANT
FG---150
*
MAXIMUM RECOMMENDED
CHANGE INTERVAL*
Subsequent Oil
Change
500 Hours
1,000 Hours
KAESER synthetic lubricant should be stored in a protected location to prevent contamination. Do not re---use drums; flush and send to reconditioner.
Although the KAESER synthetic is not highly flammable, it will burn. While KAESER synthetic compressor oil is less flammable than equal viscosity mineral oils, it cannot be classified as a fire---resistant fluid. It has a flash point above 460 F. Since the user has total control over the conditions of the compressor lubricant, he assumes total responsibility for its
safe usage.
Material Safety Data Sheets are available for each lubricant from your KAESER authorized
distributors.
1 --- 4
Technical Specification
Compatibility:
FG---150 is similar to mineral oil in its compatibility with paints, seals, gaskets and
hoses. The typical precautions are required when changing over from mineral oil to
KAESER synthetic hydrocarbon based lubricant.
Never mix lubricants of different types or brands.
When switching from mineral oil to a synthetic oil, the plants system materials must be
re---evaluated. Certain plastics are not compatible with synthetic oils. The following is a partial list of acceptable and not recommended materials:
ACCEPTABLE
Viton
Celcon
PVC
Neoprene
ABS
Teflon
Epoxy Paint
SBR Rubber
Low Nitrile Buna N
Acrylic Paint
Lacquer
Delrin
Polystyrene
Attention!
1.11
NOT RECOMMENDED
Dimensional Drawing
(see following page)
1 --- 5
Safety
2
Safety Regulations
Disregarding this notice can result in serious injury!
Read this service manual carefully and observe cautionary references before putting the
compressor unit into operation and before carrying out any maintenance on the unit.
2.1
2.1.1
Warning notices
Here is a notice warning of danger.
DANGER
Danger levels
Warning notices indicate three levels of danger identified by the signal word under the
danger symbol.
Signal word
Meaning
DANGER
warns of imminent
threatening danger
WARNING
warns of possible
threatening danger
CAUTION
warns of a possibly
dangerous situation
2 --- 7
Safety
2.1.2
2.2
Attention!
Attention!
2 --- 8
Safety
2.3
Do not allow open flame and flying sparks at the installation site.
Take necessary precaution when welding on or near the compressor unit to ensure
that sparks or high temperatures cannot cause fire or explosion.
Ensure that the compressor unit is supplied only with clean uncontaminated air.
Do not allow the maximum ambient temperature to be exceeded (see chapter 1.8),
unless special measures have been agreed upon between the manufacturer and the
customer.
Perform oil changes according to the service manual or at least once annually.
Do not mix cooling oils of different types.
Use only cooling oils recommended by the manufacturer (see chapter 1.10).
This machine is not explosion ---proof.
It may not be operated in areas in which specific requirements with regard to explosion protection are applied.
2.4
2.5
Spare Parts
Safe and reliable operation of the compressor unit is guaranteed only with KAESER original
spare parts and KAESER SIGMA compressor oil.
2 --- 9
Safety
2.6
Environmental Protection
Condensate drainage
Condensate accumulating during compression must be drained via a
suitable draining system and collected in disposal canisters. The condensate must be disposed of according to environmental care regulations.
Maintenance materials/wear items/replacement parts
Dispose of all used materials and parts accumulating during operation, maintenance and repair of the compressor unit according to
environmental care regulations!
Disposing of the Machine
When disposing of a machine, drain out all liquids and remove dirty filters.
Dispose of all used materials and parts accumulating during operation, maintenance and repair of the compressor unit according to
environmental care regulations!
Take the machine out of service (see chapter 8.1).
Drain all oil completely from the machine (see chapter 9.5).
Remove dirty filters.
Use the services of an approved local disposal specialist to ensure environmentally correct
disposal of the empty machine.
2 --- 10
General
3
General
3.1
3.2
Improper Use
Never direct compressed air toward persons. Compressed air is a concentrated form of energy and as such dangerous to life.
Never use compressed air for breathing purposes and production
methods where the air has direct contact with food without subjecting
the compressed air to additional treatment.
Attention!
Inlet air may not contain any explosive or chemically unstable gas or
vapour.
Initial filling of a fully vented air main generally creates very a high rate of flow through air
treatment devices.
These devices cannot function correctly under such conditions and compressed air quality
suffers.
KAESER recommends installation of an air main charging system to ensure required air
quality.
3.3
Copyright
KAESER COMPRESSORS, INC.
All rights reserved. No part of this manual may be reproduced in any form without permission of KAESER COMPRESSORS, INC.
3.4
Keep the service manual safe throughout the life of the machine.
3 --- 11
Transport
4
4.1
Isolate the compressor from the air main by closing the users compressed air inlet
and outlet shut ---off valves. Initial and final pressure gauges must read zero.
Allow the compressor to cool down completely.
If the compressor is water ---cooled, shut off the water supply, drain the water completely from the heat exchanger and dispose of it according to environmental regulations.
Disconnect all supply lines.
