Iris Report For Heat Exchanger: Tables of Contents
Iris Report For Heat Exchanger: Tables of Contents
Iris Report For Heat Exchanger: Tables of Contents
VQ/TI/2013/03 Rev 0
11.0Appendices
1. Inspection Summary Report
2. Heat Exchanger Status (Tube Sheet)
3. List of inspected tubes
1.0 INTRODUCTION
Internal Rotary Inspection was conducted on the QCHW PRIMARY COOLER QCC-02QWS-41-10 on 12/3/2012 to 14/3/2012
A computerized MS-5800 Multi-function non destructive testing system was used to carry
out the inspection. All results were recorded to disk with manual analysis on screen. The
equipment was calibrated as per velosi IRIS written procedure Doc. No. VQ/IRIS/01
Rev.1.
2.0
EQUIPMENT DETAILS
Equipment
Serial No
Probe
Turbine used
3.0
:
:
:
:
EXCHANGER DETAILS
Serial No
Tube Material
Configuration
:
Total number of tubes
Number of tubes Inspected
OD
:
Thickness
:
4.0
:
QCC-02-QWS-41-10
:
SA 214
Straight Tube
:
6070
:
6070
19.05mm
2.11mm
Tube
Tube
Tube Wall
INSPECTED BY
H Kruger
Maneesh George
5.0
SCOPE OF WORK
To carryout IRIS inspection on 359 tubes, to their entire length of tubes, to find out and
analyze any wall loss or any other anomaly.
6.0
TUBE IDENTIFICATION
In order to be able to identify and locate each tube, and there by create full traceability
the grid coordinates row and column were used.
Viewing From Plant East
Rows were numbered from Top to Bottom
Columns were numbered from Left to Right
LIMITATIONS
Tubes have to be pristine clean for IRIS inspection. Any internal deposit / loose scale
may create the ultrasound waves to scatter and give the wrong wall thickness and in the
worst cases the defect may remain undetected.
Tubes were inspected till the starting of U bend.
8.0
DISCUSSION / RESULTS
Tubes were found to be in an average clean condition and with isolated scaling and
deposits.
The inspected tubes were found with less than 20% of external corrosion.
Tubes were classified as follows
Classifications
Total
TUBE PERCENTAGE
No defects detected
101
21.53%
0%
Nil
Nil
Nil
Nil
0%
0%
Nil
0%
Nil
0%
Nil
0%
Plugged
Nil
0%
Restricted
16
3.41%
0%
This distribution of damage is shown in Appendices, in the form of heat exchanger drawing
9.0
CLEANING DETAILS
Good
Average
Poor
10.0