4.2
Packaging
Always observe the instructions in chapter 4.6 when packaging the machine for storage.
Use packaging suitable for the intended route if the machine is to be transported further by
the customer.
Overland
The machine should be protected from mechanical damage by a sturdy crate and from
moisture by plastic sheeting.
By sea or air
Special packaging instructions can be obtained from KAESER.
Dispose of the packaging according to environmental regulations and
recycle where possible.
4 --- 12
Transport
4.3
Transport Instructions
A fork lift truck or lifting cradle should be used to avoid damaging to the machine.
4.4
4.5
Attention!
Do not excert any side forces on the compressor unit when transporting with lifting equipment.
4 --- 13
Transport
4.6
Storage
The machine must be adequately packed.
Store the machine in a dry, frost ---free room.
Prevent entry of moisture and condensation.
If the equipment is to stand idle for a long period the prescribed measures must be taken
to avoid damage.
If any measures can not be taken, advice should be sought from the authorised KAESER
Service depot.
As an alternative to storage, the equipment can be run once a week for 30 minutes at operating temperature to ensure adequate corrosion protection.
Otherwise, the measures described under Storage for longer than 6 months are to be
taken.
Storage for longer than 6 months
Ensure the machine is dry and cover in plastic sheeting. Protect the interior with sufficient
quantities of desiccant (silica gel or similar).
Storage for longer than 12 months
Carry out the following additional maintenance tasks before putting into operation:
change the oil filter (see chapter 9.9),
change the oil (see chapter 9.5),
have the motor bearings checked by an authorised KAESER service technician.
Storage for longer than 3 years:
after 3 years at the latest the complete technical condition of the machine must be
checked before start ---up.
Damage to the machine can occur if the condition is not checked.
CAUTION
Have the the start ---up carried out by an authorised KAESER service
technician.
4 --- 14
5.1
14
16 3
26 11 2 7 24 23 22 21 20
17
10
19
1 15
18 25
KMZ052211
5 --- 15
5.2
Inlet port, entry of air from the low ---pressure air main
Compressed air outlet to the high ---pressure network
Compressor block, compresses the inlet air
Collecting pipe, collects and smoothes the incoming air
Aftercooler, collects and smoothes the compressed air and dissipates the heat
through the cooling fins
Check valve, prevents the escape of inlet air through the filter
Pressure relief valve, protects the compressor block from excessive pressure
Inlet valve
Control valve in the compressed air inlet
Relief valve, de ---pressurises the machine during standstill
De ---watering valve on the compressed air outlet
Air filter, cleans the intake air during idling
Electric motor, drives the compressor block
Casing venting with oil filter
Crankcase oil filter, cleans the compressor oil flowing through the oil pump integrated
in the crank case
Oil filler port
Oil level sight glass
Oil drain plug
Dirt trap in the compressed air inlet, cleans the incoming air
Dirt trap in the oil circuit, protects the oil pump from contamination
Temperature gauge switch, measures the compressed air discharge temperature and
switches the machine off if the maximum set value is reached
Oil pressure gauge
Initial pressure gauge
Final pressure gauge
Initial pressure switch, registers the inlet pressure and thereby regulates the switching on and off of the compressor
Temperature sensor, measures the block discharge temperature and switches the
machine off if the maximum set value is reached
Brief Description
The compressor block is driven by an electric motor via V---belts.
The compressor block may have one, two or three cylinders.
The belt pulley on the compressor crankshaft also serves as a fan to blow a stream of cooling air over the machine. Cooling fins on the cylinder and cylinder head dissipate heat.
A solenoid ---operated inlet valve is fitted at the compressed air inlet to the block.
A pneumatically operated venting valve, coupled with the control valve, is fitted to the aftercooler or base frame to de---pressurise the machine.
A further valve ensures de---watering of the pressure system.
The oil is pumped through a filter and returned to the crankcase.
A pressure switch ensures that the compressor runs only in the permitted initial pressure
range (see chapter 1.6).
5 --- 16
max.
Example
3.4
Up to 100% duty cycle
5.3
212
230
248
266
284
302
320
338
356
374
392
410
428
Final temperature [ F]
The maximum duty cycle (ED) of the booster is related to the compression ratio (discharge
pressure PB absolute / initial pressure P1 absolute), the ambient temperature and the compressed air inlet temperature (see diagram).
Example:
Initial pressure 160 psi (g)
Discharge pressure 580 psi (g)
Compression ratio: 594 psi (abs) / 174 psi (abs) = 3.4
Ambient temperature 105 F, inlet temperature 115 F
Results in a duty cycle (ED) of 80 %.
Duty cycle (ED) = Duty cycle (ED) is the portion of the total operating cycle that the
unit is under load.
ED [%] =
x 100 %
5 --- 17
5.4.1
Operating states
LOAD
The inlet valve is fully open. The airend delivers compressed air to the system.
The drive motor runs under full load.
IDLING
The inlet valve is closed. The check valve cuts off the machine from the air main. The
aftercooler is vented.
A small volume of air is drawn through the inlet filter into the compressor block and out
through the venting valve to atmosphere.
The drive motor runs without load and draws little current.
STANDSTILL
The inlet valve is closed. The check valve cuts off the machine from the air main. The
aftercooler is vented.
The drive motor is stopped.
Tasks of the Controller
Using the selected control mode, the controller switches the compressor between its various operational states in order to maintain system pressure between the set minimum and
maximum values.
DUAL
In DUAL control the compressor normally runs at full load and idle to maintain system
pressure between the set minimum and maximum values.
When the maximum pressure is reached the machine switches to idle running.
When the preset idling time has elapsed the machine is stopped.
Pressure
The shorter the idling time setting, the sooner and more frequently the motor is stopped.
The permitted starting frequency of the motor must not be exceeded.
p
max
p
min
Full load
Motor power
5.4.2
2 3
t1
5
t2
Idle
Standstill
Time
5 --- 18
Installation
6
Installation
6.1
6.2
Installation Instructions
To ensure sufficient cooling of the compressor unit the specified minimum compressor
location size, minimum distance to the walls and minimum size of the ventilation inlet and
exhaust openings must be complied with (see chapter 1.8).
The cooling air flow of the compressor unit is not greatly influenced in smaller locations
even if the door is opened, if the air flowing in through the door takes the shortest route to
the exhaust opening without flowing around the compressor.
Safe operation of the compressor unit is only guaranteed if the ambient temperature remains within the limits stated in chapter 1.8).
If the machine is installed together with other plant (compressors, refrigeration
dryers, etc.), then under no circumstances may the hot cooling air discharged from
that other plant be directed to the cooling air inlet end of the machine.
Exhaust
opening
31.5*
* Recommended
minimum door
width to allow
entry of
compressor
19.7
Inlet opening
Dimensions in inches
6 --- 19
Installation
6.2.1
Drive a fork lift carefully under the compressor and lift slightly.
There is a danger of tipping because of the centre of gravity and the
compressor weight.
2
1
3
1
2
3
4
Antivibration pad
Threaded hole for fixing the
antivibration pad under the compressor
Holes for rag bolts to fix the
antivibration pad to the floor
Compensating disc
to correct for uneven floor level
6 --- 20
Installation
Determine the positions where the levelling discs are to be installed.
Lift the compressor.
Remove the screws retaining the corresponding antivibration pads.
Insert the levelling disc between the compressor and the pad.
Re---secure the pad.
Attention!
Position the compressor and fix to the floor with rag bolts.
6.3
Installation Instructions
The machine must be installed in accordance with the following diagram to ensure correct
operation with other plant.
It must be possible to isolate the machine by means of shut ---off valves on the inlet and
outlet to enable maintenance work to be carried out with the machine de---pressurised.
6.4
up to 650 psig
Low pressure
consumers
Fine filter 1
High pressure
consumers
Prefilter
Separator
Fine filter 2
Rotary screw
compressor
Air
dryer 1
Air
receiver 1
Booster
Air
receiver 2
Air
dryer 2
Option
6 --- 21
Installation
6.4.1
1 m.
If there is no dryer between the machine and the air receiver in the low pressure network
then it is imperative that the prefilter is fitted with an automatic drain valve.
Furthermore, the machine must run in idle for approximately three minutes before shutdown to ensure that the inlet pipe is dry (idle control must be fitted).
KGB005021
1
2
4
1
2
3
4
5
6.4.2
5
6
5
6
6 --- 22
Installation
6.5
Electrical Connection
The main power supply and overcurrent protection must be installed
by a qualified electrician in accordance with NEC, OSHA and any applicable local codes.
For fuse and wire recommendations, see chapter 1.5.
The control box is wired ready for connection to the main supplies. Feed the supply cable
with cores marked L1, L2, L3 and PE through the cable inlet in the base frame of the control box and connect to the terminals marked L1, L2, L3 and PE in this box.
Attention!
Maximum dual element time --- delay fuses are selected according to
1996 N.E.C. Article 240 --- 6, 430 --- 52 and Tables 430 --- 148 & 150.
Select multi--- strand copper core wire at 40 C ambient temperature
according to 1996 N.E.C. 110 --- 14(c), 220 --- 3, 310 --- 15, Table 310 --- 16,
430 --- 6, 430 --- 22 and Tables 430 --- 148 & 150.
Wire temperature rating:
1.25 x FLA
(see chapter 1.5)
6.6
wire
temperature rating
correction factor
for 40 C
100A
60 C
0.82
100A
75 C
0.88
Controller Design
A controller that complies with EN 60 204 must be provided for connection to the power
supply.
The machine is fitted with a solenoid control valve that holds the pneumatic inlet valve
closed when not energised. The solenoid valve only opens when the air inlet is subjected
to a pressure at or above the cut ---in setting of the initial pressure switch (see chapter 1.6).
A number of components are wired together in the terminal box fixed to the compressor
(see diagram in chapter 11.1).
Six cables are fed into the terminal box (1):
1, 2, 3
Cable ((oil pressure switch, pressure switch for monitoring initial pressure, initial
pressure valve)
6 --- 23
Installation
The additional electrical components required for the controller should be designed according to the corresponding motor power (see chapter 1.4).
The lines from the motor and the terminal box are connected in the controller and the following should be noted:
--- the oil pressure switch (17.5 psig) must be bridged in the motor run ---up phase and
must switch the compressor off at a pressure of < 14.5 psig.
--- the pressure switch that monitors initial pressure must switch the compressor on at a
pressure higher than pON and into idle running at a pressure lower than pOFF (see
chapter 1.6).
Attention!
The switch for monitoring initial pressure is factory set (see chapter 1.6)
and should not be adjusted.
If a final pressure is needed lower than the initial pressure setting, however, the setting can be changed (see chapter 7.6).
The ratio of initial to final pressure should not be higher than 1 : 4.5
If the pressure in the inlet line during the load phase falls below pOFF the compressor will
be switched by the pressure switch to idle running.
If, during offload running, the pressure in the inlet line falls below pOFF, the compressor will
only switch to load again when pressure pON is reached.
Pressure switch for monitoring initial pressure.
Compressor
p > pON
starts up
p > pOFF
p < pmax
p > pOFF
p = pmax
p > pOFF
p = pmin
p < pOFF
p < pON
Pmin
remains or
switches to
idle running *)
pOFF --- cut ---out pressure of the inlet pressure monitoring switch
pmin --- cut ---in pressure of the air system pressure switch (user)
pmax --- cut ---out pressure of the air system pressure switch (user)
--- The PTC sensors must shut down the compressor if a temperature of 374 F is reached, even if only one sensor registers this temperature (series wired). The sensor
connections must be secure against wire breakage.
--- The adjustable temperature gauge switch (2) has volt ---free contacts that can be used
in the controller.
The compressor components are arranged in accordance with the P & I diagram.
6 --- 24
Installation
KFB010421
2
3
4
5
1
1
2
3
4
5
6.7
Terminalbox
Discharge temperature gauge
Pressure gauge (Oil pressure)
Pressure gauge (Pre ---pressure)
Pressure gauge (Discharge pressure)
6 --- 25
Installation
6.8
6.8.1
6.8.2
Pressure switch
The pressure switch must be fitted for the regulation of the compressed air demand. This
pressure switch is normally fitted on the corresponding air receiver and regulates the
booster between the cut ---out and cut ---in pressures.
6.8.3
Flexible hose
The flexible hose is used to connect the booster package with an existing air system (air
receiver or pipework).
6.8.4
Check valve
To prevent the compressed air from flowing back into the compressor block, the check
valve must be fitted between the booster package and the air receiver.
Attention!
6.8.5
The size of the check valve depends upon the maximum working pressure (see chapter 1.3) and the cross--- section of the connection to the
air system (see dimensional diagram) from the compressor.
safety
relief valve
high
pressure
air system
flexible
hose
air filter
high pressure
tank with drain
trap
check
valve
existing
air system
booster package
Terminal box
6 --- 28
Initial Start
7
7.1
7.2
It is expected that the user employs safe working techniques and that all lawful operating and safety regulations are followed when operating this compressor unit.
The operator of this compressor unit is responsible for its safe operating condition.
Do not operate this compressor unit in locations where heavy dust conditions, poisonous or inflammable gases could exist.
Do not connect the compressor unit to a supply voltage other than that stated on the
nameplate.
Install the compressor unit in a location not subject to freezing temperatures. The air
temperature requirements at the air intake must be complied with (see chapter 1.8).
During installation of the compressor unit, ensure that a distance of at least 19.7 is
kept between the air intake of the unit and any wall.
Lock the main disconnect in the off position in accordance with applicable lock out/tag out procedures (example: OSHA CFR 29
1910.147) to ensure the compressor does not restart.
Check all screws on the electrical connections for tightness and
tighten if necessary (carry out this check again after 50 hours of operation).
7 --- 29
Initial Start
7.3
Checklist
Is the floor at the place of installation level, solid and load ---bearing?
yes
no
Ist der Raum gro genug fr die Maschine oder deren Komponenten?
yes
no
Are inlet and exhaust air apertures available in sufficient size and number?
yes
no
yes
no
Is the power supply cable of sufficient cross---section and the fusing adequate?
(have the electrical connection carried out by a qualified electrician familiar with local
conditions)
yes
no
Are shut off valves on the compressed air inlet and outlet fitted by the user?
yes
no
Are flexible connecting hoses fitted between the machine and the compressed air lines?
yes
no
Have all screws, bolts and electrical connections been checked for tightness?
yes
no
yes
no
Has the user installed a lockable main switch compatible with the motor starting characteristics?
yes
no
Has the setting of the drive motor overload current trip been checked?
yes
no
Have you ensured that there are no other air components located in the machines exhaust air flow?
yes
no
Has the operator been instructed in safety procedures and shown how to operate the
machine?
yes
no
If the aftercooler is water ---cooled, has the supply of water been ensured?
yes
no
yes
no
7 --- 30
Initial Start
7.4
7.5
7.6
Isolate the machine from the air main by closing the users
compressed air inlet and outlet shut ---off valves.
Attention!
7 --- 31
Initial Start
KFB003521
5
---
3
---
1
3
Cap
Adjusting screw P
4
5
Adjusting screw p
Screw
Unscrew the screws (5) to the right and left of the cover (1).
Remove the cover (1) of the pressure switch.
Turn the adjusting screw P (3) clockwise using a screwdriver. The red pin on the
pressure scale indicates the pressure.
Screw the plug back into the cover of the pressure switch.
Turn the adjusting screw P (3) counterclockwise using a screwdriver. The red pin on
the pressure scale indicates the pressure.
Screw the plug back into the cover of the pressure switch.
To increase the pressure difference between the cut--- in and cut--- out pressures:
Turn the adjusting screw p (4) clockwise. The black pin on the differential pressure
scale moves in the max direction.
To decrease the pressure difference between the cut--- in and cut--- out pressures:
Turn the adjusting screw p (4) counterclockwise. The black pin on the differential
pressure scale moves in the min direction.
7 --- 32
Initial Start
7.6.1
See chapter 1.4 for the maximum cut--- in frequency from standstill to
load per hour.
Increasing the switching difference causes a decrease in the cut ---in frequency.
Decreasing the switching difference causes an increase in the cut ---in frequency.
7 --- 33
Operation
8
Operation
8.1
Do not stop the compressor unit with the main disconnect switch.
Always start and stop the compressor unit with the control switch in
the controller.
8.2
Motor
Temperature 1
Oil Pressure
Temperature 2
8 --- 34
Operation
3 Shutdown by high temperature in the cylinder head
The PTC sensor must shut down the compressor package if the temperature exceeds
374 F , i.e. even if only one sensor registers a temperature excess (this is why they are
connected in series). The wiring used to connect the PTC sensors must be open circuit
protected.
When the malfunction is corrected, reset the compressor unit by turning the control
switch from I to 0.
4 Shutdown by oil pressure switch
The compressor unit is shut down if the oil pressure in the crankcase is excessive or is
insufficient.
When the malfunction is corrected, reset the compressor unit by turning the control
switch from I to 0.
5 Temperature gauge switch for detection of excess discharge temperature
If a temperature fault occurs the compressor unit is shut down by the temperature
gauge switch. (see chapter 8.3)
The compressor is started again after the fault has been removed.
8.3
Low oil
Cooling system fault
Ambient temperature too high or too low
When the malfunction is corrected, reset the compressor unit by turning the control
switch from I to 0.
8 --- 35
Operation
8.4
8.4.1
8.4.2
8.4.3
8.4.4
Remedy:
1.
Remedy
Damaged bearings
Piston seized
(too little or wrong type of oil)
1.
Compressor overheating
Possible cause:
Remedy:
Remedy:
8 --- 36
Operation
Pressure losses within the unit
8.4.6
8.4.7
8.4.8
Remedy:
Remedy:
Safety valve blows, even though the cut --out pressure is not yet reached.
Set 10 ---15 psig above max. working pressure (see chapter 1.1) of the compressor
1.
unit;
1.
Remedy:
1.
2.
Replace piston rings and cylinder;
(ensure that the inlet air is clean, e.g. by
using an air filter with a higher grade of filtration).
2.
Remedy
V---belt(s) slipping
8 --- 37
Maintenance
9
Maintenance
9.1
Observe the following rules during all maintenance and servicing work:
Work on power driven equipment may only be carried out by trained or
specialized personnel. Follow all applicable OSHA and local safety
regulations.
The compressor unit restarts automatically after a power failure if the
line pressure is lower than the pressure setting on the air pressure
switch.
Lock the main disconnect switch in the off position in accordance
with applicable lock out/tag out procedures (example: OSHA CFR 29
1910.147) to ensure the compressor does not restart (see
chapter LEERER MERKER for main disconnect switch).
Ensure that no maintenance personnel is working on the compressor
unit, that all panels are latched back on again and all maintenance
doors are closed before restarting the compressor unit.
To start the compressor unit see chapter 8.1.
Attention!
Always tighten down any screw connection that has been loosened
during maintenance work.
The following points must be observed when handling lubricating and
cooling materials:
Avoid contact with skin and eyes.
Do not inhale vapors and oil mist.
Do not eat or drink when handling such materials.
Fire, open flame and smoking are strictly forbidden.
Ensure that all lubricants, consumable materials and replacement
parts accumulating during operation and servicing of the compressor
package are disposed of according to environmental regulations.
9 --- 38
Maintenance
9.2
Regular Maintenance
Period*
Work to be done
See chapter
daily
9.4
9.12
check all electrical screw connections for tightness and tighten if necessary
7.2
9.5
9.9
9.6
9.11
9.12
9.15
9.15
9.5
1000 hours
9.7
9.10
1.9
9.9
9.8
5000 hours
9.18
12000 hours
9.18
up to 20000/36000 h,
or at least every 8
years
1.9
2000 hours
The maintenance period can vary depending on the cycle rate and environmental
conditions.
For severe duty (i. e. ambient temperature over 90 F, relative humidity over 90 %, or dirty
environment) the maintenance periods should be cut in half.
We highly recommend that a record is kept of the maintenance work done (see
chapter 9.19).
9 --- 39
Maintenance
9.3
Work to be done
See chapter
Depending on filter
Attention!
9.4
If the oil level has sunk to the lower mark, top off the oil immediately
according to the oil recommendations (see chapter 1.10).
Never top off to a level exceeding the maximum oil mark on the oil
level sight glass.
When topping off the oil always use a strainer or pour the oil directly
from the new oil can.
KFB069421
max.
min.
Remove the crankcase venting plug (1) from the oil filler.
Attention!
Let oil settle a few minutes before filling to the maximum oil level mark.
The oil must flow through the crankcase first.
Top off the oil to the maximum mark. See chapter 1.3 for the quantity of oil required for
topping off from the minimum mark to the maximum mark.
Check the sealing ring of the filler plug (1) for damage and then replace the plug.
Open the users shut ---off valves when the machine is re---started.
9 --- 40
Maintenance
9.5
Change the oil after approximately the first 500 service hours.
For oil change requirements see chapter 1.10.
If, under unsuitable operating conditions, condensed water is observed in the oil, recognizable by the milky color in the oil level sight glass (2), carry out an oil change immediately.
Damage to the machine from unsuitable oil.
CAUTION
max.
min.
3
1 Screw plug
2 Oil level sight glass
3 Oil drain plug
Shut down the compressor (see chapter 8.1).
Lock the main disconnect in the off position in accordance with applicable lock out/tag out procedures (example: OSHA CFR 29
1910.147) to ensure the compressor does not restart. See
chapter 2.4 for the main disconnect switch.
DANGER
Isolate the machine from the air main by closing the users compressed air inlet and
outlet shut ---off valves. Initial and final pressure gauges must read zero.
Remove plug (1) from the oil filler port.
Prepare a container to catch draining oil.
Danger of explosion from oils and lubricants!
WARNING
9 --- 41
Maintenance
Catch the used oil and dispose according to environmental regulations.
Remove the oil drain plug (3) and allow the oil to drain into the container.
Flush the crankcase with a small volume of fresh oil.
Replace the oil drain plug (3).
Attention!
A sieve should be used when refilling with fresh oil unless it is from a
new can of genuine Kaeser oil.
9.6
1
1
2
3
4
Air filter
Air inlet
Filter cartridge
Snap fastener
Shut down the compressor unit (see chapter 8.1).
Lock the main disconnect in the off position in accordance with applicable lock out/tag out procedures (example: OSHA CFR 29
1910.147) to ensure the compressor does not restart. See
chapter 2.4 for the main disconnect switch.
DANGER
Isolate the machine from the air main by closing the users compressed air inlet and
outlet shut ---off valves. Initial and final pressure gauges must read zero.
Unscrew the air filter (1) from the collector pipe.
Unhook the snap fastener (4) and open the filter cap.
Attention!
Clean the filter with diesel fuel in the open air. Observe the regulations
concerning the handling of combustible fluids.
9 --- 42
Maintenance
Clean the filter cap, especially the sealing surfaces.
Wash out the filter cartridge (3) with diesel fuel or clean with a steam jet.
When the filter cartridge (3) is dry wet lightly with oil.
Attention!
Make sure that the air inlet in the filter cap (2) is facing downwards
when screwing on the air filter .
Open the users shut ---off valves when the machine is re---started.
9.7
2
1
6
5
3
4
KFB073921
1 Check valve
2 End plug
3 Valve piston
4
5
6
Valve seat
Spring
Sealing ring
9 --- 43
Maintenance
Attention!
Always wear ear protection when lifting the safety relief valve because
of the loud noise caused by the compressed air blowing off.
Vent the air receiver and the pipework by lifting the upper knurled ring of the safety
relief valve (1, see chapter 9.15) and blowing off the compressed air.
Check the pressure on the pressure gauge. It must indicate zero psi.
Unscrew the plug (2) in the check valve.
Clean the valve piston (3) and the valve seat (4).
If damage or heavy wear is noticeable replace the valve cone (3), the spring (5) and
the ring (6).
Screw the plug (2) in the check valve again.
Open the users shut ---off valves when the machine is re---started.
9.8
Do not run the booster unit without the oil filtered crankcase venting
system.
The oil filter (2) must be changed every 2000 operating hours.
3
4
2
1
1
2
3
4
Casing venting
Oil filter element
Venting cap
O ---ring
Shut down the compressor (see chapter 8.1).
Lock the main disconnect in the off position in accordance with applicable lock out/tag out procedures (example: OSHA CFR 29
1910.147) to ensure the compressor does not restart. See
chapter 2.4 for the main disconnect switch.
9 --- 44
Maintenance
DANGER
WARNING
9.9
Change the oil filter after approximately the first 500 service hours
Danger of scalding with hot oil
Danger of burns from hot components
CAUTION
It is recommended that the oil filter be changed every 2000 operating hours but in any
case when the oil is changed or if the oil pressure switch shuts down the compressor because of excessive pressure.
Changing the oil filter
Shut down the compressor package (see chapter 8.1).
Lock the main disconnect in the off position in accordance with applicable lock out/tag out procedures (example: OSHA CFR 29
1910.147) to ensure the compressor does not restart. See
chapter 2.4 for the main disconnect switch.
9 --- 45
Maintenance
Wait at least five minutes before checking for electrical voltage.
Work carefully.
Close the users shut ---off valve between the compressor package and the air main.
The compressors oil circulation system vents automatically.
The pressure gauge must indicate 0 psig.
KFB048621
2
1
1 Oil filter
2 Turn in this direction to remove
Escaping oil mist is damaging to health.
CAUTION
Twist the used or contaminated oil filter cartridge counter clockwise to remove and
catch escaping oil in a suitable container.
Dispose of the old oil filter and any used, accumulated oil according to
environmental care regulations!
Clean the face of the combination block with a lint free cloth.
Lightly oil the gasket of the new filter cartridge before screwing into position.
Screw in the new filter cartridge clockwise by hand until the gasket fits tightly.
Attention!
Do not use a tool as this may cause damage to the oil filter cartridge
and the gasket.
Lock the main disconnect in the off position in accordance with applicable lock out/tag out procedures (example: OSHA CFR 29
1910.147) to ensure the compressor does not restart. See chapter 2.4 for the main disconnect switch.
Carry out a visual check for leaks.
9 --- 46
Maintenance
9.10
If the outlet temperature of the machine rises to 50 F above the established annual average, the aftercooler should be cleaned by a KAESER service technician.
Leakage check
Machine damage from leakage
CAUTION
9.11
9.11.1
2
1
1 Plug
2 Strainer
Shut down the compressor unit (see chapter 8.1).
Lock the main disconnect in the off position in accordance with applicable lock out/tag out procedures (example: OSHA CFR 29
1910.147) to ensure the compressor does not restart. See
chapter 2.4 for the main disconnect switch.
9 --- 47
Maintenance
DANGER
Isolate the machine from the air main by closing the users compressed air inlet and
outlet shut ---off valves. Initial and final pressure gauges must read zero.
Unscrew the plug (1).
Never direct compressed air toward persons. Compressed air is a concentrated form of energy and is as such dangerous to life. Always
wear personnel protective equipment.
WARNING
4
1
2
3
4
3 1
locking screw
strainer
O ---ring
Dirt trap
Shut down the compressor (see chapter 8.1).
Lock the main disconnect in the off position in accordance with applicable lock out/tag out procedures (example: OSHA CFR 29
1910.147) to ensure the compressor does not restart. See
chapter 2.4 for the main disconnect switch.
9 --- 48
Maintenance
DANGER
Isolate the machine from the air main by closing the users compressed air inlet and
outlet shut ---off valves. Initial and final pressure gauges must read zero.
Unscrew the screw plug (1).
Attention!
If the dirt trap is cleaned with diesel fuel this must be done in the open
air. The appropriate regulations concerning the handling of combustible fuels must be observed.
Screw the strainer (2) and the plug (1) back again.
Open the users shut ---off valves when the machine is re---started.
9.12
Isolate the machine from the air main by closing the users compressed air inlet and
outlet shut ---off valves. Initial and final pressure gauges must read zero.
Remove the belt guard.
Press down the V---belt with the thumb.
If the V---belt can be depressed more than 0.4 to 0.8 it must be tightened.
Open the users shut ---off valves when the machine is re---started.
9 --- 49
Maintenance
0.4 ---0.8
9.13
Isolate the machine from the air main by closing the users compressed air inlet and
outlet shut ---off valves. Initial and final pressure gauges must read zero.
Remove the belt guard
Loosen the hexagonal nuts on the motor mounts.
Slide the motor until the V---belt(s) is (are) tight again, i.e. it cannot be depressed more
than 0.4 to 0.8.
Tighten the hexagonal nuts.
Fit the belt guard again.
Open the users shut ---off valves when the machine is re---started.
KFB008121
1
2
1 Hexagonal nut
2 Square ---headed bolts
9 --- 50
Maintenance
9.14
V---Belt Change
Shut down the compressor unit (see chapter 8.1).
Lock the main disconnect in the off position in accordance with applicable lock out/tag out procedures (example: OSHA CFR 29
1910.147) to ensure the compressor does not restart. See
chapter 2.4 for the main disconnect switch.
DANGER
Isolate the machine from the air main by closing the users compressed air inlet and
outlet shut ---off valves. Initial and final pressure gauges must read zero.
Remove the belt guard.
Loosen the hexagonal nuts on the motor mounts.
Slide the motor in the direction of the compressor block until the V---belt(s) can be removed over the motor and compressor pulley.
Place the new V---belt(s) over the motor and compressor pulley without straining it.
Slide the motor in the opposite direction until the V---belt(s) is (are) correctly tensioned.
Tighten up the hexagonal nuts.
Check the tension after the first two service hours and then again after further 24 service hours. Tighten, if necessary (see chapter 9.12).
Attention!
It is essential that all replacement belts are precisely the same length
(as a set) and absolutely oil--- proof. For this reason we recommend
that only original KAESER V--- belts are used.
V--- belts may only be replaced as a set.
9.15
When the appropriate service hours have expired (see chapter 9.2), the
safety valve must be checked by an authorized KAESER dealer.
KFB049121
1
2
1 Knurled ring
2 Safety valve
9 --- 51
Maintenance
Safety relief valve is hot!
Attention!
Always wear ear and eye protection during the safety valve check.
During this procedure hot, pressurized air is released with a loud
noise.
Turn the knurled ring (1) on the safety valve (2) counterclockwise with the booster
package running under full load until air blows off.
Attention!
9.16
1
1
2
9 --- 52
Maintenance
9.17
G2
KFB056621
1
1
2
2 1
Jet
Union nut
Shut down the booster package (see chapter 8.1).
Lock the main disconnect in the off position in accordance with applicable lock out/tag out procedures (example: OSHA CFR 29
1910.147) to ensure the compressor does not restart. See
chapter 2.4 for the main disconnect switch.
DANGER
Isolate the machine from the air main by closing the users compressed air inlet
and outlet shut ---off valves.
Unscrew fittings (2).
Unscrew the T---piece with nozzle (1).
Take out the nozzle together with the T---piece (1) and clean by blowing out with compressed air.
Attention!
If the strainer is very dirty and has already been cleaned several times
then it should be renewed.
Take out the nozzle together with the T---piece (1) and clean by blowing out.
Replace the nozzle together with the T---piece (1).
Replace the fittings (2) again.
9 --- 53
Maintenance
9.18
Have the compressor generally overhauled by your authorized KAESER distributor after
12000 service hours.
Attention!
The cylinder heads, pistons and piston rings should be inspected for
excessive wear.
To determine the level of piston ring wear, measure the ring end gap:
Gap
Required action
0.008 to 0.016
over 0.02
The cylinder head and valves should be inspected and cleaned of all varnish, carbon deposits, corrosion or rust.
Attention!
9 --- 54
Maintenance
9.19
Maintenance Schedule
Model No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Serial No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Date
Description of work
Operating hours
Signature
9 --- 55
10.1
Part no.
6.2548.0
Air filter
1 off
6.0175.0
Check valve
1 off
8.0267.0
1 off
7.6062.00010
1 off
9.2147.0
1 off
6.1901.0
1 off
8.0501.0
Gasket
1 off
6.3488.0
1 off
8.0414.00010
Gasket
1 off
5.1517.0
Name
V---belt set
Model
Part No.
Year
Serial No.
Initial press.
psig
Displ.
MWP
psig
Voltage
Package
FLA
Hz/RPM
Phase
HP
10.2
cfm
Drive Motor
FLA
MADE IN GERMANY
10 --- 56
We want to point out that maintenance parts, spare parts and accessories not supplied by
us are also not tested and authorized by us. The use of such products could change design characteristics of the compressor unit negatively and might therefore affect the safety
of the unit.
The use of such parts or accessories releases KAESER COMPRESSORS from all liabilities
and warranties for consequential damage caused by such parts or accessories.
10 --- 57
Appendix
11
Appendix
11.1
Electrical Diagram
(see following page)
11 --- 58
Appendix
11.2
11.2.1
Application
PTC thermistors are used for temperature monitoring.
They are especially suitable for embedding in the windings of electric motors and transformers. PTC thermistors, in suitable housings, are also suitable for thermal protection of
other devices such as electronic sub ---assemblies, heat sinks, etc.
Function
PTC thermistors are manufactured in accordance with DIN 44081 and DIN 44082 and have
very favourable temperature sensitivity.
Electrical resistance increases sharply in the nominal response temperature range. This
resistance change can be used to switch off a power supply by using a suitable trip relay.
Electronic monitoring of temperature in the most diverse applications is also possible.
The resistance/temperature diagram shows the principle characteristics of PTC thermistors.
Temperature/resistance diagram according to DIN 44081/44082
Resistance R ( )
11.2.2
TNF = 50 C to 200 C
in steps of 10K and 5K
4000
Specification
Resistance
Measured
voltage
Resistance in the
temperature range
---20 C to
TNF ---20 K
20 to 250
2.5 V DC
550
2.5 V DC
1330
2.5 V DC
4000
7.5 V DC
pulsed
1330
550
250
Resistance at
TNF ---5 K
Resistance at
TNF + 5 K
---20 C
Temperature
TNF ---20 K
TNF + 15 K
TNF ---5 K
TNF + 5 K
Resistance at
TNF + 15 K
TNF
11 --- 79